Home
        SCADASense 4203 DR - Control Microsystems
         Contents
1.                 Maximum   Span Maximum Working Maximum  Code   Sensor URL  DP and AP  Static  MWP  Overrange   DP AP Mpa   psi Mpa   Psi Mpa   psi  A 30 inH20  7 5 kPa  100 psia   0 7 100   0 7 100   1 0 150  B 200 inH20  50 kPa  300 psia   2 1 300   2 1 300   3 1 450  CG 840 inH20  210 kPa    300 psia   2 1 300  2 1 300  3 1 450  D 200 inH20  50 kPa  1500 psia   10 1500   10 1500   15 2250  F 300 inH20  75 kPa  1500 psia   10 1500   10 1500   15 2250  E 840 inH20  210 kPa    1500 psia   10 1500   10 1500   15 2250       Measured and Transmitted Outputs    e Absolute Pressure  Configurable for Gauge Pressure  PGP   PAP   Patm     e Differential Pressure    e Process Temperature  from External RTD     SCADASense 4203 DR  Installation and User Manual    October 19  2007    60       Process Temperature Measurement and Limits  Measurement   DIN IEC  2   3   or 4 wire  100 ohm  Platinum  Resistance Temperature Detector  RTD    Span Limits   10 and 538  C  50 and 1000  F    Range Limits     40 and  649  C   40 and  1200 F     Adjustable Damping    The transmitter response time is normally 1 0 s  or the electronically adjustable setting of 0 00   none   0 50  1  2  4  8  16  or 32 seconds  whichever is greater  for a 90  recovery from an 80   input step as defined in ANSI ISA S51 1     Suppressed Zero and Elevated Zero    Suppressed or elevated zero ranges acceptable as long as Span and Range Limits are not exceeded     Minimum Allowable Pressure  With Silicone Fill Fluid  Full vacu
2.      40251  ASCII Read Write ch user defined display text  These registers hold the text that will be    SCADASense 4203 DR  Installation and User Manual  October 19  2007       included i in the display cycle if the bit to display  the 5  user defined data set is turned on in the  Display Control register  Each register holds 2  ASCII characters  The first 7 ASCII characters  will be displayed on line 2 of the display   followed by the second 7 ASCII characters  The  Table 4 Display Module ASCII Characters  table below lists the displayable characters   40252     40253  Float Read Write  6  user defined display value  These registers hold the floating point value that  will be included in the display cycle if the bit to  display the 6  D user defined data set is turned on  in the Display Control register  Only values  between    9999 and 99999 can be displayed   Any value outside of that range will be replaced   5 dashes  on the display   254     40260  ASCII Read Write  6 user defined display text  These registers hold the text that will be  included i in the display cycle if the bit to display  the 6  user defined data set is turned on in the  Display Control register  Each register holds 2  ASCII characters  The first 7 ASCII characters  will be displayed on line 2 of the display   followed by the second 7 ASCII characters  The  Table 4 Display Module ASCII Characters  table below lists the displayable characters     40  40261     40262  Float Read Write  7  user defined 
3.     P3    Figure 20  COM3 RS 232 Wiring    4 1 2 COM1 RS 232 Serial Port Settings    The following table shows the serial and protocol communication parameters supported by COM1   These parameters are fixed and cannot be changed by users     4 1 3 COM2 RS 232 Serial Port Settings       The following table shows the serial and protocol communication parameters supported by COM2     These parameters are set from TelePACE  ISaGRAF Workbench or from an application program  running in the controller  Default values are set when a Cold Boot or Service Boot is performed on  the controller     Baud Rate 300  600  1200  2400  4800  9600  19200  38400  57600  and 115200   mg Default  9600   Duplex Full and Half   e lee       SCADASense 4203 DR  Installation and User Manual  October 19  2007    25    Protocol None  Modbus RTU or Modbus ASCII  DF1 and DNP   Default  Modbus RTU  Addressing Mode Standard or Extended Default  Standard    4 1 4 COM3 RS 232 Serial Port Settings    The following table shows the serial and protocol communication parameters supported by COM3   These parameters are set from TelePACE  ISaGRAF Workbench or from an application program  running in the controller  Default values are set when a Cold Boot or Service Boot is performed on  the controller     Parameter Supported Values    Baud Rate 300  600  1200  2400  4800  9600  19200  38400  57600  and 115200   anne Default  9600   Duplex Full and Half   pe doa OOOO    Odd  None or Even Default  None       Protocol Non
4.    3  Rotate the process covers so that the longer tab is at the bottom    4  Reinstall the process covers and bolts  Torque the cover bolts to 100 Nm  75 Ibft  in several  even increments  Torque values are 66 Nm  50 Ibft  when optional 316 ss bolts are specified    5  Pressure test the sensor and process cover assembly by applying a hydrostatic pressure of 150   of the maximum static and over range pressure  see page 3  to both sides of the process  cover sensor assembly simultaneously through the process connections  Hold pressure for one  minute  There should be no leakage of the test fluid through the gaskets  If leakage occurs   retighten the cover bolts per Step 4 or replace the gaskets and retest    CAUTION    Perform hydrostatic test with a liquid and follow proper  hydrostatic test procedures   SCADASense 4203 DR  Installation and User Manual 55    October 19  2007    8 Troubleshooting  8 1 Analog Output    Problem    Outputs are always OMA Check the power supply     Check the wiring  The analog output on this  transmitter is a sinking type and is not ground    referenced     The full scale output is less   Check that the load resistance and power supply  than 20mA  is within specification    Output is constant and Check that the analog output is not forced   should be changing     8 2 Digital Input  SES   Input is off when a voltage is   Remove the voltage  The digital input monitors  supplied  contacts or transistor collector drain only   Input is on when no signa
5.  2 to 200 inH2 O  0 50 to 50 kPa  3 to 300 psi  0 021 to 2 1 MPa   C 10 to 840 inH20    2 50 to 210 kPa    3 to 300 psi  0 021 to 2 1 MPa   D 2 to 200 inH20  0 50 to 50 kPa  30 to 1500 psi  0 21 to 10 MPa   F 3 to 300 inH20  0 75 to 75 kPa  30 to 1500 psi  0 21 to 10 MPa   E 10 to 840 inH20    2 50 to 210 kPa    30 to 1500 psi  0 21 to 10 MPa   J 2 to 200 inH20  0 50 to 50 kPa  30 to 3000 psi  0 21 to 21 MPa   K 3 to 300 inH20  0 75 to 75 kPa  30 to 3000 psi  0 21 to 21 MPa   L 10 to 840 inH20    2 5 to 210 kPa  30 to 3000 psi  0 21 to 21 MPa        Low Profile Sensor       0 5 to 30 inH20     0 12 to 7 5 kPa     1 to 100 psi    0 007 to 0 7 MPa        2 to 200 inH20    0 50 to 50 kPa     3 to 300 psi    0 021 to 2 1 MPa        10 to 840 inH20     2 5 to 210 kPa    3 to 300 psi    0 021 to 2 1 MPa        2 to 200 inH20    0 50 to 50 kPa    30 to 1500 psi    0 21 to 10 MPa        3 to 300 inH20    0 75 to 75 kPa    30 to 1500 psi       10 to 840 inH20    30 to 1500 psi    0 21 to 10 MPa       2 to 200 inH20    0 50 to 50 kPa    30 to 3000 psi       3 to 300 inH20    0 75 to 75 kPa    30 to 3000 psi    0 21 to 21 MPa       D    z   lt   N  x  s   lt   c          10 to 840 inH20                2 5 to 210 kPa         2 5 to 210 kPa                               30 to 3000 psi                 0 21 to 10 MPa            0 21 to 21 MPa          0 21 to 21 MPa                 Maximum Static Pressure  Working Pressure  MWP   and Overrange Pressure                                       
6.  7001234   ENCLOSURE TYPE 4X  20degC  lt   Ta  lt   70degC IP66 9 30VDC 384mW 300 WC 75kPa       Max  ambient temp  70degC  WARNING  EXPLOSION HAZARD   AE DONGT OPEN WHEN ENERGIZED  CONDUIT ENTRIES ARE 1 2 IN  NPT  KEEP COVER TIGHT WHILE CIRCUITS ARE ALIVE   Kanata  ON K2K 2A9 DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN    CANADA SWITCHED OFF OR THE AREA IS KNOWN TO BE NONHAZARDOUS       Absolute 1500psi 10MPa  MFG DATE 2007 MwP 1500psi 10MPa    For all other specifications please refer to product manual                WARNING    EXPLOSION HAZARD   SUBSTITUTION OF COMPONENTS MAY  IMPAIR SUITABILITY FOR CLASS 1  DIVISION 2     SCADASense 4203 DR  Installation and User Manual 65  October 19  2007    9 16 Dimensions    137    Allow 50 mm  2 in    F   a 54 124  clearance for   124  cover removal   49    both ends  Note 5     e la  Extended cover  used with optional  LCD indicator  L H Indicator  low high  mm pressure side  in  Optional side  venv drain   Note 3   Process  connector   Note 4     Note 2  e 119  47  NOTES         External  earth  I  ground     Optional  r    transmitter  mounting  bracket    Transmitter with    Mounting Options  M1 orM2    External  earth   ground     For surface mounting  replace U Bolt with two  0 375 in diameter bolts  of sufficient length to  pass through bracket  and surface     Vertical DN 50 or    2 in pipe shown   La Rotate U bolt 90      for mounting to  horizontal pipe     1  Conduit connection 1 2 NPT or PG 13 5  both sides  plug un
7.  BOTH HIGH AND LOW  SIDES SIMULTANEOUSLY              CALIBRATING  PRESSURE    SOURCE    A     SHUTOFF VALVES    Note  Altamate connection point for calibrating  equipmentis optional vant screw  not shown  on    high pressure side cover     BLEEDER VALVES   NEEDLE TYPE     Figure 6  Absolute Pressure Calibration Connections    SCADASense 4203 DR  Installation and User Manual 11  October 19  2007    3 2 Optional Display Module    The optional display module is used to provide local display of meter run data  The display may be  configured using the SCADASense 4000 Series Configurator  RealFLO  Flow Computer commands   or Modbus Register Mapping  The data to display and the interval between the displayed items is  user defined     The SCADASense 4000 Series Configurator is installed from the Hardware Documentation CD   When installed on your PC  it is found in the Windows    Programs    Control Microsystems    4000  Series program group  Refer to the online help document of this program for additional assistance  in configuring your transmitter display     The SCADASense series of transmitter can also be configured using the RealFLO application   Refer to the MVT Configuration commands section of the RealFLO User and Reference manual for  complete information on using RealFLO to configure the Display Module     The Display Control Configuration section of the TeleBUS Protocol Section of the RealFLO User  and Reference manual provides the information for using the Display Module
8.  Limit   LRL   SP signal below Lower Range Limit   LRL      10   N A    40408 Integer  Read Diagnostic Bits  This register holds a bit mapped value  The  individual bits correspond to these conditions   Bit 15   N A    SCADASense 4203 DR  Installation and User Manual  October 19  2007       Bit 14   RTD signal above Upper Range Limit   URL   10    Bit 13   RTD signal above Upper Range Limit   URL    Bit 12   RTD signal above Upper Operating  Limit  URV    Bit 11   RTD signal below Lower Operating  Limit  LRV    Bit 10   RTD signal below Lower Range Limit   LRL    Bit 09   RTD signal below Lower Range Limit   LRL      10    Bit 08   N A   Bit 07   Primary Variable is bad    Bit 06   Secondary Variable is bad    Bit 05   Tertiary Variable is bad    Bit 04   Reserved   Bit 03   Reserved   Bit 02   Reserved   Bit 01   Reserved   Bit 00   Off line Flag  see register 40206     40409 Integer  Read Diagnostic Bits  This register holds a bit mapped value  The  individual bits correspond to these conditions   Bit 15   Sensor module is not updating  Bit 14   reserved  Bit 13   Sensor microprocessor is not  responding  Bit 12   reserved  Bit 11   reserved  Bit 10   reserved  Bit 09   reserved  Bit 08   reserved  Bit 07   reserved  Bit 06   reserved  Bit 05   reserved  Bit 04   reserved  Bit 03   reserved  Bit 02   reserved  Bit 01   Hardware write protect status  Bit 00   Software write protect status    40410 Integer  Read Diagnostic Bits   NTE This register is reserved for future diagn
9.  R Connections  Connections    com3com   pg pa    IRET                   Cold Boot  Switch    Figure 9  Terminal Board Layout    3 4 Power Supply  The SCADASense 4203 DR is powered from a 9 to 30VDC input power source   e Input power is applied to the  PWR and  PWR terminals on connector P1     Refer to section 9  Specifications of this manual for the minimum and maximum operating voltages  and input power requirements     e When the input voltage is below the minimum recommended voltage the GFC will turn off    e Exceeding the maximum input voltage or applying a reverse voltage may damage the GFC   External Fusing is recommended on early production of these models    3 4 1 Fusing    The SCADASense 4203 DR requires fusing on the power supply inputs  This fusing is included on  the terminal board  The fuse is located between connectors P1 and P5  These connectors must be  removed to have access to the fuse  The replacement fuse is a Littelfuse R452 750 for the  transmitter  See Figure 11  Input Power Wiring with Internal Fuse     Littelfuse R452 750 is available from Control Microsystems as part number 200094           Note  External Fusing is recommended on early production DR Series GFC   s  Use a 0 75A Slow  Blow Fuse for the SCADASense 4203 DR as shown in Figure 10  Input Power Wiring  with External Fuse        SCADASense 4203 DR  Installation and User Manual 15  October 19  2007       0 5A 0 75A Slow P1    Power       Note  See text for fuse  recommendations and power sup
10.  Service mode stops the programs to allow reprogramming and  controller initialization  Start up in the COLD BOOT mode initializes the controller and erases all  programs     5 1 1 Run Mode    RUN meode is the normal operating mode of the controller  Ensure the Cold Boot push button is not  pushed when power is applied to start Run mode operation  When power is applied to the controller  board     e The user defined serial communication parameters  for all COM ports are used   e Ifa TelePACE Ladder Logic or ISaGRAF application program is loaded in RAM  it is executed     e Ifa TelePACE or ISaGRAF C application program is loaded in RAM and the program  checksum is correct  it is executed     e If there is no application program in RAM and there is an application program in flash ROM  then the flash ROM program will be executed     e The controller lock settings and password are used     5 1 2 Service Mode    Service mode is used during application programming and maintenance work  When the controller  is starts in Service mode     e The default serial communication parameters are used  see section 4 Serial Communication for  a description of the default parameters      e The Sensor driver is installed on Com 1  Com 1 is set to Sensor protocol  4800 Baud  no parity   8 data bits and one stop bit     e The TelePACE Ladder Logic or ISaGRAF program is stopped   e The C program is stopped   e All programs are retained in non volatile memory     e The controller lock settings and pa
11.  addition to these two serial ports these GFC   s have an internal serial port defined as COM1  This  serial port is not assessable by users and is used for communication between the controller and the  sensor     User serial ports on the transmitter are designated COM2 and COM3  Connections to COM2 and  COM3 are made using removable 3 position terminal blocks     4 1 RS 232 Serial Communications Ports    Both COM2 and COM3 are capable of RS 232 operation  RS 232 operation is selected by installing  the appropriate jumper link on the terminal board labeled COM2 and COM3  RS 232 operation uses  RxD  TxD and COM signals  Refer to Figure 19  COM2 RS 232 Wiring and Figure 20  COM3  RS 232 Wiring for connector wiring descriptions     NOTES     e The low power transmitters used in COM2 and COM3 generate 0 to 5V levels  This is less than  the RS 232 specification but still compatible with all RS 232 receivers  Cables should be limited  to a maximum of 10 ft  3m      e Shielded cable should be used to protect the signals from noise and to comply with FCC and CE  regulatory requirements  The shield is connected to Ground at one end only     4 1 1 RS 232 Wiring Examples    RS 232  9 Pin D    connector  DTE    Note  DIP Switch set to the RIGHT  on COM2 for RS 232 operation     Figure 19  COM2 RS 232 Wiring       SCADASense 4203 DR  Installation and User Manual 24  October 19  2007    Note  DIP Switch set to the RIGHT  on COMS for RS 232 operation     RS 232    9 Pin D  connector  DTE   
12.  and Nuts    ASTM A193  Grade B7 high strength alloy steel for bolts  and ASTM A194 Grade 2H high strength  alloy steel for nuts are standard  Options include NACE Class B7M bolting  17 4 ss bolting  and 316  ss bolting     Sensor Material  Process Wetted   316 L ss or Hastelloy C  as specified    Sensor Fill Fluids    Silicone Oil    Environmental Protection    Transmitter is dust tight and weather proof per IEC IP66 and provides the environmental and  corrosion resistant protection of NEMA Type 4X     Electronics Housing and Housing Covers    Housing has two compartments to separate the electronics from the field connections  The housing  and covers are made from low copper  die cast aluminum alloy with an epoxy finish  or from 316 ss   Buna N O ring seals are used to seal the threaded housing covers  housing neck  and terminal block     Electrical Connections    Field wiring enters through 1 2    NPT threaded entrances on either side of the electronics housing   Wires terminate in removable terminal blocks for ease of installation and calibration     Mounting Position    The transmitter may be mounted in any orientation     Approximate Mass   3 5 kg  7 8 Ib      without Process Connectors   4 2 kg  9 2 1b      with Process Connectors   Add 1 1 kg  2 4 Ib      with 316 ss Housing   Add 0 2 kg  0 4 Ib      with LCD Indicator Option    SCADASense 4203 DR  Installation and User Manual 64  October 19  2007    9 15 Approvals and Certifications    c CSA us Explosion proof  Class 
13.  be displayed   Any value outside of that range will be replaced    40288     40289  Float   5 dashes  on the display    40290     40296  ASCII Read Write user defined display text  These registers hold the text that will be  included i in the display cycle if the bit to display  the 10  user defined data set is turned on in the  Display Control register  Each register holds 2  ASCII characters  The first 7 ASCII characters  will be displayed on line 2 of the display   followed by the second 7 ASCII characters  The  Table 4 Display Module ASCII Characters  table below lists the displayable characters     40297     40298  Float Read Write  11  user defined display value  These registers hold the floating point value that  will be included in the display cycle if the bit to  display the 11  user defined data set is turned  on in the Display Control register  Only values  between    9999 and 99999 can be displayed      SCADASense 4203 DR  Installation and User Manual  gt  A8 4203 DR  Installation and User Manual  October 19  2007       43    ET value outside of that range will be replaced  ET dashes  on the display     be 40305 La ee 11  user defined display text  These registers hold the text that will be  included i in the display cycle if the bit to display  the 11  user defined data set is turned on in the  Display Control register  Each register holds 2  ASCII characters  The first 7 ASCII characters  will be displayed on line 2 of the display   followed by the second 7 ASC
14.  each register   Valid values are any ASCII character   40044   40059  ASCII Read Write  Message  32 characters   These registers hold the transmitter message   The message can be up to 32 characters  Two  characters are stored in each register  Valid    SCADASense 4203 DR  Installation and User Manual  October 19  2007          values are any ASCII character     ee se Read Write  Differential Pressure Units  This register holds a value representing the  engineering units for the differential pressure   Valid values are shown below   2   Pascals  Pa   3   kiloPascal  kPa   6   inches of water at 68 F   40061 Integer  Read Write  Static Pressure Units  This register holds a value representing the  engineering units for the static pressure  Valid  values are shown below   3   kiloPascal  kPa   4   megaPascal  MPa   5   pounds per square inch  psi    40062 Integer  Read Write Process Temperature Units  This register holds a value representing the  engineering units for the process temperature   Valid values are shown below   20   degrees Celsius  C   21   degrees Fahrenheit  F     40063     40125   40125    Reserved o OS    ee er    kee Display a armer Interval  This register controls the display scan interval   It will hold the value in seconds that each  reading selected in the Display Control will  remain on the display  Valid values will be  integers between 2000 and 60000 ms     moter     Dese    SSCSC d    EE 28 Bit field  Read Write  Display Control   This register contro
15.  in the display cycle if the bit to  display the 2 9 user defined data set is turned on  in the Display Control register  Only values  between    9999 and 99999 can be displayed   Any value outside of that range will be replaced    5 dashes  on the display     40218 40224  ASCII Read Write  2    user defined display text  These registers hold the text that will be  included in the display cycle if the bit to display  the 2    user defined data set is turned on in the  Display Control register  Each register holds 2    SCADASense 4203 DR  Installation and User Manual  October 19  2007       ASCII characters  The first 7 ASCII characters  will be displayed on line 2 of the display   followed by the second 7 ASCII characters  The  Table 4 Display Module ASCII Characters  table below lists the displayable characters    40225     40226  Float Read Write  3    user defined display value  These registers hold the floating point value that  will be included i in the display cycle if the bit to  display the 3   user defined data set is turned on  in the Display Control register  Only values  between    9999 and 99999 can be displayed   Any value outside of that range will be replaced    5 dashes  on the display    40227     40233  ASCII Read Write  3    user defined display text  These registers hold the text that will be  included in the display cycle if the bit to display  the 3 user defined data set is turned on in the  Display Control register  Each register holds 2  ASCII charact
16.  made if  the transmitter mode is not correct     40401   40402  Float Read Differential Pressure  DP   These registers hold the differential pressure as  a floating point number in the specified floating   point format    40403   40404  Float Read Static Pressure  SP   These registers hold the static pressure as a  floating point number in the specified floating   point format  The diagnostic bits indicate the    SCADASense 4203 DR  Installation and User Manual  October 19  2007          validity of this register     46520405 40406 aa Read Process Temperature  PT   These registers hold the process temperature  as a floating point number in the specified  floating point format     40407 Integer  Read Diagnostic Bits  This register holds a bit mapped value  The  individual bits correspond to these conditions  15 Calibration flag  see register 40206   14 The process values may not be valid       If this bit is the only bit set then contact  Technical Support   Primary Variables are outside  specification  DP signal above Upper Range Limit   URL   10   DP signal above Upper Range Limit   URL   DP signal above Upper Operating Limit   URV   DP signal below Lower Operating Limit   LRV   DP signal below Lower Range Limit   LRL   DP signal below Lower Range Limit   LRL      10   SP signal above Upper Range Limit   URL   10   SP signal above Upper Range Limit   URL   SP signal above Upper Operating Limit   URV   SP signal below Lower Operating Limit   LRV   SP signal below Lower Range
17.  order byte    The string is terminated with a NULL    0  character if it  is less than 8 characters  Set the first register to 0 to  indicate a NULL  empty  string     6 4 Modbus Registers  Table 2  Modbus Registers    40001 Integer  Read Manufacturer s Code  mod This register holds a constant value of 4000   This indicates the transmitter is manufactured  by Control Microsystems   40002 Integer  Read Type Code  This indicates the model of the transmitter   Type Code 42990   SCADASense 4203 DR  40003 Integer  Read Software Revision Level  PET register holds the revision number of the  controller firmware     40004 Integer  Read Sensor Software Version Level  This register holds the version number of the  sensor firmware  This is read from the sensor  It  uses the format  MAJOR VERSION   100    MINOR VERSION  For example  1 19 would be  viewed as 119 in register 40004     40005 40006     Dees    40007   40008 Integer  Read Transmitter Serial Number  Register 40007 holds the manufacture date as  bits in the format YYYYYYYMMMMDDDDD   where these bits correspond to  Year 1986 Month Day   Register 40008 holds the core number    40009 Integer  Read Sensor Hardware Version   lg gl register holds the version number of the  sensor hardware  This is read from the sensor    40010 Integer  Read Modbus Revision   mm PETE register holds the Modbus mapping and  protocol revision  It is fixed at 1     40011 Integer  Read Write  Sensor Type  This register selects if the Static Pressure  meas
18.  the SP lower operating  limit as a floating point number in the specified  floating point format   The transmitter must be in the offline mode to  change this register  No change will be made if  the transmitter mode is not correct   The SP lower operating limit must be greater  than or equal to 0 if absolute pressure is  selected  or    1  atmospheric reference if gage  pressure is selected  The difference between  the secondary variable UOL and secondary  variable LOL must also be larger than 0 5  of    40427   40428  Float  the secondary variable URL     40429   40430  Float Read PT Upper Range Limit  These registers hold the PT upper range value  as a floating point number in the specified  floating point format    40431   40432  Float Read PT Lower Range Limit  These registers hold the PT upper range value  as a floating point number in the specified  floating point format     40433   40434  Float Read Write  PT Upper Operating Limit  These registers hold the PT upper operating  limit as a floating point number in the specified  floating point format   The transmitter must be in the offline mode to  change this register  No change will be made if  the transmitter mode is not correct   The PT upper operating limit may be set higher  than the tertiary variable upper range limit  The  tertiary variable upper operating limit my be set     SCADASense 4203 DR  Installation and User Mnal  A8 4203 DR  Installation and User Manual  October 19  2007    Read Write  SP Upper Operat
19.  with Flow Computer  commands     The Modbus Register Mapping section of this manual contains information on configuring the  Display Module using Modbus registers           Note  Configuring a SCADASense transmitter using the local display is possible with older  transmitters only  See the application note    Configuring an older SCADASense transmitter  using the Local Dsplay pdf     located in the same directory as this document  for a detailed  procedure  Newer SCADASense transmitters no longer have this configuration menu  available off the local display  and have to be configured using other means as noted above   If you cannot access the menu  it is not available on your transmitter version        3 2 1 Adding the Optional Display  To add the optional display  refer to Figure 7 and proceed as follows     1  Turn off the transmitter power source     2  Remove the electronics compartment cover by rotating it counterclockwise  Screw in the cover  lock if applicable     Ge    Plug the display into the receptacle at the top of the electronics assembly     4  Ensure that the O ring is seated in its groove in the display housing  Then insert the display  into the electronics compartment by grasping the two tabs on the display and rotating it  approximately 10   in a clockwise direction    5  Install the new cover  with a window  onto the housing by rotating it clockwise until the O ring  contacts the housing  then continue to hand tighten it as much as possible  at least 1 4 t
20. 4203 DR transmitter provides Modbus master slave and EFM Modbus as its  native protocols  DNP 3 0 protocol is optionally available  Custom protocols can be implemented  using C programming     These transmitters can optionally be configured using the SCADASense 4000 Series Configurator  UI  which is shipped on an accompanying Configuration CD  The SCADASense 4000 Series  Configurator supports the configuration  monitoring  and calibration of all SCADASense 4000  Series transmitters          Also referred to as Gas Flow Computer  GFC  or simply transmitter    SCADASense 4203 DR  Installation and User Manual 6  October 19  2007    2 Important Safety Information    Power  input and output  I O  wiring must be in accordance with Class I  Division 2 wiring methods  Article 501 4  b  of the National Electrical Code  NFPA 70 for installations in the U S   or as  specified in Section 18 1J2 of the Canadian Electrical Code for installations within Canada and in  accordance with the authority having jurisdiction     WARNING    EXPLOSION HAZARD   SUBSTITUTION OF COMPONENTS MAY  IMPAIR SUITABILITY FOR CLASS 1  DIVISION 2        WARNING    EXPLOSION HAZARD     WHEN IN HAZARDOUS LOCATIONS  TURN  OFF POWER BEFORE REPLACING OR WIRING MODULES     WARNING     EXPLOSION HAZARD   DO NOT DISCONNECT EQUIPMENT  UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS  KNOWN TO BE NONHAZARDOUS     SCADASense 4203 DR  Installation and User Manual 7  October 19  2007    3 Installation    3 1 Mounting    The 
21. ALS     EXTERNAL EARTH  GROUND     Figure 8  Accessing Field Terminals    The GFC uses screw termination style connectors for termination of field wiring  These connectors  accommodate solid or stranded wires from 16 to 28 AWG  The connectors are removable for field  service and replacement purposes  Leave enough slack in the field wiring for the connector to be  removed           Note  The use of transient surge protection is recommended in installations prone to high levels of  electrical transients and surges        CAUTION    Remove power before servicing unit     CAUTION     The transmitter threaded end cap with the terminal board  wiring diagram must be installed on the housing end that  has the terminal board  This is a Class Div  2 Hazardous  Locations requirement     There are five connectors for field wiring  Refer to Figure 9  Terminal Board Layout for connector  locations  Connector pinouts and wiring examples are described in each of the respective sections of  this manual     SCADASense 4203 DR  Installation and User Manual 14  October 19  2007          Status    E  LED                            Input Power DC Power     Q Q AOUT  Connections  DC Power      Qp4   F QI ETR 1 Analog Output  Digital     U Input Output and Counter  COM2 COM 2 TX   A  Q S Q COM Input Connections  RS 232 or 485  Connections COM 2 RX B    Q p        CTRO DIN DOUT  L COM 2 com e  COM 2  232 485  mm Sr OQ    COM 3  232 485      Sie     coms TX a   O GIR   em  RS 232 or 485 COM 3 RX B Q Q
22. I  Div  1 Groups B  C and D  Hazardous Locations     c CSA us Class I  Div  2 Groups A  B  C and D Hazardous  Locations                 Temperature code T5 at maximum ambient  70  C           Provides non incendive field circuits for RTD     LCIE 07 ATEX6058 Ex d IIC T6  IECEx CSA 05 0011 Exd IIC T6    Digital FCC Part 15  Subpart B  Class A Verification    Emissions EN 61000 6 4  2001  Electromagnetic Compatibility  Generic Emission Standard for Industrial Environments    Immunity EN 61000 6 2  2001  Electromagnetic Compatibility  Generic Standards Immunity For Industrial Environments          9 15 1 ATEX IECEx label                CONTROL    MODEL 4202 DR22F101XA1 L SCADASense  MICROSYSTEMS 0344 126   TELEMETERING EQUIPMENT FOR USE IN HAZARDOUS LOCATIONS LCIE 07 ATEX6058 Exa IC Te  SERIAL 1001234 SpanCode   F   ENCLOSURE TYPE 4X Fres SE 9 30VDC 384mW 300 WC 75kPa        Max  ambient temp  70degC  CONDUIT ENTRIES ARE 1 2 IN  NPT    OOOO ee   4500psiMoMPa        2007  mwe   1500psi 10MPa    WARNING  EXPLOSION HAZARD   DO NOT OPEN WHEN ENERGIZED                         48 Steacie Drive KEEP COVER TIGHT WHILE CIRCUITS ARE ALIVE   Kanata  ON K2K 2A9 DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN For all other specifications please refer to product manual   CANADA SWITCHED OFF OR THE AREA IS KNOWN TO BE NONHAZARDOUS    CONTROL 4202 DS22F101XA1 L SCADASense   MICROSYSTEMS SE e  SERIAL Span Cod   TELEMETERING EQUIPMENT FOR USE IN HAZARDOUS LOCATIONS ek ATEXG05B Ex d IG T6 eens  
23. II characters  The  Display Module ASCII Characters table below  lists the displayable characters    40306     40307  Float Read Write  12 user defined display value  These registers hold the floating point value that  will be included in the display cycle if the bit to  display the 12  user defined data set is turned  on in the Display Control register  Only values  between    9999 and 99999 can be displayed   Any value outside of that range will be replaced    5 dashes  on the display     40308     40314  ASCII Read Write  12  user defined display text  These registers hold the text that will be  included in the display cycle if the bit to display  the 12  user defined data set is turned on in the  Display Control register  Each register holds 2  ASCII characters  The first 7 ASCII characters  will be displayed on line 2 of the display   followed by the second 7 ASCII characters  The  Table 4 Display Module ASCII Characters  table below lists the displayable characters     wemmer    Bees CS    Tae 40400  Float Read Write  Atmospheric Pressure  These registers hold the user specified  atmospheric pressure as a floating point  number in the specified floating point format   This value is used when the sensor type is set  to gage using register 40011  This value is  ignored if the sensor type is set to absolute   The value in this register must be in the same  units as the static pressure   The transmitter must be in the offline mode to  change this register  No change will be
24. OUT    Note  See specifications for load  resistance range and power supply  limits    Figure 14  Analog Output Wiring  SCADASense 4203 DR  Installation and User Manual 19    October 19  2007       3 7 1 Current Outputs    The analog output is a sinking output that is not ground referenced  The load connects between  connector P5  pin 4 and a positive power supply as shown in Figure 14  Analog Output Wiring   Refer the Specifications section for power supply limits and load resistance ranges     3 7 2 Voltage Outputs    To obtain voltage outputs  connect a load resistor in the current output  Connect the voltage device  across the load resistor  The table below list resistance values and output range settings for two  common voltage ranges  The resistance value listed is the parallel resistance of the device and the  load resistor     Voltage Range Output Range    0 to 5V 250Q 0 20mA    3 7 3 Analog Outputs Data Format       The analog output has a 12 bit  unipolar  digital to analog converter  There are 4096 counts in the  output signal range  The 0 20mA output range resolution is 4 88 A count  The table below shows  the output current for several D A values  Given that the analog output is referenced to a power  source  these currents have to be provided through a load     fo  Joma      B Dm    3 7 4 Digital Output Control with External Relay       The analog output can be used to control an external relay  Electromechanical or solid state relays  that meet the output requi
25. SCADASense 4203 DR    Installation and User Manual    CONTROL  MICROSYSTEMS    SCADA products    for the distance    48 Steacie Drive Telephone  613 591 1943  Kanata  Ontario Facsimile  613 591 1022  K2K 2A9 Technical Support  888 226 6876  Canada 888 2CONTROL    SCADASense 4203 DR Series  Installation and User Manual      2006 Control Microsystems Inc   All rights reserved   Printed in Canada     Trademarks    TeleSAFE  TelePACE  SmartWIRE  SCADAPack  TeleSAFE Micro16 and  TeleBUS are registered trademarks of Control Microsystems Inc     All other product names are copyright and registered trademarks or trade names  of their respective owners     Material used in the User and Reference manual section titled SCADAServer  OLE Automation Reference is distributed under license from the OPC  Foundation     SCADASense 4203 DR  Installation and User Manual 1  October 19  2007    Table of Contents    1 e UE EE 6  2 IMPORTANT SAFETY INFORMATION    rrrnnnvvvrnnnnnnvennnnnnnnvnnnnnnnnnvnnnnnnnnnennnnnn 7  3 INSTALEA HON Gara 8  3 1 Monas hee hn Sa ae oe on chon ahh SIAN 8  3 1 1 Process Mounted Transmitter    8  3 1 2 Pipe or Surface Mounted Transmitter              sseeeeesennennneeeeeeerrrrnnnreeeee 9  3 1 3 Positioning the Transmitter HOUSING EE 9  3 1 4 Manifold Types and Installation           seeeeennnnneneeeeeeeeenrnnnneesseerrnrnnnreneeee 9  3 1 5 Connections For Sensor Calibration           rrrrnnnnnnnnnnnnnnrrrrnnnnnnnnrrrnnnnnnn 11  3 2 Optional  Display Modul Cc  usgusmnomm
26. Sensor mode is selected by performing a Sensor Boot using the following procedure     1  Remove power from the controller    2  Push and hold the Cold Boot push button down   3  Apply power to the controller   4    A Sensor boot occurs when the Cold Boot push button is pushed and held for between 15 and 30  seconds  The STAT LED blinks rapidly after 15 seconds to indicate the Sensor boot mode is  selected     5  The STAT LED will blink short  short  long while the controller is in the Sensor mode     6  The Sensor Boot remains in effect until the controller is reset           Note  If the Cold Boot push button is released before the STAT LED starts to blink rapidly the  controller will start in Service mode        5 1 4 Cold Boot Mode    Cold Boot mode is used after installing new controller firmware or when it is desirable to initialize  the DR Series GFC to its default state  When the controller starts in Cold Boot mode     e The default serial communication parameters are used  see section 4  Serial Communication  for a description of the default parameters      e The Sensor driver is installed on com   Com1 serial port parameters are set to 4800 baud  no  parity  8 data bits  and one stop bit     e The TelePACE Ladder Logic or ISaGRAF programs are erased   e The C program is erased     e The registers in the I O database or I O Connection are initialized to their default values     SCADASense 4203 DR  Installation and User Manual 31  October 19  2007          e The Regist
27. ange  DINO  ON and Communication on both serial ports Full Power  Mode           9 6 Analog Input    Power Input 8 bits resolution   Voltage Monitor   Accuracy  1 0V   9 32 768V measurement range  0 32 768V scaling    Isolation Common ground return connected to negative side of Vin  power input     9 7 Analog Output    Output Signal 0 20mA  Range  Load Resistance 550 to 14000 with 30Vdc supply  Range 250 to 11000 with 24Vdc supply  0 to 8500 with 19Vdc supply  0 to 5000 with 12Vdc supply  0 to 3500 with 9Vdc supply    Note  Analog output sinks current  Maximum power  dissipation is 380mW  Example  20mA at 19V        Output Type Single ended regulation on negative side with positive side of  load connected to a positive voltage     Isolation Common ground return connected to negative side of Vin  power input     Resolution 12 bits  Accuracy Specified from 0 5 20mA    0 15  of full scale at 25  C  77  F     0 25  of full scale over temperature range  Noise and 0 04  maximum       SCADASense 4203 DR  Installation and User Manual 58  October 19  2007    Transient Transient  2 5kV surge withstand capability as per ANSI IEEE    Protection C37 90 1 1989  Response Time Less than 10us for 10  to 90  signal change                9 8 Turbine Meter Counter Input  Counter 1  Single turbine meter input   Designed for use with low voltage  turbine meter outputs   Turbine Meter Minimum input 30mVp p at 5 50Hz   Sensitivity Minimum input 150mVp p at 150Hz   Minimum input 650mVp p at 5kHz   Mi
28. ault  1 Bit   Receive Flow Control    Transmit Flow Contra  T io 65534 Default    Protocol None  Modbus RTU or Modbus ASCII  DF1 and DNP   Default  Modbus RTU    Addressing Mode Standard or Extended Default  Standard    4 2 5 COM3 RS 485 Serial Port Settings    The following table shows the serial and protocol communication parameters supported by COM3   These parameters are set from TelePACE  ISaGRAF Workbench or from an application program  running in the controller  Default values are set when a Cold Boot or Service Boot is performed on  the controller     Baud Rate 300  600  1200  2400  4800  9600  19200  38400  57600  and 115200       Default  9600  Full and Half    Default  Half    Odd  None or Even Default  None       SCADASense 4203 DR  Installation and User Manual 28  October 19  2007    Data Bits 7 or 8 Bits Default  8 Bits    Stop Bits 1 or 2 Bits Default  1 Bit    Receive Flow Control ModbusRTU Default  ModbusRTU    Transmit Flow Control Ignore CTS or None Default  None  1 10 65534 Default 1    Protocol None  Modbus RTU or Modbus ASCII  DF1 and DNP   Default  Modbus RTU    Addressing Mode Standard or Extended Default  Standard       SCADASense 4203 DR  Installation and User Manual  October 19  2007    29    5 Operation    5 1 Operating Modes    The SCADASense 4203 DR may start up in Run  Service  Sensor or Cold Boot mode  Start up in the  RUN mode automatically executes TelePACE or ISaGRAF applications and the C applications the  controller memory  Start up in the
29. be used and the  shield should be connected at one end only  There is an enclosure ground connection that can be  used for this purpose     3 8 2 Counter   Digital Input   CTRO DIN DOUT    The counter digital input is used to count or monitor contact closures and open collector drain  devices  The input circuitry provides 5mA of wetting current for the contact     Refer to Figure 17  Digital and Counter Input Wiring for examples of wiring to this input  This  input shares a Common with CTR1     The CTRO DIN DOUT counter digital input is a high speed input  Ensure that the applied input is  free of contact bounce     3 8 3 Digital Output   CTRO DIN DOUT    The CTRO DIN DOUT is an open drain  sinking  digital output  The output is typically used to  control 12VDC to 24VDC loads with currents up to 500mA  The positive side of the load connects  to a  ve  30VDC maximum  power supply  The negative side of the load connects to connector P5   1  Refer to Figure 18  Digital Output Wiring Example for wiring details     SCADASense 4203 DR  Installation and User Manual 22  October 19  2007         9 30VDC  Power    Supply       Figure 18  Digital Output Wiring Example    SCADASense 4203 DR  Installation and User Manual    October 19  2007    23    4 Serial Communication    The SCADASense 4203 DR is equipped with two serial communication ports for user interface to  the controller  Both serial communication ports support RS 232 serial communication and RS 485  serial communication     In
30. but instead are  referenced to their respective incoming electrical grounds  The grounds of the RS 485 devices on  the network must be within several volts of each other     SCADASense 4203 DR  Installation and User Manual 26  October 19  2007          Note  Shielded cable should be used to protect the signals from noise and to comply with FCC  and CE regulatory requirement  The shield is connected to Ground at one end only        4 2 1 RS 485 Wiring Examples    RS 485  2 Wire  Master    Note  COM2 DIP switch to the LEFT  for RS 485 operation  See text for  grounding and shielding  requirements        Figure 21  COM2 RS 485 Wiring    Note  COM3 DIP switch to the LEFT  for RS 485 operation  See text for  grounding and shielding  requirements     RS 485  2 Wire  Master       Figure 22  COM3 RS 485 Wiring    4 2 2 RS 485 Bias Resistors    The RS 485 receiver inputs on the SCADASense 4203 DR are biased to ensure that that received  data is driven to a valid state  space  when there are no active drivers on the network  The value of  these bias resistors is 5100 ohms from Ground to the B    input and 5100 ohms from  5V to the A   input     4 2 3 RS 485 Termination Resistors    Termination resistors are required in long networks operating at the highest baud rates  Shorter  networks in high noise environments may also benefit from terminations  Networks as long 1000 ft   operating at 9600 baud will function without termination resistors  Terminations should be  considered if the ba
31. ceeeaeeeereas 27  4 2 4 COM2 RS 485 Serial Port Settings AAR 28  4 2 5 COM3 RS 485 Serial Port Settings          rrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrrer 28  5 OPERATION seerne arenaen 30  5 1 Operating ME EE 30  5 1 1 Run Mode 30  5 1 2 Service Mode  30  5 1 3 Sensor Mode  31  5 1 4 Gold Boo Mode aS EE 31  5 2 LED Status Indicator  32  5 2 1 LED Power Control 32  6 MODBUS REGISTER MAPPING      mennnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnen 33  6 1 Write Protect Jumper    33  6 2 Software Write brotect 33  6 3 Data FOrmatS        0  ccccccceeccecceccceccecceeeceeceecauececcaeceeecuecaeeceecuecaeeseecueeneeeerens 33  6 4 eelere TEE 34  6 4 1 Default Parameters          rrrnrnnrnnnnnnrvnnnnnnvnnnnnnvnnnnnnnnnnnnennnnnennnnnnnnneennenne 51  6 4 2 Display Module ASCII Characters          nsssnneneeeeeeenenrrnrnnesseernrnnnrneeee 52  7 MAIN PENANG Eeer eebe ee 54  7 1 thum B   EN ve Aes  54  7 2 Rotating Process Covers for Venting                rrrrrrrrrrvrrrrrvrrrrrrrrrrrnnrrnnsnnnnnnnn 54  8 TROUBLESHOOTING     enrnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnennnnnnenn 56  8 1 Analog OUP UT  a aan ee EEE A RRE E RE a 56  8 2 Doms 56  8 3 Digital e TE 56  8 4 Counter IMPUS puusarasenvaenemeneneneneneneaieaemieneavenimjinnni 56  SCADASense 4203 DR  Installation and User Manual 3    October 19  2007    9 SPECIFICATIONS um cata saaudeesccaudeceisauuataccawesataeuaceeteusin 57    9 1 Es ME JE EE EEE EEE OE EE 57  92 Controler EE NE EE EE EEK EE EE c
32. contents for 2 years  RAM with no power  Clock calendar  1 minute month at 25  C   1  3 minutes month 0 to 50  C       9 3 Communications    Communication 3 position removable terminal block    Port COM2 Switch selectable RS 232 or RS485  andCOM3    TxD and RxD implemented    RS 232 compatible serial port  CMOS    Functions when COM2 3 switch is in RS232 position   2 wire half duplex    51000 bias resistors   Functions when COM2 3 switch is in RS485 position     COM2 Baud 300  600  1200  2400  4800  9600  19200  38400  57600  Rate and 115200    COM3 Baud 300  600  1200  2400  4800  9600  19200  38400  57600  Rate and 115200    Parity none  even  or odd  Word Length 7 or 8 bits  Stop Bits 1 or 2 bits    Transient COM2  COM3  2 5kV surge withstand capability as per  Protection ANSI IEEE C37 90 1 1989    Isolation Common ground return connected to negative side of Vin    SCADASense 4203 DR  Installation and User Manual 57  October 19  2007       Cable Length RS 232    maximum 10 ft  3 m   RS 485    maximum 4000 ft  1200 m     Protocol TeleBUS  compatible with Modbus RTU and Modbus ASCII     Protocol Modes Slave  master  master slave  store and forward    9 4 Visual Indicators       Status Internal  Status LED  shows functional status     9 5 Power Supply    DC power Input 9V minimum  30V maximum  Typically 165mW  at 12V  during normal operation   Reduced Power Mode   Typically 330mW  at 12V  during normal operation  Full  Power Mode   Maximum 400mW  at 30V  at full temperature r
33. display value  These registers hold the floating point value that  will be included in the display cycle if the bit to  display the 7  D user defined data set is turned on  in the Display Control register  Only values  between    9999 and 99999 can be displayed   Any value outside of that range will be replaced   5 dashes  on the display   40263     40269  ASCII Read Write  7 user defined display text  These registers hold the text that will be  included in the display cycle if the bit to display  the 7  user defined data set is turned on in the  Display Control register  Each register holds 2  ASCII characters  The first 7 ASCII characters  will be displayed on line 2 of the display   followed by the second 7 ASCII characters  The  Table 4 Display Module ASCII Characters  table below lists the displayable characters   40270     40271  Float Read Write  8  user defined display value  These registers hold the floating point value that  will be included i in the display cycle if the bit to  display the 8  user defined data set is turned on  in the Display Control register  Only values  between    9999 and 99999 can be displayed   Any value outside of that range will be replaced   5 dashes  on the display      SCADASense 4203 DR  Installation and User Manual  gt  42 4203 DR  Installation and User Manual  October 19  2007       40272     40278  ASCII Read Write  8  user defined display text  These registers hold the text that will be  included in the display cycle if the bit to d
34. e  Modbus RTU or Modbus ASCII  DF1 and DNP   Default  Modbus RTU    Addressing Mode Standard or Extended Default  Standard    4 2 RS 485 Serial Communications Ports    Both COM2 and COM3 are capable of 2 wire RS 485 operation  RS 485 operation is selected by  removing the appropriate jumper link on the terminal board labeled COM2 and COM3  RS 485  operation uses A  and B  signals  Refer to Figure 21  COM2 RS 485 Wiring and Figure 22   COM3 RS 485 Wiring for connector wiring descriptions     Data Bits 7 or 8 Bits Default  8 Bits       RS 485 uses balanced differential signals  Proper RS 485 operation requires that all devices  communicating on the signal pair be referenced to the same point  In the transmitter  this reference  point is established by the devices connected to the Power Input and I O  The incoming power       PWR on P1 1  will generally establish the reference point     The RS 485 serial communication ports transmit and receive differential voltages to other RS 485  devices on a network  The RS 485 specification allows a maximum of 32 devices connected on a  single RS 485 network  The specification for RS 485 recommends that the cable length should not  exceed a maximum of 4000 feet or 1200 meters  Termination resistors are required when using long  cable lengths and high baud rates  Refer to section 4 2 3 RS 485 Termination Resistors for  information on termination resistors     The signal grounds of the RS 485 devices in the network are not connected together 
35. e care should be used when disassembling and reassembling the device  Any cables that are  removed in the disassembly process must by carefully reconnected  Be sure not to pinch or damage  these cables during reassembly  It is necessary to replace the tie wrap to secure to mechanically  secure the battery           Note  A SCADASense transmitter must be cold booted after a battery replacement to initialize  RAM  Unpredictable operation may result if a cold boot is not performed        7 2 Rotating Process Covers for Venting    As received  the IDP10 Transmitter provides sensor cavity draining without the need for side drain  connections  regardless of whether the transmitter is mounted vertically or horizontally  Sensor  cavity venting is provided by mounting horizontally or with the optional vent screw   V   However   if you did not specify this option  you can still achieve venting  instead of draining  with vertical  mounting by rotating the process covers  See Figure 23     SCADASense 4203 DR  Installation and User Manual 54  October 19  2007                 STANDARD  ORIENTATION  PROCESS COVERS    CONDENSED  LIQUID FREELY  DRAINS    GAS FREELY VENTS   REESE    INVERTED  PROCESS  COVERS    Figure 23  Sensor Cavity Venting and Draining    To rotate the process covers  refer to Figure 23  Sensor Cavity Venting and Draining and proceed    as follows    1  Remove the process covers from the sensor by removing two hex head bolts    2  Replace the gaskets in the process covers 
36. ee E 57  9 3 E elen erte ie 57  9 4 Visual 0 e E 58  9 5  ee ele 58  9 6 EE RE EE 58  9 7 ANBIOG OUD ee 58  9 8 Turbine Meter Counter Input    59  9 9 Digital Foer 59  9 10 Be 16 LOV TEE 59  9 11 Transmitter Functional Specifications              seeeeeeseeseneenrnneeeeerrrnrnnreneeeee 60  9 12 Transmitter Temperature Specifications                ccccceceeeeeeeeeeeeeeeeeeeeeeeeeees 61  9 13 Transmitter Performance Specifications               c cccccceeceeeeeeeneeeeeeeeeeeeees 62  9 14 Transmitter Physical Specifications            0ssssneneeeeeeeenennnnreeeeerrrrnrreeeeee 63  9 15 Approvals and Re ur ee 65  9 15 1 ATEX IECEx label EE 65  9 16 EREM 66    Index of Figures    Figure 1  Process Mount  d GFG sus egeuegugeckekendeegkg geet feabeueseges eabsnabipesteaenieasedatiasttaenense 8  Figure 2  Mounting the SCADASense 4203 DR Series to a Pipe or Gurtace  9  Figure 5  PGI M573 Five Valve Manfold   aresuarsdepdnteb due ek Saved 10  Figure 6  PGI M673 Five Valve Mantold  10  Figure 7  Differential Pressure Calibration Connections         xrrrrnnvrrrrnnnnnnnrrnnnnrrrrnnnnnnnerrnnnnnn 11  Figure 8  Absolute Pressure Calibration Connections             ssssssessserrrereseerrrrrrrrrrssrrrrrrrn 11  Figure 3  Optional Display and Write Protect Jumper 13  Figure 4  Accessing Field Terminals ccisuieiectubos teense arate commas ele tye daiednasalen ae data leee nt 14  Figure 5  Terminal  Board Layouts ccccicceietee Rs eege  Zeie Matra ade ene 15  Figure 6  Input Power Wiring with Exte
37. een the tertiary variable UOL and tertiary  variable LOL is no larger than the difference  between the tertiary variable URL and tertiary  variable LRL  The difference between the  tertiary variable UOL and tertiary variable LOL  must also be larger than 0 5  of the tertiary  variable URL     40437   40438  Float Write DP offset  These registers are used to change the DP  offset as a floating point number in the specified  floating point format  This register is write only   The transmitter must be in the calibrate mode to  change this register  No change will be made if  the transmitter mode is not correct   The DP offset must be within 0 5   primary  variable URL of the default reading    40439   40440  Float Read Write  DP Slope  These registers hold the DP slope as a floating   point number in the specified floating point  format   The transmitter must be in the calibrate mode to  change this register  No change will be made if  the transmitter mode is not correct   The DP span entered must result in a slope of  between 0 5 and 2 0     40441   40442 Float Read Write  DP Damping  These registers hold the DP damping as a  floating point number in the specified floating   point format   Valid values are 0 0  damping off   0 25  0 5   1 0  2 0  4 0  8 0  16 0  and 32 0 seconds  The    SCADASense 4203 DR  Installation and User Manual  October 19  2007       49    default value is 0  damping off     The transmitter must be in the offline or  calibrate mode to change this regist
38. ense 4203 DR can be disabled to conserve power  This is  particularly useful in solar powered or unattended installations     The application program sets the default state of the LED power  The state of the STAT LED  on or  off  and the time to return to the default state may be set in the TelePACE  ISaGRAF or C  application  The default state is set for OFF and time to return to the default state is set for 5 minutes  at the factory     SCADASense 4203 DR  Installation and User Manual 32  October 19  2007       6 Modbus Register Mapping    The tables in this section of the manual describe the SCADASense 4203 DR parameters that are  assigned to Modbus registers  The registers defined may be read only or read and write registers   The Read Write column in the tables indicates the register type     e Read indicates the register is read only     e Read Write indicates the register may be read or written to     6 1 Write Protect Jumper    The transmitter can be write protected by installing the write protect jumper  See Figure 7   Optional Display and Write Protect Jumper for the location of the write protection jumper     e When the write protect jumper is installed  registers 40001 to 40499 are read only     e When the write protect jumper is not installed  the read write ability corresponds to the table           Note  When the write protect jumper is changed while the transmitter is powered it may take up to  one minute for the change to be recognized        6 2 Software Wri
39. er  No  change will be made if the transmitter mode is  not correct     40443   40444  Float SP offset  These registers are used to change the SP  offset as a floating point number in the specified  floating point format  This register is write only   The transmitter must be in the calibrate mode to  change this register  No change will be made if  the transmitter mode is not correct   The SP offset must be within 0 5  secondary  variable URL of the default reading    40445   40446  Float Read Write  SP slope  These registers hold the SP slope as a floating   point number in the specified floating point  format   The transmitter must be in the calibrate mode to  change this register  No change will be made if  the transmitter mode is not correct   The SP span entered must result in a slope of  between 0 5 and 2 0  In order to change the  span at least 5  of the rated pressure must be  applied  otherwise the calibration will be  rejected     40447   40448  Float Read Write  SP Damping  These registers hold the SP damping as a  floating point number in the specified floating   point format   Valid values are 0 0  damping off   0 25  0 5   1 0  2 0  4 0  8 0  16 0  and 32 0 seconds  The  default value is 0  damping off    The transmitter must be in the offline or  calibrate mode to change this register  No  change will be made if the transmitter mode is  not correct    40449   40450  Float Read Write  PT Offset  These registers hold the PT offset as a floating   point number in 
40. er Assignment is erased     e The controller is unlocked     5 1 4 1 Cold Boot  Cold Boot mode is selected by performing a Cold Boot using the following procedure     1  Remove power from the controller    2  Push and hold the Cold Boot push button down   3  Apply power to the controller   4    A Cold Boot occurs when the Cold Boot push button is pushed and held for more than 30  seconds  The STAT LED blinks slowly after 30 seconds to indicate the Cold Boot mode is  selected           Note  If the Cold Boot push button is released before the STAT LED starts to blink slowly the  controller will start in Sensor mode        5 2 LED Status Indicator    The STAT LED indicates an alarm condition  The STAT LED blinks when an alarm occurs  The  STAT LED turns off when all alarms clear     The STAT LED blinks a binary sequence indicating alarm codes  The sequences consist of long and  short flashes  followed by an off delay of 1 second  The sequence then repeats  The sequence may  be read as the Controller Status Code  A short flash indicates a binary zero  A long flash indicates a  binary one  The least significant bit is output first  As few bits as possible are displayed  all leading  zeros are ignored  The application program defines the values of the alarm codes     The table below shows the meaning of the sequences        _ CONTROLLER STATUS CODE     Of    0   O Normalh   sd         see 1 Long Register Assignment EE  Error    5 2 1 LED Power Control    The STAT LED on the SCADAS
41. er entered barometric pressure   Digital output accuracy     0 05  of Span for spans  gt  or   10  of URL   Digital Output Accuracy for spans of  lt 10  URL      0 005 X URL   Span    of Span   Process Temperature     0 28  C   0 5  F  for the SCADASense DR Series transmitter  This does not include RTD  uncertainties  which are additive     Stability  Long Term Drift less than  0 05  of URL per year over a 5 year period     Power up Time    Less than 10 seconds for output to reach first valid measurement     Vibration Effect     0 2  of URL per    g    for vibrations in the range of 5 to 500 Hz  with double amplitudes of 6 3 mm   0 25 in  in the range of 5 to 15 Hz  or accelerations of 3    g    in the range of 15 to 500 Hz  whichever  is smaller  for transmitter with aluminum housing  and with double amplitudes of 6 3 mm  0 25 in   in the range of 5 to 9 Hz  or accelerations of      g    in the range of 9 to 500 Hz  whichever is smaller   for transmitter with 316 ss housing        SCADASense 4203 DR  Installation and User Manual 62  October 19  2007    RFI Effect    The output error is less than 0 1  of span for radio frequencies in the range of 27 to 1000 MHz and  field intensity of 30 V m when the transmitter is properly installed with shielded conduit and  grounding  and housing covers are in place   Per IEC Std  801 3      Supply Voltage Effect    Output changes less than 0 005  of span for each 1 V change within the specified supply voltage  requirements     Static Pres
42. er of character   overrun errors on Sensor communication with  the sensor electronics  This register is cleared  when the controller is reset     Integer  Read Sensor checksum errors    This register holds the number of checksum  errors on Sensor communication with the  sensor electronics  This register is cleared when  the controller is reset     Integer  Read Sensor commands sent    SCADASense 4203 DR  Installation and User Manual  October 19  2007       This register holds the number of Sensor  commands sent to the sensor electronics  This  register is cleared when the controller is reset     40162 Integer  Read Sensor responses received  This register holds the number of Sensor  responses received from the sensor electronics   This register is cleared when the controller is  reset     a014 40203   TI eeneg    40204 Integer  Read Scaled Integer Method  This register is included only for 3095  compatibility  Scaled integers are not supported   The only valid value is 0  The register will  always return 0 when read     40205 Integer  Read Write  Reset to Default Parameters  Writing to this register resets the transmitter to  default parameters   Note  The transmitter calibration is reset to full  scale with an offset of zero  The transmitter  should be re zeroed after this action   A sequence of three numbers must be written to  the register to cause a reset  This protects  accidental modification of the register from  resetting the parameters  Use the following  procedure t
43. ers  The first 7 ASCII characters  will be displayed on line 2 of the display   followed by the second 7 ASCII characters  The  Table 4 Display Module ASCII Characters  table below lists the displayable characters     40234     40235  Float Read Write  4 user defined display value  These registers hold the floating point value that  will be included i in the display cycle if the bit to  display the 4  user defined data set is turned on  in the Display Control register  Only values  between    9999 and 99999 can be displayed   Any value outside of that range will be replaced    5 dashes  on the display    40236     40242  ASCII Read Write  4  user defined display text  These registers hold the text that will be  included in the display cycle if the bit to display  the 4  user defined data set is turned on in the  Display Control register  Each register holds 2  ASCII characters  The first 7 ASCII characters  will be displayed on line 2 of the display   followed by the second 7 ASCII characters  The  Table 4 Display Module ASCII Characters  table below lists the displayable characters    40243     40244  Float Read Write  5 user defined display value  These registers hold the floating point value that  will be included in the display cycle if the bit to  display the 5  user defined data set is turned on  in the Display Control register  Only values  between    9999 and 99999 can be displayed   ou value outside of that range will be replaced    5 dashes  on the display     40245
44. fference between the  primary variable URL and primary variable LRL   The difference between the primary variable  UOL and primary variable LOL must also be  larger than 1  of the primary variable URL     40421   40422  Float Read SP Upper Range Limit  These registers hold the SP upper range value  as a floating point number in the specified  floating point format      SCADASense 4203 DR  Installation and User Manual  gt  A0 4203 DR  Installation and User Manual  October 19  2007    Read Write  DP Upper Operating Limit  These registers hold the DP upper operating  limit as a floating point number in the specified  floating point format   The transmitter must be in the offline mode to  change this register  No change will be made if  the transmitter mode is not correct   The DP upper operating limit may be set higher  than the primary variable upper range limit  The  primary variable upper operating limit my be set  as high as 1 5 times the primary variable upper  range limit  provided that the difference between  the primary variable UOL and primary variable  LOL is no larger than the difference between the  primary variable URL and primary variable LRL        40423   40424 Float SP Lower Range Limit  These registers hold the SP lower range value  as a floating point number in the specified  floating point format     40425   40426    secondary variable LOL must also be larger  than 1  of the secondary variable URL     Read Write  SP Lower Operating Limit  These registers hold
45. ing Limit  These registers hold the SP upper operating  limit as a floating point number in the specified  floating point format   The transmitter must be in the offline mode to  change this register  No change will be made if  the transmitter mode is not correct   The SP upper operating limit may be set higher  than the secondary variable upper range limit   The secondary variable upper operating limit  may be set as high as 1 25 times the secondary  variable upper range limit  The difference  between the secondary variable UOL and       as high as 1 25 times the tertiary variable upper  range limit  provided that the difference between  the tertiary variable UOL and tertiary variable  LOL is no larger than the difference between the  tertiary variable URL and tertiary variable LRL   The difference between the tertiary variable  UOL and tertiary variable LOL must also be  larger than 0 5  of the tertiary variable URL     40435   40436  Float Read Write  PT Lower Operating Limit  These registers hold the PT lower operating  limit as a floating point number in the specified  floating point format   The transmitter must be in the offline mode to  change this register  No change will be made if  the transmitter mode is not correct   The PT lower operating limit may be set lower  than the tertiary variable lower range limit  The  tertiary variable lower operating limit my be set  as low as absolute zero   273 15   C   459 67  F   0 K  or 0   R   provided that the difference  betw
46. isplay  the 8  user defined data set is turned on in the  Display Control register  Each register holds 2  ASCII characters  The first 7 ASCII characters  will be displayed on line 2 of the display   followed by the second 7 ASCII characters  The  Table 4 Display Module ASCII Characters  table below lists the displayable characters    40279     40280  Float Read Write  9 user defined display value  These registers hold the floating point value that  will be included i in the display cycle if the bit to  display the 9  user defined data set is turned on  in the Display Control register  Only values  between    9999 and 99999 can be displayed   Any value outside of that range will be replaced    5 dashes  on the display    40281     40287  ASCII Read Write  9  user defined display text  These registers hold the text that will be  included in the display cycle if the bit to display  the 9  user defined data set is turned on in the  Display Control register  Each register holds 2  ASCII characters  The first 7 ASCII characters  will be displayed on line 2 of the display   followed by the second 7 ASCII characters  The  Table 4 Display Module ASCII Characters  table below lists the displayable characters     Read Write  10 user defined display value  These registers hold the floating point value that  will be included i in the display cycle if the bit to  display the 10  user defined data set is turned  on in the Display Control register  Only values  between    9999 and 99999 can
47. l is   Check that the digital input is not forced on   applied   Input is off when a signal is Check that the digital input is not forced off   applied     8 3 Digital Output   Problem Acton i  Using TelePACE firmware Ensure the 4203 DR 4202 DR Extended I O  cannot turn output on or off    register assignment is being used   Using ISaGRAF firmware Ensure the ss4203dr I O equipment is added to  cannot turn output on or off    I O connection   Output is on when no signal   Check that the digital input is not forced on   is applied   Output is off when a signal Check that the digital input is not forced off   is applied     8 4 Counter Inputs             Incorrect counts on CTRO DINOcounter digital input is a high speed  CTR DINO input  Ensure that the applied input is free of  contact bounce     SCADASense 4203 DR  Installation and User Manual  October 19  2007       56    9 Specifications    Disclaimer  Control Microsystems reserves the right to change product specifications without  notice  For more information visit www controlmicrosystems com         9 1 General    I O Terminations 2  3 and 4 pole  removable terminal blocks   16 to 28 AWG  8A contacts    Environment 5  RH to 95  RH  non condensing   40 C to 70  C     40  F to 158  F       9 2 Controller    Processors 32 bit ARM microcontroller  32MHz clock  integrated watchdog timer  Sensor interface co processor  Memory 4MBytes CMOS RAM  8MBytes Flash ROM  1kBytes EEPROM  Non volatile CMOS RAM with lithium battery retains 
48. ld Types and Installation  Several manifold models are available to interface a transmitter with the process piping  The PGI     M573 has      FNPT inlets and      FNPT outlets  while the PGI M673 has 1   2    FNPT inlets and    SCADASense 4203 DR  Installation and User Manual 9  October 19  2007       Instrument Flange outlets  Two options are available  The CDT option is of carbon steel  construction while the SDJ option uses 316SS NACE construction  140F max  and has a  fluorosilicone stem seal         7 126 MAX  OPEN   181    1 2 NPT   YP  N STRUMENT SIDE    Ge         PROCESS SIDE  30 KR 28 3 576  2  2818 MOUNTING HOLES     85 7   Figure 3  PGI M573 Five Valve Manifold       7 125 MAX OPEN    Figure 4  PGI M673 Five Valve Manifold    The bolts to mount the PGI M673 model to the sensor are 7 16 20 x 1       SCADASense 4203 DR  Installation and User Manual 10  October 19  2007    3 1 5 Connections For Sensor Calibration    It should be noted that when an Absolute  Static  Pressure calibration is performed the bypass or  cross feed valve on the manifold must be open  When performing a Differential Pressure calibration  the bypass valve must be closed                BYPASS VALVE HIGH PRESSURE SIDE    SHUTOFF VALVES CALIBRATING    PRESSURE  SOURCE    Note  Altemate connection point for calibrating  equipment is optional vent screw  not shown  on       high pressure side cover  BLEEDER VALVES     NEEDLE TYPE     HIGH PRESSURE SIDE    APPLY AP CALIBRATING PRESSURE   OR VENT  TO
49. ls which items are displayed   on the display  This register is a bit mapped   field  The following shows the effects of   individual bits  When a bit is turned on the   floating point value and associated text will be   cycled through on the display    Bit 00   Display DP in transmitter units   Bit 01   Display SP in transmitter units   Bit 02   Display PT in transmitter units   Bit 03   Display Communication settings   baud rate and station number    Bit 04   Display 17 user defined data set   Bit 05   Display 2    user defined data set   Bit 06   Display 3 user defined data set   Bit 07   Display 4  user defined data set   Bit 08   Display 5  user defined data set   Bit 09   Display 6  user defined data set   Bit 10   Display D   user defined data set   Bit 11   Display 8  user defined data set   Bit 12   Display 9  user defined data set     SCADASense 4203 DR  Installation and User Manual Se 4203 DR  Installation and User Manual  October 19  2007       Bit 13   Display 10  user defined data set  Bit 14   Display 11  user defined data set  Bit 15   Display 12  user defined data set    mem     Bees OOOO SS o    og Integer  Read Write  Response Delay time  This register is included for 3095FB  compatibility only  The response delay time  cannot be set  The value in this register has no  effect     40132 Integer  Read Write  Floating Point Format  This register is included for 3095FB  compatibility only  The floating point format is  fixed   This register specifies the byte o
50. nimum input 750mVp p at 10kHz   Maximum input 4Vp p using internal amplifier   Transient 2 5kV surge withstand capability as per ANSI IEEE C37 90 1   Protection 1989  Isolation Common ground return connected to Chassis Ground   9 9 Digital Counter Input  Counter 0   Dry contact input   Wetting current typically 5mA   Contact closure to ground is ON   Open input is OFF   Frequency 0 10kHz   Input Thresholds 0 8V typical turn on input voltage   Less than 0 4V guaranteed turn on input voltage   1 5V typical turn off input voltage   Greater than 2 0V guaranteed turn off input voltage   Contact Resistance ON input requires less than 1000 contact resistance   OFF input requires greater than 1kQ contact resistance   Transient 2 5kV surge withstand capability as per ANSI IEEE  Protection C37 90 1 1989  Isolation Common ground return connected to Chassis Ground   9 10 Digital Output  Load Range 500mA maximum  30VDC maximum  Transient 2 5kV surge withstand capability as per ANSI IEEE C37 90 1   Protection 1989  Isolation Common ground return connected to Chassis Ground   Note Digital Output available on version 5 and later controller  hardware     October 19  2007    9 11    Transmitter Functional Specifications    Span and Range Limits for Differential Pressure  amp  Absolute Pressure                                                 Span   Differential Pressure Absolute Pressure   Code   inches of H20 kPa psia MPa   A 0 5 to 30 inH20  0 12 to 7 5 kPa  1 to 100 psi  0 007 to 0 7 MPa   B
51. nnseninnnimmetinundnssanddddv 12  3 2 1 Adding the Optional Display  12  3 3 He Gea    i EE a ia AE E 13  3 4 Pors ee es ee oe ee e 15  3 4 1 FUSING EE 15  3 4 2 System Ee Te ue DEE 16  3 5 Internal Analog Input EE 16  3 6 EEE ERR E E 17  3 7 Anag Te TEE 19  3 7 1 HERE ENEE 20  3 7 2 Voltage Q  tp  tS raserer EE 20  3 7 3 Analog Outputs Data Fommat 20  3 7 4 Digital Output Control with External Relay         rrrrrrrnnnnnnnornnnnnnrrrnnnnn 20  3 8 Digital  O and Counters EEE EE 21  3 8 1 Turbine Meter Counter Input   CIR    22  3 8 2 Counter   Digital Input   CTRO DIN DOUT   n ssnssnneeeeeeseesnnnereeeseeeerene 22  3 8 3 Digital  Output  CTRO DIN DOUT massenes geaene ease  22  4 SERIAL  COMMUNICATION  i cvsnseseentisasnroamnsssosasctmensasapesesdsntmensdsasuensiemsnccams 24  4 1 RS 232 Serial Communications Ports           sseeeeeeeeenneneneeeseerrrernnnrenseerrnne 24  4 1 1 RS 232 Wiring Examples EE 24  4 1 2 COM1 RS 232 Serial Port Settings               cccceeeeeeeeeeeeeeeeneeeeeeeeeeeeeees 25  4 1 3 COM2 RS 232 Serial Port Settings ENNEN 25     SCADASense 4203 DR  Installation and User Manul S S2    October 19  2007    4 1 4 COM3 RS 232 Serial Port Settings         rrrrrrnnnnnnnnnnnnnnnrrrrnnnnnnnnrrrnnnnnnn 26  4 2 RS 485 Serial Communications Porte  26  4 2 1 RS 485 Wiring Examples ENEE 27  4 2 2 RS 485 Bias Resistors            cccccceeccecceeececceeceeececceeeceeceecaeececcueeaeeeeeeas 27  4 2 3 RS 485 Termination Resistors             0cccccceeceecceccecececceccaeccec
52. nsert it in the electronics module  aligning the tabs on the sides  of the assembly  and twist it in the clockwise direction     3 3 Transmitter Wiring    The installation and wiring of the GFC must conform to local code requirements           Note for North America  Seal not required when installed with rigid conduit per requirements of  the applicable electrical code  When using instrument cable approved for the hazardous  location  a seal must be made with an approved cable gland or conduit seal per the  requirements of the applicable electrical code        SCADASense 4203 DR  Installation and User Manual 13  October 19  2007             Note for ATEX IECEx  Seal required when installed with rigid conduit per requirements of the  applicable electrical code  When using instrument cable approved for the hazardous  location  a seal must be made with an approved cable gland or conduit seal per the  requirements of the applicable electrical code        For access to the field terminals  thread the cover lock  if present  into the housing to clear the  threaded cover and remove the cover from the field terminals compartment as shown in Figure 8   Note that the embossed letters FIELD TERMINALS identify the proper compartment     PG 13 5 OR 1 2 NPT CONDUIT CONNECTION FOR   USER WIRING  ONE ON OPPOSITE SIDE ALSO    PLUG UNUSED OPENING WITH METAL PLUG PROVIDED   OR EQUIVALENT  TO MAINTAIN RFIVEMI  ENVIRONMENTAL  AND EXPLOSIONPROOF RATINGS        REMOVE COVER TO ACCESS  WIRING TERMIN
53. o reset the parameters   Write the value 493 to the register   Write the value 27254 to the register   Write the value 6003 to the register   To abort the sequence once it is started write  any value other than the next value in the  sequence   See the  Default Parameters table for default  values        40206 Integer  Read Write  Sensor operating mode  This register controls the operating mode of the  transmitter  online mode  offline mode  or  calibrate mode   Note  Process values are updated only in the  online mode  Ensure the system is in a safe  state before switching to offline or calibrate  mode   This register must be set to offline mode before  changing engineering units or re ranging the  transmitter   This register must be in either offline mode or  calibrate mode before changing the damping  values   This register must be set to calibration mode  before changing the span or the zero   Changes are not applied until the unit is placed     SCADASense 4203 DR  Installation and User Manual 39 4203 DR  Installation and User Manual  October 19  2007    online  Valid values shown below  The default  value is 0  online     0  online mode  normal operation   63  offline mode  change engineering units   re range transmitter or change damping values   255  calibrate mode  change zero  span or  damping values    The display will indicate OFFLINE when the  transmitter is in the offline or calibrate modes   The display will operate normally in the online  mode  When the transmi
54. oo SSS    w  9 osr  w    SCADASense 4203 DR  Installation and User Manual  October 19  2007       53    7 Maintenance    A SCADASense 4203 DR transmitter requires little maintenance  If the program is lost during  power outages  the lithium battery may require replacement     The analog input and output circuitry is calibrated at the factory and does not require periodic  calibration  Calibration may be necessary if the module has been repaired as a result of damage     If the controller is not functioning correctly  contact Control Microsystems Technical Support for  information on returning the SCADAPack Controller for repair     CAUTION     Do not connect or disconnect any field wiring  including the  wiring to the RS 232 ports  unless the power is off or the  area is know to be non hazardous     7 1 Lithium Battery    A small lithium battery powers the CMOS memory and real time clock when input power is  removed     The battery should not require replacement under normal conditions  The shelf life of the battery is  10 years  The battery is rated to maintain the real time clock and RAM data for two years with the  power off  Accidental shorting or extreme temperatures may damage the battery     The battery is plugged into the circuit board and secured with a tie wrap  If necessary it can be  replaced with an identical battery available from Control Microsystems     Battery replacement requires complete disassembly of the electronics assembly inside the controller   Extrem
55. ostic  bits  This register always contains 0    40411 Integer  Read Diagnostic Bits   mag rett This register is reserved for future diagnostic  bits  This register always contains 0     SCADASense 4203 DR  Installation and User Manual  October 19  2007       40412 Integer  Read Diagnostic Bits  This register is reserved for future diagnostic  bits  This register always contains 0   40413 40414  Float Read DP Upper Range Limit  These registers hold the DP upper range value  as a floating point number in the specified  floating point format   40415   40416  Float Read DP Lower Range Limit  These registers hold the DP lower range value  as a floating point number in the specified  floating point format     40417   40418    The difference between the primary variable  UOL and primary variable LOL must also be  larger than 1  of the primary variable URL     40419   40420  Float Read Write  DP Lower Operating Limit  These registers hold the DP lower operating  limit as a floating point number in the specified  floating point format   The transmitter must be in the offline mode to  change this register  No change will be made if  the transmitter mode is not correct   The DP lower operating limit may be set lower  than the primary variable lower range limit  The  primary variable lower operating limit my be set  as low as 1 5 times the primary variable lower  range limit  provided that the difference between  the primary variable UOL and primary variable  LOL is no larger than the di
56. ounter input identified as CTR1  Counter input  CTR1 includes a built in pre amplifier and is designed to work with turbine meter inputs  This  counter input operates as a counter only     SCADASense 4203 DR  Installation and User Manual 21  October 19  2007    In addition to the turbine meter input the SCADASense 4203 DR has a multi purpose counter input  and digital input output connection identified as CTRO DIN DOUT     The CTRO DIN DOUT counter   input is used with open collector or drain output devices  relay  contacts or switches  The CTRO DIN DOUT digital output is an open drain  sinking  digital output     Refer to the appropriate software manual for information on using counter Inputs in application  programs  For TelePACE applications and ISaGRAF applications  refer to the Register Assignment  and I O Complex Equipment respectively for the GFC     P5    Turbine  Meter    Sensor       CTRO DIN DOUT       Note  Counter 0 is shown as a relay  or switch contact  Counter 1 is shown    as a turbine meter sensor        Figure 17  Digital and Counter Input Wiring    3 8 1 Turbine Meter Counter Input   CTR1    The SCADASense 4203 allows for the direct connection to one turbine meter sensor  These sensors  produce millivolt outputs and do not require an external pre amplifier when used with the GFC  The  turbine meter input can be used in low noise environments with shielded cabling  Counter I is  shown with a direct connection to a turbine meter sensor  Shielded wiring must 
57. ply  requirements        Figure 10  Input Power Wiring with External Fuse      Power    Note  See text for power supply  requirements        Figure 11  Input Power Wiring with Internal Fuse    3 4 2 System Grounding    The SCADASense 4203 DR circuitry is electrically isolated from the housing for voltages up to  550Vac  All terminal board connections labeled COM on connectors P2  P3 and P5 are tied together  and connected to  PWR on the input power terminal block P1  The Serial Communication Ports   Counter Digital Inputs  Analog Outputs and Input Power all share the same electrical common     3 5 Internal Analog Input    A SCADASense 4203DR Series transmitter has one internal analog input  These internal analog  inputs are accessed from the user application program  The analog input monitors the supply  voltage     The analog input returns 16 bit integer values  Valid values are 0 to 32700  The input value is scaled  to represents the voltage in mV with 100mV resolution     For TelePACE applications use     e The 4203 DR 4202 DR Extended I O module register assignment to read the supply voltage in  mV ona SCADASense 4203 DR     SCADASense 4203 DR  Installation and User Manual 16  October 19  2007    For ISaGRAF applications use     e The ss4203dr complex equipment to read the supply voltage in mV on a SCADASense 4203  DR     3 6 RTD Input    The SCADASense 4203 DR requires a connection to an RTD  A 4 wire connection to the RTD is  recommended for the highest accuracy  Refer 
58. rder of floating   point registers  All floating point numbers are in  the IEEE 754 format  Numbers are made up of  one sign bit  S   eight exponent bits  E   and  twenty three mantissa bits  M   A number  consists of 4 bytes as shown below   Byte A Byte B Byte C Byte D  SEEE EEEE EMMM MMMM MMMM MMMM MMMM  MMMM  The only valid value is 0  The register will  always return 0 when read   0  ABC D  default  RealFLO format   1  C DAB  not available   2 DCBA  not available   3   B A D C  not available     40133   40144    Reseved o OS    40145     keng        com2 ee ES errors  This register holds the number of framing errors  on com2  This register is cleared when the  controller is reset    40146 Integer  Read com2 parity errors  This register holds the number of parity errors  on com2  This register is cleared when the  controller is reset    40147 Integer  Read com2 overrun errors  This register holds the number of character   overrun errors on com2  This register is cleared  when the controller is reset    40148 Integer  Read com2 Modbus checksum errors  This register holds the number of Modbus  checksum errors on com2  This register is  cleared when the controller is reset    40149 Integer  Read com2 Modbus commands received  This register holds the number of Modbus  commands received on com2  This register is  cleared when the controller is reset     SCADASense 4203 DR  Installation and User Manual  October 19  2007       40150 Integer  Read com2 Modbus responses sent  This 
59. register holds the number of Modbus  responses sent on com2  This register is  cleared when the controller is reset     40151 Integer  Read com3 framing errors    This register holds the number of framing errors  on com3  This register is cleared when the  controller is reset     Integer com  parity errors    This register holds the number of parity errors  on com3  This register is cleared when the  controller is reset     Integer  Read com3 overrun errors  This register holds the number of character   overrun errors on com3  This register is cleared  when the controller is reset   Read com3 Modbus checksum errors  This register holds the number of Modbus  checksum errors on com3  This register is  cleared when the controller is reset   Read com3 Modbus commands received  This register holds the number of Modbus  commands received on coms  This register is  cleared when the controller is reset   Read com3 Modbus responses sent  This register holds the number of Modbus  responses sent on coma  This register is  cleared when the controller is reset   Read Sensor framing errors  This register holds the number of framing errors  on Sensor communication with the sensor  electronics  This register is cleared when the  controller is reset   Read Sensor parity errors  This register holds the number of parity errors  on Sensor communication with the sensor  electronics  This register is cleared when the  controller is reset     Read Sensor overrun errors  This register holds the numb
60. rements of the analog output can be used  An example of AC and DC  digital outputs is shown using solid state relay modules  These examples use DIN rail mounted  output modules from Crouzet Gordos  These modules have a 4 32VDC input range     Turn OFF an output module by writing 0 to the Analog Output  Turn ON an output module by  writing 32767  20mA  to the Analog Output  Lower currents can be used to save power  Refer to the  relay specifications for the input requirements for the selected relay     Model 84130104 is a 5 60V DC  3A DC output module with integrated fuse  Refer to Figure 15  DC  Digital Output Wiring Example for wiring details     SCADASense 4203 DR  Installation and User Manual 20  October 19  2007    Solid State Relay VT D GC     3  VDC  84130104 5 60VDC  3A  9 30VDC Input DC Output Module Output    Power  4  VDC  Supply            Load may be wired in location A or B   DC inductive loads must be diode  suppressed             Figure 15  DC Digital Output Wiring Example    Model 84130105 is a 12 280V AC  5A AC output module with integrated fuse  Refer to Figure 16   AC Digital Output Wiring Example for wiring details     Solid State Relay           G  3 1  LOAD  A  VAC Hot  84130105 12 280VAC  5A  9 30VDC Input AC Output Module Output  Power  4 2  LOAD  B  VAC Neutral    Supply       Note   Load may be wired in location A or B           Figure 16  AC Digital Output Wiring Example    3 8 Digital I O and Counters    The SCADASense 4203 DR has a turbine meter c
61. rnal Fuse           ssssssssesessssseesrrnrersserrrrrrrnnerssrrrrrernn 16  Figure 7  Input Power Wiring with Internal FUSe          rnrnnnnnnnannrnnnnnrnnnnnnnnnnrrnnnnrrnnnnnnnnnrrnnnnnn 16  Figure 8  Transmitter 4 Wire RTD Wiring      rrrnnnnnnnnnnnnrrrnnnnnnnnnnnnnnrrrnnnnnnnnernnnnrrrnnnneesnerrnnnnnn 17  Figure 9  Transmitter 3 Wire RTD Wiring           eononnnnnnnnnnvnnnnnnnnnnnnnnnnennnnnennnnnnnnnnnennnnnnnennennnnn 17  Figure  11  Analog Output Wri Nee due ee ind kjen EAR EE EEN 19  Figure 12  DC Digital Output Wiring Example        ornnnnvrrrnnnnnnnonnnnnrrrrnnnnnnnnrnnnnnrrrrnnnnnnnerrnnnnnn 21  Figure 13  AC Digital Output Wiring Example AAA 21  Figure 14  Digital and Counter Input Wiring               cece eeeeeeeee tere eee eeeeee eset etree eeennaeeeeeeeeeeteeee 22     SCADASense 4203 DR  Installation and User Manul A    October 19  2007    Figure 15  Digital Output Wiring Example 2 eeeceutgergetsgerhesetgoe Sege eRg eege ege 23    Figure 16  COM2 RS 232 Wiring mun kurven smiueadansu 24  Figure 17  COM3 RS 232 Wiring BE 25  Figure 18  COM2 RS 485 Wirnguuumssnsinijndjemkjeadduuintjedadmskjnakt end 27  Figure 19  COM3 RS 485 Wiring 2 seeeccensssicceet ve chewentas cues netkeweareasteukse shoves EES ENNEN 27  Figure 20  Sensor Cavity Venting and Draining        rrvrrrrnnnnnnonrnnnnrrrrnnnnnnnrrnnnnrrrrnnnnenrerrnnnnnn 55  Index of Tables  Table 1  Data Form  l ae 33  Fable  2 MOdbus FOG SES Leed 34  Table 3  SCADASense 4203 DR  Default Parameter    52  Table 4  Di
62. splay Module ASCII Characters AEN 52  SCADASense 4203 DR  Installation and User Manual 5    October 19  2007    1 Overview    The SCADASense 4203 DR  is a two meter run flow computer with an integrated multivariable  sensor  The transmitter is supplied with a pre configured gas flow application and can also be  programmed in TelePACE Relay Ladder Logic  compiled C  and IEC 61131 3     The SCADASense 4203 DR transmitter provides a discrete input output that can be used as status  input  or as a high frequency counter input or a sinking digital output  A second high frequency  counter input accepts low level inputs from devices such as turbine meters  Standard analog output  provides flexible control for variable speed motor drives  control valves  emergency shutdowns  or  whatever your site requires  The applied power source voltage is internally monitored and available  for communication to the SCADA host     These SCADASense 4203 DR transmitters provide a Modbus mapping of all transmitter functions  that is compatible with the Rosemount 3095FB MVT  The transmitter can be used with or without  the flow computer program     This DR Series Gas Flow Computers  GFC   s  provide two fully functional RS 232 485 selectable  serial ports  Either or both ports can be used with remote I O  radios  local displays  or other serial  devices  Either of the two provided serial ports can be used to communicate with another member of  the SCADAPack family for I O expansion     The SCADASense 
63. ssword are used     5 1 2 1 Service Boot  Service mode is selected by performing a Service Boot using the following procedure     1  Remove power from the controller    2  Push and hold the Cold Boot button down   3  Apply power to the controller   4    Continue holding the Cold Boot push button down STAT LED turns on solid  This will take  about 3 seconds     5  Release the Cold Boot push button     SCADASense 4203 DR  Installation and User Manual 30  October 19  2007    6  The Service Boot remains in effect until the GFC is reset           Note  If the Cold Boot push button is released before the STAT LED turns on  the controller will  start in RUN mode        5 1 3 Sensor Mode    The Sensor Mode allows direct communication with the sensor electronics  This mode is provided  to allow use of applications and tools that must communicate directly with the sensor electronics   When the controller starts in Sensor mode     e The coml and com  serial ports operate at 4800 baud  no parity  8 data bits  and one stop bit   e The com3 serial port does not function     e Sensor messages received on com  are transmitted on com1 with the initial FF removed  Sensor  messages received on com  are transmitted on com2  Sensor timing restrictions are observed  when transmitting  In effect  the transmitter is acting as a repeater     e The TelePACE Ladder Logic or ISaGRAF program is stopped   e The C program is stopped     e No other controller features are available     5 1 3 1 Sensor Boot  
64. sure Effect on Differential Pressure   The zero and span shift for a 7 MPa   1000 psi   change in static pressure is   ZERO SHIFT  0 05  of URL   SPAN SHIFT  0 1  of Reading    Position Effect    Transmitter may be mounted in any position  Any zero effect caused by mounting position can be  eliminated by re zeroing  There is no span effect     Ambient Temperature Effect    Total effect for a 28  C  55  F  change within Normal Operating Condition limits for both absolute  and differential pressure measurements is     DIGITAL OUTPUT    0 03  URL   0 06  Reading    For Span Codes A and L   DIGITAL OUTPUT    0 18  URL   0 025  Reading      Switching and Indirect Lightning Transients    The transmitter can withstand a transient surge up 2000 V common mode or 1000 V normal mode  without permanent damage  Output shift is  lt 1 0    Per ANSI IEEE C62 41 1980 and IEC Std  801   5      Electromagnetic Compatibility    Complies with NAMUR Part 1 Interference Immunity Requirement  EMC   Complies with  Electromagnetic Compatibility Requirements of European EMC Directive 89 336 EEC by  Conforming to following CENELEC and IEC Standards  EN 50081 2  EN 50082 2  IEC 801 2  through 801 6    9 14 Transmitter Physical Specifications    Process Cover and Connector Material  Process Wetted   316 ss or Hastelloy C  as specified     SCADASense 4203 DR  Installation and User Manual 63  October 19  2007    Process Cover and Process Connection Gaskets  Glass filled ptfe  Chemloy     Process Cover Bolts
65. te Protect    The Flow Computer must log all changes to measurement parameters  When the flow computer is  running the software write protect is enabled  This prevents Modbus protocol commands and logic  applications from writing the transmitter registers     e When the software write protect is enabled  registers 40001 to 40499 are read only via Modbus  commands  Ladder Logic register access  and ISaGRAF register access  C programs can write to  the registers in the normal fashion     e When the software write protect is disabled  the read write ability corresponds to the table     The software write protect is disabled by default at reset     6 3 Data Formats    Data formats defined in the table below are used in the GFC DR Series controllers     Table 1  Data Format    Data Type Registers Description  Required    Unsigned integer in the range 0 to 65535        Float 2 IEEE single precision floating point number  The byte  order is determined by the contents of the Floating Point  Byte Order register  40132   Floating point values are stored in two consecutive  registers  Both registers must be read or written in the  same Modbus command  Failure to do so may result in  indeterminate values     SCADASense 4203 DR  Installation and User Manual 33  October 19  2007       Data Type Registers Description  Required       ASCII 1 Two characters are stored in each register  Valid values  are any ASCII character  The first character is in the low  order byte  the second in the high
66. the specified floating point  format   The transmitter must be in the calibrate mode to  change this register  No change will be made if  the transmitter mode is not correct   The PT offset may be adjusted from the default  value by up to 1  of the tertiary URL     40451 40499     fReseved o    40500 Integer  Read Write Here for resevet mig mir output   see default register assignment     SCADASense 4203 DR  Installation and User Manual  October 19  2007       6 4 1 Default Parameters    A SCADASense 4203 DR Series transmitter is reset to default values when the correct sequence is  written to register 40205  The following table shows the registers that are reset and their default    values     SCADASense 4203 DR  Installation and User Manual  October 19  2007    51    Table 3  SCADASense 4203 DR  Default Parameters    ao wech BiagnosteBis         man meer hb fBiagnosieBis            mag   wech Deoeicn    mag eet foo  DPLowerOperaiing Limit    40427 40428  Fot bi  SPLowerOperainglimit    4047 4048 eg o0 Daf      man 40442  Flot o0 Dien            0443 40444 bet  00 Eed         mam Foa o0 EE         0449 40450 Foa o0 O EI oo o       6 4 2 Display Module ASCII Characters    The table below lists the useable ASCII characters for the Display Module  The User Defined  Display Text registers use these characters     Table 4  Display Module ASCII Characters    04 TH me   gt          SCADASense 4203 DR  Installation and User Manual  October 19  2007       52    geg  SES E  o p os po 
67. the transmitter using the two lock  washers and screws provided  Mount the GFC with mounting bracket to a vertical or horizontal  DN  50 or 2 in pipe  To mount to a horizontal pipe  turn the U bolt 90   from the position shown in  Figure 2  The mounting bracket can also be used for wall mounting by securing the bracket to a wall  using the U bolt mounting holes     APPROXIMATELY 3 IN  CLEARANCE REQUIRED  FOR ACCESS TO MOUNTING  BOLTS AND VENT SCREW     FOR SURFACE MOUNTING      REPLACE U BOLT WITH TWO  0 375 IN DIAMETER BOLTS  OF SUFFICIENT LENGTH TO  PASS THROUGH BRACKET    AND SURFACE    a oe DN 50 OR 2 IN PIPE    SHOWN  ROTATE U BOLT 90    FOR MOUNTING TO HORIZONTAL  PIPE    OPTIONAL SIDE VENT          Figure 2  Mounting the SCADASense 4203 DR Series to a Pipe or Surface    3 1 3 Positioning the Transmitter Housing    The SCADASense 4203 DR housing  top works  can be rotated up to one full turn in the  counterclockwise direction when viewed from above for optimum access to adjustments  display  or  conduit connections           Note  Do not rotate the housing more than one turn from the    as received    position  If there is  doubt about the housing rotational position  turn fully clockwise and then back off no more  than one full turn     WARNING  The small setscrew on the housing keeps the housing from being rotated too far   This is NOT a locking screw  Do not tamper with this screw  Damage to the housing  can occur if this setscrew is tampered with        3 1 4 Manifo
68. to Figure 12  Transmitter 4 Wire RTD Wiring for  wiring information for 4 Wire RTDs to the transmitter     I Excite       Figure 12  Transmitter 4 Wire RTD Wiring    A 3 wire RTD can be used with a minimal reduction in accuracy in the transmitter  When using 3  wire RTDs run 4 wires as long as possible from the terminal board to the RTD  See Figure 13 for  wiring information for 3 Wire RTDs to the transmitter        RTD    3 RTD Exicite SE ES      EN    P4    Figure 13  Transmitter 3 Wire RTD Wiring    A 3 wire RTD can be used with the SCADASense 4203 DR  The transmitter RTD circuitry will  compensate for the resistance in the connection to pin 3  See Figure 13 for wiring information for 3   Wire RTDs on the transmitter     SCADASense 4203 DR  Installation and User Manual 17  October 19  2007    The transmitter RTD inputs have been declared as non incendive for use in Class I Div  2  Hazardous locations  Ordinary wiring methods can be used in accordance with the NEC and CEC     SCADASense 4203 DR  Installation and User Manual  October 19  2007    18    3 7 Analog Output    The SCADASense 4203 includes one 0 20mA current sinking analog output  The analog output is a  sinking type in the sense that it limits the current flowing through its terminals to 0 20mA  When a  value of 0 is written to the D A converter  the analog output allows OmA of current flow through its  terminals  When a value of 32760 is written to the D A converter  the analog limits the current flow  through i
69. transmitter can be supported by the process piping as shown in Figure I or mounted to a  vertical or horizontal pipe or surface using the optional mounting bracket shown in Figure 2           Note  If the GFC is not installed in the vertical position as shown in Figure I or Figure 2  readjust  zero output to eliminate the position zero effect  The GFC should be mounted so that any  moisture condensing or draining into the field wiring compartment can exit through one of  the two threaded conduit connections        CAUTION     To avoid damage to the GFC sensor  do not use any impact  devices  such as an impact wrench or stamping device  on  the transmitter           Note  Use a suitable thread sealant on all connections        3 1 1 Process Mounted Transmitter    Figure I shows a SCADASense 4203 DR transmitter mounted to and supported by the process  piping        FIELD TERMINALS COMPARTMENT   CONTAINS TERMINAL BLOCK FOR USER  MRING CONNECTIONS               A  TiN er D    at  l  1  i  ANT    at         i     ab hh iL    MARK INDICATING LOW AND HIGH PRESSURE SIDES    HIGH PRESSURE  PROCESS CONNECTION    LOW PRESSURE  PROCESS CONNECTION    PROCESS CONNECTORS  2     Figure 1  Process Mounted GFC    SCADASense 4203 DR  Installation and User Manual  October 19  2007          3 1 2 Pipe or Surface Mounted Transmitter    To mount the transmitter to a pipe or surface  use the Optional Mounting Bracket Set  Model Code  Option  M   Referring to Figure 2  secure the mounting bracket to 
70. ts terminals to 20mA  Given that the analog output is referenced to a power source  these  currents have to be provided through an external load     Refer to the appropriate software manual for information on using the analog output in an  application programs  For TelePACE and ISaGRAF applications refer to the Register Assignment or  I O Complex Equipment respectively  for the controller     When a sinking analog output is wired to an external device care must be taken to ensure the  operating characteristics of the analog output are considered  As can be seen in Figure 14  Analog  Output Wiring the LOAD does not connect to ground at any point  The LOAD must be able to  float above ground in order for the analog output to function  The analog output must be connected  to a differential input device    For example  in the wiring example shown in Figure 10  the points A and B will each be at a  positive voltage based on the sinking current output  the LOAD resistance and the Power Supply  voltage     e Fora sinking current of 0 mA  a LOAD resistance of 250 Ohms and a power supply voltage of  24VDC the voltage at both A and B points is 24VDC     e Fora sinking current of 20 mA  a LOAD resistance of 250 Ohms and a power supply voltage of  24VDC the voltage at point B is 24VDC and the voltage at point A is 24VDC minus 5VDC  20  mA x 250 Ohms  or 19VDC           NOTE  The LOAD cannot be connected to ground in any wiring configuration for the analog             output   A B  P5   A
71. tter is in offline mode  the only valid mode change is to online mode   Note  This register is cleared when the power  is lost to the transmitter  The transmitter always  starts in online mode  If power is lost while in  either calibration or offline mode the transmitter  may report incorrect measurement values   Should this occur put the GFC in offline mode  and write a valid DP Damping value  The GFC  will now need to be returned to online mode to  complete the recovery     40207     40208  Float Read Write  1  user defined display value  These registers hold the floating point value that  will be included in the display cycle if the bit to  display the 1  user defined data set is turned on  in the Display Control register  Only values  between    9999 and 99999 can be displayed   Any value outside of that range will be replaced    5 dashes  on the display     40209 40215  ASCII   Read Write  1  user defined display text  These registers hold the text that will be  included in the display cycle if the bit to display  the 1  user defined data set is turned on in the  Display Control register  Each register holds 2  ASCII characters  The first 7 ASCII characters  will be displayed on line 2 of the display   followed by the second 7 ASCII characters  The  Table 4 Display Module ASCII Characters  table below lists the displayable characters    40216     40217  Float Read Write  2    user defined display value  These registers hold the floating point value that  will be included
72. ud rate is higher and the network is longer     When termination resistors are required  they are installed on the first and last station on the RS 485  wire pair  All other stations should not have termination resistors     SCADASense 4203 DR  Installation and User Manual 27  October 19  2007       RS 485 networks are generally terminated with 120 ohm resistors on each end  The required 120   ohm resistor must be supplied and installed by the user  When using termination resistors it is  necessary to increase the line biasing by adding lower value bias resistors in order to generate at  least 0 2V across RS 485 line  The suggested value of the bias resistors is 470 ohms  One bias  resistor is installed from the RS 485 line B    to COM  The second bias resistor is installed from the  RS 485 line A  to  5V   5V is not available on the transmitter but may be available on another  device on the RS 485 network     4 2 4 COM2 RS 485 Serial Port Settings    The following table shows the serial and protocol communication parameters supported by COM2   These parameters are set from TelePACE  ISaGRAF Workbench or from an application program  running in the controller  Default values are set when a Cold Boot or Service Boot is performed on  the controller     Baud Rate 300  600  1200  2400  4800  9600  19200  38400  57600  and 115200  Default  9600   Duplex Full and Half  Default  Half   Odd  None or Even Default  None   Data Bits 7 or 8 Bits Default  8 Bits   Stop Bits 1 or 2 Bits Def
73. um  up to 121   C  250   F     9 12 Transmitter Temperature Specifications    Sensor Body    Reference conditions 24    2 0 C  75 4    0 F   Normal operating conditions  29 to 82 o C   20 to 180 o F   Operative limits  46 to 121 o C   50 to 250 o F   Storage and transportation limits N A    Sensor Electronics    Reference conditions 24    2 0 C  75 4    0 F    Normal operating conditions  29 to 82 o C   20 to 180 o F    Operative limits  40 to 85 o C   40 to 185 o F    Storage and transportation limits  54 to 85 o C   65 to 185 o F    LCD Display   Reference conditions 24    2 0 C  75 4    0 F    SCADASense 4203 DR  Installation and User Manual 61    October 19  2007    Normal operating conditions  29 to 82 o C  20 to 180 o F   Operative limits  29 to 85 o C   20 to 185 o F   Storage and transportation limits  54 to 85 o C  65 to 185 o F     Although the LCD will not be damaged at any temperature within the Storage and Transportation  Limits updates will be slowed and readability will be decreased at temperatures outside the Normal  Operating Conditions     9 13 Transmitter Performance Specifications    Zero Based Calibrations  Stainless Steel Sensor with Silicone Fluid  Under Reference Operating  Conditions unless otherwise specified  URL Upper Range Limit and Span Calibrated Span    Accuracy   Accuracy stated includes the effects of Linearity  Hysteresis  and Repeatability    Differential and Absolute Pressure   For gauge pressure accuracy  add anticipated variation from us
74. ures gage or absolute pressure   A value of 1 means gage pressure  The gage  pressure is calculated by measuring the  absolute pressure and adding the contents of    SCADASense 4203 DR  Installation and User Manual  October 19  2007       register 40399  The user must set the value in  register 40399 for the gage pressure to be  accurate    A value of 0 means absolute pressure     a0012 40014   TI ee    SSSCSC    d    40015 Integer  Read Write  Baud rate  com2   This register is used to set the baud rate on  Com2 of this transmitter  When the value of  this register changes  the baud rate on Com2 is  changed accordingly   Valid values are   0 75  1 110  2   150  3   300  4   600  5   1200  6   2400  7   4800  8   9600  default   9   19200  10   38400  11   57600  12 115200    40016 Integer  Read Write  Transmitter Address  This register holds the transmitter address  This  information comes from the COM2 station  number  Changing this value also changes the  COM serial port settings to the new Modbus  station number and makes the settings  permanent   40078 40081    40032   40035  ASCII Read Write  Tag name  8 characters   These registers hold the transmitter tag name   The tag name can be up to 8 characters  Two  characters are stored in each register  Valid  values are any ASCII character   40036   40043  ASCII Read Write  Description  16 characters   These registers hold the transmitter description   The description can be up to 16 characters   Two characters are stored in
75. urn   If  cover locks are present  align the serration in the cover with the lock and unscrew the lock until  it extends into the cover serration to prevent unwanted cover rotation     6  Turn on the transmitter power source   3 2 1 1 Write Protect Jumper    The write protect jumper is located to the right of the display connector as shown in figure 3  The  jumper is used to connect two of the three pins on the write protect header     e Connecting the top two pins with the jumper disables the write protection     SCADASense 4203 DR  Installation and User Manual 12  October 19  2007       e Connecting the bottom two pins with the jumper enables the write protection     See the Write Protect Jumper section for information on the effects of the Write Protect jumper     Jumper on top two pins  DISABLES write protection    Jumper on bottom two pins       ENABLES write protection       Lesser  HOUSING ASSEMBLY    WRITE PROTECT JUMPER       TO REMOVE DISPLAY FROM  ELECTRONICS MODULE   TWIST DISPLAY COUNTER   CLOCKWISE TO RELEASE  TABS AND PULL OUT  THEN  UNPLUG CABLE CONNECTOR     Figure 7  Optional Display and Write Protect Jumper    The optional display can be rotated within the housing to any of four positions at 90   increments     To do this  grasp the two tabs on the display and rotate it about 10   in a counterclockwise direction   Pull out the display  Ensure that the O ring is fully seated in its groove in the display housing  Turn  the display to the desired position  rei
76. used connection with metal plug     supplied     2  Process connectors may be removed and connections made directly to process cover using 1 4    NPT internal thread in process cover    3  Process cover can be inverted making optional side vents or side drains    Process connectors can be inverted to give either 51  54  or 57 mm  2 0  2 125  or 2 25 in     center to center distance between high and low pressure connections    5  Topworks can be rotated to any position within one turn counterclockwise of the fully tightened    position    6  Process cover end plugs are substituted for vent screws when optional side vents  Note 3  are    specified    SCADASense 4203 DR  Installation and User Manual  October 19  2007    66    
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
TS・570SG TS・570MG TS・570VG  Troubleshooting for the Online Moderator  Eagle EHCN1 Instructions / Assembly  DI-707P User Manual  Cotek SK200 & SK350 Manual  Series 4000 - Mensor Corporation  Humanscale M8  Dialight LED-Highbay, RD, 756, 146W  User Manual  T rnsformer - 2    Copyright © All rights reserved. 
   Failed to retrieve file