Home
        Marley Quadraflow Cooling Tower Installation, Operation and
         Contents
1.      Single winding motor requires a starter with a shorting contactor    e Two winding motor requires a starter with out a shorting contactor        All two speed starters must have a 20 second time delay relay when  switching from high speed to low speed             5    Note    Note       Installation    Do not start the motor more than four to five times per hour  each  low speed start and each high speed start count as one start      When using a VFD     Before beginning  ensure that the motor is rated for    Inverter Duty     per NEMA MG 1  part 31     e Set the VFD solid state overload protection to 119  of motor name   plate amps and set    maximum current parameter    in the VFD to motor  nameplate amps     Maximum current parameter    will reduce fan speed  and limit amp draw to nameplate amps during cold weather opera   tion  If furnished with a mechanical O L  set this at 110  over motor  nameplate amps    e Motor rotation must be the same in both VFD mode and By pass  mode    e If cable distance between the VFD and motor is greater than 100 feet  a DV DT output filter is recommended to avoid damage to the motor   100 feet distance is based on our field experience  the VFD manufac   ture may state different distances and distance does vary depending  on the VFD manufacture    e Program the VFD for variable torque output  Flux vector and constant  torque modes may damage the gearbox    e Do not start and stop the motor using the safety switch at the motor   If the 
2.    Check voltage and current of all three lines against nameplate  values        Wrong motor RPM    Check nameplate against power supply  Check RPM of motor  and gear ratio        Bearings overgreased    Remove grease reliefs  Run motor up to speed to purge  excessive grease        Wrong lubricant in bearings    Change to proper lubricant  See motor manufacturer s  instructions        One phase open    Stop motor and attempt to start it  Motor will not start if single   phased  Check wiring  controls and motor        Poor ventilation    Winding fault    Clean motor and check ventilation openings  Allow ample  ventilation around motor     Check with Ohmmeter        Bent motor shaft    Straighten or replace shaft        Insufficient grease    Remove plugs and regrease bearings        Too frequent starting    Limit cumulative starting time to a total of 30 seconds each  hour        Deterioration of or foreign material  in grease    Flush bearings and re lubricate        Bearings damaged    Replace bearings        Incorrect fan blade pitch    Measure actual fan pitch and compare to that recommended   Correct  if necessary  See Fan User Manual        Geareducer noise Geareducer bearings    Gears    If new  see if noise disappears after one week of operation   Refer to Geareducer User Manual     Correct tooth engagement  Replace badly worn gears  Replace  gears with imperfect tooth spacing or form     23    SP      COOLING TECHNOLOGIES    7401 WEST 129 STREET   OVERLAND PARK  KANSA
3.   Marley QuadraFlow  Cooling Tower    User Manual 92 1333H    Mwa        Marley           AN SPX BRAND    Note    A Warning    A  Caution    Note       Contents    This manual contains vital information forthe proper installation and  operation of your cooling tower  Carefully read the manual before  installation or operation of the tower and follow all instructions   Save this manual for future reference     Page  TOWEL OG AON      krak ant enn kan kind n esti apa            sen es apa              4  Tower Shipment  kebek pa Sees kok pon cits ti a nek do ke ta pa pi ka e ak pa ae kad a ank Pa a 5  Receiving TOWON sisi  e sisie oo see do tease doua                     5  Tower ASSO MDYa ainn doi koko bn de den dane pab ponp                        5  Motor                                  bone oke dad tease poko                   5  Tower Start Up    ei b  s pake oi ad gwat ok ako di a ana pi e pi e ae bb a a kk an   s 10  Tower                               ak ak ak               e ka aha ap kk kb 13  Water Treatment and                                                     13  Schedule of Tower                                                                         15  Seasonal Shutdown INStructions              18  Motor Relubrication INStructions       escesseeeceeeteseeseeeeseeseeeseeneaeeteseeeeeteees 19  Prolonged ShUtCOWN      ran ente anban antik restan ae saa si poo depan deske tan 19  Additional SEA OO Sissies pis pa atin Eaei                              20  Additio
4.  Leave the basin drain open     During shutdown  clean the tower and make any necessary repairs  Pay par   ticular attention to mechanical equipment supports and driveshafts     Tower Framework  Check structural bolted connections and tighten as  required     Driveshaft  Check driveshaft alignment  tightness of cap screws and set screws   and condition of all components  Refer to driveshaft service manual     Fan  Check fan assembly bolting and tighten as required  Use torque settings  prescribed on the fan nameplate  Refer to fan service manual     Electric Motor  Clean and lubricate motor at close of each operating season    Refer to motor manufacturer s recommendations   Check motor anchor bolts  and tighten as required  See Page 19 for motor lubrication instructions     Do not start motor before determining that there will be no interfer   ence with free rotation of the fan drive     The motor should be operated for three hours at least once a month  This  serves to dry out windings and re lubricate bearing surfaces  Refer to    Marley  Electric Motor User Manual    Manual 92 1475     At start of new operating season  make sure bearings are adequately lubricated  before returning motor to service     A Warning       Maintenance    Drive Shaft Air Seals       ff Motor    Motor Lubrication Instructions    Open and lock out disconnect switch to make certain motor cannot  be started     1  Remove interior driveshaft air seals as shown above  Opposite end motor  bearing is acc
5.  Manuals on each  major operating component of the tower  and it is recommended that you  read them thoroughly  Where discrepancies may exist  the separate Service  Manuals will take precedence     Do not use the top horizontal surface of the tower as a working  platform  The tower is designed so that all maintenance can be  performed from the exterior and interior of the tower  Do not use  the upper basin covers as a walking surface or working platform   Remove basin covers and use portable ladders whenever performing  service on the hot water basin  Use of ladder should be in accord  with manufacturer   s recommendations    The following is recommended as a minimum routine of scheduled mainte     nance     Always shut off electrical power to the tower fan motor prior to  performing any inspections that may involve physical contact with  the mechanical or electrical equipment in or on the tower  Lock out  and tag out any electrical switches to prevent others from turning  the power back on  Service personnel must wear proper personal  protective clothing and equipment     Weekly  Inspect for bacterial growth and general operation conditions  Bacte   rial growth should be reported to your water treatment expert for immediate  attention     Monthly  Weekly at Start up   Observe  touch  and listen to the tower  Become  accustomed to its normal appearance  sound  and level of vibration  Abnormal  aspects relating to the rotating equipment should be considered reason to  shut dow
6.  Resume treatment with the biocide which had been used prior to shut   down  Utilize the services of the water treatment supplier  Maintain the  maximum recommended biocide residual  for the specific biocide  for       Operation    a sufficient period of time  residual and time will vary with the biocide   to bring the system under good biological control  or   e Treat the system with sodium hypochlorite to a level of 4 to 5 mg L   ppm  free chlorine residual at a pH of 7 0 to 7 6  The chlorine residual  must be held at 4 to 5 mg L  ppm  for six hours  measurable with  standard commercial water test kits     If the cooling tower has been in operation and then shut down for a duration  of time and not drained  perform one of the two previous biocidal treatment  programs directly to the cooling water storage vessel  cooling tower sump   drain down tank  etc   without circulating stagnant water over the cooling  tower fill or operating the cooling tower fan     After biocidal pretreatment has been successfully completed  cooling water  may be circulated over the tower fill with the fan off     When biocidal treatment has been maintained at a satisfactory level for at least  six hours  the fan may be turned on and the system returned to service  Resume  the standard water treatment program  including biocidal treatment     Wintertime Operation    During operation in subfreezing weather  the opportunity exists for ice to form  in the colder regions of the tower  Your primary conce
7.  attempt any service unless the fan motor is  locked out     Operators of evaporative cooling equipment  such as water cooling towers   should follow maintenance programs which will reduce to an absolute minimum  the opportunity for bacteriological contamination  US Public Health Service  publications have recommended that    good housekeeping    procedures be  followed  such as  regular inspections for concentrations of dirt  scale  and  algae  periodic flushing and cleaning  and the following of a complete water  treatment program including biocidal treatment  See Tower start up instruc   tions on page 10     13    Note    14       Maintenance    The visual inspection should take place at least once a week during the operat   ing season  The periodic flushing and cleaning should be done before and after  each cooling season  but in any event at least twice a year  The louvers  drift  eliminators  and easily accessible fill surfaces should be flushed by use of a  moderate pressure water nozzle  being careful not to cause physical damage   A reliable water treatment program should be installed and maintained  Filtra   tion devices may be employed to reduce the suspended solids concentrations   thus increasing the effectiveness of the water treatment program     Blowdown    Acooling tower cools water by continuously causing a portion of it to evaporate   Although the water lost by evaporation is replenished by the makeup system  it  exits the tower as pure water   leaving behi
8. D system and repairing any  damage that may have occurred during its operation  SPX Cool   ing Technologies does not assume responsibility for any technical  support or damages for problems associate with non Marley brand  VFD systems     Changing the operational fan speed from the factory settings could  cause the fan to operate in an unstable region which may result in  damage to the equipment and possible injury     Mechanical Equipment    Always make certain that mechanical equipment is inoperable  during periods of maintenance or during any situation of possible  endangerment to personnel  If your electrical system contains a  disconnect switch  lock it out until the period of exposure to injury  is over     1  Check the Geareducer oil level at the sight glass near the motor  If oil is  required  fill to the proper level     2  Spin the fan manually to assure that all fan blades properly clear the inside  ofthe fan cylinder  Observe the action of the driveshaft couplings to be sure  that the motor and Geareducer are properly aligned  If necessary  correct  the alignment in accordance with the included driveshaft manual    3  Momentarily energize     bump     the motor and observe rotation of the fan   The fan should rotate in a counterclockwise direction when viewed from  below  If rotation is backwards  shut off the fan and reverse two of the  three primary leads supplying power to the motor     m    A Caution    Note       Installation    If tower is equipped with a tw
9. S 66213 UNITED STATES   913 664 7400   spxcooling spx com   spxcooling com    In the interest of technological progress  all products are subject to design and or material change without notice     2009 SPX Cooling Technologies  Inc    Printed in USA    M92 1333H    
10. ach wintertime shutdown period     If tower basin is drained  verify that all basin heaters have been shut  off either by automatic cutoff or disconnect switch     A Warning       Maintenance    Water Treatment and Blowdown    Maintaining Water Quality     The materials used in the QuadraFlow tower are selected to offer long  corrosion     free service in a    normal    cooling tower environment  defined as follows     e Circulating water with a pH between          8  a chloride content  as NaCl   below 750 ppm  a sulfate content  SO   below 1200 ppm  a maximum  inlet water temperature not to exceed 125  F  no significant contamina   tion with unusual chemicals or foreign substances  and adequate water  treatment to minimize scaling     e Chlorine  if used  shall be added intermittently  with a free residual not to  exceed 1 ppm     maintained for short periods  Excessive chlorine levels  may deteriorate sealants and other materials of construction     e An atmosphere surrounding the tower no worse than    moderate indus   trial     where rainfall and fog are no more than slightly acid  and they do  not contain significant chlorides or hydrogen sulfide     5      Cooling Tower Cleaning    Any evaporative type cooling tower must be thoroughly cleanedona  regular basis to minimize the growth of bacteria  including Legionella  Pneumophila  to avoid the risk of sickness or death  Service per   sonnel must wear proper personal protective equipment during de   contamination  Do NOT
11. ater  treatment expert before startup     Remove any and all accumulated debris from tower  Pay particular attention  to inside areas of cold water basin  entire hot water basin  and hot water  inlet  Make sure that cold water suction screens are clear and installed  in place    Fill the water system to an approximate depth of 3  in the elevated section  of the cold water basin  This is the recommended operating water level   Adjust the float valve so that it is essentially closed at that level  Continue  filling the system until the water reaches a level approximately    below  the lip of the overflow     Start your pump s   Observe system operation  Since the water system  external to the tower will have been filled only to the level achieved in the  cold water basin  a certain amount of    pump down    of the basin water  level will occur before water completes the circuit and begins to fall from  the fill  The amount of initial pump down may be insufficient to cause the  float valve to open  However  you can check its operation by pressing down  on the operating lever to which the stem of the float valve is attached     Continue pump operation for about 15 minutes  after which it is recom   mended that the water system be drained  flushed  and refilled in order  to clean the system     While operating the condensing water pump s  and prior to operating the   cooling tower fan  execute one of the two alternative biocidal treatment   programs described in the following    e
12. ater temperature attainable    under any operating circumstance     2  Air Wet Bulb Temperature  Cold water temperature will also vary with  the wet bulb temperature of the air entering the louvered faces of the tower   Reduced wet bulb temperatures will result in colder water temperatures   However  the cold water temperature will not vary to the same extent as  the wet bulb  For example  a 20  F reduction in wet bulb may result in only  a 15  F reduction in cold water temperature     Note    Note       Installation    3  Water Flow Rate  Increasing the water flow rate  GPM  will cause a  slight elevation in cold water temperature  while reducing the water flow  rate will cause the cold water temperature to lower slightly  However  at  a given heat load  see formula above   GPM reductions also cause an  increase in the incoming hot water temperature  Use care to prevent the  hot water from exceeding 125  F  in order to prevent damage to the tower  components     4  Airflow Rate  Reducing airflow through the tower causes the cold water  temperature to rise  This is the approved method by which to control leav   ing water temperature     If your tower is equipped with a single speed motor  the motor may be  shut off when the water temperature becomes too cold  This will cause  the water temperature to rise  When the water temperature then becomes  too warm for your process  the motor can be restarted     Fan cycling limits     Considering the normal fan and motor sizes utilize
13. d      MCW towers   anticipate that approximately 4 to 5 starts per hour are allowable     If your tower is equipped with a two speed motor  greater opportunity  for temperature control is afforded you  When the water temperature  becomes too cold  switching the fan to half speed will cause the cold  water temperature to rise   stabilizing at a temperature a few degrees  higher than before  With a further reduction in water temperature  the fan  may be cycled alternately from half speed to off     Do not start the motor more than four to five times per hour  each  low speed start and each high speed start count as one start      If your tower consists of two or more cells  cycling of motors may be shared  between cells  increasing your steps of operation accordingly  For greater  insight on cold water temperature control  please read Marley Technical  Report  H 001 A      Cooling Tower Energy and its Management    available  for download at spxcooling com     A Warning    10       Operation    Tower Start Up    Among other sources  outbreaks of Legionnaires    Disease have  reportedly been traced to cooling towers  Maintenance and water  treatment procedures that prevent amplification and dissemination  of Legionella and other airborne bacteria should be formulated and  implemented BEFORE systems are operated and continued regularly  thereafter to avoid the risk of sickness or death     Water System    1     New installations should be cleaned and treated with biocides by a w
14. drive is being commanded to run and the load side is cycled ON  and OFF with the safety switch this may damage the VFD     Using a VFD in cooling applications has advantages over traditional single  or two speed motor control  A VFD can reduce the cost of electrical energy  being used and provide better temperature control  In addition  it reduces the  mechanical and electrical stress on the motor and mechanical equipment   Electrical savings can be large during periods of low ambient temperature  when the cooling requirement can be satisfied at reduced speeds  To benefit  from these advantages  it is important that the drive be installed correctly    Marley supplies VFD and VFD controls specifically designed for our cool   ing products  If you have purchased a Marley VFD and or controls package   please follow the instructions in the User Manual for that system  Most VFD    A Warning    A Warning    A Warning       Installation    problems can be avoided by purchasing the Marley drive system  If you are  installing a VFD other than the Marley drive  please refer to that drives instal   lation manual     Improper use of a VFD may cause damage to equipment or personal  injury  Failure to correctly install the VFD drive will automatically  void all warranties associated with the motor and any equipment  that is either electrically or mechanically  directly  attached to the  VFD drive system  The length of this warranty avoidance will be  contingent on properly installing the VF
15. e of damage in shipment  If damage is apparent  note the freight  bill accordingly  This will support your future recovery claim     Tower Assembly    Your Marley sales representative is able to provide for the tower assembly by  SPX   s construction division or through a qualified subcontractor  Our subcon   tractors provide safe  efficient assembly which complies with all requirements  for five year warranty protection of your tower by SPX     Motor Wiring    Wire motor leads as shown on the motor nameplate matching the supply  voltage  Do not deviate from the motor nameplate wiring     Either of following symbols may be shown on the motor nameplate      A  AA  Y  or YY  These symbols represent how the motor is constructed on  the inside and in no way have anything to do with a Delta or Wye electrical  distribution system serving the motor     When using a starter     e Set motor overload protection to 110  of motor nameplate amps   This setting allows the fan motor to operate during cooler weather   During cooler weather it is common for the motor to draw 6 to 10   higher than the nameplate amps  High amps are common during tower  commissioning when the tower is dry and the ambient air temperature  is cool    Do not start the motor more than four to five times per hour  Short  cycling the tower will cause fuses  breakers or O L s to operate and  will decrease motor life     When using a two speed starter     e Motor rotation must be the same at slow speed and high speed   
16. ent Parts    With the exception of the motor  every component of your tower is designed  and manufactured by SPX Cooling Technologies  We do this because com   mercially available components have not proved capable of withstanding the  harsh environment of a cooling tower    nor do they contribute their share to  the thermal capability and operating characteristics intended     A complete stock of all parts and components is maintained at one or more  of the various Marley plants  In cases of emergency  they can normally be  shipped within 24 hours   by air freight  if necessary  However  you would  obviously benefit from anticipating your need in advance  thus avoiding the  cost of special handling     Be sure to mention your tower serial number  from the tower nameplate  when  ordering parts  Refer to assembly manual for part identification     Periodic Maintenance    You may wish to contract with Marley for regularly scheduled visits   for the  purpose of inspecting and reporting your tower s condition   to make recom   mendations intended to prevent emergencies   and to perform maintenance  considered outside the norm     This service is not intended to replace the important function performed by  your maintenance staff  Their attention assures the tower s routine operating  performance  and is invaluable  However  Marley recognizes that the unusual  manner in which a cooling tower performs its function   as well as the unique  forces which act upon it may be consideratio
17. escribed on the  fan nameplate     Clean and disinfect cooling tower with biocides  Systems with biofouling  high  general bacterial counts  or positive cultures of legionella may require additional  cleaning  Refer to    Cooling Tower Cleaning    section on page 13  Consult your  water treatment expert as to prudent biological evaluation testing      To maintain five year change intervals  use only oil designed specifi   cally for these Geareducers  If  after five years  turbine type mineral oil  is used  the oil must be changed semiannually  Refer to Geareducer  User Manual for oil recommendations and further instructions     Annually  Inspect the tower thoroughly  making maximum use of instructions  given in the separate service manuals  Check structural bolted connections  and tighten as required  Make preventive maintenance repairs as necessary     Every 5 Years  Change Geareducer oil  Refer to Geareducer User Manual  for instructions        Maintenance Schedule                                                                                     Maintenance Service Monthly Semi annually Seasonal Startup or Annually   Inspect General Condition and Operation        Observe Operation of    Mechanical   motor  fan and drive mechanism         Makeup valve  if equipped  x x   Inspect for unusual noise or vibration x x  Inspect and Clean    Air inlet x x   PVC drift eliminators         Distribution basin  nozzles and collection basin x      Fan motor exterior        Check    Col
18. essible by removing motor cover  24000 models do not  have a motor cover  on the exterior of the tower     2  Relubricate motor according to the manufacturer s instructions     Fiberglass Components  Check all fiberglass parts for exposed glass fibers   If found  the affected surfaces should be roughened up and solvent wiped   Surfaces must be clean and dry and free of oil  grease or other contaminants  before applying new coating  The best coating system requires using a two   part polyamide epoxy primer to promote adhesion and a two part acrylic poly   urethane enamel for the topcoat  Contact your Marley sales representative if  additional information is required     Prolonged Shutdown    If shutdown period is longer than seasonal  contact your Marley sales engineer  for additional information     19    20       Maintenance    Additional Services    SPX s interest in your Marley QuadraFlow cooling tower does not end with  the sale  Having conceived  designed  and manufactured the most reliable  and longest lasting cooling tower of its class  we want to make sure that you  gain the maximum possible benefit from its purchase     Therefore  the following services are available which are intended to assure  the maximum possible service life under your operating conditions  tailor the  operating characteristics to your specific needs  and maintain consistent op   timum thermal performance capability  They are available by contacting your  Marley sales representative     Replacem
19. et cold water temperature produced by the  entire tower     2  As cold air enters the louvers  it causes the falling water to be drawn inward  toward the center of the tower  Thus  under fan operation  the louvers and  lower periphery of the tower structure remain partly dry  seeing only random  splashing from within the tower   plus normal atmospheric moisture from  the entering air  Such lightly wetted areas are most subject to freezing     Although ice is unlikely to cause structural damage to the fill  it may build  up sufficiently to restrict the free flow of air through the louvers  This will  have the effect of reducing the tower s thermal performance efficiency   When excessive ice forms on the louvers  stop the fan for a few minutes   With the fan off  the increase in the water temperature and the action of  the cascading water will reduce the ice buildup on the louvers     Intermittent Wintertime Operation    If periods of shutdown  nights  weekends  etc   occur during freezing weather   measures must be taken to prevent the water in the cold water basin    and all  exposed pipework from freezing  Several methods are used to combat this   including automatic basin heater systems available from Marley  It is recom   mended that you discuss your freeze prevention options with your local Marley  sales representative     Unless some means of freeze prevention is incorporated into your  system  the tower basin and exposed pipework should be drained  at the beginning of e
20. etailed  information on a variety of cooling tower operation and service topics available  to download at spxcooling com  For complete parts and service assistance   contact the Marley sales or representative office in your area  If you need help  locating the office nearest you  please phone 913 664 7400 or check the  web at spxcooling com     21       Troubleshooting    Trouble Cause    Motor will not start Power not available at motor terminals    Remedy    1  Check power at starter  Correct any bad connections  between the control apparatus and the motor     2  Check starter contacts and control circuit  Reset overloads   close contacts  reset tripped switches or replace failed  control switches     3  If power is not on all leads at starter  make sure overload  and short circuit devices are in proper condition        Wrong connections    Check motor and control connections against wiring diagrams        Low voltage    Check nameplate voltage against power supply  Check voltage  at motor terminals        Open circuit in motor winding    Check stator windings for open circuits        Motor or fan drive stuck    Disconnect motor from load and check motor and Geareducer  for cause of problem        Rotor defective    Look for broken bars and rings        Unusual motor noise Motor running single phase    Stop motor and attempt to start it  Motor will not start if single   phased  Check wiring  controls and motor        Motor leads connected incorrectly    Check motor connecti
21. lean of debris        Overpumping    Reduce water flow rate to tower to design conditions        Cold water too warm Overpumping    Reduce water flow rate to tower to design conditions         See    Tower Operation     Not enough air    22    Check motor current and voltage to be sure of correct contract  horsepower  Clean louvers  fill and eliminators        Troubleshooting       Trouble Cause Remedy  Unusual fan drive Loose bolts and cap screws Tighten all bolts and cap screws on all mechanical equipment  vibration and supports        Unbalanced driveshaft or worn couplings    Make sure motor and Geareducer shafts are in proper alignment  and    match marks    properly matched  Repair or replace worn  couplings  Rebalance driveshaft by adding or removing weights  from balancing cap screws  See Driveshaft Service Manual        Unbalanced fan    Be sure blades are properly positioned in correct sockets   See  match numbers   Make certain all blades are as far from center  of hub as safety devices permit  All blades must be pitched the  same  See Fan User Manual  Clean off deposit buildup on  blades        Worn Geareducer bearings    Check fan and pinion shaft endplay  Replace bearings as  necessary        Unbalanced motor    Disconnect load and operate motor  If motor still vibrates   rebalance rotor        Bent Geareducer shaft    Motor runs hot Motor overload  wrong voltage or    unbalanced voltage    Check fan and pinion shafts with dial indicator  Replace if  necessary  
22. lection water basin level         Blowdown adjust as required x x  Geareducer Drive   Check for loose fasteners including oil drain plug x   Check for   repair oil leaks x x   Check oil level x x   Change oil R   Make sure vent is open x   Check driveshaft alignment x   Check for loose driveshaft or coupling fasteners x   Check driveshaft flex element for unusual wear x x  Lube lines    Check for oil leaks in hoses or fittings x x  Fan    Check and tighten blade and hub fasteners x   Check fan blade pitch and tip clearance x   Check fan cylinder for loose fasteners x  Motor    Lubricate  grease as required  R   Check mounting bolts for tightness x    Operate at least    3 hours a month    3 hours a month    3 hours a month       Basin Heater  if equipped                  Check for proper operation of temp low water level sensor x   Inspect clean buildup of contaminant from sensor x x  Structure    Inspect tighten all fasteners         Inspect and touch up all metal surfaces x                R     Refer to Component User Manual       Note  It is recommended at least weekly  that the general operation and condition be observed  Pay attention to    any changes in sound or vibration that may signify a need for closer inspection     17    A Warning    18       Maintenance    Seasonal Shutdown Instructions    When the system is to be shut down for an extended period of time  it is  recommended that the entire system  cooling tower  system piping  heat  exchangers  etc   be drained 
23. n the tower until the problem can be located and corrected  Observe  operation of the motor  driveshaft  Geareducer and fan  Become familiar with  the normal operating temperature of the motor  as well as the sight and sound    of all components as a whole     Check Geareducer oil level  Shut down the unit and allow 5 minutes for the  oil level to stabilize  Add oil if required  Check system for leaks if the amount  of oil required appears unusual   If oil is added at the external fill port  allow  adequate time for the level to stabilize before reading final level      15    Note    16       Maintenance    Inspect louvers  drift eliminators and basin trash screens and remove any  debris or scale which may have accumulated  Replace any damaged or worn  out components  Use of high pressure water may damage the eliminator and    louver material     Observe operation of the float valve  Depress the operating lever to make  sure that the valve is operating freely  Inspect the suction screen for plugging   Remove any debris that may have accumulated     Check for any buildup of silt on the floor of the cold water basin  Mentally note  the amount  if any  so future inspections will enable you to determine the rate  at which it is forming     Semi Annually  Relubricate motor according to the manufacturer s instruc   tions  See instructions on page 19     Check to see that all bolts are tight in the fan and mechanical equipment  region  including the fan guard  Use torque settings pr
24. nal Information         a avviLat eke re tete teka aea ta sanas se sanas asse satan anne               21  Troubleshooting               a inpe kapa anken ankinn di 22    Indicates presence of a hazard which can cause severe personal  injury  death or substantial property damage if ignored     Indicates presence of a hazard which will or can cause personal  injury or property damage if ignored     Indicates special instructions on installation  operation or main   tenance which are important but not related to personal injury  hazards     A Warning       Installation    The Marley QuadraFlow cooling tower purchased for this installation repre   sents the current state of the art in corrosion resistant cooling tower design  and construction  The QuadraFlow represents a major step forward in low     maintenance  long life cooling towers     These instructions   as well as those offered separately on motors  fans   Geareducers  driveshafts  float valves  etc    are intended to assure that the  tower serves you properly for the maximum possible time  Since the Quadra   Flow s warrantability may well depend upon your actions  please read these  instructions thoroughly prior to operation     If you have questions about the operation and or maintenance of this tower   and you don t find the answers in this manual  please contact your Marley  sales engineer  When writing for information  or when ordering parts  please  mention tower serial number shown on the tower s nameplate     To
25. nd its burden of dissolved solids to  concentrate in the remaining water  Given no means of control  this increasing    concentration of contaminants can reach a very high level     In order to achieve water quality which is acceptable to the cooling tower  as  well as the remainder of your circulating water system   the selected water  treatment company must work from a relatively constant level of concentra   tions  This stabilization of contaminant concentrations is usually accomplished  by blowdown  which is the constant discharge of a portion of the circulating  water to waste  As a rule  acceptable levels on which to base a treatment  schedule will be in the range of 2 4 concentrations  The following table gives  approximate rates of blowdown  percent of total water flow rate constantly  wasted  to achieve those concentrations at various cooling ranges     Blowdown Rate       Cooling Two Four  Range    F  Concentrations Concentrations  10 0 7  0 17    15 1 1  0 30   20 1 5  0 43      Range   Difference between hot water temperature entering the tower and cold water tempera   ture leaving the tower     When water treatment chemicals are added  they should not be in   troduced into the circulating water system via the cold water basin  of the cooling tower  Water velocities are lowest at that point  which  results in inadequate mixing     A Warning    A Warning       Maintenance    Schedule of Tower Maintenance    Included with this instruction packet are separate Service
26. ns which occasionally require  the services of an expert technician        Additional Information    Increased Load Requirements  QuadraFlow towers are designed such  that cells of either equal or unequal capacity can be added in the future  This  allows you to compensate for the load increases that normally occur with the  replacement or addition of production equipment and still retain continuity  with respect to your cooling tower system     Tower Renewal  Marley routinely rebuilds and upgrades cooling towers of  all materials and manufacture  If your tower ever reaches the limit of its service  life  we recommend that you investigate the cost of rebuilding before you  routinely order a new replacement tower     Each QuadraFlow tower includes a document package containing general  orientation drawings and manuals to accomplish field assembly and instal   lation  These drawings and manuals contain important information  relating to safe installation and operation of the cooling tower  A  separate installation drawing for each purchased option is included in the  document package  If you have purchased an option and can   t find the ap   propriate installation drawing  contact your local Marley sales representative  before proceeding     SPX also provides several sets of a separate packet of pertinent operating  and maintenance manuals  The manuals vary somewhat depending on the  tower model purchased     In addition  SPX publishes numerous technical reports including more d
27. o speed motor  check for proper rota   tion at both speeds  Check also to see that starter is equipped with  a 20 second time delay which prevents direct switching from high  speed to low speed  This delay will allow the fan to slow down and  will prevent abnormal stress from being applied to the mechanical  equipment and the electrical circuit components     4  Runthe motor and observe the operation of the mechanical equipment  Opera   tion should be stable  and there should be no evidence of oil leakage     If the water supply system is not being operated or if there is no  heat load on the system   motor amps read at this time may indicate  an apparent overload of as much as 10 20   This is because of the  increased density of unheated air flowing through the fan  Deter   mination of an accurate motor load should await the application of  the design heat load     General    The cold water temperature obtained from an operating cooling tower will vary  with the following influences     1  Heat Load  With the fan in full operation  if the heat load increases  the  cold water temperature will rise  If the heat load reduces  the cold water    temperature will reduce     Heat Load  Btu hr     Range    F     GPM x 500       Note that the number of degrees     range     through which the tower cools  the water is established by the system heat load and the amount of water  being circulated  in accordance with the following formula     The cooling tower establishes only the cold w
28. ons against wiring diagram on motor        Bad bearings    Electrical unbalance    Check lubrication  Replace bad bearings     Check voltage and currents of all three lines  Correct if required        Air gap not uniform    Check and correct bracket fits or bearing        Rotor unbalance    Rebalance        Cooling fan hitting end bell guard    Reinstall or replace motor fan        Fan noise Blade rubbing inside of fan cylinder    Adjust cylinder to provide blade tip clearance        Loose bolts in blade clamps    Check and tighten if necessary  Check fan blade pitch  Refer to  Fan Service Manual        Scale or foreign sub  Lack of or insufficient bleed off    See    Water Treatment    section of this manual        stance in water system Water treatment    Consult competent water treating specialist  See    Water    Treatment    section of this manual        Motor does not come up  to speed    Voltage too low at motor terminals  because of line drop    Check transformer and setting of taps  Use higher voltage on  transformer terminals or reduce loads  Increase wire size or  reduce inertia        Broken rotor bars    Look for cracks near the rings  A new rotor may be required   Have motor service center check motor        Wrong rotation  Motor  Wrong sequence of phases    Switch any two of the three motor leads        Excessive water drift Faulty drift elimination    1  See if all louvers and eliminators are in place and clean   2  Check to see that nozzles are in place and c
29. rn is to prevent the  formation of destructive ice on the cooling tower fill  Your understanding of  cold weather operation will be enhanced if you read Marley Technical Report   H 003      Operating Cooling Towers in Freezing Weather     available for down   load at spxcooling com  augmented by the following guidelines     1  Do not allow the tower   s leaving water temperature to drop  below a minimum allowable level about 40   F established as  follows     During the coldest days of the first winter of operation  observe whether  any ice is forming on the louver face  particularly near the bottom of the  louver face  If hard ice is present on the louvers  an appropriate elevation  in the allowable cold water temperature is mandatory  If the coldest pos   sible water is beneficial to your process  ice of a mushy consistency can  be tolerated   but routine periodic observation is advisable     If the minimum allowable cold water temperature is established at or near  minimum heat load  it should be safe for all operating conditions       4    11    A Caution    A Warning    12       Operation    Having established the minimum allowable cold water temperature   maintaining that temperature can be accomplished by fan manipulation   as outlined in Item 4 under Tower Operation on page 8  However  in  towers of more than one cell  the limiting temperature established applies  to the water temperature of the cell or cells operating at the highest fan  speed   not necessarily the n
30. wer Location    Space available around the tower should be as generous as possible to pro   mote ease of maintenance   and to permit freedom of airflow into and through  the tower  If you have questions about the adequacy of the available space  and the intended configuration of the tower  please contact your Marley sales  engineer for guidance     Prepare a stable  level support foundation for the tower  utilizing weight  wind  load  and dimensional information appearing on appropriate Marley submittal  drawings  Supports must be level to insure proper operation of the tower     The cooling tower must be located at such distance and direction  to avoid the possibility of contaminated tower discharge air being  drawn into building fresh air intake ducts  The purchaser should ob   tain the services of a Licensed Professional Engineer or Registered  Architect to certify that the location of the tower is in compliance  with applicable air pollution  fire  and clean air codes     Tower Shipment    QuadraFlow towers ship by truck  on flat bed trailers  in an unassembled  condition  Single cell towers ship on one truck  Multicell towers  depending  on their size  may require more than one truck  Responsibility for the condition  of the tower upon its arrival belongs to the trucker   as does the coordination  of multiple shipments  if required     Note       Installation    Receiving Tower    Prior to unloading the tower from the delivering carrier  inspect the shipment  for evidenc
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
MAC 300 - Textfiles.com  MicroCloud 5038ML  ポリエック  TC-741 manual (cable tester)  Hampton Bay CIL1692M Instructions / Assembly  Motor Lessons ABS (C..  取扱説明書 - AKTIO解体事業部  KANGOO  Radica Games MONSTER TRUCK 74026 User's Manual      Copyright © All rights reserved. 
   Failed to retrieve file