1. crate terminating after completion initialization jn_led 1 1 E n LED Ul on run_once_init function somewher lse in the script jn_led 1 0 turn LED UL off After a run once initialization section an infinite loop is executed calling as often as possible the doevents function Automatic jn_led 1 1 turn LED ul on execution of run_once_init function somewher lse in the script monitoring while 1 do loop doevents run_in_loop function somewhere else in the script pause 100 wait 100 msec end jn_led 1 1 turn LED Ul on run_once_init function somewhere else in the script while 1 do doevents COMBO if nim_testint 1 1 then servicing do_something function somewhere else in the script nim cack 1 end end ZP ENGINEERING srl JENET User s Manual v 1 0 2 JENET Ethernet based CAMAC controller 8 Firmware Upgrade It is possible to upgrade a section of FLASH memory contents in order to allow firmware upgrades on the field either to correct any problems that may show up during usage or to load application specific executables Internal FLASH is structured into two banks one for the operating system and one for the application the application bank includes all the executables related to J enet When using a NFS mapped disk please remember to add the following line Note lt nfs_directory gt lt IP addres
2. lua_getlog Lua related command returns log file in place of stdout SYSTEM I DENTFICATION and VARIOUS ver TES Returns a string containing firmware and FPGA versions jn_fpgaver jn_fpgaver Returns a string containing FPGA details read only information from FPGA registers jn_fwver jn_fwver Returns a string containing the current firmware version running on the system jn_initstat Get results of board initialization it should always be O jn_led lt which gt lt value gt jn_led which value Set front panels LEDs U1 U2 U3 U4 lt which gt 1 to 4 lt value gt 0 or 1 web_setuser lt text gt web_setuser text Sets text that appears in User page see web server section web_getuser web_getuser Returns text appearing in User page see web server section Lua only commands doevents Enable system control of Lua loop pause msec Wait for specified interval in msec band a b bor a b Binary operators bxor a b bmod a b AND a amp b OR a b bsl a b bsr a b XOR a b MOD a b BSL a lt lt b BSR a gt gt b zP ENGINEERING se EA 27 28 JENET Ethernet based CAMAC controller 11 System Specifications Power Supply Required voltages on crate Ethernet interface 24 V 100 mA 24 V 100 mA 6V 100 mA 6V 700 mA Settings 10 100 Mbit autonegotiating Default configuration
3. Serial port IP address 192 168 0 98 subnet mask 255 255 255 0 default gateway 0 0 0 0 DHCP client 0 disabled default configuration can be changed through serial port Settings 38400 baud 8 N 1 no flow control Function CAMAC bus interface for configuration changes system settings startup options Compliance NIM interface to ANSI IEEE std 583 1982 Connectors CPU section SUHNER type Processor ARM7TDMI running at 44 MHz Operating System uClinux ver 2 4 17 FLASH 4 Mbytes SDRAM 16 Mbytes ZP ENGINEERING srl JENET User s Manual v 1 0 2
4. in order to trigger update operations in the optimal way it is best to click on the link available on the navigation bar instead of hitting the refresh button of the browser i e F5 on Internet Explorer This is due to the difference in HTTP requests that are sent by various web browsers when refreshing the page gt help Web interface to CAMAC commands gt Commands with local log capability Control panel for NIM section inputs HOME gt NIM 1 0 outputs COMBO 1 0 counters pulse generator 3 f Currently not used for future gt Configurations releases R Voltage monitoring and Crate Scan gt Diagnostics result Application controlled content from gt User Lua or socket Read only settings for network and gt System hardware ZP ENGINEERING sri JENET User s Manual v 1 0 2 11 28 JENET Ethernet based CAMAC controller 6 1 Commands page The local web server contains a page dedicated to CAMAC commands in order to allow immediate testing of crate functions There is a log capability currently limited to actions performed on the web page A drop down selection box allows the choice of one of 7 CAMAC commands on the entry box the relevant parameters have to be entered when pressing the EXECUTE button the commands will be executed For read functions the result is available on the data field of the log section for testing functions
5. C2 26 E0 0A ee_setrob lt value gt Sets Run on Boot flag to specified value 0 or 1 ee_getrob Returns current Run on Boot flag value 0 or 1 ee_getserial Returns J enet serial number ee_setcscan Sets Crate Scan flag to specified value 0 or 1 ee _getescan Returns current Crate Scan flag value 0 or 1 ee_storeconf Stores current NIM section configuration into EEPROM default settings ZP ENGINEERING srl J ENET User s Manual v 1 0 2 25 28 JENET Ethernet based CAMAC controller TCP control socket Lua Description NIM I O SECTION nim_getin nim_getin Returns NIM input values it returns a 1 a 2 a 3 a 4 where a n 0o0r 1 nim_getins lt which gt nim_getins which Returns a single NIM input value 0 or 1 lt which gt 1 2 3 or 4 nim_setievent lt which gt lt en gt lt pol gt nim_setievcnt which en pol ext_reset Sets Input Event Counter with parameters lt which gt lt enable gt lt trig lt ext_reset gt edge polarity gt lt external reset enable gt nim_getievent lt which gt nim_getievcnt which Returns Input Event Counter settings nim_geticnt lt which gt nim_geticnt which Returns current Input Event Counter value nim_reseticnt lt which gt nim_reseticnt which Reset specified Input Event Counter lt which gt 1 or 3 nim_getouts lt which gt nim_getouts w
6. all functions through TCP socket Dynamic local web server allows advanced monitoring and control without the need to install dedicated software perfect for crate setup and maintenance User page with results from script Embedded script interpreter allows local execution of C like code with full control on CAMAC and NIM functions No need to install cross compilation toolchains X and Q signals on last access 4 user LEDs controllable from script Fault connection status and NIM default indicators ZP ENGINEERING srl JENET User s Manual v 1 0 2 JENET Ethernet based CAMAC controller 2 Starting up 1 Please insert the controller into slots 24 and 25 ONLY of a standard CAMAC crate rightmost when looking the crate from the front side 2 if default network settings are compatible with your setup connect a LAN cable to the front panel RJ 45 socket 3 Power up the CAMAC crate 4 Wait about 20 seconds to allow completion of operating system boot 5 If default network settings are not suitable for your network environment connect a terminal to the front panel serial port and make the necessary variations see Serial port control section After that reboot either by cycling the main power or by pressing the RESET front panel button and wait about 20 seconds 6 For instant gratification please open your favorite browser on a host connected to the same LAN used by Jenet and point to its IP address if default settings
7. crates is shown ZP ENGINEERING srl JENET User s Manual v 1 0 2 JENET Ethernet based CAMAC controller JENET CAMAC CRATE 192 168 0 98 CONTROLLER EE TCP client lt gt M gt socket CRATE 1 WN CRATE server O 1 TCP client Z gt IRQ TCP socket m U client gt di TU CRATE 2 oO 3 E 5 O JENET TCP socket lt gt CAMAC CRATE 163 168 0 08 client lt p gt lt gt a CONTROLLER CRATE 3 O _ Lo O CRATE Q Z port N 2 TCP client TCP ry o IRQ pl socket gt server lt gt gt gt IRQ all crates JENET CAMAC CRATE CONTROLLER 192 109 0 190 H O ST 3 TCP client IRQ A special command is represented by CNAME and deserves an additional explanation CNAME stand for Connection Name and is a string identifier internally used by Jenet to understand who is talking to the local socket server This feature is useful when multiple clients are connected and talking to the socket server It is currently optional in firmware release 1 0 but we suggest using it at the beginning of connection to provide an upward compatibility for future releases On Windows 2000 XP it is possible to perform a quick test with the Hyperterminal application by specifying connection with TCP IP and Note port 2000 on linux hosts you can use the standard telnet client in
8. raw mode by typing telnet lt IP addr JNTO1 gt 2000 5 2 ESONE library The ESONE library is an ANSI C library delivered in source form providing an ESONE like abstraction to the socket protocol including multiple crate support Documentation specific to the ESONE C library is on a separate document available on the J enet support web site Note that the ESONE library is not mandatory it is always possible to develop a library to directly handle communication at the socket level however the ESONE library facilitates migration of existing code and can be used as a reference for direct implementations ZP ENGINEERING srl JENET User s Manual v 1 0 2 10 28 JENET Ethernet based CAMAC controller 6 Local web server The local web server is a dynamic server in the sense that gathers relevant data and information directly from the machine therefore depending on page contents page refresh may be slower than expected if compared to a fully static web site Z JENET Microsoft Internet Explorer DER File Edit View Favorites Tools Help Address E http 192 168 0 93 Vv Ss Ar Jenet CAMAC CRATE CONTROLLER VAZP Engineering Home Commands NIM I O Configurations Diagnostics User System Web Enabled The upper navigation CAMAC Crate enet anst oas Controller Official support site on internet Configuration amp Control Web Server Jenet support site at www zpeng com jenet Note
9. that in order to be ready to accept new events the COMBO section must be explicitly served by the user in one of the following ways with a script section that resets the relevant COMBO FF within the application running on host with a routine that in response to the COMBO event resets the relevant COMBO FF by clicking on the RESET button on the NIM I O web page SET COMBO I O Event Counter Incremented on BUSY output rising edge Trigger event TRIG input rising edge Dead Time Counter 1 92 67 usec to 65535 6 7 sec TRIG to BUSY response 35 ns EXAMPLES Acknowledge COMBO 1 trigger Notes TCP socket commands Lua code snippet nim_cack 1 nim_cack 1 Wait for TRIG on 1 and then turn NIM outs 3 4 ON TCP socket commands Lua code snippet nim_waitint 1 nim_cack 1 Blocking mode wait not jn_led 3 1 jn_led 4 1 available on socket nim_testint 1 repeat then if nim_waitint 1 1 then Test mode nim_cack 1 nim_cack 1 jn_led 3 1 jn_led 4 1 jn_led 3 1 end jn_led 4 1 ZP ENGINEERING srl JENET User s Manual v 1 0 2 23 28 JENET Ethernet based CAMAC controller 10 Commands reference A reference of available commands on both the TCP control socket server and the local Lua scripting language is detailed in this section Note that whenever possible TCP control commands are as short as possible in order to minimize Ethernet traffic on the other
10. the result is available in the data section with values 0 or 1 Please remember that in the current implementation logging is enabled only for commands executed from this web page Logging is ten events deep it is also possible to clear the log directly on the web page execute a CAMAC command response in Q CSSA lt function gt lt slot gt lt subaddr gt lt data gt with 16 bit data function 0 31 slot 1 23 subaddr 0 15 execute a CAMAC command responsen Q CFSA lt function gt lt slot gt lt subaddr gt lt data gt With 24 bit data function 0 31 slot 1 23 subaddr 0 15 CCCcCc generate dataway initialize IA CCCI lt value gt set clear dataway inhibit value 0 reset value 1 set CTCI test dataway inhibit response in Q field response in Q field lt gt test LAM A JENET Microsoft Internet Explorer DER File gdt View Favorites Tools Help Address E http 1192 168 0 93 Ho amp Jenet CAMAC CRATE CONTROLLER VAZP Engineering Home Commands NIM I O Configurations Diagnostics ser System command parameters Commands Leef Nn a mode data o x Clearlog quick 8 1 16 e o o o reference test_I o test_L o 3 c 0 o a Clear log entries ZP ENGINEERING srl JENET User s Manual v 1 0 2 12 28 JENET 6 2 NIM I O page The NIM I O page is arranged like a real control panel in order to allow immediate interaction with the I O section available on the
11. 0 Control socket commands for Lua control added section 7 2 2 24 02 04 UZ Revised jsm description section 7 2 3 ZP ENGINEERING srl JENET User s Manual v 1 0 2 3 28 JENET Ethernet based CAMAC controller 1 General information This manual is intended to provide a reference for operating and programming JENET an Ethernet based CAMAC crate controller 1 1 Warranty HARDWARE ZP Engineering srl warrants the JENET JNTO1 product to operate within specifications under normal use and service for a period of 2 two years from the date of shipment Component products replacement parts and repairs are warranted for 90 days This warranty extends only to the original purchaser Should the product in ZP Engineering s opinion malfunction within the warranty period ZP Engineering will at its discretion repair or replace the product upon receipt with an equivalent Any replaced parts become property of ZP Engineering This warranty does not apply to a product that has been damaged due to accident misuse abuse improper installation usage not in accordance with product specifications and instructions natural or personal disaster or unauthorized alterations repairs or modifications Please note the following The warranty applies only to defects in workmanship The warranty makes no claims regarding suitability of the product for a particular use or environment A serial number is required for any warranty serv
12. JENET Ethernet based CAMAC controller ES ZP Engineering srl Ethernet CAMAC Crate Controller ETHERNET 2 ty CAMACCRATE 2 CONTROLLER www zpeng com jenet User s Manual P N JNTO1 Ver 1 0 2 Date 25 Feb 2004 ZP Engineering srl Via Michelangelo Peroglio 15 00144 Rome ITALY www zpeng com ZP ENGINEERING srl JENET User s Manual v 1 0 2 1 28 JENET Ethernet based CAMAC controller INDEX 1 GOoneral informati n asee ds 4 A A A aueiee hele wtyietleaeutte dels A 4 ES OVERVIC O coh lous iat ian 5 1 3 Summary Of features vives cssece cece iee ce tees ease de eed eva eden dee k ca ey ew aA Ea EEE aaa ees 5 2 StAPCinG WU Pisa fete h tet here E EE ded ahem taut nieda he huntnn bitin bealetaabiinindreb a ataabtomiecarets 6 3 Serial port Control cssa emma ii aa 7 4 Startup OPtlonS ir IR a A aia 7 E Al A A avi Sea eae ea nts ei a ee eee Me ee 7 4 2 JUMper SettiNg Sis sc coved iaasa Saleen ed tans eee ele rege lena eu dabei ee ieee eee 8 5 Remote Control secon secant deine ieee ae ae 9 5 LTGP c ntrol SOCK EE sage dee narrar 9 D2 ESONE lbn to eco ceder gid ince cael oleada aid 10 6 Local Web Server vscegecegs niyii ips ents Wied evened a end 11 6 1 Commands Page esis ceca en elec dge ees ey ee een aa es da 12 6 2 NIMiL O Pag Eana ao 13 6 2 1 INPUT Section rta iaa As 13 6 22 OUTPULSECHON ni A ee ina AA O A eel eee nla 14 6 2 3 COMBO Section soto tates sees A edness de ee a ee
13. LACK slot LAM acknowledge CTSTAT CTSTAT Returns Q and X values from last access on bus ZP ENGINEERING srl J ENET User s Manual v 1 0 2 24 28 JENET Ethernet based CAMAC controller TCP control socket Lua Description DIAGNOSTIC SECTION vn24 vn24 Returns the measured voltage on 24V power supply in float format vn12 vn12 Returns the measured voltage on 12V power supply in float format vn6 vn6 Returns the measured voltage on 6V power supply in float format vp6 vp6 Returns the measured voltage on 6V power supply in float format vp12 vp12 Returns the measured voltage on 12V power supply in float format vp24 vp24 Returns the measured voltage on 24V power supply in float format vp33 vp33 Returns the measured voltage on 3 3V power supply in float format vps vps Returns the measured voltage on 5V power supply in float format SYSTEM PARAMETERS stored in EEPROM ee_getdhcp ee_getdhcp Returns 0 if DHCP client is not enabled 1 otherwise ee_getdns ee_getdns Returns current DNS in dotted notation ee_getgw ee_getgw Returns current Gateway in dotted notation ee_getip ee_getip Returns current IP address in dotted notation ee_getmask ee_getmask Returns current IP mask in dotted notation ee_getmac ee_getmac Returns current MAC address in hex format with delimiters like in 00 50
14. acing or removing internal jumpers Only experienced personnel should perform this operation The operation is described in steps as follows switch off power from the crate remove the controller from the crate remove the lateral cover left side when looking on the front panel of the controller you should see the internal boards with components facing your side locate the jumper block right behind the serial port connector note that if all jumpers are removed default condition then the unit will perform in the standard mode insert jumpers only if you want to modify the standard setup according to the table Insert to disable Notes jumper on Disable telnet to avoid system access to local resources used only for performing a firmware upgrade or for debug Disable web server if HTTP access not required in order to J MP9 WEB SERVER obtain maximum performance note that it cannot run if application is also disabled Disable application if the system hangs after powerup i e after failing a firmware upgrade Disable serial port application if the system keeps hanging J MP7 COM SERVER after powerup it may also be used to prevent local access to critical parameters i e network settings JMP10 TELNET J MP8 APPLICATION ZP ENGINEERING srl JENET User s Manual v 1 0 2 JENET Ethernet based CAMAC controller 5 Remote control The unit has been designed to allow full
15. apply the default IP address is 192 168 0 98 From the werb server pages you already have control over the NIM I O section and the possibility to perform individual commands on the CAMAC bus Jenet NIM output 1 O can be set as a pulse 4 4 generator Power supply presence indicators ZP Engineering srl NIM outputs Status of X ery LEDs are ON when and Q signals output is active on last CAMAC access User LEDs COMBO trigger busy controllable from sections Lua and socket LEDs are ON when output is BUSY Connect status LED ON when a socket connection is active Ooms 00 00500 NIM inputs IN 1 and 3 can be set as event counters IN 2 and 4 can be enabled as external reset for event Pushbutton and counter and or external SYSTEM COMBO sections RESET ZP ENGINEERING srl JENET User s Manual v 1 0 2 6 28 JENET Ethernet based CAMAC controller 3 Serial port control A serial port connector located on the front panel allows the user to modify system settings this procedure is required if current network parameters are incompatible with the local network It is also possible to modify startup options Connection parameters are the following 38400 baud 8 N 1 no flow control Echo is not enabled on the serial port so please enable character echo on your serial terminal The following commands are available help Provides a quick li
16. control from a remote location taking advantage of the available high speed Ethernet interface A summary of the implemented TCP IP services is detailed Service Port Notes HTTP server 80 Dynamic Web Server it serves up to N client browsers at the same time TCP server 2000 TCP control socket up to N different clients are allowed at the same time TCP client Connects to host TCP server for interrupt management only Telnet server 23 System telnet server it is used mainly for firmware updates and may be disabled by the user see Startup options section Please note that the telnet connection is unsafe no password protected access no encryption The internal software architecture is designed to allow control of multiple crates It must be considered that when using an Ethernet based CAMAC controller the distinction between crates is implicit as every crate is identified by a different IP address Therefore the crate number is typically not a parameter in many command definitions The local web server allows quick testing and monitoring of the CAMAC crate while the socket connection is the main control method for general applications the availability of an internal scripting engine represents an additional plus 5 1 TCP control socket Remote control is organized as follows the local firmware opens a TCP socket server on port 2000 and waits for connection from a remote client when a client connect
17. e intermittent failure i e the web page sometimes does not reload and all other communications will fail ZP ENGINEERING sri JENET User s Manual v 1 0 2 JENET Ethernet based CAMAC controller 6 4 Diagnostics page A JENET Microsoft Internet Explorer AHK File Edit view Favorites Tools Help Address E http 192 168 0 113 Jenet CAMAC CRATE CONTROLLER YA ZP Engineering Commands NIM I O Configurations Diagnostics CAMAC Power Supplies Local Power Supplies momia ooo o ewo sv Update Voltages Crate Scan Result JENET has detected cards in the following slots 6 18 This page shows current voltage readouts divided into crate power supplies and local digital only power supplies Note that J enet requires the following voltages to be present in order to work properly 24V 6V 6V 24V On the bottom of the page results of the Crate Scan performed only at power up if the CSCAN flag is enabled see Startup Options section are shown in textual form Remember that if Crate Scan is problematic depending on which cards are inserted into the crate it can be disabled either by serial or control socket ZP ENGINEERING srl JENET User s Manual v 1 0 2 16 28 JENET Ethernet based CAMAC controller 7 Local scripting 7 1 Lua scripting language An on board script interpreter is available allowing complex interactions with the CAMAC bus and local NIM I O section The scripting language is Lua ext
18. ee 14 6 3 System SettiNGS PAGE 2 eee EEE erate ee tenet a ARANA 15 6 4 DiagGnOStics Pages eeu e uae cee agenda a end 16 7 LOCAL SEF PUING ti Ada 17 7 I LUa seripting language isise e id dl de TAA a 17 7 2 Lua engine in J net een narrar rr nn tenant nana eae nates 17 7 2 1 Bit manipulation extension eee eee eee eee e netted 18 7 2 2 Socket commands for Lua CONntrol cece eee eee eee eee eee eee eee ed 18 7 2 3 Jenet Script Manager jSM cece eee eee tenet ene e eee need 19 7 2 4 Scripting ON net piisi ec cece iisi es Sees ed il 19 8 Firmware Upgrade a tee aed 20 9 NIM SUbDSECEON A A cabin ceed eed aan wat eee eed ete 20 9 1 Default DUtCON sorsia eens cece can IAEA ERASE Rate 20 OF 2 IMPULS ict canteen trea A A A esl oudeca eaten ae ayaanghees 21 YAQUI UE A aide iid eae ens 22 9 4 COMBO O shh ee ie eh es a ene OM tee eh cheba hb AS 23 10 Commands reference 0 ccc nr ea akea aaiae apada adinan 24 11 System Specifications oc sis a a a a ee eed dia ee shine 28 ZP ENGINEERING srl JENET User s Manual v 1 0 2 JENET Ethernet based CAMAC controller This log identifies those portions of this document which have been revised since the original issue and the date of each revision Summary of changes to previous version Date Approval First version 15 01 04 UZ PP MV FP Notes added to sections 3 5 1 and 8 11 02 04 UZ Lua binary operators added section 7 2 1 and section 1
19. ended with a TCP IP library and with specific commands that allow management of the underlying hardware Lua is a powerful lightweight programming language designed for extending applications frequently used as a general purpose stand alone language More information is available at www lua org Please take not that while being free software it is property of Tecgraf http www tecgraf puc rio br of which we acknowledge the excellent work A brief description of the scripting engine and its extensions follows This is the base scripting engine It has been conceived as an efficient Lua Version 4 0 compact add on scripting library for various applications Extension to Lua 4 0 developed by i Diego Nehab that adds TCP and UDP Luasocket library Version 1 4 functionality to the Lua scripting language Bit manipulation Added by ZP Engineering srl to offer extension bit wise AND OR XOR functions Added by ZP Engineering srl to offer full control of the local NIM I O section Added by ZP Engineering srl to offer full control of system functions Added by ZP Engineering srl to offer CAMAC extension full control over CAMAC commands and functions NIM I O extension System extension Note that a complete reference of Lua is available on www lua org and on the J enet support site courtesy of the Lua community at www zpeng jenet 7 2 Lua engine in Jenet One of the d
20. esirable features of Lua is that the language can be easily extended with new commands this technique has been applied to allow full control of J enet from a script A detailed reference of available extension commands is presented in chapter 9 Commands Reference A dedicated application that connects to the control socket server allows the user to load the script and control its execution The script is launched and executed directly in case of error the FAULT red LED on the front panel is lit and script execution is halted By issuing a stop command it is possible to restore the script engine to idle state The special function doevents has been added to deal with the single threaded nature of the scripting engine it allows the system to terminate execution of the script itself If this call is missing or called rarely then it may not be possible to halt execution of the current script ZP ENGINEERING srl JENET User s Manual v 1 0 2 JENET Ethernet based CAMAC controller The ROB Run On Boot dedicated flag is available on the local EEPROM to indicate whether the FLASH script should be executed at startup Note that there is no assumption of the temporal evolution coded into the script therefore many different uses may be made of the scripting capabilities 7 2 1 Bit manipulation extension As the base Lua library does not provide bit manipulation operands ZP Engineering added some commands to allow binary operatio
21. front panel of the unit In addition it is possible to retrieve default settings by pushing the DEFAULT front panel button just above the RESET button Default settings are stored with a specific socket command Note that not all interactions are allowed a fuller control is available from socket or scripting as browser access is considered unsafe from the remote control point of view 6 2 11 nput section Ethernet based CAMAC controller JENET Microsoft Internet Explorer File Edit View Favorites Tools Help Address http 192 168 0 93 HBe a 3enet CAMAC CRATE CONTROLLER Commands NIM I O Configurations Diagnostics User System event VAZP Engineering event counters COMBO E BUSY LO gt HI 26881 reset COMBO 1 event 1 counter reset event counter enable pulse generator COMBO E reset COMBO 2 7 reset event counter period 1024 0 dth 264ns reverse polarity counters 26881 readout Enable async reset counter soft reset Event counter ZP ENGINEERING sri JENET User s Manual v 1 0 2 two event counters can be enabled on inputs 1 and 3 independently by selecting the required triggering transition HI to LO or LO to HI in the drop down box event counter on input 1 can be asynchronously reset by input 2 if the checkbox is flagged there is also a button on t
22. guration of the system The same settings are applied at power up and can be set through the control socket The green LED located just below the DEFAULT pushbutton is turned on when default settings are applied and turned off whenever any of the relevant settings is altered providing an immediate visual feedback of the validity of default settings ZP ENGINEERING srl JENET User s Manual v 1 0 2 JENET Ethernet based CAMAC controller 9 2 Inputs The NIM INPUT subsection implements four independent NIM inputs that may be read asynchronously to retrieve input status or configured to perform event counting specifically inputs 1 and 3 can be set as event counter triggering on rising or falling transition more Counter reset is performed either with a dedicated control command or with an external reset derived from input 2 for counter on input 1 and from input 4 for counter on input 3 Note that external reset capability must be enabled with the proper commands External reset is active when relevant input is HI while HI counter is kept to zero and will not count further NIM in 1 EVENT COUNTER vv Jot th vv Fil NIM in 2 C on INPUTS NIM in 3 EVENT COUNTER NIM in 4 O gt Co RESET INPUTS EXAMPLES toe ds LO to HI trigger HI to LO trigger Read from inputs Notes TCP socket commands Lua code snippet nim_getin nim_geti
23. hand Lua commands are more descriptive Some general rules follow Control socket commands ALWAYS return an error code as first parameter 2 if the command is non existent command parameters are wrong return values as it must be always O to yield a correct answer TCP control sockets are not case sensitive while Lua commands are case sensitive this is a specific property of the language As much as possible all commands have the same name for Lua and for TCP control socket it is equal to O if the commands executed with success 1 if in the table below this error code is NOT indicated when describing TCP control socket Lua Description CAMAC bus control 24 bit CAMAC command returns Q and data CCG CCCZ Generate Dataway Init Cece CCCC Generate Crate Clear CFSA lt function gt lt slot gt lt addr gt lt data gt CFSA function slot addr data f CSSA lt function gt lt slot gt lt addr gt lt data gt unction slot addr data 16 bit CAMAC command returns Q and data CSSA I CCCI lt value gt CCCI value Change Dataway Inhibit to specified value 0 or 1 CTCI CTC CAMAC test Inhibit returns O or 1 CTLM lt slot gt CTLM slot CAMAC test LAM on specified slot 1 23 CCLWT slot CAMAC wait for LAM on specified slot only for Lua CLMR CLMR Returns current LAM register in hex LACK lt slot gt
24. he page that allows a software reset of the counter event counter on input 3 can be asynchronously reset by input 4 if the checkbox is flagged there is also a button on the page that allows a software reset of the counter 13 28 JENET Ethernet based CAMAC controller 6 2 2 Output section enable pulse generator period 1024 0 l tee width 264ns v O reverse polarity b Read current Pulse output state Manual generator output set settings output 1 can be set as a programmable pulse generator for which the period pulse width and polarity can be specified numerical entry of pulse generator period is automatically adjusted to fit the available resolution when the page is reloaded 6 2 3 COMBO section COMBO BUSY Reset COMBO stage IMA SEM event 1 Event counter number of BUSY activations Bao es Event counter counter COMBO input 1 can be reset with the dedicated button the usual way to reset a COMBO input would be from software COMBO input 2 can be reset with the dedicated button the usual way to reset a COMBO input would be from software Dead Time Counter for both COMBO inputs is not shown on web page as it has relevant meaning only immediately before resetting the COMBO input ZP ENGINEERING srl JENET User s Manual v 1 0 2 JENET Ethernet based CAMAC controller 6 3 System settings page A JENET Microsoft Internet Explorer DER File Edit View Favor
25. hich Returns current value of specified output lt which gt 1 4 nim_getout nim_getout Returns current value of all outputs nim_setouts lt which gt lt value gt nim_setouts which value Sets value of specified output lt which gt 1 4 nim_setout lt vl gt lt v2 gt lt v3 gt lt v4 gt nim_setout vl v2 v3 v4 Sets current value of all output lt which gt 1 4 nim_setpulse lt period gt lt width gt nim_setpulse period width polarity Sets Pulse Generator values in decimal period 1 1023 lt polarity gt width 1 7 polarity O or 1 nim_getpulse nim_getpulse Returns Pulse Generator settings nim_pulseoff nim_pulseoff Returns Pulse Generator settings nim_setcthr lt which gt lt value gt nim_setcthr which value Sets threshold value for COMBO section lt which gt 1 or 2 nim_getcthr lt which gt nim_getcthr which Returns current threshold value for COMBO section lt which gt 1 or 2 nim_getcdtc lt which gt nim_getcdtc which Returns current COMBO Dead Time Counter value lt which gt 1 2 nim_cack lt which gt nim_cack which Resets COMBO input lt which gt 1 or 2 nim_getcev lt which gt nim_ge tcev which Returns current COMBO Event Counter value lt which gt 1 2 nim_resetcev lt which gt nim_resetcev which Reset specified COMBO Event Counter lt which gt 1 or 2 nim_resetcombo lt which gt nim_resetcombo wh
26. ice Proof of purchase may be required ZP Engineering srl accepts originals photocopies and faxes as proof of purchase when required Unauthorized repairs to a ZP Engineering board level product will void the warranty offered by ZP Engineering srl ZP Engineering srl reserves the right to refuse to service any product that has been altered modified or repaired by non ZP service personnel Standard warranty service consists of repair upon receipt You are responsible for the cost of shipping the product to ZP ZP pays the cost of returning a product to you ZP Engineering srl reserves the right to replace the product with a service product at their sole discretion at any time This warranty does not apply to the software component of a product Components and schematics are property of ZP Engineering srl and are not available to end users SOFTWARE Software included in the unit has been carefully tested but is supplied as is with no warranty covering detailed performance Critical problems are covered by a software warranty for a period of 3 three months from the date of shipment Within this period software upgrades will be provided software upgrades will be performed by the customer using the available tools DOCUMENTATION The documentation included with the unit represents the latest version document and is continually refined end edited Please refer to the support web site at www zpeng c
27. ich Resets specified COMBO section lt which gt 1 or 2 nim_waitcombo ch Wait for COMBO interrupt it returns only when COMBO is busy blocking call ch 1 2 or 3 both nim_waitdtc ch Wait for DTC interrupt it returns only when DTC has crossed the threshold blocking call ch 1 2 or 3 both nim_testcombo lt ch gt nim_testcombo ch Test COMBO interrupt it immediately returns current values 1 if COMBO busy 0 otherwise ch 1 2 or 3 both nim_testdtc lt ch gt nim_testdtc ch ZP ENGINEERING srl J ENET User s Manual v 1 0 2 Test DTC interrupt it immediately returns current value 1 if DTC has crossed the threshold O otherwise ch 1 2 or 3 both 26 28 JENET Ethernet based CAMAC controller TCP control socket Lua Description Control socket only commands cname lt id gt Optional command it passes to Jenet an string identifier of local client socket lua_setfile lt data gt Lua related command enables direct transfer of script file lua_store Lua related command stores transferred filew into non volatile memory lua_getfile Lua related command enables direct retrieval of script file lua_getrun Lua related command returns Lua RUN flag lua_setrun lt value gt Lua related command sets Lua RUN flag lua_geterr Lua related command returns last Lua error message
28. ion is detected front panel LED status lights up it will remain on until there are active connection to the socket server the server accepts commands from the remote client see section Commands Reference return string is always in the following format 1 Command exists but parameter format or number is wrong 2 Command does not exist O lt return value gt Command returns correctly the return value it may also be null note that more than one remote client can connect to the socket server it is up to the programmer to avoid conflicts when accessing the same resources as there is no built in protection for access conflicts in other words stick to one remote client only unless you really know what your are doing Multi client usage is useful especially during development and debug The socket server NEVER generates data autonomously in the special case when Jenet needs to communicate to the host that a specific event has occurred analogously to an interrupt request it works through a separate communication channel IRQ like messages is handled in the following way a TCP socket server is opened on the host at a specified port N On Jenet a TCP socket client is launched and connects to the IRQ socket server on host port number N is passed with a dedicated message The host must wait for data on the IRQ socket server and act accordingly In the following diagram a typical scenario with 3 separate
29. ipt text from specified file on host to J enet jsm ip lt IP addr gt run starts execution of current script jsm ip lt IP addr gt stop halts execution of current script jsm ip lt IP addr gt s stores current script on non volatile memory for Run on Boot option jsm ip lt IP addr gt rob lt value gt sets rob Run on Boot flag to specified value 0 or 1 jsm ip lt IP addr gt d lt filename ext gt downloads script text from Jenet to specified file on host jsm ip lt IP addr gt d stdout downloads script text from Jenet to stdout on host jsm ip lt IP addr gt e lt filename ext gt stores error message if any from Jenet to specified file on host jsm ip lt IP addr gt e stdout stores error message if any from Jenet to stdout on host jsm ip lt IP addr gt I lt filename ext gt stores log message if any from Jenet to specified file on host jsm ip lt IP addr gt stdout stores log message if any from Jenet to stdout on host The jsm application is available in both source and compiled form on the documentation section of the Jenet web site www zpeng com jenet it uses dedicated commands to transfer files Please check periodically for updates 7 2 4 Scripting on J enet A few usage examples follow Script usage examples In certain cases it may be safe to initialize inserted CAMAC target cards as soon as possible after power up With ROB 1 the FLASH script performs the required initialization
30. ites Tools Help Address E http 192 168 0 93 Y Go Ar Jenet CAMAC CRATE CONTROLLER VAZP Engineering Home Commands NIM I O Configurations Diagnostics User System Network Parameters MAC address 00 50 C2 26 E0 0D aa System Identification serial number 00000100 firmware version 1 0 Jan 16 2004 FPGA version 02 03 30 12 2003 This is a read only page that displays relevant network settings and local ID details please always check that your documentation is referring to the same firmware version release date is NOT relevant The MAC address is a read only property that cannot be changed in any way it may be useful in certain network environments the local IP address subnet mask default gateway and DHCP enable flag can be modified from the serial port console see Serial Port Control section or form the control socket take into account that these settings are effective only after rebooting If DHCP 1 then the local DHCP client is enabled Please refer to your system administrator for additional information relevant to these settings Note that wrong or conflicting IP address settings are the most typical issue that creates connection problem when first using the system Before connecting a board with static IP DHCP 0 you can perform an additional check by issuing a PING command to verify that the IP address on the unit is really available If another system is answering at the same address you may experienc
31. n j A nim_getin B nim_getins j Basic reading of input values 3 1 2 3 4 Set event counter on IN 3 t o falling edge TCP socket commands Lua code snippet nim_setievent 3 1 1 0 nim_setievcnt 3 1 1 0 Enable async reset for counter on IN 1 TCP socket commands Lua code snippet nim_setievent 11 1 0 a b c nim_getievcnt 1 nim_setievcnt 1 a b 1 ZP ENGINEERING srl JENET User s Manual v 1 0 2 21 28 JENET Ethernet based CAMAC controller 9 3 Outputs The OUTPUT subsection implements four independent NIM output that can be independently set and reset in addition a programmable pulse generator that can be enabled on the first output PULSE GENERATOR Period 186 2 us to 95325 2 us in 93 1 us steps 10791 Hz base clock Width 88 ns to 616 ns HI Direct LO Output polarity H Reverse LO Please note that duty cycle is never higher than 0 05 with reversed polarity flag disabled therefore it may be difficult in certain cases to see the pattern on a scope EXAMPLES Write to outputs Notes TCP socket commands Lua code snippet Basic output control nim_setout 1 1 1 1 nim_setout 1 1 1 1 out 1 2 3 4 nim_setouts lt out gt lt val gt nim_setouts 2 0 val 0 1 Set pulse generator to 1 ms period 440 ns width TCP socket commands Lua code snippet 11 93 1 1 024 ms nim_
32. ns an essential feature for any embedded system As an example the CLMR Camac function returns the current LAM mask and a binary AND operator is almost mandatory to allow individual bit testing The following additional functions are provided all with two operands and one result function Description C equivalent band a b 32 bit binary AND a amp b bor 32 bit binary OR a b bxor 32 bit binary XOR exclusive OR a b bmod binary module a b bsl binary shift left a lt lt b bsr binary shift right a gt gt b 7 2 2 Socket commands for Lua control A subset of control socket commands is dedicated to management of the local Lua interpreter engine these commands are used by the jsm application Jenet Script Manager see below Note that these socket commands are the only messages to violate the principle to have one command per line The following commands are available lua setfile It transfers a script from host to Jenet the file is placed in RAM and can be saved on FLASH with the z lua_store command The following procedure is required e host sends to control socket the following command lua_setfile lt filesize gt where lt filesize gt is expressed in bytes e control sockets answers with OK e host sends the file directly e control socket answers with OK lua_getfile It transfers a script from Jenet to host the following procedure is required e host sends to control socket
33. om jenet for the latest version ZP ENGINEERING srl JENET User s Manual v 1 0 2 4 28 JENET Ethernet based CAMAC controller 1 2 System overview JENET is a complete CAMAC controller that allows advanced interaction by means of standard Ethernet services such as a local web server and TCP socket based communication protocol The basic hardware architecture of J ENET is illustrated below CAMAC bus CAMAC LAN 10 100 bus Front panel control ae Front panel serial port RISC PROCESSOR uClinux OS 4NIM in NIM input output control 4NIM out Voltage CRATE power monitoring supplies COMBO 2 A local processor runs a version of Linux optimized for low memory footprint a CAMAC bus control subsection handles all bus access operations and interactions and a separate NIM subsection manages I O signals located on the front panel 1 3 Summary of features CAMAC Full CAMAC bus control including LAM detection bus access Plugs into slots 24 and 25 4 outputs 4 inputs event counters 2 COMBO 1 0 trigger busy modules programmable pulse generators input event counters NIM default settings can be reloaded with front panel button Local NIMI O Section Remote ANSI C remote control library derived from the ESONE standard with Control Library Local Web Server Advanced Scripting Engine Front Panel Indicators extensions to control local resources Remote control of
34. plication its main usage is for automated crate initialization and for unattended control Crate Scan is a function available on Jenet to allow automatic detection of cards inserted into the crate It is a quick way of verifying the presence of cards that may be required by the acquisition code either within the Lua script or on the host application Being a heuristic approach to card detection there is no formal way of detecting a card when inserted into the crate the Crate Scan function may interfere with specific CAMAC cards it is thus possible to disable the Crate Scan function Note that Crate Scan is executed only at startup in order to avoid possible interaction with ongoing script or actions from host if the feature is disabled it will not be possible even from socket Note ZP ENGINEERING srl JENET User s Manual v 1 0 2 JENET Ethernet based CAMAC controller A description in pseudo code of the Crate Scan function follows for slot 1 slot lt 23 slot end_slot 0 for fun 0 fun lt sizeof SCAN_FUNCTION fun for addr 0 addr lt 32 addr X CSSA slot SCAN_FUNCTION fun addr 0 if X 1 slot_status slot 1 end_slot 1 if end_slot slot_status slot 0 where SCAN_FUNCTION is the following array O Ls 2 3 8 9y TO Til 24 257 26 27 16 17 T8 19 4 2 Jumper settings It is possible to force some startup options by pl
35. s JNT01 gt rw all_squash to the etc exports file on the computer where disk is located Firmware upgrade limited to the application bank is performed using a telnet connection to the unit as follows copy the new binary file on a known location on a network disk establish a telnet connection on default port 23 please note that depending on fw version it may be possible that the internal telnet server must be enabled by means of HW jumpers of course you must know the unit IP address type the following commands cd www sh flash lt nfs_directory gt lt jffs2 filename gt and wait until reprogramming completes reboot the unit either by pressing the RESET button on the front panel or by turning crate power off and on again An example of a typical fw upgrade command line is the following sh flash 192 168 0 91 home wet bootdir jffs2 img 9 NIM subsection Please note that on the present document the following notation is used for NIM signals LO No current flowing into load HI Current flowing into load corresponding to a 0 8 V voltage level across a 50 ohm load This notation is maintained also on the NIM I O web page A command parameter equal to 1 means HI 9 1 Default button A DEFAULT pushbutton located on the front panel above the reset section allows immediate manual reload of a default configuration for the NIM I O subsection thus allowing a quick reconfi
36. setpulse 11 5 0 nim_setpulse 11 5 0 5 88 440 ns Turn pulse generator off and activate outputs 1 3 TCP socket commands Lua code snippet nim_pulseoff nim_pulseoff nim_setouts 1 1 nim_setouts 1 1 nim_setouts 3 1 nim_setouts 3 1 ZP ENGINEERING srl JENET User s Manual v 1 0 2 JENET Ethernet based CAMAC controller 9 4 COMBO I O The COMBO I O subsection implements a commonly requested Trigger Busy functional block The diagram below details one of the two COMBO subsections TRIG in Q BUSY out front panel LED RESET RESET DTC COUNT ENABLE 10 791 kHz o DEAD TIME COUNTER INTERRUPT REQUEST gt EVENT COUNTER RESET EVC Whenever a LO to HI transition occurs on the TRIG input an internal Flip Flop is set to capture the event the Flip Flop output is connected to the BUSY output and its associated LED The Dead Time Counter starts counting at a 10 791 kHz rate and it is reset when the software application resets the Flip Flop therefore the Dead Time Counter provides an indication of the service time of the TRIG input It is automatically reset when BUSY is reset therefore it must be read before the BUSY reset command An independent Event Counter is incremented at each LO to HI transition of the BUSY output providing an indication of the number of pulses The Event Counter can be reset by means of an explicit command through control socket or from the NIM I O web page Please note
37. st of commands on terminal setip lt new IP addr gt sets a new IP address to be written in the format aaa bbb ccc ddd setmask lt new mask gt sets anew IP mask setgw lt new gw addr gt sets a new gateway IP address setdhcp lt 0 1 gt if set to 1 enables the local DHCP client getip getmask Allows retrieval of current network settings getgw getdhcp setrob lt 0 1 gt if set to 1 enables the Lua Run On Boot option setcscan lt 0 1 gt if set to 1 enables the Crate Scan function executed at startup only aea Allows retrieval of current startup settings Lua Run On Boot and Crate Scan The front panel connector requires a straight serial cable pin 2 to pin 2 pin 3 to pin 3 only RX and TX are required 4 Startup options Jenet startup options can be tuned in order to provide a fine control over performance and connectivity There are some settings stored in nonvolatile memory that can be changed with the control socket or from the serial port and some options that require placement or removal of jumpers inside the unit 4 1 Startup flags Two flags are available for startup fine tuning Lua script Run On Boot flag Crate Scan Enable flag Both are stored in the local EEPROM and can be modified with dedicated commands on the serial port getrob setrob getcscan setcscan or from the control socket The Lua Run On Boot flag when enabled tells the system to run the stored Lua script after starting up the ap
38. the following command lua_getfile e control sockets answers with lt filesize gt expressed in bytes e host sends OK e control socket sends the file directly lua store It saves the current script on FLASH lua_getrun It returns the current execution state of the script interpreter lua setrun It changes the executionstate lua_setrun lt value gt where 1 run O stop lua_geterr It returns the error message if any returned by the script interpreter being a multi line string it follows the same protocol of lua_getfile lua_getlog It returns the stdout log file returned by the script interpreter it s useful as a debugging aid as print messages are sent to the log Being a multi line output it follows the same protocol of lua_getfile WARNING using print on Lua may crash the system if the log file gets too long Please use it only for debug ZP ENGINEERING srl JENET User s Manual v 1 0 2 JENET Ethernet based CAMAC controller 7 2 3 Jenet Script Manager jsm It is a dedicated application available for Windows and Linux that allows full control over all operations related to script management all operations are specified with command line parameters The following syntax is implemented version 1 0 jsm h displays program version and a list of allowed parameters jsm ip lt IP addr gt u lt filename ext gt uploads scr

Download Pdf Manuals

image

Related Search

Related Contents

User Manual - Datamax  CATALOGUE IKI VOICE  Lenovo ThinkServer RD640  Manuel d`utilisation - Günther Heisskanaltechnik  ADPRO® FastTrace 2 FastTrace 2E by Xtralis  Manual MultiMax 6ds  WA470・7 - コマツ建機販売  lrm 1200 / lrm 1500 lrm 1500spd laser range finder    Harley Davidson Tech. 1 - Motorcycle Mechanics Institute course notes  