Process Diagnosis ProAgent for OP

image

Contents

1. Configuring and Downloading ALARM_S Messages It is therefore important that the shared database is always up to date during the compilation process and that data synchronization is active see Shared Database with STEP 7 Chapter 6 1 2 ProAgent User s Manual Issue 12 99 7 13 Message Processing 7 5 7 14 Use of Resources ALARM_S messages are configured in STEP 7 The data is then stored in a shared database imported during the process of compiling the ProTool project and finally downloaded to the operating unit That means that ALARM_S messages use up resources on the operating unit The shorter the messages are the less storage space they will require A maximum of 2000 event messages and 2000 alarm messages can be created It is of no consequence in this regard which message procedure is used More detailed instructions can be found in the Appendix Chapter B 1 The appendix contains information about the memory requirement of configurations in the basis of which you can assess whether or not the memory of your operating unit is large enough for the intended configuration Note In STEP 7 there are restrictions regarding the number and size of tags that can be used within a message For more precise details please consult your STEP 7 documentation ProAgent User s Manual Issue 12 99 7 6 Message Processing Communicat
2. Compiling and Downloading ProAgent User s Manual 6 20 Issue 12 99 Configuring in ProTool Note Before starting the compilation process make sure that the database is up to date If you have made any alterations in STEP 7 retranslate the blocks concerned The process of translation updates the database at the same time see Shared Database with STEP 7 Chapter 61 2 Data is only imported from the shared database if synchronization has not been deactivated in ProTool under File Settings Compile Proceed As Follows To compile and transfer the finished project do the following 1 Make sure that under menu option File Settings Compile all options are selected this is not absolutely necessary if no changes have been made ina particular category since the last compilation run 2 Choose the menu option File gt Compile as normal in ProTool 3 As normal in ProTool choose the menu option File Download The diagnosis compatible project is now on the operating unit ProAgent User s Manual Issue 12 99 6 21 Configuring in ProTool 6 1 9 Replacing the Overview Screen Alternative Overview Screen If you are using your system with units programmed in S7 GRAPH you can replace if you wish the normal Overview Screen with the Alternative Overview Screen for S7 GRAPH On it you can see the step names associated with the d
3. Operating unit Stages Involved in Configuring the Process Diagnosis ProAgent User s Manual 3 6 Issue 12 99 Introduction Programming the PLC Depending on the programming language you are using for the PLC the preparations for the process diagnosis will differ as follows e f you are using S7 GRAPH your programs will automatically be capable of diagnosis e f you are programming in LAD CSF STL you need the S7 PDIAG option package S7 PDIAG creates additional blocks for monitoring your process for the purposes of fault detection This is mostly done automatically Thanks to the global nature of S7 process diagnosis you can also work with different programming languages within the same system entirely as circumstances demand You can also detect and locate process faults in mixed sequential and logic control systems Programming the PLC and defining the settings in S7 PDIAG are the first steps in creating the process diagnosis That is followed by configuration of the operating units using ProTool and ProAgent Common Database as Interface When translating the PLC program the STEP 7 option packages store all the data required for the process diagnosis in a shared database ProTool then accesses that database when the operating unit is configured during the next stage Configuring the operating unit Once the STEP 7 program has been created the process di
4. A CPU 315 can process a maximum of 50 simultaneously pending messages Accordingly an operating unit can handle a maximum of four CPU 315s sending ALARM_S messages without overflow problems occurring Updating Since the CPU stores the message information when a fault occurs individual network stations e g an OP can log on at a later date and obtain an update However the CPU only stores information about pending messages Once all events arrival departure acknowledgement have occurred the message is deleted from the CPU When obtaining an update therefore the operating unit processes any missing events automatically if a message is not known to the PLC but the arrival and acknowledgement events are not entered on the operating unit The events are not entered in the message buffer in that case however Events processed in this way are identified on the operating unit by displaying the message status symbols in inverse type thus 1234567 A Kf HH MM SS DD MM YYYY GRUOO Boiler 13 temperature 190 degrees Inform shift supervisor Tel 007 Automatically Processed Events ProAgent User s Manual Issue 12 99 7 19 Message Processing 7 11 Buffer Overflow Message Archive All message events for event and alarm messages are automatically stored ina message archive The message archive can hold up to 512 message events Overflow Warning When the remaining buffer capacity specif
5. 8 9 Modifying the Diagnosis Screens Adjusting Selecting and Scrolling TP only 8 4 4 If you change the display of the Detail Screen STL you only have to adjust the scroll areas since not every line can be selected individually in these areas Use the mouse to enlarge the corresponding buttons so that the new line s are also covered If you change a diagnosis screen in which the lines or columns can be selected individually that is an Overview Screen Message Screen Movement Screen or Detail Screen LAD you must cover each new line with a new hidden button You can also make this job easier for yourself by simply copying the bottom button and positioning it over the new line All you then have to do is adapt the parameters of the ProAgent Select Screen Element and ProAgent Scroll Display functions configured for the button The simplest way is to look at the parameters of the existing buttons from which you will quickly recognize the basic formula Tip K Use the Display hidden buttons key to display the Selection and Scroll buttons in the diagnosis screens for TP Displaying Symbols and Remarks Detail Screen STL Display Mode Limited Space on C7 626 OP25 OP27 TP27 6 8 10 On the C7 626 OP25 OP27 and TP27 6 either a symbol comment or the absolute address of a statement is displayed on the Detail Screen STL or signal list You can switch between the various display modes by way of an input field
6. Alternative Overview Screen for S7 GRAPH As Shown on OP25 ProAgent User s Manual 5 28 Issue 12 99 5 4 5 4 1 Display 5 4 2 Display on the Operating Unit Step Screen What is the Step Screen Used for The step screen shows the unit selected on the overview screen from which you opened the step screen together with its name and the current step with number and name If the unit was programmed with S7 GRAPH you can activate a certain step in the sequence of steps or deactivate one or all steps to obtain certain processes specifically for diagnostic purposes If the unit was programmed with S7 PDIAG a system message is issued Since steps cannot be defined with STL and LAD together with S7 PDIAG you can indeed see the step screen but cannot set or reset steps What You See on the Step Screen General Layout Like all the diagnosis screens the step screen has a standardized layout There are only minor differences between the various types of operating units The illustration below shows an example of the step screen as it appears on an OP25 909p pp Y Unit DB13 C belt 1 Ol ni onveyor be Lo 2 Step oo 12 Start conveyor belt Para 12 13 5 18 2 14 7 pO Mode Man O step no 1 Step name Start conveyor belt Step Screen As Shown on OP25 Note that no display appears in areas 1 2 and 6 through 11 if the selected unit was programmed with S7 PDIAG Steps ca
7. Message Processing Advantages of ALARM_S As compared with the message bit procedure ALARM_S has the following advantages e ALARM S is an active message procedure When a message is issued the CPU actively notifies all networked units The operating unit is relieved of the task of continually polling the message area e The process data always precisely reflects the situation at the time of the message This can not be guaranteed with the message bit procedure The time stamp precisely indicates when an event occurred even if the operating unit is not connected until a later time Display Classes Priorities 7 2 The individual messages can be assigned different display classes in STEP 7 When configuring in ProTool you then can then choose a specific selection of display classes for an operating unit In that way you can distribute the messages selectively between different display units You can assign the messages different priorities when configuring ALARM S messages as well The priorities are handled in precisely the same way as you are familiar with from the message bit procedure For more precise details please consult your ProTool documentation Tip Make sure that you assign messages that can bring about consequential errors a higher priority than the consequential errors Tip After additional configuration of a suitable filter on the message screen refer to Defining filter criteria message screen Chapte
8. Swaziland Siemens Pty Ltd e Mbabane Tanzania Tanzania Electrical Services Ltd e Dar es Salaam Tunesia Sitelec S A e Tunis Zaire SOFAMATEL S P R L Kinshasa The following table lists all Siemens Companies and Representatives of Siemens AG in America Argentina Siemens S A Bah a Blanca Buenos Aires C rdoba Mendoza e Rosario Bolivia Sociedad Comercial Industrial Hansa Ltda aPaz Brazil Siemens S A Bel m Belo Horizonte Brasilia e Campinas Curitiba Fortaleza e P rto Alegre Recife Rio de Janeiro e Salvador de Bahia e Sado Paulo e Vit ria Canada Siemens Electric Ltd Montreal Qu bec Toronto Chile INGELSAC Santiago de Chile Colombia Siemens S A Barranquilla Bogot Cali Medell n Costa Rica Siemens S A Panama e San Jos Cuba Respresentaci n Consult iva EUMEDA LaHabana D 5 Siemens worldwide Asia D 6 Ecuador Siemens S A Quito El Salvador Siemens S A e San Salvador Guatemala Siemens S A Ciudad de Guatemala Honduras Representaciones Electroindustriales S de R L Relectro Tegucigalpa Mexico Siemens S A de CV Culiac n G mez Palacio Guadalajara Le n M xico D F Monterrey Puebla Nicaragua Siemens S A Managua Paraguay Rieder amp Cia S A C I e Asunci n Peru Siemsa Lima United States of A
9. System messages System requirements T Target groups Target system ProAgent Terms 3 9 TP Transition Changing on detail screen LAD Changing on detail screen STL switch to Detail Screen Signal List Transitions Translation 8 17 Types of direct key U UDT Uninstalling ProAgent Unit Could not be acknowledged Selecting during configuration Was acknowledged Unit acknowledgement 8 18 Units Displaying all 5 26 Displaying faulty Hierarchical in movement screen Hierarchical on overview screen Updating Upgrade diagnosis screens 6 27 Steps Upgrade to new diagnosis screens 6 27 Upgrading Requirements Use of resources Using password levels W Weitere Unterst tzung ProAgent User s Manual Issue 12 99
10. Display more units simultaneously on the overview screen ZP_UNITS or ZP_UNITS_S7G Show more instructions simultaneously in the detail screen in signal list and STL format ZP_DETAILSYM und ZP_DETAILAWL Display more switches at once on the Detail Screen in LAD display mode ZP_DETAILLAD Delete the last movement on the Movement Screen ZP_MOTION if you want to use the soft keys for different functions ProAgent User s Manual Issue 12 99 Modifying the Diagnosis Screens Copy Existing Lines The simplest method is to copy an existing line to the Clipboard and paste a new copy at the new position You should always copy the bottom line The necessary modifications are then simpler to perform because most values merely need to be increased by one increment Start Values You must inform ProAgent how many lines and columns there are on the screen concerned This is done by means of the start value of specific tags If you have added or removed lines therefore you must also change the start values of those tags A list of the tags involved is given in the chapter Internal Structure of the Diagnosis Screens Chapter 8 2 Setting Tag Indices All input output fields that you add must be linked to the correct tags and those in turn to the correct tag indices in order that they can be supplied with the correct data when the system is running To do so you configure the function ProAgent Set Tag Index for the tags concerned For
11. Display on the Operating Unit Modifying the View Options There are a number of ways in which you can adapt the view options to suit your personal preferences ef If you want to be able to view all signals i e including those that have not led to a fault press this key see Toggling Between Partial and Full View LAD Chapter 5 6 4 4 If you wish you can have the current status bits displayed instead of the displayed initial values status bits at the time the error occurred To do so use this key see Toggling Display of Initial Values and Current Status LAD Chapter 5 6 4 5 A Device specific If you wish to view the symbols and remarks relating to the individual instructions use the ENTER key to open the corresponding list box see Toggling Display of Symbol and Remarks LAD Chapter B On a TP you open this same list by touching the corresponding input output field Exiting the Detail Screen ha This key returns you to the screen from which you activated the Detail Screen 5 6 4 4 Toggling Between Partial and Full View LAD Format You can choose whether to e view all instructions of the network displayed full view or e view only those instructions that have set the monitored signal to the incorrect status partial view P To toggle between the two display modes use the this key Za When partial view is active this symbol appears above the ladder diagram
12. Partial view is particularly useful if you want to be able to quickly locate the critical instructions that have resulted in the issue of an alarm message If you project does not specify otherwise partial view is automatically selected when the screen is selected ProAgent User s Manual 5 70 Issue 12 99 5 6 4 5 5 6 4 6 Display on the Operating Unit Toggling Between Initial Values and Current Status LAD The default setting is for display of the status as it was at the time the fault monitoring routine first detected the process fault For that reason those values are also referred to as initial values Those values are accordingly also the basis for the results of logical operations In addition you can also inquire the current status Viewing the current status allows you to monitor online what effect corrective measures have on the condition of the system If you have set the display mode to partial view see Toggling Between Partial and Full View LAD Format Chapter 5 6 4 4 you can see right away if the fault has been put right In that case no more signals are displayed on the screen ied To toggle display of initial values and current status use this key e When the display mode is set to current status this symbol appears above the statement list Changing the Action or Transition LAD You can easily switch to other faulty actions and transitions by pressing a key Changing Action A unit may ha
13. make a copy of the output field for symbol remarks and insert the copy in the blank line below the original field it is important that you recopy the field for each line and do not insert multiple copies of the same field For each of the output fields both original and copy delete the multiplex functions to do so click the Multiplex button and the two Remove buttons Assign the output fields on the longer lines i e on the lines on which the actual instructions appear the following tags e first line ZP DSYMBOLO e second line ZP DSYMBOL1 e Assign the output fields on the in between lines the following tags e first line ZP DCOMMENTO e second line ZP DCOMMENT 1 If you have changed the length width of the output fields you must also change the length of the tags ZP DSYMBOLO ZP DSYMBOLX and ZP_DCOMMENTO ZP DCOMMENTX to match the new field lengths ProAgent User s Manual Issue 12 99 8 11 Modifying the Diagnosis Screens 8 4 5 8 For TP only Check whether the Scroll buttons still match the new layout of the display If necessary adjust the size of the touch areas When the system is running the symbols will now appear on the operating unit on the full width lines and the remarks on the in between lines Switching Over SIMATIC IEC Display Mode Detail Screen The SIMATIC display mode is used for commands operands and operators in the Signal List ZP_DETAILSYM STL ZP DETAILAWL and LAD ZP
14. Considerations When Upgrading an Existing Project 6 2 1 Requirements of PLC Program and Project when Upgrading 6 2 2 Overview of the Steps Required when Upgrading 6 2 3 Upgrading Existing Projects to New Diagnosis Screens 6 2 4 Message Window and Message Screen 6 28 7 Message Processing 7 1 Message Number Procedure ALARM S 7 2 Display Classes 7 3 Configuring ALARM S Messages 7 6 7 4 Incorporating ALARM S Messages 7 13 7 5 Use of Resources 7 14 7 6 Communication Sequence 7 15 7 7 Message Acknowledgement 7 8 Printing Messages 7 9 Message Overload 7 10 Updating 7 11 Buffer Overflow is m o ProAgent User s Manual Issue 12 99 iii Contents 8 Modifying the Diagnosis Screens 8 1 8 1 Modifying the Diagnosis Screens Introduction 8 2 Internal Structure of the Diagnosis Screens 8 3 Internal Nomenclature 8 4 Modifying Design and Information Content 8 4 1 Modifying the Design 8 4 2 Change Font Size and Font 8 4 3 Adding or Removing Lines 8 4 4 Displaying Symbols and Remarks Detail Screen STL Display Mode 8 4 5 Switching Over SIMATIC IEC Display Mode Detail Screen 8 4 6 Changing the Mode of Enabling Movements Movement Screen 8 4 7 Changing the Number of Target Positions Movement Screen 8 4 8 Defining Filter Criteria Message Screen 8 4 9 Defining Operating Modes Overview Screen 8 5 Using Additional Functions 8 5 1 Working with Password Levels 8 5 2 Multi Language Projects 8 5 3 Configuring a Unit Acknowledgement
15. DETAILLAD detail screens If you prefer the international IEC display mode you can change this setting by configuring the ProAgent Switch Over SIMATIC IEC function with an appropriate parameter for the Detail Screen in question If this function is not configured for a Detail Screen the SIMATIC display mode will automatically be used for German while the IEC display mode will be used for all other languages Proceed As Follows 8 4 6 To switch the display mode over from SIMATIC to IEC 1 Click the right mouse button in the Detail Screen in question and select Properties Functions 2 In the function group ProAgent select the function ProAgent Switch Over SIMATIC IEC 3 Under Parameters set Mode 1 IEC display mode 4 Under Conditions select the condition Select Screen All commands and operands will now be displayed in IEC display mode in the Detail Screen in question Changing the Mode of Enabling Movements Movement Screen Default Setting in the Diagnosis Screens 8 12 All the movements displayed in the Diagnosis Screens for OPs can be triggered by means of soft keys In the case of a TP safety reasons dictate that you can normally only trigger a movement manually if it has been selected beforehand Movements that have not been selected are disabled ProAgent User s Manual Issue 12 99 Modifying the Diagnosis Screens Changing the Default Setting You can switch over this default setting
16. Diagnosis ProAgent User s Manual Issue 12 99 3 1 Introduction Avoiding Problems Many problems can be avoided from the outset The flexibility of the process diagnosis system enables potential problems in the process sequence to be identified before they actually occur A worn tool for example is normally signaled by an increase in the forces involved The process diagnosis system can monitor those forces and initiate replacement of the tool at the appropriate time Identifying Problems Problems can still be identified without a process diagnosis The SIMATIC operating units allow you to visualize installations that is display them and to control them with ease A powerful message system draws your attention to process faults An error message appears on the operating unit as an indication Rectifying Problems 3 2 Situation relevant information assists you in locating the fault When problems occur in the process sequence you can easily retrace the faults to the units from which they originate To do so you can examine on the operating unit the logical operation results in the statement list or ladder diagram You don t have to connect up a PU And the fault can be located just as quickly You can quickly remedy the problem You can selectively initiate movements on the operating unit to remedy the problem If a number of installation components have been damaged this is indicated on the operating unit and you
17. Iceland Smith amp Norland H F Reykjavik Ireland Siemens Ltd e Dublin ProAgent User s Manual Issue 12 99 ProAgent User s Manual Italy Siemens S p A Bari Bologna Brescia Casoria Firenze Genova Milano e Padova Roma e Torino Luxemburg Siemens S A Luxembourg Malta J R Darmanin amp Co Ltd Valletta Netherlands Siemens Nederland N V Den Haag e Rijswijk Norway Siemens A S Bergen e Oslo Stavanger e Trondheim Poland Siemens GmbH Gdansk Letnica e Katowice Warszawa Portugal Siemens S A e Albufeira Coimbra e Lisboa Amadora e Matosinhos e Porto Siemens worldwide Romania Siemens birou de consultatii tehnice Bucuresti Russia Siemens AG oppure Mosmatic Moskau Siemens AG Ekaterinburg Slovak Republic Siemens AG e Bratislava Slovenia Siemens d o o Ljubljana Spain Siemens S A Barcelona Bilbao e Gij n e Granada La Coru a Las Palmas de Gran Canaria Le n Madrid M laga Murcia e Palma de Mallorca Pamplona e Sevilla Valencia e Valladolid Vigo Zaragoza Sweden Siemens AB e G teborg e J nk ping Malm e Sundsvall Upplands V sby Stockholm D 3 Siemens worldwide Non European Companies and Re presentatives Africa D 4 Switzerland Siemens Albis AG Basel Bern Z rich Siemens Albis S A e Rene
18. Messages A 3 Detail Screen System Messages A 3 1 No Faulty Unit Selected Message Number Cause Remedy This message appears when the Detail Screen is opened if e the Detail Screen is called up from the Message Screen but the selected unit is not diagnosable the Detail Screen is called up from a blank Overview Screen the Detail Screen is called up from the Overview Screen but none of the steps has a fault if PLC programmed in S7 GRAPH a communication fault or temporary shortage of memory has occurred A 3 2 No Faulty Action Present Message Number Cause Remedy 4042 This message appears when the Detail Screen is opened if e the Detail Screen is called up from the Message Screen but the fault has since departed again the Detail Screen is called up from the Overview Screen but the selected unit does not have a fault the function ProAgent Change Action has been used to change to the unit with a fault but there are no more actions a communication fault or temporary shortage of memory has occurred ProAgent User s Manual A 6 Issue 12 99 Appendix System Messages A 3 3 Error Identifying Transitions in Fault Mode Message Number Cause Remedy 4043 It has not been possible to read from the PLC which transition was taking place at the time of occurrence of the fault This message can only appear in the case of PLCs whose program is written in S7 HiGraph The cause is generally a communication fau
19. Movement screen Change number of limits Design Direct keys Hierarchical units Keys Purpose Use in practice Movements 3 9 Multilingual projects Multiple Assignments N Name conventions No acknowledgeable unit selected No current unit selected No diagnosable units present No faulty action present No faulty unit selected No S7 GRAPH selected No valid step selected Not enough memory available for process diagnosis Not enough memory for display in fault mode O OB Online Help OP Operating mode Changing on overview screen Operating modes Changing on step screen 5 32 8 16 Define on overview screen Operating principles of diagnosis screens 5 10 0 Operating unit ProAgent User s Manual Issue 12 99 Overview screen 5 9 Changing display Define cei modes Design For S7 GRAPH Hierarchical units Keys Practical procedure Purpose Replacing 6 22 P PC 1 5 Performance capabilities of process diagnosis PLC Selecting PLC ecina 645 Porting to computer without STEP 7 Printing ALARM S messages ProAgent Functions Menu item Procedure for process diagnosis Process diagnosis Configuring Enable Performing ProTool additional menu items due to ProAgent PU R Reference dasa 5 73 remark 5 5 53 5 63 5 73 Display i in El Screen STL Display on detail screen LAD Display on detail screen STL Removing lines from diagnosis screens Requirements For the PLC prog
20. PLC is programmed either in STEP 7 STL or LAD or in S7 GRAPH e Ifyou are using LAD CSF STL you will need the S7 PDIAG options pack S7 PDIAG allows you to extend the PLC program so that individual signals such as for the status of inputs outputs markers etc are monitored e f you are using S7 GRAPH the PLC programs are automatically diagnosable without having to use an additional options pack The currently active steps are always monitored Monitoring functions are available across the whole sequence and are integrated in the sequence blocks Only if you wish to trigger movements for S7 GRAPH units will you need the S7 PDIAG options pack as well The procedure for programming the PLC and the particular aspects to be considered when doing so are explained in the documentation for S7 PDIAG and or S7 GRAPH ProAgent User s Manual Issue 12 99 6 1 Configuring in ProTool Points to Bear in Mind The PLC program must work correctly When working with S7 PDIAG make sure that the fault detection FB is invoked in OB1 the program contains no loops as the fault detection FB is invoked only once per cycle fault detection has been activated for the individual fault monitoring routines initial value detection has been activated for the individual monitoring routines if you want to use the Detail Screen the UDT Movement has been used if you want to use the Movement Screen The UDT Movement creates a standardized interface with
21. ProAgent User s Manual Issue 12 99 5 75 Display on the Operating Unit 5 6 5 4 Exclusion Operands What are Exclusion Operands Example 5 76 The criteria analysis treats all operands equally This might result in subnetworks being identified as faulty that are jointly responsible for the error strictly according to the logic but being capable of exclusion as the cause of the error with the help of additional knowledge One example is the different system operating modes which by definition can never occur simultaneously on a unit or individual operands for different product versions which similarly cannot be produced simultaneously For this reason S7 PDIAG features the option of defining exclusion operands on alist ProAgent then only marks signals on a network as faulty on which the exclusion operand is detected with a value not equal to 0 The following example illustrates operand monitoring from A 1 0 to 0 status with the two operating modes Auto and Manual Without exclusion operands RLO Status U Auto 1 1 U 10 0 0 0 0 0 1 U Manual 0 0 A U 101 0 0 A 01 0 0 0 1 Exclusion operands R Status U Auto 1 1 U 10 0 0 0 0 1 U Manual 0 0 U 101 0 0 5 010 0 0 Example of Exclusion Operands ProAgent User s Manual Issue 12 99 Display on the Operating Unit From a strictly logical point of view the marking of the faulty lines in the upper section of the program is correct T
22. Start M r TT d Number 13 14 15 17 mM bero m IS FEU S Sumbal Detail Screen example of STL format on an OP25 programmed with S7 PDIAG 4 This field displays the text Netw for the network selected 5 This field displays the number of the network displayed 6 This field displays the name of the network displayed ProAgent User s Manual Issue 12 99 5 55 Display on the Operating Unit 7 This field displays the module in which the network was configured 8 This field displays the text Number for Network Number 9 This field displays the network numbers of networks that set the same operand Line 4 of the display remains blank when the unit is programmed with S7 PDIAG There are no differences between programming with S7 GRAPH and with S7 PDIAG with regard to the remaining areas of the Detail Screen Changing the Display Mode 12 In this input output field you can see or specify whether symbols or remarks relating to the individual instructions are to be shown at 17 Representation of the Network The center section of the screen shows an excerpt from the program code for the network with the fault The instructions which have led to the issue of an alarm message are highlighted Specifically you are shown the following 13 The operators If SIMATIC display mode is set the SIMATIC names are displayed otherwise the international IEC names are shown see Switching Over SIMATIC IEC Display Mo
23. are separated by arrows The complete route to the menu option in question is always shown Names of dialog boxes input boxes and buttons appear in italics ProAgent User s Manual Issue 12 99 1 5 ProAgent User s Manual Issue 12 99 Preface Abbreviations The abbreviations used in this documentation stand for the following AM CPU DB EM FB FC HMI LAD MPI OB OP PC PLC PU RLO STL TP UDT Alarm message Central processing unit Data block Event message Function block Function Human machine interface Ladder diagram Multipoint interface Organization block Operator panel Personal computer Programmable logic control Programming unit Result of logical operation Statement list Touch panel User defined data type Preface 1 6 Other Sources of Assistance SIMATIC Customer Support Hotline Available round the globe 24 hours a day Telephone 49 911 895 7000 Fax 49 911 895 7002 Simatic Basic Hotline through 5 p m Telephone 1 423 461 2522 Fax 1 423 461 2231 Nuremberg Johnson City Singapore SIMATIC BASIC Hotline SIMATIC BASIC SIMATIC BASIC Hotline Hotline Local time Local time Local time Mo Fr 8 a m through 6 p m Mo Fr 8 a m Mo Fr 8 30 a m through 5 30 p m Telephone 65 740 7000 Fax 65 740 7001 e mail simatic support e mail e mail nbgm siemens de simatic hotline simatic sea siemens com SIMA
24. at the time of occurrence of the fault initial values or the current values See Toggling Display of Initial Values and Current Status STL Chapter 5 6 3 5 You use this key to change to the next error in other words to the next faulty action of this unit refer to Changing the Action or Transition STL Chapter 5 6 3 6 With units programmed with S7 GRAPH and using movement blocks created with S7 PDIAG the change is made initially to all other transitions and then to the movement blocks ProAgent User s Manual Issue 12 99 5 57 Display on the Operating Unit You use this key to change within an error The change is normally to the next transition see Changing the Action or Transition STL Chapter 5 6 3 6 In the case of Multiple Assignments to a monitored operand the change is to the next network containing an assignment to that operand This key is used to change the display to LAD format see What You See on the Detail Screen LAD Format Chapter 5 6 4 1 This key is used to return to the screen from which you opened the STL Display Keys Used with Detail Screen in STL Display Mode 5 6 3 3 How to Work with the Detail Screen STL This chapter gives a general outline of how to use the Detail Screen STL in practice Aims You have opened the Detail Screen in order to see which instructions in the program have resulted in a particular alarm message By doing so you can tell which monitori
25. description of the Message Screen is given in the chapter Message Screen Chapte ProAgent User s Manual 5 4 Issue 12 99 Display on the Operating Unit Overview Screen Units where there are faults Unit DB13 Conveyor belt 1 Step 1 Start conveyor belt Para 12 13 5 if 2 14 7 P Mode Man b A Action Mode 5 Auto 3 Auto AConveyor belt 7 7 Auto Weld door panel 15 Auto Weld door hinge 18 Auto Paint Auto Overview Screen As Shown on OP25 The Overview Screen shows all the units present in your system This shows you at a glance the current operating mode and condition of each individual unit Blocked units are identified as such Once a fault has been rectified the marker disappears again A detailed description of the Overview Screen is given in the chapter Overview Screen Chapter 5 3 If your system contains units programmed with S7 GRAPH you can use a slightly modified overview screen as an alternative refer to Alternative Overview Screen for S7 GRAPH Chapter 5 3 7 ProAgent User s Manual Issue 12 99 5 5 Display on the Operating Unit Step Screen Set step Input of step number Reset step Unit DB13 Conveyor bel Sie 12 Start conveyor felt Pard 12 13 f l4 7 P Mod Man gtep no 12 tep name Start conveyor belt Step Screen As Shown on OP25 If your system has units that were programmed in S7 GRAPH you can operate a S7 GR
26. diagnosis screens from the existing screens Normally a function for selecting the Diagnosis Start Screen is entirely adequate Conversely you must provide a means of returning from the diagnosis screens to your own screens The simplest way of doing this is to configure an appropriate screen selection function on the Diagnosis Start Screen The remaining steps are the same as for creating a new project i e 3 Selecting the Units 4 Selecting the display classes You can use ALARM_S alongside the message bit procedure if your existing project still uses the message bit procedure 5 Compiling and Downloading Special Considerations The Message Screen can only be selected by means of the Select Screen function The functions Change EM Page Buffer and Change AM Page Buffer should no longer be used Since the extended functions provided by the diagnosis Message Screen offer considerably more powerful capabilities in any case it is better to use the diagnosis Message Screen in the first place You should modify the configuration of your keys accordingly ProAgent User s Manual 6 26 Issue 12 99 Configuring in ProTool 6 2 3 Upgrading Existing Projects to New Diagnosis Screens The latest version of ProAgent also contains new standard diagnosis screens for which new ProAgent functions have been used during configuration To ensure you have the full functionality at your disposal you must use these new standard diagnosis scre
27. diagnosis screens require the whole of the operating unit screen area If your project uses the Fixed Window it will hide important parts of the diagnosis screens and prevent you from using some of the diagnosis screen functions For that reason you should deactivate the Fixed Window and move its contents to another screen Alternatively you can modify the diagnosis screen accordingly see Modifying the Diagnosis Screens Chapter 8 Uniform Design 6 24 Information on how you can modify the diagnosis screens so that they are visually in harmony with the rest of your system configuration is also given in the chapter Modifying the Diagnosis Screens Chapter 8 ProAgent User s Manual Issue 12 99 6 2 2 Overview Configuring in ProTool Overview of the Steps Required when Upgrading Upgrading an existing project to include process diagnosis is not significantly different from the process of creating a new project with diagnosis capability The diagram below shows the steps required in chronological order Add monitoring routines Configure messages Translate program NT Incorporate the diagnosis screens Link the diagnosis screens Select displayed messages Compile and download Configuration Steps Involved in Upgrading a Configuration to Include Process Diagnosis Tip A special breakdown of the steps required when creating a new project with diagnosis capability is given in the cha
28. guidance notes given in the chapter Adding or Removing Lines Chapter 8 4 3 ProAgent User s Manual Issue 12 99 8 7 Modifying the Diagnosis Screens 4 Select the text to which you wish to assign the new font 5 Choose the Edit Fonts from the menu and select the font you require All previously selected text is now shown in the new font If you subsequently create new text fields the new font will also be used for them Note for TPs Use at least font size 8x16 or better still a font with the height 32 If you don t the text elements will be too small for you to be able to select them If you have reduced the font size you can join lines together and add extra lines to the diagnosis screens When doing so be certain to follow the guidance notes given in the chapter Adding or Removing Lines Chapte 8 4 3 Tip You can modify several text elements at once by holding down the Shift key and selecting all the elements you wish to change When you have selected all the text elements you wish to change you then select the new font and assign it collectively 8 4 3 Adding or Removing Lines Basic Requirements Before you add extra lines to a diagnosis screen you normally first have to reduce the font size see Changing the Font Size and Font Chapter 8 4 2 Or you must delete individual screen elements that you do not require Options Depending on the diagnosis screen involved you can do the following 8 8
29. in Field 11 If no operating mode is defined in the STEP 7 program or the operating mode display is hidden the field 4 remains empty An operating mode cannot be set in this case 5b If there are more units than can be displayed in the list at one time the arrow down and arrow up symbols appear In that case you can then scroll the list up or down 6 If hierarchically lower order or high order units exist for the unit selected the arrow right and arrow left symbols appear In that case you can switch to another hierarchical level see Hierarchical Units on the Overview Screen Chapter 5 3 6 7 A warning triangle appears here if the display mode selected is such that the cursor moves directly from one unit with a fault to the next unit with a fault Units without faults are displayed but can not be selected see Changing the Display Mode Chapter 5 3 5 Information on the Selected Unit The top section of the display shows detailed information relating to the unit selected by the cursor 8 This shows the block type of the selected unit i e FC DB or OB 9 This field shows the block number of the selected unit 10 At this point text assigned to the unit appears the symbol for a block or an absolute identifier 11 Here you can specify the operating mode of the selected unit The operating modes that are possible depend on how the unit has been programmed If the STEP 7 program does not define an operating mo
30. line shows the user number of the active step and an associated text On the third line you will see the transitions belonging to each step The transition to which the program code displayed belongs is highlighted in inverse type The fourth line shows the name of that transition Which Network In S7 PDIAG units the second line shows the number and the name of the network displayed On the third line the wording Number appears and on the fourth line the network numbers of networks appear that set the same operand Changing Display Mode i If you prefer to see the information displayed in STL format you can use this key to switch from Signal List to STL display mode If you then press the corresponding key again the LAD mode will be displayed If you then press the corresponding key again the display will return to the Signal List mode The icon on the key always indicates the mode that will be shown next Deducing Information You can see the individual operands symbols and remarks in the signal list a All operands that have led to the issue of an alarm message are identified by this symbol This means you can see right away where your fault monitoring system gave the alarm If you examine the instructions concerned you will quickly be able to locate the cause of the fault Additional Actions Transitions and Networks You use this key to change to the next error in other words to the next fault AT y ac
31. of selected units Process diagnosis can then not be performed on that unit during operation Selecting the display classes ALARM S Message Procedure The process diagnosis requires the ALARM S Message Procedure Only units that use ALARM S can be diagnosed Detailed information about ALARM S is provided in the chapter Message Processing Chapter 7 If you use ProAgent the Alarm S message procedure is preset in ProTool Note You can use ALARM S with the message bit procedure If you have selected only ALARM S as the message system for a project in ProTool the Editors window no longer offers the event and alarm messages options ProAgent User s Manual Issue 12 99 Configuring in ProTool Once the ALARM_S message procedure is activated all messages are automatically displayed on the operating unit If you don t want this you can set in ProTool the messages from which units and which display classes to be displayed at the operating unit The display classes Chapter 7 2 were defined when programming the PLC in STEP 7 This involves specifying for each message the display class to which it belongs You will normally limit the number of messages by selecting the units You can restrict the messages displayed on the operating unit to very specific messages by targeted selection of specific display classes As well as the selection of messages by display classes you will also normally make the selection of messages depende
32. only issue ALARM S messages These ALARM S messages are accessed during configuration of a process diagnosis Installing ProAgent Pro automatically activates the ALARM S message procedure in ProTool You can use ALARM S in parallel with the previously used message bit procedure e g to continue using existing projects In this case you must also activate this message procedure in the Message Settings dialog box which can be opened with the menu item Target System Messages Settings What is ALARM S ALARM S is a message number procedure The message numbers are issued automatically during the configuration process in STEP 7 The numbers are used as the basis for assignment of the correct message text The individual messages can be assigned different display classes When configuring you then can then choose a specific selection of display classes for an operating unit In that way you can distribute the messages selectively between display units When a fault occurs the CPU transmits not only the status of the message arrived departed acknowledged but also the time Changes as a Result of ALARM S Using the ALARM S message number procedure initiates the following changes e The messages are no longer configured in ProTool but beforehand when programming the PLC in STEP 7 You also assign a display class to each message at that point e The message screen display marks diagnosable messages by an asterisk before the me
33. overview screen that had been programmed in S7 GRAPH The step screen is indeed displayed but a step number cannot be entered Go back to the overview screen and select a suitable unit ProAgent User s Manual A 10 Issue 12 99 Appendix System Limits B Overview B 1 The appendix contains information about the memory requirement of projects in the basis of which you can assess whether or not the memory of your operating unit is large enough for the intended configuration On the basis of a concrete example you are shown how the memory requirement for a project is determined This will then enable you to apply this knowledge to your own projects System Limits Introduction Whether or nor your diagnosis project runs on the operating unit being used depends among other things on how much memory space the diagnosis requires In this context you have to take two system limits into account e First of all you have to ensure that the diagnosis structures do not exceed a specified total number and do not exceed a size of 64 kbytes This limit applies to all operating units e Another system limit concerns the size of the DRAM available In the case of an OP 25 this is for example only 2 Mbytes of which the operating system requires 1 Mbyte This leaves just 1 Mbyte for configurations Tip The precise technical data of the operating unit you are using can be found in the Appendix of the respective equipment manual It i
34. precise details refer to the chapter Internal Structure of the Diagnosis Screens Chapter 8 2 Dynamic Attributes Many input output fields use dynamic attributes to control display of inverse type or flashing characters Those attributes are set via a control tag that must be linked to the correct tag indices in order that they can be supplied with the correct data when the system is running You must set the values for the dynamic attributes accordingly for every field on every line and make sure that the correct control tag is assigned The simplest way is to look at the values of the dynamic attributes of existing fields from which you will quickly recognize the basic formula Showing Hiding Lines If when the system is running not all lines are required for display of data those lines should appear blank On the Overview Screen ZP UNITS for example this will be the case if there are only a few units in your system The lines concerned then remain blank The showing hiding of lines is controlled by the value of a tag On the Overview Screen for example this is the tag ZP UROWS ON When the system is running the value of that tag corresponds to the number of lines to be displayed You must set the value for hiding accordingly for every field on every line The simplest way is to look at the settings for hiding the existing lines from which you will quickly recognize the basic formula ProAgent User s Manual Issue 12 99
35. that you can also modify or add to the diagnosis screens supplied and thus seamlessly integrate them in your systems You will find essential information about how to do so in the chapter Modifying the Diagnosis Screens Chapter 8 Integrated Operation Step One Note ProAgent requires that ProTool has been installed integral with STEP 7 If you have only been using ProTool as a stand alone product up to now please first consult your ProToo User s Guide for details of working with integrated operation ProTool Standard Project If you would like to create a new diagnosable project proceed exactly as you would with a ProTool project You begin by opening one of the standard projects supplied To do this select the corresponding option box in the project wizard and the standard screens are integrated automatically A precise description can be found in the User s Guide entitled Configuring ProTool Graphics Displays ProAgent User s Manual Issue 12 99 6 9 Configuring in ProTool Step Two Step Three 6 10 Deactivating the Fixed Window In the ProTool standard project the fixed window is activated However this moves essential elements of the diagnosis screens and must therefore be disabled It may be necessary to move the contents of the Fixed Window to one or more other screens To deactivate the fixed window proceed as follows 1 In ProTool choose System Screen Keys and deselect the box next to Fixed Win
36. the Movement Screen Always make sure that if you are working with more than one language that the languages to be selected and configured in ProTool have definitely been configured in the PLC program if you are working in one language only that the same language has been used in the PLC program as is to be used to configure the operating unit the PLC program has been translated Message Text 6 2 As part of the process of programming the PLC you define the text of messages that will subsequently appear on the operating unit as alarm messages In other words the text of diagnosable messages is not entered in the Message Editor in ProTool as would normally be the case but in STEP 7 ProAgent User s Manual Issue 12 99 Configuring in ProTool 6 1 2 Shared Database with STEP 7 Accessing the Database STEP 7 and its option packages store all the data required for the process diagnosis in a shared database S7 PDIAG S7 GRAPH Shared database ProAgent Shared Database ProTool accesses the required information about the PLCs present from that database i e e which units are diagnosable e which signals are monitored for which statuses e which display classes have been defined e which message texts have been defined Updating the Database The database is always updated whenever a monitoring block is retranslated in STEP 7 You must be take account of this relationship Note The databa
37. you have to keep touching the screen until scrolling is activated depends on the repeat time set menu item System Functions Initialization gt Functions What s more the following peculiarities apply to the different diagnosis screens gt e Inthe Overview Screen you can use these keys to switch between iq hierarchical units e Inthe Detail Screen LAD you scroll by touching the outermost switch in the scroll direction until scrolling is activated Common Symbols 5 12 Irrespective of the operating unit you are using various graphical symbols are displayed on the screen You have already come across two graphical symbols in connection with cursor control 52 Indicates that you can scroll vertically Indicates that you can scroll horizontally or that hierarchically subordinate superior units can be displayed Indication of Cursor Function Other symbols are used to identify units where there are faults and incorrect logical operation results as follows Identifies a blocked movement or a faulty unit The unit whose fault occurred first chronologically is identified by a flashing symbol aA Denotes a failed operand Indication of Faults ProAgent User s Manual Issue 12 99 Display on the Operating Unit Pictograms identify the keys for selecting diagnosis screens as follows A Symbolizes the Message Screen Symbolizes the Overview Screen Symbolizes the Detail Screen Symbolize
38. 2 Click the key that is to be used for selecting the screen 3 Configure the function ProAgent Analyze Faults as the first function This function must be executed before the screen is selected As the event use the default setting Press Key No parameters are required 4 Next configure the function Select Screen Here too you should use the default setting Press Key as the result Specify the following parameters e the screen name ZP ALARM if you wish to activate the Message Screen e the screen name ZP UNITS if you want to activate the Overview Screen 5 Finally confirm your entries by choosing OK The diagnosis screen concerned can now by accessed directly using the key configured ProAgent User s Manual Issue 12 99 6 1 6 Configuring in ProTool If you access the Message Screen or the Overview Screen directly rather than via the Diagnosis Start Screen you doubtless want the Previous Screen key to take you back to the last screen you were on rather than to the Diagnosis Start Screen On the standard diagnosis screens supplied this key is assigned the function Select Screen with the parameter ZP PROAGENT Change that parameter accordingly so that your own start screen is selected Caution Do not use the Select Previous Screen function As this function only goes one step back and does not have a stack there is a risk of getting stuck in an endless loop Selecting the Units Clarity through Carefu
39. 2 Not Enough Memory for Display in Fault Mode Message Number Cause Remedy 4022 There is not enough memory available on the operating unit to switch to fault mode on the Overview Screen The change of mode is not carried out The standard mode remains active The cause is generally use of large amounts of memory by OEM functions invoked Try the operation again at another time ProAgent User s Manual A 4 Issue 12 99 Appendix System Messages A 2 3 Error Identifying Faulty Units Message Number Cause Remedy 4023 The next unit with a fault could not be identified in fault mode on the Overview Screen The highlight is repositioned on the first unit The cause is generally a communication fault between the operating unit and the PLC In most cases you will receive other system messages which provide more information about the cause of the fault This might be such things as faulty connectors a modified program on the PLC or insufficient memory on the operating unit A 2 4 No Units Capable of Diagnosis Present Message Number Cause Remedy 4024 This message appears when the Overview Screen is opened if there are no diagnosable units on the configured system If necessary modify your PLC program accordingly using one of the STEP 7 language packages translate it and download it to the PLC In ProTool choose the menu option System ProAgent ProAgent User s Manual Issue 12 99 A 5 Appendix System
40. 2 and 3 of the display look as follows Unit E bel Op Network 1 Start d r jun at Number 13 14 15 17 Detail Screen example of signal list format on an OP25 programmed with S7 PDIAG 4 5 6 7 8 9 This field displays the text Netw for the network selected This field displays the number of the network displayed This field displays the name of the network displayed This field displays the module in which the network was configured This field displays the text Number for Network Number 4 S 6 7 8 9 This field displays the network numbers of networks that set the same operand Line 4 of the display remains blank when the unit is programmed with S7 PDIAG There are no differences between programming with S7 GRAPH and with S7 PDIAG with regard to the remaining areas of the Detail Screen Changing the Display Mode 11 In this input output field you can see or specify whether symbols or remarks relating to the individual instructions are to be shown at 13 ProAgent User s Manual 5 46 Issue 12 99 Display on the Operating Unit Representation of the Network The center section of the screen shows an excerpt from the program code for the network with the fault Only the signals that trigger an Alarm Message are shown here Specifically you are shown the following 12 The individual operands If SIMATIC display mode is set the SIMATIC names are displayed otherwise
41. 8 5 4 Moving Directly to the Detail Screen 8 6 Using Direct Keys 8 6 1 Direct Keys Introduction 8 6 2 Configuring Direct Keys TP Movement Screen 8 6 3 Using Direct Keys OP Movement Screen 8 6 4 Important Information About Using Direct Keys A Appendix System Messages B Appendix System Limits C SIMATIC HMI Documentation D Siemens worldwide Hi l Index ProAgent User s Manual iv Issue 12 99 Preface 1 Overview This chapter explains how the manual is organized and where to find what information 1 1 Guide to the Manual Contents This manual provides you with all the information you need to do the following e configure an installation specific process diagnosis e identify a process fault on the operating unit locate the cause of the fault and eliminate it e adapt the standard diagnosis screens to suit your own particular requirements What You are Expected to Know Already This manual assumes that you already have some general experience of configuring with ProTool The information in this manual is therefore restricted to the description of functions and procedures that are part of ProAgent and are not among the standard range of functions provided by ProTool It also assumes that you have a basic knowledge of STEP 7 ProAgent User s Manual Issue 12 99 1 1 Preface Where to Find What The chapters of this manual are arranged by topic as follows e The chapter Installation explains how to install the option
42. 82 86 1997 GRUB x 543971 A K 13 13 27 H2 86 1997 GRUA 8512888 A RG 11 17 28 H2 86 1997 DRUHH Hssembly of electronics workpiece supply interrupted Conveyor belt 1 jammed Press 1 oil pressure too low Message Screen As Shown on OP25 Filtering Out Messages v Select this key in order to gain an overview of all diagnosable messages first of all This hides all messages that are not diagnosable Selecting a Message Before you can perform a process diagnosis for a specific message you first have to select that message To do so on an OP you use the cursor keys to move the cursor to the message concerned On the TP all you have to do is touch the desired message on the screen ProAgent User s Manual Issue 12 99 Display on the Operating Unit Switching to the Overview Screen Vu To obtain an overview of which units of your system are affected by the faults use this key to switch to the Overview Screen From there you can subsequently move on to the Movement Screen in order to manually execute individual Movements for a specific unit Switching to the Detail Screen LD Once you have selected the required message you can use this key to switch to the Detail Screen This shows you the section of the STEP 7 program code responsible for triggering the alarm message Switching to the Movement Screen PY Once you have selected a message you can use this key to switch directly t
43. 99 5 9 Display on the Operating Unit 5 1 4 The point of entry to the diagnosis is normally provided by the Diagnosis Start Screen the Message Screen or the Overview Screen You can access any of the other diagnosis screens from the Message Screen and the Overview Screen Your particular configuration may differ from this arrangement of links If your project provides the means you may also be able to move directly to specific diagnosis screens from other system screens The Previous Screen key will then take you back to that system screen General Principles of Using the Diagnosis Screens Standardization The way in which the diagnosis screens are used is not significantly different from the way in which the other screens are used Likewise the appearance of diagnosis screens differs only minimally for different types of operating unit e g OP and TP For this reason we will always refer to control elements that are activated on an OP by means of a softkey or function key and on a TP by means of a key shaped button by the generic term keys There are however a number of peculiarities that depend on whether you are using a key controlled operator panel OP or a touch panel TP These peculiarities are summarized below There are various symbols used on the diagnosis screens Once you are familiar with them you will find your way around all the diagnosis screens very easily Cursor Control on the OP 5 10 On the
44. APH sequencer on sequencer the step screen You can set or reset every step in the A detailed description of the step screen is given in the chapter Step Screen Chapter 5 4 5 6 ProAgent User s Manual Issue 12 99 Display on the Operating Unit Movement Screen Movement possible Movement blocked DB21 Hssembly door ale P otary a E IE The Movement Screen provides assistance with rectifying faults You can use the keys at the sides to initiate specific movements on individual units Movement Screen As Shown on OP25 The symbols displayed help you to see at a glance whether a movement is blocked A detailed description of the Movement Screen is given in the chapter Movement Screen Chapter 5 5 ProAgent User s Manual Issue 12 99 5 7 Display on the Operating Unit Detail Screen These signals led to the process fault Results of logical operations Status bits Ste 12 Start convevor be B12 Trans BS 12 13 14 15716 17 p Ab tat Symbol an a ann p rn The process diagnosis analyzes which signals in the PLC program have led to an error message The Detail Screen shows the results of that analysis This means that you can not only see that a fault has occurred you are immediately shown what has caused it as well The detail screen displays the corresponding section of the STEP 7 program code in signal list in STL or LAD format At the same time the status bits of the
45. Diagnosis Screen Names The names of the standard diagnosis screens supplied are as follows Name bmwessSeem ZP DETAILSYM Detail Screen signal list format ZP_DETAILAWL Detail Screen STL display mode ZP_DETAILLAD Detail Screen LAD display mode ZP_STEP Step Screen Names of the Diagnosis Screens Tags for Each Diagnosis Screen In order to simplify assignment of tags the tag names always start with the first letters of the name of the screen on which they are used Example e All tag names for the Overview Screen start with ZP_U e All tag names for the Detail Screens start with ZP_D etc ProAgent User s Manual 8 6 Issue 12 99 8 4 8 4 1 8 4 2 Modifying the Diagnosis Screens Modifying Design and Information Content Modifying the Design You can modify the design of the diagnosis screens at any time in the same way as you are familiar with in ProTool For example you can use different pictograms colors or fonts Caution If you delete individual elements or lines from a diagnosis screen or add new ones make sure you follow the guidance notes given in the chapter Adding or Removing Lines Chapter 8 4 3 Otherwise the functional capacity of the diagnosis system could be significantly impaired Tip You can modify several elements at once by holding down the Shift key and selecting all the elements you wish to change When you have selected all the desired elements you can then as
46. If there are more possible movements than can be shown on the Movement Screen at once you can similarly use these keys to scroll up or down a complete page at a time Cursor Function in the Individual Diagnosis Screens Toggling Cursor Control OP only sz You can use the Change Windows key to toggle between the special eo diagnosis screen cursor control features and the standard cursor control If the Message Window or the Fixed Window are open you can also switch to those windows In that case the sequence is as follows Diagnosis cursor normal cursor Message Window Fixed Window Diagnosis cursor ProAgent User s Manual Issue 12 99 5 11 Display on the Operating Unit Peculiarities of a Touch Panel When you use a touch panel you select individual elements of the diagnosis screens by touching the corresponding location on the screen Selected elements are then inverted At locations on the screen at which it is not possible to invert the display of such elements a hand appears on the screen indicating that a touch function has been activated If there are more lines than can be shown on the screen of the operating unit at one time you can scroll the display of the TP e To scroll up touch the top most entry in the scrollable area of the screen until scrolling is activated To scroll down touch one of the other entries until scrolling is activated The length of time
47. OP2 OP35 OP3 Overview Screen Profgent V5 H Takes you to the Message Screen Copyright C 1997 99 SIEMENS AG Rl Rights Reserved Can be configured to take you to one of your own screens Diagnosis Start Screen As Shown on OP25 The Diagnosis Start Screen forms the point of entry and distribution for the diagnostic functions From there you can move to the Message Screen and the Overview Screen where you can obtain an initial overview of pending error messages Whether or not the Diagnosis Start Screen is actually used depends on the particular configuration concerned ProAgent User s Manual Issue 12 99 5 3 Display on the Operating Unit Message Screen Diagnosable alarm messages Pending Hlarm Messages m723d4567 A K 14 15 95 2 86 1997 GRUB Hssembly of electronics workpiece supply interrupted x 643071 A K 13 13 27 BZ 85 1997 GRUB Conveyor belt 1 jammed 8517898 A KG 11 17 28 02 06 1997 GRUA Press 1 oil pressure too low Message Screen As Shown on OP25 Like the Diagnosis Start Screen the Message Screen also often serves as the point of entry into the diagnosis Its structure is similar to that of a conventional alarm message window except that additional keys are provided for selecting other diagnosis screens Diagnosable messages are identified by an asterisk in front of the message number You can only carry out a diagnosis for that type of message A detailed
48. Only the messages of the units selected here will be displayed on the operating unit Note The necessary information is obtained by ProTool from the database shared with STEP 7 If you can t find a particular diagnosable unit you are looking for on the list recompile the PLC program see Shared Database with STEP 7 Chapter 6 1 2 If you change the name of a PLC that name will be displayed instead of the name used in STEP 7 ProAgent User s Manual Issue 12 99 Configuring in ProTool Adding Units To select a unit for diagnosis proceed as follows 1 In the Diagnosable Units box select the unit you wish to include in the diagnosis By clicking or you can view or hide information on the individual blocks of the PLCs 2 Click the gt gt button The unit selected then appears in the list of selected units This unit can then be diagnosed during operation i e messages that concern the units will be displayed on the operating unit Note Only select units for diagnosis if you are actually going to use the diagnosis functions i e if you want to configure a Diagnosis Screen or use ProAgent functions Otherwise you will be using system resources on the operating unit unnecessarily Removing Units 6 1 7 To remove a unit from the list of selected units proceed as follows 1 In the Selected Units box select the unit you wish to remove 2 Click the lt lt button The unit selected then disappears from the list
49. Partial and Full View LAD Chapter 5 6 4 4 Partial view shows only those operands that have led to a fault being triggered This key is used to determine what status and therefore which logical operation results are shown i e the values at the time of occurrence of the fault initial values or the current values see Toggling Displav of Initial Values and Current Status LAD Chapter 5 6 4 5 You use this key to change to the next error in other words to the next faulty action of this unit refer to Changing the Action or Transition LAD Chapter 5 6 4 6 With units programmed with S7 GRAPH and using movement blocks created with S7 PDIAG the change is made initially to all other transitions and then to the movement blocks You use this key to change within an error The change is normally to the next transition see Changing the Action or Transition LAD Chapter 5 6 4 6 In the case of Multiple Assignments to a monitored operand the change is to the next network containing an assignment to that operand This key is used to change the display to signal list format see What You See on the Detail Screen Signal List Chapter 5 6 2 1 This key is used to return to the screen from which you opened the LAD Display Mode Keys Used with Detail Screen in LAD Display Mode ProAgent User s Manual Issue 12 99 5 67 Display on the Operating Unit 5 6 4 3 How to Work with the Detail Screen LAD Th
50. ProAgent User s Manual Issue 12 99 approx 15 MB on the drive on which ProTool is installed SIMATIC S7 with ALARM S compatible CPU Version 5 0 or higher Version 4 02 or higher Version 4 0 or higher Version 4 0 or higher 2 1 Installation 2 2 Installing ProAgent Integrated Installation ProAgent requires that ProTool has been installed integral with STEP 7 At least one of the STEP 7 option packages S7 PDIAG or S7 GRAPH is also required If STEP 7 and S7 PDIAG or S7 GRAPH are not currently installed on your system install those programs first before installing ProAgent Note STEP 7 is the first program that has to be installed Installing ProAgent To install ProAgent proceed as follows 1 Start SETUP EXE on the installation medium A dialog box appears for entering the destination folder 2 f you wish to install ProAgent in a folder different from the one proposed click the Browse button However the destination folder must be a folder in which a version of ProTool meeting the above system requirements has been installed 3 Click the Next button Setup shows you the exact amount of space in kilobytes you require and how much is available on the destination drive If the amount of space available on the drive you selected is insufficient delete any programs or files you no longer require Tip It is frequently sufficient to empty the recycle bin to release sufficient space on the hard disk 4 f you
51. ProAgent is installed These functions are not required unless you change the diagnosis screens or use individual diagnosis elements in your own screens Details of how to modify the diagnosis screens and what you should bear in mind when doing so are explained in the chapter Modifying the Diagnosis Screens Chapter 8 A detailed description of all functions is provided in the ProAgent Online Help under the heading Functions Overview Additional Standard Screens Diagnosis Screens When ProAgent is installed an additional STEP 7 project called ProAgent is created That project contains standard screens for the individual diagnosis tasks In order to distinguish them from the conventional standard screens they are referred to as diagnosis screens How to incorporate the diagnosis screens in your own projects and link them to other screens is explained in the chapter ncorporating the Diagnosis Screens Chapter 6 1 4 A detailed description of the individual screens is given in the chapter Display on the Operating Unit Chapte In general it is not necessary to alter the diagnosis screens Nevertheless they can be adapted to individual circumstances if necessary and how this is done is explained in the chapter Modifying the Diagnosis Screens Chapte ProAgent User s Manual Issue 12 99 4 3 Effects on ProTool 4 4 ALARM_S Message Procedure Why ALARM S The STEP 7 option packages S7 PDIAG S7 GRAPH and S7 HiGraph
52. SCS Memes w 1 Target E mew S Soe sequences se w Deme w s et ProAgent User s Manual Issue 12 99 Appendix System Limits B 7 Form DRAM Requirement of the Project Components The Component and Max bytes columns already contain all project components and their maximum memory space 1 Inthe 3rd column enter how often you use each component 2 Inthe 4th column Byte enter how many bytes the components you are using actually take up 3 In the 5th column enter the number of languages A has already been entered for components whose memory requirement is independent of the language being used 4 In the 6th column Number Bytes Languages calculate the memory requirement of each component class 5 Add up the values in the 6th column to calculate the overall memory requirement The result must be less than 1 Mbyte 1 048 576 bytes Bytes Language Number Bytes LJ Basic configuration standard ProTool ProAgent eae User Diagnosis Texts 1 text per S7 PDIAG block 2 texts per network 2 texts per movement 1 text per target position 1 text per S7 Graph step sequence ProAgent User s Manual Issue 12 99 B 9 Appendix System Limits Basic requirement for structure Analysis of Criteria Remark texts 40 m B 10 ProAgent User s Manual Issue 12 99 SIMATIC HMI Documentation Target groups This manua
53. SIEMENS SIMATIC HMI Process Diagnosis ProAgent for OP User s Manual 6AV3681 1AC05 1PB0 Issue 12 99 7 Message Processing Modifying Diagnosis Screens Appendix A A System Messages Appendix B B System Limits SIMATIC HMI C Documentation D Siemens worldwide I Trademarks SIMATIC is a registered trademark of SIEMENS AG Other terms used in this document may also be trademarks the use of which by third parties for their own purposes may violate the rights of the owners of those trademarks Copyright Siemens AG 1999 All Rights Reserved Distribution or duplication of this document commercial exploitation or communication of its content is prohibited unless expressly authorised Violation of these conditions shall render the perpetrator liable for compensation All rights reserved in particular with respect to the issue of patents or registration of trademarks Siemens AG Bereich Automatisierungstechnik Gesch ftsgebiet Industrie Automatisierung Postfach 4848 D 90327 N rnberg Siemens Aktiengesellschaft Liability Disclaimer The content of the printed document has been checked for consistency with the hardware and software described The possibility of inaccuracies can nevertheless not be entirely eradicated as a result of which no guarantee of absolute accuracy is offered The information in this document is regularly checked and any alterations found to be necessary included in the subsequent revision
54. TIC Premium Hotline with charges with SIMATIC Card only Time Mo Fr 24 hours Telephone 49 911 895 7777 singnet com sg Fax 49 911 895 7001 ProAgent User s Manual Issue 12 99 Preface SIMATIC Customer Support Online Services SIMATIC Customer Support offers you a great amount of additional information about SIMATIC products via online services e Up to date general information can be found inthe Internet under http Awww ad siemens de simatic via fax polling no 08765 93 02 77 95 00 e The latest product information sheets and downloads that may be of practical use can be found inthe Internet under http www ad siemens de support html 00 via the Bulletin Board System BBS in Nuremberg SIMATIC Customer Support Mailbox under the number 49 911 895 7100 To call the mailbox use a modem that complies with at least V 34 28 8 kbaud and whose parameters are set as follows 8 N 1 ANSI Or use an ISDN card X 75 64 kbit ProAgent User s Manual Issue 12 99 1 7 Installation Overview 2 This chapter explains how to install ProAgent under STEP 7 and under ProTool 2 1 System Requirements Hardware Requirements The hardware requirements are the same as for the basic ProTool program In addition you will also need the following Free hard disk space PLC Software Requirements Microsoft Windows 95 or Windows NT 4 0 ProTool STEP 7 S7 PDIAG and or S7 GRAPH
55. Unit The most efficient way of configuring the function ProAgent Acknowledge Unit Is to assign it to a global function key When the system is running pressing that key will acknowledge the following unit depending on the diagnosis screen displayed e the unit to which the message selected on the Message Screen belongs e the unit selected on the Overview Screen e the steps of which are displayed on the Step Screen e the unit whose movements are displayed on the Movement Screen e the unit whose signals are displayed on the Detail Screen In order to be able to acknowledge a unit the UDT Unit must be used in S7 PDIAG The function ProAgent Acknowledge Unit only sets the relevant bit The PLC must make sure that the bit is reset again after acknowledgement Moving Directly to the Detail Screen If you attempt to call up the Detail Screen ZP DETAILSYM ZP_DETAILAWL or ZP DETAILLAD from any screen other than the Message Screen ZP ALARM a system message is normally returned The reason for this is that you will not have been able to select an alarm message and the system will therefore not have been able to identify for which message the process diagnosis is to be performed In principle however it is possible on an OP to open the Detail Screen from any other screen as long as the Message Screen is visible In that case the system will know for which message the process diagnosis is to be carried out In order to be able to
56. View Options There are a number of ways in which you can adapt the view options to suit your personal preferences wu 6c ENTER If you want to be able to view all signals i e including those that have not led to a fault press this key see Toggling Between Partial and Full View STL Format Chapter 5 6 3 4 If you wish you can have the current status bits displayed instead of the displayed initial values status bits at the time the error occurred To do so use this key see Toggling Display of Initial Values and Current Status STL Chapter 5 6 3 5 Device specific for OP If you wish to view the symbols and remarks relating to the individual instructions use the ENTER key to open the corresponding list box see Toggling Display of Symbol and Remarks STL Chapter 5 6 3 7 On a TP you open this same list by touching the corresponding input output field Exiting the Detail Screen 5 60 T This key returns you to the screen from which you activated the Detail Screen ProAgent User s Manual Issue 12 99 Display on the Operating Unit 5 6 3 4 5 6 3 5 Toggling Between Partial and Full View STL Format You can choose whether to e view all instructions of the network displayed full view or e view only those instructions that have set the monitored signal to the incorrect status partial view Wu To toggle between the two display modes use th
57. You can easily switch to other actions steps and transitions simply by pressing a key Changing Action A unit may have more than one fault at the same time Use key combination to switch to the next fault in the same unit The action of the unit affected by this fault will be displayed A Press this key to switch to the next fault Display of the steps and transitions in the top section of the screen then changes accordingly see What You See on the Detail Screen STL Format Chapte Note Once all actions of a unit have been run through and the unit concerned has other hierarchically subordinate units the function moves on to the actions of those units This means that you do not need to return to the Overview Screen and select a hierarchically subordinate unit there in order to be able to see the actions with faults on the subunit Change transition or network Sometimes the cause of a fault cannot be recognized at first glance e n S7 PDIAG units the detail screen always shows one network only However the cause of the fault may be located in more than one network e Inthe same way with S7 GRAPH units the interlocking condition of the step or individual transitions could be the cause of the error message Use this key to switch from one possible cause of a fault to the next With S7 PDIAG units from one associated network to the next With S7 GRAPH units that report an interlocking fault from the i
58. a Action Mo E uto 4 Gy tress f 3 Auto AConveyor belt 7 7 Auto Weld door panel 15 Auto Weld door hinge 18 Auto Paint Auto Overview Screen As Shown on OP25 Note that no display appears in fields 12 through 17 if the selected unit was programmed with S7 PDIAG ProAgent User s Manual 5 20 Issue 12 99 Display on the Operating Unit Overview of Units The center section of the display shows a list of all diagnosable units in your system Their order of display corresponds to the sequence of screen numbers and position numbers which can be assigned as attributes when you program the units in S7 PDIAG If no default values are specified at that stage or if individual positions are assigned twice over including on several CPUs the order is arbitrary 1 This field displays the name of a unit from the PLC program as the symbol for a block or as an absolute name 2 The warning triangle indicates that a unit has a fault The unit on which the fault occurred first is identified by a flashing warning triangle This tells you that the fault in question was not a consequential error 3 The content of this field depends on how the unit has been programmed e if programmed in S7 PDIAG a value of zero is displayed e if programmed in S7 GRAPH the active step number is displayed 4 This shows the current operating mode of the unit in question You can change the operating mode
59. a notebook or a PU Although all the data shared with STEP 7 is held in a common database see Shared Database with STEP 7 Chapter 6 1 2 and ProTool plus ProAgent has to run integral with STEP 7 it is possible with certain limitations to open to compile and to download to an operating unit existing ProTool configurations using ProTool as a stand alone product This is possible since a working copy of all necessary data is stored internally in the ProTool project PDB file Caution When opening a configuration in ProTool as a stand alone project data is not synchronized with the shared database Limitations AN All dialog boxes relevant to diagnosis functions can be selected in stand alone operation but can not be edited Caution You are responsible yourself for ensuring that data is synchronized with the shared database if any changes are subsequently made to the STEP 7 program Exporting a Project To copy a ProTool project from a STEP 7 project to another computer proceed as follows 1 Start the SIMATIC Manager 2 Open the STEP 7 project 3 Select the operating unit whose project you want to copy 4 Choose the menu option Edit Object Properties and open the OP Properties dialog box 5 Make a note of the path specified for Configuration File and the name of the file with the extension PDB This is the project you are looking for 6 Copy the file using the Windows Explorer for example to the computer
60. able lists all Siemens Sales Offices in the Federal Republic of Koblenz K ln Konstanz Laatzen Leipzig Lingen Magdeburg Mainz Mannheim M nchen M nster Westf N rnberg Osnabr ck Regensburg Rostock Saarbr cken Siegen Stuttgart Ulm Wetzlar Wilhelmshaven Wuppertal W rzburg D 1 Siemens worldwide European Companies and Representatives D 2 The following table lists all European Siemens Companies and Representa tives Austria Siemens AG Osterreich Bregenz Graz e Innsbruck Linz e Salzburg Wien Belgium Siemens S A Bruxelles Li ge Siemens N V e Antwerpen Bosnia Herzegovina Generalexport Predstavnistvo Sarajevo e Sarajevo Bulgaria Siemens AG rappresentanza in Bulgaria e Sofia Croatia Siemens d o o Zagreb Cyprus GEVO Ltd oppure Jolali Ltd e Nicosia Czech Republic Siemens AG Brno e Mlad Boleslav Praha Denmark Siemens A S Koebenhavn Ballerup Finland Siemens Oy e Espoo Helsinki France Siemens S A Haguenau ille Seclin Lyon Caluire et Cuire Marseille Metz Paris Saint Denis Strasbourg Toulouse Great Britain Siemens plc Birmingham Walsall Bristol Clevedon Congleton Edinburgh Glasgow Leeds Liverpool London Sunbury on Thames Manchester Newcastle Greec Siemens A E e Athen Amaroussio Thessaloniki Hungaria Siemens Kft Budapest
61. action numbers ZP UNITS S7G transition numbers displayed Overview screen ZP_UROWS Max number of units displayed scrollable lines ZP_MOTION ZP_MCOLUMNS Max number of target positions Movement screen ZP_MROWS Max number of movements displayed ZP_STEP ZP SACT MAX Max number of action Step screen numbers transition numbers displayed ZP DETAILSYM ZP DROWS Max number of instructions Signal list detail displayed screen ZP DETAILAWL ZP DTRAN MAX Max number of action numbers STL detail screen transition numbers displayed ZP DETAILLAD ZP DLAD COL Max number of adjacent switches LAD detail screen ZP DLAD ROWS Max number of vertically adjacent switches ZP DTRAN MAX Max number of action numbers transition numbers displayed Tags with Important Start Values ProAgent User s Manual 8 4 Issue 12 99 Modifying the Diagnosis Screens Consequences If the number of fields or lines changes the start value of the corresponding tags must be modified to match the new number of lines or columns Dynamic Attributes Many input output fields use dynamic attributes to control display of inverse type or flashing characters If you add new lines you must similarly define the appropriate dynamic attributes and assign them the correct values see Adding or Removing Lines Chapter 8 4 3 Showing Hiding Lines Lines that are not required are hidden when the system is running To achieve this many fields ar
62. ae screens Basic requirement for approx 200 approx 200 diagnosis 000 000 User Diagnosis Texts 1 text per S7 PDIAG 20 20 1 400 block 1 text per target 320 40 1 12 800 position 1 text per S7 Graph 10 20 1 200 step sequence asee Md T MM structure Symboismtes 1000 20 200000 mmm O NA E c i Sum 1012 200 At an estimate the project requires 1 012 200 bytes of memory space The system limit of 1 Mbyte 1 048 576 bytes is therefore complied with Please note that the result calculated is an estimate that is accurate only to within approximately 100 kbytes At the end of this Appendix you will find a blank form on which you can easily calculate the memory requirement of your own project You can also print out the same form from the Online Help for ProAgent ProAgent User s Manual Issue 12 99 B 7 Appendix System Limits B 6 B 8 Form Memory Requirement of the Diagnosis Structures The Structure and Bytes columns already contain all diagnosis structures and their memory requirement 1 In the 3rd column enter how often you use each structure 2 In the 4th column Number Bytes calculate the memory requirement of each type of structure 3 Add up the values in the 4th column to calculate the overall memory requirement The result must be less than 64 000 bytes Suse Byes Number Number amp ines wma ws ol CSCS frewors m SSC C
63. agnosis can be configured for the operating unit It is only at this stage that the ProTool option package ProAgent comes into play It goes without saying that you do not need to repeat any of the entries already made in STEP 7 All relevant information has been stored in the shared database that ProTool now accesses This is what makes the process of configuration in ProTool so quick and easy to complete All you have to do is Diagnosis screen incorporation Selecting the units display classes Compiling and downloading 44r Configuring the Operating Unit for Process Diagnosis ProAgent User s Manual Issue 12 99 3 7 Introduction The first step involves adopting the standard diagnosis screens supplied with ProAgent The screens are now fully ready If in certain situations you should nevertheless wish to modify any of the screens to suit your own particular requirements that presents no problem Next you select the units of your S7 PLC for which you wish to set up a process diagnosis Making that selection is simple ProTool compiles a list from the shared database and all you need to do is click the relevant units You can also specify which messages are to be displayed on the operating unit Selection is made by display class which once again you simply select from a list By judicious selection you can restrict the range of messages displayed on the operating unit The remaining messages could then b
64. agnosis screens 8 7 Add lines to diagnosis screens Additional support Adjust Filter criteria on message screen Number of limits Operating modes on overview screen 16 ALARM_S Acknowledgement 7 16 Buffer overflow Communication sequence 7 15 Display classes Message overload 7 1 Message printing Message text configuration Setting AM 1 5 ProAgent User s Manual Revision 01 99 Benefits of process diagnosis Branch Instructions Buffer overflow C Calculation example Memory requirement of an OP25 project BS Change Font size and font Mode of enabling movements 8 12 Number of limits Chapter summary Comment Display simultaneously with symbol Compile Index Configuration ALARM_S messages 7 change mode of ine movements 8 T 6 20 Diagnosis screen incorporation 6 12 Diagnosis screens Direct branch to detail screen 8 18 Direct keys 8 19 Downloading 6 20 Overview of steps 6 6 6 25 Porting to computer without STEP 7 Replacing the overview screen Selecting display classes Selecting units Setting message procedure Unit acknowledgement 8 18 Upgrade to new diagnosis screens Configuring Process diagnosis Configuring Direct Keys on a TP Conventions Abbreviations On M screens Styles 1 4 With e gnment of names CPU 1 M 6 15 Create message procedure Cursor control D Database Access to Importing message text 7 13 Shared with STEP 7 DB Delete lines from diagnosis sc
65. and directory of your choice You can now open the project on the destination computer using ProTool alone If you make any changes you can subsequently reintegrate the project see ProTool User s Guide ProAgent User s Manual Issue 12 99 6 23 Configuring in ProTool 6 2 6 2 1 Special Considerations When Upgrading an Existing Project Requirements of PLC Program and Project when Upgrading PLC Program As a basic requirement ProTool plus ProAgent requires a diagnosable PLC program And the same is true whether you are creating a new project or upgrading an existing project to include process diagnosis An overview of the basic requirements is given under the heading Basic Requirements of the PLC Program in the chapter Configuring a Process Diagnosis Chapter 6 1 f Project There are no particular requirements placed on the project being upgraded On basic requirement however is that the operating unit configured is diagnosable that is an OP25 OP27 C7 626 TP27 6 TP27 10 OP35 OP37 or TP37 Your project can include more than one PLC including ones which do not meet the requirements for process diagnosis In that case however those PLCs will not be capable of diagnosis You can also integrate various different diagnosable PLCs in your project and even program them in different languages according to the particular requirements e g one PLC in STL using S7 PDIAG and another in S7 GRAPH Fixed Window The
66. appears Add Display Device Inserting a Display Unit There you select the required display unit and you can also assign it a symbolic name Select device type OP25 for the OP25 OP27 TP27 6 and C7 626 and device type OP35 for the TP27 10 OP35 OP37 and TP37 In the bottom section of the dialog box you will see the details of the display options for the selected device you can not enter settings at this point Once you have selected a device that operating unit appears in the Special Object Properties Messages dialog box in the list of display units ProAgent User s Manual Issue 12 99 Message Processing If you then select that operating unit additional tabs appear in the lower half of the dialog box on which you can finally specify the device specific settings men motn 00 m M No part arrived within monitoring period a u Please check Stock feed Magazine Device Specific Settings For an OP25 for example you can do the following Specify acknowledgement group and priority Activate message logging Enter two lines of text of up to 35 characters in length and assign individual characters the attributes flashing and underlined Enter explanatory text which will provide the operator with additional information that can be obtained by pressing the Info key Finally you confirm your entries by choosing OK ProAgent User s Manual Issue 12 99 7 9 Messa
67. ays a text that is assigned to the step displayed under 5 5 6 7 This field displays the module in which the network was configured 8 This field displays the text Transi for Transitions 9 This field displays the numbers of the transitions of the step displayed The transition displayed is highlighted in inverse type If step monitoring view is displayed rather than a transition then accordingly the step number is highlighted 10 This field displays the text Tr Name for Transition Name The field remains blank if the locking condition of the step is shown 11 This field displays the name of the transition displayed The field remains blank if the locking condition of the step is shown If the unit has been programmed with S7 PDIAG lines 2 and 3 of the display look as follows Unit B13 bel ON Network 12 Start M r TT d Number 13 14 15 17 mM bero m MIS FEU s Sumbal Detail Screen example of LAD format on an OP25 programmed with S7 PDIAG 4 This field displays the text Netw for the network selected 5 This field displays the number of the network displayed 6 This field displays the name of the network displayed ProAgent User s Manual Issue 12 99 5 65 Display on the Operating Unit This field displays the module in which the network was configured This field displays the text Number for Network Number co This field displays the net
68. ble the initial step of the step sequence press this key The number of the enabled step then appears on the third line of the step screen Limited number of simultaneously active steps Depending on how the PLC is programmed only a limited number of simultaneously active steps is allowed As soon as this number is exceeded upon enabling the step concerned no longer appears in the list of active steps You can then enable the required step only after you have deleted another active step ProAgent User s Manual Issue 12 99 5 33 Display on the Operating Unit 5 5 Movement Screen 5 5 1 The Purpose of the Movement Screen Movements The Movement Screen helps you when rectifying a fault or operating the installation It allows you to execute specific movements for individual units manually by means of keys For example you could move the die of a stamping press back to its starting position before removing a jammed workpiece Each movement can be executed in two directions e g in out open close up down forward backwards Blocked Movements If a movement is blocked and can therefore not be executed this is indicated clearly on the Movement Screen Target Positions The Movement Screen also shows which target positions have already been passed This means that on a stamping press for example you could see what the current position of the die is If the movement is blocked you can see at what point it was blocked Ba
69. can initiate simultaneous repair of the individual components And that means that your installation will be ready for operation again as quickly as possible ProAgent User s Manual Issue 12 99 Introduction m Backwards X axis Forward 2 Rectifying faults by guided manual operations 11 0 01 0 P Har j ip Process diagnosis X axis not moved Display of message Message Diagnosis Assistance with Fault Rectification Reducing Costs Early identification and elimination of faults increases installation availability reduces down times and thus ultimately reduces costs ProAgent User s Manual Issue 12 99 3 3 Introduction 3 2 How a Process Diagnosis is Carried Out Diagnosis Screens 3 4 When the process diagnosis is configured various additional standard diagnosis screens diagnosis screens for short are incorporated in the project Those screens are linked to one another by keys The contents of the screens automatically adapt to the technical units of the installation For the operator on the operating unit process diagnosis is simple in view of these diagnosis screens When a fault occurs an alarm message appears on the Message Screen on the operating unit By identifying this alarm message by an asterisk the operator sees that the malfunction is capable of being diagnosed in other words it indicates that he can trace the cause of the fault on the operating
70. chical Units on the Overview Screen Hierarchical Units 5 26 When programming a PLC it is possible depending on the programming language used to define a hierarchy of individual units Thus in the case of S7 PDIAG a unit can be equated with a block which as a rule also represents a process unit By virtue of the multi instance concept of STEP 7 a unit can also contain other units As soon as at least one subunit has a fault the immediately superior unit is also marked as having a fault The marker is thus passed on from one level to the next right up to the highest hierarchical level Note If the PLC has been programmed in S7 GRAPH there are no hierarchical units ProAgent User s Manual Issue 12 99 Display on the Operating Unit Identifying Hierarchical Units You can tell whether there are subordinate or superior units related to a particular unit by means of graphical symbols shown on the operating unit They appear above the list of units They always relate to the unit currently selected by the cursor 4 4 indicates that there is a superior unit gt indicates that there is a subordinate unit gt gt K indicates that there is a superior unit and subordinate units In order to be able to tell whether there are more hierarchical levels related to a unit you thus proceed as follows 1 Select the unit in question 2 Observe the symbol displayed Changing Hierarchical Level To change the hierarchica
71. creen LAD as well The bottom line of the screen shows the operand symbol or remarks relating to the switch highlighted on the ladder diagram To toggle between display of operand symbols and remarks proceed as follows 1 Select the switch for which you would like to have the relevant information displayed 2 Onan OP press the ENTER key A text or graphic list then opens from which you can select the required display mode On a TP you open the same list by touching the corresponding input output field that is the word Address Symbol or Remark Note If no symbol or remarks were stored the absolute operand is shown Enhanced Possibilities with S7 PDIAG Reference Networks The program code displayed by ProAgent is not always absolutely identical with the program code that was entered in LAD FUP STL In order to provide you with as meaningful an excerpt as possible corresponding reference networks are created if possible For example ProAgent shows the complete assignment instead of a flag Programming in STL Display with ProAgent U 11 0 U 11 1 Uu n2 M1 0 iU no U n2 U n4 U M1 0 01 0 01 0 Forming Auxiliary Networks ProAgent User s Manual Issue 12 99 5 73 Display on the Operating Unit 5 6 5 2 Branch Instructions ProAgent s criteria analysis is in a position to resolve even complex PLC programs with labels and display them on the operating unit The display
72. d the operating unit as the active user master in the PROFIBUS DP network Configuring The OP As A PROFIBUS DP Slave If you want to be able to use DP direct keys you have to configure the OP as a PROFIBUS DP slave The operating unit is configured with the same address both as the active user and as a DP slave 8 22 1 Start the STEP 7 hardware configurator and in the hardware catalogue under stations already configured in the SIMATIC OP group select the corresponding hardware e g OP25 DP KEYS Connect the OP to the DP network You are then presented with a list of all the operating units already configured in this network 3 Select the operating unit with the same address as the OP has as master 4 You are now also able to configure CPI modules in addition to the DP direct keys Your hardware is now configured for the use of DP direct keys ProAgent User s Manual Issue 12 99 Modifying the Diagnosis Screens 8 6 4 Important Information About Using Direct Keys A number of points must be observed when using the direct keys in a project e After a system crash the operating unit does indeed reset all enable functions during startup but the direct keys are available as soon as voltage is applied In order to prevent incorrect movements during the time the operating unit takes to start up again you must monitor the failure of the operating unit and if necessary cancel the enable functions and or display orders o
73. de Chapte 14 The individual operands Here too the display depends on whether SIMATIC or IEC display mode is set 15 the operand status The information displayed relates either to the values at the time of occurrence of the fault initial values or the current status see Toggling Display of Initial Values and Current Status STL Chapter 5 6 3 5 16 The corresponding logical operation result 17 Symbol or remark for the signal as per the text or graphic list or remark list in Step 7 If the operating unit display does not provide sufficient space to show symbol and remark parallel to each another you can toggle between the symbol display and the remarks display see Toggle Between Symbol and Remark Signal List Chapter 5 6 2 6 In the case of tags within DBs only the symbolism is displayed if a symbolic identifier has been stored in the symbol table If no symbol has been created the operating unit only shows the absolute address of the tag 18 A lightning flash symbol appears here if the signal shown next to it has led to an alarm message 19 If there are more instructions than can be displayed on the operating unit at one time the arrow right and arrow left symbols appear You can then scroll the display up or down ProAgent User s Manual 5 56 Issue 12 99 Display on the Operating Unit 20 A lightning flash symbol appears here if partial view is active this lists only those instructions that have se
74. de the field remains blank ProAgent User s Manual Issue 12 99 5 21 Display on the Operating Unit Fields 12 through 17 only appear if the selected unit has been programmed in S7 GRAPH 12 This field displays the text Step 13 This field displays the user number of the active step If several actions are active at the same time the step number of the action that appears first on the list at 15 is shown 14 This field displays the step name 15 This field displays the text paral to identify the subsequent numbers as parallel steps 16 These fields display the numbers of the active actions The numbers of the actions with faults always appear first reading from left to right Actions with faults are shown flashing 17 The arrow right symbol appears here if there are more parallel actions than can be shown at 16 at once 5 3 3 Overview Screen Keys You can use the following keys on the Overview Screen On an OP you use these cursor keys to move the cursor between units On a TP you can select a message by touching it on the screen If there are more messages than can be shown on the screen at the one time you can scroll the display On an OP you use these keys to switch between hierarchical units You can tell whether subordinate or superior units are present by means of these symbols Ona TP you use these keys to switch between hierarchical units The corresponding key is only displayed i
75. diagnosis functions K Use the Display hidden buttons key to display the Selection and buttons in the diagnosis screens for the TP ProAgent User s Manual 8 2 Issue 12 99 Modifying the Diagnosis Screens 8 2 Internal Structure of the Diagnosis Screens Conventions The powerful process diagnosis system involves a particularly complex process and therefore demands that certain rules and conventions are adhered to The diagnosis screens supplied with ProAgent conform to those rules If you make modifications to the screens you must make sure that the changes you make do not break any of the rules This applies particularly to minor and apparently insignificant alterations You can not for example simply delete certain screen elements without further thought Tag Indices Tags that are used for input output fields in the diagnosis screens require an internal four digit index The index values are set with the aid of the function ProAgent Set Tag Index Internal linking of the tags to the indices is necessary in order that the operating unit can supply those tags with the current diagnosis data The indices are allocated on the basis of a fixed number code They are therefore not randomly assignable You can identify the number code by looking at the parameters of the function ProAgent Set Tag Index for a number of the tags used on the diagnosis screens If you wish to add a tag to a project for a specific purpose e g to ext
76. diagnosis screens the cursor keys are not used to move between input fields as is normally the case but to scroll the list displayed v These symbols are displayed if there are more lines than can be shown 2 on the operating unit at one time You then have to scroll the screen to see the remaining lines wA You always use these keys to scroll up or down ProAgent User s Manual Issue 12 99 Display on the Operating Unit What s more the cursor keys have the following functions in the individual diagnosis screens In the Message Screen you use the cursor keys to move the cursor up and down If there are more messages than can be shown on the screen the display is scrolled as soon as you move the cursor beyond the top or bottom of the screen In the Overview Screen you use these cursor keys to move the cursor between the individual units If there are more units than can be shown on the screen at a time once again the display is scrolled as soon as the cursor is moved beyond the top or bottom of the screen You use these cursor to switch between hierarchical units in the Overview Screen If this is possible these symbols are displayed on the operating unit If there are more lines on the Detail Screen STL than can be displayed at once on the operating unit you use these cursor keys to scroll a complete page up or down If you are viewing the screen in an LAD you can use these cursor keys to scroll horizontally
77. dow 2 If you do not wish to deactivate the Message Indicator as well you should drag it with the mouse to the top right corner Copying the Diagnosis Screens Your project now contains the normal standard screens but as yet no diagnosis Screens The diagnosis screens for the various types of operating unit are all located in the STEP 7 project ProAgent which is automatically created in the ProTool directory in the subdirectory PROAGENT STANDARD when ProAgent is installed This next step now involves copying the diagnosis screens you require from that project to your own project via the Clipboard bs Projekt dokutest Di x 3 22 OP25 dokutestop Nant Sa OP25 Prodgent25 Name Nummi amp amp Bilder Z BACKUP 10 amp J Bilder EA 4 E Meldungen 37 FORCE 2 Meldungen ba Rezepturen EZ MARCHIVE 14 Rezepturen ea Xf Variablen BZ MESSAGES 4 Xf Variablen B Steuerungen Sz PASSWORD 5 Steuerungen TL Symbollisten 37 PRINTER 8 TL Symbollisten E f amp Grafiken 51 amp Grafiken bd 37 RECORD 1 6 B K Kurven 37 nECORD 2 8 K Kurven EZP UNITS 576 a 37 SETTINGS 7 z_status 1 37 SYSTEM MEN 3 ia E B t H bd m 4 a11 Objekt e 1 Objektfe markiert 8 biekt e Objekt e markiert i Copying the Diagnosis Screens via the Clipboard ProAgent User s Manual Issue 12 99 Step Four Configuring in ProTool To copy the diagnosis screens from the STEP 7 project ProAge
78. e e configuration and parameters required for connecting devices to the PLC and the network user data areas used for exchanging data between operating unit and PLC C 5 SIMATIC HMI Documentation Other PLCs Programmers Provides information on connecting devices to PLCs such as Mitsubishi Allen Bradley Online Help Telemecanique Modicon Omron SIMATIC WinAC When the drives are installed the relevant Online Help is installed at the same time ProAgent for OP Configurers Provides the following information about the ProAgent optional package process diagnosis for OPs e configuring system specific process diagnosis User s Manual detecting locating the cause of and eliminating process errors customizing standard diagnostic screens supplied with the software ProAgent User s manual C 6 Issue12 99 Siemens worldwide In this Appendix In this appendix you will find a list of All cities in the Federal Republic of Germany with Siemens Sales Offices and All European and non European Siemens Companies and Representatives Siemens Sales Offices in the Germany Federal Republic of Germany Aade Augsburg Bayreuth Berlin Bielefeld Bonn Braunschweig Bremen Chemnitz Darmstadt Dortmund Dresden Duisburg D sseldorf Erfurt Essen Frankfurt a M Freiburg Hamburg Heilbronn Karlsruhe Kassel Kempten Allg Kiel ProAgent User s Manual Issue 12 99 The following t
79. e configured with a show hide attribute or Removing Lines Chapter If you add new lines you must similarly configure a show hide attribute see Adding 343 Selecting and Scrolling TP only With a touch panel TP selecting and scrolling are performed by directly touching specific areas of the screen This means then that each screen contains hidden buttons in addition to the visible keys If you alter the way a diagnosis screen is laid out e g by adding lines or columns you must also adjust the size and position of these buttons accordingly see Adding or Removing Lines Chapter 8 4 3 Functions Linked to Screen Selection Specific functions that control important processes are linked to selection of the diagnosis screens Examples of the functions involved are ProAgent Switch Cursor ProAgent Identify Screen Type and ProAgent Specify Geometry You must not delete those functions ProAgent User s Manual Issue 12 99 8 5 Modifying the Diagnosis Screens 8 3 Internal Nomenclature Common Prefix ZP_ So that all the elements which affect process diagnostics are listed together in the different editors of ProTool all names begin with the abbreviation ZP The Z ensures that these elements are placed at the end of the lists in other words they appear after your own elements The P stands for ProAgent Since ProAgent is used in a large number of countries all over the world all names are in English
80. e fourth line the network numbers of networks appear that set the same operand You now have the information you need to correctly place the program code displayed Changing Display Mode i If you prefer to see the information displayed in symbol table format you can use this key to switch from LAD to symbol list display mode If you then press the corresponding key again the STL mode will be displayed If you then press the corresponding key again the display will return to the LAD mode The icon on the key always indicates the mode that will be shown next Deducing Information The ladder diagram shows the individual switches and operands The status bits are identified by virtue of the thickness of the line used to represent the switch e actuated switches are represented by bold symbols e disabled switches are represented by feint symbols With this information you can easily ascertain at what point your fault monitoring system gave the alarm and how the fault occurred Additional Actions Transitions and Networks You use this key to change to the next error in other words to the next fault AT y action of the unit 9i Use this key within the same fault to switch to the next transition or the next network that could have triggered this fault You will find details of this in the chapter called Changing the Action or Transition LAD Chapter 5 6 4 6 ProAgent User s Manual Issue 12 99 5 69
81. e g forward backwards up down Units are logical hierarchical criteria and structure the view of the process They may store data that is shared by all hierarchically subordinate objects Hierarchically subordinate objects can in turn be other units or movements for example Each unit can incorporate one or more actions Actions Actions are components of a unit Their purpose within the process is to control a single actuator In program terms an action is e a network in a LAD CSF STL program e astep ina S7 GRAPH program Transitions A transition describes a condition for progressing from one step to the next within a sequence of steps Transitions exist only in S7 GRAPH Movements Movements relate to sequences in the process that can be monitored with the aid of error definitions in the process diagnosis There can be several error definitions for each movement A movement can be contained within a unit and represents an actual movement on the part of a physical object within the process e g a die moves up and down Movements are defined in S7 PDIAG by using the UDT Movement within a block ProAgent User s Manual Issue 12 99 3 9 Effects on ProTool 4 Overview Installing the ProAgent option package adds a number of new menu options and functions to the basic ProTool program This chapter shows you what those new menu options and functions are and what their purpose is 4 1 Additional Menu Options in ProTool Installi
82. e output to another operating unit or control desk for example Conclusion 3 4 3 8 As you can see configuring a process diagnosis is not all complicated Thanks to the seamless integration of ProTool and ProAgent with the relevant STEP 7 option packages it need take only a few minutes If you should have very particular requirements in certain cases the open architecture allows you to easily adapt the functions to meet special demands Before You Start In order to be able to configure a process diagnosis certain basic requirements must be met They can be summarized as follows e ProTool must be installed integral with STEP 7 e ProAgent must be installed e The PLC must already be programmed with LAD CSF STL and S7 PDIAG or with S7 GRAPH both S7 PDIAG and S7 GRAPH can be used for a PLC e Ifthe PLC has been programmed in LAD FUP STL additional error detection blocks must have been created using the option package S7 PDIAG Error detection must have been activated e The PLC program must have already been compiled ProAgent User s Manual Issue 12 99 Introduction 3 5 Important Terms Units In S7 PDIAG a unit is a block in S7 GRAPH it is a sequence of steps Units are objects of the process diagnosis that are monitored with the aid of error definitions There can be several error definitions for each unit Units can be physical objects in the process e g a press or die which in turn can incorporate movements
83. e symbols as you require Do not however alter the order of the symbols relative to one another and do not shift symbols onto a different line 3 Set the value for hiding for all symbols You count from the extremities inwards starting from the far left moving to the far right and so on With 10 target positions for example the figures would be as follows from left to right 1 3 5 7 9 10 8 6 4 2 4 Alter the start value of the tag ZP_MCOLUMNS to the number of target positions now remaining for each movement Defining Filter Criteria Message Screen The Message Screen ZP_ALARM makes use of a truncated ProTool Message Page for the purposes of displaying messages see Message Window and Message Screen Chapter 6 2 4 You can filter the messages using the same filter function and filter criteria as you are familiar with in ProTool This is done with the Filter Messages function In addition to the known range of functions there is the Diagnostic Messages parameter That parameter can have the value 0 or 1 as follows e 0 Display all messages e 1 Display diagnosis messages only PV This key also invokes the filter function You can change the filter criteria of the function or assign other keys additional filter functions A detailed description of the function Message Filters is provided in the ProTool reference documentation A detailed description of the function Message Filters is provided in the ProToo
84. een programmed in S7 GRAPH you can use this key to the x d Step Screen and then set or reset individual steps of a sequence Exiting the Overview Screen You use this key to return to the Diagnosis Start Screen Or you can use this key to switch to the Message Screen There you can watch whether other faults occur ProAgent User s Manual Issue 12 99 5 25 Display on the Operating Unit 5 3 5 Changing the Display Mode Display Modes A V Ifyou are using an OP as your operating unit you can specify whether the cursor keys move the cursor in the Overview Screen one unit at a time or directly from one unit with a fault to the next To toggle between display modes use this key When to Use Which Mode Moving directly from one unit with a fault to the next is particularly useful if your system has a large number of individual units If however you wish to select a unit without a fault e g to execute a movement you must switch back to the display mode that allows you to select units with or without faults How to Tell Which Mode is Active 5 3 6 The display mode that is active at any particular time is indicated by a graphical symbol on the operating unit as follows A This symbol appears above the list of units when direct navigation between units with faults is active The symbol does not appear when the display mode which allows you to select units with or without faults is active Hierar
85. en to enable or disable one or more steps in the sequencer This means that you can specifically move individual system components as necessary in order to continue with the diagnosis or clear the malfunction Unit DB13 Conveyor belt 1 Step 12 Start conveyor belt Paras 12 13 5 18 2 14 7 p Mode Man Step no 12 Step name Start conveyor belt Step Screen As Shown on OP25 Selecting a step 5 32 One of the active steps of the unit selected on the overview screen is preassigned on the step screen To set or delete the step you want in the step sequence enter its number directly on the operator panel and confirm by pressing ENTER On a TP touch the input output field and enter the step number The name of the step then appears on the line below the input field ProAgent User s Manual Issue 12 99 Display on the Operating Unit Enabling a step hy If you wish to enable the step you entered press this key The number of the enabled step then appears on the third line of the step screen Disabling a step ox If you wish to disable the step you entered press this key The number of the step is deleted from the corresponding line of the step screen Deactivating all steps aX If you wish to disable all steps press this key The numbers of the steps are deleted from the corresponding line of the step screen Enabling an initial step my Ifyou wish to ena
86. end the display by a line increase the index by one increment Example On the Overview Screen ZP_UNITS on the OP25 7 units are displayed on 7 lines The tags used for the input output fields include ZP_UUNIT_NAO ZP UUNIT NA1 to ZP UUNIT NAG The tags are assigned the following tag indices in ascending order Tag Index ZP_UUNIT_NAO 1 0 3 0 ZP_UUNIT_NA 1 1 0 3 1 ZP_UUNIT_NA6 1 0 3 6 The number of lines is 7 ProAgent User s Manual Issue 12 99 8 3 Modifying the Diagnosis Screens If you now want to add an extra line to the display and require a new tag for the input output field it makes sense to give it the name ZP_UUNIT_NA7 For that tag you must then configure the function ProAgent Set Tag Index using the index values 1 0 3 7 Consequences Since the indices increase incrementally in ascending order you must not alter the order of individual fields and lines within a screen When deleting individual elements you should always start deleting from the end bottom Line Number and Column Number The number of lines and columns on the individual diagnosis screens has to be stored as the start value of certain tags The value of those tag tells the operating unit how many input output fields there are to be supplied with data The following tags are of significance to the various diagnosis screens ZP_ProAgent Diagnostics Start Screen ZP_ALARM Message screen ZP_UNITS ZP_UACT_MAX Max number of
87. ens in existing projects too There are essentially two ways to link your own screens in an existing project to the new standard screens instead of the old ones Which of these ways is the better for you depends on the layout of your old project Upgrade for Projects with a Large Number of Global Settings If your project contains a large number of global settings e g for alarm messages event messages or for printer parameterization that you wish to retain delete all the old standard screens the tags and text or graphic lists You recognize the elements that belong to diagnostics by the ZP_ at the beginning of the name Only once you have made these deletions are you able to copy the relevant new elements into your project 1 Open you existing project 2 To delete the screens you have to release the existing links first To do this select the screen in question and call the menu item View gt Cross reference The Cross reference dialog window then displays all the links of the screen selected 3 Double click the first reference element with an oval border The screen in which the link is located opens The element with which the standard screen is linked is marked 4 Delete the link Proceed in exactly the same way for the remaining cross references and screens 5 In the project window select all the screens and delete them 6 If necessary delete for a second time any screens that may have not have been deleted f
88. erating and monitoring device Its central function therefore is to provide the user with an easy to use interface by means of which it is possible to identify process faults at a glance and rectify them quickly Ready Made Diagnosis Screens 6 8 When ProAgent is installed ready made diagnosis screens for the various types of operating unit are stored in the appropriately named STEP 7 projects They need only to be incorporated into your configuration in order to be ready for use Names of projects Since ProAgent is used in many different countries around the world the standard diagnosis screens supplied have been given English names as follows Mame piagrosisseren o y ZP_PROAGENT Diagnosis Start Screen ZP_UNITS Overview Screen ZP UNITS S7G Alternative overview screen for S7 GRAPH ZP DETAILSYM Detail Screen signal list format ZP_DETAILAWL Detail Screen STL display mode ZP_DETAILLAD Detail Screen LAD display mode ZP_STEP Step Screen Names of the Diagnosis Screens ProAgent User s Manual Issue 12 99 A Configuring in ProTool Caution Only adopt the diagnosis screens in your project if you actually want to be able to carry out process diagnoses When the diagnosis screens are downloaded to the operating unit the full range of diagnosis functions is automatically downloaded as well This will use up system resources even if you do not use those functions at all Easy to Adapt It goes without saying
89. erating mode For example you can switch from Automatic to Manual mode in order to be able to rectify a fault manually Once you have selected a unit you can analyze it in more detail on the Detail Screen and then switch to the Movement Screen to execute individual movements manually in order to rectify the fault A description of the Detail Screen is given in the chapter Detail Screen Chee oh A description of the Movement Screen is given in the chapter Movement Screen Chapter 5 5 Alternative Overview Screen for S7 GRAPH If your system has units programmed in S7 GRAPH your project can use a slightly modified version of the standard overview screen in which you can see the step name as well Operation is largely the same as with the standard overview screen which is described in the sections that follow A summary of differing special features will be found in the chapter called Alternative Overview Screen for S7 GRAPH Chapter 5 3 7 ProAgent User s Manual Issue 12 99 5 19 Display on the Operating Unit 5 3 2 What You See on the Overview Screen General Layout Like all the diagnosis screens the Overview Screen has a standardized layout There are only minor differences between the various types of operating units The illustration below shows an example of the Standard Overview Screen as it appears on an OP25 os 4 Anit DB13 7 Conveypf belt 18 step MZ Start conveyor belt om v c t 2 14 do B O
90. ers may also be followed by a full stop followed by the number of decimal places to be shown In the example above one decimal place is specified for the second process data item If the number of decimal places is not specified no decimal places are shown Finally the last parameter determines how the value to be displayed is interpreted and represented In the example above the first process data item is represented as a decimal number and the second as a fixed point number ProAgent User s Manual Issue 12 99 7 11 Message Processing The following data types are permissible ID Code Data Type Max Representable Range Decimal with plus minus 2147483648 2147483647 sign Decimal without plus minus 0 4294967295 sign E 0 FFFFFFFF Fixed point with plus minus 2147483648 2147483647 sign i Example 8 2f produces the following Value of tag 1234567 Output 12345 67 Binary 0 11111111111111111111111111111111 ProAgent User s Manual 7 12 Issue 12 99 7 4 Message Processing Incorporating ALARM_S Messages Incorporating When Configuring Messages in STEP 7 the message text and attributes entered are stored in the database shared with ProTool During the process of compiling the project ProTool automatically imports the necessary data and subsequently downloads it to the operating unit Shared database
91. et position does not necessarily mean that the maximum physical limit of movement has been reached If a target position has not yet been reached it is shown as an empty rectangle If a target position has been reached or passed the symbol appears as a solid rectangle Note For the different devices you will see explanatory text for each target position below the symbols if stored in the PLC program 8 The triangle in the margin of the movement shows you whether a movement can be executed If the movement can be executed the triangle appears as a solid area If the movement can not be executed either because it is blocked or because it is locked by a locking condition e g furthest target position already reached the triangle appears in outline only 9 The rectangle next to the triangle flashes while the movement is being executed 10 If there are more movements than can be displayed on the display you can scroll the list of movements up or down v 2 You recognize this by the fact that one of these symbols appears on the left next to the unit ProAgent User s Manual Issue 12 99 5 37 Display on the Operating Unit 5 5 3 Movement Screen Keys You can use the following keys on the Movement Screen Side keys The keys at the sides are used to activate the individual movements A movement can only be executed if the associated triangle symbol appears with a solid inner area If the symbol appears in outli
92. eter ProAgent User s Manual Issue 12 99 Modifying the Diagnosis Screens 4 f necessary assign a password level to the button on the Enable tab so that only authorized persons are able to use it ProTool interprets the number entered in step 4 as a PROFIBUS bit number if all of the following conditions are met at the same time e You have installed that is integrated ProTool at the time of generating the configuration e During operation the TP is connected to a SIMATIC S7 by means of PROFIBUS DP e You have defined the bit area for direct keys in STEP 7 and the corresponding bits are set in the PLC Examples of how to program direct keys for various purposes can be found in the User s Manual entitled S7 PDIAG If not the number entered is interpreted as a port number for the direct key module If the number is greater than the number of ports available an error message is output during generation Caution In order to ensure safe operation of the installation when using direct keys you should query the screen number in the PLC as the condition for triggering direct key To this end use the PROFIBUS Screen Number function to transmit the screen number to the PLC at the same time as the direct key Further information about this function can be found in the Online Help for ProTool 8 6 3 Using Direct Keys OP Movement Screen You can use the F and K keys in the OP movement screens ZP_MOTION as direct keys and i
93. ether or not the system limits are complied with is explained by the calculation example ProAgent User s Manual Issue 12 99 Appendix System Limits B 3 DRAM Requirement of the Project Components On a number of operating units e g the OP 25 only 1 Mbyte of the DRAM is available for projects Projects that are to run on these operating units must therefore require no more than 1 Mbyte of DRAM Irrespective of the layout of the project there is a fixed basic requirement for memory since certain components must always be integrated into any project Operating system 1 Mbyte Basic configuration standard 200 kbytes ProTool ProAgent screens Maximum basic requirement 200 kbytes for diagnosis Depending on your diagnosis project STEP 7 the basic requirement for the diagnosis can also be below 200 kbytes More far reaching configuration data for visualization of the installation have not been taken into account in the basic requirement The amount of memory your project will require on top of the basic requirement depends on which and how many of the components listed below you use Component Maximum number Requirement per component User diagnosis texts 1 600 texts 7 PDIAG maximum of 40 characters per unit 1 byte per character network movement maximum of 40 bytes and target position monolingual text S7 GRAPH 1 byte per character maximum of 40 i e maximum of 40 bytes characters per step monol
94. f subordinate or superior units are present On an OP you use the ENTER key to open the text or graphic list for selecting the operating mode On a TP simply touch the operating mode on the Screen to open a selection window that contains the associated text or graphic list This key is used to change the Display Mode This determines whether the cursor moves through all units or only between units with faults ProAgent User s Manual 5 22 Issue 12 99 Display on the Operating Unit This key is used to switch to the Step Screen This key is used to switch to the Message Screen This key is used to switch to the Detail Screen You must first have selected a faulty unit You use this key to switch to the Movement Screen Overview Screen Keys 5 3 4 How to Work with the Overview Screen This chapter gives a general outline of how to use the Overview Screen most effectively in practice Aims You use this key to return to the Diagnosis Start Screen You have opened the Overview Screen to see on which units of your system there are faults You want to see which unit caused the problem and what triggered it Finally you want to be able to move specific system components in order to rectify the fault Unit DB13 Conveyor belt 1 step 12 Start conveyor belt Bara 12 13 2 14 7 Mode Man Fnit b A Action Mode Press 1 5 Auto mgeonveyor belt 1 Dress z 23 Auto AConveyor belt 7 7 A
95. ferent pictograms or colors change the soft key assignments and restrict the use of certain functions by password protection Designing Your Own Screens You will only need to create your own diagnosis screens or merge diagnosis screens with other screens on your system in very rare cases In principle this is possible but a diagnosis screen must always be used as the master As the next step you can then delete all elements that you do not require Following this procedure ensures that all functions required for diagnosis are present e g ProAgent Switch Cursor ProAgent Identify Screen Type and ProAgent Specify Geometry Fundamental Rules The fundamental rules can be summarized as follows e Always modify existing diagnosis screens do not create completely new diagnosis screens Do not copy elements from a diagnosis screen to a system screen instead where necessary copy elements from a system screen to a diagnosis screen e Itis not possible to combine several diagnosis screens or elements from them into a single screen For example you can not combine the functions of the Overview Screen and the Movement Screen or the Overview Screen and the Detail Screen to form a single screen Each screen is assigned a specific screen type by means of the function ProAgent Identify Screen Type andis thereby allocated a quite specific task within the diagnosis system e Observe the limitations on cursor control resulting from the
96. follows 1 Incorporating the Diagnosis Screens To begin with you import the supplied standard diagnosis screens into your project You can copy them simply by the Drag amp Drop method or via the Clipboard If you are using S7 GRAPH units in your project and would like to see the step names of the units displayed on the overview screen replace overview screen ZP_UNITS with the alternative overview screen ZP_UNITS_S7G refer to Replacing the overview screen Chapter 6 1 9 Note Note that the PLC name of the ProAgent project has to be identical with one of the PLC names in the destination project If necessary modify one the names accordingly Linking the Diagnosis Screens In order to be able to activate the diagnosis screens once they have been incorporated you must assign one or more keys the appropriate screen selection function s Selecting the Units This next step involves selecting the units of your system for which you wish to be able to carry out a process diagnosis You will receive detailed information for these units only Selecting the display classes Finally you can restrict the display of fault messages to specific display classes Compiling and Downloading Once configuration is complete compilation and transfer to the operating unit is carried out as usual ProAgent User s Manual Issue 12 99 6 7 Configuring in ProTool Incorporating the Diagnosis Screens An OP or TP is an op
97. found in the User s Manual entitled Communicationand about that for TPs in the Equipment Manual entitled Touch Panel TP27 TP37 Basic Requirements The operating unit is equipped with a direct key module and the PROFIBUS direct keys are not configured The number of ports that can be configured depends on the device OP25 OP27 TP27 6 8 1 8 OP35 OP37 TP37 TP 27 10 16 1 16 Each direct key module for OPs is equipped with 8 ports If you want to be able to configure 16 ports on an OP35 or OP37 the OP must be equipped with two direct key modules Configuring Direct Keys TP Movement Screen You can use direct keys in the Movement Screen ZP_MOTION to trigger movements without communication related delays To this end you have to assign the function Direct Key together with the function Set Bit to those buttons that are to be used to trigger the movements You can also use this function to set assignment of the pressed key and set bit To use a button on the TP as a direct key 1 In the open screen select the button to which you want to configure a direct key If the hidden buttons are not displayed Use the Display hidden buttons key to display the Select and Scroll buttons in the diagnosis screen for the TP The Button window opens 2 Assign the function Direct Key from the Keyboard group to the button 3 Specify the port number or the number of the bit that is to be set when the button is touched as the param
98. g by Diagnosability 5 3 Overview Screen 5 3 1 The Purpose of the Overview Screen 5 3 2 What You See on the Overview Screen 5 3 3 Overview Screen Keys 5 3 4 How to Work with the Overview Screen 5 3 5 Changing the Display Mode 5 3 6 Hierarchical Units on the Overview Screen 5 3 7 Alternative Overview Screen for S7 GRAPH 5 4 Step Screen 5 4 1 What is the Step Screen Used for 5 4 2 What You See on the Step Screen 5 4 3 Keys on the Step Screen 5 4 4 How to Work with the Step Screen 5 5 Movement Screen 5 5 1 The Purpose of the Movement Screen 5 5 2 What You See on the Movement Screen 5 5 3 Movement Screen Keys 5 5 4 How to Work with the Movement Screen 5 5 5 Hierarchical Units on the Movement Screen 5 6 Detail Screen 5 6 1 The Purpose of the Detail Screen 5 6 2 Detail Screen as Signal List 5 6 3 Detail Screen in STL Format 5 6 4 Detail Screen in LAD Format 5 6 5 Enhanced Possibilities with S7 PDIAG ProAgent User s Manual ii Issue 12 99 Contents s 6 Configuring in ProTool 6 1 Configuring a Process Diagnosis 6 1 1 Basic Requirements of the PLC Program 6 1 2 Shared Database with STEP 7 6 1 3 Overview of Configuration Steps in ProTool 6 6 6 1 4 Incorporating the Diagnosis Screens 6 8 6 1 5 Linking the Diagnosis Screens 6 12 6 1 6 Selecting the Units 6 1 7 Selecting the display classes 6 1 8 Compiling and Downloading 6 20 6 1 9 Replacing the Overview Screen 6 1 10 Porting onto Computers without STEP 7 6 2 Special
99. ge Processing Process Data in the Message Text A message can include dynamically updated process data associated data For example in the message Furnace 1 temperature 10 5 degrees too high the figures 1 and 10 5 are process data Each ALARM_S message can supply one item of process data That item of process data can however consist of an array of data so that in practice more than one item of data can be communicated An array can contain a maximum of 12 bytes of usable data Whether and which process data is available depends on the PLC program S7 GRAPH always automatically offers one item of process data When programming in LAD CSF STL you must create the necessary program code yourself S7 PDIAG does not provide any process data Syntax for Process Data You can insert process data at any point within a message by using special syntax Every call of a process value starts and ends with a Between these two characters are parameters specifying the value that will be output and the manner in which output will be formatted A maximum of four items of data can be included in each message Example The message Furnace 1W S1ld temperature 3W 4 1f degrees too high might for example actually appear on the operating unit during operation of the system as Furnace 1 temperature 10 5 degrees too high The figures shown in this case 1 and 10 5 represent the current process data Element Referenced The
100. gt 1 Time v Monitoring Active C 4 Edge150 5000 m Criteria Analysis IV Initial Value Acquisition C Positive Citera Analysis Negative Criteria Analysis Message Number Priority Text fi No part arrived within monitoring period Message lontiquration C Sombolie Hame IV With Acknowledgement Symbol eoriment Configure Cancel Help Configuring Simple Message Texts ProAgent User s Manual Issue 12 99 Message Processing If you have no special output requirements for the message all you need to do is enter the message text in the Text box If however you wish to make use of the particular display capabilities of your operating unit you can click the Configure button to define a display specific message configuration The Special Object Properties Message dialog box then opens As soon as you have selected a message from the list you can specify general attributes for that message such as Display Classes and Acknowledgement Method Those attributes are globally valid i e they are not exclusive to a specific display unit Special Object Properties Message Jv Message m SEITE General Attributes In order to be able to specify attributes for a specific display unit you must first create the display unit To do so click the New Device button ProAgent User s Manual Issue 12 99 7 7 Message Processing 7 8 The nsert Display Unit dialog box
101. guration e a detailed description of configurable objects and functions This documentation is valid for Windows based systems ProTool Configurers Provides information on working with m the ProTool configuration software It Configuring A contains Graphics Displays e information on installation User s Guide basic principles of configuration e a detailed description of configurable objects and functions This documentation is valid for graphic display operating units ProAgent User s manual C 2 Issue12 99 SIMATIC HMI Documentation ProTool Configuring Text based Displays User s Guide ProTool Online Help ProTool Pro Runtime User s Guide Copy Protection Start up Guide ProAgent User s manual Issue12 99 Configurers Configurers Commissioning engineers Users Commissioning engineers Users Provides information on working with the ProTool Lite configuration software It contains e information on installation basic principles of configuration e a detailed description of configurable objects and functions This documentation is valid for text based display operating units Provides information on the configuration computer while working with ProTool Online Help contains context sensitive help detailed instructions and examples detailed information all the information from the user guide Provides information on working with ProTool Pro Runtime software It con
102. have sufficient space click the Next button All the languages you configured for ProTool are configured automatically Installed Files The installation program copies the necessary program files to the folder specified In addition a further folder called PROAGENTNSTANDARD is created beneath this folder Here you will find a STEP 7 project with the supplied standard diagnosis Screens ProAgent User s Manual 2 2 Issue 12 99 Installation Symbols on the Taskbar ProAgent does not have a program icon of its own All ProAgent s functions are accessible only through ProTool Nevertheless two new logical links are added to the Windows Start menu You use this symbol to call ProTool s online documentation It contains all the information described in the User s Guide ProAgent for OP You use this symbol to open an electronic document containing a graphic introductory example This example guides you through getting started with S7 PDIAG and ProAgent for OP ProAgent and therefore helps to get you going Example Description To view this example you need the program Acrobat Reader If the program has not yet been installed on your system you can install it from STEP 7 s Setup Up to date Information You will find late breaking information on ProAgent in the Readme txt files Please note all the tips mentioned in that file 2 3 Uninstalling ProAgent You can uninstall ProAgent in the customary manner under Wind
103. he directions in which you can move the cursor 17 A lightning flash symbol appears here is partial view is active this shows only those switches that have led to an alarm message see Toggling Between Partial and Full View LAD Chapter 5 6 4 4 18 A spectacles symbol appears here if the current status is displayed rather than the status at the time of occurrence of the faults initial values see Toggling Display of Initial Values and Current Status LAD Chapter 5 6 4 5 ProAgent User s Manual 5 66 Issue 12 99 Display on the Operating Unit 5 6 4 2 Detail Screen Keys LAD You can use the following keys on the Detail Screen in LAD display mode On an OP you can use the cursor keys to move the cursor though the network displayed On the left above the ladder diagram appears a small arrow for each direction in which you can move On a TP you can select a switch simply by touching it To scroll on an OP move the cursor past the edge of the display The screen is moved and regenerated accordingly To scroll on a TP touch the outermost switch in the scroll direction until the scrolling is activated On an OP you can use the ENTER key to open a list for selecting whether symbols or remarks relating to the individual instructions are to be displayed device dependent On a TP you can open the same list by touching the display This key is used to toggle between partial and full view see Toggling Between
104. he subnetwork which Manual mode is handling is not causing an error by definition since the system is already in Auto mode and cannot be in another mode simultaneously By taking this additional knowledge into account the substantially clearer error identification results in the lower section of the program Display by ProAgent As a result of definition of the exclusion operands fewer lines are identified as causing the error ef This key is used to toggle between full and partial view see Toggling Between Partial and Full View e With non partial display all the lines are still visible but fewer lines are marked with the lightning flash symbol as causing the error e Correspondingly fewer lines are displayed at partial view In either case transparency is far greater and analysis is facilitated ProAgent User s Manual Issue 12 99 5 77 Configuring in ProTool 6 Overview 6 1 6 1 1 This chapter shows you in detail how you incorporate a process diagnosis in a new project or how you can upgrade an existing project to include process diagnosis Configuring a Process Diagnosis Basic Requirements of the PLC Program In order to configure a process diagnosis both the PLC and the operating unit must be configured ProTool and ProAgent can only be used for configuring the operating unit As a basic requirement ProTool plus ProAgent requires a diagnosable PLC program Programming Language The
105. hen control your system in the normal way In addition you configure a key which can be used to start the diagnosis package as you would a subroutine The key in question activates the Diagnosis Start Screen from where you can then access all other diagnosis screens Advantage the project is very easy to create and maintain Operation is largely separate from operation of the system Disadvantage the indirect route to the diagnosis functions via the Diagnosis Start Screen is not as straightforward from the operator s point of view as direct selection of the diagnosis screens System Diagnosis Start Screen g UNS Diagnosis Access to Diagnosis Functions via Diagnosis Start Screen To configure a screen selection function for the Diagnosis Start Screen proceed as follows 1 Configure the function Select Screen and assign it to a key 2 As the function parameter select ZP PROAGENT When subsequently the key concerned is pressed it opens the Diagnosis Start Screen from where all other diagnosis screens can be accessed by means of keys You must also make sure that you provide a means of returning from the Diagnosis Start Screen ZP_PROAGENT to your own screens To do so you should assign at least one key an appropriate screen selection function You can use the symbol ZP ESC as the pictogram Caution Do not use the Select Previous Screen function As this function only goes
106. hes between areas 4 to 11 depending on whether the unit has been programmed with S7 PDIAG or with S7 GRAPH 1 This shows the block type of the unit with the fault i e FC DB or OB 2 This field shows the block number of the unit with the fault At this point text assigned to the unit appears the symbol for a block or an absolute identifier If the unit has been programmed with S7 GRAPH lines 2 to 4 of the display have the following contents 4 This field identifies the step selected by means of the test Step This field displays the user number of the step selected This field displays a text that is assigned to the step displayed under 5 5 6 7 This field displays the module in which the network was configured 8 This field displays the text Transi for Transitions 9 This field displays the numbers of the transitions of the step displayed The transition displayed is highlighted in inverse type If step monitoring view is displayed rather than a transition then accordingly the step number is highlighted 10 This field displays the text Tr Name for Transition Name The field remains blank if the locking condition of the step is shown 11 This field displays the name of the transition displayed The field remains blank if the locking condition of the step is shown If the unit has been programmed with S7 PDIAG lines 2 and 3 of the display look as follows Unit B13 bel ON Network 12
107. however in the Movement Screen This is configured in the screen editor by choosing the menu option Edit gt Properties Functions Set the Mode parameter appropriately for the ProAgent Define Enabling of Movements function e Fora TP Mode 1 automatic enabling of all movements e Foran OP Mode 0 only the selected movement is enabled Under the Duration parameter set the number of seconds after which the screen element is to be automatically deselected and under Conditions select Select Screen Note When working with an OP make sure you use the Movement Screen of the latest version of ProAgent since changing of the default settings is only provided for in this version Instructions on how to adopt the latest diagnosis screens supplied with the upgrade into existing projects can be found under Upgrading Existing Projects to New Diagnosis Screens Chapter 6 2 3 Further Steps To Be Taken With A TP When you are configuring for a TP you also have to adjust the Selection and Scroll buttons All that is now required are two Scroll buttons in the centre of the display similar to the Detail Screen STL The buttons on the left and right above the arrows which trigger the movements must of course be left unchanged Proceed as follows 1 Delete the bottom buttons in the centre of the display until only the top two buttons remain 2 Use the mouse to enlarge the lower button so that it covers the second line and all other l
108. iagram below shows the chronological sequence of all steps to be completed when configuring a process diagnosis Plan the system Z Program the PLC Add monitoring routines Configure messages Translate program EU Incorporate the diagnosis screens Link the diagnosis screens Select displayed messages Compile and download Configuration Steps for Process Diagnosis Tip A special breakdown of the steps required when upgrading an existing configuration is given in the chapter Overview of the Steps Required When Upgrading Chapte 6 2 2 Requirements of the PLC Program 6 6 As universal system tools ProTool and ProAgent are closely compatible with the STEP 7 software A breakdown of the minimum requirements to be satisfied by the PLC program is given in the chapter Requirements of the PLC Program Chapter 6 1 1 In order that you do not have to define the same data more than once the system uses a common database as an interface As a general rule therefore the PLC program should already exist and have been translated before you start working in ProTool A list of which steps should have been completed in STEP 7 at what point is given in the chapter Shared Database with STEP 7 Chapte 6 1 2 ProAgent User s Manual Issue 12 99 Configuring in ProTool Configuration Steps in ProTool The process of configuration in ProTool requires only a few operations as
109. ial values In addition you can also inquire the current status Viewing the current status allows you to monitor online what effect corrective measures have on the condition of the system This allows you to recognize immediately when the fault is corrected signals are no longer shown on the display ud To toggle display of initial values and current status use this key e When the display mode is set to current status this symbol appears above the statement list ProAgent User s Manual Issue 12 99 Display on the Operating Unit 5 6 2 5 Switching to action or transition Signal List You can easily switch to other actions steps and transitions simply by pressing a key Changing Action A unit may have more than one fault at the same time Use key combination to switch to the next fault in the same unit The action of the unit affected by this fault will be displayed A Press this key to switch to the next fault Display of the steps and transitions in the top section of the screen then changes accordingly see What You See on the Detail Screen Signal List Chapter 5 6 2 1 Note Once all actions of a unit have been run through and the unit concerned has other hierarchically subordinate units the function moves on to the actions of those units This means that you do not need to return to the Overview Screen and select a hierarchically subordinate unit there in order to be able to see the action
110. ied in ProTool default setting 10 is reached an overflow warning is automatically issued Deleting Message Events In the Event of a Buffer Overflow If the message archive has insufficient space to accept any more message events message events are automatically deleted until the specified remaining buffer capacity is reached Deletion is carried out in the following order 1 The oldest departed messages For departed event messages the message events arrival and departure are deleted For departed alarm messages the message events arrival departure and acknowledged are deleted 2 Pending messages The oldest pending messages are deleted to make space for the newly received events Printout If Buffer Overflow Message Logging has been specified and a printer is connected and switched on all deleted alarm and event messages are printed out in the event of a buffer overflow ProAgent User s Manual 7 20 Issue 12 99 Modifying the Diagnosis Screens 8 Overview This chapter provides detailed background information on how you can modify the standard diagnosis screens where necessary and adapt them to specific requirements 8 1 Modifying the Diagnosis Screens Introduction Standard Screens The standard diagnosis screens supplied with ProAgent enable you to perform all diagnosis tasks easily without having to bother with configuration yourself You should take advantage of that opportunity and only make alte
111. ifferent units Procedure In order to replace the standard overview screen ZP_UNITS with the alternative overview screen ZP_UNITS_S7G perform the following steps 1 If not already available copy screen ZP_UNITS_S7G to your project from the STEP 7 ProAgent project subdirectory called PROAGENT STANDARD On the screens ZP PROAGENT and ZP ALARM modify the screen selected by the Overview Screen key from ZP UNITS to ZP UNITS S7G Since there are fewer lines available on the alternative overview screen for S7 GRAPH than on the standard overview screen you have to change the start value of the ZP UROWS tag background information on the significance of this type of start value can be found in the chapter called Modifying Diagnosis Screens Chapter 6 Select the Tags object type in the project window and right click on the ZP_UROWS tag Choose the Properties option from the shortcut menu and change the start value in the dialog box that opens on the Options tab in the following manner OP25 OP27 C7 626 TP27 6 Start value 3 OP35 OP37 TP27 10 TP37 Start value 8 4 Delete the ZP_UNITS screen 6 22 ProAgent User s Manual Issue 12 99 6 1 10 Configuring in ProTool Porting onto Computers without STEP 7 Computers without STEP 7 AN It may be that you have only installed ProTool plus ProAgent and STEP 7 on your workstation PC but would like to take a finished project to a machine location on
112. inate units are shown To hide the movements for subordinate units again press the same key again ProAgent User s Manual Issue 12 99 5 41 Display on the Operating Unit 5 6 5 6 1 Detail Screen The Purpose of the Detail Screen Analysis of Criteria Retracing an error to the relevant points in the program code is referred to as analysis of criteria The Detail Screen shows the results of the analysis of criteria Signal list STL or LAD Depending on the configuration the diagnosis result is initially displayed in a signal list restricted to the most essential items in a detailed instruction list STL or as ladder diagram LAD A key allows you to switch easily between the three display formats Note Both Detail Screen display formats are basically the same in effect but they differ in the way in which the information is presented and how they are used For that reason they are described in separate chapters The LAD display format does not allow all commands to be represented however The following are permissible U op UN op U O op ON op O O NOT op S op R op X X XN XN Label op operand Label only at start of network U corresponds to A in IEC display mode If a command which can not be represented in LAD format needs to be displayed a system message appears You can then use the key to switch to the signal list display Program Excerpt 5 42 The display of the STEP 7 program c
113. ines below it 3 Select the ProAgent Scroll Display function for both buttons and and then click Events for both buttons 4 Activate the Press key check box 5 Delete the ProAgent Select Screen Element function for both buttons You can now scroll the Movement Screen in the same way as you are used to doing with the Detail Screen STL ProAgent User s Manual Issue 12 99 8 13 Modifying the Diagnosis Screens 8 4 7 Changing the Number of Target Positions Movement Screen The Movement Screen ZP_MOTION normally shows 8 target positions for each movement Depending on your system however there may be more or perhaps fewer target positions than that ProAgent supports up to 16 target positions for each movement Adding Target Positions 8 14 To add extra target positions on the Movement Screen you must work line by line This is important because the individual fields are configured with functions organized on a line by line basis 1 Shift the existing target position symbols to the left until there is enough space on the right for an extra symbol 2 On the line you are modifying copy the far right target position symbol to the Clipboard Paste the copy in the empty space Double click the symbol to edit the input output field Under Tag open the menu and select Duplicate Then select Edit from the same menu NO O KR OW In the dialog box for entering the tag parameters select the Funct
114. ing for all keys is no password protection password level 0 By altering the password level you could for example prevent an operator e selecting specific screens e setting the operating mode on the Overview Screen e executing movements on the Movement Screen You set the password level in exactly the same way as you are familiar with in ProTool Multi Language Projects All text that appears on the diagnosis screens is basically stored in multi lingual form provided that facility is supported by STEP 7 When the function Language is executed the screen is reconstructed in the relevant language Most text items are not configured in ProTool but provided by the S7 packages Conflicts can occur if no text items have been defined in STEP 7 for the language configured in ProTool A warning message to that effect is then issued during the compilation process in ProTool When the system is running the text is shown in the default language For more details of configuring in different languages please consult your User s Manual entitled Configuring ProTool Graphics Displays ProAgent User s Manual Issue 12 99 Modifying the Diagnosis Screens 8 5 3 8 5 4 8 18 Configuring a Unit Acknowledgement Unit acknowledgement should not be confused with message acknowledgement For each unit there is one bit on the PLC which can be used for acknowledging the unit That bit can be set with the aid of the function ProAgent Acknowledge
115. ingual sequence step and transition Analysis of Criteria 24 000 criteria Basic requirement per criterion 15 bytes Remark texts 1 byte per character maximum of 40 maximum of 40 bytes characters monolingual 1 byte per character Symbolism texts maximum of 40 bytes maximum of 40 characters ProAgent User s Manual Issue 12 99 B 3 Appendix System Limits B 4 Alarm messages 2 000 alarm messages Texts maximum of 1 byte per character 80 characters maximum of 80 bytes monolingual Help texts 1 byte per character maximum of 245 maximum of 245 bytes characters monolingual In multilingual projects you must multiply the memory requirement for the texts by the number of languages What you therefore have to know for your project is the e number of components e type of components e scope of the associated texts On the basis of this you can approximately estimate whether the memory of your operating unit is large enough for the planned project The calculation example can serve as a sample ProAgent User s Manual Issue 12 99 Appendix System Limits B 4 How Can You Save on Memory Space If your configuration requires more memory space than is available on the operating unit being used make the texts shorter If your configuration still won t fit in the memory of the operating unit the only option left open to you is to use an operating unit with a larger memory B 5 Calculation E
116. ins installation and commissioning instructions operating unit description connecting the PLC printer and programming computer operating modes operation description of the standard screens supplied with the operating unit and how to use them fitting options maintenance and fitting of spare parts ProAgent User s manual Issue12 99 SIMATIC HMI Documentation OP3 Equipment Manual PP7 PP17 Equipment Manual Communication User s Manual Communication for Windows based Systems User s Manual ProAgent User s manual Issue12 99 Commissioning engineers Users Programmers Commissioning engineers Users Programmers Programmers Describes the hardware of the OP3 its general operation and the connection to the SIMATIC S7 Describes the hardware installation and commissioning of push button panels PP7 and PP17 Provides information on connecting text based and graphics displays to the following PLCs e SIMATIC S5 e SIMATIC S7 e SIMATIC 500 505 e drivers for other PLCs This documentation describes the e configuration and parameters required for connecting the devices to the PLC and the network user data areas used for exchanging data between operationg unit and PLC Provides information on connecting Windows based systems to the following PLCs e SIMATIC S5 e SIMATIC S7 e SIMATIC 505 e Allen Bradley PLC 5 SLC 500 This documentation describes th
117. ion Sequence Logging On For ALARM_S More than one station e g more than one OP PU etc on a network can log on for ALARM_S messages Each station that wants to display ALARM_S messages logs on to the CPU for ALARM_S S7 S7 CPU CPU OP TP PU MPI Network When A Message Event Occurs When a message triggering event occurs the CPU actively sends telegrams to that effect to all stations that have logged on The message number identifies the corresponding message text that has previously been downloaded to the operating unit This means that the CPU does not have to be actively scanned for messages by regular polling as was the case with the message bit procedure The operating unit CPU and network are completely relieved of that burden on the system Time Stamp With the ALARM_S procedure the time stamp is not issued by the operating unit but by the CPU The messages are stored in chronological order on the basis of their time stamp in the message buffer on the operating unit even if they originate from different CPUs Information Stored The CPU stores not only the time of the message but also the status arrived departed acknowledged and any process parameters That information is retained until a message has been completely processed i e until it has arrived departed and been acknowledged On the operating unit the information in the mes
118. ions tab then under Selected Functions click the item ProAgent Set Tag Index and then click the Parameters button 8 In the Parameters dialog box position the cursor on Index 4 and increase the value specified by 1 9 Finally close all open dialog boxes by choosing OK 10 Repeat steps 1 to 9 until you have the desired number of target positions on the line you are modifying 11 Set the value for hiding for every symbol on the line You count from the extremities inwards starting from the far left moving to the far right and so on With 10 target positions for example the figures would be as follows from left to right 1 3 5 7 9 10 8 6 4 2 12 Repeat the complete process for all other lines until there are the same number of target positions on each line 13 Finally you must set the start value of the tag ZP_MCOLUMNS to the number of target positions defined for each movement That start value tells the operating unit how many target positions there are to be supplied with data ProAgent User s Manual Issue 12 99 Modifying the Diagnosis Screens Deleting Target Positions 8 4 8 You do not normally need to delete excess target positions as they are automatically hidden if they are not needed If you nevertheless want to delete surplus target positions proceed as follows 1 Delete the surplus target positions from each line starting from the right All lines must have the same number of target positions 2 Shift th
119. irst time round 7 In the project window delete all the tags of the standard screens You recognize these by the ZP at the beginning of the tag name 8 Double click the tags that cannot be deleted straight off 9 In the Tag window delete the function s that use the tag 10 Delete all the tags that have been left in the project window 11 Delete the text or graphic lists in the project window 12 Copy the standard diagnosis screens of the new version of ProAgent to the project The tags functions and text or graphic lists required are copied in the process Detailed instructions on how to copy screens can be found under Integrating the Diagnosis Screens Chapter 6 1 4 13 Now remake the links between the new diagnosis screens and your project ProAgent User s Manual Issue 12 99 6 27 Configuring in ProTool Upgrade for Projects with a Small Number of Global Settings 6 2 4 If you project contains only a small number of global settings it is easier to merge your own old screens with the new diagnosis screens in a new project The global settings e g for alarm messages event messages or for printer parameterization of your old project are however lost in the process and have to be entered into the new project manually 1 Create a new project under menu item File gt New 2 Assign the same PLC name as you have already used in the project you want to link to the new diagnosis screens 3 Copy the standard diagnosi
120. is Start Screen The way in which you start the diagnosis depends on the Project concerned In the simplest case there is a key that is used to activate the diagnosis start screen From there you can then move to other diagnosis screens as required Other Routes Your project may also provide specific keys for moving directly to individual diagnosis screens You then start the diagnosis from those screens bypassing the diagnosis start screen Message Acknowledgement On completion of the diagnosis and rectification of the fault you must acknowledge the message by pressing the ACK key as normal If the alarm message belongs to an acknowledgement group when it is acknowledged all other alarm messages in that group are acknowledged at the same time as normal ProAgent User s Manual 5 2 Issue 12 99 Display on the Operating Unit The Purpose of the Individual Diagnosis Screens If you have read the preceding chapters you will be aware from the Introduction that when a process diagnosis is configured a number of additional standard diagnosis screens are incorporated The process diagnosis is performed from those screens All diagnosis screens are standardized to a large degree and differ in only minor details from one operating unit to another The illustrations below show examples of diagnosis screens as they appear on an OP25 Diagnosis Start Screen SIMATIC HMI Process Diagnosis System Takes you to the for C7 626 OPZ5
121. is chapter gives a general outline of how to use the Detail Screen LAD in practice Aims You have opened the Detail Screen in order to see which instructions in the program have resulted in a particular alarm message By doing so you can tell which monitoring routine triggered the error message and accordingly where the fault is to be found Unit DE13 Conveyor belt 1 Step 12 Start conveyor belt B12 Trans Est 12 13 14 15 16 17 p Tr Name Mator power on od cy Symbol AUN 4r ER 07 0 Feed switch gp Detail Screen LAD Format As Shown on OP25 The center section of the screen shows an excerpt from the program code for the networks with the fault Which Unit The first line of the display shows you to which unit the network shown underneath belongs You are given details of the block type block number and assigned text symbol or absolute identifier ProAgent User s Manual 5 68 Issue 12 99 Display on the Operating Unit Which Step Which Transition In S7 GRAPH units the second line shows the user number of the active step and an associated text On the third line you will see the transitions belonging to each step The transition to which the program code displayed belongs is highlighted in inverse type The fourth line shows the name of that transition Which Network In S7 PDIAG units the second line shows the number and the name of the network displayed On the third line the wording Number appears and on th
122. is key 4 When partial view is active this symbol appears above the statement list Partial view is particularly useful if you want to be able to quickly locate the critical instructions that have resulted in the issue of an alarm message If you project does not specify otherwise partial view is automatically selected when the screen is selected Toggling Display of Initial Values and Current Status STL The default setting is for display of the status bits as they were at the time the fault monitoring routine first detected the process fault For that reason those values are also referred to as initial values Those status bits are accordingly also the basis for the results of logical operations RLO displayed In addition you can also inquire the current status Viewing the current status allows you to monitor online what effect corrective measures have on the condition of the system If you have set the display mode to partial view see Toggling Between Partial and Full View STL Format Chapter 5 6 3 4 you can see right away if the fault has been put right In that case no more signals are displayed on the screen Ow To toggle display of initial values and current status use this key e When the display mode is set to current status this symbol appears above the statement list ProAgent User s Manual Issue 12 99 Display on the Operating Unit 5 6 3 6 Changing the Action or Transition STL
123. is such that all code parts that can be evaluated become visible Programming in STL Display with ProAgent Network 1 Label U M50 U M 6 0 U M1 0 M20 U ba S S 1 U M50 LU M60 Network 2 M 3 0 U M10 U M20 M 3 0 Resolving Branch Instructions Labels Outside the Start of the Network In the LAD display mode of the detail screen display is possible only if the label is at the start of the network In the STL and Signal List display mode display is possible at all times but the display unit sets the initial query in the case of labels The following statement is the basically treated like the start of a network Caution This behavior may differ from actual execution on the PLC This may result in differences between logical results displayed on the operating unit and those actually present on the PLC ProAgent User s Manual 5 74 Issue 12 99 5 6 5 3 Multiple Assignments Display on the Operating Unit If your PLC program performs multiple assignments to a monitored operand for example with SET RESET or even with a direct assignment you can change from one affected network to another on the detail screen by means of a key Programming in STL Network 1 U M10 UN M20 S 1 M70 Network 2 UN M 1 0 U M20 R M70 Change via key Multiple Assignment of the Monitored Operand M 7 0 You can see which network is currently being displayed from the second line of the detail screen
124. it has been programmed in S7 GRAPH the word Para appearsto identify the subsequent numbers as parallel steps 10 If the selected unit has been programmed in S7 GRAPH the numbers of the active actions appear in these fields The numbers of the actions with faults always appear first reading from left to right Actions with faults are shown flashing 11 The arrow right symbol appears here if there are more parallel actions than can be shown at 10 at once 12 Here you can specify the operating mode of the selected unit The operating modes that are possible depend on how the unit has been programmed If the STEP 7 program does not define an operating mode this field remains blank ProAgent User s Manual 5 30 Issue 12 99 Display on the Operating Unit 5 4 3 Keys on the Step Screen You can use the following keys on the step screen You use this key to set enable the displayed step in the step sequence You use this key to reset the displayed step in the step sequence You use this key to reset all the steps in the step sequence You use this key to reset the initial step in the step sequence You use this key to return to the Overview Screen Keys on the step screen ProAgent User s Manual Issue 12 99 5 31 Display on the Operating Unit 5 4 4 Aims How to Work with the Step Screen This chapter gives a general outline of how to use the step screen most effectively in practice You have opened the step scre
125. ition is being displayed the inverted step number is displayed Multiple Assignments of Monitored Operands 5 6 2 6 With Multiple Assignments Chapter 5 6 5 3 to a monitored operand the cause of the error may reside on different networks You can use this key to switch between the networks affected You can see which network is currently being displayed from the second line of the detail screen Hover the block number displayed on the first line remains as it is Switch between symbol and remark Signal List An instruction can be assigned a symbol and remarks in STEP 7 On the Detail Screen Signal List these are then shown at the end of each line Note If no symbol or remarks were stored the absolute operand is shown Depending on the device the space available only allows either symbols only or remarks only to be displayed In order to toggle between display of symbols and remarks press the ENTER key on an OP A text or graphic list then opens from which you can select the required display mode On a TP you open the same list by touching the corresponding input output field that is the word Symbol or Remark ProAgent User s Manual Issue 12 99 5 53 Display on the Operating Unit 5 6 3 5 6 3 1 Detail Screen in STL Format What You See on the Detail Screen STL Format Faults Displayed The faults displayed when the Detail Screen is opened depend on the point from which the Detail Scree
126. keys are configured e from a truncated ProTool message page that is superimposed over the diagnosis Message Screen but leaves the keys visible ProAgent User s Manual Issue 12 99 Configuring in ProTool The truncated Message Page is automatically displayed with the aid of the function Display Messages when the diagnosis Message Screen is selected Pending Alarm Messages 234567 A K 14 15 35 H2 86 1997 GRUB Hssembly of electronics workpiece supply interrupted e2b49921 A K 13 13 27 O2 86 1997 GRUB Conveyor belt 1 jammed 85128908 A KG 11 17 28 W2 86 1997 GRUBB Truncated Message Page Background screen Diagnosis Message Screen Layout of the Diagnosis Message Screen If you create your own message screen you must therefore configure the function Display Messages for screen selection Exiting the Message Screen The ESC key is inactive To simultaneously close the background screen and the truncated Message Page i e the diagnosis Message Screen you must select another screen Effects on ProTool The truncated Message Page and full size Message Page can not be used together in the same project As soon as the Display Messages function opens the truncated message page at one or more locations the truncated message page is always opened Tip Ifthe Display Events function or the Display Alarms function is configured outside the message screen they do not react any more in the case of a diagn
127. l Online Help ProAgent User s Manual Issue 12 99 8 15 Modifying the Diagnosis Screens 8 4 9 8 16 Defining Operating Modes Overview Screen On the Overview Screen ZP_UNITS or ZP_UNITS_S7G the user can change the operating mode of a unit by means of an input field That input field is password protected The password level is set to 8 as the default Operating modes are referenced by a 16 bit value and must be uniform across the whole S7 project Each bit identifies an operating mode The operating modes for Automatic Bit 0 and Manual Bit 1 are permanently fixed Each unit has an operating mode that is independent of the operating mode of the superior or subordinate units Note If changing the operating mode of a parent unit is to affect all subunits this must be implemented in the PLC program The preset names are Auto Man and Mod02 to Mod07 To change those names edit the text or graphic list ZP_MODE If you are creating multi language projects you must also take account of the relevant foreign languages ProAgent User s Manual Issue 12 99 8 5 8 5 1 8 5 2 Modifying the Diagnosis Screens Using Additional Functions Working with Password Levels Input fields and keys can be password protected Use of those keys fields is then restricted to suitably authorized and qualified personnel Password protection can of course also be incorporated in the diagnosis screens The default sett
128. l Selection ProAgent User s Manual Issue 12 99 In ProTool you can define specifically which PLCs and units you want to monitor from a particular operating unit It may be for example that your system has more than one operating unit In that case you would naturally only want to carry out diagnoses on each operating unit for the units actually operated by the operating unit in question Note Only ever monitor one unit at a time from one operating unit otherwise the operating units could block each other when you trigger movements from the Movement Screen As well as or instead of the selection of messages by units e Bj th also make the display of messages dependent on the display class Chapter B that has been assigned to the message in STEP 7 6 15 Configuring in ProTool System ProAgent 6 16 You specify the units that are to be included in the process diagnosis by choosing the menu option System ProAgent A two column selection box allows you to specify the units you want to include Diagnosable Units Selected Units PLC 1 Cancel Press 1 PLC 2 Press 2 3 PLC 2 Gripper Swing arm Units for Diagnosis d Only those units are offered for selection that are actually diagnosable i e that have been programmed accordingly in S7 PDIAG or S7 GRAPH The tree structure shown corresponds to the hierarchy that results from the PLC program concerned
129. l is part of the SIMATIC HMI documentation The documentation is aimed at the following target groups e Newcomers e Users e Configurers Programmers e Commissioning engineers How the documentation is organized The SIMATIC HMI documentation consists of the following components User s Guides User s Manuals for Configuration software Runtime software Communication between PLCs and operating units Equipment Manuals for the following operating units MP Multi Panel OP Operator Panel TP Touch Panel TD Text Display PP Push Button Panel e Online Help on the configuration software e Start up Guides e First Steps ProAgent User s manual Issue12 99 C 1 SIMATIC HMI Documentation Overview of complete documentation The following table provides an overview of the SIMATIC HMI documentation and shows you when you require the different documents First Steps with Newcomers This documentation guides you step ProTool by step through the configuration of Product Brief e a screen with various objects e changing from one screen to another e amessage This documentation is available for e OP3 OP5 OP7 OP15 OP17 e OP25 OP27 OP35 OP37 TP27 TP37 e Windows based systems ProTool Configurers Provides information on working with Configuring the ProTool Pro configuration Windows based software It contains Systems e information on installation User s Guide e basic principles of confi
130. l level proceed as follows 1 Select the unit whose subordinate or superior units you wish to display 2 Change the hierarchical level gt On an OP press this key if you wish to display the subordinate units or lt press this key if you want to call up the superior unit gt On a TP press this key if you wish to display the subordinate units or 4 press this key if you want to call up the superior unit When you move down a hierarchical level only the subordinate units of the selected unit are shown When you move up a hierarchical level all units on that level are once again displayed ProAgent User s Manual Issue 12 99 5 27 Display on the Operating Unit 5 3 7 Alternative Overview Screen for S7 GRAPH If your system has units programmed in S7 GRAPH you can use depending on the configuration a slightly modified form of the Overview Screen Layout The list of units extends over two lines for this version of the overview screen The top line corresponds to the entry on the standard overview screen and shows the unit name number of the active step and where appropriately programmed the operating mode for units programmed in S7 GRAPH The step name of the active step is displayed beneath it as well Display of the remaining fields and operation are similar to the standard overview screen Step name Chain name Step number A M Start conveyor belt Press 2 Assembly Line 23 Auto Lower die
131. lass In all there are 16 display classes display classes 0 to 15 Example Messages that are to appear on the machine might be assigned display class 1 those that are to appear on the control desk display class 2 The various operating units then only analyze those messages that belong to specific display classes Any other ALARM S messages are immediately discarded Assigned Selected display class display classes L Message A HHH LILL L1 LEE 1 LELELILD zb Message B LI IIGE ITI OVO Message C Message D Display Classes Determine which Groups of Messages are to be Displayed on the OP ProAgent User s Manual Issue 12 99 Message Processing Specifying Display Classes The display class to which an ALARM_S message belongs is determined when the message is configured in STEP 7 For a precise description of the procedure please consult the information on message configuration in your STEP 7 documentation If you do not specify a display class in STEP 7 the message concerned is automatically assigned to display class 0 Selecting Display Classes In ProTool you must specify which display classe
132. le Execution of movements using soft keys Detail Screen Results of fault analysis Status and results of logical operations The Different Diagnosis Screens Standardization Introduction The user interface on the operating unit is standardized so that operation follows a uniform pattern for all installations and components A detailed description of the individual Display on the Operating Unit Chapte ProAgent User s Manual Issue 12 99 iy nosis screens is given in the chapter 3 5 Introduction 3 3 How a Process Diagnosis is Configured System Concept ProAgent is a universal system concept and designed for optimum interaction between STEP 7 STEP 7 option packages and the operating unit configuration program ProTool Configuring the process diagnosis in ProTool is quick and simple to perform And the same is true whether you are incorporating process diagnosis in a new or an existing PLC program Subtasks Just as when configuring an installation there are two main subtasks involved in implementing a process diagnosis 1 programming the PLC 2 configuring the operating unit ProAgent like ProTool is used for the second step only i e configuring the operating units S7 PDIAG S7 GRAPH PLC Shared database O O00 QOO000 QOL 00000 ProAgent ooma xn
133. letters on dark background if multiple arrivals and departures of the message have not been able to be recorded IPE A KCO HH MM SS DD MM YYYY GRUOO Boiler 13 temperature 190 degrees Inform shift supervisor Tel 007 Multiple Arrivals and Departures Could Not Be Recorded CPU Memory Overload 7 18 If there are more messages pending than the CPU can process any new messages are discarded Only when a message has been fully processed can a new message be processed The date and time of a message appear on the operating unit in inverted type light letters on dark background if it is the last message that could be accepted by the CPU message buffer 1234567 A KCO MEREMEES BEBISBIRREI cr 00 Boiler 13 temperature 190 degrees Inform shift supervisor Tel 007 Last Message Accepted by the CPU ProAgent User s Manual Issue 12 99 Message Processing Operating Unit Memory Overload 7 10 An operating unit can process a maximum of approx 200 simultaneously pending messages total number of event and alarm messages If the operating unit then receives more messages from the CPUs on the network they can no longer be displayed A system message to that effect is then displayed on the operating unit The maximum number of messages that could theoretically be simultaneously pending on an operating unit is calculated from the sum of the maximum numbers possible on the connected CPUs Example
134. lized by the left side of the screen and the other by the right side The two keys immediately to the left and right of the representation of the movement are assigned to each movement These keys are used to execute the movements ProAgent User s Manual 5 36 Issue 12 99 Display on the Operating Unit Each movement line is made up of the following elements 4 This shows you what movements are involved The text is assigned to the movement when the unit is programmed variable name of movement Only the last two components of the variable name which are separated by are displayed The mode for enabling movements can be set in such a way that a movement has to be selected first before it is enabled default setting on the TP When you then select a movement it is displayed in inverted i e in reverse video see Changing The Mode of Enabling Movements Chapter 4 6 5b If this movement is disturbed a warning triangle is appears to indicate the fault 6 This shows you which direction of movement is symbolized by which side of the screen Those are the directions in which the movement will be executed when you press the appropriate key 7 Here you are shown a symbolic representation of various target positions A target position corresponds to a specific limit of movement e g a specific conveyor position a specific angle of rotation etc Each movement can have more than one target position The reaching of a targ
135. lt between the operating unit and the PLC In most cases you will receive other system messages which provide more information about the cause of the fault This might be such things as faulty connectors or changed addresses on the PLC A 3 4 Error Identifying Signal Statuses Message Number Cause Remedy 4044 The Detail Screen is in the Show current status bits display mode however only the status bits at the time of occurrence of the fault can be read from the PLC Current status bits are only provided by S7 GRAPH A 3 5 Error Determining Initial Values Message Number Cause Remedy 4045 The Detail Screen is in the Show initial values display mode however the status of the signals at the time of occurrence of the fault can not be read from the PLC The cause is generally a communication fault between the operating unit and the PLC In most cases you will receive other system messages which provide more information about the cause of the fault This might be such things as faulty connectors or changed addresses on the PLC ProAgent User s Manual Issue 12 99 A 7 Appendix System Messages A 4 Movement Screen System Messages A 4 1 No Current Unit Selected Message Number Cause Remedy This message appears when the Movement Screen is opened if e the Movement Screen is called up from the Message Screen but the selected unit is not diagnosable the Movement Screen is called up from a blank Overvie
136. ment Progression The small rectangle next to the triangle flashes while the movement is being executed As soon as a particular target position is reached the corresponding target position symbol changes its appearance as follows Target position not yet reached Target position reached or passed Exiting the Movement Screen This key returns you to the screen from which you activated the Movement Screen 5 5 5 Hierarchical Units on the Movement Screen Hierarchical Units When programming a PLC it is possible depending on the programming language used to define a hierarchy of individual units Thus in the case of S7 PDIAG a unit can be equated with a block which as a rule also represents a process unit By virtue of the multi instance concept of STEP a unit can also contain other units Display Mode The Movement Screen always shows all movements for a specific unit of your system Which unit that is depends on where the Movement Screen was activated from see What You See on the Movement Screen Chapter 5 5 2 If there are a number of hierarchical levels between the units of a system the Movement Screen initially shows only the movements for the current unit If you wish to execute movements for subordinate units you have to change the display mode Changing Display Mode To view the movements for subordinate units press this key After the display mode has been changed all movements of subord
137. merica Siemens Energy amp Automation Inc Automation Division e Alpharetta Georgia Numeric Motion Control Elk Grove Village Illinois Uruguay Conatel S A Montevideo Venezuela Siemens S A Caracas Valencia The following table lists all Siemens Companies and Representatives of Siemens AG in Asia Bahrain Transitec Gulf Manama Bangladesh Siemens Bangladesh Ltd e Dhaka Brunei Brunei Darussalam Hong Kong Siemens Ltd Hong Kong India Siemens Limited e Ahmedabad Bangalore Bombay Calcutta Madras e New Delhi e Sec nderabad Indonesia P T Siemens Indonesia P T Siemens Dian Grana Elektrika Representative Siemens AG e Jakarta ProAgent User s Manual Issue 12 99 ProAgent User s Manual Iraq Samhiry Bros Co Limited oder Siemens AG Iraq Branch Baghdad Iran Siemens S S K Teheran Japan Siemens K K Tokyo Korea Siemens Ltd e Changwon Seoul e Ulsan Kuwait National amp German Electrical and Electronic Services Co NGEECO e Kuwait Arabia Lebanon Ets F A Kettaneh S A Beyrouth Malaysia Siemens Electrical Engineering Sdn Bhd e Kuala Lumpur Nepal Amatya Enterprises Pvt Ltd e Kathmandu Oman Waleed Associates e Muscat Pakistan Siemens Pakistan Engineering Co Ltd e Islamabad Karachi Lahore Peshawar Quetta Siemens worldwide People s Republic of China Sieme
138. message number General System Messages Error Initializing Process Diagnosis Message Number Cause Remedy 4000 Initialization of communication between PLC and operating unit failed when the diagnosis firmware was launched Make sure that you have the correct version of the firmware on your operating unit Switch off operating unit and PLC Check all connections and then restart ProAgent User s Manual Issue 12 99 A 1 Appendix System Messages A 1 2 A 1 3 A 1 4 A 2 Not Enough Memory for Process Diagnosis Message Number Cause Remedy 4001 A memory request by the diagnosis package failed There is not enough memory available on the operating unit for process diagnosis Check that the operating unit hardware meets the system requirements When powering up the operating unit check whether hardware faults are reported during the memory test If necessary simplify your project by dispensing with unnecessary OEM functions Diagnosis Data Inconsistency Between PLC and Operating Unit Message Number Cause Remedy 4002 A conflict has occurred between the action numbers stored on the PLC and the numbers expected by the operating unit In order to obtain data consistency first retranslate the STEP 7 program and then reload it onto the PLC Then recompile the OP project in ProTool and download it to the OP Unit has been Acknowledged Message Number Cause Remedy 4081 This system message confi
139. n below shows an example of the Detail Screen in LAD format as it appears on an OP25 You can find an illustration and a description of the list variations in the chapter What You Can See in the Detail Screen Signal List Chapte 5 6 2 1 you can find an illustration and description of the STL variation in the chapter What You Can See in the Detail Screen STL Chapter 5 6 3 1 Z 12 Start Nut a f JD 12 13 14 15 16 17 r Wame Motor power an Ol ef smod D br T8 B 1 4 7 4 a NENNEN Feed switch a Detail Screen example of LAD format on an OP25 programmed with S7 GRAPH ProAgent User s Manual Issue 12 99 Display on the Operating Unit Information About the Unit The top section of the display shows detailed information relating to the unit on which the process fault occurred The display distinguishes between areas 4 to 11 depending on whether the unit has been programmed with S7 PDIAG or with S7 GRAPH 1 This shows the block type of the unit with the fault i e FC DB or OB 2 This field shows the block number of the unit with the fault At this point text assigned to the unit appears the symbol for a block or an absolute identifier If the unit has been programmed with S7 GRAPH lines 2 to 4 of the display have the following contents 4 This field identifies the step selected by means of the test Step This field displays the user number of the step selected This field displ
140. n is called up e If you have called up the Detail Screen from the Message Screen or from the Message Page Window you will have first had to select a message The Detail Screen then shows the fault which triggered the message you have selected on the Message Screen e If you have called up the Detail Screen from the Overview Screen you will have first had to select a unit The Detail Screen then shows the fault in the first action of that unit with a fault General Layout 5 54 Like all the diagnosis screens the Detail Screen has a standardized layout There are only minor differences between the various types of operating unit The illustration below shows an example of the Detail Screen in STL format as it appears on an OP25 You can find an illustration and a description of the list variations in the chapter What You Can See in the Detail Screen Signal List Chapter 5 6 2 1 you can find an illustration and description of the LAD variation in the chapter What You Can See in the Detail Screen LAD Chapter 5 6 4 1 a O Step 12 Start conveyor belt i GO Trans EAE 12 13 14 15 15 17 Tr Mame Hator powe Detail Screen example of STL format on an OP25 programmed with S7 GRAPH ProAgent User s Manual Issue 12 99 Display on the Operating Unit Information About the Unit The top section of the display shows detailed information relating to the unit on which the process fault occurred The display distinguis
141. n order to see which logical operation results in the program code triggered the error message To do so use this key to call up the Detail Screen Changing to Manual Mode If you know what has caused the fault you will naturally want to rectify it as quickly as possible so that the system can be started up again To that end you can execute specific movements on particular units in Manual mode Note It depends on your PLC program whether you are able to and need to change to Manual mode before executing manual operations ProAgent User s Manual 5 24 Issue 12 99 Display on the Operating Unit To change the operating mode select the unit on which you wish to carry out a movement If there are other hierarchically subordinate units related to that unit this symbol appears above the list of units see Hierarchical Units in the Overview Picture Chapter 5 3 6 On an OP you can use this key to move down a hierarchical level and define your selection even more precisely gt On a TP you have to press this key to do this Finally you open the text or graphic list for selecting the operating modes using the ENTER key on an OP and by touching the displayed operating mode on a TP Executing Movements PY Once you have selected the unit or subunit that you wish to move and have set the correct operating mode use this key to switch to the Movement Screen Setting or resetting a step hf If a unit has b
142. n this way trigger movements without communication related delays All that has to be done to enable direct keys to be used on an OP is to carry out the appropriate configuration The assignment of the key and of the bit set when the key is pressed is fixed The exact assignment can be found in the User s Manual entitled Communication Configuration involves the following steps e The OP must be configured as the active user master for general communication reading and writing of tags e To enable DP direct keys to be used the OP must also be configured as a slave in the PROFIBUS DP network Detailed information about this can be found in the User s Manual entitled Communication ProAgent User s Manual Issue 12 99 8 21 Modifying the Diagnosis Screens Configuring The OP As Master To configure the OP as the active user for general communication please proceed as follows 1 Generate a STEP 7 project and configure the hardware with a DP compatible CPU Copy a standard project e g for OP25 to your STEP 7 project The standard projects are located in the STEP 7 project named ProTool Open ProTool by double clicking the operating unit Select the menu item System PLC and click the Edit and Parameters buttons one after the other In the dialog box now open select the network and the CPU to which the operating unit is to be connected The network parameters are then taken over You have now configure
143. nd of each line Note If no symbol or remarks were stored the absolute operand is shown Depending on the device the space available only allows either symbols only or remarks only to be displayed In order to toggle between display of symbols and remarks press the ENTER key on an OP A text or graphic list then opens from which you can select the required display mode On a TP you open the same list by touching the corresponding input output field that is the word Symbol or Remark ProAgent User s Manual Issue 12 99 5 63 Display on the Operating Unit 5 6 4 5 6 4 1 Detail Screen in LAD Format What You See on the Detail Screen LAD Format Faults Displayed The faults displayed when the Detail Screen is opened depend on the point from which the Detail Screen is called up e If you have called up the Detail Screen from the Message Screen or from the Message Page Window you will have first had to select a message The Detail Screen then shows the fault which triggered the message you have selected on the Message Screen If you have called up the Detail Screen from the Overview Screen you will have first had to select a unit The Detail Screen then shows the fault in the first action of that unit with a fault General Layout 5 64 Like all the diagnosis screens the Detail Screen has a standardized layout There are only minor differences between the various types of operating unit The illustratio
144. ne only the movement can not be carried out The mode for enabling movements can be configured in ProTool in such a way that a movement has to be selected first before it is enabled default setting on the TP Execution of the movement continues for as long as you keep the key pressed If the movement is successfully executed the rectangle next to the triangle flashes If you use direct keys Chapter 8 6 1 the keys communicate directly with the PLC which is of particular interest where critical timing and safety related functions are involved The PLC program must be capable of supporting the direct keys If there are more movements for a unit than can be displayed on the operating unit at once you can scroll the list up or down using the cursor keys To scroll up on a touch panel touch the top most movement until scrolling is activated To scroll down touch one of the other movements This key is used to specify whether only the movements of the selected superior unit are displayed or all movements of subordinate units as well see Hierarchical Units on the Movement Screen Chapter 5 5 5 The superior unit concerned is the unit selected on the screen from which the Movement Screen was activated This key is used to return to the screen from which you opened the Movement Screen Movement Screen Keys ProAgent User s Manual 5 38 Issue 12 99 Display on the Operating Unit 5 5 4 How to Work with the Movemen
145. ng ProAgent changes very little on the ProTool user interface System ProAgent The System menu now includes the item ProAgent By choosing this option you can select the ones for which you wish to configure the diagnosis from the units of your system The messages that belong to these units will then be shown at the operating unit Diagnosable Units Selected Units PLC 1 s PLC Cancel Press 1 Press 2 PLC 2 Gripper Swing arm Selecting units by choosing System ProAgent ProAgent User s Manual Issue 12 99 4 1 Effects on ProTool System Messages Settings By selecting the menu item System Messages Settings you open the ProTool dialog box Message Settings Message Settings 9 e Messages Dialog Box with New Message Procedure Section Installing ProAgent Pro adds a new section entitled Message Procedure to this dialog box This is where you specify the ALARM S Message Procedure Chapte required for diagnosis You can also restrict the display to messages of specific display classes ProAgent User s Manual 4 2 Issue 12 99 4 2 4 3 Effects on ProTool Additional Functions in ProTool There is a number of additional functions available in ProTool for process diagnosis after ProAgent has been installed These additional functions all begin with ProAgent They are used on the Diagnosis Screens that are added when
146. ng routine triggered the error message and accordingly where the fault is to be found Unit DB13 Conveyor belt 1 step 12 Start conveyor belt DB12 Trans s 17 13 14 15 16 17 Tr Name Motor power on Ab Status Symbol H IH W Grid A 1 4 UM Feed 0 2 Ma Main drive Nef t E Detail Screen STL Format As Shown on OP25 ProAgent User s Manual 5 58 Issue 12 99 Display on the Operating Unit The center section of the screen shows an excerpt from the program code for the networks with the fault The instructions which have led to the issue of an alarm message are highlighted Which Unit The first line of the display shows you to which unit the excerpt from the program code shown underneath belongs You are given details of the block type block number and assigned text symbol or absolute identifier Which Step Which Transition In S7 GRAPH units the second line shows the user number of the active step and an associated text On the third line you will see the transitions belonging to each step The transition to which the program code displayed belongs is highlighted in inverse type The fourth line shows the name of that transition Which Network In S7 PDIAG units the second line shows the number and the name of the network displayed On the third line the wording Number appears and on the fourth line the network numbers of networks appear that set the same operand You now have the informati
147. nnot then be set and deleted ProAgent User s Manual Issue 12 99 5 29 Display on the Operating Unit Information on the selected step You will see the step number and step name in the center area of the display 1 The wording step No and the user number of the active step appear here If several actions are active at the same time the step number of the action that appears first on the list at 10 is shown Here you can enter the required step number of the current unit that you want to set or delete 2 The wording step name and following confirmation by pressing ENTER the name of the step entered under 1 appear here Information on the Selected Unit In the upper area of the display you obtain information on the unit selected in the overview screen from which the step screen was opened 3 This shows the block type of the selected unit i e FC DB or OB 4 This field shows the block number of the selected unit 5 This shows text assigned to the unit the symbol for the block or an absolute name 6 If the unit has been programmed in S7 GRAPH the word Step appears 7 If the selected unit has been programmed in S7 GRAPH the user number of the active step appears here If several actions are active at the same time the step number of the action that appears first on the list at 10 is shown 8 If the selected unit has been programmed in S7 GRAPH the step name appears 9 If the selected un
148. ns Lausanne Turkey SIMKO e Adana e Ankara Bursa e Istanbul Izmir e Samsun Ukraine Siemens AG Kiew The following table lists all non European Siemens Companies and Representati ves of Siemens AG The following table lists all Siemens Companies and Representatives of Siemens AG in Africa Algeria Siemens Bureau d Alger Alger Angola TECNIDATA Luanda Bophuthatswana Siemens Ltd e Mafekeng Egypt Siemens Technical Office e Cairo Mohandessin Siemens Technical Office Alexandria EGEMAC S A E e Cairo Mattaria Ethiopia Addis Electrical Engineering Ltd Addis Abeba Ivory Coast Siemens AG e Abidjan Libya Siemens AG Branch Libya Tripoli Marocco SETEL Soci t Electrotechnique et de T l com munications S A e Casablanca Mozambique Siemens Liaison Office e Maputo Namibia Siemens Pty Ltd e Windhoek Nigeria Electro Technologies Nigeria Ltd ELTEC Lagos Rwanda Etablissement Rwandais Kigali ProAgent User s Manual Issue 12 99 America ProAgent User s Manual Issue 12 99 Sambia Electrical Maintenance Lusaka Ltd Lusaka Simbabwe Electro Technologies Corporation Pvt Ltd ETC e Harare South Africa Siemens Ltd Cape Town e Durban Johannesburg e Middelburg Newcastle e Port Elizabeth Pretoria Siemens worldwide Sudan National Electrical amp Commercial Com pany NECC Khartoum
149. ns AG Representation Beijing e Guangzhou e Shanghai Philippine Islands Maschinen amp Technik Inc MATEC Manila Qatar Trags Electrical Engineering and Air Conditioning Co Doha Saudi Arabia Arabia Electric Ltd Equipment e Al Khobar Jeddah Riyadh Singapore Siemens Pte Ltd Singapore Sri Lanka Dimo Limited Colombo Syria Siemens AG Branch A S T E Damascus Taiwan Siemens Ltd TELEUNION Engineering Ltd oder TAI Engineering Co Ltd Taichung Taipei Thailand Berti Jucker Co Ltd Bangkok United Arab Emirates Electro Mechanical Co oder Siemens Resident Engineers e Abu Dhabi Scientechnic oder Siemens Resident Engineers Dubai D 7 Siemens worldwide Australia D 8 Vietnam Yemen Arab Republic OAV Representative Office Tihama Tractors amp Engineering Co Ltd Hanoi oder Siemens Resident Engineers Sanaa The following table lists all Siemens Companies and Representatives of Siemens AG in Australia Australia New Zealand Siemens Ltd Siemens Ltd e Adelaide e Auckland Brisbane Wellington Melbourne e Perth Sydney ProAgent User s Manual Issue 12 99 Index A Abbreviations Acknowledgement Action Changing on detail screen LAD Changing on detail screen STL switch to Detail Screen Signal List Actions Adapt Design of diagnosis screens Diagnosis screens Font size and font Adapt design of di
150. nt on the unit Chapte from which the message originates Selecting Display Classes 1 Choose the menu option System Messages Settings The Message Settings dialog box opens Message Settings Ed Alarm Messages OK First _ C Last Cancel m Printout Message Event C Buffer Overflow C Off r Overflow Warning v Messages at fi D Remaining Buffer m Character Titles Language German Page Arrived K Buffer g Alarm Messages EI o Ack Group face Buffer I r Message Procedure Message Bit v Alam 5 Event Messages Departed Dialog box Message Settings ProAgent User s Manual 6 18 Issue 12 99 Configuring in ProTool 2 Press the command button Alarm_S to select specific display classes The dialog box SIMATIC S7 Messages opens The left hand side of the dialog box shows a list of all the PLCs in your system SIMATIC 7 Alarm_S Selected PLCs PLE Description 4 i ac PLC 2 All messages transferred CENE dc 18 of ld display classes selected Details Dialog box S MATIC S7 Messages 3 For every PLC specify what messages should be displayed on the operating unit ProAgent User s Manual Issue 12 99 In order not to display messages on the operating unit deselect the check box on the left next to the PLC In order to display all messages on the operating unit select
151. nt to you own project proceed as follows 1 If you have not already done so open your STEP 7 project and the operating unit project to which you want to copy the diagnosis screens 2 Also open the STEP 7 project ProAgent and the operating unit project that corresponds to the operating unit being configured e g ProAgent25 for an OP25 3 Select the Screens object type in the left column of the project window 4 In the right column select the screen or screens that you want to copy You can select more than one screen at once by holding down the CTRL key Generally speaking you should copy all screens but only one version of the overview screen meaning either ZP UNITS or ZP UNITS S7G If you use the alternative overview screen ZP UNITS S7G take into account the note contained in the chapter called Replacing the Overview Screen Chapter 1 9 5 To copy the selected screens to the Clipboard choose Edit Copy This process may take a little while depending on the performance of your computer and how busy it is 6 Switch to the project to which you want to copy the diagnosis screens 7 Select the Screens object type in the left column of the project window 8 Insert the contents of the Clipboard by choosing Edit Paste from the menu The diagnosis screens are now available for use in your project All the necessary functions and tags have been copied along with the screens Remark It is not sufficient to open a
152. ntaining an assignment to that operand This key is used to change the display to STL format see What You See on the Detail Screen STL Format Chapter 5 6 3 1 This key is used to return to the screen from which you opened the Signal List Display Keys Used with Signal List Display in the detail screen ProAgent User s Manual 5 48 Issue 12 99 Display on the Operating Unit 5 6 2 3 How you work with the Detail Screen Signal List This chapter gives a general outline of how to use the Detail Screen Signal List in practice Aims You have opened the Detail Screen in order to see which signals have resulted in a particular alarm message By doing so you can tell which monitoring routine triggered the error message and accordingly where the fault is to be found Unit D613 Conveyor belt 1 step oo 12 Start conveyor belt B12 Trans tll 31 13 14 15 16 17 p Tr Name Mator power on er Symbol B 8 brid 1 4 Feed SE Detail Screen Signal List Format As Shown on OP25 The middle section of the display shows only the signals that have just triggered an Alarm Message Which Unit The first line of the display shows you to which unit the signals shown underneath belong You are given details of the block type block number and assigned text symbol or absolute identifier ProAgent User s Manual Issue 12 99 5 49 Display on the Operating Unit Which Step Which Transition In S7 GRAPH units the second
153. nterlocking condition of the step to the first and then to all other transitions With S7 GRAPH units that report a monitoring fault from one transition to the next With units programmed with S7 GRAPH and using movement blocks created with S7 PDIAG the change is made initially between the transitions and then to the movement blocks ProAgent User s Manual 5 62 Issue 12 99 Display on the Operating Unit The display of the transitions in the third and fourth lines then changes accordingly see What You See on the Detail Screen STL fd ED Once the last transition has been reached the locking condition of the step is displayed and the cycle starts again from the beginning You can tell which transition is currently being displayed from the inverted transition number If the locking condition is being displayed the inverted step number is displayed Multiple Assignments of Monitored Operands 5 6 3 7 With Multiple Assignments Chapter 5 6 5 3 to a monitored operand the cause of the error may reside on different networks You can use this key to switch between the networks affected You can see which network is currently being displayed from the second line of the detail screen Hover the block number displayed on the first line remains as it is Toggling Display of Symbol and Remarks STL An instruction can be assigned a symbol and remarks in STEP 7 On the Detail Screen STL these are then shown at the e
154. o the Movement Screen i e without having to go via the Overview Screen The Movement Screen shows all movements for the units where there are faults and allows you to execute those movements directly as well Exiting the Message Screen You use this key to return to the Diagnosis Start Screen 5 2 5 Selecting by Diagnosability On the Message Screen you can use a key to toggle between display of all messages and display of diagnosable messages only Displaying only diagnosable messages improves clarity for the purposes of process diagnosis m To toggle between the two display modes use this key Diagnosable messages are identified by an asterisk in front of the message number ProAgent User s Manual 5 18 Issue 12 99 5 3 5 3 1 Display Functions Display on the Operating Unit Overview Screen The Purpose of the Overview Screen The Overview Screen shows all the diagnosable units in your system It gives you the following information about each unit e whether it has a fault e when appropriately programmed in S7 PDIAG in what operating mode you are e g manual or automatic mode If there are faults on more than one unit you can see on which one the fault first occurred In that way you can tell immediately where the actual cause lies and which faults are consequential errors You can select a unit from the list and when appropriately programmed in S7 PDIAG set its op
155. ode itemizes the sections of the PLC program that have triggered a process fault This should not be confused with a programming error Instead the occurrence of a process fault has brought about a specific condition the incidence of which the process is monitored for That condition is characteristic of a system fault and an alarm message is issued Since the process diagnosis system can monitor a whole range of conditions and mutual interdependencies can also be defined it is of course of interest to see which signals have led to the issue of an alarm message From that information it is possible to deduce what the cause of the fault was and how it can be most quickly rectified ProAgent User s Manual Issue 12 99 Display on the Operating Unit Additional Information In addition to the program code you can also view operands symbols and remarks At the same time you are shown the status of the operands and all results of logical operations All signals whose conditions have contributed to the alarm message are identified In that way you can see at a glance which conditions have led to the issue of an alarm message 5 6 2 Detail Screen as Signal List 5 6 2 1 What you see in the Detail Screen Signal List Faults Displayed The faults displayed when the Detail Screen is opened depend on the point from which the Detail Screen is called up e If you have called up the Detail Screen from the Message Screen or from the Me
156. of the relevant program is used on each device If therefore changes are made to the PLC program at some later date you must also recompile and re download the operating unit configuration so that there are no inconsistencies between devices When compiling the operating unit configuration the stored messages and diagnosis data are imported from the database shared with STEP 7 Changes to shared database Interdependencies Activating Data Synchronization By choosing File Settings Compile you can select which data in the database shared with STEP 7 is to be synchronized i e re imported if necessary when compiling Normally synchronization with the complete database should remain selected In that case you can be sure that the most up to date data is always made available to the operating unit In order to speed up the compilation process or if you deliberately wish to continue working with old STEP 7 data you can deactivate synchronization Compilation Settings dialog box In that case however you are responsible yourself for ensuring that the compiled data is kept up to date as required ProAgent User s Manual Issue 12 99 6 5 Configuring in ProTool 6 1 3 Overview Overview of Configuration Steps in ProTool The d
157. on the Operating Unit 5 2 2 What You See on the Message Screen Familiar Layout Basically the layout of the Message Screen is the same as the normal message pages you are familiar with from the standard functionality Additional Functions Compared with the normal way in which messages are displayed however there are a few minor changes see Changes in the Display of Messages Chapte B The important feature is the identification of diagnosable messages by means of an asterisk at the beginning ON p ding Alarm Messages B72345607 A KE 14 15 35 82 86 1997 GRUA Assembly of electronics workpiece C xu y interrupted x 643021 AR 13 13 27 82 86 1297 GRUB Conveyor belt 1 jammed 8512888 A KG 11 17 28 HB2 86 1997 GRUBB Press 1 oil pressure too low Message Screen As Shown on OP25 1 An asterisk appears here if the message displayed is diagnosable i e if a process diagnosis can be carried out for that message You can only call up the Detail Screen or the Movement Screen 2 The message number is shown here in the normal way However it is three digits longer than the numbers you are familiar with from previous projects ProAgent User s Manual Issue 12 99 5 15 Display on the Operating Unit 3 If the message concerned is an ALARM S message only this type of message is diagnosable the message number is followed by the letter A The remaining text is arranged in the way you are familiar with f
158. on you need to correctly place the program code displayed Changing Display Mode If you prefer to see the information displayed in LAD format you can use this key to switch from STL to LAD display mode If you then press the corresponding key again the symbol table mode will be displayed If you then press the corresponding key again the display will return to the STL mode The icon on the key always indicates the mode that will be shown next Deducing Information The statement list shows the individual operators and operands status bits logical operation results symbols and remarks a All instructions that have led to the issue of an alarm message are identified by this symbol This means you can see right away where your fault monitoring system gave the alarm If you examine the instructions concerned you will quickly be able to locate the cause of the fault The logical operation results will help you in that regard ProAgent User s Manual Issue 12 99 5 59 Display on the Operating Unit Additional Actions Transitions and Networks At E You use this key to change to the next error in other words to the next fault action of the unit Use this key within the same fault to switch to the next transition or the next network that could have triggered this fault You will find details of this in the chapter called Changing the Action Transition or Network STL Chapter 5 6 3 6 Modifying the
159. one step back and does not have a stack there is a risk of getting stuck in an endless loop ProAgent User s Manual Issue 12 99 6 13 Configuring in ProTool Moving Directly to the Diagnosis Screens 6 14 You can also bypass the Diagnosis Start Screen by activating the Message Screen or the Overview Screen directly from any other screen in your configuration You can then move from the Message Screen or Overview Screen to the Detail Screen or Movement Screen You can also activate the Detail Screen and the Movement Screen from any other system screen but in that case a diagnosable message must have been selected in the Message Window or the Message Line System QC X Diagnosis Direct Access to Individual Diagnosis Screens Caution In the case of a direct call from your own system screens specific functions have to be executed prior to changing screens Omission of those functions will result in errors in the process of constructing the diagnosis screens To access the Message Screen or the Overview Screen from any of the screens in your project proceed as follows 1 If you wish to assign the function to a soft key open the screen from which you wish to be able to access one of the diagnosis screens If you wish to assign the function to a function key choose the menu option System Screen Keys If you wish to assign a button on a TP create this button under the menu item Paste Button
160. onfiguration Configuration on a TP is conducted by means of the Direct Key function PROFIBUS Direct Keys You use PROFIBUS direct keys to set bits in the I O area of the SIMATIC S7 directly from the operating unit The bit area is defined in STEP 7 The bit is set when you touch the direct key and reset again when you release the key or exit the Screen Basic Requirements e You have installed that is integrated ProTool at the time of generating the configuration e During operation the operating unit is connected to a SIMATIC S7 by means of PROFIBUS DP e You have defined the bit area for direct keys in STEP 7 Information relating to configuration can be found in the User s Manual entitled Communication If these basic requirements are not met ProTool interprets the configured button as a direct key to be used for activating the direct key module The number of PROFIBUS bits that can be manipulated by means of direct keys depends on the device OP25 OP27 TP27 6 24 0 23 OP35 OP37 TP37 TP 27 10 40 0 39 ProAgent User s Manual Issue 12 99 8 19 Modifying the Diagnosis Screens Direct Keys for Direct Key Module 8 6 2 8 20 You can use these direct keys to activate the outputs ports of the optional direct key module at the rear of the operating unit The port is set when you touch the key and reset again when you release the key Further information about the direct key module for OPs can be
161. onment The tools for programming the PLCs under STEP 7 have their own documentation which is not included in the above diagram Whereas with ProTool the configuration software and devices are described separately from each other the User s Guide and online Help for ProAgent explain both the configuration and operation on the devices The online Help and User s Guide are identical to a large extent However detailed descriptions of individual dialog box elements and a reference section of all functions and error messages are available only in the Online Help ProAgent User s Manual Issue 12 99 Preface 1 3 History The different releases of the User s Guide describe the following software versions Release 06 97 Release 07 98 Release 01 99 Release 09 99 1 4 Notation ProTool 3 0 through 4 0 ProAgent 3 0 through 4 0 ProTool Version 5 0 or higher ProAgent Version 5 0 or higher Functional Expansions ProAgent Version 5 1 or higher Expansions for Touch Panel ProAgent Version 5 2 or higher Functional Expansions Different character formats are used to help you find your way through the text as follows Output F1 System ProAgent Messages dialog box Words in typewriter font Courier represent inputs and outputs as they appear on the screen of the PC PU or on the operating unit display Names of keys are printed in bold type face Menu options are shown in italics Successive submenus options
162. open the Detail Screen from any point you must on an OP assign a corresponding screen selection function to a global function key je If when the system is running the Message Window then appears you can lt 0 use the Change Window key to switch to that window and then use the specially configured function key to call up the Detail Screen On a TP you must assign a corresponding screen selection function to a button in the screen from where you want to open the Detail Screen A global opening function is not possible on a TP ProAgent User s Manual Issue 12 99 Modifying the Diagnosis Screens 8 6 8 6 1 Using Direct Keys Direct Keys Introduction In Movement Screens ZP_MOTION of the standard projects movements are triggered by means of the Set Bit function As an alternative you can also use the direct key functionality to operate your installation Direct keys enable you to implement operating actions quickly without any communication related delays Quick operating actions are essential for example for typing mode You can use two different types of direct key depending on the hardware e PROFIBUS Direct Keys e Direct keys for activating the direct key module It is not possible to use PROFIBUS direct keys and direct keys for the direct key module at the same time within a project If you use the F and K keys on an OP as direct keys all you require is the appropriate hardware and hardware c
163. operands and all logical operation results are also detailed Signals that have caused a fault are highlighted A detailed description of the Detail Screen is given in the chapter Detail Screen Chapter 5 6 Detail Screen STL Format As Shown on OP25 ProAgent User s Manual 5 8 Issue 12 99 Display on the Operating Unit 5 1 3 How the Diagnosis Screens are Linked to One Another Five Diagnosis Screens The five diagnosis screens Message Screen Overview Screen Detail Screen Movement Screen and Step Screen are linked by means of keys so that you can switch to and fro between the different screens One Diagnosis Start Screen There is also a Diagnosis Start Screen that often serves as the point of entry to the diagnosis functions see How to Activate Diagnosis Chapter 5 1 1 Links The diagram below shows the ways in which you can navigate between the screens Diagnosis Start Screen ua LN Overview Screen Message Screen AN f 5 ASIE ZPAS Previous sc Previous screen Step Screen Movement Screen had i Previous screen hel E Previous screen Detail Screen he E Previous screen Possible Navigation Routes Between the Diagnosis Screens ProAgent User s Manual Issue 12
164. osable project Therefore remove these functions from your project if necessary ProAgent User s Manual Issue 12 99 6 29 Message Processing 7 Overview This chapter provides detailed information about the message number procedure ALARM_S It explains how ALARM_S differs from the message bit procedure and how the system behaves in the event of critical overloads 7 1 Message Number Procedure ALARM_S Why ALARM S The STEP 7 option packages S7 PDIAG and S7 GRAPH only issue ALARM S messages For that reason the message number procedure ALARM S must be used for configuring process diagnosis in ProTool as well What is ALARM S ALARM S is a message number procedure The message numbers are issued automatically during the configuration process in STEP 7 The numbers are used as the basis for assignment of the correct message text When a fault arises the operating unit receives a message containing the message number On the basis of the number the corresponding message text is identified and displayed When a fault occurs the CPU stores not only the status of the message arrived departed acknowledged but also the time This enables precise diagnosis of the cause of the fault The message information is stored on the PLC and is not discarded immediately after issue of the message This means that individual network components e g the OP can later log themselves on for Updating ProAgent User s Manual Issue 12 99 7 1
165. ows 95 and Windows NT 1 From the Windows Start Menu choose Settings Control Panel gt Add Remove Programs 2 Choose the nstall Uninstall tab 3 From the list of programs select S MATIC ProAgent V5 x 4 Click the Add Hemove button and follow the instructions on the screen ProAgent is then removed from your system ProAgent User s Manual Issue 12 99 2 3 Introduction 3 Overview 3 1 This chapter explains the benefits of process diagnosis and shows you how to locate a fault on the operating unit and rectify it An overview shows the steps required for configuration and where the interfaces between STEP 7 ProTool and ProAgent are At the end of the chapter a number of important terms that are frequently encountered in the context of process diagnosis are explained What Process Diagnosis Can Achieve When you use SIMATIC S7 controllers you can configure a powerful process diagnosis system It will help you to rapidly identify potential problems and to eliminate them In that way you will be able to increase the availability of your installation reduce down times and bring down costs Alarm message on the operating unit a Automatic analysis Display of cause of fault on the operating unit ProAgent process diagnosis option package System availability f C 3 Down times Execution of movements 9Costs from the operating unit to rectify faults Sequence and Benefits of Process
166. p to the first and then to all other transitions With S7 GRAPH units that report a monitoring fault from one transition to the next With units programmed with S7 GRAPH and using movement blocks created with S7 PDIAG the change is made initially between the transitions and then to the movement blocks The display of the transitions in the third and fourth lines then changes accordingly see What You See on the Detail Screen LAD Chapter 5 6 4 1 Once the last transition has been reached the locking condition of the step is displayed and the cycle starts again from the beginning You can tell which transition is currently being displayed from the inverted transition number If the locking condition is being displayed the inverted step number is displayed Multiple Assignments of Monitored Operands 5 72 With Multiple Assignments Chapter 5 6 5 3 to a monitored operand the cause of the error may reside on different networks You can use this key to switch between the networks affected You can see which network is currently being displayed from the second line of the detail screen Hover the block number displayed on the first line remains as it is ProAgent User s Manual Issue 12 99 5 6 4 7 5 6 5 5 6 5 1 Display on the Operating Unit Toggling Display of Operand Symbol and Remarks LAD An instruction can be assigned a symbol and remarks in STEP 7 You can have these displayed on the Detail S
167. package on your system under STEP 7 and ProTool e The chapter Introduction explains the benefits of process diagnosis and shows you how to locate a fault on the operating unit and rectify it An overview shows the steps required for configuration and where the interfaces between STEP 7 ProTool and ProAgent are At the end of the chapter a number of important terms that are frequently encountered in the context of process diagnosis are explained e Installing the ProAgent option package adds a number of new menu options and functions to the basic ProTool program The chapter Effects on ProTool show you what those new menu options and functions are and what purposes they have e The chapter Display on the Operating Unit explains how the individual diagnosis screens appear on the operating unit what they show and what functions you can activate This is information you need to know before you create your own projects e The chapter Configuring in ProTool then explains how to start configuring in ProTool yourself It shows you how to incorporate a process diagnosis in a new project or how you can upgrade an existing project to include process diagnosis The chapter Message Processing provides detailed information about the message number procedure ALARM S which replaces the message bit procedure previously used in ProTool e The chapter Modifying Diagnosis Screens shows you how you can modify the diagnosis screens to suit specific requi
168. parameters in front of the percent sign specify the number of the element referenced and the data type of the array In the example above the elements 1 and 3 are referenced The data type of the array is W WORD The data type depends on the program code as follows e n S7 GRAPH an element of the type W WORD is always used ProAgent User s Manual 7 10 Issue 12 99 Message Processing e Otherwise the following data types are permissible WORD mw mm n Note The element and data type do not need to be specified if the item referenced is the first element of an array of the type INT Formatting Output The parameters between the percent sign 96 and the final delimiter determine the output format of the data The syntax is based with some minor restrictions on the familiar syntax of the C command sprint f Flags for alignment of the output are not supported The first figure specifies how many characters are to be used for output The number of characters includes the decimal point and decimal places if they are to be shown In the example above 1 character and 4 characters respectively are to be used for output of the data If the actual figure to be displayed cannot be shown in full because it exceeds the number of characters specified hash characters are printed in place of the digits thus If the process data item to be displayed is a fixed point number the number of charact
169. pter Overview of Configuration Steps in ProTool Chapter 6 1 3 Requirements of the PLC Program As universal system tools ProTool and ProAgent are closely compatible with the STEP 7 software A breakdown of the minimum requirements to be satisfied by the PLC program in order that you can define a process diagnosis in ProTool is given in the chapter Requirements of the PLC Program and the Project when Upgrading Chapter 6 2 1 In order that you do not have to define the same data more than once the system uses a common database as an interface As a general rule therefore the PLC program should already exist and have been translated before you start working in ProTool A list of which steps should have been completed in STEP 7 at what point is given in the chapter Shared Database with STEP 7 Chapte 6 1 2 ProAgent User s Manual Issue 12 99 6 25 Configuring in ProTool Configuration Steps in ProTool The process of configuration in ProTool requires only a few operations as follows A detailed description of the individual steps is given in the chapter Configuring a Process Diagnosis Chapte The list below outlines the special considerations when upgrading an existing project 1 Incorporating the Diagnosis Screens To begin with you copy the supplied standard diagnosis screens into your project This can be done easily via the Clipboard 2 Linking the Diagnosis Screens You have to create a means of accessing the
170. r 8 4 8 you can filter messages below a given priority The operator can then concentrate on the causal errors in the case of messages overload ProAgent User s Manual Issue 12 99 Message Processing Types of ALARM_S Message Configuration of messages in STEP 7 involves two types of ALARM S message They differ in the way in which they are acknowledged e Alarm messages Alarm messages may or may not need to be acknowledged Alarm messages are supported by diagnostics e Event messages Event messages normally do not need to be acknowledged These messages are not supported by diagnostics Configuring ALARM_S Messages ALARM_S Messages Chapter 7 3 The advantage of this is that the messages ALARM_S messages are not 173 ured in ProTool but in STEP 7 see Configuring are compiled centrally and only have to be created once ProAgent User s Manual Issue 12 99 7 3 Message Processing 7 2 Display Classes What Are Display Classes 7 4 The CPU of a PLC always issues ALARM_S messages to all stations that are logged in However it may be that you do not want to display all messages on a particular operating unit because there would be too many for the operator to deal with for example In that case specific messages could be displayed only on a control desk for example In order to be able to selectively control display of messages in that way in STEP 7 each message can be assigned what is termed a Display C
171. ram When upgrading ProAgent User s Manual Issue 12 99 Index Requirements before starting work RLO S S7 GRAPH Requirements Special overview screen S7 PDAS E MELLON Select Display ae Selecting by diagnosability Selection Units during configuration Settings menu item 4 1 Shared database Access to Importing message text With STEP 7 Signal List SIMATIC HMI documentation Soft keys Detail screen LAD Detail screen STL Message screen Movement screen 5 38 Overview screen Softkeys Detail Screen Signal List 5 48 Software requirements Standard screens Additional 4 3 Incorporating Linking 6 6 12 81 e Starting process diagnosis STEP 7 Access to database during compilation 6 20 Requirements 6 15 6 24 Shared database with Index Step screen Design Keys Practical procedure 5 32 Usage STL Structure of the documentation XE Additional support XE Support XE Help desk Support Support Switching Over SIMATIC IEC Display Mode Detail Screen 8 12 symbol Display in Detail Screen Signal List 53 Display on detail screen LAD 5 73 Display on detail screen STL Display simultaneously with comment 8 10 Symbols on diagnosis screens Synchronize 6 3 6 20 System limits DRAM requirement of the project components How can you save on memory space B 5 Memory requirement calculation example The diagnosis structures System limits introduction B 1
172. rations to the diagnosis screens or create your own in exceptional circumstances Note If you are using an upgrade of ProAgent make sure that the standard screens match the current program release Instructions on how to adopt the latest diagnosis screens supplied with the upgrade into existing configurations can be found in the Installation Instructions manual of the upgrade You can ignore this and the following chapters if you are not intending to make any alterations to the diagnosis screens Caution If you make changes to the diagnosis screens please be sure to take note of the guidance offered as otherwise the functional capability of the diagnosis system could be significantly impaired ProAgent User s Manual Issue 12 99 8 1 Modifying the Diagnosis Screens Sensible Adaptations The diagnosis screens have a uniform design that is based on the design of the standard screens supplied with ProTool That design represents the best possible compromise between a range of different requirements profiles but can of course not reflect very specific requirements in particular cases If your system is particularly complex you might decide for example to use a smaller font size so that more units can be shown on the display at once Or you may have no use for certain items of information and therefore delete the output fields concerned And of course you can always adapt the layout to match the rest of your project use dif
173. reens Detail screen 3 4 5 3 5 9 5 42 Branch direct 18 18 Usage Detail Screen LAD Action Ln 5 71 ee Design 5 64 5 64 Display change 5 Displaying T ak 5 73 Initial values Current status 5 71 Keys Transition change Use in practice Detail Screen Signal List Design Display symbol remark Initial values current status Keys practical usage Switch action 582 Switch transition 15 52 Detail Screen STL Action change Design Display change Displaying SEE 5 63 Initial values Current status 5 61 Keys Symbol ET comment displayed simultaneously 8 10 Transition change 5 Use in practice Diagnosis screen structure Diagnosis screens Add lines Changing font size and font Cursor control Incorporation 6 8 Link Linking Modify Name conventions 8 6 Operation Remove lines Symbols Tasks Diagnosis start screen 5 3 5 9 6 12 Direct keys 810 020 821 B23 Display 5 15 5 20 29 535 5 43 5 54 Changing on detail screen LAD Changing on detail screen STL Changing on overview screen ProAgent User s Manual Issue 12 99 Display classes Selecting Documentation components Download DRAM requirement of the project components B 3 E EM 1 5 Enabling process diagnosis Errors Exclusion Operands F FB 1 5 FC Files installed Filter criteria definition 8 15 Fixed screen Font modification Foreign languages Form DRAM Requirement of the Project Components Memor
174. rements e Finally the Appendix provides a reference section detailing all system messages that appear on the operating unit in the event of an error along with details of the possible causes and remedies The Appendix also contains information about the system limits that you must take into consideration in your project Other Sources of Information More reference information is available from the Online Help Note With regard to the description of general ProTool functions please also consult the ProTool User s Manual and the ProTool Online Help Information about STEP 7 and its option packages is provided by the relevant manuals for STEP 7 S7 PDIAG and S7 GRAPH These programs too have extensive online Help systems ProAgent User s Manual 1 2 Issue 12 99 1 2 Preface Position within the Information Environment There are a number of manuals and online help systems relating to ProTool and the various types of operating unit The diagram below illustrates the position of the ProAgent documentation within the overall documentation structure ProAgent Option Package ProAgent User s Guide Online Help ProTool Operating units p fI O n User guides and Equipment online help manuals Position within the Information Envir
175. rmation relating to the unit on which the process fault occurred The display distinguishes between areas 4 to 11 depending on whether the unit has been programmed with S7 PDIAG or with S7 GRAPH 1 This shows the block type of the unit with the fault i e FC DB or OB 2 This field shows the block number of the unit with the fault 3 Atthis point text assigned to the unit appears the symbol for a block or an absolute identifier If the unit has been programmed with S7 GRAPH lines 2 to 4 of the display have the following contents 4 This field identifies the step selected by means of the test Step This field displays the user number of the step selected This field displays a text that is assigned to the step displayed under 5 This field displays the text Transi for Transitions This field displays the numbers of the transitions of the step displayed The transition displayed is highlighted in inverse type If step monitoring view is displayed rather than a transition then accordingly the step number is highlighted 9 This field displays the text Tr Name for Transition Name The field remains blank if the locking condition of the step is shown 10 This field displays the name of the transition displayed The field remains blank if the locking condition of the step is shown ProAgent User s Manual Issue 12 99 5 45 Display on the Operating Unit If the unit has been programmed with S7 PDIAG lines
176. rms successful acknowledgement of the current unit ProAgent User s Manual Issue 12 99 Appendix System Messages A 1 5 Unit Could Not be Acknowledged Message Number Cause Remedy 4082 A communication fault has occurred when attempting to acknowledge the current unit In most cases you will receive other system messages which provide more information about the cause of the communication problems Attempt to acknowledge the unit again A 1 6 No Unit Capable of Acknowledgement Selected Message Number Cause Remedy 4083 This message appears if you attempt to acknowledge a unit when no unit capable of being acknowledged is selected That will be the case if e the Message Screen is open but no diagnosable message is selected on it e the Overview Screen is open but the unit selected on it does not offer an acknowledgement bit ProAgent User s Manual Issue 12 99 A 3 Appendix System Messages A 2 Overview Screen System Messages A 2 1 Error Identifying Faults on a Unit Message Number Cause Remedy The list of active steps and or steps with faults could not be read from the PLC The cause is generally a communication fault between the operating unit and the PLC In most cases you will receive other system messages which provide more information about the cause of the fault This might be such things as faulty connectors a modified program on the PLC or insufficient memory on the operating unit A 2
177. rom a standard message page i e Message status arrived departed acknowledged Time of arrival event 4 5 6 Date of arrival event 7 Acknowledgement group 8 Message text 5 2 3 Message Screen Keys You can use the following keys on the Message Screen On an OP you use the cursor keys to move the cursor up and down On a TP you can select a message by touching it on the screen If there are more messages than can be shown on the screen at the one time you can scroll the display You use this key to specify whether all messages are to be displayed or diagnosable messages only see Selecting by Diagnosability Chapter 5 2 5 You use this key to switch to the Overview Screen Use this key to switch to the Detail Screen in Signal List format You must have selected a diagnosable message first You use this key to switch to the Movement Screen You must have selected a diagnosable message first You use this key to return to the Diagnosis Start Screen Message Screen Keys ProAgent User s Manual 5 16 Issue 12 99 Display on the Operating Unit 5 2 4 How to Work with the Message Screen This chapter gives a general outline of how to use the Message Screen in practice Aims You have opened the Message Screen in order to obtain an overview of the pending alarm messages You wish to carry out a process diagnosis for specific messages Pending Hlarm Messages Berd4so7 A K 14 15 35
178. rom the Message Screen the selected unit is determined by the alarm message that was highlighted by the cursor when the Overview Screen was quit The unit to which that alarm message is attributable becomes the selected unit on the Movement Screen e f you have activated the Movement Screen from the Overview Screen the selected unit is the unit that was highlighted by the cursor when the Overview Screen was quit If there are a number of hierarchical levels between the units the unit on the highest hierarchical level is always displayed see Hierarchical Units on the Movement Screen Chapter 5 5 5 Specifically the information about the selected unit is made up of the following details 1 the block type 2 the block number 3 the block symbol or an absolute identifier List of Movements Below the information line for the selected unit the movements are displayed The individual movements are listed one below the other on separate lines and separated by a ruled line Their order of display corresponds to the sequence of screen numbers and position numbers which can be assigned as attributes when you program the movement blocks in S7 PDIAG If no default values are specified at that stage or if individual positions are assigned twice over including on several CPUs the order is arbitrary Each movement can be executed in two directions e g in out open close up down forward backwards One direction of movement is symbo
179. s All suggestions for improvements gratefully received Copyright Siemens AG 1999 Subject to alteration on the basis of technical modifications or advances Order No 6AV3681 1AC05 1PBO Contents 1 Preface 1 1 Guide to the Manual 1 2 Position within the Information Environment 1 3 History 1 4 Notation 1 5 Abbreviations 1 6 Other Sources of Assistance 2 Installation 2 1 System Requirements 2 2 Installing ProAgent 2 3 Uninstalling ProAgent 3 Introduction 3 1 What Process Diagnosis Can Achieve 3 2 How a Process Diagnosis is Carried Out 3 3 How a Process Diagnosis is Configured 3 4 Before You Start 3 5 Important Terms 4 Effects on ProTool 4 1 Additional Menu Options in ProTool 4 2 Additional Functions in ProTool 4 3 Additional Standard Screens Diagnosis Screens 4 4 ALARM_S Message Procedure ProAgent User s Manual Issue 12 99 a ee l AI S ae BIR D X E m m oO IN S Qe e Oo gt F E co a cd o A 6 eo Contents 5 Display on the Operating Unit Overview of the Diagnosis Screens 1 How to Activate Diagnosis 2 The Purpose of the Individual Diagnosis Screens 3 How the Diagnosis Screens are Linked to One Another 4 General Principles of Using the Diagnosis Screens 5 2 Message Screen 5 2 1 The Purpose of the Message Screen 5 2 2 What You See on the Message Screen 5 2 3 Message Screen Keys 5 2 4 How to Work with the Message Screen 5 2 5 Selectin
180. s are to be displayed on the operating unit being configured You make your selection by choosing System Messages Settings You can find a detailed description in the chapter Selecting the Display Classes Chapter 6 1 7 If you do not make a selection all display classes display classes 0 to 15 are displayed as the default ProAgent User s Manual Issue 12 99 7 5 Message Processing 7 3 Configuring ALARM_S Messages Configuring Messages in STEP 7 ALARM_S messages are always configured in STEP 7 rather than in ProTool The advantage of this is that you can use the messages on different display units but only have to enter them once When configuring messages in STEP 7 you can either enter simple unformatted text or make use of the facility for device specific message configuration Depending on the display unit in question you can then specify such effects as flashing text and define additional information Detailed reference information on the individual dialog boxes is given in the STEP 7 Online Help The sections which follow provide a brief overview of the general procedure General Procedure 7 6 If for example you create an operand monitoring routine in S7 PDIAG the following dialog box appears initially ETE PDIAG Address Monitoring x General Definition Initial Diagnostic Address 41 0 m Monitoring Definition fONDT AT 0 5000 C 1 Level 2 Level Iv Delay C 3 Edge O
181. s difficult to calculate the amount of memory required for diagnosis precisely in advance since the various diagnosis data are dependent on each other You will however find below a listing of how much memory space potential components of a project may each take up Not taken into account in the listing are more far reaching configuration data for visualization of the installation On the basis of the general specifications and the current figures from your project you can estimate your minimum requirement for memory space How this is done is explained in a concrete calculation example ProAgent User s Manual Issue 12 99 B 1 Appendix System Limits B 2 B 2 System Limits of the Diagnosis Independent of the operating unit a diagnosis must comply with the following system limits e The diagnosis structures used must not exceed the following quantity limitations S7 PDIAG unit incl subunits or S7 GRAPH step sequences Total number of messages with and without analysis of criteria of which messages with analysis of criteria or S7 GRAPH steps or transitions Simultaneously pending messages Criteria per analysis of criteria 64 0 Total number of criteria 24 00 e Overall the diagnosis structures must take up no more than 64 kbytes of memory space The memory requirement of the diagnosis structures of a project depends on which and how many of the structures listed below you use How you can determine wh
182. s in STEP 7 see automatically logged directly to the connected printer If you configure device specific messages you can specify separately for each message whether it is to be logged or not If there are several CPUs in a network this means that messages may not always be received in chronological order by the operating unit Messages are always printed in the order in which they are sent by the CPUs This is also the case with every synchronisation Printing Messages In the Event of a Buffer Overflow Printing of the message buffer contents in the event of a Buffer Overflow is carried out in the same way as with the familiar message bit procedure All messages are printed before being deleted ProAgent User s Manual Issue 12 99 Message Processing 7 9 Message Overload It can happen that a large number of ALARM_S messages are issued within a short space of time This can result in the build up of processing backlogs Communication Overload If the time gap between the first occurrence of a message and a subsequent occurrence is very short it may be that the first message has not yet even been sent In that case the CPU reports the current status i e the most recent occurrence of the message Every station i e including the operating unit is informed at the same time however that at least one signal change that could not be sent has occurred The message number appears on the operating unit in inverted type light
183. s screens of the new version of ProAgent to the new project by means of drag amp drop Detailed instructions on how to copy screens can be found under Integrating the Diagnosis Screens Chapter 6 1 4 4 Copy your own screens that you wish to continue to use from your old project to the new one The old standard diagnosis screens are not copied over at the same time The links between your own screens and the new diagnosis screens are now automatically correct 5 Likewise per drag amp drop copy the messages that you wish to continue to use from your old project to the new one 6 If you had made specific settings in your old project in the System menu re enter them now for your new project 7 In the same way you also have to re enter any inputs you had made under File Project Info You can now open the new standard diagnosis screens in your existing project Message Window and Message Screen Standard Message Page 6 28 The diagnosis Message Screen makes use of the functions provided by the standard message page for the purposes of displaying messages The Message Page always occupies the whole of the screen and does not permit use of any keys Accordingly no pictograms can be displayed either In order to make it possible to do so for the purposes of diagnosis the diagnosis Message Screen is made up of two superimposed screens i e e inthe background the blank diagnosis Message Screen on which the relevant
184. s the Movement Screen Symbolizes the Step Screen Keys for Selecting Diagnosis Screens ProAgent User s Manual Issue 12 99 5 13 Display on the Operating Unit 5 2 5 2 1 Message Screen The Purpose of the Message Screen The Message Screen shows all pending process messages The messages are listed on the screen in chronological order The Message Screen often serves as the point of entry to the diagnosis On it you can observe whether faults occur and which faults those are and you can then switch to any of the other diagnosis screens as required Additional Functions Compared to the Message Page 5 14 The Message Screen is structured in a very similar way to a normal message page However it provides some additional information and functions For example you can see at a glance which messages are diagnosable You can then carry out a process diagnosis for those messages You can select a specific message and use keys to call up other context sensitive diagnosis screens such as e The Detail Screen which shows the program code the monitoring of which led to the alarm message selected e The Movement Screen which shows all movements for the unit with the fault And of course you can also execute those movements directly from that point as well If you want to see an overview of the various different units of your system you can call up the Overview Screen ProAgent User s Manual Issue 12 99 Display
185. s with faults on the subunit Change transition or network Sometimes the cause of a fault cannot be recognized at first glance e n S7 PDIAG units the detail screen always shows one network only However the cause of the fault may be located in more than one network e Inthe same way with S7 GRAPH units the interlocking condition of the step or individual transitions could be the cause of the error message Use this key to switch from one possible cause of a fault to the next With S7 PDIAG units from one associated network to the next With S7 GRAPH units that report an interlocking fault from the interlocking condition of the step to the first and then to all other transitions With S7 GRAPH units that report a monitoring fault from one transition to the next With units programmed with S7 GRAPH and using movement blocks created with S7 PDIAG the change is made initially between the transitions and then to the movement blocks ProAgent User s Manual 5 52 Issue 12 99 Display on the Operating Unit see What You See on the Detail Screen Signal List Chapter 5 6 2 1 Once the last transition has been reached the locking condition of the step is displayed and the cycle starts again from the beginning The display of the transitions in the third and fourth lines is ptor 56 accordingly You can tell which transition is currently being displayed from the inverted transition number If the locking cond
186. sage buffer is kept even longer ProAgent User s Manual Issue 12 99 7 15 Message Processing 7 7 Message Acknowledgement ALARM S Messages Requiring Acknowledgement When a message is acknowledged by a station on the network the CPU is immediately notified The CPU then distributes the acknowledgement to all connected stations It is only to this message that the operating unit responds i e only at this point does it enter the acknowledgement in the message buffer Note The CPU issues a time stamp for the acknowledgement event but does not store it It is therefore not possible in the event of a subsequent update to determine whether or when a message has been acknowledged see Updating Chapter 7 10 ALARM S Messages Not Requiring Acknowledgement 7 16 In the case of those ALARM_S messages that although they are configured as alarm messages do not require explicit acknowledgement by the user the CPU acknowledges the message automatically when it arrives The acknowledged event is then immediately entered in the message buffer along with the arrived event ProAgent User s Manual Issue 12 99 7 8 Message Processing Printing Messages You specify which messages are to be printed in the usual way in ProTool by choosing the menu option System Messages Settings Message Logging Configuring ALARM S Messages Chapter 7 3 all message events are If you do not specify any device specific MN setting
187. screen and merely copy some or all of the screen contents In order to ensure that full diagnosis capability is obtained you need the complete screen including all tags and functions Essential information such as key assignment and functions configured for screen selection are not included when individual screen elements are copied If you do not require all the information contained within a diagnosis screen you should nevertheless still copy the complete screen to begin with You can then delete individual screen elements or add new ones afterwards When doing so make sure that you also observe the guidance notes given in the chapter Modifying the Diagnosis Screens Chapter Checking the Target Positions You only need to change the number of target positions on the Movement Screen ZP MOTION if your PLC supports movements and defines more than 8 target positions per movement see Changing the Number of Target Positions Movement Screen Chapter 8 4 7 ProAgent User s Manual Issue 12 99 6 11 Configuring in ProTool Continuing Configuration You can now continue with the process of configuration as normal But do not forget to configure a screen change to the new diagnosis screens and back again refer to Linking the Diagnosis Screens Chapter 6 1 5 Linking the Diagnosis Screens Once you have incorporated the diagnosis screen see Incorporating the Diagnosis Screens Chapter 6 1 4 you must make them accessible
188. se is not updated if you make changes in STEP 7 without subsequently retranslating the monitoring blocks ProTool will then not have access to the latest data ProAgent User s Manual Issue 12 99 6 3 Configuring in ProTool Content Requirements At certain times ProTool places specific minimum requirements on the data stored in the database It is always preferable of course if the PLC program is already complete and fully tested In practice however this will not always be the case and you may want to be working on the PLC program and the operating unit configuration at the same time The table below shows which data is absolutely necessary at which point A description of the individual stages in the process is provided in the chapter Overview of the Configuration Steps in ProTool Chapter 6 1 3 Incorporating the System plan ProTool STEP 7 diagnosis screens Linking the Diagnosis System plan ProTool STEP 7 Screens Selecting the Units Definition of monitoring routines STEP 7 Translated monitoring blocks STEP 7 Selecting the display Message configuration STEP 7 classes Compiling and Final translated PLC program STEP 7 Downloading Minimum Database Requirements ProAgent User s Manual 6 4 Issue 12 99 Configuring in ProTool Consistency of Data PLCs and operating units exchange data during operation but not their programs As the programmer you are responsible for ensuring that the latest version
189. sic Requirements A PLC must have been suitably programmed in order that movements can be executed from the operating unit The UDT Movement must be used and appropriately wired up More detailed information on programming movements is provided in the S7 PDIAG manual Note Movements can not be defined when programming in S7 GRAPH But in S7 GRAPH you can assign movements from S7 PDIAG to a unit ProAgent User s Manual 5 34 Issue 12 99 Display on the Operating Unit 5 5 2 What You See on the Movement Screen The Movement Screen shows a list of all movements that can be executed for a unit General Layout Like all the diagnosis screens the Movement Screen has a standardized layout There are only minor differences between the various types of operating unit The illustration below shows an example of the Movement Screen as it appears on an OP25 Screwdriver position x R O b Screwdriver position v E l7 OE O F Carriage B B gn L Rotary table R LILI A Im Movement Screen As Shown on OP25 ProAgent User s Manual Issue 12 99 5 35 Display on the Operating Unit Information About the Unit The first line shows information about the selected unit The selected unit is that unit of your system for which the movements are displayed further down the screen Which unit is the selected unit depends on where the Movement Screen was activated from e If you have activated the Movement Screen f
190. sign the new properties collectively Change Font Size and Font On any operating unit there is only a limited area available for display of information For that reason only a limited amount of information can be shown at a time That amount of information can be increased by reducing the size of the font though at the price of a corresponding loss of legibility What s more operating with a touch panel can be made more difficult if screen elements are too small Which criterion is given the greater priority i e maximizing the amount of information displayed or optimizing the legibility of that information and ease of operation depends on the nature of the individual application and can not be decided on the basis of a universal formula The diagnosis screens supplied with ProAgent represent the best compromise for the majority of applications If you wish to see more information on a diagnosis screen you can change the font size by selecting a smaller font size To change the font size or font of text perform the following steps 1 Make sure that the font and font size you want have been defined for the configured languages by choosing System Fonts from the menu If necessary select a different font 2 Open the screen on which you wish to make the alterations 3 If you wish to increase the size of the font first delete enough lines so that no text will subsequently be covered over When doing so be certain to follow the
191. splayed on the operating unit at one time you can scroll the list up or down using the cursor keys To scroll up the list on a touch panel touch the top most line until scrolling is activated To scroll down touch one of the other lines If you are able to scroll an arrow symbol that indicates the possible scroll direction appears above the statement list On an OP you can use the ENTER key to open a list for selecting whether symbols or remarks relating to the individual instructions are to be displayed device dependent On a TP you can open the same list by touching the display This key is used to determine what status is displayed values at the time of occurrence of the fault initial values or the current values see Toggling Display of Initial Values and Current Status Signal List Chapter 5 6 2 4 You use this key to toggle to the next fault in other words to the next faulty action of this unit refer to Changing the Action or Transition Signal List Chapter 5 6 2 5 With units programmed with S7 GRAPH and using movement blocks created with S7 PDIAG the change is made initially to all other transitions and then to the movement blocks You use this key to change within an error The change is normally to the next transition see Changing the Action or Transition Signal List Chapter 5 6 2 5 In the case of Multiple Assignments to a monitored operand the change is to the next network co
192. ssage Page Window you will have first had to select a message The Detail Screen then shows the fault which triggered the message you have selected on the Message Screen e If you have called up the Detail Screen from the Overview Screen you will have first had to select a unit The Detail Screen then shows the fault in the first action of that unit with a fault ProAgent User s Manual Issue 12 99 5 43 Display on the Operating Unit General Layout 5 44 Like all the diagnosis screens the Detail Screen has a standardized layout There are only minor differences between the various types of operating unit The illustration below shows an example of the Detail Screen in Signal List format as it appears on an OP25 You can find an illustration and a description of the STL variation in the chapter What You Can See in the Detail Screen STL Chapte you can find an illustration and description of the LAD variation in the chapter What You Can See in the Detail Screen LAD Chapter 5 6 4 1 5 6 4 1 6 4 1 5 6 4 1 Unit T Conveyor belt 1 7 CN Step 12 Start conveyor belt B Trans Est 12 13 14 15 16 17 Oa Name Mator power on A i Symbol D 8 8 Grid he D i d Feed O 9 Detail Screen example of signal list format on an OP25 programmed with S7 GRAPH ProAgent User s Manual Issue 12 99 Display on the Operating Unit Information About the Unit The top section of the display shows detailed info
193. ssage number Other Sources of Information 4 4 More information on the subject of message processing and ALARM S is available in the chapter Message Processing Chapter 7 You can find a description of the procedure to be followed during configuration in the chapter Selecting the Display Classes Chapter 6 1 7 ProAgent User s Manual Issue 12 99 Display on the Operating Unit 5 Overview 5 1 5 1 1 This chapters shows you in detail how the individual diagnosis screens appear on the operating unit what they contain and what functions you can activate Overview of the Diagnosis Screens How to Activate Diagnosis Diagnosable Messages You are already familiar from ProTool with the options available for working with message lines and message windows depending on the operating unit and configuration alarm messages are either displayed in a message line or in an alarm message window The message line and alarm messages window are still used even if a process diagnosis has been configured using ProTool and ProAgent However diagnosable messages are now identified by an asterisk in front of the message number You can only carry out a diagnosis for that type of message 1234567 A KGQ HH MM SS DD MM YYYY GRUOO Boiler 13 temperature 190 degrees Inform shift supervisor Tel 007 Structure of an Alarm Message ProAgent User s Manual Issue 12 99 5 1 Display on the Operating Unit Diagnos
194. t Screen This chapter gives a general outline of how to use the Movement Screen most effectively in practice Aims First of all you will have opened the Message Screen or the Overview Screen There you will have selected an alarm message or a unit and subsequently opened the Movement Screen Now you want to eliminate the fault and execute certain movements manually on the unit with the fault You also want to see which movements are blocked Unit DBZ1 Hssembly door L Screwdriver position x R IE a A LIU F Screwdriver position v B l7 i LIU F Carriage B b a Bis L Rotary table R gt LI A ia Movement Screen As Shown on OP25 Which Unit You check the top line of the display to make sure that you are on the right unit as only the movements of that unit are displayed ProAgent User s Manual Issue 12 99 5 39 Display on the Operating Unit Which Movements The rest of the screen lists all the available movements one below the other on separate lines You can scroll the list up or down if there are more possible movements than can be shown on the screen at once In the top left corner of the screen there are small arrows indicating the presence of additional movements If a unit also has hierarchically subordinate units you can use this key to view the movements of those subunits as well see Hierarchical Units on the Movement Screen Chapter 5 5 5 Which Faults A If a movemen
195. t is blocked this symbol appears in the centre of the line below the name of the movement Whether a movement can be executed in a particular direction is indicated by the triangle symbols at either end of each line e Afilled in symbol indicates that the movement can be carried out in the specified direction e f the symbol appears in outline only the movement can not be carried out in the specified direction Note The fact that a movement can not be executed does not mean that is must be blocked There may be exclusion criteria specified in the PLC program or the maximum limit of movement may already have been reached Executing a Movement 5 40 You have now found the movement that you wish to execute and established that it is not blocked and can be executed On an OP execute the movement by pressing the soft key to which the relevant triangle symbol is pointing that is to the left or right next to the display On a TP proceed as follows 1 Select the movement to enable it to be operated 2 Execute the movement by touching the appropriate triangle symbol If you do not execute a movement within a specific length of time the movement selected is automatically deselected again and thus disabled Warning The corresponding bit is still set on the PLC even if a movement is not possible Subsequent handling depends on the PLC program ProAgent User s Manual Issue 12 99 Display on the Operating Unit Tracking Move
196. t the monitored signal to the incorrect status Refer to Togaling Between Partial and Full View STL Format Chapter 5 6 3 4 21 A spectacles symbol appears here if the current status bits are displayed rather than the status bits at the time of occurrence of the fault initial values see Toggling Display of Initial Values and Current Status STL Chapter 5 6 3 5 5 6 3 2 Detail Screen Keys STL You can use the following keys on the Detail Screen in STL display mode If there are more instructions than can be displayed on the operating unit at one time you can scroll the list up or down using the cursor keys To scroll up the list on a touch panel touch the top most line until scrolling is activated To scroll down touch one of the other lines If you are able to scroll an arrow symbol that indicates the possible scroll direction appears above the statement list On an OP you can use the ENTER key to open a list for selecting whether symbols or remarks relating to the individual instructions are to be displayed device dependent On a TP you can open the same list by touching the display This key is used to toggle between partial and full view see Toggling Between Partial and Full View STL Format Chapter 5 6 3 4 Partial view shows only those instructions that have led to a fault This key is used to determine what status and therefore which logical operation results are shown i e the values
197. tains e installation of the ProTool Pro Runtime visualization software commissioning and running the software on Windows based systems The ProTool Pro Runtime visualization software is a copyright product This manual contains information on the installation repair and uninstallation of authorizations C 3 SIMATIC HMI Documentation Application Example Newcomers Start up Guide MP270 Equipment Manual Commissioning engineers Users OP37 Pro Equipment Manual Commissioning engineers Users TP27 TP37 Equipment Manual OP27 OP37 Equipment Manual OP25 OP35 OP45 Equipment Manual OP7 OP17 Equipment Manual OP5 OP15 Equipment Manual TD17 Commissioning engineers Users Equipment Manual ProTool is supplied with example configurations and the corresponding PLC programs This documentation describes how you load the examplesonto the operating unit and PLC run the examples and upgrade the connection to the PLC to suit your own specific application Describes the hardware and the general operation of Multi Panel MP270 It contains installation and commissioning instructions a description of the equipment operating instructions instructions for connecting the PLC printer and programming computer maintenance instructions Describes the hardware installation and inclusion of upgrades and options for the OP37 Pro Describes the hardware and general operation It conta
198. the check box on the left next to the PLC To have only a selection of messages of specific display classes displayed on the operating unit select the desired PLC click the button Details and then make your selections in the Display Classes dialog box The check box to the left of the name of the PLC then appears with a gray background During operation of the system only those messages that belong to a selected display class will then appear on the operating unit 6 19 Configuring in ProTool 6 1 8 Compiling and Downloading Familiar Sequence Compiling and downloading the finished project is done in exactly the same way as you are familiar with from ProTool The process diagnosis configuration is checked at the same time as the general consistency checks are carried out Tip Help on the relevant error messages can be obtained by positioning the cursor on the line with the message concerned and pressing F1 Access to the Shared Database During the process of compilation ProTool accesses the database shared with STEP 7 and imports from it the message texts defined in STEP 7 as well as all diagnosis data required The message texts and the data are then downloaded to the operating unit together with the remaining project data fi ProAgent Shared database with STEP 7 Configuration Messages Compile Diagnosis data Download
199. the international IEC names are shown see Switching Over SIMATIC IEC Display Mode Chapter 8 4 5 13 Symbol or remark for the signal as per the text or graphic list or remarks list in Step 7 If the operating unit display does not provide sufficient space to show symbol and remark parallel to one another you can toggle between the symbol display and the remarks display see Toggle Between Symbol and Remarks Signal List Chapter 5 6 2 6 In the case of tags within DBs only the symbolism is displayed if a symbolic identifier has been stored in the symbol table If no symbol has been created the operating unit only shows the absolute address of the tag 14 A lightning flash symbol appears here because the signal shown next to it has led to an alarm message 15 If there are more instructions than can be displayed on the operating unit at one time the arrow right and arrow left symbols appear You can then scroll the display up or down 16 A spectacle symbol appears here if the current status is displayed rather than the status at the time of occurrence of the faults initial values see Toggling Display of Initial Values and Current Status Signal List Chapter 5 6 2 4 ProAgent User s Manual Issue 12 99 5 47 Display on the Operating Unit 5 6 2 2 Keys in the Detail Screen Signal List You can use the following keys on the Detail Screen in signal list display mode If there are more instructions than can be di
200. tion of the unit 5 Use this key within the same fault to switch to the next transition or the next network that could have triggered this fault You will find details of this in the chapter called Changing the Action or Transition Signal List Chapter 5 6 2 5 ProAgent User s Manual Issue 12 99 5 50 Display on the Operating Unit Modifying the View Options There are a number of ways in which you can adapt the view options to suit your personal preferences Oo If you wish you can have the current status displayed instead of the status displayed at the time the error occurred To do so use this key see Toggling Display of Initial Values and Current Status Signal List Chapter 5 6 2 4 2 Device specific for OP If you wish to view the symbols and remarks relating to the individual instructions use the ENTER key to open the corresponding list box see Toggling Display of Symbol and Remarks Signal List Chapter 5 6 2 6 On a TP you open this same list by touching the corresponding input output field Exiting the Detail Screen 5 6 2 4 This key returns you to the screen from which you activated the Detail Screen Toggling between initial values and current status Signal List The default setting is for display of the status as it was at the time the fault monitoring routine first detected the process fault For that reason the displayed values are also referred to as init
201. to the operator You must therefore assign at least key the function of selecting a diagnosis screen or you must make one of the diagnosis screens the start screen Using Only the Diagnosis Screens 6 12 The simplest approach is for your project to use only the diagnosis screens Diagnosis Start Screen as Diagnosis Use of Diagnosis Screens Only The diagnosis screens are already linked with one another see How the Diagnosis Screens Are Linked to One Another Chapter 5 1 3 All you have to do is to make the Diagnosis Start Screen the start screen of your project as follows 1 Select the Screens object type in the ProTool project window 2 Click the object ZP_PROAGENT with the right mouse button This is the Diagnosis Start Screen 3 Choose Properties from the shortcut menu 4 On the General tab in the dialog box that opens select the Start Screen check box The Diagnosis Start Screen will then be displayed automatically when the operating unit is switched on And from that point you can access all the other diagnosis screens one after the other by means of keys ProAgent User s Manual Issue 12 99 Configuring in ProTool Activating the Diagnosis Start Screen Normally your project will contain other system specific screens in addition to the diagnosis screens In such cases it is useful to make one of those screens the start screen or to create a general start screen From that point you can t
202. unit At the press of a button the operator can switch either to an overview screen a Step screen a movement screen or a detail screen e On the Overview Screen all the units of the system are displayed together with their subunits This shows the operator at a glance the current operating mode and condition of each individual unit e Inthe case of units programmed with S7 GRAPH individual steps of a chain can be set or reset by selecting an additional Step Screen e The Movement Screen provides quick assistance with rectifying faults By looking at the display the operator can tell at a glance which movements are blocked and which can still be executed It can be used to initiate movements by individual units by means of keys e The Detail Screen shows the results of the fault analysis automatically instigated from the operating unit A brief signal list a detailed instruction list STL or a ladder diagram LAD showing the relevant section of the STEP 7 program code appears on the display for that purpose At the same time the status bits of the operands and all the logic operation results can be displayed Signals that have caused a fault are highlighted You can quickly trace the cause of an error in this manner ProAgent User s Manual Issue 12 99 Message Screen Alarm messages Overview Screen Units Status of units Step Screen Operation of S7 GRAPH step chains Movement Screen Movements possib
203. uta Weld door panel 15 Auto Weld door hinge 14 Auto Paint i Auto Overview Screen As Shown on OP25 ProAgent User s Manual Issue 12 99 5 23 Display on the Operating Unit On Which Units are there Faults First of all you want to be able to see on which units there are faults A y Onan OP you can use these keys to move the cursor through the list All units with faults are identified by a warning triangle On a TP you can select the unit you want by touching it on the screen A In order to be able to move more quickly between the units with faults you can use this key to change the Display Mode The cursor then moves directly from one unit with a fault to the next On Which Unit did a Fault Occur First The unit on which the fault occurred first is identified by a flashing warning triangle There is a very strong possibility that the cause of the fault is to be found here and that the other faults are consequential on the original fault Information About the Unit You select the unit with the flashing warning triangle In the top section of the Screen you can now see detailed information about that unit i e block type block number text assigned to the unit and step numbers of the active action and parallel actions see What You See on the Overview Screen Chapter 5 3 2 Detailed Analysis yc If the cause of the fault is not obvious you will want to investigate the fault more thoroughly i
204. utput by the PLC program Further information can be found in the User s Manual entitled S7 PDIAG It makes sense to use the slave monitoring OBs when using DP direct keys e To guarantee proper functioning of the direct keys on a TP Do not position any direct keys in the fixed window Do not configure any trend graphics in a screen containing direct keys Do not configure any trend graphics in the fixed window Erroneously triggered movements can arise if you have used the same port twice For this reason make sure that you use each port only once The Direct Key function can be used only once per button ProAgent User s Manual Issue 12 99 8 23 Appendix System Messages A Overview A 1 A 1 1 This Appendix contains a reference list of all system messages that are displayed on the operating unit in the event of an error It provides information about possible causes of errors and how they can be remedied System messages inform you about critical operating conditions on the operating unit As soon as such an operating condition occurs the operating unit automatically displays a window showing a system message A description of the standard system messages is given in the device manual for your operating unit There are however a number of other system messages that are related to the process diagnosis functions Only those system messages are described here You can look up the explanation easily by the
205. ve more than one fault at the same time Use key combination to Switch to the next fault in the same unit The action of the unit affected by this fault will be displayed A Press this key to switch to the next fault Display of the steps and transitions in the top section of the screen then changes accordingly see What You See on the Detail Screen LAD Chapter 5 6 4 1 Note Once all actions of a unit have been run through and the unit concerned has other hierarchically subordinate units the function moves on to the actions of those units This means that you do not need to return to the Overview Screen and select a hierarchically subordinate unit there in order to be able to see the actions with faults on the subunit ProAgent User s Manual Issue 12 99 5 71 Display on the Operating Unit Change transition or network Sometimes the cause of a fault cannot be recognized at first glance e In S7 PDIAG units the detail screen always shows one network only However the cause of the fault may be located in more than one network e Inthe same way with S7 GRAPH units the interlocking condition of the step or individual transitions could be the cause of the error message Use this key to switch from one possible cause of a fault to the next With S7 PDIAG units from one associated network to the next With S7 GRAPH units that report an interlocking fault from the interlocking condition of the ste
206. w Screen a communication fault or temporary shortage of memory has occurred A 4 2 Error Enabling or Disabling Movements Message Number Cause Remedy 4062 A communication fault or temporary shortage of memory has occurred when attempting to enable or disable a movement These situations can occur when e the system is being started up e the Movement Screen is selected e scrolling within the Movement Screen Repeat the action ProAgent User s Manual A 8 Issue 12 99 Appendix System Messages A 4 3 Error Determining Limit Number Message Number Cause Remedy 4063 ProAgent User s Manual Issue 12 99 The number of defined target positions could not be read from the PLC The cause is generally a communication fault between the operating unit and the PLC In most cases you will receive other system messages which provide more information about the cause of the fault This might be such things as faulty connectors a modified program on the PLC or insufficient memory on the operating unit A 9 Appendix System Messages A 5 Step Screen System Messages A 5 1 No Valid Step Selected Message Number Cause Remedy You have specified a step number that does not exist in the sequencer displayed Specify an existing step number A 5 2 No S7 GRAPH Unit Selected Message Number Cause Remedy You have attempted to open the step screen from the overview screen but no unit had been selected in the
207. with a list of options You can modify the Detail Screen STL or signal list to display the symbol and comment at the same time Note On the OP35 OP37 TP27 10 and TP37 symbols and remarks are already displayed alongside one another The following description therefore refers solely to projects for the C7 626 OP25 OP27 or TP27 6 In order to create sufficient space on the display delete every second line Place the additional output fields on the lines thus freed The symbol and remarks will then appear one underneath the other ProAgent User s Manual Issue 12 99 Modifying the Diagnosis Screens Since two lines are now required for each instruction only half the number of instructions can be display at once as with the standard layout Instruction Status RLO Symbol Instruction Status RLO Symbol Instruction Status RLO Symbol Instruction Status RLO Symbol Instruction Status RLO Symbol Remark Instruction Status RLO Symbol Remark Displaying Symbol and Remarks at the Same Time OP25 Proceed As Follows To have symbol and remarks displayed simultaneously Delete the bottom four lines on the list of instructions it is important that you delete the bottom lines and not any others With the exception of the top line space out the remaining lines evenly over the free space thus made available This should mean that there is at least one blank line between the lines On each line
208. work numbers of networks that set the same operand Line 4 of the display remains blank when the unit is programmed with S7 PDIAG There are no differences between programming with S7 GRAPH and with S7 PDIAG with regard to the remaining areas of the Detail Screen Changing the Display Mode 12 In this input output field you can see or specify whether symbols remarks or operands relating to the individual instructions are to be shown at 15 Representation of the Network The center section of the screen shows an excerpt from the program code for the network with the fault Specifically you are shown the following 13 The switches An actuated switch is represented by a bold symbol a disabled switch by a feint symbol 14 The operands If SIMATIC display mode is set the SIMATIC operand names are displayed otherwise the international IEC names are displayed see Switching Over SIMATIC IEC Display Mode Chapter 8 4 5 15 An additional line of text showing in full the operand symbol or remarks relating to the switch that is highlighted The display mode can be toggled see Toggling Display of Operand Symbol and Remarks LAD Chapter 5 6 4 7 In the case of tags within DBs only the symbolism is displayed if a symbolic identifier has been stored in the symbol table If no symbol has been created the operating unit only shows the absolute address of the tag 16 The arrow symbols appear here They indicate t
209. xample Memory Requirement of an OP25 Project Basic Requirements The project planned encompasses the following components e S7 PDIAG 20 units 300 networks 20 movements 320 target positions 16 per movement e S7 Graph 10 step sequences 150 steps 15 per step sequence 150 transitions 15 per step sequence e Miscellaneous 10 000 initial values signals or criteria 1 300 alarm messages e Text lengths Target position texts 40 bytes each All other texts 20 bytes each e 1 language ProAgent User s Manual Issue 12 99 B 5 Appendix System Limits Memory Requirement of the Diagnosis Structures The memory requirement of the diagnosis structures is calculated as follows Sure Number Byes numeorByis S7 PDIAG reworks 3 em mew Step 10 130 1 300 sequences The diagnosis structures require a total of 54 200 bytes The system limit of 64 000 bytes is therefore complied with At the end of this Appendix you will find a blank form on which you can easily calculate the memory requirement of your own project You can also print out the same form from the Online Help for ProAgent ProAgent User s Manual B 6 Issue 12 99 Appendix System Limits DRAM Requirement of the Project Components The memory requirement of the components that make up the example project is calculated as follows Component Bytes Language Number Bytes E Basic configuration approx 200 approx standard 000 000 see c
210. y Requirement of the Diagnosis Structures B 8 Functions E M after installing ProAgent G Guide to manual H Hardware requirements Help desk ProAgent User s Manual Issue 12 99 Index Hierarchical units In movement screen On overview screen Hotline How can you save on memory space B 5 How to configure direct keys on an OP 21 Important information about using direct keys Inconsistent diagnostic data between PLC and operating unit Incorporating diagnosis screens Initial values 5 51 5 61 5 71 Installation Integrated installation J Jump options Between diagnosis screens Changing K Keys Detail screen LAD 5 67 Detail Screen Signal List Detail screen STL Message screen Movement screen Overview screen Step screen Index L LAD Languages Limits Change number Number check 6 8 Linking diagnosis screens 6 12 Literature Manual Memory requirement Memory requirement of the diagnosis structures Menu items Added by ProAgent Synchronize Target system gt ptwin Message buffer Message overload Message page Message procedure ALARM_S Setting Message screen 5 18 6 28 Define filter criteria 8 15 Use in practice 5 17 Message window Messages Acknowledgement Diagnosable Use of resources Modify Design of diagnosis screens 8 7 Diagnosis screens Filter criteria on message screen Operating modes on overview screen 8 16 Monitor types