Home
FlowFinder MK
Contents
1. To switch off the FlowFinder mk2 press the button on the left side of the display The display will turn black for a moment and will then show an infor mation screen displaying among other info the serial number the software version and the last calibration date This screen can also be found through the touch screen under Options Information 16 STORING THE FLOWFINDER MK2 1 Place the hood 230x230x145mm upside down over the top of the FlowFinder mk2 2 Place the FlowFinder mk2 in the transport case with the display facing up Take care the display is not tilted but laying horizontally 3 Behind the elastics in the lid paperwork can be stored If any resistance is felt when closing the lid of the case don t push but try to remove the cause 5 When the FlowFinder mk2 will not be used for a longer period of time the battery pack has to be removed It can be stored in the bottom of the transport case 6 Consequently when the FF hasn t been used for several weeks the battery has to be charged fully before using 17 CALIBRATION We recommend to have the FlowFinder mk2 calibrated once every year Please contact us or your distributor to arrange 12 manual 19 11 2013 acin instrumenten bv 18 NOTES Model FlowFinder mk2 DATE Serial no housing Serial no battery pack Delivered to Contact person Department Address Zip code eoeeceeeeee eee eee eee eee eee eee eee co eee eee eee eee eee
2. 77 13 8 C 73 0 m3 u 13 05 2013 08 18 A conkamer 1 14 1 C 71 1 m3 u 13 05 2013 08 19 9 Select as separator and Continue 10 The data are now ready for further processing and reporting In dit venster kunt u voor elke kolom het gegevenstype instellen Standaard os De optie Standaard converteert numerieke waarden naar getallen datumwaarden naar Tekst datums en alle overige waarden naar tekst paum Kolom overslaan bij importeren 2 Badkamer 77 13 8 C 73 0 m3 u 13 5 2013 8 18 3 Woonkamer 1 141 C 71 1 m3 u 13 5 2013 8 19 19 11 2013 manual 11 acin instrumenten bv 13 NAMING THE DATA STORAGE LABELS 1 Connect de microSD card using the USB or SD adapter with picts Range your computer a Eg ER EEE DEE T E 2 Open the file names txt with a text editor like WordPad This file should already be on the micro SD card rad 3 The labels for the buttons are listed where each label is given in Reuken Slaapkamer square brackets like kitchen da 4 All these identifiers can be edited to your wish so project Gang name apartment type room grill type dann 5 IMPORTANT take care always to use these brackets around the labels For instance kitchen 6 Save the file to the microSD card overwriting the old file 14 EMERGENCY STOP If for any reason it is needed to interrupt the measurement just press the red button shortly 15 SWITCHING OFF OF THE FLOWFINDER MK2
3. MODE 6 6 DEFAULT SETTINGS 6 7 USING THE HOODS 7 8 MEASURING WITH THE FLOWFINDER MK2 8 9 ADDING OF MEASUREMENTS 9 10 STORING THE DATA 9 11 PROCESSING THE STORED DATA 10 12 PROCESSING THE DATA IN EXCEL 11 13 NAMING THE DATA STORAGE LABELS 12 14 EMERGENCY STOP 12 15 SWITCHING OFF OF THE FLOWFINDER MK2 12 16 STORING THE FLOWFINDER MK2 12 17 CALIBRATION 12 18 NOTES 13 g Despite the fact that this manual has been carefully put together by ACIN instrumenten bv no responsibility is accepted for any errors in the manual and possible consequences We are obviously very interested in your comments and additions No part of this publication may be reproduced and or published by print photocopy microfilm or any other method without prior written permission of ACIN instrumenten bv 19 11 2013 manual 3 1 PARTS OF THE FLOWFINDER 1 FlowFinder mk2 with display Use the packing list to verify all 2 Transport case with key elements of the FlowFinder mk2 are 3 Battery pack mounted onto the present Avoid lifting the FlowFinder mk2 FlowFinder mk2 or stored in the case while holding onto a hood 4 Battery charger 5 Hood 230x230x145mm C O ASS E 6 Hood 600x600mm optional 6 7 MicroSD card USB adapter SD adapter i FlowFinder made in Holland 4 2 SPECIFICATIONS OF THE FLOWFINDER MK2 SPECIFICATIONS Air flow range supply and exhaust 10 550 m uur with zero pressure
4. compensation 551 850 m uur with calculated compensation Air temperature range 20 80 C Uncertainty 20 C 3 of the reading with a minimum of 3 mY hr Repeatability better than 1 with a minimum of 3 mY hr Resolution 1 m hr 0 1cfm 0 11 s RV range 0 100 Full charge capacity 8 hours Weight 2230 gram battery pack included Dimensions FlowFinder 260 x 350mm Uncertainty is defined as the square root of the sum of the squares of non lineairity hysteresis and repeatability 4 manual 19 11 2013 acin instrumenten bv 3 REMOVING AND CHARGING OF THE BATTERY PACK The battery pack has to be removed from the FlowFinder mk2 before the charger can be connected While charging the colour of the LED indicates the status yellow no battery pack connected green trickle charging orange fast charging orange green ERROR green yellow top of charging The battery pack has to be removed from the FlowFinder mk2 before the charger can be connected While charging the colour of the LED indicates the status 4 SWITCHING ON OF THE FLOWFINDER MK2 ENS Bo 00 Pa T 242C RH 53 There are two measuring modes Validate and Adjust In validate mode the FF decides when it is ready with a measurement The measured value will be displayed only when the FF is ready In adjust mode after pushing the red button a measured value is displayed continuously One can then adjust the ventilat
5. Finder mk2 has two measuring modes The so called validation mode and the adjustment mode In the options menu one of these modes can be set as default At start up the FF mk2 will be ready to measure in the default mode The measuring mode can be recognized by the red blinking 0 adjustment mode or the validation mode In validation mode the FF mk2 a measurement starts by pushing the red button behind the left knob The FF mk2 decides when the measurement is ready normally within 10 to 15 seconds It will display the measurement result which then can be stored by touching store In adjustment mode the FF mk2 a measurement starts by pushing the red button The blinking number turns green and will change depending on the air flow volume The measurement will only stop after the red button is pushed again This way you can adjust the diffuser or valve to the desired air flow You may take down the FF mk2 to adjust the valve Wait long enough until a more or less stable reading is reached also after placing the FF mk2 back again Always stop and start again when going from one measuring location to another The measuring result can t be stored Switching between modes push the return button in the right upper corner Then you can select either validate or adjust To change the default mode you have to go to the options menu To do a measurement hold the FlowFinder mk2 by the left
6. FlowFinder made in holland VALIDATING AND ADJUSTING VENTILATION SYSTEMS MANUAL The FlowFinder mk2 is the successor of the well known FlowFinder 153 which has proven itself as the benchmark for air flow measurements to balance mechanical air supply and exhaust systems The new FlowFinder mk2 is fully zero pressure compensated in the range 10 to 550 m m hr 6 to 323cfm and has a calculated compensation for its resistance up to 850 m hr 500cfm Large range 10 to 850 m hr or 6 to Ventilation systems also with low terminal 500cfm supply and exhaust resistance Light and easy to handle Small air volumes Short measuring cycle Heat exchange units With full battery 8 hours of Natural ventilation measurement at flows lt 100m hr Line and large diffusers with optional hoods or High accuracy by adding measurements Standard equipment Options Battery charger Foldable hood 600 x 600mm Transport case Non foldable hood 400 x 400mm User manual Extra battery pack Calibration certificate traceable to primary standards MicroSD card with USB and SD adapter Rijswijk Look at for more information tel 31 70 3070703 fax 31 70 3070938 email www acin nl web www acin nl KH acin instrumenten bv CONTENTS PARTS OF THE FLOWFINDER MK2 Al 2 SPECIFICATIONS OF THE FLOWFINDER MK2 4 3 REMOVING AND CHARGING OF THE BATTERY PACK 5 4 SWITCHING ON OF THE FLOWFINDER MK2 5 5 THE DISPLAY IN MEASURING
7. and right round handles and place the instrument over the outlet or inlet you want to measure Make sure to make a tight connection by pushing enough to avoid measuring secondary air Press the red button behind the left knob shortly in order to start the measurement In validation mode the text compensating pressure will appear after a few seconds followed by mea suring Also an arrow will appear on the bottom of the display indicating the direction of the flow After approximately 10 seconds the result of the measurement will appear expressed in l s m u of CFM In adjustment mode the colour of the blinking number will turn green and change until it reaches the air flow amount As a consequence of variations in the ventilation system itself and to lower the total uncertainty we advise to repeat the measurement 2 or 3 times shortly after each other A new measurement can be started by pressing the red button Best is to wait until the ventilator in the FF has come to a rest at low flows or runs at its non zero pressure compensated speed as dictated by the flow manual 19 11 2013 acin instrumenten bv 9 ADDING OF MEASUREMENTS Thanks to the zero pressure compensation of the FlowFinder mk2 it is possible to measure the air flow at part of the diffuser Because the FlowFinder mk2 actively compensates its own resistance the flow through the other free part of the diffuser will not or hardly be influenced As a
8. e np e eee ese eee ese see eeeeeeeeeeeeeeeeeeeeeeee eee ee eeeeeeeeeee eee eee eee eee eee Country Telephone eee ee eee eee eee ee eee ee eee eee eee eee eee eee eee eee eee ne eee eee eee non eee eee eee eee eee eee ee ee eee eee eee eee eee nene np ne e ee eee Email Last calibration Initials Remarks Next calibration 19 11 2013 manual 13
9. en met Windows ReadyBoost 6 Now you should see a list of text files with the name format yyyymmdd year month day The file names txt will be discussed further down Afdrukken Branden Nieuwe map Gewijzigd op Type Tekstdocument Tekstdocument 5 4 2013 8 46 Tekstdocument 7 An example of the data format is given below Badkamer 77 13 8 0 73 0 m3u 13 05 2013 08 18 woonkamer 1 414 1 C 71 41 m3 u 13 05 2013 08 19 10 manual 19 11 2013 acin instrumenten bv 12 PROCESSING THE DATA IN EXCEL Turn off the FF mk2 Remove the micro SD card by pushing on it and then releasing it Either the SD adapter or the USB adapter can be used to connect to your computer When inserted a screen Automatic will pop up Ignore this screen or click cancel Open Excel Select Data From text The Wizard Import text will be activated Select the data file and next N A dk A Het volgende gegevenstype is geconstateerd Gescheiden Als dit juist is kiest u Volgende of kiest u het gegevenstype dat het beste overeenkomt met de gegevens Oorspronkelijk gegevenstype Kies het bestandstype dat het beste overeenkomt met de gegevens Gescheiden Tekens zoals puntkomma s of tabs vormen de scheidingstekens tussen de velden Vaste breedte Velden worden uitgelijnd in kolommen met spaties tussen de velden Importeren siaren bi ri ooren MSDS PDE Voorbeeld van bestand D 20130513 TXT Badkamer
10. ion system while measuring Important When the FlowFinder mk2 is stored away for a longer period of time one should store the battery pack separately after having it charged first Extra battery packs can be ordered from ACIN 19 11 2013 manual 5 acin instrumenten 5 THE DISPLAY IN MEASURING mn JM Flow inder Start Meru M28 02 05 MODE RD The display in measuring mode shows a number of parameters time date USB connected yes no status battery pack pressure difference AP in Pascal to be compensated temperature in C of F relative humidity RH in 8 measured flow in l s m u of CFM ae ha Below the unit of flow is a bar that during a measurement will fill up in green the length of the green bar is proportional to the airflow When the FlowFinder mk2 is in rest and in measuring mode you will find below this bar a 1 blinking O this means that the FF has been set to adjust 2 E this means that the FF has been set to validate On the sides of the display there are a slot for a micro SD card a mini USB port and a programming cable At this moment the SD card and the USB port cannot be used yet 6 DEFAULT SETTINGS Press the white arrow in the right upper corner of the starting screen to go to Start Menu Choose Options This screen allows for the settings to be changed Once you are ready these settings will be stored as the default settings Choose language Nederla
11. n example the flow through a line diffuser can be measured by moving the FF across the diffuser evenly after every measurement and adding each measured value 10 STORING THE DATA 1 Execute a measurement in Validate 5 Select one of the options and a mode as described in chapter 8 numerical keypad will show 2 After the measurement is ready the re 6 Here you can add a 4 digit numerical sult will appear together with a button identifier to the record of this measure Store ment This number can be a house number or some num ber from a plan or some clever combi 08 19 13 05 2013 USB lt 0 nation You are free to dP 0 0 Pa design your own data id system 3 Touch Store 4 Now a screen with 8 buttons will show The text in the buttons can be defined by the user 7 After touching ok the display will re turn to the measuring mode 08 17 13 05 2013 USB SD CB dP 0 0 Pa 1119 00 RH 76 19 11 2013 manual 9 acin instrumenten bv 11 PROCESSING THE STORED DATA 1 Turn off the FF mk2 2 Remove the micro SD card by pushing on it and then releasing it 3 Either the SD adapter or the USB adapter can be used to connect to your computer 4 After inserting the card a screen Automatic will pop up 5 Select Show maps and files SD SD Card D Opties Algemeen met Windows Verkenner was voor back ups gebruiken met Windows Back up De computer versnell
12. nds or English Choose Units Choose the unit of temperature Celcius or Fahrenheit Choose the unit for flow l s mu or CFM oS i 6 manual 19 11 2013 acin instrumenten bv Leave this menu by pressing the white arrow again The Options menu appears again 5 Choose Validate or Adjust as default start up measurement of the FlowFinder mk29 6 Set the Date 7 Set the Time 6 1 Press date 7 1 Press time 6 2 Enter the year yyyy 7 2 Enter the hour 0 tot 23 6 3 OK 1 3 OK 6 4 Enter the month mm 7 4 Enter the minutes 6 5 OK 1 5 OK 6 6 Enter the day dd 6 7 OK Leave the Options menu by pressing the white return arrow The Start Menu appears From the Start Menu the FlowFinder mk2 will go into measuring mode by touching validate or adjust 7 USING THE STRAIGHT HOOD 230X230X145mm AND THE HOOD 600X600mm Preferably the FlowFinder mk2 is used with at least the straight hood certainly for most supply grilles If space is limited certainly exhaust can be measured without a hood The straight hood is placed on top of the housing and is hold in place by pulling the O rings over the little black knobs The same procedure can be used to mount the 600x600mm foldable hood For flows above 50CFM it is assumed that the 600x600mm hood is used Avoid lifting the FlowFinder mk2 just using the hoods 19 11 2013 manual 7 acin instrumenten bv 8 MEASURING WITH THE FLOWFINDER MK2 The Flow
Download Pdf Manuals
Related Search
Related Contents
Music in Paris - Visit Paris Region PROZAC - Psychaanalyse ES-S6A - eTIGER Emerson Y690A Instruction Manual Life Fitness Cardio Series 90 User's Manual 取扱説明書 NI-CL602 NI ventilador gemelo BW2300 Primor 2060M, 3570M & 5570M ADPC240x 2400 User manual R2V3.indd User guide Copyright © All rights reserved.