1. D wn gt TELECOM OPERATING MANUAL AC POWER DISTRIBUTION UNITS VIGILANT SERIES WWW UNIPOWERTELECOM COM Manual No PDUACIUSM 1 2010 UNIPOWER Corp 10 10 pduactus man All Rights Reserved UNIPOWER Telecom Division of UNIPOWER Corporation NORTH AMERICA 3900 Coral Ridge Drive Coral Springs Florida 33065 USA Tel 1 954 346 2442 Fax 1 954 340 7901 sales unipower corp com EUROPE Parkland Business Centre Chartwell Road Lancing BN158UE ENGLAND Tel 44 0 1903 768200 Fax 44 0 1908 764540 telecom unipower europe com UNIPOWER Wp TELECOM VIGILANT SERIES OPERATING MANUAL VIGILANT Series PDU User Manual Page 2 10 10 pduacius man UNIPOWER Wp TELECOM VIGILANT SERIES OPERATING MANUAL Table of Contents ntrod uction EEN p aaa aeai aaan 4 PDU Package 00 5 FUN ON J uu O IONE 6 a nstallatiomn 71 03020 8 Web Interface 1 10 20000r erre nananana aaa anaE aianei an 10 Ul WN F VIGILANT Series PDU User Manual Page 3 10 10 pduacius man UNIPOWER Ww TELECOM VIGILANT SERIES OPERATING MANUAL 1 Introduction The VIGILANT Series is a family of Internet ready Power Distribution Units PDU designed and is equipped with an intelligent current meter True RMS that will indicate the total power consumption of the connected loads These PDUs offer easy to set up user friendly communication sof
2. MS Current Meter Ethernet Functions Description Ethernet RJ 45 port for network communication port Audible Alarm Warning 1 beep in 1 second Overload 3 beeps in 1 second Note The audible alarm will keep beeping until the current returns to normal and is also at least 0 5A lower than the alarm threshold Function Button Press and release to turn off the warning beep The overload beep cannot be cancelled Press and hold the key for 1 beep the meter shows the total current Press and hold the key for 2 beeps the meter shows the IP address Press and hold the key for 4 beeps sets DHCP ON or OFF Note that VIGILANT Series PDUs are shipped with DHCP set to ON Press and hold the key for 6 beeps Resets the PDU back to it s default settings Meter 3 digits to display current or IP Address VIGILANT Series PDU User Manual Page 6 10 10 pduactus man UNIPOWER w TELECOM VIGILANT SERIES OPERATING MANUAL LED Indicator SSL yellow Light on means web access is protected by SSL DHCP Green Light on means the PDU gets its IP address through DHCP A H Green Indicates the status of each outlet Circuit Breaker Overload power protection Push to reset VIGILANT Series PDU User Manual Page 7 10 10 pduac1us man UNIPOWER Wp TELECOM VIGILANT SERIES OPERATING MANUAL 4 Installation This section provides quick instructions to install the PDU Rack Mount I nstructions A Elevate
3. arning and overload threshold Click on the APPLY button to lock in the new settings a PDU Total load 0 0 A Status Normal Information 5 Threshold Amp ame PDU Warning Overload System PDU 5 Control Outlet Configuration PDU Threshold User Network ail N SL n VIGILANT Series PDU User Manual Page 15 10 10 pduactus man uNIpower w TELECOM VIGILANT SERIES OPERATING MANUAL Configuration User Change ID and password Default ID is snmp and password is 1234 Click on the APPLY button to lock in the new settings 34 PDU Total load 0 0 A Status Normal Information Original PDU ID System Control Password Outlet New Configuration ID PDU Threshold Password User Apply Network Mail SNMP SSL VIGILANT Series PDU User Manual Page 16 10 10 pduactus man UNIPOWER Wp TELECOM VIGILANT SERIES OPERATING MANUAL Configuration Network PDU network information Enable DHCP When checked the PDU will obtain it s IP from the server Click on the APPLY button to lock in the new settings 3a PDU Total load 0 0 A Status Normal Information a PDU Host Name DIGIBOARD System IP Address Control Outlet Subnet Mask Configuration Gateway 13 i PDU Enable DHCP Threshold DNS Server IP Primary DNS IP Network Secondary DNS IP Mail Apply SNMP SSL VIGILANT Series PDU User Manual Page 17 10 10 pdua
4. ctus man UNI POWER w TELECOM VIGILANT SERIES OPERATING MANUAL Configuration Mail When an event occurs the PDU can send out an email message to a pre defined account Email Server Enter the Mail Server s Domain Name Sender s Email Enter the sender email address Email Address Enter the recipient email address Click on the APPLY button to lock in the new settings The message in the email Indicates OutletA H XXXXXXXX status in order X 0 means power off X 1 means power on Note Make sure DNS server can resolve the Email Server s domain name 3a PDU Total load 0 0 A Status Normal Information Email Setting PDU Q Email Server mail your com System Control Sender s Email sender yourcom com 0 Outlet Recipient s Email Address Configuration Email Address PDU Threshold User Network Mail SNMP SSL VIGILANT Series PDU User Manual Page 18 10 10 pduactus man VIGILANT SERIES OPERATING MANUAL UNI POWER w TELECOM Configuration SNMP When event occurs PDU can send out trap message to pre defined IP address Trap Notification Sets receiver IP for alarm traps Community Sets the SNMP community Read Community is public and fixed Default Write Community is public and can be modified by the user Click on the appropriate APPLY button to lock in the new settings 34 PDU Total load 0 0 A Status Normal Trap Notificat
5. d Operating Ambient If installed in a closed or multi unit rack assembly the operating ambient temperature of the rack environment may be greater than room ambient Therefore consideration should be given to installing the equipment in an environment compatible with the maximum ambient temperature specified by the manufacturer B Reduced Air Flow Installation of the equipment in a rack should be such that the amount of air flow required for safe operation of the equipment is not compromised C Mechanical Loading Mounting of the equipment in the rack should be such that a hazardous condition is not achieved due to uneven mechanical loading D Circuit Overloading Consideration should be given to the connection of the equipment to the supply circuit and the effect that overloading of the circuits might have on over current protection and supply wiring Appropriate consideration of equipment nameplate ratings should be used when addressing this concern E Reliable Earthing Reliable earthing of rack mounted equipment should be maintained Particular attention should be given to supply connections other than direct connections to the branch circuit e g use of power strips Diagram PDU Install In the Rack PDU Install In Y PDU Install In Remote Monitor The multiple PDU power S PDU Install In the Rack PDU Install In the Rack Local Monitor PDU Install In VIGILANT Series PDU Us
6. er Manual Page 8 10 10 pduactus man UNIDOWER w TELECOM VIGILANT SERIES OPERATING MANUAL Hardware 1 Install mounting brackets The PDU comes with brackets for mounting in a rack To mount the PDU into a rack perform the following procedure Attach the mounting brackets to the unit using the four retaining screws provided for each of the brackets Choose a location for the brackets Align the mounting holes of brackets with the notched hole on the vertical rail and attach with the retaining screws 2 Connect input and output power 3 Connect Ethernet cable to the PDU 4 Switch on the PDU Note 1 The default setting for obtaining an IP address is via DHCP If a DHCP server is not available the IP address can be programmed as desired manually using a PC set to the same network segment and connected with a cross over Ethernet cable The default IP address is 192 168 0 216 Note 2 TO SETUP THE NETWORK SYSTEM FOR VIGILANT PDUSs IT IS STRONGLY RECOMMENDED TO BUILD UP THE POWER MONITORING NETWORK ISOLATED FROM ANY OTHERS VIGILANT Series PDU User Manual Page 9 10 10 pduacius man UNIPOWER w TELECOM VIGILANT SERIES OPERATING MANUAL 5 Web I nterface Login Enter the PDU IP address in a web browser in the format http 192 168 0 216 Default ID is snmp Password is 1234 Connect to 192 168 0 59 The server 192 168 0 59 at Protected requires a username and password Warning This s
7. erver is requesting that your username and password be sent in an insecure manner basic authentication without a secure connection User name X Password Remember my password E I VIGILANT Series PDU User Manual Page 10 10 10 pduactus man UNIPOWER Wp TELECOM VIGILANT SERIES OPERATING MANUAL Information PDU Displays the total PDU load current as well as the WARNING and OVERLOAD threshold settings la PDU Total load 0 0 A Status Normal Information PDU PDU PDU 0 0 A Normal System Control Threshold Outlet Warning 8 0 A Configuration Overload 10 0 A PDU Threshold User Network Mail SNMP SSL VIGILANT Series PDU User Manual Page 11 10 10 pduactus man UNI POWER Wp TELECOM VIGILANT SERIES OPERATING MANUAL Information System Indicates PDU system information including Model No Firmware Version MAC Address System Name System Contact Location 34 PDU Total load 0 0 A Status Normal Information Model No XXXXXXXXXXX PDU Firmware Version s4 82 091012 1cb08s System MAC Address 00 16 18 77 04 51 Control System Name PPU OOOO Pa RE DE System Contact Admin PDU Location Office Threshold FApply User Network Mail SNMP SL VIGILANT Series PDU User Manual Page 12 10 10 pduactus man UNI POWER Wp TELECOM VIGILANT SERIES OPERATING MANUAL Control Outlet Indicates PDU outlet on off status and controls each outlet Select the outlet by checking the box a
8. ion Receiver IP 192 168 0 1 Community Read public Write public Page 19 10 10 pduactus man Information PDU System Control Outlet Configuration PDU Threshold User Network Mail SNMP SSL VIGILANT Series PDU User Manual UNIDOWER Ww TELECOM VIGILANT SERIES OPERATING MANUAL Configuration SSL Enables SSL for web communication User must enter the correct ID and password to enable SSL function These must be the same as the settings in User Click on the APPLY button to lock in the new settings a PDU Total load 0 0 A Status Normal Information Enable SSL 6 epu Confirmation System Control Outlet Password Configuration nn Threshold User Network Mail SNMP SSL VIGILANT Series PDU User Manual Page 20 10 10 pduactus man
9. nd then click ON or OFF button to control the outlet ON Press the icon to turn on the assigned outlets OFF Press the icon to turn off the assigned outlets OFF ON Press the icon to reboot the assigned outlets ia PDU Total load 0 0 A Status Normal Information Outlet Name Status F PDU OutletA ON O System OutletB ON Control OutletC ON d Outlet OutletD ON d Configuration OutletE ON O PDU OutletF ON Threshold OutletG ON User OutletH ON d Network OFF Mail SNMP SSL VIGILANT Series PDU User Manual Page 13 10 10 pduactus man UNI POWER Wp TELECOM VIGILANT SERIES OPERATING MANUAL Configuration PDU Sets the outlet name and delay time Name Rename the outlet ON Set delay time for power on sequencing OFF Set delay time for power off sequencing Click on the appropriate APPLY button to lock in the new settings Note The maximum delay time is 255 seconds a PDU Total load 0 0 A Status Normal Information ON OFF PDU Name Delay Delay sec sec Syst masan OutletA 1 1 Control OutletB 2 2 Outlet Configuration OutletC 3 3 PDU OutletD 4 4 Threshold OutletE 5 5 58 OutletF 6 6 Network 7 f OutletG T 7 Mail SNMP OutletH 8 8 VIGILANT Series PDU User Manual Page 14 10 10 pduactus man lt UNIPOWER w TELECOM VIGILANT SERIES OPERATING MANUAL Configuration Threshold Sets the w
10. tware which provides the functions to assist network manager in remotely monitoring multiple PDU power consumption for the entire enterprise Features e Built in web server the network manager can monitor the current consumption of the PDU in real time e Build in true RMS current meter e Easy setup the meter can display the IP address directly e Homepage supports SSL e Provides an audible alarm when power consumption is in excess of preset warning and overload limits e Can send emails and SNMP Alarm Traps when the power consumption exceeds the above limits e The supplied software utility can monitor a large number of PDUs at the same time SNMP support with provided MIB allows for the PDU to be monitored by a NMS e Real time to control of individual outlets LED outlets status indication Power on sequencing VIGILANT Series PDU User Manual Page 4 10 10 pduac1us man UNI POWER w TELECOM VIGILANT SERIES OPERATING MANUAL 2 PDU Package The standard package contains a VIGILANT Series PDU with supporting hardware and software The components of the package are Power Distribution Unit Rack mount Brackets CD ROM containing m User Manual mg PDU Software m MIB Management Information Base for Network PDUMIB mib m Adobe Acrobat Reader VIGILANT Series PDU User Manual Page 5 10 10 pduacius man UNIPOWER Wp TELECOM VIGILANT SERIES OPERATING MANUAL Interface True R