Operation and Maintenance Manual

image

Contents

1. Enforcer One LLC Copyright 2012 Page 14 Scheduled Maintenance Form E60PMCS Maintenance Recommended Date Due Date Performed By Activity Interval Complete d Nitrogen Every 6 months Cylinder Pressure Check Nitrogen Annually Cylinder Visual Inspection Nitrogen Every 2 years Regulator Inspection Nitrogen Every 5 Years Cylinder Hydrostatic Test Premix Every 5 Years Cylinder and Discharge Hose Hydrostatic Test Enforcer One LLC Copyright 2012 Page 15 Enforcer One LLC Copyright 2012 Page 16 Unscheduled Maintenance Maintenance Activity Date Performed Comments Notes Complete By d Enforcer One LLC Copyright 2012 Page 17 5 7 Servicing Under Normal Conditions a System Pressure Check 1 Make sure that the Fill Tower Cap is secure the Foam Discharge Valve and Pressure Relief Valve are closed 2 Open the Nitrogen Cylinder Valve and check the Nitrogen pressure on the High Pressure Gauge for normal operating pressure of 1800 2200psi 3 Check the Working Pressure Gauge is in the normal operating position 150psi 4 Conduct a leak check if the High Pressure Gauge reads below 1500 psi or if the Working Pressure Gauge reads below 150 psi a Spray a soap solution on all airlines fittings b Tighten leaking fittings replace O rings or replace defective components 5 Ble
2. Operation and Maintenance Manual Enforcer One LLC Copyright 2012 Page 1 Table of Contents Chapter 1 Page Product Introduction 3 Product Warranty 3 4 Safe Operating Procedures 4 5 Chapter 2 Page System Description 6 System Specifications 6 Chapter 3 Page Operating Instructions 7 9 Recommended Foam 7 Preventative Maintenance Checks and Services 7 8 Chapter 4 Page Training 10 Chapter 5 Page Maintenance 11 Servicing and Maintenance Activities 12 16 Troubleshooting 16 17 Enforcer One LLC Copyright 2012 Page 2 Chapter 6 Page Pictures 18 20 Chapter 1 Introduction 1 Manufacturer a The Enforcer 60 is Manufactured by Enforcer One LLC 180 Etowah Trace Suite B Fayetteville GA 30214 United States of America Phone 678 788 8413 Fax 6787 788 8415 E mail Info enforcerone com Website www enforcerone com b EnforcerOne is committed to the satisfaction of our owners and operators of the Enforcer 60 If you have any problems questions or concerns please contact EnforcerOne via phone Fax or E mail 2 _ Warranty Luc Copyright 2012 Page 3 Limited Warranty CAUTION User should read and follow all Safety Rules and Operating Instructions BEFORE first use of this product Enforcer One LLC warrants to the original owner user that Enforcer One LLC products will be free from failures due to defects in workmanship for a period of thirty year
3. 90 cu ft 2200 psi 151 6 bar Recharge Time 3 5 minutes 2 4 Transporting The Enforcer 60 should be secured when transporting in trailers or vehicles Chapter 3 Operating Instructions 3 1 Initial Setup The Enforcer 60 comes fully assembled The 60 gallon Premix Tank and Compressed Nitrogen Cylinder must be filled prior to use The proper FireAde 2000 product should be selected based on operational ambient temperatures and type of anticipated fires before putting the unit into service 3 2 Fireade 2000 Products a Enforcer 60 should only be used with Fireade products mixed at a 3 or 6 solution b It is recommended that a Fireade 2000 Freeze Protected Product be used when positioning the unit outside during extended subfreezing weather 3 3 System Depressurization Enfor LC Copy Page 8 Ensure the system is depressurized before conducting maintenance a Close the Nitrogen Cylinder Valves b Open nozzle until all Nitrogen is deployed and working pressure gauge reads zero or open Pressure Relief Valve 3 4 Preventative Maintenance Checks amp Services PMCS a It is recommended that the PMCS CHECKLIST be completed every month b Personnel conducting the PMCS should be thoroughly familiar with the Enforcer 60 system and the information contained in this manual Form E3PMCS Preventative Maintenance Checks and Services PMCS w i Checklist Date Completed Name ee _ Signature
4. 7 1 Conduct a visual inspection of the system for chaffing or loose hose s dirt corrosion or damage Enforcer One LLC Copyright 2012 Page 9 2 Check the Nitrogen Cylinder for normal operating pressure 1800 2200 psi Ensure System is depressurized Disconnect Nitrogen Cylinders and pull out of unit Connect Nitrogen Cylinder Pressure Check Gauge Open Nitrogen Cylinder and check for normal operating pressure 1800 2200psi e Close Nitrogen Cylinder and slowly disconnect Pressure Check Gauge allowing for pressure bleed off f If the Nitrogen Cylinder pressure is below 1500 psi remove recharge and replace the Nitrogen Cylinder oo D The Nitrogen Cylinder should normally be left in the closed position 3 Check the Premix Tank Level a Disconnect fill tower Cap check liquid level b Fill up the Premix Tank if low 4 Check the tire condition Note any other Problems 3 5 Operating Instructions A Warning Always refer to the product MSDS for proper precautions and tr atment s if foam is ger V a Extend hose ensure the Nozzle and the Foam Discharge Valve are in the closed position b Charge the system by turning the Nitrogen Cylinder Valves counter clockwise Enforcer One LLC Copyright 2012 Page 10 c Open the Foam Discharge Valve slowly to the full open position d Grasp the nozzle with hand e Aim the nozzle at the base of the fire and open valve to discharge foam 3 6
5. Cold Weather Operations a It is recommended that FireAde 2000 Climate Control Premix foam is used when freezing is anticipated 3 7 Emergency Procedures a Loose Hose 1 2 Go to the unit and close the Foam Discharge Valve Go to the Nozzle and close the valve b No Foam Discharge 1 2 3 4 Check to see if Nitrogen Cylinder is full Verify the Nitrogen Cylinder Valve is turned completely on Ensure Nitrogen Pressure Hose is attached properly Check for obstruction in discharge hose c Shut Down Procedures 1 2 Close the Nozzle Valve Close the Nitrogen Cylinder Valve Open Nozzle valve to depressurize the system or open Pressure Relief Valve Secure discharge hose Enforcer One LLC Copyright 2012 Page 11 Chapter 4 Training 4 1 Training Program a Training on the Enforcer 60 should be conducted or reviewed annually for all operators b Maintenance personnel should complete initial training and refresher training as required c Trainers should be thoroughly familiar with the system fire behavior hazard identification and basic firefighting techniques d Operator training should be accomplished in live fire scenarios Live fire training can often be accomplished through coordination with a local fire department 4 2 Training Program of Instructions a Operators and Maintenance Personnel 1 2 2 4 PMCS Normal and Cold Weather Operating Instruc
6. EGARDING THE PRODUCT S INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE Enforcer One LLC Copyright 2012 Page 4 No person or entity is authorized to bind Enforcer One LLC to any other warranty obligation or liability to distributer purchaser or any third party for any loss of profits economic loss indirect incidental punitive special or consequential damages whatsoever and howsoever caused Operation or use of this or any Enforcer One LLC product for which this warranty is issued shall constitute acceptance of the terms hereof CAUTION Prior to attempting to operate this or any Enforcer One LLC product you MUST read and understand all directions and instructions in this user manual Until you have read and understand all CAUTIONS Warnings Requirements Instructions for Set up amp Testing Operation and Maintenance NO ATTEMPT should be made to operate this or any Enforcer One LLC product In order to assure that your Enforcer One LLC product s are ready when needed they must be regularly maintained as outlined FAILURE TO COMPLY WITH ALL CAUTIONS WARNINGS REQUIREMENTS INSTRUCTIONS SAFE OPERATING REQUIREMENTS 1 DO NOT attempt to use this or any Enforcer One LLC product s if they appear damaged and or broken Missing or damaged components MUST be properly repaired or replaced as soon as possible Safe Operating Requirements continu
7. Nitrogen line is pinched cracked or broken System is Not Fully Discharging There is insufficient volume of Nitrogen in the Nitrogen Cylinder The Foam Discharge Nozzle is not fully opening The Foam Discharge Hose has a restriction The NitrogenRegulator has a malfunction The Foam solution is frozen or near freezing There is a blockage in the Premix Tank 5 12 Storage and Protection a The Enforcer 60 does not have any special storage requirements if stored inside b A protective cover is recommended and should be used if the equipment is stored outside as this will reduce sun damage to hoses and gauges Chapter 6 Enforcer One LLC Copyright 2012 6 1 Pictures Tire w w fre Fr Z D w bo amp VI 2 g GR E Se gt e u 53 Ka Ka Le a 3 kl _ HI n Ka 22 as c Sp o lt Caster Wheel Enforcer One LLC Copyright 2012 Page 22 Foam Discharge Valve Hose Tray f f f f f e f f Fill Tower Port Presssure Relief Valve Enforcer One LLC Copyright 2012 Page 23 Nitrogen Cylinders Premix Tank Enforcer One LLC Copyright 2012 Page 24
8. e Check pressure every 6 months Cylinder Visual inspection and certification annually Hydrostatic testing every 5 years Cleaning Wash with soap and water minimum annually Nitrogen Check Operation every 2 years Regulator Premix Tank amp Discharge Hose Pressurize and check for leaks annually Hydrostatic testing should be completed every 5 years Enforcer One LLC Copyright 2012 Page 19 Follow Foam Manufacturer quality testing recommendations Foam Solution 5 10 Unscheduled Maintenance Unscheduled maintenance will need to be performed as required 5 11 Trouble Shooting the System Users should contact Enforcer One if malfunctions cannot be corrected after employing good troubleshooting practices Use the matrix on page 17 for assistance Trouble Shooting Matrix Problem or Possible Solution Symptom No Pressure on Gauges Nitrogen Cylinder Valve is not turned on Nitrogen Cylinder is empty Pressure Gauge is inoperative Broken or blocked air hose Nitrogen Regulator has malfunctioned Enforcer One LLC Copyright 2012 Page 20 Foam Does Not Discharge From Hose Premix Tank is empty Nitrogen Cylinder is empty Nitrogen Cylinder is not turned on Nozzle is in the off position Nozzle valve has malfunctioned Blockage on dispensing hose Foam solution is frozen Nitrogen line Leak Nitrogen hose fittings are loose or broken
9. ed 2 DO NOT attempt to use this or any Enforcer One LLC product s if you are tired injured or under the influence of drugs medication or alcohol 3 DO keep children and bystanders away from the area where Enforcer One LLC product s are in use 4 DO NOT attempt to use this or any Enforcer One LLC product s in the event that the fire represents a situation that is beyond the capabilities of the Operator and or the Equipment Enforcer One LLC Copyright 2012 Page 5 5 DO follow the proper Set up Testing and Maintenance amp Inspection Procedures to assure that your Enforcer One LLC product s is are ready for use when needed 6 DO exit the area IMMEDIATELY if progress in fighting the fire is not being made and DO NOT return to the area 7 DO comply with all local Laws amp Regulations related to the proper use installation maintenance training and inspection of Fire Fighting Equipment WARNING The act of fighting fire is both hot and dangerous work avoid serious injury or death If ever in an attempt to extinguish a fire you are unsure that progress is being made contain the fire if possible and move quickly and safely away from the threat ADDITIONAL INFORMATION http www usfa fema gov safety sheets htm http www nfpa org education index html http www ilpi com safety extinguishers html 3 Manual Changes 1 EnforcerOne will provide equipment update changes to this manua
10. ed off any stored pressure through Pressure Relief Valve b Changing and Servicing Nitrogen Cylinder Ensure the system is depressurized before conducting Ay maintenance on the system Extreme care should be used when transporting the Nitrogen Cylinder s Ensure Nitrogen Cylinder Valves are closed Depressurize the system Lift out the Nitrogen Cylinders Have the Nitrogen Cylinders filled to 2200 psi by a certified technician 5 Replace the Nitrogen Cylindesr in the holder 6 Reconnect the Nitrogen Cylinders P LA PM EH c Refilling the Premix Tank 1 Close the Nitrogen Cylinder Valves 2 Ensure System is depressurized Enforcer One LLC Copyright 2012 Page 18 6 7 Remove Fill Tower Cap Add water until Premix Tank is full Add appropriate amount of foam using funnel allowing clear water to be displaced from top of Premix Tank Replace Fill Tower Cap ensuring it is tightened properly Important Note The Fill Tower Cap should be tightened by hand Refilling the Premix Tank continued 5 8 Servicing In Cold or Freezing Conditions Fill the Premix Tank with FireAde 2000 Freeze Protected Foam solution whenever temperatures are below 32 degrees Fahrenheit Freeze Protected Foam should be used in the concentrate form in cold or freezing temperature conditions 5 9 Scheduled Maintenance Interval Recommendations Component Maintenance Activity and Recommended Interval Nitrogen
11. l on an as need basis Enforcer One LLC Copyright 2012 Page 6 2 This manual and associated updates will be posted on the EnforcerOne web site 3 This manual supersedes all previous Operating Instructions for the Enforcer 60 system Enforcer is a registered trademark of EnforcerOne LLC FireAde is a registered trademark of Fire Service Plus Inc Chapter 2 System Description 2 1 General Information The Enforcer 60 Compressed Air Foam System utilizes compressed nitrogen to propel firefighting foam Enforcer 60 produces air aspirated foam providing a thick vapor sealing blanket that will inhibit re ignition The Enforcer 60 will produce up to 600 gallons of finished foam with discharge duration of up to 4 minutes The system can be easily recharged by the end user Model Configuration The Enforcer 60 consists of a Premix Tank which holds 60 gallons of pre mixed Fireade 2000 Two compressed nitrogen cylinders are attached to the Premix Tank through a regulator and hose assembly One 50 section of lay flat hose and one pistol grip style Nozzle Specifications Height 38 5 97 79 cm Length 54 5 138 34 cm Depth 42 106 68 cm Empty Weight 495 Ibs 224 5 kg Loaded Weight 995lbs 451 3 kg Premix Tank 60 US Gallons 227 1 Finished Foam Capacity 1200 US Gallons 6814 1 Enforcer One LLC Copyright 2012 Page 7 Foam Discharge Distance Up to 95 Feet 29 m Nitrogen Cylinders
12. s from the date of original purchase During the warranty period Enforcer One LLC at its sole discretion will repair or replace at no charge the product that in its sole opinion is defective The purchaser is responsible for packing the product for shipment and for charges to ship the product to the location specified by Enforcer One LLC including at the purchasers sole discretion insurance on the shipment Enforcer One LLC will return the product pre paid to the purchaser If the product has been altered modified or repaired in any way or if the failure is the result of misuse abuse or misapplication without the prior consent of Enforcer One LLC this warranty shall be void and Enforcer One LLC shall have no obligation to repair or replace the failed The use of any foam product other than FireAde 2 products will void the warranty Warranty continued When used in conjunction with sound fire management practices and strictly as per the manufacturer s instructions the products may provide protection against anticipated fires and may accelerate the extinguishing of existing fires CAUTION The unpredictable nature of fires the techniques used to apply product s as well as the knowledge understanding and judgment of the individual s attempting to extinguish or control THIS WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY FOR Enforcer One LLC PRODUCT S AND DISCLAIMS AND EXCLUDES ANY AND ALL IMPLIED WARRANTIES R
13. tions Emergency Procedures Operation in live fire scenario b Maintenance Personnel 1 2 8 9 Enforcer One LLC Copyright 2012 General Maintenance Instructions and Technical Assistance Foam Product Maintenance Log Servicing Under Normal and Cold Conditions Scheduled Maintenance Unscheduled Maintenance Troubleshooting Procedures Storage and Protection Page 12 Chapter 5 Maintenance 5 1 General Instructions a It is recommended that the preventative and maintenance PMCS be conducted monthly b It is recommended that qualified personnel be assigned the responsibility to service and maintain the system c All maintenance activity should be documented and should include copies of the completed PMCS Checklist Premix Tank Filling Calendar type ratio of product used component changes and any other problems encountered A MSDS should be maintained for the type of foam being used 5 2 Technical Assistance Maintenance personnel should contact EnforcerOne whenever any problem arises that cannot be solved using the information in this manual or when unusual situations are encountered or expected Enforcer One LLC Copyright 2012 Page 13 Form E60PMCS Enforcer 60 Maintenance Log Preventative Maintenance Checks and Services PMCS Refer to Chapter 5 Maintenance for specific activities Maintenance Date Performed By Notes Comments Activity Completed

Download Pdf Manuals

image

Related Search

Related Contents

Guide du forum - Carrefours pour l`emploi  sparco spanish Manual 0150  the User`s Manual in PDF format - Honeywell C  Bedienungsanleitung  FLY FUSION PENTOP COMPUTER USER GUIDE  Stochastic Transport in PPCD Discharges  カタログ  GUÍA DEL USUARIO USER`S GUIDE - Support  Manual for DZ Range  TAFCO WINDOWS NU2-083V-I Installation Guide  