Home
        UTA Manual (ver. 2a)
         Contents
1.    0 056     1 25 volts     51 42 klux per volt    64 3 klux    Values in the box above are typical for full sun readings  Those will be fine for many purposes  But for low light conditions  or for use with other sensors  you may wish to set a different gain  The switch settings inside the UTA can be manipulated  with reference to the chart on page 6  There are a couple of guidelines for choosing the gain of stage 1 and stage 2  For the  HOBO  the gain of stage 2 should be x2 or greater   S2 setting 14 or less  not 15   Within that constraint  it is best to use the  highest gain possible on stage 1  switch S1     Note  There is a 4 5 millisecond pause between the wake up and the first measurement  Subsequently  it takes up to four    measurements spaced 14 5 millisecond apart  then the power supply turns off and the HOBO goes back to sleep  It may be  best to connect the UTA HOBO to one of the later HOBO channels to allow more time for warm up     ver 2A   2007 EME Systems  2229 Fifth St   Berkeley CA 94710   510  848 5725  fax   510  848 5748  www emesys com 15    
2.   7 0  0 12 3 15   6 14   7 13   9 11   10 10   12 7   13 6   14 3 p  4 5   5 4  0 128 11 8 2 1 2 6   6 2  0 14 2 15   8 11   10 9   14 2 2 4 1 6   3 5   6 1   5 3  0 144 9 10 2 5 4 4  0 16 1 15   5 14  7 12   10 8   11 7   13 5   14 1 2 7 0 6   6 0  0 168 8 10   9 9 2 8 2 5   5 2  0 18 0 15   6 13   12 6   14 0 3 3 4  43  0 192 9 8 3 2 1 5 5 1  0 196 8 9 3 5 2 4   4 2  0 2 4 14   7 11   10 7   13 4 3 6 0 5   3 3   5 0  0 224 8 8 4 1 4 4 1  0 24 3 14   5 13   6 12   7 10   9 7   11 6   12 5   13 3 42 2 3   3 2  0 28 2 14   7 9   8 7   13 2 4 5 0 4   4 0  0 3 4 13   6 11   10 6   12 4 4 8 1 3   3 1  0 32 1 14   5 12   7 8   11 5 4 9 2 2  0 36 0 14   3 13   6 10   9 6 5 4 0 3   3 0  0 4 4 12   5 11   7 7   10 5   11 4 5 6 1 2   2 1  0 42 2 13   6 9   8 6   12 2 6 3 0 2   2 0  0 48 1 13   3 12   5 10   6 8   9 5   11 3   12 1 6 4 1 1  0 5 4 11   10 4 12 0 1   1 0  0 54 0 13   12 0 8 1 0 0  0 56 2 12   5 9   8 5   11 2  On  x dE P  q D  S1i3 mi  44 E p    Figure 2  Location of Switch 1  S1  and Switch 2  S2  on the UTA circuit board  See          Figure 3 for switch setting information     ver 2A   2007 EME Systems  2229 Fifth St   Berkeley CA 94710   510  848 5725  fax   510  848 5748  www emesys com                                                                                                                                                                                                                             Figure 3a  Settings for Switch 1  S1   d  Glob d   Glob d  Eob 
3.   Check for evidence of water entry into the cabinet  In regions of extreme humidity or precipitation it may be wise to  place a dessicant  such as silica gel  inside the UTA   s cabinet     2  Amplifier seems to be responding to light  but the output seems too low or too high    Things to check   2a  Be sure you are using the correct multiplier in your calculations  Refer to Table 2  and the switch block positions in the  box  The version of the UTA number should be printed on the top label or on the calibration label  Be sure the UTA version  matches with the version of the instruction manual   2b  Place sensor in full unobstructed sunlight  you should see a significant increase in output voltage  Indoor lighting is much   much weaker than full sunlight  The standard amplification factors are designed to accommodate full tropical sunlight condi   tions  If you will be using your sensor in generally low light conditions  say indoors  in the arctic  under a plant canopy  or in  deep water  LI 192 or LI 193   you may wish to select a higher output voltage setting to bring the signal into the dynamic  range of your data logger  Please consult the LI COR literature and references  or contact EME Systems for assistance   2c  The power supply must be at least 2 volts greater than the desired full scale output voltage  except the UTA HOBO ver   sion  which operates rail to rail      3  The amplifier output is unstable and readings fluctuate too much under constant lighting conditio
4.  OO1O 1010 OLLO LLO OOO  LOOL OLOL LOL OOLL LOLL OLLE JILL    LL ras eL YL    suonisod  Z YOUMS    O    Ge oz SL OL 8 7A 9 S v     Z L R    suoljyisod  L YOUMS    JOA SI OA Cp   URS SUIAIS    0000 UONIsod Yo IMs 0   JJOA S OA     UlS SUIAIS    T    uonsod yoyms woy     33s IOIfI dure puodds 107 suonrsod yams opts doy      V1 S JOA QT  Q UILS SUTATS    0000 UONTsod Yyo IMs 0   VU SIOA p000 US SUIAIS    QT TT UoTsod yoyms Wo     3gs Idur ISM  OY  107 UOTISOd YAMS    opts YOT   SOSBdIDOP JOQUINU UOMISOd YYIMS SE SOSedIOUI UIeS Y  9 0U  UO YOUMS      o YOUMS      9721S JOIFI due puoses pue sxy 10  suowisod yoyms Iq  d0  pue yo    V SIOA   8 0  W1 S  OA p000 Wo osuer    duwor Jad s  OA se passoidxa sues YLA     19A0  9 1qe1 Jo Apog     UoT ISOd YOIMS JO UOTOUNY V sv URN      BIquyL    ver 2A   2007 EME Systems  2229 Fifth St   Berkeley CA 94710   510  848 5725  fax   510  848 5748  www emesys com    Recalibrate the UTA    The switches in the UTA select many possible values for the transconductance gain  The gains are set by precision 0 1   accuracy metal film resistors  The diagram below shows the location of the gain adjustment trimmer  This trimmer can be  adjusted to achieve the best possible gain on one particular switch setting  The gain at other switch settings should then fall  within 0 3  of the correct value  but may not be as good as the switch position that has been trimmed     The timmer can be adjusted as follows  Use a precision current sink as the input signal for t
5.  SZ model LI COR  sensor  while the    UTA   HOBO BNC    is for use with the SA model LI COR sensors which have BNC connectors  It should  be noted that BNC connectors are not waterproof  and should be used only in areas that are sheltered from water exposure   For best water resistance  use the SZ model LI COR sensors Additionally  both the UTA   HOBO and UTA    HOBO BNC are  available with a high precision  high gain setting for use in low light level conditions  e g  indoor lighting studies  or nD    water studies using the LI 192 or LI 193   Please specify either UTA   H   OBO HG or UTA   HOBO BNC HG for the high gain option     The HOBO power supply is a small 3V lithium battery  but despite its small  size  it is capable of operation for long periods of time between battery chang   es  Most of the time  the HOBO is in a sleep mode wherein it requires little  power  At a specific time interval  which you determine when you launch the  HOBO   the data logger wakes up  turns on the external power supply  red  wire on the HOBO volt cable   and records the data coming in from the sen   sors  The UTA is powered from the 2 5 volts provided by the HOBO during  the measurement interval  The UTA draws about the same current  125 uam   ps  as the Onset thermistor temperature probe  so the UTA   HOBO does not  compromise the HOBO battery life  In the UTA    HOBO  some components  of the base model UTA have been replaced in order to meet the special low  voltage  low current  and hi
6.  amps for special  purposes  low light levels  special supply voltages or micro power  high speed operation  dual output  Some special options my  also entail changes to gain or compensation components   Standard gain op amp    LT1490I  220u Vos  4nalb  200khz GBP  r r i o  2V   44V  100ua power  PSRR 98db   LT1078I1  70uVos  6na Ib  200khz GBP  output to Vd 0 8V  5V   44V 100ua power  PSRR 114db  Low offset high gain highest accuracy CAZ op amp    LTC1051  1pVos  15pa Ib  2 5mhz GBP  output to Vd 1 5V  5V 16V 2ma power  PSRR 140db   LTC2055HV  Similar to the LTC1051  but operates on lower power supply voltage and current   Higher speed    TLV2462  500uVos  1na Ib  6 4mhz GBP  r r i o  2 7V   5 5V  Ima power  PSRR 95db    LTC6241  125uVos  1pA Ib  18mhz GBP  r ro  2 8V 11V  3ma power  PSRR 104dB  low noise CMOS     ver 2A   2007 EME Systems  2229 Fifth St   Berkeley CA 94710   510  848 5725  fax   510  848 5748  www emesys com 12    Appendix  UTA HOBO    The UTA   HOBO is designed as a precision interface between LI COR light sensors  Quantum PAR  Pyranometer or  Photometer  and the Onset HOBO data logger  LICOR sensors provide a small signal in the range of microamps  whereas  the HOBO inputs require a signal in the range of 0 2 5 volts  The UTA   HOBO provides this amplification  and it also has    features that allow it to operate directly from the HOBO power supply     The UTA   HOBO is manufactured in two models  The base model        UTA   HOBO         is for use with a
7.  compensate for the effects of aging and degradation on the sensor     ver 2A   2007 EME Systems  2229 Fifth St   Berkeley CA 94710   510  848 5725  fax   510  848 5748  www emesys com 9    Troubleshooting     1  UTA appears to be dead  the output voltage is stuck at zero or full scale regardless of light level    Things to check   la  Be sure protective red plastic cap has been removed from the top of the LI COR sensor   1b  Check supply voltage and polarity at the red and black terminals of the UTA circuit board   Ic  Check the sensor polarity  make sure that the center conductor on the sensor wire is connected to the white terminal and  the outer shield wire is connected to the black terminal on the UTA input   Id  Check the screw terminal connections  make sure all of the wires are clamped solidly in place  The sensor wire should  be clamped in the terminal  not loose underneath it  The center conductor of the sensor wire is delicate  be sure it is not bro   ken   Je  If you are testing the unit on a bench indoors you may have to move it very close to an artificial light source to get a  response  Light levels indoors are much  much weaker than sunlight   1f  Check that the gain selecting switches are completely pushed to one side or the other  depending on the desired gain   1g  Has there been a lightning strike in close proximity  Although the UTA is protected against excess or reversed power  supply voltages  it can not be expected to survive catastrophic extremes   Ih
8.  micro station  Onset Part  H21 002    Use the 12 bit DC voltage input adapter  Onset part  S VIA CM14  to connect with the UTA HOBO  You will  need a 3 conductor cable to connect between the UTA   HOBO and the voltage input adapter  Make the following  connections between the 3 terminal block on the UTA   HOBO and the voltage input adapter  terminal block red  connects to    TRIG  SOURCE     terminal block green connects to    VOLTAGE INPUT     and terminal block black  connects to    GROUND     Once these connections have been made  plug the voltage input adapter into the HOBO    datalogger via the RJ11  telephone type  connection     ver 2A   2007 EME Systems  2229 Fifth St   Berkeley CA 94710   510  848 5725  fax   510  848 5748  www emesys com 13    Connections to Onset  HOBO H8 U12 series                common    signal    Insert cable through  UTA HOBO gland nut  and then             Voltage Input Cable     CABLE 2 5 STEREO             screw down under terminal  according to color      black to black     white to green   ered to red    UTA HOBO    Insert LI COR sensor  cable through gland nut     then       screw down under two input  terminal according to color   eshield to black   ecenter conductor to white       SZ    model So  LI COR sensor    Figure 8  UTA to HOBO H8 U12 series    Connections to Onset  HOBO Weather Station and  HOBO Micro Station    To HOBO Weather Station  or HOBO Micro Station    4    Onset 12 bit Voltage  Input Adapter    TRIG  SOURCE    VOLTAG
9.  that if the  LICOR sensor needs to be replaced or recalibrated  then its attached UTA must also be recalibrated     For example  suppose you have a Quantum PAR sensor  LI 190   and that its calibration tag states a multiplier of  187 5  uE m2s per pA  Suppose you want to calibrate the UTA to have an output of exactly 4 0 volts when the solar input is 2000    uE m2s  Note that the sensor output when the solar radiation is 2000pE m2s will be 10 667 microamps   2000 187 5    One way to do the calibration would be to apply a current of exactly 10 6667 microamps to the UTA input and then adjust the  trimmer in the UTA to give an output of 4 0 volts  It may be more convenient to use a standard current sink  say 10  microamps  and then set the output to 3 750 volts    4 10 10 667   The range of the trimmer may not be sufficient to reach  some settings  Please consult with EME Systems if you need special calibration for a UTA     Alternatively  a calibrated light source such as LI COR   s 1800 02 Optical Radiation Calibrator can be used to match the sen   sor to the UTA  Place the sensor in the calibrator and adjust the first stage gain trimmer to match the desired voltage output   Or  you can use one recently calibrated LI xxx as your standard for calibrating others of the same type  given a stable light  source  such as stable  midday sun     e LI COR recommends that all LI X XX series sensors be returned for re calibration every two years  This will ensure proper  calibration and
10. 2i    EME SYSTEMS    Universal Transconductance Amplifier    Universal Voltage Output Amplifier for LI COR    Sensors   Amplifies LI COR sensor current to voltage logger level  Version 2A    User Manual    Contents    Overview  amp  specifications 1  Connect the input and output 2  Calculate the light level 3  Configure the amplifier gain switches 4  Recalibrate the UTA 9  Troubleshoot 10  Physical dimensions 11  UTA circuit operation 12  Appendix  UTA HOBO special 13    Tables  Figures and Equations     table 1 UTA standard gain settings 3  table 2  switch positions vs gain required 6  table 3  gain vs switch positions 8  table 4  UTA HOBO standard gain settings 15  figure 1  UTA connections 2  figure 2  location of switches 6  figure 3  switch positions 7  figure 4  re calibration setup 9  figure 5  UTA enclosure  physical dimensions 11  figure 6  UTA schematic diagram 12  figure 7  UTA to HOBO connection 13  figure 8  UTA to HOBO H8 U12 series 14  figure 9  UTA to HOBO Micro Station 14    equation 1 calculate light level from UTA output 3  equation 2  calculate UTA gain required     gt     rev 2a 20071204    ver 2A   2007 EME Systems  2229 Fifth St   Berkeley CA 94710   510  848 5725  fax   510  848 5748  www emesys com    This page intentionally left blank    ver 2A   2007 EME Systems  2229 Fifth St   Berkeley CA 94710   510  848 5725  fax   510  848 5748  www emesys com    Universal Voltage Output Amplifier for LI COR    Sensors   Amplifies LI COR sensor current to volta
11. E INPUT      GROUND    Connect one side of a 3 conductor  cable  not included  to the TRIG   SOURCE  VOLTAGE INPUT  and  GROUND connections on the Onset  Voltage Input Adapter  Insert the  other end of the cable through the  UTA HOBO gland nut and then            Screw down under the 3 terminal block in the  following manner     Voltage Input Adapter  TRIG  SOURCE  VOLTAGE INPUT    UTA HOBO terminal  RED  GREEN  BLACK    Insert LI COR sensor  cable through gland nut     then       screw down under two input  terminal according to color   eshield to black   ecenter conductor to white       SZ    model faa  LI COR sensor    Figure 9  UTA to Micro Station and Weather Station    ver 2A   2007 EME Systems  2229 Fifth St   Berkeley CA 94710   510  848 5725  fax   510  848 5748  www emesys com    14    Calculate the light level     The external channels on the Onset HOBO data loggers record voltage  When you acquire readings from the logger  using  the ONSET   Boxcar software  those readings will be in volts  You will want to convert Volts to units of light measurement   Drop the negative sign from the LI COR sensor multiplier when making this conversion      UTA HOBO volt output   sensor gain     Light Level   1                                 equation 3    UTA HOBO transconductance gain     Table 4  Gain Settings for UTA HOBO    UTA HOBO 190    UTA HOBO 200 UTA HOBO 210  UTA Transconductance Gain  V A  0 056     Note that LI 190  LI 191  LI 192  and LI 193 Quantum PAR sensors all 
12. as this may cause the cover to deform  or    saddle    which can compromise the seal     Notes    e Noise sources  For long runs in the presence of halide lamps or other noise sources  you should consider using shielded   three wire cable for the power and signal connections between the logger and the UTA  with the shield tied to common at one  end only    e Long wire runs  The LI COR sensors come with 10 feet or 50 feet of cable  The rest of the wire run from the UTA to the  data logger or controller should be made with  22 gage or heavier wire  The current flowing in the ground lead creates an  error voltage that is added to the apparent output signal  For example  1000 feet of 22 gage wire has a resistance of approxi   mately 15 ohms  The UTA power supply current of 0 0005 amp flowing in that wire would create a 7 5 millivolt offset  On  the 5 volt scale  the error would be 0 0075 5   100   0 15   It is unlikely that you will be using such long wire runs  How   ever  poor connections in the ground lead can provoke similar errors  Be sure the ground lead is well secured  The UCLC  amplifier  also offered by EME Systems  is better suited to transmission of data as a current over long distances     Calculate the light level     In order to convert the UTA   s output voltage into the appropriate units of light  you will have to program your equipment to  multiply the UTA output voltage times the LI COR calibration multiplier and divide by the UTA   s transconductance gain   vo
13. ase refer to the next section or contact EME Systems  For example  this  would be called for if you need a different full scale voltage  or if you are measuring a low light level    2 Note that LI 190  LI 191  LI 192  and LI 193 sensors all use roughly the same UTA transconductance gains  The LI 192  and LI 193 have different calibration multipliers underwater and above water     Configure the amplifier gain switches     Most UTA users select from the standard 1  2  5  or 10 volt output settings  However  the UTA can be ordered or set by the  end user to a gain setting to fit a particular requirement  The gain settings that can be had through the switch settings are  shown in table 2  and the manner of setting the switches in figures 2 and 3     Find the transconductance gain necessary for your application using the following equation      desired UTA full scale output volts     UTA ee On er                       are    expected UTA input current from light sensor at full scale  Equation 2     Once the transconductance gain has been calculated  use Table 2 and Figure 3 to find a switch configuration that sets the actu   al UTA gain close to the calculated gain  Insert the transconductance gain found in Table 2 into equation   to calculate the  actual light level detected by your sensor     Examples of custom UTA gain settings     e Say you are working with a photometer in moderate light level conditions indoors where you expect to see top light levels  around 10 klux  Standar
14. d  LEop  0 aS  AD  4 aS  AD  8 lS  RAD  12 a  aa    el D  oH D  ob D  eH D  dsl p dq  p qem D da D    q  Bop d  E iop d  Bop d  Bop  Hoa  amp  1 q gt     g VE  9  SEZ  13 doez  no GG q  p qe p q  D  em p  Fii  Lal D dee p d gt  D  BS D     H qd   op d b op d E loD qd  lop   ODIE  ADX GY dy 4p  ODIAN  2 6 10 14   ub D q    BA D  eb p q  BE D    b p dsb D   B D dB D  JE ioh 1  io d  BoP d  BoD  GADI AN DLAN   Hp a  mo cay  3 Bi 7 qs DX  1 Ce BM 15 DX  d    p d i D  eb p qe BH D   Lal D dha p dB D  SBE D  Figure 3b  Settings for Switch 2  S2   1 Mab 1 m   q   p qd   isd  0 d E  4 d E eb 8 d Band 12 d  D  NADE GON NADE GN NDE GN NADE ON  q0  D q0   CHAD NODE EY  d E   d E   d E   d E  d  1 GEDEG 5 d E  9 d Hop 13 d Eep  NDX ON NDE GN  ADE GN MADE ON  JOL  p qo  p JOL  p dom  D  d eae  d W   d E   d E    1 Bip q Y iep 1 Wip 1 P iep  2 6 10 14  dz  ap dz    p Jz ied dzb ep     C Hp q0 1 D q0  q0  p  d E   d Be p d E   d E    q oD q oD q oD d cap  3 BZ  7 ZE 11 B44 15 LE  dz  ap dz  ap dzb ep  zh ied  JOL  D do  p JoL  p qo  p                                                 Figure 3  Settings for Switch 1  S1  and Switch 2  S2   Use combinations of S1 and S2 settings as described in Table 2 to set desired  gain of UTA     ver 2A   2007 EME Systems  2229 Fifth St   Berkeley CA 94710   510  848 5725  fax   510  848 5748  www emesys com       WJOA S JOA  ule6 obeys puz   SV  Aseuig   0000    Ov Ge  L000 0100    ywnl sioa    urep  obeys jsp Aseuig    0  L           v  S  9  Z  8    L100
15. d UTA gain settings will not sufficiently amplify such low light levels at a good resolution  You  have a photometer with a calibration multiplier of 2 78 klux per pA  The controller you are using has analog input channels  that allow 0 5 volts  Using equation 2  the necessary transconductance gain is     SV   2 78 klux pA    10 klux   1 39 V pA   Looking at Table 2  we find that switch 1  index 2  switch 2  index 7 provides a transconductance gain of 1 400 V A  which  is close to the calculated gain  Configure the switches to the correct positions  then use equation 1 to calculate the actual light  level from the observed UTA voltage output    Light Level   UTA volts     sensor multiplier   UTA transconductance gain from Table 2    Light Level   UTA volts    2 78 klux per pA   1 400 Volts per uA     ver 2A   2007 EME Systems  2229 Fifth St   Berkeley CA 94710   510  848 5725  fax   510  848 5748  www emesys com 4    e Say you are working with a quantum PAR sensor in a greenhouse with high intensity lighting where measured PAR can  achieve levels of 2500 wE m s  Standard UTA gain settings could saturate at such high light levels  You have a quantum  PAR sensor with a calibration multiplier of 138 31 wE m s per uA  Your controller has analog input channels that allow 0 1  volt  Using equation 2  the necessary transconductance gain is     1V   138 31 wE m2s per uA     2500 pE m s    0 0553 V pA   Looking at Table 2  we find that switch 1  index 8  switch 2  index 14 provides a 
16. ear wire  coax core             Switch Block S2  4 position   Use to select desired 2nd  stage gain              Figure 1  UTA switch and connections diagram    ver 2A   2007 EME Systems  2229 Fifth St   Berkeley CA 94710   510  848 5725  fax   510  848 5748  www emesys com 2    age you select for the UTA  e g   if using the 10 0 V F S setting  your power supply must provide at least 11 volts  or it  must provide 6 volts power for 5 volt output  or 5 volts power for a 1 to 4 volt output   The UTA uses a dual opera   tional amplifier integrated circuit that is capable of low offset voltage and operation on power supplies up to 28 volts   For special gain settings  we may employ a special op amp that has even lower offsets  but will only operate from  lower supply voltages  If that is the case  it will be noted on the amplifier calibration tag  The UTA draws less than  ImA of current  making a battery a viable option for a power supply     c  The signal from the UTA should be taken between the green and black terminals  Green is signal and black is common   The green terminal should be connected to the signal input of your logger and the black terminal should be connected  to common  Note that the black terminal is common to both the power supply and signal line     3  Check all connections for proper polarity and be sure all wires are clamped solidly in place  Replace the top cover on the  enclosure and tighten the corner screws  Take care not to over tighten the cover screws 
17. el  and a Sharpie    marker for the new one     ver 2A   2007 EME Systems  2229 Fifth St   Berkeley CA 94710   510  848 5725  fax   510  848 5748  www emesys com 5    Table 2  Switch positions as a function of gain required  Note that some of the gain settings can be achieved with multiple  switch combinations  When this is the case  it is usually preferable to choose a high gain  low switch position  in the first  amplifier stage  S1                                Gain  V A  Possible Switch Setting Combinations  S1   2  Gain  V uA  Possible Switch Setting Combinations  S1  S2   0 004 14 15 0 6 3 11   4 10   6 7   7 6   9 4   10 3  0 008 13 15   14 14 0 64 1 12   5 8  11 1  0 012 12 15   14 13 0 7 2 11   4 9   8 4   10 2  0 016 11 15   13 14   14 12 0 72 0 12   3 10   9 3   11 0  0 02 10 15   14 11 0 8 1 11   4 8   5 7   7 5   10 1  0 024 9 15   12 14   13 13   14 10 0 84 2 10   3 9   8 3   9 2  0 028 8 15   14 9 0 9 0 11   6 6   10 0  0 032 11 14   13 12   14 8 0 96 1 10   3 8   9 1  0 036 12 13 0 98 2 9   8 2  0 04 7 15   10 14   13 11   14 11 1 4 7 7 4  0 048 9 14   11 13   12 12   13 10 1 08 0 10   9 0  0 056 8 14   13 9 1 12 1 9   2 8   8 1  0 06 6 15   10 13   12 11   14 6 1 2 3 7   5 6   6 5   7 3  0 064 11 12   13 8 1 26 0 9   8 0  0 072 9 13   12 10 1 28 1 8  0 08 5 15   7 14  10 12   11 11   13 7   14 5 1 4 2 7   7 2  0 084 8 13   12 9 1 44 0 8  0 096 9 12   11 10   12 8 1 5 4 6   6 4  0 1 4 15   10 11   14 4 1 6 1 7 5 5   7 1  0 112 8 12   11 9 1 8 0 7   3 6   6 3 
18. er i o terminals                 Ordering example  UTA 200 5 standard UTA configured for LI200 and 5 volts full scale output  UTA BNC gx 0 56 UTA with BNC input connector  gain set at 0 56 volts per microamp     1 LI 190  LI 191  LI 192  LI 193  LI 200 LI 210 and part designations are trademarks and the exclusive property of LI COR Biosciences   Lincoln  Nebraska  www licor com     2 HOBO is a trademark of ONSET Computer Corporation  Bourne  MA   U S A   www onsetcomp com     ver 2A   2007 EME Systems  2229 Fifth St   Berkeley CA 94710   510  848 5725  fax   510  848 5748  www emesys com 1    Connect the input and output    The first step in using the UTA is to configure it for the LI COR sensor and output voltage scaling you wish to use  You may  have ordered your UTA pre configured for the appropriate sensor and full scale output voltage you need  The preset value is  marked on a label outside the UTA enclosure  If you need to set or reset the gain factor  please refer to pages 4 8      Configure the amplifier gain switches        1  UTA amplifiers are enclosed in a protective enclosure  To gain access to the connection terminals and switch blocks   remove the two corner screws using a standard screwdriver and lift up on the top  There is a connection diagram under the  cover     2  Refer to figure 1  The UTA has connections for the LI COR sensor input at one end of the circuit board and for the power  supply and signal output at the other end     a  LIXXX SZ  bare wire ter
19. ge logger level  Version 2A    The following instructions are provided to assist you in the installation and operation of your amplifier  While we have made  every effort to protect the amplifier from faults  improper installation or misuse may result in incorrect readings  or at worst   failure of the amplifier  Please read the manual in its entirety before connecting power to the UTA  If you have questions  about the UTA or any portion of this manual  please contact EME Systems technical support    e mail   support emesystems com   phone   510  848 5725  between the hours of 10 00 AM to 5 00 PM PST   fax   510  848 5748     Overview and specifications     The UTA is a special purpose amplifier that converts the microamp level current output of LI COR  light sensors to a corre   sponding signal voltage  and provides a simple interface between LI COR sensors and voltage input data loggers  chart  recorders  HVAC  and greenhouse controls  The UTA can be configured at EME Systems or by the end user for any one of a  large number of gain settings  through manipulation of two switch blocks  The calibration tag provided by LI COR    with  each sensor  in conjunction with the preset amplifier gain factor  can be used to compute the light levels incident on the sensor  with a high degree of accuracy     Typical settings     LI COR sensor Typical full sun response UTA output  user selectable    LI 190  191  192  193 PAR sensors 14 pA   2000 uE m s 1  2  5  10 Volts out   16 67pA inpu
20. gh speed  requirements of the HOBO data loggers     1  12 bit DC voltage input adapter  Onset Part  S VIA CM14  required for UTA con   nection to HOBO weather station  H21 001  and HOBO micro station  H21 002   dataloggers    2  Cable 2 5 Stereo  Onset Part  HOBO VOLT  required for UTA connection to H8  and U12 series HOBO dataloggers    Connect the UTA HOBO input and output        Figure 7  UTA to HOBO connection   A UTA  serves as a link between a LI COR sensor and the  Onset HOBO data logger  The UTA amplifies the  tiny current signal from the LI COR sensor and  outputs a voltage compatible with the HOBO     Figures 8 and 9  the UTA HOBO Connections Diagrams  on the following page  lay out connections between the UTA  the  LI COR sensor  and the Onset   HOBO data logger  The connection between the UTA and the HOBO depends on the type    of HOBO data logger you are using        HOBO H8 U12 series     Use the HOBO Voltage cable from EME Systems or the    cable 2 5 volt    from Onset  Onset Part  HOBO VOLT    to connect he UTA   HOBO to the HOBO   The mini stereo plug connects to one of the input ports on the side of  the HOBO data logger  The other end of the cable end has three bare wires and goes through the gland nut on the  side of the UTA nearest the three position terminal on the UTA circuit board  The wires are screwed down under  the terminals according to color code  Red to Red  White to Green  Black to Black     e HOBO weather station  Onset Part  H21 001  and HOBO
21. he amplifier and an accurate dig   ital voltmeter to read the amplifier output voltage  Set the output of the precision current sink to the desired the full scale sink  current  Adjust the first stage gain trimmer to give the corresponding full scale output  For example  to calibrate for a Quan   tum PAR sensor  we standardize with a 16 667 microamp input current  and a 5 0 volt output voltage  The adjustment range  is   3  of the dip switch gain value        Precision  4 digit   DVM    Vin    UTA Circuit board           Precision Floating  Current Source    foo        Isink Gnd  i o oO P               Regulated DC power supply    MA eoe     Vou Gnd  t    p     First stage gain  trimmer adjustment    Figure 4  UTA re calibration setup  Notes     e Each LICOR sensor has an individual calibration tag  The standard calibration of the UTA requires that the calibration con   stant be entered in software  Alternatively  a UTA can be calibrated to match an individual LI COR sensor  For example     1000 watts meter2 input can give 1 00 volt output so the formula is simple  W m    volts   1000   That UTA then has to stay  with that particular LI COR sensor  In effect the calibration is done in the hardware  rather than in the software  This simpli   fies the software  particularly where a low resolution converter will be used  or where calibration constants cannot be entered  in software  or where several light sensors must be interchangeable without reprogramming  The disadvantage is
22. lts per Amp      UTA output volts     sensor multiplier   Light Level                W         ____  Equation 1    UTA transconductance gain     Each individual LI COR sensor has a distinct calibration multiplier  You can find the multiplier for your particular sensor on  the calibration tag on the cable of your LI COR sensor  or the calibration certificate that came along with the sensor  Drop  the minus sign from the multiplier when carrying out the conversion calculation     The gain factor for each UTA as shipped from EME Systems is printed on a calibration tag on the side of its enclosure   Please refer to Table 2 to find the UTA transconductance gain for standard UTA output settings  NOTE  If you ordered a    UTA HOBO  please refer to the appendix section entitled    Calculating light level from the UTA HOBO    for conversion  calculations     Table 1  standard output   transconductance gain in volts per microamp  and switch setting   Standard full scale output voltage  1 volt fs 2 volts fs 5 volts fs 10 volts fs    LI 190 series 0 06 V A 0 12 V A 0 3 V pA 0 6 V uA  LI COR sensor   Quantum PAR S1 6  S2 15   S1 6  S2 14 S1 6  S2 11 S1 6  S2 7    LI 200 0 008 V A 0 016 V A 0 04 V uA 0 08 V uA  Pyranometer S1 13  S2 15   S1 13  S2 14 S1 13  S2 11 S1 13  S2 7  LI 210 0 02 V uA 0 04 V A 0 1 V A 0 2 V uA  Photometer S1 10  S2 15   S1 10  S2 14 S1 10  S2 11 S1 10  S2 7    ver 2A   2007 EME Systems  2229 Fifth St   Berkeley CA 94710   510  848 5725  fax   510  848 5748  www eme
23. mination    LI COR part numbers ending with    SZ    are terminated with a stripped and  tinned bare coaxial cable  The LI COR cable may need to be enlarged in diameter to make a snug fit in the cable  gland  Use heat shrink or silicone tubing for this purpose  On the inside of the box  connect the inner conductor   white  or clear  to the white colored terminal on the UTA board and connect the outer wire  shield or tinned copper  wire  to the neighboring black terminal    or  LIXXX SA  BNC termination   LI COR part numbers ending with a    SA    are terminated with a BNC connector and  should be used with the UTA BNC amplifier  Simply align the connector with its mate on the outside of the UTA   BNC and twist the two halves together  The BNC connectors should lock together when they are properly seated     b  Connect the power supply from your data logger between the black  common  and red    DC voltage  terminals in the  group of three  The power supply voltage must be at least 5 volts  and must be greater than the full scale output volt     from LI xxx sensor           T  ree conductor cable         Output       calibration tag      Mult  11 1           heatshrink tubing  or  silicone rubber tubing 3 32  i d   72  a d  for larger diameter and snug fil irt garki rut       Switch Block S1  4 position   Use to select desired 1st  stage gain       Gnd Power supply  Signal Out input and                            f Vcc signal output  Licor   Sae hro  5 24 vDo   Sensor  Input Cl
24. ns    Things to check   3a  Check all of the connections to the screw terminals  Make sure all connections are tight and secure   3b  Check for an AC component in the power supply voltage  The power supply should be filtered direct current and should  stay at least 2 volts above the full scale output voltage   3c  Is the sensor close to a strong electromagnetic field  such as a halide lamp or a refrigerator motor or other AC power  equipment  If so  try to reroute the sensor cable  or run the sensor cable inside a grounded metal conduit  Avoid running the  sensor cable in the same conduit as AC power lines   3d  Occasionally  oscillations can arise due to reactive loading on the signal cable  Placing a 0 1uF capacitor between the  signal terminal and the common terminal at your data logger input will usually suppress the oscillation     ver 2A   2007 EME Systems  2229 Fifth St   Berkeley CA 94710   510  848 5725  fax   510  848 5748  www emesys com 10    UTA  Polycarbonate Enclosure  Physical Dimensions     UTA  standard  UTA BNC                                                                                                                      2  Holes 0 175  ID  Screws Supplied     Mounting Template   not to scale        Figure 5  UTA enclosure  physical dimensions    ver 2A   2007 EME Systems  2229 Fifth St   Berkeley CA 94710   510  848 5725  fax   510  848 5748  www emesys com 11    UTA Schematic     The information contained herein is provided as an aid to resolving que
25. stions about the amplifier and its application   It is not meant for general distribution and remains the exclusive property of EME Systems     UTA     Universal Transconductance Amplifier   Version 2    Version 2  Rev  A UTA June 2006  UTA06g   EME Systems  2229 Fifth St   Berkeley CA 94710  tel   510  848 572  fax   510  848 5748  www emesystems com  info emesystems com    ae 40k       10k  INPUT pa OUTPUT  l    10k  40K Jok  10k 50k   le Inf 2 5k  Ot Volts  200 B 10k power  1k     O Output  LL103 2k Volts  40k  40k inf Q 1yf  O Common    Figure 6  UTA schematic diagram    Switches are represented as dashed lines  and are either open or closed to allow or short the parllel resistor s     Switches on input stage select transconductance gains from 0 004 to 0 18 volts per microamp    Switches on output stage select voltage gains from x1 to x45    Composite gains from 0 004 to 8 1 volts per microamp    High gain settings use split T feedback    Provision is made for a solder jumper on the bottom of the circuit board to boost the first or second stage gain by shorting the  10kQ resistors marked with   in the split T networks  Gains of 28 volts per microamp are possible for low light levels    There is also provision on the circuit board for a voltage regulator for the power supply  which would replace diode CD214   Special for Onset HOBO    jumper 1a shorts diode     Op amps for this circuit are socketed to allow field replacement and also to allow substitution of alternative op
26. sys com 3       Example calculations     Example 1  UTA 190 1  amplify LI 190 PAR sensor output up to level of 0 1 volt full scale   e UTA gain  1st column  1st row in Table 1   0 06 V uA  1 Volt full scale at 16 67 uA input from LI 190     e multiplier  from LI 190 Quantum PAR sensor calibration tag or certificate   148 50 wE m2s per pA  hypothetical    e volts reading  0 836 Volts  hypothetical        gt  light level   UTA volts    148 50   0 06     0 836 volt     2475 uwE m2s per volt    2069 nE m2s    Example 2  UTA 200 5  Amplify pyranometer output to 5 volts full scale   e UTA gain  3rd column  2nd row in Table 1   0 04 V uA  5 Volts full scale at 125 uA input from LI 200     e multiplier  from LI 200 Pyranometer sensor calibration tag or certificate   9 80 Wim2 per pA  hypothetical   e volts reading  3 80 Volts  hypothetical        gt  light level   UTA volts    9 80   0 04     3 80 volts     245 0 W m2 per volt    931 W m2    Example 3  UTA 210 10  Amplify photometer output to 10 volts full scale  sunlight   e UTA gain  4th column  3rd row in Table 1   0 2 V uA  10 Volts full scale at 50 uA input from LI 210   e multiplier  from LI 210 Photometer calibration tag or certificate   2 63 klux uA  hypothetical     volts reading  6 25 Volts  hypothetical      gt  light level   UTA volts    2 63   0 2     6 25 volts     13 15 klux per volt    82 2 klux   If you need units in footcandles  1 footcandle 10 764 lux     Notes    1  If you need a different calibration setting  ple
27. t  LI 200 Pyranometer 100nA   1000 W m  1  2  5  10 Volts out   125A input  LI 210 Photometer 40uA   100 klux   9290 fted  1  2  5  10 Volts out   50uA input    These settings correspond to those of an earlier version of our UTA amplifier  and are still our    standard    settings  Many  alternate gain settings are available from the table on page 6  amp  8  Those are useful for different full scale ranges of equip   ment or for sensors under special lighting conditions  Higher gain settings are useful for low light levels  typical of photome   ters indoors or PAR deep underwater  A special UTA HOBO is available for use with ONSET HOBO  data loggers   appendix A      Specifications  standard configuration      e Supply Voltage  5 24 VDC  single supply  at least 1 volt higher than full scale cat   Special versions are available that have different power requiremeni     e Supply Current  less than ImA   e Gain accuracy   0 2  on factory preset range    0 5  all ranges     Voltage output in darkness   lt 4 millivolts   e Supply Voltage variation effect  less than 0 01  per Volt   e Response  2 milliseconds  special versions available    e Operating Temperature   30  C to  70  C   e Tempco  less than 0 01  per   C   e Output impedance  1000Q  1    e NEMA 4 gasketed white polycarbonate  also available without   enclosure  1 37    x 1 96    x 2 55     4 15    w glands   PG7 gland nut or BNC at input  PG7 gland nut at output     RoHS compliant  lead free   e Phoenix   beryllium copp
28. transconductance gain of 0 056  which is  close to the calculated gain  Configure the switches to the correct positions  then use equation   to figure out the actual light  level from the observed UTA voltage out    Light Level   UTA volts     sensor multiplier   UTA transconductance gain from Table 3    Light Level   UTA volts    138 31 uE m s per uA   0 056 Volts per uA     Notes       Choose a full scale output voltage less than or equal to your logger   s input capability  but not too much less  For   example  if your logger has a full scale input range of 2 5 volts  you should choose a setting that will never exceed 2 5 volts   but will come close to that at its maximum    e If you select too low a setting  you will lose resolution and your logger will not register subtle changes and may fail to reg   ister the lowest light levels of interest    e If you select too high a setting  the amplifier may overdrive or saturate the input circuit on your meter or even damage its  inputs  The highest light levels will all register as one value  off scale    e You may wish to purposely select a higher output setting to achieve greater sensitivity at low light levels  This might be use   ful in studies of indoor lighting  or deep water studies with the LI192 or LI193  where full sun intensities will never be  attained    e The UTA power supply must always be greater than or equal to the full scale output voltage    e You can use alcohol to rub off the old mark on the calibration lab
29. use the same transconductance gain          Examples of light level calculations for UTA HOBO   Below are examples that show the conversion from Volts to light level for different types of LI COR light sensors     LI190 Quantum PAR sensor example   e Switch settings S1 5  S2 14  gain   0 16 volts per microamp  e UTA HOBO gain   0 16 volts per microamp  2 5 Volts full scale output at 15 625 amps input   e multiplier  from LI190 calibration tag or certificate   145 00 umoles m s per pamp  hypothetical   e Volts reading from HOBO   1 25 V  hypothetical     gt  light level   HOBO Volts    145 00   0 16     1 25 volts     906 25 umol m s per volt    1132 8 pmoles m 2s    LI200 Pyranometer sensor example   e Switch settings S1 14  S2 11  gain   0 02 volts per microamp  e UTA   HOBO gain   0 02 volts per microamp  2 5 volts full scale output at 125 amps input   e multiplier  from L1200 calibration tag or certificate   11 50 watts m  per pamp  hypothetical   e volts reading from HOBO   1 25 V  hypothetical     gt  light level   HOBO volts    11 50   0 02     1 25 volts     575 0 watts m  per volt    718 8 watts m2    LI210 Photometer sensor example   e Switch settings S1 8  S2 14  gain 0 056 volts per microamp  e UTA   HOBO gain   0 056 volts per microamp  2 5 volts full scale output at 41 667 amps input   e multiplier  from LI210 calibration tag or certificate   2 88 klux per pamp  hypothetical   e volts reading from HOBO 1 25 V  hypothetical     gt  light level   HOBO volts    2 88
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
GERENCIAMENTO DE FACILIDADES EM SISTEMA - Poli  BEDIENUNGSANLEITUNG BS HDVR 10804 H.264 4-Kanal HD  Smith Cast Iron Boilers GB250 SERIES User's Manual  User Manual - BC Group International Inc.  取扱説明書 - ソニー製品情報    Tripp Lite USB 3.0 SuperSpeed Device Cable (AB M/M) Black, 10-ft.  PISCiNES BOiS `WEVA” OCTOGONALES  DCU System for FlexAct® COM  MANUAL DE USUARIO: Gestor    Copyright © All rights reserved. 
   Failed to retrieve file