        GP-470/570 Series Profibus User`s Manual
         Contents
1.  470E  i e  S7 315 2 DP Wiring  GP070 PF11  GP 570L  Diagram 1 GP 570S  GP 570T  GP 675  GP 870VM       GP 470 570 series Profibus User   s Manual    Introduction    1 2 System Configuration    Use RS 485 cables to make the connection  This will allow for a maximum   of 64 slaves  in DIO mode  with the Seimens S7 300    With same Seimens PLC  and using Packet mode the limilt is four  4  slaves   RS 485 RS 485    L IL   r L     GP GP     to a maximum of 64 slaves GP                                       qi                                                      1 3 When Using Screen Creation Software    When selecting the PLC type to use on your screen creation software  choose     Profibus        For detailed selection procedures  refer to the Operation Manual  for the respective screen creation software     e When using the GP PRO PB III for Windows 95 software  refer to     1 8 2 Select a Project Create a New Project  in the    GP PRO   PB III for Windows 95 Operation Manual       e When using the GP PRO PB III  DOS  software  refer to    1 5 2  Select Project  in the    GP PRO PB III Operation Manual        1 2 GP 470 570 series Profibus User   s Manual    Chapter  2 1 Profibus Specifications    2 2 Parts Names and Functions    Specifications    This chapter describes the specifications  names  and figures for the Profibus  unit     2 1 Profibus Specifications    1 General Specifications    Rated voltage 5 VDC   596  Scppied by the GP unit   Less than 3 W  Typically 1 9W     
2.  adam ie Data A AEA 2 3  Chapter 3 Installation    Sel  dnstallmb the Profibus Unit soseen ES DUI M DUE EUM BIS  3 1  Chapter 4 Troubleshooting    Zr Troubleshooting eusiueessediadiedtiebu sinebuii deditus ib EE E dedu tubo EU bud aene 4 1  4 1 1 uc dscl MP              4    Aad  Possible SONOS Mer                          4    4 1 3 No Data CODI acces onuc indo ien ode ut blank eulos dene bpm e vun et 4 3  4 2  Error Messages  C          M             E ioei 4 5    GP 470 570 series Profibus User   s Manual    Preface     AN Essential Safety Precautions    For the safe and correct use of the Profibus and GP series  be  sure to follow the guidelines stated below     Due to the possibility of an electrical shock  be sure that the power sup   ply for the GP is not plugged in when installing the Profibus unit     Do not attempt to modify or alter the Profibus unit  Doing so may cause  a fire or an electric shock     To prevent the danger of either personal injury or machinery material  damage  please design your machine   s control system so it will not mal   function due to a communication problem between the GP and host con   troller  PLC      To Avoid Damaging the Profibus unit     Do not allow water  liquids  or metal particles to enter into the Profibus  unit   s case  since it can cause a malfunction or electrical shock     Avoid storing or operating the Profibus unit in locations where it will be  exposed to direct sunlight  high temperature  excessive dust  or vibra   ti
3.  the GP with your left hand and insert  the Profibus unit into its slot with your right  hand    Be sure that the unit is seated correctly in place   so that no gaps remain between the GP and the  Profibus unit            oy     qo    m Screw holes    G Reattach the attachment screws and secure  Attachment the Profibus unit to the GP   Screws       3 2 GP 470 570 series Profibus User s Manual    Chapter  4 1 Troubleshooting    4 2 Error Messages       Troubleshooting    This chapter describes the usual troubleshooting procedures to use when a problem  occurs with the Profibus unit     4 1   Troubleshooting    The following section describes standard problems and their possible solutions     1 Possible Problems    The most common problems that could occur while operating the GP are as follows      1  No Data Communication    Data communication does not take place between the GP and Host  In some  cases  an error message will be displayed on the screen     icon For error messages  refer to    4 2 Error Messages   and the respective GP    unit s Users Manuals      2  OFFLINE mode menu appears on the main unit during operation     2 Possible Solutions      For problem  1   use the following troubleshooting flowchart to diagnose the  problem s cause and find a possible solution       For problem  4   the cause may be due to a main  GP  unit system error     E Please remember that the GP unit   s OFFLINE mode will display if you    touch the upper left corner of the screen within 1
4. 0 seconds after start up     GP 470 570 series Profibus User   s Manual    4 2    Troubleshooting       WARNING    Before installing the Profibus DP unit       Before beginning installation  due to the possibility of an electrical shock  be  sure the main unit  GP  s power cord is unplugged from the power supply              This chapter describes only GP unit problems  and assumes there are no PLC prob   lems  For PLC problem causes  please refer to the PLC maker s Operation Manual           GP 470 570 series Profibus User s Manual    Troubleshooting    3 No Data Communication    If the GP can not communicate with the host  follow the flowchart described below to  find the cause of the trouble and correct the problem     In cases where an error message is displayed on the GP   s screen  check the error code  list and correct the problem     as Refer to    4 2 Error Messages   and the respective GP unit   s Users Manuals       No data communication can be  performed    Turn off the GP   s power supply              p et S Select    Target PLC    when entering the  we E PLC type         Has the PLC type info  been    NO  4    entered correctly           Z8 Refer to  1 3 When Using  Te ud Screen Creation Software    TEE ie as well as the GP PRO PB  I YES III Operation Manual          d       NO  Insert the Profibus unit correctly and      Has the Profibus unit been Soe  The installed correctly         tighten the attachment screws securely     n   EE Refer to    3 1 Installing t
5. Contact your local dis   tributor for further assistance             The original Profibus unit is  L defective                 4 4 GP 470 570 series Profibus User   s Manual    Troubleshooting    4 2   Error Messages    B The PLC does not respond  02 FE     This error message is displayed when a time out occurs while receiving data or  there is too much noise on the line     The possible causes are described below  Select the solution below that applies to your  particular problem        Cause Solution    The master PLC   s power is OFF  or in   Turn on the PLC power supply   stop mode     The PLC and the GP have been First turn on the GP power supply  then  turned on in the wrong order turn on the PLC power supply after 2 to 3  seconds        The communication cable is not Check the wiring of the communication  connected properly  cables  and wire them correctly   B PLC Communication Error    One possible cause of this error message is that the address value set for the tag ex     ceeds the range specified by the processor  Check the displayed error number  and  proceed by following the respective solutions     e PLC Communication Error   02   x x   02  xx      Error No              F6 1  Be sure that your screen data uses  only the designated LS area s    2  Reset the System Area  to all zeroes      B Target PLC has not been set up    This error message is displayed when data other than that used by the target PLC is  transferred     Reinitialize the GP  and then send the 
6. Cores  model name  ZCAT2035 0930A  TDK Co       or equivalent    _       D sub 9pin connector   Metal case            Profibus  Unit          2 4 GP 470 570 series Profibus User s Manual    Chapter  3 1 Installing the Profibus Unit    Installation    This chapter describes how to install and wire the Profibus unit and how to set  the Profibus address      3 1  Installing the Profibus Unit    To install the Profibus unit in the GP  follow the steps below     AN WARNING    Before installation      Due to the possibility of an electrical shock  be sure the GP   s power cord is not  plugged in to the power supply     e Be sure not to touch the surface of the printed circuit board           Disconnect the power cable from the GP       Use a screwdriver to unscrew the GP rear cover   s 2 attachment screws and  remove the rear cover     Attachment screws          Profibus Unit          Rear of GP      This figure describes how to install the Profibus module into a GP 470 series display  unit     GP 470 570 series Profibus User s Manual 3 1    Installation    Protruding tabs      Mi  Be careful not to touch the surface of    the Profibus unit s printed circuit board              Insert the protruding tabs of Profibus unit  into the installation holes   Holes for installing Besure to install the unit so thatthe smooth metal  euni face of the Profibus unit points outward        call 4  Be careful not to touch the surface of  WEB the Profibus unit   s printed circuit board          Hold
7. Preface       Thank you for purchasing the Profibus DP unit  hereafter referred to as the     Profibus unit     This unit is intended for use with the Digital Electronics  Corporation   s GP 470 570 675 870 series touch panels  hereafter referred  to collectively as the  GP   and as an interface between the Profibus data  network and any of the abovementioned GPs    This manual describes the procedures  settings  wiring  etc  required to per   form communication on the Profibus network via the GP s   also  each GP  has its own reference manual you can refer to for detailed GP operation  information  Before actually beginning to use the Profibus unit  please be  sure to the GP s User s Guide s section    1 1 Prior to Operating the GP      The following GP series displays can be used with the Profibus unit   GP 470 EG  GP 570 TC  GP 570 SC  GP 570 TV  GP 571 TC   GP 675  GP 870V    All company or manufacturer names used in this manual are the registered  trademarks of their respective companies        1  It is forbidden to copy the contents of this manual  either in whole or in part   except for the purpose of the user s personal use  without the express written  permission of the Digital Electronics Corporation of Japan     2  The information provided in this manual is subject to change without notice     3  This manual has been written with care  however  should the user discover any  errors or omissions  please contact the Digital Electronics Corporation and  inform them of 
8. Voltage capacitance 1500 Eid 20 n 1 min   between live and FG  500 VDC  more than 10 MQ  between live and FG  terminals     Ambient operating 0 to 50  C  Do not operate in temperatures in  temperature excess of aS s specified range    Ambient operating 30 to 85  RH  Do not operate in areas where  humidit humidity is higher than GP   s specified range   Ambient storage  10 to 60  C   temperature    Ambient storage humidity   20 to 85  RH  no condensation     Vibration resistance 10 to 25 Hz  X  Y  Z directions for 30 minutes each  at 2G     Noise endurance Noise voltage  1000 Vp p  Pulse length  1 us  Rise time  1 ns  with simulator     Operating Atmosphere Free of corrosive gases   Grounding          jClass3    GP 470 570 series Profibus User s Manual       2 1    2 2    2       Specifications    Physical Specifications    a Installed as an option board in GP 470 570  series large units    s expansion slots  167 W  x 116 1 H  x 25 1 D   mm     Main unit only  including terminal block   Weight O    Approx  330 g  Cooling method Natural air circulation       Performance Specifications   Memory          2 portRAM  KB    GP connection I F GMU buses  Address bus  16 Bit  Data bus  8 Bit  Interrupt function  1 ch  IRQ A  FIX   Communication I F Connector used  D SUB 9 pin  Input output   Complies with RS 485  insulated type   Transfer rate  12 Mbps  1500 kbps  500 kbps  187 5 kbps  93 75 kbps  19 2 kbps  9 6 kbps  Recommended cable  EIA RS 485 twisted pair  Terminating resistor  Bu
9. correct data     GP 470 570 series Profibus User s Manual    4 6    Troubleshooting    MEMO    This page intentionally left blank     GP 470 570 series Profibus User   s Manual    
10. he                                    YES Profibus Unit         Havethe   YES u   lt  Profibus unit connector pins  gt  gt  Contact your local distributor   RI been bent  P    NO  P di M S  pd Nc Confirm that the rotary switch address  P T Has the address lim NO settings for the Profibus unit are cor   ET  gt      gt   S setting for the ea peer 26 rect  Refer to Section 2 2 Part Names  lus OR uen and Functions for details     YES        GP 470 570 series Profibus User   s Manual    Troubleshooting    z  M SE    ao           Has the Profibus unit ber ls NO  Check that none of the connector pins        installed correctly  oe have become bent or skewed  Then  re    ic M n install the Profibus unit in the back ofthe  lur d GP so that its connector is correctly con   2 YES      f nected     Turn ON the power supply                   o  p    v di    Doesthe    ERR       YES             LEDlighup               NOk YES     network configured           pw 7  eomectly     7 rectly        Configure the network cor                 Doesthe     7   YES    a C PWR    LED light up  D 7    Bat ee NO   Does the        NO  lt  unit communicate  gt     T normally               Contact your local distribu  Ws  tor for assistance and pos    YES    sible replacement of the unit  m  Assuming an authorized replace                    ment unit has been sent to you     pi    YES   Does the     7   L     new Profibusunitcommunicate  gt             momally   d    NO   The GP unit may be defec     tive  
11. ilt in   turns ON OFF via DIP switches     Usage Environment Specifications  1  Gp Data Transfer Settings             PGP Settings O  DataTransferSpeed          96Ktoi2Mbps  J    Data Transfer Method RS 485   System Area Start Address DB2WO DB60W 65514   Station No  0  127         Default Settings     1   The data transfer speed is automatically changed  according to the ladder  software s specifications  Thus  setting this speed via the GP is uneeded         2   Station No s are set via the Profibus Rotary Switches     GP 470 570 series Profibus User s Manual    Specifications    2 2 Parts Names and Functions    Profibus Unit LED Indicators    The figure below shows the Top Mounted placement of the Profibus module   s LED    indicators   Top Mounted LED Unit      Power LED     anes ie  p     E  E  N    The following table shows the function of each LED indicator                    LED NAME COLOR FUNCTION  ERR RED Lit Normal Operation  Unlit  Bus is OFF or has error  DIA  NONE  Not Used  POWER GREEN Lit  Poweris ON  Unlit  Power is OFF          Terminating the First and Last Profibus Module    The first and last Profibus module must be terminated for the bus unit to operate prop   erly  To do this  simply turn on the terminating switch on the first and last Profibus I F  unit   See figure below  Also  be sure to turn all other Profibus unit termination  switches OFF     Profibus Unit Rotary Switches    The rotary switches are used to set the Profibus DP slave node number  The
12. nt damage if the instructions are not followed     Explains a situation that requires a moderate amount of user caution     Indicates the GP screen editing creation software  GP PRO PBIII     Programmable Logic Controller    Indicates supplemental explanatory information is located at the bottom of  the page     Indicates additional  relevant information     Reference pages of related sections and topics    The Tag Reference  Operation  Software Operation  PLC Connection  and  Parts List Manuals referred to here are those included in the GP PRO III  or GP PRO PBIII for Windows  95 software package     Indicates procedure numbers  Be sure to follow these steps to perform a  particular task correctly     GP 470 570 series Profibus User   s Manual    This page intentionally left blank     GP 470 570 series Profibus User   s Manual    Chapter  1 1 Operating the Profibus Unit  1 2 System Configuration  1 3 When Using Screen Creation Software    Introduction    This chapter describes the operation of the Profibus unit and the cautions  necessary for correct data communication     1 1 Operating the Profibus Unit    The Profibus unit allows one of the following GP series units to be con   nected directly to a PLC that supports the Profibus network       How to set up the Profibus unit         CPU Connection   Data Cable I F Module GP  Diagram Types                                           oll                                      S7 300 Series See Cable RS 485 Profibus DP Module   GP
13. on     Because the Profibus unit is a precision instrument  do not store or oper   ate it in locations where something may strike or hit the unit     Do not store or operate the Profibus unit where chemicals or acids are  stored  or where high concentrations of fumes are present     Do not use paint thinner or organic solvents to clean the outside of the  Profibus unit  Instead  soak a soft cloth in a diluted neutral detergent   wring it tightly  and then wipe the unit   s outside case     GP 470 570 series Profibus User   s Manual    Preface    Packing Box Contents       The Profibus unit   s packing box contains the items listed below  Please  confirm that everything illustrated here has been included     B Profibus Unit BE GP Series Profibus  User   s manual   this manual     GP Series   470 570 675 870     Profibus  User s  MANUAL       E Ferrite Cores  2           This unit has been carefully packed  however  should you find any item to  be either damaged or missing  please contact your local GP distributor  immediately for service     GP 470 570 series Profibus User   s Manual    Preface    Symbols       A       A    call   w    GP PRO PB III    PLC    e           The list below describes the symbols and abbreviations used in this manual     Indicates a potentially hazardous situation which could result in serious    injury or even death  if the instructions are not followed     Indicates a potentially hazardous situation which could result in minor in   jury or equipme
14. se must be set  tothe same value as that specified in the Profibus DP slave configuration  If the GP is to be  the last node on the Profibus DP network  then the TERM switch must be set to the    ON     position to mark the network termination  The diagram below shows an example where  the node address is set to 1  thus the rotary switches are set to    0 1           GP 470 570 series Profibus User s Manual   2 3    Data Cable Wiring  The following cable diagram should be used when making a cable for the Profibus DP  cable   s connector     lt Cable Wiring Diagram gt     Station 1 Station 2    9 pin   9 pin   RxD TxD P  3         3  RxD TxD P  DGND  5         5 DGND  VP  6         6 vP  RxD TxD N  8  O     8  RxD TxD N    Protective pe      Ground    cally  Be sure to earth the PLC   s FG according to Class 3 earthing standards      For details  please refer to the PLC maker   s manual   Collect all the data cable   s shield wires and connect them to the PLC   s FG  I    Cable Data  for S7315 2 DP model   Parameters  Line A Line B  according to Profibus DP DIN  19245 part1 4 91  section 3 1 2 3  Wire Gauge   gt 0 64mm  gt 0 53mm  Conductor Area   gt 0 34mm    022mnY       1  Be sure to attach the ferrite cores shown below to the data transfer cables leading to the  Profibus unit  and use a D sub connector with a metal case  This will help to suppress the  effect of any noise created by surrounding equipment  TDK ferrite cores  or their equivalent     are recommended  Ferrite 
15. your findings     4  Please be aware that the Digital Electronics Corporation is not responsible for  any damages resulting from the use of its products  regardless of article 3  above                 Copyright 1997  Digital Electronics Corporation    MS DOS   and Windows  95 are registered trademarks of the Microsoft Cor   poration     IBM  DOS  are registered trademarks of IBM     GP 470 570 series Profibus User s Manual    Preface    Table of Contents       Preface      Preface M ane ae erse E A        M                   1  UE is gto NR 2  Essential Safety Precautlols  uestes vatanudlonnensadsestwunstauecwugeeusan qu eM pe DRE E E ME 3  Packing Box Contents eee eee ee tere Pe ee ne rene ne Porn eee eee ae rere eee 4  PO MNOS MT                                                      S 5       Chapter 1 Introduction j             Del Operating the Profibus Wait iere e ion eterne ee st rc ste iieiaei 1 1  1 2 System OE UI AO ices deve ee ka sediede attendent pumau c bled ese duca iaeia 1 2  1 3 When Using Screen Creation Software 25 ocio ptit ectetuer eH SEN Eines 1 2  Chapter 2 Specifications    2 1 Ptolib  s Specifications  sccsciccedeseusceacviesenteebedancnceidepiavveiceadededstdasuntenasusliddelseeeauase 2 1  2 1 1 G  nera  l Spec iC ais oct solace odors Ronan a ma Unde 2 1  2 1 2 Physical Speciications sssmoisrisieicosssiccsieriicai iieri iiaii 2 2  2 1 3  Performance Specific  ti  nS sesisssssisrcosies senectae aoei ees 2 2  2 2 Part Names and FUNCHONS soracuate ciii eo
    