Home
JY997D32901B GT10 General Description
Contents
1. 10 to 90 RH non condensing The wet bulb temperature is 39 C or less 10 to 90 RH non condensing The wet bulb temperature is 39 C or less Sweep Count 10 times each in X Conforms to JIS B3502 IEC 61131 2 147m s2 11 ms Sine half wave pulse 3 times each in the X Y and Z directions Must be free of lamp black corrosive gas flammable gas or excessive amount of electroconductive dust particles and must be no direct sunlight Same as for saving Class D grounding 100Q or less To be connected to the panel when grounding is not possible 1 Do not use or store the GOT under pressure higher than the atmospheric pressure of altitude Om Oft Failure to observe this instruction may cause a malfunction 2 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the machinery within the premises Category II applies to equipment for which electrical power is supplied from fixed facilities The surge voltage withstand level for up to the raged voltage of 300 V is 2500 V 3 This index indicates the degree to which conductive material is generated in the environment where the equipment is used In pollution degree 2 only non conductive pollution occurs but temporary conductivity may be produced due to condensation 1 2 Performance Specifications Item GT1045 QSBD STN color liquid crystal STN monochrome white blue
2. Operating atmosphere Operating altitude Installation location Inside control panel Overvoltage category 2 ll or less Pollution degree s 2 or less Cooling method Self cooling Grounding Class D grounding 100Q or less To be connected to the panel when grounding is not possible 1 Do not use or store the GOT under pressure higher than the atmospheric pressure of altitude Om Oft Failure to observe this instruction may cause a malfunction 2 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the machinery within the premises Specifications GT1045 QSBD RS 422 485 1ch Transmission speed 115 200 57 600 38 400 19 200 9 600 4 800bps Connector shape D sub 9 pin Female Application PLC communication Terminating resistor 4 Open 110Q 330Q Switched by terminating resistor selector switch At factory shipment 330Q RS 232 1ch Transmission speed 115 200 57 600 38 400 19 200 9 600 4 800bps Connector shape D sub 9 pin Male Application PLC communication bar code reader connection PC communication Project data upload download OS installation transparent function USB Full Speed 12Mbps ich USB Connector shape Mini B Receptacle Application PC communication Project data upload download OS installation transparent function Item GT1040 QBBD RS 422 485 Built in interface RS 232 G
3. 4 Panel Mounting Packing 1 GT10 General Description This manual 1 Explanation of the GOT model name GT1040 xxx L_ Power type D 24VDC L 5VDC B Black S STN color L STN monochrome black white B STN monochrome blue white l Resolution Q 320 x 240 QVGA Panel color type Display device type Blank less than 320 x 240 5 256 colors supported 0 Monochrome black white Display color type Screen size type Lope He Ag 4 4 7 3 4 5 Z3 GOT1000 series GT10 1 Specifications 1 1 General Specifications Specifications GT1045 QSBD GT1040 QBBD Item Operating ambient Display section 0 to 50 C temperature Other than display section 0 to 55 C When mounted horizontally 0 to 50 C When mounted vertically 20 to 60 C 10 to 90 RH non condensing The wet bulb temperature is 39 C or less Storage ambient temperature Operating ambient humidity 10 to 90 RH non condensing The wet bulb temperature is 39 C or less OOOO O f Feo Accetrton Paama meee eme e Conforms to JIS B3502 IEC 61131 2 147m s2 11 ms Sine half wave pulse 3 times each in the X Y and Z directions Must be free of lamp black corrosive gas flammable gas or excessive amount of electroconductive dust particles and must be no direct sunlight Same as for saving 2000 m 6562 ft max Storage ambient humidity Sweep Count Conforms to JIS Vibration resistance B3502 and IEC61131 2 Shock resistance
4. in medium or slight personal injury or physical damage Depending on circumstances procedures indicated by CAUTION may also be linked to serious results In any case it is important to follow the directions for usage DESIGN PRECAUTIONS lt SDANGER e Some failures of the GOT or cable may keep the outputs on or off An external monitoring circuit should be provided to check for output signals which may lead to a serious accident Not doing so can cause an accident due to false output or malfunction If a communication fault including cable disconnection occurs during monitoring on the GOT communication between the GOT and PLC CPU is suspended and the GOT becomes inoperative A system where the GOT is used should be configured to perform any significant operation to the system by using the switches of a device other than the GOT on the assumption that a GOT communication fault will occur Not doing so can cause an accident due to false output or malfunction Do not use the GOT as the warning device that may cause a serious accident An independent and redundant hardware or mechanical interlock is required to configure the device that displays and outputs serious warning Failure to observe this instruction may result in an accident due to incorrect output or malfunction Incorrect operation of the touch switch s may lead to a serious accident if the GOT backlight is gone out When the GOT backlight goes out causes the monitor scr
5. liquid crystal Specifications GT1040 QBBD 16 dot standard font 40 characters x 15 lines 12 dot standard font 53 characters x 20 lines Horizontal format 256 colors Monochrome white blue 16 scales ft Right 50 degrees Top 40 degrees Bottom 70 degrees Left Right 45 degrees Top 20 degrees Bottom 40 degrees 320 x 240 dots Horizontal format W96 3 77 x H72 2 83 mm inch Horizontal format Display Horizontal format Horizontal format 16 level adjustment 300 ear Approx 50 000h Time for display intensity to become 1 5 at operating ambient temperature of 25 C Backlight LED Backlight off screen saving time can be set Maximum 50 keys screen Matrix resistive film touch panel Minimum 16 x 16 dots per key Touch Simultaneous pressing of panel two or more areas Enable 2 point press Life 1 million times or more operating force 0 98N max User memory 2 Memory ife Number of write times 100 000 times Battery GT11 50BAT lithium battery Backup target Clock data alarm history and recipe data Flash memory ROM Internal for storing project data 3M bytes or less and OS Life Approx 5 years Operating ambient temperature of 25 Buzzer output a buzzer that sounds when touch Single tone LONG SHORT OFF adjustable keys are pressed Environmental protective structure 3 External dimensions Equivalent to IP67 JEM1030 front section W139 5 47 x H112 4 4 x D41 1 61 mm in
6. local Mitsubishi Electric sales site Notes for compliance to EMC regulation 1 General notes on the use of communication cables Any device which utilizes a data communication function is susceptible to the wider effects of local EMC noise Therefore when installing any communication cables care should always be taken with the routing and location of those cables The GOT units identified on the previous chapter are compliant with the EMC requirement when the following communication cables are used GOT Unit Existing Cables User Made Cables GT1045 QSBD GT01 C30R4 8P and modified as GT1040 QBBD shown in EX 1 Those cables need to be independently tested by the user to demonstrate EMC compatibility when they are used with Mitsubishi GOT unit and FX3U Programmable Controllers Ex 1 F Ferrite core Ex NEC TOKIN ESD R 17S or similar GT01 C30R4 8P 250mm 100mm 9 84inch 3 93inch oe ele M GOT units Comes capped Added by user Added by user Programmable controller 2 General notes on Power supply The GT1045 QSBD and GT1040 QBBD unit requires an additional ferrite filter to be attached to the 24V DC power supply cables The filter should be attached in a similar manner as shown in the figure opposite i e the power cables are wrapped around the filter However as with all EMC situations the more correctly applied precautions the better the systems Electro magnetic Compatibility The ferrite
7. the product fails install appropriate backup or failsafe functions in the system a MITSUBISHI ELECTRIC CORPORATION HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN HIMEJI WORKS 840 CHIYODA CHO HIMEJI JAPAN Side JY997D32901B B EA JAPANESE SE ENGLISH a MITSUBISHI GT1045 QSBD GT1040 QBBD GT10 General Description SPANAT ENPE Manual Number JY997D32901B Tiooo Ro 20e This manual describes the specifications of the product Before use read this manual and manuals of relevant products fully to acquire proficiency in handling and operating the product Make sure to learn all the product information safety information and precautions And store this manual in a safe place so that you can take it out and read it whenever necessary Always forward it to the end user Registration The company name and the product name to be described in this manual are the registered trademarks or trademarks of each company Effective Nov 2008 Specifications are subject to change without notice 2008 Mitsubishi Electric Corporation Changes for the Better Safety Precaution Read these precautions before using Before using this product please read this manual and the relevant manuals introduced in this manual carefully and pay full attention to safety to handle the product correctly The precautions given in this manual are concerned with this product In this manual the safety precauti
8. Side JY997D32901B B EA JAPANESE S E ENGLISH a MITSUBISHI GT1045 QSBD GT1040 QBBD GT10 General Description Manual Number JY997D32901B This manual describes the specifications of the product Before use read this manual and manuals of relevant products fully to acquire proficiency in handling and operating the product Make sure to learn all the product information safety information and precautions And store this manual in a safe place so that you can take it out and read it whenever necessary Always forward it to the end user Registration The company name and the product name to be described in this manual are the registered trademarks or trademarks of each company Effective Nov 2008 Specifications are subject to change without notice 2008 Mitsubishi Electric Corporation Changes for the Better GRAPHIC OPERATION TERMINAL Nooo Safety Precaution Read these precautions before using Before using this product please read this manual and the relevant manuals introduced in this manual carefully and pay full attention to safety to handle the product correctly The precautions given in this manual are concerned with this product In this manual the safety precautions are ranked as DANGER and CAUTION Indicates that incorrect handling may cause hazardous lt gt DANGER conditions resulting in death or severe injury Indicates that incorrect handling may cause hazardous CAUTION conditions resulting
9. T10 50FMB Panel cutting dimensions For connecting GT10 50FMB memory board W130 5 11 x H103 4 05 mm inch Horizontal format Weight 0 45kg Excluding mounting fixtures GT Designer2 Version 2 85P or later Compatible software package 1 Bright dots always lit and dark dots unlit may appear on a liquid crystal display panel It is impossible to completely avoid this symptom as the liquid crystal display comprises of a great number of display elements Flickers may be observed depending on the display color Please note that these dots appear due to its characteristic and are not caused by product defect When the same screen is displayed for a long time an incidental color or partial discoloration is generated on the screen due to heat damage and it may not disappear To prevent heat damage the screen saver function is effective For details on the screen saver function refer to the following GT10 User s Manual 2 ROM in which new data can be written without deleting the written data 3 Note that this does not guarantee all users operation environment 4 Set the terminating resistor selector switch of the GOT in accordance with the connection type when adopting GOT multidrop connection For details of GOT multidrop connection refer to the following GOT1000 Series Connection Manual 1 3 Power Supply Specifications For details on power supply wiring such as the allowable cable size and tightening torque r
10. aracteristic and are not caused by product defect When the same screen is displayed for a long time an incidental color or partial discoloration is generated on the screen due to heat damage and it may not disappear To prevent heat damage the screen saver function is effective For details on the screen saver function refer to the following GT10 User s Manual ROM in which new data can be written without deleting the written data Note that this does not guarantee all users operation environment Set the terminating resistor selector switch of the GOT in accordance with the connection type when adopting GOT multidrop connection For details of GOT multidrop connection refer to the following GOT1000 Series Connection Manual 1 3 Power Supply Specifications For details on power supply wiring such as the allowable cable size and tightening Input power supply voltage Fuse built in not torque refer to the additional manual GT10 User s Manual Specifications GT1045 QSBD 24VDC 10 15 Item GT1040 QBBD exchangeable THR Power 3 6W 150mA 24VDC or less consumption 2 9W 120mA 24VDC or less At backlight off Inrush current 15A or less 26 4VDC 2ms Permissible instantaneous Within 5ms power failure time 1 Noise immunity Dielectric withstand Noise voltage 1000Vp p Noise width 1us by noise simulator of 30 to 100Hz noise frequency 500VAC for 1 minute across powe
11. ch Excluding mounting fixtures Horizontal format Item GT1045 QSBD RS 422 485 1ch Connector shape RS 422 485 D sub 9 pin Female Specifications GT1040 QBBD Transmission speed 115 200 57 600 38 400 19 200 9 600 4 800bps Terminating resistor 4 Open 110Q 330Q Switched by terminating resistor selector switch At factory shipment 330Q Application PLC communication RS 232 1ch Built in Transmission speed 115 200 57 600 38 400 19 200 9 600 4 800bps interface RS 232 Connector shape D sub 9 pin Male Panel cutting dimensions Weight Compatible software package 4 2 3 4 Application USB Full Speed 12Mbps ich USB Connector shape Mini B Receptacle PLC communication bar code reader connection PC communication Project data upload download OS installation transparent function Application PC communication Project data upload download OS installation transparent function GT10 50FMB For connecting GT10 50FMB memory board 0 45kg Excluding mounting fixtures GT Designer2 Version 2 85P or later W130 5 11 x H103 4 05 mm inch Horizontal format Bright dots always lit and dark dots unlit may appear on a liquid crystal display panel It is impossible to completely avoid this symptom as the liquid crystal display comprises of a great number of display elements Flickers may be observed depending on the display color Please note that these dots appear due to its ch
12. changing the settings or current values of the timer or counter read through the manual carefully and make yourself familiar with the operation method During test operation never change the data of the devices which are used to perform significant operation for the system False output or malfunction can cause an accident STARTUP MAINTENANCE PRECAUTIONS DANGER When power is on do not touch the terminals Doing so can cause an electric shock or malfunction Connect the battery correctly Do not discharge disassemble heat short solder or throw the battery into the fire Incorrect handling may cause the battery to generate heat burst or take fire resulting in injuries or fires Before starting cleaning or terminal screw retightening always switch off the power externally in all phases Not switching the power off in all phases can cause a unit failure or malfunction Undertightening can cause a short circuit or malfunction Overtightening can cause a short circuit or malfunction due to the damage of the screws or unit STARTUP MAINTENANCE PRECAUTIONS CAUTION Do not disassemble or modify the unit Doing so can cause a failure malfunction injury or fire Do not touch the conductive and electronic parts of the unit directly Doing so can cause a unit malfunction or failure The cables connected to the unit must be run in ducts or clamped Not doing so can cause the unit or cable to be damaged due to the dangling m
13. duct has been manufactured under strict quality control However when installing the product where major accidents or losses could occur if the product fails install appropriate backup or failsafe functions in the system afa MITSUBISHI ELECTRIC CORPORATION HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN HIMEJI WORKS 840 CHIYODA CHO HIMEJI JAPAN
14. een to appear blank while the input of the touch switch s remains active This may confuse an operator in thinking that the GOT is in screensaver mode who then tries to release the GOT from this mode by touching the display section which may cause a touch switch to operate DESIGN PRECAUTIONS CAUTION e Do not bundle the control and communication cables with main circuit power or other wiring Run the above cables separately from such wiring and keep them a minimum of 100mm 3 94in apart Not doing so noise can cause a malfunction MOUNTING PRECAUTIONS DANGER e Be sure to shut off all phases of the external power supply used by the system before mounting or removing the GOT to from the panel Not doing so can cause the unit to fail or malfunction e When installing the battery wear an earth band etc to avoid the static electricity The static electricity can cause the unit to fail or malfunction MOUNTING PRECAUTIONS CAUTION Use the GOT in the environment that satisfies the general specifications described in this manual Not doing so can cause an electric shock fire malfunction or product damage or deterioration When mounting the GOT to the control panel tighten the mounting screws in the specified torque range Undertightening can cause the GOT to drop short circuit or malfunction Overtightening can cause a drop short circuit or malfunction due to the damage of the screws or the GOT WIRING PRECAUTIONS
15. efer to the additional manual GT10 User s Manual Category II applies to equipment for which electrical power is supplied from fixed facilities The surge voltage withstand level for up to the raged voltage of 300 V is 2500 V 3 This index indicates the degree to which conductive material is generated in the environment where the equipment is used In pollution degree 2 only non conductive pollution occurs but temporary conductivity may be produced due to condensation 1 2 Performance Specifications Specifications GT1045 QSBD GT1040 QBBD Type STN color liquid crystal STN monochrome white blue liquid crystal Screen size 4 7 320 x 240 dots Horizontal format W96 3 77 x H72 2 83 mm inch Horizontal format 16 dot standard font 40 characters x 15 lines 12 dot standard font 53 characters x 20 lines Horizontal format 256 colors Monochrome white blue 16 scales Left Right 50 degrees Top 40 degrees Bottom 70 degrees Left Right 45 degrees Top 20 degrees Bottom 40 degrees Horizontal format Horizontal format 16 level adjustment 150 cd m2 300 cd m2 Item Resolution Display size Display character Display section Display color Display angle Contrast adjustment Intensity of LCD only Life Approx 50 000h Time for display intensity to become 1 5 at operating ambient temperature of 25 C Backlight LED Backlight off screen saving time can be set Number of touch keys Maximum 50
16. ening can cause a short circuit or malfunction Overtightening can cause a short circuit or malfunction due to the damage of the screws or unit lt SDANGER Before performing the test operations of the user creation monitor screen such as turning ON or OFF bit device changing the word device current value changing the settings or current values of the timer or counter read through the manual carefully and make yourself familiar with the operation method During test operation never change the data of the devices which are used to perform significant operation for the system False output or malfunction can cause an accident DANGER When power is on do not touch the terminals Doing so can cause an electric shock or malfunction Connect the battery correctly Do not discharge disassemble heat short solder or throw the battery into the fire Incorrect handling may cause the battery to generate heat burst or take fire resulting in injuries or fires Before starting cleaning or terminal screw retightening always switch off the power externally in all phases Not switching the power off in all phases can cause a unit failure or malfunction Undertightening can cause a short circuit or malfunction Overtightening can cause a short circuit or malfunction due to the damage of the screws or unit CAUTION Do not disassemble or modify the unit Doing so can cause a failure malfunction injury or fire Do not touch the co
17. ic shock fire malfunction or product damage or deterioration When mounting the GOT to the control panel tighten the mounting screws in the specified torque range Undertightening can cause the GOT to drop short circuit or malfunction Overtightening can cause a drop short circuit or malfunction due to the damage of the screws or the GOT DANGER Be sure to shut off all phases of the external power supply used by the system before wiring Failure to do so may result in an electric shock product damage or malfunctions Please make sure to ground FG terminal of the GOT power supply section by applying 100 or less which is used exclusively for the GOT Not doing so may cause an electric shock or malfunction Correctly wire the GOT power supply section after confirming the rated voltage and terminal arrangement of the product Not doing so can cause a fire or failure Tighten the terminal screws of the GOT power supply section in the specified torque range Undertightening can cause a short circuit or malfunction Overtightening can cause a short circuit or malfunction due to the damage of the screws or the GOT Exercise care to avoid foreign matter such as chips and wire offcuts entering the GOT Not doing so can cause a fire failure or malfunction WIRING PRECAUTIONS NCAUTION Plug the communication cable into the connector of the connected unit and tighten the mounting and terminal screws in the specified torque range Undertight
18. in unit and or relevant unit s in the manner they will not be exposed to the impact exceeding the impact resistance described in the general specifications of this manual as they are precision devices Failure to do so may cause the unit to fail Check if the unit operates correctly after transportation Compliance with EC directive CE Marking This note does not guarantee that an entire mechanical module produced in accordance with the contents of this note will comply with the following standards Compliance to EMC directive for the entire mechanical module should be checked by the user manufacturer For more details please contact the local Mitsubishi Electric sales site Requirement for Compliance with EMC directive The following products have shown compliance through direct testing to the identified standards and design analysis forming a technical construction file to the European Directive for Electromagnetic Compatibility 89 336 EEC when used as directed by the appropriate documentation Type Programmable Controller Open Type Equipment Standard Remark Compliance with all relevant aspects of the EMI standard EN61131 2 2003 Radiated Emissions Programmable Compliance with all relevant aspects of the controllers Equipment standard requirement and tests EMS ESD RF electromagnetic field EFTB Surge RF conducted disturbances and Power frequency magnetic field For more details please contact the
19. keys screen Matrix resistive film touch panel Key size Minimum 16 x 16 dots per key Touch Simultaneous pressing of panel two or more areas Enable 2 point press Life 1 million times or more operating force 0 98N max User memory 2 Flash memory ROM Internal for storing project data 3M bytes or less and OS Memory Life Number of write times Battery GT11 50BAT lithium battery Backup target 100 000 times Clock data alarm history and recipe data Life Approx 5 years Operating ambient temperature of 25 Buzzer output a buzzer that sounds when touch Single tone LONG SHORT OFF adjustable keys are pressed Equivalent to IP67 JEM1030 front section W139 5 47 x H112 4 4 x D41 1 61 mm inch Excluding mounting fixtures Horizontal format Environmental protective structure s External dimensions Specifications GT1045 QSBD Input power supply j voltage 24VDC 10 15 Item GT1040 QBBD Fuse built in not exchangeable ven Power consumption oon ll i are At backlight off l Inrush current 15A or less 26 4VDC 2ms Permissible instantaneous power failure time 1 Within 5ms Noise voltage 1000Vp p Noise width 1us by noise NOSE Mny simulator of 30 to 100Hz noise frequency Dielectric withstand 500VAC for 1 minute across power supply terminals and voltage earth Insulation resistance 10MQ or larger by insulation resistance tester across power supply termi
20. l Check if the unit operates correctly after transportation Compliance with EC directive CE Marking This note does not guarantee that an entire mechanical module produced in accordance with the contents of this note will comply with the following standards Compliance to EMC directive for the entire mechanical module should be checked by the user manufacturer For more details please contact the local Mitsubishi Electric sales site Requirement for Compliance with EMC directive The following products have shown compliance through direct testing to the identified standards and design analysis forming a technical construction file to the European Directive for Electromagnetic Compatibility 89 336 EEC when used as directed by the appropriate documentation Type Programmable Controller Open Type Equipment Standard Remark Compliance with all relevant aspects of the standard Radiated Emissions EMI EN61131 2 2003 Programmable controllers Equipment requirement and tests EMS Compliance with all relevant aspects of the standard ESD RF electromagnetic field EFTB Surge RF conducted disturbances and Power frequency magnetic field For more details please contact the local Mitsubishi Electric sales site Notes for compliance to EMC regulation 1 General notes on the use of communication cables Any device which utilizes a data communication function is susceptible to the wider effects of local EMC
21. lt SDANGER e Be sure to shut off all phases of the external power supply used by the system before wiring Failure to do so may result in an electric shock product damage or malfunctions Please make sure to ground FG terminal of the GOT power supply section by applying 100 or less which is used exclusively for the GOT Not doing so may cause an electric shock or malfunction Correctly wire the GOT power supply section after confirming the rated voltage and terminal arrangement of the product Not doing so can cause a fire or failure Tighten the terminal screws of the GOT power supply section in the specified torque range Undertightening can cause a short circuit or malfunction Overtightening can cause a short circuit or malfunction due to the damage of the screws or the GOT Exercise care to avoid foreign matter such as chips and wire offcuts entering the GOT Not doing so can cause a fire failure or malfunction WIRING PRECAUTIONS CAUTION e Plug the communication cable into the connector of the connected unit and tighten the mounting and terminal screws in the specified torque range Undertightening can cause a short circuit or malfunction Overtightening can cause a short circuit or malfunction due to the damage of the screws or unit TEST OPERATION PRECAUTIONS lt SDANGER e Before performing the test operations of the user creation monitor screen such as turning ON or OFF bit device changing the word device current value
22. nals and earth This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual The GOT continues to operate even upon 5ms or shorter instantaneous power failure The GOT stops operating if there is extended power failure or voltage drop while it automatically resumes operation as soon as the power is restored Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi opportunity loss or lost profits caused by faults in the Mitsubishi products damage secondary damage accident compensation caused by special factors unpredictable by Mitsubishi damages to products other than Mitsubishi products and to other duties e This product has been manufactured as a general purpose part for general industries and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life e Before using the product for special purposes such as nuclear power electric power aerospace medicine or passenger movement vehicles consult with Mitsubishi Electric e This product has been manufactured under strict quality control However when installing the product where major accidents or losses could occur if
23. nductive and electronic parts of the unit directly Doing so can cause a unit malfunction or failure The cables connected to the unit must be run in ducts or clamped Not doing so can cause the unit or cable to be damaged due to the dangling motion or accidental pulling of the cables or can cause a malfunction due to a cable connection fault When unplugging the cable connected to the unit do not hold and pull the cable portion Doing so can cause the unit or cable to be damaged or can cause a malfunction due to a cable connection fault Do not drop or apply any impact to the battery If any impact has been applied discard the battery and never use it The battery may be damaged by the drop or impact Before touching the unit always touch grounded metal etc to discharge static electricity from human body etc Not doing so can cause the unit to fail malfunction DISPOSAL PRECAUTIONS CAUTION When disposing of the product handle it as industrial waste TRANSPORTATION PRECAUTIONS CAUTION Before transporting the GOT turn the GOT power on and check that the battery voltage status is normal on the Time setting amp display screen utilities screen In addition confirm that the adequate battery life remains on the rating plate Transporting the GOT with the low battery voltage or the battery the reached battery life may unstabilize the backup data unstable during transportation Make sure to transport the GOT ma
24. noise Therefore when installing any communication cables care should always be taken with the routing and location of those cables The GOT units identified on the previous chapter are compliant with the EMC requirement when the following communication cables are used GOT Unit Existing Cables User Made Cables Those cables need to be independently GT1045 QSBD GT01 C30R4 8P tested by the user to demonstrate EMC and modified as compatibility when they are used with GT1040 QBBD shown inEX 1 Mitsubishi GOT unit and FX3U Programmable Controllers Ex 1 F Ferrite core Ex NEC TOKIN ESD R 17S or similar GT01 C30R4 8P Programmable GOT units controller Comes capped Added by user Added by user 2 General notes on Power supply The GT1045 QSBD and GT1040 QBBD unit requires an additional ferrite filter to be attached to the 24V DC power supply cables The filter should be attached ina similar manner as shown in the figure opposite i e the power cables are wrapped around the filter However as with all EMC situations the more correctly applied precautions the better the systems Electro magnetic Compatibility The ferrite recommended is a TDK ZCAT3035 1330 or similar The ferrite should be placed as near to the 24V DC terminals of the GT1045 QSBD and GT1040 QBBD as possible which should be within 75mm of the GOT terminal Up to 75mm 2 95inch Associated Manuals The following manuals are releva
25. nt to this product When these loose manuals are required please consult with our local distributor Manual name Contents Manual Number Model Code Describes the GT10 hardware relevant content such as part names external dimensions mounting power supply wiring specifications and introduction to option devices GT10 User s Manual sold separately JY997D24701 09R819 GOT1000 Series Connection Manual 1 3 2 3 3 3 sold separately 1 Describes system configurations of the connection method applicable to SH 080532ENG GOT1000 series and cable creation 1D7M26 method GT Designer2 Version2 Basic Operation Data Transfer Manual A For GOT1000 Series operation for drawing and transmitting data to GOT1000 series Describes methods of the GT Designer2 installation operation basic SH 080529ENG 1D7M24 sold separately 1 GT Designer2 Version2 Screen Design Manual Describes specifications and settings For GOT1000 Series of the object functions used in GT 1 3 2 3 3 3 Designer2 sold separately 1 SH 080530ENG 1D7M25 Stored in the GT Works 2 GT Designer2 in PDF format For details of a PLC to be connected refer to the PLC user s manual respectively Bundled Items Model Name Remark GT1045 QSBD GT1040 QBBD GOT main unit The maintenance supplies below are packed with the product Maintenance Supplies Quantity Panel Mounting Bracket with M4 x 20 screws
26. ons are ranked as DANGER and CAUTION Indicates that incorrect handling may cause hazardous lt gt DANGER conditions resulting in death or severe injury Indicates that incorrect handling may cause hazardous CAUTION conditions resulting in medium or slight personal injury or physical damage Depending on circumstances procedures indicated by CAUTION may also be linked to serious results In any case it is important to follow the directions for usage DESIGN PRECAUTIONS lt SDANGER e Some failures of the GOT or cable may keep the outputs on or off An external monitoring circuit should be provided to check for output signals which may lead to a serious accident Not doing so can cause an accident due to false output or malfunction If a communication fault including cable disconnection occurs during monitoring on the GOT communication between the GOT and PLC CPU is suspended and the GOT becomes inoperative A system where the GOT is used should be configured to perform any significant operation to the system by using the switches of a device other than the GOT on the assumption that a GOT communication fault will occur Not doing so can cause an accident due to false output or malfunction Do not use the GOT as the warning device that may cause a serious accident An independent and redundant hardware or mechanical interlock is required to configure the device that displays and outputs serious warning Failure to observe
27. otion or accidental pulling of the cables or can cause a malfunction due to a cable connection fault When unplugging the cable connected to the unit do not hold and pull the cable portion Doing so can cause the unit or cable to be damaged or can cause a malfunction due to a cable connection fault Do not drop or apply any impact to the battery If any impact has been applied discard the battery and never use it The battery may be damaged by the drop or impact Before touching the unit always touch grounded metal etc to discharge static electricity from human body etc Not doing so can cause the unit to fail malfunction DISPOSAL PRECAUTIONS CAUTION e When disposing of the product handle it as industrial waste TRANSPORTATION PRECAUTIONS CAUTION e Before transporting the GOT turn the GOT power on and check that the battery voltage status is normal on the Time setting amp display screen utilities screen In addition confirm that the adequate battery life remains on the rating plate Transporting the GOT with the low battery voltage or the battery the reached battery life may unstabilize the backup data unstable during transportation Make sure to transport the GOT main unit and or relevant unit s in the manner they will not be exposed to the impact exceeding the impact resistance described in the general specifications of this manual as they are precision devices Failure to do so may cause the unit to fai
28. r supply terminals and voltage earth Insulation 10MQ or larger by insulation resistance tester across power resistance supply terminals and earth The GOT continues to operate even upon 5ms or shorter instantaneous power failure The GOT stops operating if there is extended power failure or voltage drop while it automatically resumes operation as soon as the power is restored This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi opportunity loss or lost profits caused by faults in the Mitsubishi products damage secondary damage accident compensation caused by special factors unpredictable by Mitsubishi damages to products other than Mitsubishi products and to other duties e This product has been manufactured as a general purpose part for general industries and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life e Before using the product for special purposes such as nuclear power electric power aerospace medicine or passenger movement vehicles consult with Mitsubishi Electric e This pro
29. recommended is a TDK ZCAT3035 1330 or similar The ferrite should be placed as near to the 24V DC terminals of the GT1045 QSBD and GT1040 QBBD as possible which should be within 75mm of the GOT terminal Up to 75mm 2 95inch Associated Manuals The following manuals are relevant to this product When these loose manuals are required please consult with our local distributor Contents Manual Number Model Code Describes the GT10 hardware relevant content such as part names external dimensions mounting power supply wiring specifications and introduction to option devices Manual name GT10 User s Manual sold separately JY997D24701 09R819 GOT1000 Series Describes system configurations of the Connection Manual connection method applicable to SH 080532ENG 1 3 2 3 3 3 GOT1000 series and cable creation 1D7M26 sold separately 1 method GT Designer2 Version2 Basic Operation Data Transfer Manual For GOT1000 Series sold separately 1 Describes methods of the GT Designer2 installation operation basic operation for drawing and transmitting data to GOT1000 series SH 080529ENG 1D7M24 GT Designer2 Version2 Screen Design Manual For GOT1000 Series 1 3 2 3 3 3 sold separately 1 Describes specifications and settings of the object functions used in GT Designer2 SH 080530ENG 1D7M25 4 Stored in the GT Works 2 GT Designer2 in PDF format For details of a PLC to be connected
30. refer to the PLC user s manual respectively Bundled Items Model Name GT1045 QSBD GT1040 QBBD Remark GOT main unit The maintenance supplies below are packed with the product Maintenance Supplies Quantity Panel Mounting Bracket with M4 x 20 screws 4 Panel Mounting Packing 1 GT10 General Description This manual 1 Explanation of the GOT model name GT1040 x L_ Power type D 24VDC L 5VDC B Black S STN color L STN monochrome black white B STN monochrome blue white Resolution Q 320 x 240 QVGA Panel color type Display device type Blank less than 320 x 240 5 256 colors supported 0 Monochrome black white Display color type Screen size type 5 5 7 4 4 7 3 4 5 2 3 7 GOT1000 series GT10 1 Specifications 1 1 General Specifications Item Operating ambient Display section 0 to 50 C temperature Storage ambient temperature 20 to 60 C Operating ambient humidity Storage ambient humidity Conforms to JIS B3502 and vibration Vibration resistance 1IEC61131 2 vibration Shock resistance Operating atmosphere Operating altitude 2000 m 6562 ft max Installation location Inside control panel Overvoltage category 2 ll or less Pollution degree s 2 or less Cooling method Self cooling Grounding Specifications GT1045 QSBD GT1040 QBBD Other than display section 0 to 55 C When mounted horizontally 0 to 50 C When mounted vertically
31. this instruction may result in an accident due to incorrect output or malfunction Incorrect operation of the touch switch s may lead to a serious accident if the GOT backlight is gone out When the GOT backlight goes out causes the monitor screen to appear blank while the input of the touch switch s remains active This may confuse an operator in thinking that the GOT is in screensaver mode who then tries to release the GOT from this mode by touching the display section which may cause a touch switch to operate DESIGN PRECAUTIONS CAUTION e Do not bundle the control and communication cables with main circuit power or other wiring Run the above cables separately from such wiring and keep them a minimum of 100mm 3 94in apart Not doing so noise can cause a malfunction MOUNTING PRECAUTIONS DANGER e Be sure to shut off all phases of the external power supply used by the system before mounting or removing the GOT to from the panel Not doing so can cause the unit to fail or malfunction e When installing the battery wear an earth band etc to avoid the static electricity The static electricity can cause the unit to fail or malfunction MOUNTING PRECAUTIONS CAUTION WIRING PRECAUTIONS TEST OPERATION PRECAUTIONS STARTUP MAINTENANCE PRECAUTIONS STARTUP MAINTENANCE PRECAUTIONS Use the GOT in the environment that satisfies the general specifications described in this manual Not doing so can cause an electr