Home
guide-installation-a..
Contents
1. Input Voltage DC24V gt Rated Voltage DC19 2 to 28 8V 2 Allowable G d Voltage Drop Sms max 10ms max o Power Consumption 26W max 18W max 28W max In Rush Current 30A max Voltage Endurance AC1000V 20mA for 1minute between charging and FG terminals Insulation Resistance DC500V 10MQ min between charging and FG terminals W Environmental Specifications Surrounding Air 0 to 50 C Temperature Storage Temperature 20 to 60 C 10 to 90 RH E si A Ambient Humidity Wet bulb temperature 39 C max no condensation p M 10 to 90 RH Storage Humidity Wet bulb temperature 39 C max no condensation Dust 0 1mg m and below non conductive levels Pollution Degree For use in Pollution Degree 2 environment 1 When using GP 3300 Series or STN Color LCD model in an environment where the temperature becomes or exceeds 40 C for an extended period of time the screen contrast level may decrease from its original level of brightness External Interfaces IMPORTANT This GP units serial port is notisolated When the host PLC unit is also not isolated and to reduce the risk of damaging the RS232C RS422 RS485 circuit be sure to connect the 5 SG Signal Ground terminal B COM1 Recommended Cable Connector XM2D 0901 made by OMRON Corp Recommended Jack Screw XM2Z 0073 made by OMRO
2. Installations 1 Installation Requirements For easier maintenance operation and improved ventilation be sure to install the GP at least 100 mm 3 94 in away from adjacent structures and other equipment Unit mm in Be sure that the surrounding air tempera ture and the ambient humidity are within their designated ranges Surrounding air temperature 0 to 50 C Ambient humidity 10 to 90 RH Wet bulb temperature 39 C max When installing the GP on the panel of a cab inet or enclosure Surrounding air tempera ture indicates both the panel face and cabinet or enclosure s internal temperature Panel Face Inside Cabinet Be sure that heat from surrounding equip ment does not cause the GP to exceed its standard operating temperature 2 GP Installation 1 Create a Panel Cut and insert the GP into the panel from the front Unit mm in Under4 R3 Panel x 10 12 thickness GP A Panel GP x M thickness GP 1560 e 123 5 a 4 6 0 06 3300 to Series 6 140 04 4 86 50 04 5 0 0 20 GP 2045 159 5 E 1 6 0 06 3400 to Series 8 05 70 4 6 28 70 04 10 0 0 39 2 Confirm that the installation gasket is attached to the GP unit and then place the GP unit into the Panel from the front IMPORTANT It is strongly recommended that you use the installation gasket since it absorbs vibration in addition to repel
3. To reduce noise make the power cord as short as possible If the supplied voltage exceeds the GP unit s range connect a voltage transformer Between the line and the ground be sure to use a low noise power supply If there is an excess amount of noise connect a noise reducing transformer The temperature rating of field installed conductors 75 C only IMPORTANT Use voltage and noise reducing trans formers with capacities exceeding Power Consumption value Must be used with a Class 2 Power Supply 24VDC Connect a surge absorber to handle power surges IMPORTANT Be sure to ground the surge absorber E1 separately from the GP unit E2 Select a surge absorber that has a maximum circuit voltage greater then that of the peak voltage of the power supply E1 E2 E aiaiai N Lightening Surge Absorber 3 Grounding Cautions Be sure to create an exclusive ground for the Power Cord s FG terminal Use a grounding resistance of 100Q a wire of 2mm or thicker or your country s applica ble standard The SG signal ground and FG frame ground terminals are connected internally in the GP unit When connecting the SG line to another device be sure that the design of the sys tem connection does not produce a short ing loop The grounding wire should have a cross sectional area greater then 2mm Create the connection point as close to the GP unit as
4. 4 RS RTS Request for Send ERA Data Terminal Ready A 5 SG Signal Ground SG Signal Ground 6 VCC 5V 5 Output 0 25A CSB Clear to Send B T RDB Receive Data B SDB Send Data B 8 SDB Send Data B CSA Clear to Send A 9 TRMTX NO de 1000 FRB Data Terminal Ready B Shell FG Common with se FS Common with SG 1 The VCC output for Pin 6 is not protected against overcurrent To prevent damage or unit malfunctions use only the rated current W AUX Input Output and Sound Output Interface Supported by GP 3400 series only Recommended Cable Connector 2L3 5 12 90F90F made by Weidmuller gt Terminal Block B2L3 5 12LH made by Weidmuller gt Pin Arrangement Pin Signal Name Direction Meaning 1 RESETIN A Input External Reset Input 2 RESETIN B Input 3 RUN Output RUN Signal ol 4 RUN Output OR 5 ALARM Output OI ALARM Signal op 6 ALARM Output OL 7 BUZZER Output OL Buzzer Signal H 8 BUZZER Output 9 NC Not Connected Cable connection side 10 NC Not Connected 11 SP Output Speaker Out 12 SP_GND Output Speaker Ground Input Circuit Output Circuit 3 pec ER 1 i 3 pT i Load O lieti sme SPR 08 ieac d 4DpF i DC EH 1 i E Foll bf S Loo yAV m eee aise g i E 5AkQ E 10KQ M
5. mended Pin Al 0 75 8GY 3200519 Terminals Al 1 8RD 3200030 Al 1 5 8BK 3200043 Al 2 5 8BU 3200522 Recom mended Pin CRIMPFOX ZA 3 Terminal Crimp 1201882 Tool W Connecting the GP Power Cord 1 Confirm that the GP unit s Power Cord is unplugged from the power supply 2 When using GP 3300 Series remove the power connector plug from the main unit When using GP 3400 Series the power connector plug is packaged with other accessories 3 Strip the power cord twist the conductor s wire ends insert them into the pin terminal and crimp the terminal Attach the terminal to the power connector Use a flat blade screwdriver Size 0 6 X 3 5 to tighten the terminal screws The torque required to tighten these screws is 0 5 to 0 6 Nem 5 7 Lbeln Do not solder the cable connection 4 Attach the Power connector Plug to the Power Connector Power Connector Socket Power connector Plug 2 Power Supply Cautions Input and Output signal lines must be sepa rated from the power control cables for operational circuits To improve the noise resistance be sure to twist the ends of the power cord wires before connecting them to the Power con nector Plug The GP unit s power supply cord should not be bundled with or kept close to main circuit lines high voltage high current or input output signal lines
6. 10BASE T 100BASE TX This interface uses an RJ 45 type modular jack connector 8 pins Except for AGP 3301 AGP 3302B E Power Connector Socket Complies with USB 1 1 Uses a TYPE A connector Power supply voltage 5 VDC 5 F USB Host Interface USB Output current 500mA max The maximum communication distance 5m Dsub 9 pin plug type RS232C RS422 and RS485 are G Serial Interface COM1 switched by software AGP 3302B supports RS232C only Dsub 9 pin socket type RS422 and RS485 are H Serial Interface COM2 supported AGP 3302B has Dsub 9 pin plug type and supports RS422 only CF amp rd Cover Except for AGP 3302B J Dip Switches Located inside the CF Card Cover P Except for AGP 3302B Left Side s AGP 3300T AGP 3450T K AUX Input Output and Sound Used for external reset alarm output buzzer output Output Interface AUX and sound output Except for GP 3300 series Its an interface to which a microphone is connected A L SNO us mini jack connector 3 5 mm is used Supported by AGP 3450T only It s an interface to which a video camera is connected M VIDEO Input Interface NTSC 59 9 Hz and PAL 50 Hz are supported ARCA V IN connector 750 is used Supported by AGP 3450T only General Specifications W Electrical Specifications AGP 3300 3301 AGP 3302B AGP 3400 3450T
7. Series units W Attaching the USB Holder 1 Before starting the procedure orient the two tabs on both sides of the USB Holder in the direction ofthe arrows in the figure and remove the USB Cover Tabs wW Attach the USB holder to the USB Host Interface part of the main unit Hook the lower pick of the USB holder to the attachment hole of the main unit and 2 then insert the upper pick as shown below to fix the USB holder 3 Insert the USB cable into the USB Host Interface 4 Attach the USB cover to fix the USB cable Insert the USB cover into the tab of the USB holder USB Holder When using the GP be sure to attach all the 2 USB covers W Removing the USB Holder 1 Lift up the tab of the USB holder and then remove the USB cover as shown below USB Holder USB Cover 2 After removing the USB cable remove the picks pushing the USB holder from both top and bottom UL c UL CSA Approval The GP 3300 3400 Series units are UL c UL CSA listed products UL File No E220851 UL File No E182139 CSA File No 219866 UL c UL CSA Registration Model No AGP3300 L1 D24 3280007 03 AGP3300 S1 D24 3280007 02 AGP3300 T1 D24 3280007 01 AGP3301 L1 D24 3280007 13 AGP3301 S1 D24 3280007 12 AGP3302 B1 D24 3280007 24 AGP3400 T1 D24 3280035 01 AGP3400 S1 D24 3280035 02 AGP3450 T1 D24 3280035 31 Product Model No These products co
8. possible and make the wire as short as possible When using a long grounding wire replace the thin wire with a thicker wire and place it in a duct Exclusive Grounding BEST Other Equipment GP unit Common Grounding OK Other Ce unr Equipment Common Grounding Not OK Other Equipment GP unit 12 4 Input Output Signal Line Cautions All GP Input and Output signal lines must be separated from all operating circuit power cables If this is not possible use a shielded cable and ground the shield To prevent the USB cable from coming off IMPORTANT When using USB Host Interface in Hazardous Locations provided in UL 1604 please fix the USB cable with the USB Holder If it s not fixed so that the connector on the GP s side and the PLC s side cannot come out the USB Host Interface cannot be used in the Hazardous Locations 1 GP 3300 Series units W Attaching the USB Cable Clamp 1 Insert the USB holder into the slot in front of the GP unit s USB port and pull it down and forward 2 Pass the band of the USB cable clamp through the bridge of the USB holder Bridge USB Holder 3 Insert the USB cable into the port Fasten the band around the plug and secure it with the clamp USB Holder W Removing the USB Cable Clamp 1 Lower the tab and lift the clamp to release the plug Clamp 2 GP 3400
9. GP 3300 3400 Series Installation Guide Eee Caution Be sure to read the Warning Caution Information on the attached sheet before using the product Package Contents 1 GP Unit 1 2 English and Japanese installation Guides 1 of each This Guide gt 3 Warning Caution Information 1 4 Installation Gasket 1 attached to the GP unit 5 Installation Fasteners Set of 4 6 RCA BNC Convertor 1 Only for AGP 3450T d 7 AUX Connector 1 Only for GP 3400 Series Cp 8 Power Connector 1 Attached to the GP unit for GP 3300 Series Distribu par 2rue Ren Laennec 51500 Taissy France Fax 03 26 85 19 08 Tel 03 26 82 49 29 9 USB Cable Clamp 2 port 1 set Holder 1 Cover 2 Only for GP 3400 Series 10 USB Cable Clamp 1 port 1 Holder 1 Clamp 1 Only for GP 3300 Series This unit has been carefully packed with special attention to quality However should you find anything damaged or missing please contact your local GP distributor immediately About the Manual For the detailed information on GP3000 series refer to the following manuals GP3000 Series Hardware Manual Maintenance Troubleshooting The manuals can be selected from the help menu of GP Pro EX or downloaded from HVS System Home Page URL http www hvssystem com When using GP 3300 Series with Pro Designer refer to AGP 3300 Seri
10. N Corp Recommended Cable Cover XM2S 0913 made by OMRON Corp Common with SG pini RS232C RS422 RS485 Except AGP 3302B Signal Name Meaning Signal Name Meaning 1 CD Carrier Detect RDA Receive Data A 2 RD RXD Receive Data RDB Receive Data B 3 SD TXD Send Data SDA Send Data A 4 ER DTR Data Terminal Ready ERA Data Terminal Ready A 5 SG Signal Ground SG Signal Ground 6 DR DSR Data Set Ready CSB Clear to Send B 7 RS RTS Request to Send SDB Send Data B 8 CS CTS Clear to Send CSA Clear to Send A 9 jarwo laye Output D zaa ERB Data Terminal Ready B Shell FG Frame Ground FG Frame Ground Common with SG 1 The RI VCC selection for Pin 9 is switched via software The VCC output is not protected against overcurrent To prevent damage or unit malfunctions use only the rated current m COM2 Recommended Cable Connector XM2A 0901 made by OMRON Corp XM2D 0901 made by OMRON Corp AGP 3302B only Recommended Jack Screw XM2Z 0073 made by OMRON Corp Recommended Cable Cover XM2S 0913 lt made by OMRON Corp gt Pin RS422 RS485 Except AGP 3302B RS422 AGP 3302B only Signal Name Meaning Signal Name Meaning 1 TRMRX SRM de 1000 RD Receive Data A 2 RDA Receive Data A RDB Receive Data B 3 SDA Send Data A SDA Send Data A
11. e inserting or pulling it C E Marking The AGP3300 L1 D24 AGP3300 S1 D24 AGP3300 T1 D24 AGP3301 L1 D24 AGP3301 S1 D24 AGP3302 BI D24 AGP3400 S1 D24 AGP3400 TI D24 AGP3450 TI D24 units are CE marked EMC compliant products These units also conform to EN55011 Class A EN61000 6 2 directives Inquiry Do you have any questions about difficulties with your GP Please access our site anytime that you need help with a solution http www pro face com otasuke Note Please be aware that Digital Electronics Corporation shall not be held liable by the user for any damages losses or third party claims arising from the uses of this product Digital Electronics Corporation 8 2 52 Nanko higashi Suminoe ku Osaka 559 0031 JAPAN TEL 81 0 6 6613 3116 FAX 81 0 6 6613 5888 http www proface com Copyright 2005 Digital Electronics Corporation All rights reserved 070220K AGP3300 3400 MT02E BTH 2006 11 JM C
12. ed in order to access the narrow hole of the connector X O Screwdriver Tip Shape W Detachment Turn the tabs on the levers at both ends of the connector and the connector is released from the GP W Wiring and attachment 1 Insert the tip of the screwdriver into one ofthe square holes Then insert the cable into the corresponding round hole When you pull out the screwdriver the cable is locked For the pin assignment of the AUX connector refer to External Interfaces Quy Wire 2 Screwdriver 2 Insert the wired AUX connector into the auxiliary I O or sound output interface AUX on the left side of the GP unit on If the connector cannot be fully inserted turn the tabs on the levers at both ends of the connector in the reverse direction and insert the connector 1 Wire should be AWG22 to AWG18 thick and twisted Applicable wire sizes are UL1015 and UL1007 2 Be sure to strip from 6 5 to 8 0mm 0 26 to 0 31in of cover from the wire Be sure to strip only the amount of cover required If too much cover is removed the end wires may short against each other or against an electrode which can create an electric shock If not enough cover is removed the wire cannot carry a charge Do not solder the wire itself This could lead to a bad or poor contact Insert each wire completely into its opening Failure to do so can lead to a unit malfunction or short either against wire filame
13. es User Manual PDF File AGP 3300 Series User Manual can be selected from Man ual in the dialog box displayed after the CD ROM of Pro Designer is inserted Email hvssystem hvssystem com Site web www hvssystem com Part Names and Functions Front Rear Right Side Bottom CF Card Cover Open At Rr J AGP 3300T AGP 3300T AGP 3300T AGP 3300T DF B ic i r J Pasi TEESE 4 a d c E im on iic AGP 3450T AGP 3450T AGP 3450T AGP 3450T Name Description Logic execution mode Color Indicator Operation Mode when logic is Drawing enabled ON OFFLINE Green In operation RUN Flashing In operation STOP A Status ED Red ON When power is turned on Flashing In operation Major Error Orance ON Backlight burnout 9 Flashing During software startup The logic program is disabled in the AGP 3302B 3301L 3301S The Status LED turns on only in Operation Mode Drawing Expansion Unit Interface EXT Used to connect an expansion unit that can transmit data C CF Card Access LED Lit in green when the CF Card is inserted and thecover is closed or when the CF Card is being accessed Except for AGP 3302B D Ethernet Interface LAN
14. hin the United States and in accor dance with Section 18 152 of the Cana dian Electrical Code for units installed within Canada Q Suitable for use in Class I Division 2 Groups A B C and D Hazardous Locations or Non Hazardous Locations only WARNING Explosion hazard substitution of components may impair suitability for Class I Division 2 and AVERTISSEMENT RISQUE D EXPLOSION LA SUBSTITUTION DE COMPOSANTS PEUT RENDRE CE MATERIAL INACCEPTABLE POUR LES EMPLACEMENTS DE CLASSE I DIVISION2 WARNING Explosion hazard when in hazardous locations turn OFF power before replacing or wiring modules G 4 5 6 7 WARNING Explosion hazard confirm that the power supply has been turned OFF before disconnecting equipment or confirm that the location is not subject to the risk of explosion WARNING Explosion hazard do not disconnect equipment unless power has been switched off or the area is known to be Non Hazardous and AVERTISSEMENT RISQUE D EXPLOSION AVANT DE DECONNECTER L EQUIPEMENT COUPER LE COURANT OU S ASSURER QUE LEMPLACEMENT EST DESIGNE NON DANGEREUX In the case of use in Hazardous Locations be sure to check that the externally connected unit and each interface have been fixed with screws and locked In Hazardous Locations it s impossible to insert or pull the cable from the applicable port Be sure to check that the location is Non Hazardous befor
15. ling water For the procedure for replacing the installation gasket refer to GP3000 Series Hardware Manual 3 The following figures show the four 4 fastener insertion slot locations Insert each fastener s hook into the slot and tighten it with a screwdriver Insert the installation fasteners securely into the insertion slot recess TOP C S eco S Insertion Slots so Ci ELELEE N Bottom The figure shows the GP 3300 series Insertion Slot Recess Hook the fastener on the Recess V Installation Fastener e GP S gt and secure the fastener Hook on the panel with a screw Tightening the screws with too much force can damage the GP unit s plastic case The necessary torque is 0 5Nem Panel 3 Wiring and attaching detaching the AUX connector GP 3400 series only IMPORTANT Be sure to remove the AUX Connector from the GP unit prior to starting wiring Failure to do so may cause an electric shock W items Required to Wire Connectors Screwdriver Recommended type SDI Product No 900837 Weidmuller Japan If another manufacturer is used be sure the part has the following dimensions point depth 0 4mm 0 02in point height 2 5mm 0 10in length from the point to the handle 80mm 3 15in Point shape should be DINS264A and meet Security Standard DN EN60900 Also the screwdriver s tip should be flat as indicat
16. nform to the following standards ULS08 Industrial Control Equipment UL1604 Electrical Equipment for Use in Class I and II Division 2 and Class III Hazardous classified Locations CSA C22 2 No 14 M95 Industrial Control Equipment CSA C222 No 213 M1987 Non Incendive Electrical Equipment for Use in Class I Division 2 Hazardous Loca tions lt Cautions gt Be aware of the following items when building the GP into an end use product The GP unit s rear face is not approved as an enclosure When building the GP unit into an end use product be sure to use an enclosure that satisfies standards as the end use product s overall enclosure The GP unit must be used indoors only Install and operate the GP with its front panel facing outwards If the GP is mounted so as to cool itself naturally be sure to install it in a vertical panel Also it s recommended that the GP should be mounted at least 100mm away from any other adjacent structures or machine parts The temperature must be checked on the final product in which the GP is installed Serial Interface COM2 is not Limited Power Source For use on a flat surface of a Type 4X Indoor Use Only and or Type 13 Enclo sure UL1604 CSA C22 2 No 213 Compliance and Handling Cautions 1 Power and input output wiring must be in accordance with Class I Division 2 wir ing methods Article 501 4 b of the National Electrical Code NFPA 70 wit
17. nts or against an electrode 3 Do not rotate the point of the screwdriver inside the square shaped opening It may cause a malfunction Wiring NWARNING To avoid an electric shock prior to con necting the GP unit s power cord termi nals to the power terminal block confirm that the GP units power supply is completely turned OFF via a breaker or similar unit Any other power level can damage both the GP and the power supply When the FG terminal is connected be sure the wire is grounded 1 Wiring the DC type power supply cable W Power Cord Specifications Use copper conductors only Power Cord 0 2 to 2 5mm Diameter 0 0001 to 0 0097 inch 24 12 AWG Conductor Simple or Stranded Wire Type Conductor E i028 Length EE 0000 1 If the Conductor s end individual wires are not twisted correctly the end wires may either short against each other or against an electrode W Power Connector Plug Specifications 24V ov Grounding Terminal connected to the GP chassis The power connector plug is CA5 DCCNM 01 made by Pro face or MSTB2 5 3 ST 5 08 made by Phoenix Contact When connecting the Power Cord use the following items when performing wiring Items are made by Phoenix Contact SZF 1 0 6x3 5 1204517 Recom mended Driver Al 0 25 6BU 3201291 Al 0 34 8TQ 3200865 Recom AI 0 5 8WH 3200014