Home
INSTALLATION MANUAL
Contents
1. OOO 3 0 D QUO OU oo Oo OC p C a e 406mm Y 11 480mm 100mm ro OOO Fix the enclosure to the wall using the three mounting holes provided Check the build amp condition of the wall to decide a suitable screw fixing The mounting holes are designed for No 8 roundhead or countersunk woodscrews or similar Remove any debris from the enclosure Take care not to damage the FACP during installation Approved Document No GLT MAN 111 PAGE 8 Issue 1 0 Authorised GH Date 14 01 2005 PREMIER M PLUS INSTALLATION MANUAL 4 CONNECTING MAINS amp BATTERY POWER 4 1 CONNECTING THE MAINS POWER The panel should be connected to 220 240V AC by INLET MAINS rated spur to the fuse box with 1mm to 2 5mm SUPPLY 3 core cable Nothing else should be connected to this supply This cable should be fire resistant The Live Earth and Neutral connections are marked by the Connection Block The Mains is protected by a quick blow 20mm 3 15A HBC fuse Also known as HRC The incoming mains cable should be kept separate from the zone cables to help minimise mains interference MAKE SURE ANY SPARE ENTRY HOLES ARE COVERED WITH THE RUBBER GROMMETS PROVIDED It is advisable to apply power to the panel before connecting any devices to check for correct operation and to familiarise yourself with the fire alarm panels controls
2. Figure 3 Power Supply PCB layout and Mains connection details 4 2 CONNECTING THE BATTERIES Although there are many sizes of suitable battery the sizes we usually recommend are 12V 7Ah The enclosure has been designed to hold this size battery To calculate the exact requirement use the equation in section 10 but as a rough guide Panel 4 6Ah 50 Detectors 0 1 Ah 5 Bells 0 1Ah BATTERY CONNECTIONS 12V 7 Ah 12V 7 Ah The ve of one battery is connected to the red battery lead The of the other battery is connected to Figure 4 Battery location and connection details the black battery lead The ve of the first battery is connected to the ve of the second battery using the link wire supplied Approved Document No GLT MAN 1 11 PAGE 9 Issue 1 0 Authorised GH Date 14 01 2005 PREMIER M PLUS INSTALLATION MANUAL 5 FIELD DEVICE TERMINATION 5 1 TERMINATING THE DETECTION AND ALARM SOUNDER CIRCUITS All cables entering the enclosure should have brass cable glands which will ensure a good ground to the EMC enclosure coating The Detector and Sounder circuits should be connected to the appropriate connector block on the Termination PCB as shown in Figure 6 below For detailed detector and alarm circuit wiring diagrams please refer to pages 4 a
3. Approved Document No GLT MAN 1 11 PAGE 4 Issue 1 0 Authorised GH Date 14 01 2005 PREMIER M PLUS INSTALLATION MANUAL 2 FIRST FIX All wiring must be installed to meet BS5839 Pt1 2002 and BS 7671 Wiring Regs standards Other National standards of fire alarm system installation should be adhered to where applicable 2 1 RECOMMENDED CABLE TYPES AND THEIR LIMITATIONS Screened cables should be used throughout the installation to help shield the Panel from outside interference and ensure EMC compatibility The two categories of cable according to BS5839 Pt1 2002 Clause 26 Fire Detection and Alarm Systems for Buildings Code of Practice for System Design Installation and Servicing are Standard fire resisting cable to PH30 classification of EN 50200 Enhanced fire resisting cable to PH120 classification of EN 50200 Note that all cables should be at least 1mm cross section On the Premier M Plus Panel the general recommendation would be to use standard fire resistant cable such as Firetuff FP200 or an equivalent These cables are screened and will provide good ECM shielding when properly grounded at the panel Certain system specifications may demand the use of a particular type of cable and due regard should be paid to this fact Depending on the environment the cables may need mechanical protection such as a conduit 2 2 MAINS WIRING RECOMMENDATIONS The Mains supply to the FACP is fixed w
4. select The LEDs will now flash on and off This Zone is now in test mode 6 Once testing of that zone is completed press select to exit test mode for that zone The LEDs will now flash 3 quick flashes then off 7 Press scroll button to move to another Zone to test or turn the control key switch to off position to exit test mode Approved Document No GLT MAN 1 11 PAGE 14 Issue 1 0 Authorised GH Date 14 01 2005 PREMIER M PLUS INSTALLATION MANUAL 9 GENERAL FAULT FINDING 9 1 ZONE FAULTS The Zone Faults are non latching faults That is if the fault has been cleared the panel will automatically reset itself Open circuit faults will be indicated by zone s fault LED being lit steady the internal Fault Buzzer will sound and the General Fault LED will be lit Short circuit faults will be indicated by zone s fault LED and the short circuit LED Flashing the internal Fault Buzzer will sound and the General Fault LED will be lit Suggested Action a If a bank of 8 zones are all showing O C check zone fuse FS1 on the relevant zone expansion card b Check that the correct end of line device has been fitted 100uF capacitor Disconnect the wiring for the zone showing fault and refit the end of line capacitor at that zone terminal in the panel If the fault condition for that zone clears this confirms there is a wiring fault d Double check the wiring and the end of line capacitor on the zone Trace the fault with
5. 5 18 111 CONNECTIONS 112 FUSES 12 CONTROL PANEL ELECTRICAL SPECIFICATIONS 19 12 4 ENCLOSURE SPECIFICATIONS 12 2 ELECTRICAL SPECIFICATIONS Approved Document No GLT MAN 1 11 PAGE 3 Issue 1 0 Authorised GH Date 14 01 2005 PREMIER M PLUS INSTALLATION MANUAL 1 INTRODUCTION THIS FIRE ALARM CONTROL PANEL IS CLASS 1 EQUIPMENT AND MUST BE EARTHED This equipment must be installed and maintained by a qualified and technically experienced person 1 1 HANDLING THE PCBS If the PCBs are to be removed to ease fitting the enclosure and cables care must be taken to avoid damage by static The best method is to wear an earth strap but touching any earth point eg building plumbing will help to discharge any static Hold PCBs by their sides avoiding contact with any components Always handle PCBs by their sides and avoid touching the legs of any components Keep the PCBs away from damp dirty areas e g in a small cardboard box 1 2 USING THIS MANUAL This manual explains in a step by step manner the procedure for the installation of the Premier M Plus Range of Fire Alarm Control Panels For full operational and maintenance information please refer to document GLT MAN 112 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK It also contains a System set up table and Design Installation and Commissioning Certificates that must be completed by the appropriate engineers prior to syst
6. Loss of Mains power Remedy a Check mains fuse in fused mains block Also check that main power is present b Check charger fuse FS1 2 Loss of Battery power Remedy a Check battery fuse FS2 b Check that battery connections are secure 3 Low Battery Remedy a Check battery voltage replace if necessary Approved Document No GLT MAN 1 11 PAGE 15 Issue 1 0 Authorised GH Date 14 01 2005 PREMIER M PLUS INSTALLATION MANUAL 4 Wrong Charging Voltage The charging voltage should be 28 4V off load at 20 C If it has been altered reset using potentiometer VR1 5 Overcharged Batteries Remove the batteries and measure the voltage If it is reading over 27 4 then the batteries are overcharged Try to run the panel on batteries only for half an hour or so to try to discharge the batteries If this doesn t solve the problem replacement batteries will be required 9 4 EARTH FAULTS An EARTH fault indicates that something is shorting to earth usually through the cable screen Disconnect the earth screens one at a time to determine the problem line Note connecting other equipment eg an oscilloscope to the panel can give an earth fault The voltage between battery and earth should be 14 16 volts If it is not the voltage measured should indicate what is shorting to earth 9 5 SOUNDER FAULTS Check that the correct END of Line resistor has been fitted 10K brown black orange gold Check tha
7. consideration for the type of fault indicated HINT splitting the cable half way down the zone and fitting the end of line capacitor to the new end point helps to determine which section of cable is giving the fault Note A possible fault is a detector head badly seated in a base that is not making a good connection A short circuit a zone could be caused by the end of line capacitor being fitted backwards d Check that the detectors are compatible with this FACP Note that some makes of detector will require a series resistor or diode to be fitted to work properly There is usually a spare connector on the base to accommodate this check instructions that came with the detector e Measure the resistance of the zone cabling Remove from panel and short out end of line Ideally this should be less than 50 ohms Above 70 ohms may cause an open circuit fault 9 2 SYSTEM FAULT system fault is an abnormal microprocessor running condition due to various unexpected phenomena This will result in the panel attempting to correct itself Should this fault occur the System Fault LED General Fault LED General Fault relay and fault internal buzzer will be constantly active until the control keyswitch is turned from off position to control enable position This should cause this fault condition to reset If not consult your supplier 9 3 SUPPLY FAULTS A power supply fault is indicative of one or more of the following faults 1
8. 1 0 Authorised GH Date 14 01 2005 PREMIER M PLUS INSTALLATION MANUAL 8 ZONE TEST 8 1 WHY USE ZONE TEST To aid commissioning and assist routine maintenance check a non latching one man test facility is available When a detector or manual call point is triggered on any zone in Test the Alarm sounders operate for approximately four seconds on and four seconds off This cycle continues until the cause of the Alarm is removed either by the test smoke clearing from the detector or the manual call point being reset at which point the detector circuit also automatically resets Should an Alarm occur on a zone that is not programmed to test the Alarm will be processed in the normal way The testing of the zone in test will temporarily be suspended until the Alarm s from the other zones are investigated and then reset At this point zone retesting may resume 8 2 TO PROGRAMME ZONE IN TEST NOTE Only one zone can be programmed in test at any one time 1 Insert and turn control key to enabled position 2 Press engineer button until the General Zone test LED is on flashing fast 3 Press Delay Override Silence Silence Delay Override The General Zone Test LED will now flash 3 quick flashes then off 4 Press scroll switch and Zone one fault amp test LEDs will flash in synchronisation with the General Zone test 5 Press scroll button to the desired Zone for test Once the desired Zone LED is flashing press
9. ENDATIONS 2 3 DETECTOR CIRCUIT WIRING DIAGRAM 2 4 SOUNDER CIRCUIT WIRING DIAGRAM 2 5 AUXILIARY OUTPUT WIRING 3 MOUNTING THE FIRE 8 3 1 PLANNING CABLE ENTRY 3 2 FIXING THE BACKBOX TO THE WALL 4 CONNECTING MAINS amp BATTERY 9 4 1 CONNECTING MAINS POWER 4 2 CONNECTING THE BATTERIES 5 FIELD DEVICE 11 10 5 1 TERMINATING THE DETECTION AND ALARM SOUNDER CIRCUITS 5 2 AUXILIARY INPUT AND OUTPUT TERMINATIONS 6 CONFIGURING THE 2 2 11 6 1 SETTING THE ADD ON SOUNDERS FOR COMMON OR ZONAL OPERATION 6 2 SOUNDER ACTIVATION DELAY 6 2 1 DECIDING TO SET A DELAY 6 2 2 TO SET A DELAY 6 2 3 DELAY INDICATION AND OVERRIDE 6 3 USING SOUNDER DELAY amp ZONAL TO COMMON TIMER 7 ZONE DISABLEMENT 13 ccciccccecsscsccvsvevcscvcavaseviscveveudececsvisivaeendecwe 13 7 1 WHY USE ZONE DISABLEMENT 7 2 TO PROGRAM A ZONE OR SOUNDERS AS DISABLED 8 E 14 8 1 WHY USE ZONE TEST 8 2 TO PROGRAM ZONE IN TEST 9 GENERAL FAULT 02 4 1 121 15 9 1 ZONE FAULTS 9 2 SYSTEM FAULT 9 3 SUPPLY FAULTS 9 4 EARTH FAULTS 9 5 SOUNDER FAULTS 9 6 REPEATER FAULTS 9 7 F A R E FAULTS 10 STANDBY BATTERY CALCULATION GUIDE 17 11 TERMINATION
10. FIRE ALARM CONTROL PANEL DESIGNED TO COMPLY WITH EN54 PT2 amp PT4 1997 INSTALLATION MANUAL PREMIER M PLUS INSTALLATION MANUAL PREMIER M PLUS OVERVIEW The Premier M plus is the latest medium size conventional panel from Zeta Alarm Systems and is designed to replace the existing Premier M and Premier MZ panels Its Features include Designed to EN54 Parts 2 amp 4 It is available in sizes from 8 to 24 zones in 4 zone increments Automatically uses diode bases for line continuity Four common sounder circuits 150mA Each Serial Repeater Output Fire amp Fault Relays SELV F A R E Output which can be disabled Auxiliary supply 29 Volts 250 mA Optional add on Zonal Sounder Circuits 50 Max Zonal sounders protected by self resetting thermal fuse Zone amp Sounder Disablement facility One man test mode Sounder delay facility Zonal to common timer when fitted with zonal sounder boards 3 amp power supply Approved Document No GLT MAN 1 11 PAGE 2 Issue 1 0 Authorised GH Date 14 01 2005 PREMIER M PLUS INSTALLATION MANUAL CONTENTS 1 INTROD GTION octaua 4 11 HANDLING THE PCBS 1 2 USING THIS MANUAL 1 3 ABOUT THE PREMIER M PLUS FACP amp INTEGRAL PSE 1 4 DESIGNING THE SYSTEM 1 5 EQUIPMENT GUARANTEE 2 FIRST FIX 5 04 1 211 5 2 1 RECOMMENDED CABLE TYPES AND THEIR LIMITATIONS 2 2 MAINS WIRING RECOMM
11. LLATION MANUAL 6 2 3 DELAY INDICATION AND OVERRIDE If a delay is set the fire panel will light the General Disablement LED and Sounder Delay LED to indicate that the sounders are delayed If an alarm occurs the fire LEDs will light as usual but the sounders will not start until the delay period has expired After the delay period the Gen Disablement and Delay LEDs will extinguish amp the sounders will start Pressing the OVERRIDE SOUNDER DELAY switch will override the delay at any time and results in the sounders being turned on immediately If on investigation the panel was activated by a false alarm turn the keyswitch to Controls Enabled and press the reset button This will return the system to normal without the sounders being activated Assuming the cause of the false alarm has been removed The delay can be removed by returning the rotary switch SW2 to position 0 6 3 USING SOUNDER DELAY amp ZONAL TO COMMON TIMER If BOTH the delay and the timer are set on receiving an alarm the panel will Light the relevant Zone Fire LED and the common fire LED Turn on its internal Buzzer Turn on the fire relay and F A R E circuit It will then wait for the delay set on rotary switch SW2 Turn on the 4 common sounder circuits Turn on the zonal sounder of the zone that signalled the alarm It will then wait for the timer delay set on rotary switch SW3 Turn on all the zonal sounders When selecting Delay amp Timer settings c
12. R E Continue to press scroll until the desired Zone or sounder is flashing 5 When an item has been disabled the DISABLEMENT LED will be lit The item that has been disabled will now flash 3 quick flashes then on This means that it has been disabled but is still the focus of the disablement select mode If scroll is pressed once more the disabled part s LED will now be lit steady and the next item will flash 3 quick flashes then off 6 If more than one zone needs to be disabled then press scroll again until the required zone is selected 7 If the panel needs to be taken out of SELECT DISABLEMENT MODE eg to silence a fault on another part of the system turn the keyswitch off then back on again 8 Once all the work has been done the zones need to be enabled again If the panel is still in SELECT DISABLEMENT MODE jump to paragraph 9 otherwise turn the keyswitch to controls enabled press FUNCTION button GENERAL DISABLEMENT LED will flash fast Press scroll and it will flash with a 3 quick flashes then off pattern The panel is now in SELECT DISABLEMENT MODE 9 Press the scroll button until the disabled zone or sounder has been selected Press engineer button Scroll to any other disabled zone and enable in the same way When all zones are enabled again the GENERAL DISABLEMENT LED will flash 3 quick flashes then off Turn the keyswitch to off to return the system to normal Approved Document No GLT MAN 1 11 PAGE 13 Issue
13. VALUE CALCULATIONS PANEL CURRENT IN MAINS FAIL NO ZONE SOUNDERS PANEL CURRENT IN MAINS FAIL WITH ZONE SOUNDERS PANEL CURRENT IN ALARM Approved Document No GLT MAN 1 11 Issue 1 0 Authorised GH Date 14 01 2005 150mA 125 mA with buzzer silenced 175mA 150 mA with buzzer silenced 270mA PAGE 19
14. are should be taken not to exceed any local recommendations for maximum sounder delay Approved Document No GLT MAN 1 11 PAGE 12 Issue 1 0 Authorised GH Date 14 01 2005 PREMIER M PLUS INSTALLATION MANUAL 7 ZONE DISABLEMENT 7 1 WHY USE ZONE DISABLEMENT To aid commissioning and assist routine maintenance checks any of the zones or the sounder circuits can be disabled When a zone or sounder circuit is disabled the panel will not respond to any fault or fire signals it receives from that zone This might be used if the system requires routine maintenance and the customer needs the system to continue running but doesn t want spurious false alarms The panel will respond in the usual manner to any events in any non disabled zones 7 2 TO PROGRAMME ZONE OR SOUNDERS AS DISABLED Any number of zones or the sounders can be disabled but it is good practice to only disable one zone at a time 1 Insert and turn control key to enabled position 2 Press Function button and the GENERAL DISABLEMENT LED will come on flashing fast 3 Press Scroll switch and the GENERAL DISABLEMENT LED will flash with a 3 quick flashes then off pattern Zone 1 fault and zone 1 Test Disablement LEDs will also flash with the same pattern The panel is now in SELECT DISABLEMENT MODE 4 Press select to disable Zone 1 or scroll to the item to disable The panel will scroll through zones 1 24 then zone sounder 1 24 then common sounders then F A
15. ault condition the output relay turns off to ensure failsafe operation even in the event of total power loss That is the normally open contact will be closed when there is no fault and open when there is a fault This should be taken into account when any device is connected to the fault relay FAULT Trigger I P INDICATION F DEVICE The fault relay is used to connect to a remote NOTE THE NC CONTACT indication device IS OPEN WHEN THERE IS 99 C9 C9 NO FAULT NO CM NC FAULT RELAY Or OUTSTATION Here the relays are used to FIRE TO ADDRESSABLE communicate with a larger INPUT FIRE ALARM PANEL addressable fire alarm system An LA example use of this might be a FAULT eet warehouse which uses several INPUT flame detectors and needs to be 69 69 69 62 62 62 part of a larger system NO CM NC NO CM NC FIRE RELAY FAULT RELAY 2 5 3 Fire Alarm Routing Equipment Output F A R E Monitored 24V nominal output This is 24V 100mA output that activates in any fire condition and is used for driving local fire fighting equipment such as sprinkler systems magnetic door holders air conditioning shut off etc It is active until the panel is reset It can be disabled through the zone sounder disablement function which may be useful during maintenance tests if the panel is connected to a central station via an autodialler 2 5 4 Serial Repeater Output The Premier M Plu
16. e as shown on page 9 2 4 SOUNDER CIRCUIT WIRING DIAGRAM SND SND SOUNDER SOUNDER SOUNDER SOUNDER 10K cC EDO Line Resistor Note If non polarised alarm devices eg some types of old mechanical bell or a relay are used then a diode will have to be placed in line with the device to enable fault monitoring They may also need a back EMF protection diode symptoms Chattering sounder relays that don t turn off SND CONNECTOR BLOCK L POLARISING DIODE SND 10K End of Line Resistor Approved Document No GLT MAN 111 PAGE 6 Issue 1 0 Authorised GH Date 14 01 2005 PREMIER M PLUS INSTALLATION MANUAL 2 5 AUXILIARY OUTPUT WIRING 2 5 1 Auxiliary Fire Output AUX Voltage free changeover contacts Changes over in any fire condition and is used for driving local fire fighting equipment such as sprinkler systems magnetic door holders air conditioning shut off etc AUTO Trigger I P_ DIALER The fire relay can be used to connect to various devices which are activated on fire alarm Eg Auto dialer magnetic door release 24V sprinkler system etc SID S NO CM NC FIRE RELAY 2 5 2 Fault Output FAULT Voltage free changeover contacts This Output is energised in the quiescent condition In a f
17. em handover Unlike the User Manual this Installation Manual must not be left accessible to the User 1 3 ABOUT THE PREMIER M PLUS FIRE ALARM CONTROL PANEL amp INTEGRAL PSE The PREMIER M PLUS Fire alarm control panel is e t has a maximum battery capacity of 7 Ah available in 8 12 16 20 amp 24 Zone sizes It has an in built capability of operating with Diode It has 4 common sounder output circuits each bases for line continuity on head removal capable of supplying 150mA It will operate in ambient temperatures of 5 to It has the option of fitting zonal sounder circuits 40 C These can be configured as common triggered It will operate a relative humidity of up to 93 or zone triggered non condensing It has a 250mA auxiliary 30V output It will withstand vibrations between 5 amp 150 Hz It has a set of fire relay contacts voltage free rated t has a maximum capacity of 32 devices per zone at 1A SELV But for locating potential future problems or It has a set of fault relay contacts voltage free events we would usually recommend a practical rated at 1A SELV normally energised maximum of 20 devices per zone It has the ability to disable any zone any zonal The PSE is linear with a 3 0A output at system sounder or the common sounder circuits voltage 18 32V It has a one man test mode which resets the zone The charger amp battery are both fused at 3 15A TD in test after 4 seconds EN54 option with The PSE wi
18. et the sounders to common set the rotary switch SW3 to 0 To set the sounders to Zonal with delay to common select the desired delay 1 9 minutes on rotary switch SW3 6 2 SOUNDER ACTIVATION DELAY 6 2 1 DECIDING TO USE A DELAY A delay of up to nine minutes from the Fire Alarm Panel being triggered to its Alarm sounder outputs being activated can be programmed into the panel by the Engineer This is a particularly useful feature for schools nightclubs and other public places where the nuisance and panic caused by a false alarm must be avoided It should be noted that the delay period will apply to ALL zones When an Alarm occurs on any zone it is processed as normal However the activation of the sounders is postponed until the delay period has expired thus allowing the cause of the Alarm to be investigated by the User If the alarm is false the alarm can be cancelled 6 2 2 TO SET A DELAY Open the panel door and set the SND DELAY rotary switch 2 SW2 using a terminal screw driver to the delay required SW2 Setting External sounder delay in minutes No delay 1 minute 2 minutes Oo 3 minutes pe 4 minutes 5 minutes p Co 6 minutes 7 minutes 8 minutes 9 minutes 00 EG The above example would have a delay of 1 minute Approved Document No GLT MAN 111 PAGE 11 Issue 1 0 Authorised GH Date 14 01 2005 PREMIER M PLUS INSTA
19. for ZONAL SOUNDER 11 25 ZONAL SOUNDER 12 amp Connector for ZONAL SOUNDER 12 26 ZONAL SOUNDER 13 amp Connector for ZONAL SOUNDER 13 27 ZONAL SOUNDER 14 amp Connector for ZONAL SOUNDER 14 28 ZONAL SOUNDER 15 amp Connector for ZONAL SOUNDER 15 29 ZONAL SOUNDER 16 amp Connector for ZONAL SOUNDER 16 Premier Plus fire alarm panel has 3 banks of detection zones or detection zones with zonal sounders The ones in bank 1 will be for zones 1 8 the ones in bank 2 will be for zones 9 16 and the ones in bank 3 will be for zones 17 24 11 2 FUSES FUSE NO DESCRIPTION RATING FS1 ZONE Zone Fuse 500mA time delay 5 x 20mm glass FS1 Charger Fuse 3 15A time delay 5 x 20mm glass FS2 Battery Fuse 3 15A time delay 5 x 20mm glass FS3 F A R E Fuse 100mA time delay 5 x 20mm glass FS4 Sounder circuit 1 150mA time delay 5 x 20mm glass FS5 Sounder circuit 2 150mA time delay 5 x 20mm glass FS6 AUX Supply 250mA time delay 5 x 20mm glass FS7 Sounder circuit 3 150mA time delay 5 x 20mm glass FS8 Sounder circuit 4 150mA time delay 5 x 20mm glass INLET FUSE Mains Protection Fuse 3 15A Quick Blow HBC 5 x 20mm ceramic Approved Document No GLT MAN 111 Issue 1 0 Authorised GH Date 14 01 2005 PAGE 18 PREMIER PLUS INSTALLATION MANUAL 12 PANEL SPECIFICATIONS 12 1 ENCLOSURE SPECIFICATIONS DESCRIPTION VALUE ENCLOSURE SIZE 480 x 395
20. iring using Fire resisting 3 core cable Between 1 mm and 2 5mm or a suitable 3 conductor system fed from an isolating double pole switch fused spur fused at 5A IT SHOULD NOT BE CONNECTED THROUGH AN RCD This should be secure from unauthorised operation and be marked FIRE ALARM DO NOT SWITCH OFF The supply must be exclusive to the Fire Panel MAKE SURE ANY SPARE ENTRY HOLES ARE COVERED WITH THE GROMMETS PROVIDED For information on how to connect Mains to the Panel s Power Supply PCB see page 8 Also refer to rating information on the mains cover inside the FACP 2 3 DETECTOR CIRCUIT WIRING DIAGRAM The Premier M Plus comes with 8 12 16 20 or 24 Detection circuits Zones A maximum of 32 devices i e smoke detectors heat detectors or Manual Call Points can be fitted to each circuit ALL DEVICES MUST BE POLARISED Typical detector circuit wiring Fyreye Detectors ZONE END of LINE CAPACITOR 100uF 25 100V END of LINE CAPACITOR 100uF 25 100V If ALL the call points are connected to the start of the zone then conventional bases can be used instead of diode bases Approved Document No GLT MAN 1 11 PAGE 5 Issue 1 0 Authorised GH Date 14 01 2005 PREMIER M PLUS INSTALLATION MANUAL An End of Line capacitor provided in the Panel must be connected across the terminals of the last device on each circuit to allow the wiring to be monitored It is polari
21. ised GH Date 14 01 2005 PREMIER PLUS INSTALLATION MANUAL 11 PCB TERMINATION CONNECTIONS 9 LL 11 1 CONNECTIONS Connection No Description Use 1 ZONE 1 amp Connect to Zone 1 2 ZONE 2 amp Connect to Zone 2 3 ZONE 3 amp Connect to Zone 3 4 ZONE 4 amp Connect to Zone 4 5 ZONE 5 amp Connect to Zone 5 6 ZONE 6 amp Connect to Zone 6 7 ZONE 7 amp Connect to Zone 7 8 ZONE 8 amp Connect to Zone 8 9 SND 1 amp Connect to sounder circuit 1 sirens bells 10 SND 2 amp Connect to sounder circuit 2 sirens bells 11 SND 3 amp Connect to sounder circuit 3 sirens bells 12 SND 4 amp Connect to sounder circuit 4 sirens bells 13 FIRE RELAY NO CM NC Activates on fire including test mode 14 FAULT RELAY NO CM NC Activates on fault 15 EARTH MONITORING POINT FOR EARTH FAULTS 16 F A R E amp FIRE ALARM ROUTING EQUIPMENT 17 SERIAL REP A amp B RS485 SERIAL REPEATER CONNECTION 18 AUX SUPPLY 250 mA Supply System voltage 29 31 V dc 19 BATTERY amp Connect 2 x 12V SLA batteries SERIES ie 24V 20 Thermistor Connector to protect batteries 21 AC AC Connected to transformer secondary 30VAC 22 ZONAL SOUNDER 9 amp Connector for ZONAL SOUNDER 9 23 ZONAL SOUNDER 10 amp Connector for ZONAL SOUNDER 10 24 ZONAL SOUNDER 11 amp Connector
22. ll draw a maximum of 25uA from the requirements battery in the event of mains failure The FACP It has a sounder delay facility 0 9 minutes in 1 will continue to take around 150mA minute steps EN54 option with requirements The FACP amp PSE should be maintained as When the add on sounders are configured as described in section 3 of the User Manual zonal there is a timer which determines when all Maintenance Guide amp Log Book other sounders will start evacuation 1 4 DESIGNING THE SYSTEM This manual is not designed to teach Fire Alarm System design It is assumed that the installer has an understanding of Fire Alarm System components and their use We strongly recommend consultation with a suitably qualified competent person regarding the design of the Fire Alarm System The System must be commissioned and serviced in accordance with our instructions and the relevant National Standards Contact the Fire Officer concerned with the property at an early stage in case he has any special requirements If in doubt read BS 5839 Pt 1 2002 Fire Detection and Alarm Systems for buildings Code of Practice for System Design Installation and Servicing available from the BSI or at your local reference library 1 5 EQUIPMENT GUARANTEE If this equipment is not fitted and commissioned according to our guidelines and the relevant National Standards by an approved and competent person or organisation the warrantee may become void
23. nd 5 Brass Glands 144 d GR ee 22 COVERED WITH THE RUBBER GROMMETS PROVIDED ay 12V 7Ah 12 7 Ah Figure 6 Detector and Sounder Circuit Connection 5 2 AUXILIARY INPUT AND OUTPUT TERMINATIONS Connect auxiliary input and output cables to the appropriate connector block terminals on the Termination PCB See Page 15 Screened cables should be terminated as per figure 6 For a full description of the inputs and outputs available on the Premier M Plus range of Fire Panels including typical wiring diagrams please refer to pages 5 amp 6 Approved Document No GLT MAN 1 11 PAGE 10 Issue 1 0 Authorised GH Date 14 01 2005 PREMIER M PLUS INSTALLATION MANUAL 6 CONFIGURING THE PANEL 6 1 SETTING THE ADD ON SOUNDERS FOR COMMON OR ZONAL OPERATION The add on sounders zonal sounders can be configured in one of 2 ways Common all sounders will start immediately when the panel receives an alarm signal Zonal with timer to common At first only the sounders in the zone that signalled the alarm will start After the delay set with the rotary switch 1 9 minutes in 1 minute increments all the zonal sounders will start This may be useful in a large building where you may not want to start a full building evacuation immediately To s
24. ones Eg lon detector 0 00005 Amp 50 Optical Detector 0 0001 Amp 100 uA Typical Example A system comprises of 24 zones Each zone has 20 smoke detectors detectors each zonal sounder has 1 bell connected 14 bells are connected to the common sounder circuit The required standby is 24 hours It will need to operate in alarm for v2 hour Calculate the battery size required TALM 0 5 Hr panel 0 270 24 14 x 0 025 0 95A This typical bell current is 25 mA Most alarm Devices show their operating current Tspy 24 Hr lap 0 150A laz 24 x 20 x 0 00006 0 0288A the quiescent current for a typical optical detector is 60 pA Therefore using the equation Battery Size Standby time in Amp Hours 1 25 x X larm Tspy X lap loz Battery Size Standby time in Amp Hours 1 25 x 0 5 x 0 270 0 95 24 x 0 150 0 0288 Battery Size Standby time in Amp Hours 1 25 x 0 61 24 x 0 1788 Battery Size Standby time in Amp Hours 1 25 x 0 61 4 2912 Battery Size Standby time in Amp Hours 1 25 x 4 9012 Battery Size Standby time in Amp Hours 6 13Amp Hours This system would require a minimum of 6 13Ah batteries so we would recommend using 7Ah batteries a system with a heavier load it may be necessary to use larger batteries This may require a separate battery box to hold the batteries Approved Document No GLT MAN 111 PAGE 17 Issue 1 0 Author
25. s has an optional serial repeater It is connected to the main panel by 4 cores 2 for power 2 for RS485 Data The Repeater is fully functional and can silence and reset the panel The termination for the above inputs must be as indicated on the main PCB See page 15 The Earthing of the cable screens should be as shown on page 9 Approved Document No GLT MAN 1 11 PAGE 7 Issue 1 0 Authorised GH Date 14 01 2005 PREMIER M PLUS INSTALLATION MANUAL 3 MOUNTING THE FIRE ALARM PANEL It is recommended that the panels door be removed to avoid accidental damage Also the termination PCB could be removed and stored in a safe place while fixing the back box to the wall 3 1 PLANNING CABLE ENTRY Fig 2 below shows the location of the cable entries to facilitate planning of wiring home runs to be brought to the panel The grommets can be easily removed by a push from inside the control panel box If a grommet is removed fill the hole with a brass cable gland lf any knockout is removed but subsequently not used it should be covered up The 230Va c Mains cable must be fed into the enclosure via one of the cable entries at the top right corner of the back box Refer to Connecting the Mains on Page 8 3 2 FIXING THE BACK BOX TO THE WALL Figure 2 Plan view inside the enclosure without PCBs Side view for surface flush installation
26. t all sounder fuses are OK FS4 FS5 FS7 amp FS8 150mA If working on an existing installation check that the devices are polarised See Page 5 Check cable continuity remove from panel and measure continuity Should read 10K 9 6 REPEATER FAULTS Check that the power and RS485 connections between the panel and repeater are correct Check The AUX supply fuse in the panel FS6 250 Check the supply fuse in the repeater 51 500mA 9 7 F A R E FAULTS Check that the correct END of Line resistor has been fitted 10K brown black orange gold Check there are no open or short circuits on the F A R E line Check that the fuse is OK FS3 100mA QB Approved Document No GLT MAN 1 11 PAGE 16 Issue 1 0 Authorised GH Date 14 01 2005 PREMIER M PLUS INSTALLATION MANUAL 10 STANDBY BATTERY CALCULATION In order to calculate the standby battery size required the following formula can be used Battery Size Standby time in Amp Hours 1 25 x X larm Tsev X laz iid Maximum time in hours required for the alarm gt hour is most common time Total Alarm Current amps for all alarm devices connected to the alarm circuits Standby time in hours for the system after mains failure normally 24 48 or 72 hr lap Quiescent current in amps of control panel in fault condition because of mains failure loz Quiescent current in amps of all detection z
27. ty sensitive and connected with the arrows pointing to zone ve Using detector bases with continuity diodes fitted will allow all devices including Manual Call Points to remain operational if a detector is removed from its base Old Manual call points which just cause a short circuit not directly compatible as they would cause RESISTOR 1 WATT MIN short circuit fault Fitting a 470R resistor in line with the OD red call point will allow it to work PONT Note if this is the last device the end of line ve will TO NEXT DEVICE connect to the connector block NOT the call point OR END OF LINE Other makes of detector will have different connections but in general they are wired in one of 2 ways SPLIT NEGATIVE IN amp OUT to same terminal IN to stripe side of continuity diode OUT to non stripe side of continuity diode Or SPLIT POSITIVE IN to non stripe side of continuity diode OUT to stripe side of continuity diode IN amp OUT to same terminal Some makes of detector will connect the ve to a 470R load resistor or a polarisation diode to enable the detector to work correctly with European Fire Alarm Panels For more specific device wiring information please refer to the device manufacturers own instructions The termination of each detection circuit must be as indicated on the main PCB See page 15 The Earthing of the cable screens should b
28. x 100 mm TOP CABLE ENTRIES 20 x 19mm DIA GROMMETED ENTRIES BOTTOM CABLE ENTRIES 10 x 19mm KNOCKOUT ENTRIES REAR CABLE ENTRIES 2 SNAP OUTS 60 x 20mm 12 2 ELECTRICAL SPECIFICATIONS ELECTRICAL DESCRIPTION VALUE MAINS VOLTAGE 230V AC 10 50 60 Hz BATTERY VOLTAGE 24V DC 2 X 12V SLA BATTERY SYSTEM VOLTAGE 24V DC NOMINAL 18 32 V SYSTEM VOLTAGE RIPPLE 2N PK PK MAX CHARGER SIZE UP TO 7AH in 24 Hours ZONE VOLTAGE 21V DC NOMINAL 20 22 5V SOUNDER ALARM OUTPUTS 4 x 150mA 29V DC Nominal ZONAL SOUNDER CIRCUITS OPTIONAL 8 12 16 20 24 x 50mA 29V DC Nominal AUXILIARY FAULT OUTPUT 1 x RELAY SELV 1A MAX AUXILIARY FIRE OUTPUT 1 x RELAY SELV 1A MAX F A R E OUTPUT 1 X 100mA Q 29V DC NUMBER OF ZONES 8 12 16 20 24 MAXIMUM ZONE CAPACITY 32 DEVICES PER ZONE MAXIMUM ZONE RESISTANCE 70 ohms AUXILIARY SUPPLY 250 29 V dc NOMINAL SOUNDER ACTIVATION DELAY 0 9 MINUTES IN 1 MIN INCREMENTS ZONAL TO COMMON TIMER 0 9 MINUTES IN 1 MIN INCREMENTS ZONE END OF LINE DEVICE 100uF CAPACITOR STRIPE TO ZONE VE SOUNDER END OF LINE DEVICE 10 K RESISTOR CHARGER VOLTAGE 28 4V 25 C NO BATTERY CONNECTED CHARGER SHORT CIRCUIT PROTECTION Batteries less than 20V TOTAL PSU OUTPUT 3 Amp MAXIMUM CHARGING CURRENT 600mA PANEL LOAD FOR BATTERY
Download Pdf Manuals
Related Search
Related Contents
Maytag MFD2562VEA10 User's Manual Electronic Breaker EB1 Manuale di installazione ed uso MMusb2232 User`s Manual 20歳の記念日 CD AUDIO OCTOBRE 2011 Toshiba Satellite Pro R50 取扱説明書 125mm 防じんマルノコ Manual da impressora - Epson America, Inc. Excellence 50XT RCH Copyright © All rights reserved.
Failed to retrieve file