         Contents
1.       BATTERY PACK REPLACEMENT    The UPS is also equipped with a dedicated battery pack that allows for easy replacement of batteries  hot swap  in  complete safety  thanks to the protected connection system     WHEN THE BATTERY PACK IS DISCONNECTED  THE LOADS CONNECTED TO THE UPS ARE    e  NOT PROTECTED IN THE EVENT OF A MAINS FAILURE  e THE BATTERY PACK IS VERY HEAVY  USE EXTREME CAUTION WHEN REPLACING IT     1  Set the UPS in    battery swap    mode by pressing and holding both the ON and SEL button for 4 seconds  See  par  USE   Operating mode configuration  on the display will appear the code  C02  NOTE  in this condition the    load is powered from the mains supply        4 sec  ON SEL    2  The battery pack is positioned behind the UPS front panel  Remove the front panel as shown in the figure  below        17    3  Remove the battery pack s retention panel carrying out the operations shown in the figure below  Disconnect  the connector that connects the battery pack to the UPS        4  Slip off the battery pack pulling it towards the outside  as shown in the figure below  Be careful when extracting  and lifting up the battery pack as it is heavy   ATTENTION  the new battery pack must contain the same number  and type of batteries  see the label located on the battery pack near the connector         5  Insert the new battery pack into the compartment  sliding it into the UPS  Connect the battery pack cable to the  UPS  Replace the battery pack retaining plate and clo
2.     USE    CONNECTIONS AND SWITCHING ON FOR THE FIRST TIME  SWITCHING ON FROM THE MAINS  SWITCHING ON FROM THE BATTERY  SWITCHING OFF THE UPS    DISPLAY PANEL MESSAGES  UPS STATUS MESSAGES  MEASUREMENT DISPLAY AREA  CONFIGURING THE OPERATING MODE  POSSIBLE SETTINGS  ADDITIONAL FUNCTIONS  SOFTWARE    MONITORING AND CONTROL SOFTWARE  CONFIGURATION SOFTWARE    UPS CONFIGURATION    COMMUNICATION PORTS  RS232 CONNECTOR  COMMUNICATION SLOT    BATTERY PACK REPLACEMENT    TROUBLESHOOTING    ALARM CODES  FAULT  LOCK    TECHNICAL DATA                O O O IO           Q A                     O                      N N N                 hhh                         o OQO        N     i        NN    Xx    PRESENTATION    The VISION RACK series is the ideal solution for high end users who require high security and versatility from their  power systems  The VISION RACK is the best protection system available for network devices  servers and conventional  storage systems    The VISION RACK series is a range of UPS which utilises the very latest Line Interactive technology and sinusoidal    output voltage waveforms  This technology allows high efficiency and reduced energy consumption  whilst guaranteeing  a high level of protection against disturbances from the mains supply              UPS ViEWS    FRONT VIEW          Q  Display  2  Removable front panel     2  Multipurpose buttons  5  Battery pack retention panel     3  ON OFF Switch  6  Battery pack connector    REAR VIEW       rs       C
3.    supply is not required  When a contact is closed  a maximum current of 15mA circulates   All connections with the remote control terminal board are made through a cable which guarantees a double insulation    connection   Logic of the connections     e PIN 1 2 REPO    The function is activated when the contact is opened              2 HR  REPO                                     e PIN 2 3 REMOTE ON  REMOTE ON OFF    The feature is activated by closing the contact   Set by default as REMOTE ON  also configurable as REMOTE ON OFF using UPSTools software     o  3   ON  ON OFF   2                                                       13       SOFTWARE       MONITORING AND CONTROL SOFTWARE    The PowerShield  software guarantees effective  intuitive UPS management  displaying all the most important  information such as input voltage  applied load and battery capacity    It is also able to perform shutdown operations and send e mails  text messages and network messages automatically  when certain events  selected by the user  occur     INSTALLATION OPERATIONS    1  Connect one of the UPS s communication ports to one of the PC s communication ports using the cable  supplied     2  Download the software from the web site www riello ups com selecting the specific operating system   3  Follow the installation program instructions     4  For more detailed information please read the user manual which can be downloaded from www riello   ups com     CONFIGURATION SOFTWARE    The UPStoo
4.  seconds to turn off the UPS  For  complete shutdown  press the ON OFF switch        DISPLAY PANEL MESSAGES    This chapter describes  in detail  the various information that can be displayed on the LCD     UPS STATUS MESSAGES    ICON STATUS DESCRIPTION    Indicates a fault  Flashing The UPS is in stand by mode    Indicates regular operation    The UPS is operating from the mains    The UPS is operating from the battery  In this condition  the UPS emits  Fixed ages  an acoustic signal  beep  at regular 4 second intervals   Low battery pre alarm  Indicates that battery autonomy is coming to an  Flashing end  In this condition  the UPS emits a beep at regular 1 second  intervals     AVR active    Flashing Maintenance is required  Contact the support centre     Indicates that the timer is active  programmed switch on and switch off    The timer can be activated deactivated using the software provided     Flashing 1 minute until the UPS switches back on or 3 minutes until it switches off    Using UPStools software an event associated with the EnergyShare  Continuous    sockets was configured  e g  end of discharge pre alarm threshold  but  the sockets are active at this time     Flashina   The associated event occurred  the EnergyShare outlets have been  9 disconnected       For more information about the configuration of the EnergyShare sockets  see  Additional Features     Fixed       10    MEASUREMENT DISPLAY AREA    The front panel can be used to display important UPS operati
5. O EXCEED THE SET 2 seconds   THRESHOLD    THE DISPLAY SHOWS  THE FOLLOW CODE  A63    THE BUZZER SOUNDS   CONTINUOUSLY AND   THE DISPLAY SHOWS  THE FOLLOW CODE  F38    THE UPS IS If possible  disconnect the power to the load  switch the  MALFUNCTIONING  IT WILL   UPS off and back on again  if the problem occurs again   PROBABLY LOCK SOON    call the support centre     THE BUZZER SOUNDS  CONTINUOUSLY AND THE TEMPERATURE OF  THE DISPLAY SHOWS THE HEATSINKS INSIDE  ONE OF THE FOLLOWING THE UPS IS TOO HIGH  CODES  F04  L04    Check that the temperature of the environment in which  the UPS is located does not exceed 40  C     THE BUZZER SOUNDS  CONTINUOUSLY AND  THE DISPLAY SHOWS  ONE OF THE FOLLOWING  CODES  F53  L53    THERE IS A FAULT ON ONE  OR MORE OF THE  UTILITIES POWERED BY  THE UPS    Disconnect all the utilities  switch the UPS off and back  on again  reconnect the utilities one at a time to identify  which one is faulty     THE BUZZER SOUNDS   CONTINUOUSLY AND   THE DISPLAY SHOWS  ONE OF THE FOLLOWING    If possible  disconnect the power to the load  switch the  UPS off and back on again  if the problem occurs again   CODES  F60  L05  L07  call the support centre   L13  L20  L21  L40  L41    L42  L43    THE UPS IS  MALFUNCTIONING    THE DISPLAY SHOWS  ONE OF THE FOLLOWING  CODES  C01  C02  C03    A REMOTE COMMAND IS  If unwanted  check the status of the command inputs on  ACTIVE any optional contact card        THE DISPLAY SHOWS THE  BATTERY SWAP    To exit from the  bat
6. TION automatically return to mains operation   FROM THE BATTERY    uw Ma um Qu If present  reset the circuit breaker by pressing the  INTERVENTION OF THE  button on the back of the UPS   INPUT CIRCUIT BREAKER   CAUTION  Check that there is no output overload to the  UPS     THE UPS DOES NOT THE TEMPERATURE OF   Check the temperature of the environment in which the         THE UPS IS LOWER THAN  UPS is located  if it is too low  bring it past the minimum  0  C threshold  0  C      CODE  A06  A08    THE DISPLAY SHOWS  THE FOLLOW CODES  INPUT RELAY FAULTY  L11    Switch off and disconnect the UPS from the power  supply and contact the support centre        19    PROBLEM POSSIBLE CAUSE SOLUTION    THE BUZZER SOUNDS  CONTINUOUSLY AND Reduce the load to within the threshold of 100   or user  THE DISPLAY SHOWS THE LOAD APPLIED TO  threshold in the case of code A54      ONE OF THE FOLLOWING THE UPS IS TOO HIGH If the display shows a lock  remove the load and switch  CODES  A54  F50  F51  the UPS off and back on again   F52  L50  L51  L52    THE DISPLAY SHOWS  THE FOLLOW CODE  A61 REPLACE THE BATTERIES   Contact the support centre for battery replacement     THE DISPLAY SHOWS   BATTERY MISSING OR NOT  THE FOLLOW CODE  A62   CONNECTED       Check that the battery pack is present and connected    THE BATTERIES ARE FLAT   THE UPS IS WAITING FOR   Wait until the batteries have recharged or force power   THE BATTERY VOLTAGE       manually by holding down the    ON    button for at least  T
7. Tochange the mode  press the  ON  button     e      confirm the mode chosen  hold down the    SEL    button for at least 3 seconds     POSSIBLE SETTINGS    The UPS is designed to be configured in various operating modes   e  L l normal operating mode  e        is the mode with which the UPS consumes the least amount of power  and is therefore the most efficient    e MODE using the UPS Tools software it is possible to customise the UPS operational characteristics     ADDITIONAL FUNCTIONS    MODE  BATTERY SWAP     The  battery swap  mode ensures that the UPS remains in normal operation from the mains supply  In this condition the  load is powered directly by the input mains  any disruption in the mains directly affects the load     ATTENTION   PRIOR TO PERFORMING THE FOLLOWING PROCEDURE ENSURE THAT THE UPS IS NOT IN  BATTERY OPERATION MODE    Attention  even when the UPS is switched on  the load is disconnected in the event of a mains blackout   If the input mains deviates from the established tolerances  the UPS automatically switches to Stdby mode and  disconnects the load     To force the UPS into  battery swap  mode press and hold the ON and SEL keys at the same time for at least 4 sec   The code  C02  appears on the display   To return to the normal operation mode press the ON and SEL keys again for at least 4 sec     PROGRAMMABLE AUXILIARY SOCKET  EnergyShare     The EnergyShare sockets are outlets that allow for the automatic disconnection of the load applied to them in 
8. certain  operating conditions  The events that determine automatic disconnection of the EnergyShare sockets can be selected by  the user through the UPStools configuration software  For example  it is possible to select disconnection after a certain  period of battery operation  or when the pre alarm threshold for battery discharge has been reached  or when an  overloading event occurs    By default the Energyshare sockets are not configured and therefore function as other outlets    The EnergyShare function is associated with an icon on the display whose meaning is explained in the paragraph  entitled  Display panel indications    The presence and the number of these sockets depend on the UPS type  and they are distinguished by a different colour  with respect to other sockets     12    REMOTE CONTROL TERMINAL BOARD    The remote control terminal allows for implementation of the REPO function  Remote Emergency Power Off  and to  remotely switch on off the UPS     The UPS is provided by the manufacturer with the REPO terminals short circuited  For installation remove the short    circuit and connect to the device s normally closed contact   In case of an emergency  if the stop device is used  the REPO control is opened and the UPS goes into stand by mode    and the load is completely disconnected   Attention  before restarting the UPS  reset the stop device   The circuitry of the remote control terminal board is self powered with SELV circuits  Therefore  an external voltage 
9. ls software allows the configuration and full display of the status of the UPS via USB or RS232   For a list of possible configurations available to the user  refer to the UPS Configuration paragraph     INSTALLATION OPERATIONS    1  Connect one of the UPS   s communication ports to one of the PC   s communication ports using the cable  supplied     2  Follow the installation instructions shown within the software manual which can be located in the UPSTools  directory or downloaded from the web site www riello ups com     CAUTION   If the RS232 communication port is used  it is not possible to communicate with the USB port and vice    versa   It is advisable to use a cable which is shorter than 3 metres for communication with the UPS   To obtain additional communication ports with different functions  independent from the standard USB and  RS232 ports on the UPS  various accessories are available which can be inserted into the communication  card slot     T 0     4         check the availability of new  more updated software versions and for more information about the       0   accessories available  consult the website www riello ups com     14       UPS CONFIGURATION    The table below illustrates all the possible configurations available to the user in order to best adapt the UPS for  individual requirements  It is possible to perform these operations using the UPStools software     FUNCTION DESCRIPTION   DEFAULT   POSSIBLE CONFIGURATIONS      e 50 Hz  Selects the nominal 
10. manuale d installazione ed uso     installation and use manual   installations  und bedienungsanleitung  manuel d installation et d utilisation e manual de instalaci  n y uso    VISION RACK VSR 800 1100    ppe      y riello ups  VISIONRAC        RIELLO ELETTRONICA    vAriello ups     i  INTRODUCTION    Congratulations on purchasing a UPS Vision Rack product and welcome to Riello UPS  To use the support service  offered by Riello UPS  visit the site www riello ups com    Our Company is a specialist in the design  development and manufacturing of uninterruptible power supplies  UPS    The UPS described in this manual is a high quality product which has been carefully designed and built in order to  guarantee the highest levels of performance    This device can be installed by anyone on the condition that they have READ THIS INSTALLTION AND USER  MANUAL CAREFULLY    The UPS and the Battery Box generate DANGEROUS internal electrical voltages  All maintenance operations    must be carried out by suitably qualified operators     This manual contains detailed instructions for using and installing the UPS and any additional Battery boxes   For information on how to use and maximise the performance of your device  please retain the CD containing  this manual and read it carefully before operating the equipment        lt   ENVIRONMENTAL PROTECTION    In the development of its products  the company devotes abundant resources to analysing the environmental aspects   All our products purs
11. mote  control terminal board  ON    e Pin 1 2 REPO  e Pin 2 3 Remote ON  Remote ON OFF    Remote Switch  on off feature       15                                                      COMMUNICATION PORTS    On the back of the UPS  see UPS Views   the following communication ports are present   e RS232 connector  e USB connector    e Expansion slot for additional communication cards    RS232 CONNECTOR  RS232 CONNECTOR             6 7 8 9  O f ooo   O  OO ON OMS                 PINE   SIGNAL NOTES  Programmable output      default  UPS in lock   TXD     Opto isolated contact max   30Vdc     5       RXD These contacts can be associated with other events using  GND the software provided    Power supply DC  Imax   20mA    Programmable output    For further information about interfacing with the UPS  refer to   default  low battery pre alarm  the manual provided   Programmable output      default  battery operation                         COMMUNICATION SLOT    The UPS is equipped with an expansion slot for optional communication  cards  see figure on right  which allows the device to communicate using  the main communication standards    Some examples     e Second RS232 and USB port   e Serial duplicator   e Ethernet network card with TCP IP  HTTP and SNMP protocols  e JBUS   MODBUS protocol converter card   e PROFIBUS protocol converter card       e Card with relay isolated contacts      A   To check the availability of other accessories  visit the website www riello ups com     16 
12. ng information  When the UPS is switched on  the display  shows the main voltage value    To display a different measurement  press the  SEL  button repeatedly until the desired measurement appears    In the event of a fault alarm  FAULT  or a lock  LOCK   the display will automatically show the type and code of the  corresponding alarm     Some examples are shown below     GRAPHIC EXAMPLE     DESCRIPTION GRAPHIC EXAMPLE     DESCRIPTION    Battery charge    Mains voltage percentage    Mains frequency Total battery voltage    UPS output voltage Applied load percentage    Current absorbed by the    Output voltage frequency load    Temperature of the    Residual battery autonomy electronics cooling  system inside the UPS                Faut Alam  the            4 Lock  2  the    2    corresponding code            LL  l     corresponding code is    Lir   displayed     L IL   displayed            1 been mmm    M The values shown in the images in the table are purely as an indication     2        FAULT   LOCK codes can only be displayed if they are active  presence of a fault alarm or a lock      11       CONFIGURING THE OPERATING MODE    The area of the display shown in the figure displays the active operating   ECO    mode and allows the user to choose other modes directly from the  display panel    MODE 5    HOW TO PROCEED   e      access the configuration area  hold down the  SEL  button for at least 3 seconds   e The icon corresponding to the mode currently set lights up   e  
13. o                  _       21       Active commands  Indicates the presence of an active remote command     CODE DESCRIPTION    C01 Remote control 1  Switch On Off     C02 Remote control 2  Load supplied by the mains   C03 Remote control 3  Switch On Off     C04 Battery test in progress       Lock    LOCK alerts are normally preceded by an alarm signal and their scale leads to the powering off of the inverter with the  load being powered by the bypass line  this procedure is excluded for locks due to serious  persistent overloads and  short circuits      L04  Los  Lo7  120  L2   140  La  La2  La3  L50  L51  L52  L53       22    TECHNICAL DATA    UPS MODELS VSR 800 VSR 1100  INPUT  Nominal voltage  Vac  220   230   240    Nominal frequency  Hz  90   60  Rated curent  1                          Recharge time  standard versions   h     4h for 8096 of the load  No  of internal batteries    OUTPUT    Nominal power       From mains  locked after 5 min       Overloading  100     load    110   From battery  locked after 60 sec    From mains  locked after 10 sec  Overloading  11096    load    15096  From battery  locked after 5 sec    From mains  locked after 1 sec  Load overload    15096  From battery  locked 0 5 sec       OTHER DATA    Leakage current towards ground  mA     Room temperature  3         0     40    Humidity    9096 without condensation        excessive battery discharge   over current   short circuit   over  Protection devices  voltage   under voltage   thermal  Dimen
14. ommunication port RS232  USB communication port  Remote control terminal board    Communication Card Slots       000          IEC 10A input plug  Cooling fans  IEC 10A output socket    Energyshare       DISPLAY PANEL VIEW    A                     ON SEL STBY ERES  FAULT  EE  Hz min ser  c   EC             3588 pend  Hz min             ON  button Load level indicator     SEL  button  Select  Configuration area     STAND BY    button Maintenance request  Regular operation Timer  Mains operation Measurement display area    Battery operation Stand by   alarm     6    7    9   49   42    AVR active EnergyShare                              Battery charge indicator    INSTALLATION          INITIAL CONTENT CHECK    After opening the packaging  it is first necessary to check the contents   The package must contain     UPS Schuko power cable   IEC 10A       2 IEC 10A connection cables USB cable       User manual CD   Safety manual Handles kit for rack installation                INSTALLATION ENVIRONMENT    The UPS and the Battery Box must be installed in ventilated  clean environments which are sheltered from bad weather   The relative humidity in the environment must not exceed the maximum values shown in the Technical Data table    The ambient temperature  whilst the UPS is in operation  must remain between 0 and 40  C  and the UPS must not be  positioned in places which are exposed to direct sunlight or to hot air     This is a category C2 UPS product  In a residential environment  
15. onfiguring operating modes     paragraph to set the required mode  For advanced UPS configurations execute the software UPSTools which  can be downloaded from the web site www riello ups com     SWITCHING ON FROM THE MAINS    1  Press the  ON  button for 1 second  After pressing it  all the icons on the display light up for 1 second and the  UPS beeps     2  Switch on the equipment connected to the UPS   When switching on for the first time only  after 30 seconds  check that the UPS is operating correctly     1  Simulate a blackout by disconnecting power to the UPS     2  Theload must continue to be powered  the icon on the display must light up and there must be a beep  every 4 seconds     3  When power is reconnected  the UPS must go back to operating from the mains     SWITCHING ON FROM THE BATTERY  1  Press the ON OFF switch located on the front panel   2  Hold down the  ON  button for at least 5 seconds  All the icons on the display light up for 1 second     3  Switch on the equipment connected to the UPS     SWITCHING OFF THE UPS  In order to switch off the UPS  hold down the  STBY  button for at least 2 seconds  The UPS goes back to stand by  mode and the AN icon starts to flash    1  Ifthe mains power is present  the ON OFF switch must be pressed to completely turn off the UPS     2  During battery mode operation with the timer not set  the UPS automatically switches off after 30 seconds   However if  the timer is set  press and hold down the  STBY  key for at least 5
16. output e 60 Hz    Output frequency frequency    e Auto  automatic learning of the input frequency    Selects the nominal output 220   240 in 1V steps    Output voltage voltage      e       Select one of the available n e ECO    Operating mode   5    modes  p g e OTHER  MODE     Automatic UPS power off in  battery operation mode if Disabled   cbe  the charge is lower than 596             Autonomy limit   Meximum battery operation Disabled e Disabled  complete battery discharge   time  1   65000  sec  in 1 sec steps    Estimated autonomy time  remaining for the battery in   1   255  min  in 1 min steps  low warning    Power off due to  minimum charge    Battery low  warning    Interval time for e Disabled  patery tesi automatic os test  1   1000  h in 1 hour steps    Maximum charge   Selects the user overcharge Disabled e Disabled  alarm threshold   limi e  0   103    in 1  steps    e Always connected  e Disconnection after no  seconds of battery  Select the auxiliary socket Always operation  operating mode connected e Disconnection after no  seconds of the battery  discharge pre alarm signal  e      see UPStools manual     EnergyShare    Select the required input  frequency range for normal     3    10    in 1  steps  operation    Input frequency  tolerance range    Waiting time for automatic a ny  Power on delay   switching back      after Disabled    mains power returns e  1 255  sec  in 1 sec steps    Select the feature  Pin 1 2 REPO  associated with the remote   Pin 2 3 Re
17. se the front panel  Set the UPS to normal operation mode  by pressing ON   SEL for at least 4 seconds     6  Make sure that the display does not show the code C02     7  Press the ON key for 5 seconds to start the battery status verification procedure     18    TROUBLESHOOTING    Irregular UPS operation is not always an indication of a fault  and can be due to minor or easy to resolve issues  It is therefore advisable to consult the table below as it contains information which is useful for solving the most common  UPS problems     PROBLEM POSSIBLE CAUSE SOLUTION    ON OFF SWITCH NOT  PRESSED Press the ON OFF switch on the front panel     MAIN    SABES Check that the power cable is connected correctly     THE DISPLAY DOES NOT  LIGHT UP NO MAINS VOLTAGE Check that the power reaches the socket where the UPS     BLACKOUT  is connected  try it with a table lamp  for example      If present  reset the circuit breaker by pressing the  INTERVENTION OF THE  button on the back of the UPS   INPUT CIRCUIT BREAKER   CAUTION  Check that there is no output overload to the  UPS     THE UPS IS IN STAND BY  Press the    ON    button on the front panel to power the  THE DISPLAY IS ON BUT MODE loads   THE LOAD IS NOT  POMWERES NO               Check the connection to the load     THE INPUT VOLTAGE IS          OUTSIDE THE PERMITTED Problem with the mains  Wait until the input mains    TOLERANCE RANGE FOR voltage returns within the tolerance range  The UPS will    THE UPS IS OPERATING MAINS OPERA
18. sions W x Dx H  mm  438 x 420 x 44    Weight  Kg        For additional details regarding technical data refer to website www riello ups com     7    rated load  rated voltage of 220 Vac  battery charging    To maintain output voltage within the accuracy range specified  recalibration may be necessary after a long period of operation     3  20 25      for longer battery life    23       RIELLO ELETTRONICA        riello Ups    www riello ups com    RPS SpA   Riello Power Solutions  Viale Europa  7  37045 Legnago  VR   Italy    OMNVSRS800RUENUA    
19. tery swap  mode  press and hold the  C02 MODE IS ACTIVATED    ON SEL buttons for at least 4 seconds  ATTENTION   The UPS in case of a permanent failure will be not able to supply the load  To ensure total protection of  your equipment we suggest you install an ATS device  Automatic Transfer Switch  or an external automatic  by pass     For more information visit www riello ups com    20         ALARM CODES    Using a sophisticated self diagnosis system  the UPS is able to check its own status for any anomalies and or faults  which may occur during normal operation and display them on the display panel  If there is a problem  the UPS signals  the event by showing the code and the type of active alarm on the display  FAULT and or LOCK      FAULT  FAULT alerts can be divided into three categories      gt  Anomalies  these are    minor    problems which do not cause the lock of the UPS but reduce performance or  prevent certain functions from being used      A06 T      _  A08  C Aasa   Load percentage greater than the user threshod set      A61   Replace batteries      A62   Batteries missing or Battery Box missing or not connected      A63   Waiting for battery charging          Alarms  these are more critical problems than anomalies because  if they persist  they could cause the UPS to  lock in a very short time              ear overtemperatre _    Fo   Temeawesmsollaly       F07    F8    Paeycageuly        FS    Ova                                             ad 809     at  Fe
20. this product may cause radio interference     The recommended operating temperature for the UPS and the batteries is between 20 and 25  C  The actual  operating life of the batteries is 5 years on average with an operating temperature of 20  C  If the operating  temperature reaches 30 C  the operating life is halved   in which case the user may be required to take additional measures     SE    _AAA A A A A  CONNECTIONS AND SWITCHING ON FOR THE FIRST TIME    1  Confirm that the installation upstream of the UPS is adequately protected against overloads and short circuits  lt  is recommended that the rating of this protection is either 10A or 16A type B or C  depending on the UPS power  rating   always check prior to connection     2  Power the UPS using the input cable provided   3  Press the ON OFF switch located on the front panel     4  After a few moments  the UPS will switch on  the display will light up  there will be a beep and the A icon will  start to flash  The UPS is in stand by mode  meaning that it is only consuming a small amount of power  The  microcontroller supervising the self diagnoses is powered  the batteries are charging  and everything is ready  for UPS activation  Battery operation is also in stand by mode provided that the timer is active     5  Ensure that the cables connecting any devices to the output sockets of the UPS do not exceed a maximum of  10m in length          6  Check which operating mode is set on the display and  if necessary  see the  C
21. ue the objectives defined in the environmental management system developed by the company in  compliance with applicable standards     No hazardous materials such as CFCs  HCFCs or asbestos are used in this product     When evaluating packaging  the choice of material has been made favouring recyclable materials   For correct disposal  please separate and identify the type of material of which the packaging is made according to the  table below  Dispose of all material in compliance with applicable standards in the country in which the product is used     DESCRIPTION MATERIAL    Packaging corner Stratocell  Protective bag Polythene             DISPOSING OF THE PRODUCT    The UPS and the Battery Box contain electronic PCBs and batteries which are considered TOXIC and HAZARDOUS  waste  When the product reaches the end of its operating life  dispose of it in accordance with applicable local legislation   Disposing of the product correctly contributes to respecting the environment and personal health        The reproduction of any part of this manual  in whole or in part  is forbidden without the prior consent of the manufacturer   In order to make improvements  the manufacturer reserves the right to modify the product described at any moment and without  notice                                                                    9    CONTENTS    PRESENTATION    UPS ViEWS  FRONT VIEW  REAR VIEW    DISPLAY PANEL VIEW    INSTALLATION  INITIAL CONTENT CHECK    INSTALLATION ENVIRONMENT
    