Eaton 5125 Rack-Mount UPS (5000/6000 VA) User`s Guide
Contents
1. Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 15 www eaton com powerquality SAFETY WARNINGS Advertencias de Seguridad INSTRUCCIONES DE SEGURIDAD IMPORTANTES GUARDE ESTAS INSTRUCCIONES Este manual contiene instrucciones importantes que debe seguir durante la instalaci n y el mantenimiento del SAI y de las bater as Por favor lea todas las instrucciones antes de poner en funcionamiento el equipo y guarde este manual para referencia en el futuro Este SAI contiene VOLTAJES MORTALES Todas las reparaciones y el servicio t cnico deben ser efectuados SOLAMENTE POR PERSONAL DE SERVICIO T CNICO AUT
2. 40 95
3. To hardwire the UPS 1 If you are installing power management software connect your computer to the USB port UPS communication port or optional X Slot card see page 47 For the communication port use only the serial cable supplied in the accessory kit 2 Switch off utility power at the distribution point where the UPS will be connected Be absolutely sure there is no power Communication Load Segment USB Port Port Circuit Breakers Battery Circuit Breaker 0 Je 47 7 p 0 N Eu E lg ao IEC 320 C13 T Receptacles LET Il Ji y Battery Connector REPO Port Terminal IEC 320 C19 Receptacles Block Cover Figure 17 PW5125 6000 HW UPS Rear Panel 3 Remove the terminal block cover and the wiring knockouts Retain the terminal block cover 4 Pull the input and output wires through separate conduit leaving approximately 0 5m 2 ft of exposed wire Attach a flexible metal fitting to the end of each conduit 5 Insert each conduit through a wiring access entry and attach the conduit fitting to the panel Strip 1 5 cm 0 5 of insulation from the end of each incoming wire 6 Connect the input and ground wires to the terminal block according to Figure 18 and Table 1 7 Connect the output and ground wires to the terminal block according to Figure 18 and Table 1 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D
4. Communication Load Segment USB Port Port Circuit Breakers Battery Circuit Breaker X Slot N Communication m m Bay wl CNE CN M e Ne U 16 20 NED i Receptacles Ground TATARSTAN Bonding Screw 020 092 002 205 IEEE Battery Connector REPO PON IEC 320 C13 Receptacles Power Cord with L6 30 Plug 16 30 Receptacle Figure 15 PW5125 5000 UPS Rear Panel Communication Load Segment USB Port Port Circuit Breakers Battery Circuit Breaker X Slot Communication E le J EEE IEC 320 013 n _ Receptacles Ground Bonding Screw Jl JN Ji e Battery Connector 9 Port IEC 320 C19 Receptacles Power Cord with 32A 1EC 309 Plug D IEC 309 324 Receptacle Figure 16 PW5125 6000i UPS Rear Panel 32 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality 3 INSTALLATION Plug the equipment to be protected into the appropriate UPS output receptacles see page 51 for more information on load segments NOTE DO NOT protect laser printers with the UPS because of the exceptionally high power requirements of the heating elements NOTE Verify that the total equip
5. E 22 EBM Cable EBM Battery Connectors EM m ri Im Battery Circuit Breakers Figure 31 EBM Connections 58 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality UPS MAINTENANCE Recycling the Used Battery or UPS Contact your local recycling or hazardous waste center for information on proper disposal of the used battery or UPS e Do not dispose of the battery or batteries in a fire Batteries may explode Proper disposal of batteries is required Refer to your local codes for disposal requirements e Do not open or mutilate the battery or batteries Released electrolyte is harmful to the skin and eyes It may be toxic CAUTION Do not discard the UPS or the UPS batteries in the trash This product contains sealed lead acid batteries and must be disposed of properly For more information contact your Pb local recycling reuse or hazardous waste center CAUTION Do not discard waste electrical or electronic equipment WEEE in the trash For proper disposal contact your local recycling reuse or hazardous waste center Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 59 www eaton com powerquality UPS MAINTENANCE 60 Eaton 5125 Rack
6. e Netledningen m ikke fjernes og stikket m ikke tr kkes ud mens UPS en er t ndt Dette fjerner sikkerhedsjorden fra UPS en og fra det udstyr der er sat til e Installer denne UPS i et temperatur og fugtighedskontrolleret indend rsmilj frit for ledende forureningsstoffer for at formindske risikoen for brand og elektrisk st d Rumtemperaturen m ikke overstige 40 C UPS en b r ikke betjenes n r vand eller h j fugtighed maksimalt 95 4 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality SAFETY WARNINGS For UPS systemer med h rdledningsudgange skal overstramsbeskyttelse for vekslestrammens udgangskredslgb forsynes af andre For UPS systemer med h rdledningsudgange skal egnede nominelle afbryderkontakter for vekslestrgmmens udgangskredslgb forsynes af andre ADVARSEL Batterierne kan give risiko for elektrisk stgd eller brands r for rsaget af hgj kortslutningsstram Overhold gaeldende forsigtighedsregler Servicering skal udfgres af kvalificeret servicepersonale med kendskab til batterier og g ldende forsigtighedsregler Hold uautoriseret personale v k fra batterierne Korrekt bortskaffelse af batterier er p kraevet Overhold g ldende lokale regler for bortskaffelsesprocedurer Skaf dig aldrig af med batterierne ved at braende dem Batterierne kan eksplodere ved ben ild Belangrijke Veiligheidsinstructies BELANGRIJKE VEILIG BEWAAR D
7. Figure 26 UPS Load Segments PW5125 5000 Model Shown Load Segment 1 Load Segment 2 Circuit Breake Circuit Breaker Load Segment 2 Load Segment 1 Figure 27 UPS Load Segments PW5125 6000 HW Shown Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 51 www eaton com powerquality ADDITIONAL UPS FEATURES 52 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality Chapter 7 UPS Maintenance This section explains how to Care for the UPS and batteries Replace the electronics module Replace the batteries Recycle used batteries or UPS UPS and Battery Care For the best preventive maintenance keep the area around the UPS clean and dust free If the atmosphere is very dusty clean the outside of the system with a vacuum cleaner For full battery life keep the UPS at an ambient temperature of 25 C 77 F NOTE If the UPS requires any type of transportation verify that the battery circuit breaker on the UPS rear panel is in the OFF 0 position see Figure 31 on page 58 NOTE The batteries in the UPS are rated for a 3 5 year service life The length of service life varies depending on the f
8. Company shall not be responsible for any charges for testing checking removal or installation of Warranted Items COMPANY DOES NOT WARRANT EQUIPMENT NOT MANUFACTURED BY COMPANY IF PERMITTED BY THE APPLICABLE MANUFACTURER COMPANY SHALL PASS THROUGH SUCH MANUFACTURER S WARRANTIES TO END USER COMPANY DOES NOT WARRANT SOFTWARE INCLUDING SOFTWARE EMBEDDED IN PRODUCTS THAT IS NOT CREATED BY COMPANY WITHOUT LIMITING THE FOREGOING COMPANY SPECIFICALLY DOES NOT WARRANT SOFTWARE SUCH AS LINUX THAT WAS CREATED USING AN OPEN SOURCE MODEL OR IS DISTRIBUTED PURSUANT TO AN OPEN SOURCE LICENSE THIS WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY OFFERED BY COMPANY WITH RESPECT TO THE PRODUCTS AND SERVICES AND EXCEPT FOR SUCH FOREGOING WARRANTY COMPANY DISCLAIMS ALL OTHER WARRANTIES INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY TITLE NON INFRINGEMENT AND FITNESS FOR A PARTICULAR PURPOSE CORRECTION OF NON CONFORMITIES IN THE MANNER AND FOR THE PERIOD OF TIME PROVIDED ABOVE SHALL CONSTITUTE COMPANY S SOLE LIABILITY AND END USER S EXCLUSIVE REMEDY FOR FAILURE OF COMPANY TO MEET ITS WARRANTY OBLIGATIONS WHETHER CLAIMS OF THE END USER ARE BASED IN CONTRACT IN TORT INCLUDING NEGLIGENCE OR STRICT LIABILITY OR OTHERWISE LIMITATION OF LIABILITY The remedies of the End User set forth herein are exclusive and are the sole remedies for any failure of Company to comply with its obligations hereunder In no event shall Company b
9. Chapter 1 Introduction The Eatone 5125 uninterruptible power system UPS protects your sensitive electronic equipment from basic power problems such as power failures power sags power surges brownouts and line noise Power outages can occur when you least expect it and power quality can be erratic These power problems have the potential to corrupt critical data destroy unsaved work sessions and damage hardware causing hours of lost productivity and expensive repairs With the Eaton 5125 you can safely eliminate the effects of power disturbances and guard the integrity of your equipment The Eaton 5125 is designed for critical applications such as workstations servers networks telecommunications equipment and rack applications Figure 1 shows the Eaton 5125 UPS with an optional Extended Battery Module EBM Figure 1 The Eaton 5125 UPS with Optional EBM Providing outstanding performance and reliability the Eaton 5125 s unique benefits include the following e ABMe technology that uses advanced battery management to increase battery service life optimize recharge time and provide a warning before the end of useful battery life Hours of extended runtime with up to four EBMs e Start on batt
10. INSTALLATION 13 Switch all battery circuit breakers to the ON position 14 If an emergency power off disconnect switch is required by local codes see Remote Emergency Power off Installation on page 30 to install the REPO switch before powering on the UPS 15 Switch the main utility breaker on The indicator flashes indicating the UPS is in Standby mode with the equipment offline 16 Press and hold the On button for approximately three seconds The indicator illuminates solid and the load level indicators display the percentage of load being applied to the UPS The UPS is now in Normal mode and supplying power to your equipment If the alarm beeps or a UPS alarm indicator stays on see Table 10 on page 66 To change the factory set defaults see Configuration on page 43 17 If you installed an optional REPO test the REPO function Activate the external REPO switch De activate the external REPO switch and restart the UPS 18 If optional EBMs are installed continue to Configuration on page 43 to specify the number of 5 installed NOTE The batteries charge to 80 capacity in approximately 3 hours However it is recommended that the batteries charge for 48 hours after installation or long term storage Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 37 www eaton com powerquality INSTALLATION 38 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Re
11. include reimbursement for or restoration of any data loss This Guaranty does not cover any defects or damages caused by a failure to properly store the Product before installation including the charge of batteries no later than the date indicated on the packaging b shipping and delivery of the Product if shipping is FOB Factory c neglect accident abuse misuse misapplication or incorrect installation of Product d repair or alteration of Product not authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or Agent e improper testing operation maintenance adjustment or modification of any kind to the Product not authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or Agent or f use of the Product under other than normal operating conditions or in a manner inconsistent with the Product s labels or instructions This Guaranty is not valid a unless the End User returns to Company the Warranty Registration Card or completes the registration form on www eaton com PQ Register within thirty 30 days of purchase or b if the Product s serial numbers have been removed or are illegible Company shall not be responsible for any charges for testing checking removal or installation of any items LIMITATION OF LIABILITY THE REMEDIES OF THE END USER SET FORTH HEREIN ARE EXCLUSIVE AND ARE THE SOLE REMEDIES FOR ANY FAILURE OF C
12. Contact your service representative Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 19 www eaton com powerquality INSTALLATION Installation Overview Assemble the rails UPS and EBM in the rack see page 21 Install the UPS internal batteries see page 27 i Are you installing optional EBMs Yes No See Extended Battery Module Installation on page 29 See Remote Emergency Power off Installation on page 30 UPS have receptacles Are you Vad installing a REPO gt switch Does th oes the Yes See Plug Receptacle UPS Installation on page 32 See Hardwired UPS Installation on page 34 i Installation is complete 20 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality INSTALLATION Installing the Rail Kit The rail kit can be mounted in 48 cm 19 inch panel racks from 61 to 76 cm 24 to 30 inches deep and includes e Left and right adjustable rail assemblies Two rear hold down brackets Two mounting brackets e Four U shaped 10 32 clip nuts Twelve hex head screws e Four 46 32 x 3 8 flat head screws 8 NOTE Mounting rails are required for each individual cabinet NOTE If placed in a rack with existing equipment the rack must be reconfigured to install the heaviest i
13. Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality Chapter 8 Table 4 Model List Specifications This section provides the following specifications Model list Electrical input and output Weights and dimensions Environmental and safety e Battery Model Number Power Levels Rated at Nominal Inputs LUPUS connectors Output Connections PW5125 5000 5000 VA 4500W L6 30P power cord 1 L6 30R 2 L6 20R 4 10A IEC 320 C13 PW5125 6000i PW5125 6000 HW 32A IEC 309 power cord 1 IEC 309 32A 4 15A IEC 320 C19 4 10A IEC 320 C13 6000 VA 5400W Hardwired 4 15A IEC 320 C19 4 10A IEC 320 C13 Hardwired Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerguality 61 SPECIFICATIONS Table 5 Electrical Input and Output Nominal Voltage PW5125 5000 and PW5125 6000 HW 200 208 220 230 240V selectable PW5125 6000i 220 230 240V selectable Voltage Range 160 288V nominal Nominal Frequency 50 60 Hz auto sensing Frequency Range 50 Hz 46 54 Hz 4 60 Hz 56 64 Hz 4 Noise Filtering MOVs and line filter for normal and common mode noise Input Power Factor gt 0 95 Regulation 10 to 6 of nominal voltage Normal Mode Regulation Nominal output voltage 5 Battery Mode Voltage Waveform Normal mode Sine wave lt 5 THD with typical PFC load Battery mo
14. O 51 75 26 50 25 0 25 Figure 20 Load Level Indicators When all of the load level indicators and the indicator are illuminated power requirements exceed UPS capacity see page 68 for more information Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 41 www eaton com powerquality OPERATION 42 Battery Mode When the UPS is operating during a power outage the alarm beeps intermittently the indicator illuminates and the indicator flashes When utility power returns the UPS transfers to Normal mode operation while the battery recharges If battery capacity becomes low while in Battery mode the indicator starts flashing and the alarm becomes continuous Immediately complete and save your work to prevent data loss and similar difficulties When utility power is restored after the UPS shuts down the UPS automatically restarts The indicator flashes until the battery has recharged to an acceptable level Bypass Mode In the event of a UPS overload or internal failure the UPS transfers your equipment to utility power Battery mode is not available however the utility power continues to be passively filtered by the UPS The alarm sounds and the indicator illuminates red The UPS transfers to Bypass mode when The UPS has an overtemperature condition The UPS has an overload condition of 102 to 11096 for 2 minutes The UPS has an overload condition 11096 for 12 cyc
15. a um OO i 1 Status LED yellow Off Me DP Switch 12 On Additional Ethernet Connectors COM Port 50 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality Reset Button Figure 25 ConnectUPS X Panel Details Load Segments ADDITIONAL UPS FEATURES Load segments are sets of receptacles that can be controlled by power management software providing an orderly shutdown and startup of your equipment For example during a power outage you can keep key pieces of equipment running while you turn off other equipment This feature allows you to save battery power See your power management software manual for details refer to the Software Suite CD or www eaton com powerquality for the latest information NOTE If power management software is not used the individual load segments cannot be controlled NOTE The circuit breaker for Load Segment 1 does not include the corded receptacle or terminal block Each UPS has two load segments as shown in Figure 26 and Figure 27 Load Segment 1 Load Segment 2 Circuit Breaker Circuit Breaker Bl 16 Ns N E ME E egmen e Ne E Load 020 Goo vo Geo ER Segment 1 EA o jp lo
16. com powerquality SAFETY WARNINGS B 200 240 B 0 100 120
17. da permane am energizadas Se a alimenta o da sua aplica o for do tipo fase neutro como ocorre na maioria das aplica es na Europa a tens o das tomadas de sa da de 0 V Com a alimenta o fase fase a tens o das tomadas de sa da de 100 120V medida como fase terra ou fase neutro dependendo da instala o el trica do no break remova ou desconecte cabo de entrada quando a UPS estiver ligada Isto remover o aterramento de seguran a da UPS e do equipamento conectado Para reduzir o risco de inc ndios ou choques el tricos instale a UPS em ambiente interno com temperatura e umidade controladas e livres de contaminadores condut veis A temperatura ambiente n o deve exceder 40 C N o opere pr ximo a gua ou em umidade excessiva m x 95 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 13 www eaton com powerquality SAFETY WARNINGS e Para sistemas UPS com sa das conectadas a prote o de sobrecarga para circuitos de sa da de corrente alternada deve ser fornecida por outros Para sistemas UPS com sa das conectadas interruptores de desconex o devidamente qualificados para circuitos de sa da de corrente alternada devem ser fornecidos por outros e As baterias podem oferecer risco de choque el trico ou queimadura ocasionados por alta tens o com possibilidade de curto circuito Tome as precau es adequadas A manuten o deve ser realizada por pessoal qual
18. eer tate t e ne gen t HO De eS e RA aa 7 UPS Maintenance ssc asi mx x nre une e RR Falc UPS and B ttery Gare went 0 eR dep en mekin Storing the UPS and Batteries es ex pubes KUKAN oe e AERE dq es Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerguality TABLE OF CONTENTS 10 Replacing the Electronics Module When to Replace Batteries entes tex de e Replacing Batteries os det ee eec ht eue IE ah ars etui RO TE S How to Replace UPS Internal Batteries How to Replace Extended Battery Modules Recycling the WSed BattenyorUPS maanosa t Fete da eo eR rele Specificatl lis css tes Due rep au Troubleshooting usares s sa ex oe x ERA EE YA e CR E OX ED Audible Alarms and UPS Conditions Silencing an Audible Alarm Service and Support aester ped bcc e eet tte e bebo Ca ana Warranty u 2 oce us e e Sus a ra Nen Two Year Limited Warranty with Extension to Three Year Limited Warranty US and Canada Load Protection Guarantee US and Canada en Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality 54 55 55 56 57 59 61 65 65 65 69 71 7 73
19. for the rear hex head screws If you are installing additional rails the next rail should be placed 7 holes above the last installed screw Position 13 Second Rail Position 11 Position 4 First Rail Position 2 Figure 5 Rear Rail Screw Positions 5 LIT eo e Clip Nuts b LI XX X3 X3 6 6 6 66 Figure 6 Securing the Rear Rail Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 23 www eaton com powerquality INSTALLATION 5 Repeat Steps 3 and 4 for the other rail 6 Tighten the assembly wing nuts on both rail assemblies 7 Place the UPS on a flat stable surface with the front of the UPS facing toward you 8 Align the mounting brackets with the screw holes on the sides of the UPS and secure with the supplied 46 32 x 3 8 flat head screws see Figure 7 9 If installing optional EBMs repeat Steps 7 and 8 for each cabinet Mounting Bracket Figure 7 Installing the Mounting Brackets 24 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality INSTALLATION CAUTION The UPS and EBM are heavy see page 62 A minimum of two people are required to lift the cabinets into the rack NOTE The EBMs must be installed below the UPS as shown in Figure 8 10 Slide
20. lead acid Charging Internal battery approximately 3 hours to 80 usable capacity at nominal line voltage after full load discharge External battery no more than 15x discharge time to 90 usable capacity at nominal line voltage after full load discharge Monitoring Advanced monitoring for earlier failure detection and warning Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D e3 www eaton com powerquality SPECIFICATIONS Table 9 Battery Runtimes in Minutes 5000 VA 4500W Models Load Weg 1 EBM 42 EBMs 43 EBMs 4 EBMs Batteries 900W 59 169 303 452 612 1350W 39 108 192 284 384 1800W 26 79 138 204 274 2250W 19 61 106 156 210 2700W 15 49 85 125 168 3150W 12 41 71 104 139 3600W 9 31 60 88 118 4050W 8 27 52 76 102 4500W 7 24 46 67 89 6000 VA 5400W Models Load PAS ILU 1 EBM 2 EBMs 43 EBMs 44 EBMs Batteries 1080W 49 138 247 367 497 1620W 33 88 156 230 311 2160W 20 64 111 164 221 2700W 15 49 85 125 168 3240W 11 40 68 100 134 3780W 9 33 57 83 111 4320W 7 25 48 70 94 4860W 6 22 42 61 81 5400W 5 19 36 53 7 NOTE Battery times are approximate and vary depending on the load configuration and battery charge 64 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality Chapter 9 Troubleshooting This section explains UPS alarms and conditions How to silence an alarm e Service and sup
21. of their respective companies Copyright 2004 2010 Eaton Corporation Raleigh NC USA All rights reserved No part of this document may be reproduced in any way without the express written approval of Eaton Corporation Class A EMC Statements FCC Part 15 NOTE This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense ICES 003 This Class A Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment Regulations ICES 003 Cet appareil num rique de la classe A respecte toutes les exigences du Reglement sur le mat riel brouilleur du Canada IEC 62040 2 Some configurations are classified under IEC 62040 2 as Class A UPS for Unrestricted Sales Distribution For these configurations the following applies WARNING This is a Class A UPS Product In a domestic environment this product may cause radio interfer
22. options see Figure 21 and Table 2 Scrolling past the last LED returns to the first configuration option If you press the On button and nothing happens the UPS is still in Operation mode Repeat Step 1 to enter Configuration mode and then perform Step 2 Press the Off 1 button ONCE to select the Voltage or Extended Battery Module EBM option or to toggle the Site Wiring Fault Alarm on or off 1 NOTE The UPS exits Configuration mode automatically after two minutes of inactivity 4 Press the button to confirm the selection and exit Configuration mode If you do not press the button the UPS defaults to the original settings Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 43 www eaton com powerquality CONFIGURATION 0 0 Press and hold the On and Alarm Reset Press the On button to buttons simultaneously to enter scroll to the next option Configuration mode ea EN On Button 0 O O NO 10060 0 Off Butt 0 Bane e 25 O Ss Alarm Reset Button 6 0 Configuration Mode LEDs Press the Off button ONCE to Press the Alarm Reset button select the option to save the setting and exit Configuration mode Figure 21 Using Configuration Mode Table 2 Configuration Mode LEDs and Options Configuration Mode L
23. sa propre source d alimentation batteries Il est possible que les prises de sortie soient sous tension m me lorsque l onduleur n est pas connect e une alimentation CA e Ence qui concerne les mod les 200 240 V il est possible que les prises de sortie restent sous tension Si la source d alimentation de votre application est c bl e phase et neutre comme dans la majorit des applications europ ennes la tension vers les prises de sortie est de 0 V Avec un c blage d entr e phase phase la tension vers les prises de sortie est de 100 120 V mesur e entre phase et terre ou phase et neutre suivant le c blage de l onduleur e Ne pas retirer le cordon d alimentation lorsque l onduleur est sous tension sous peine de supprimer la mise la terre de l onduleur et du mat riel connect Pour r duire les risques d incendie et de d charge lectrique installer l onduleur uniquement l int rieur dans un lieu d pourvu de mat riaux conducteurs o la temp rature et l humidit ambiantes sont contr l es La temp rature ambiante ne doit pas d passer 40 C Ne pas utiliser proximit d eau ou dans une atmosph re excessivement humide 95 96 maximum e Pour les models l onduleur ayant des sorties c bl es la protection contre une surintensit pour le s circuit s de sortie de courant alternatif doit tre fournie par un autre fournisseur e Pour les models l onduleur ayant des sorties c bl es le
24. service m kun utf res av AUTORISERT SERVICEPERSONALE BRUKERE KAN IKKE UTF RE SERVICE NOEN AV DELENE i UPS en e UPS enheten inneholder sin egen energikilde batterier Utgangsstikkene kan v re str mf rende selv n r UPS enheten ikke er koblet til et str muttak e Utgangsstikkene kan v re str mf rende for 200 240V modellene Spenningen til gangsstikkene vil v re 0 V dersom din enhets str mkilde er fase til n ytral som p de este europeiske enheter Med ledningsf rt fase til fase inngang vil spenningen til gangsstikkene v re 100 120V m lt fra fase til jord eller fase til n ytral avhenging av PS ledningsf ringen r mforsyningskabelen m ikke fjernes eller trekkes ut n r UPS en er p slik at ikke sikkerhetsjordingen fjernes fra UPS en og det utstyret som er forbundet med den e For 8 redusere fare for brann eller elektriske st t b r denne UPS en installeres i et innendgrs miljg med kontrollert temperatur og luftfuktighet som er fritt for ledende forurensende stoffer Romtemperaturen m ikke overskride 40 C Den m ikke brukes i naerheten av vann eller ved meget hay luftfuktighet 95 maks e For UPS systemer med fastkoplete uttak m overstramvern for vekselstramuttak ene stilles til r dighet av andre e For UPS systemer med fastkoplete uttak m passende utkoplingsbrytere for vekselstramuttaklene stilles til r dighet av andre 12
25. service representative Please have the following information ready when you call the Help Desk Model number e Serial number e Version number if available e Date of failure or problem e Symptoms of failure or problem e Customer return address and contact information If repair is reguired you will be given a Returned Material Authorization RMA Number This number must appear on the outside of the package and on the Bill Of Lading if applicable Use the original packaging or reguest packaging from the Help Desk or distributor Units damaged in shipment as a result of improper packaging are not covered under warranty A replacement or repair unit will be shipped freight prepaid for all warrantied units NOTE For critical applications immediate replacement may be available Call the Help Desk for the dealer or distributor nearest you Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 69 www eaton com powerquality TROUBLESHOOTING 70 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality Chapter 10 Warranty Two Year Limited Warranty with Extension to Three Year Limited Warranty US and Canada Eaton UPS Models 3105 5110 5115 5125 and 5130 WARRANTOR The warrantor for the limited warranties set forth herein is Eaton Corporation an Ohio Corporation company Company LIMITED WARRANTY This limited warranty this Warranty applies
26. the USB port on the UPS rear panel see Figure 22 Connect the other end of the USB cable to the USB port on your computer EB 2 USB Port Figure 22 The USB Port 2 Install the LanSafe software and USB drivers according to the instructions provided with the Software Suite CD Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 47 www eaton com powerquality ADDITIONAL UPS FEATURES DB 9 Communication Port To establish communication between the UPS and a computer connect your computer to the UPS communication port using the supplied communication cable When the communication cable is installed power management software can exchange data with the UPS The software polls the UPS for detailed information on the status of the power environment If a power emergency occurs the software initiates the saving of all data and an orderly shutdown of the equipment Figure 23 identifies the cable pins and Table 3 describes the pin functions 0000 00006 Figure 23 Communication Port Table 3 Communication Port Pin Assignment Pin Number Signal Name Function Direction from the UPS 1 Low Batt Low Battery relay contact 20 mA 30 Vdc contact rating Out 2 TxD Transmit to external device Out 3 RxD Receive from external device In 4 DTR PnP Plug and Play from external device tied to Pin 6 In 5 GND Signa
27. 35 www eaton com powerguality INSTALLATION OM GROUND 98 INPUT NEUTRAL I 1 I I 12 INPUT LINE TE OUTPUT NEUTRAL OO OUTPUT LINE OM toutPuT GROUND 1 r Figure 18 UPS Terminal Block Table 1 UPS Wiring Specifications Wire Terminal 2 Terminal Wire Tightening Function Position Aids iso Function Size Rating Torque Input 4 Input Neutral 25 16 mm 3 Input Line 14 6 AWG i Output 2 Output Neutral 25 16 mm Tem 1 Output Line 14 6 AWG Use 2 0 mm 10 AWG 75 copper wire minimum 8 Replace the terminal block cover 9 f your rack has conductors for grounding or bonding of ungrounded metal parts connect the ground cable not included to the ground bonding screw 10 Plug the equipment to be protected into the appropriate UPS output receptacles see page 51 for more information on load segments NOTE DO NOT protect laser printers with the UPS because of the exceptionally high power requirements of the heating elements NOTE Verify that the total equipment ratings do not exceed the UPS capacity to prevent an overload alarm 11 Verify that all load segment circuit breakers are in the ON position 12 Remove the breaker tie from all battery circuit breakers 36 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality
28. Connect isolated normally open dry contacts rated to handle 60 Vdc maximum 30 Vac RMS maximum and 20 mA maximum across the REPO device to Pin 1 and Pin 2 see Figure 14 Use stranded non shielded wiring size 0 75 mm 0 5 mm 18 20 AWG 1 NOTE A separate contact must simultaneously cause UPS input AC power to be removed Pin 1 Pin 2 L Figure 14 REPO Connector 4 Reconnect the REPO connector to the REPO port 5 Verify that the externally connected REPO switch is not activated to enable power to the UPS output Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 31 www eaton com powerquality INSTALLATION Plug Receptacle UPS Installation NOTE Do not make unauthorized changes to the UPS or accessories otherwise damage may occur to your equipment and void your warranty To install a plug receptacle UPS 1 If you are installing power management software connect your computer to the USB port UPS communication port or optional X Slot card see page 47 For the communication port use only the serial cable supplied in the accessory kit 2 f your rack has conductors for grounding or bonding of ungrounded metal parts connect the ground cable not included to the ground bonding screw
29. E Pull the battery trays out onto a flat stable surface See Recycling the Used Battery or UPS on page 59 for proper disposal Figure 30 Removing the Battery Trays Slide the left battery tray into the chassis Repeat for the right battery tray Reinstall the battery retaining bracket removed in Step 2 Replace the UPS front cover How to Replace Extended Battery Modules CAUTION The Extended Battery Module EBM is heavy see page 62 A minimum of two people are required to lift the EBM when it is replaced To replace the EBMs 1 Switch all battery circuit breakers to the OFF position see Figure 31 Unplug the EBM cable from the UPS If additional EBMs are installed unplug the EBM cable from the battery connector on each EBM Install the supplied mounting brackets on the new EBM Replace the EBM See Recycling the Used Battery or UPS on page 59 for proper disposal Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 57 www eaton com powerquality UPS MAINTENANCE 5 Plug the EBM cable into the UPS as shown in Figure 31 For additional EBMs plug the EBM cable into the battery connector on the adjacent EBM 6 Remove the breaker tie from the circuit breaker on all EBMs 7 Switch all battery circuit breakers to the ON position Battery Circuit N y 5 e Breaker NA gt pan UPS Battery 20 e Connector
30. EDs Option LED Status Explanation IAD v 200 208V On Selecting this option changes the nominal output voltage to Nominal Output 200 208V 0 O O O Voltage Default for PW5125 5000 models Flashing 200 208V is disabled one of the other output voltage options is selected 60 Vv 220V Nominal On Selecting this option changes the nominal output voltage to Output Voltage 220V Queer FOLD FO Flashing 220V is disabled one of the other output voltage options is selected PESE Av 230V Nominal On Selecting this option changes the nominal output voltage to Output Voltage 230V 00 Default for PW5125 60001 and PW5125 6000 HW models Flashing 230V is disabled one of the other output voltage options is selected B 240V Nominal On Selecting this option changes the nominal output voltage to Output Voltage 240V O O i Ru ne Flashing 240V is disabled one of the other output voltage options is selected 44 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality Configuration Mode CONFIGURATION LEDs Option LED Status Explanation AD Vv Site Wiring On Alarm sounds when the polarity of the outlet is reversed or the Fault Alarm ground connection is missing have a qualified electrician o O O O e repair the outlet wiring Flashing Alarm DOES NOT sound when the polarity of the outlet is default reverse
31. EZE HEIDSINSTRUCTIES INSTRUCTIES Deze handleiding bevat belangrijke instructies die u dient te volgen tijdens de installatie en het onderhoud van de UPS en de accu s Lees alle instructies voordat u de apparatuur in bedrijf neemt en bewaar deze handleiding als naslagwerk A Deze UPS bevat LEVENSGEVAARLIJKE ELEKTRISCHE SPANNING Alle reparaties en onderhoud dienen UITSLUITEND DOOR ERKEND SERVICEPERSONEEL te worden uitgevoerd Er bevinden zich GEEN ONDERDELEN in de UPS die DOOR DE GEBRUIKER kunnen worden GEREPAREERD Deze UPS bevat een eigen energiebron batterijen De uitgangscontactdoos kan onder spanning staan zelfs wanneer de UPS niet is aangesloten op de netspanning Bij de modellen van 200 240V kan de uitgangscontactdoos onder spanning blijven staan Als de bedrading van de ingangsspanningsbron in uw systeem loopt van fase naar aarde zoals bij de meeste Europese systemen dan bedraagt de spanning op de uitgangscontactdozen O V Als de ingangsb edrading loopt van fase naar fase dan bedraagt de spanning op de uitgangscontactdozen 100 120V gemeten tussen fase en aarde of tussen fase en neutraal afhankeli Eaton 5125 Rack Mount UPS 5000 6000 VA jk van de UPS bedrading User s Guide 164201541 Rev D www eaton com powerquality a SAFETY WARNINGS e Verwijder de ingangsnoer niet of haal de stekker van de ingangsnoer er niet uit terwijl de UPS aan staat Hierdoor zou de UPS en uw
32. Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality SAFETY WARNINGS FORSIKTIG e Batterier kan utgj re en fare for elektrisk st t eller branns r pga h y kortsluttingsstram Treff passende forholdsregler Service b r utf res av kvalifisert servicepersonale med kjennskap til batterier og n dvendige forholdsregler Hold uautorisert personale borte fra batteriene Batterier m fjernes p korrekt m te Se lokale forskrifter vedr rende krav om fjerning av batterier e Kast aldri batterier i flammer da de kan eksplodere hvis de utsettes for pen ild Regulamentos de Seguranca INSTRU ES DE SEGURAN A IMPORTANTES GUARDE ESTAS INSTRU ES Este manual cont m instru es importantes que devem ser seguidas durante a instala o e manuten o do no break e das baterias Leia todas as instru es antes de operar o equipamento e guarde este manual para consult lo futuramente CUIDADO A UPS cont m VOLTAGEM MORTAL Todos os reparos e assist ncia t cnica devem ser executados SOMENTE POR PESSOAL DA ASSIST NCIA T CNICA AUTORIZADO N o h nenhuma PE A QUE POSSA SER REPARADA PELO USU RIO dentro da UPS ADVERT NCIA Este no break possui sua pr pria fonte de energia baterias As tomadas de sa da podem estar energizadas mesmo que o no break n o esteja conectado a uma fonte de energia el trica Nos modelos 200 240V pode ser que as tomadas de sa
33. OMPANY TO COMPLY WITH ITS OBLIGATIONS HEREUNDER EXCEPT AS OTHERWISE PROVIDED FOR IN THIS GUARANTY IN NO EVENT SHALL COMPANY BE LIABLE IN CONTRACT IN TORT INCLUDING NEGLIGENCE OR STRICT LIABILITY OR OTHERWISE FOR DAMAGE TO PROPERTY OR EQUIPMENT OTHER THAN THE PRODUCTS INCLUDING LOSS OF PROFITS OR REVENUE LOSS OF USE OF PRODUCTS LOSS OF DATA COST OF CAPITAL CLAIMS OF CUSTOMERS OF THE END USER OR ANY SPECIAL INDIRECT INCIDENTAL OR CONSEQUENTIAL DAMAGES WHATSOEVER THE TOTAL CUMULATIVE LIABILITY OF COMPANY HEREUNDER WHETHER THE CLAIMS ARE BASED IN CONTRACT INCLUDING INDEMNITY IN TORT INCLUDING NEGLIGENCE OR STRICT LIABILITY OR OTHERWISE SHALL NOT EXCEED THOSE SET FORTH ABOVE Company shall not be responsible for failure to provide repair or replacement under this Guaranty due to causes beyond Company s reasonable control END USER S OBLIGATIONS In order to receive the benefits of this Guaranty the End User must use the Product in a normal way follow the Product s user s guide and protect against further damage to the Product if there is a covered defect OTHER LIMITATIONS Company s obligations under this Guaranty are expressly conditioned upon receipt by Company of all payments due to it including interest charges if any During such time as Company has not received payment of any amount due to it for the Product in accordance with the contract terms under which the Product is sold Company shall have no obligation under thi
34. ORIZADO No hay NINGUNA PARTE QUE EL USUARIO PUEDA REPARAR dentro del SAI ADVERTENCIA e Este SAI contiene su propia fuente de energ a bater as Los recept culos de salida pueden transportar voltaje activo aun cuando el SAI no est conectado con una fuente de CA e Para los modelos 200 240V es posible que los recept culos de salida permanezcan el ctricamente activos Si la fuente de energ a de entrada de su aplicaci n est cableada de l nea a neutro como la mayor a de las aplicaciones europeas el voltaje a los recept culos de salida es OV Con cableado de entrada de l nea a l nea el voltaje hacia los recept culos de salida es 100 120V medido de l nea a tierra o de l nea a neutro lo que depender del cableado del SAI e No retire o desenchufe el cable de entrada mientras el SAI se encuentre encendido Esto suprime la descarga a tierra de seguridad del SAI y de los equipos conectados al SAI Para reducir el riesgo de incendio o de choque el ctrico instale este SAI en un lugar cubierto con temperatura y humedad controladas libre de contaminantes conductores La temperatura ambiente no debe exceder los 40 C No trabaje cerca del agua o con humedad excesiva 9596 m ximo e los sistemas SAI con salidas cableadas permanentamente la protecci n contra exceso de corriente para el los circuitos de CA de salida ser suministrada por terceros e los sistemas SAI con salidas c
35. Powerware Series Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide E T N Powering Business Worldwide This product is covered by one or more of the following US Patent numbers 5177676 6314007 6330176 6391489 6483730 and 6599657 Requesting a Declaration of Conformity Units that are labeled with a CE mark comply with the following harmonized standards and EU directives e Harmonized Standards IEC 62040 1 1 and IEC 62040 2 IEC 60950 Third Edition EU Directives 73 23 EEC Council Directive on equipment designed for use within certain voltage limits 93 68 EEC Amending Directive 73 23 EEC 89 336 EEC Council Directive relating to electromagnetic compatibility 92 31 EEC Amending Directive 89 336 EEC relating to EMC The EC Declaration of Conformity is available upon request for products with a CE mark For copies of the EC Declaration of Conformity contact Eaton Power Quality Oy Koskelontie 13 FIN 02920 Espoo Finland Phone 358 9 452 661 Fax 358 9 452 665 68 Eaton Powerware ABM FERRUPS LanSafe and X Slot are registered trademarks and ConnectUPS is a trademark of Eaton Corporation or its subsidiaries and affiliates Modbus is a registered trademark of Schneider Automation Microsoft is a registered trademark of Microsoft Corporation in the United States and other countries National Electrical Code and NEC are registered trademarks of National Fire Protection Association Inc All other trademarks are property
36. aangesloten apparatuur geen aardebeveiliging meer hebben Teneinde de kans op brand of elektrische schok te verminderen dient deze UPS in een gebouw met temperatuur en vochtigheidregeling te worden geinstalleerd waar geen geleidende verontreinigingen aanwezig zijn De omgevingstemperatuur mag 40 C niet overschrijden Niet gebruiken in de buurt van water of bij zeer hoge vochtigheid max 9596 e Voor UPS systemen met vast bedrade uitgangen moet de overstroombeveiliging voor wisselstroom uitvoercircuit s door anderen worden geleverd e Voor UPS systemen met vast bedrade uitgangen moeten de juiste hoofdschakelaars voor wisselstroom uitvoercircuit s door anderen worden geleverd OPGELET e Batterijen leveren gevaar op voor elektrische schokken en kunnen brandwonden veroorzaken door een grote kortsluitstroom Neem de juiste voorzorgsmaatregelen in acht Het onderhoud moet worden uitgevoerd door bevoegde onderhoudsmonteurs die verstand hebben van accu s en op de hoogte zijn van de vereiste voorzorgsmaatregelen Houd onbevoegden uit de buurt van de accu s e De batterijen moeten op de juiste wijze worden opgeruimd Raadpleeg hiervoor uw plaatselijke voorschriften e Nooit batterijen in het vuur gooien De batterijen kunnen ontploffen Tarkeita turvaohjeita T RKEIT TURVAOHJEITA SUOMI S ILYT N M OHJEET T m k ytt ohje sis lt t rkeit ohjeita joita on noudatettava UPS virtal hteen ja akkujen asennuksen
37. ableadas permanentemente los interruptores de desconexi n debidamente clasificados para el los circuito s de CA de salida ser n suministrados por terceros 16 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality SAFETY WARNINGS PRECAUCION e Las bater as pueden constituir un riesgo de descarga el ctrica o quemaduras por corriente alta de corto circuito Adopte las precauciones debidas Personal calificado de servicio que conozca de bater as y est al tanto de las precauciones requeridas debe darle servicio al equipo Mantenga al personal no autorizado alejado de las bater as e Es necesario desechar las bater as de un modo adecuado Consulte las normas locales para conocer los requisitos pertinentes e Nunca deseche las bater as en el fuego Las bater as pueden explotar si se las expone a la llama S kerhetsf reskrifter VIKTIGA SAKERHETSFORESKRIFTER SPARA DESSA F RESKRIFTER Den h r anvisningen inneh ller viktiga instruktioner som du ska f lja under installation och underh ll av UPS enheten och batterierna L s alla instruktioner innan du anv nder utrustningen och spara den h r anvisningen f r framtida referens Denna UPS enhet inneh ller LIVSFARLIG SP NNING ENDAST AUKTORISERAD SERVICEPERSONAL f r utf ra reparationer eller service Det finns inga delar som ANV NDAREN KAN UTF RA SERVICE P inuti UPS enheten e Den h r UPS enheten inneh ller sin ege
38. anted Item is to be replaced by Company and the End User supplies a credit card number or purchase order for the value of the replacement Product Company will use commercially reasonable business efforts to ship via standard ground shipment and at no cost to the End User the replacement Warranted Item to the End User within one 1 business day after Company receives notice of the warranty claim In such case the End User must eturn at Company s expense the defective Warranted Item to Company in the same packaging as the eplacement Warranted Item received by the End User or as otherwise instructed by Company If Company does not receive the defective Warranted Item Company will either charge the End User s credit card or send the End User an invoice which the End User agrees to pay for the value of the replacement Product f the Warranted Item is to be replaced by Company but the End User is unwilling or unable to supply a credit card number or purchase order for the value of the replacement Product Company will use commercially reasonable business efforts to ship via standard ground shipment and at no cost to the End User the replacement Warranted tem to the End User within one 1 business day after Company receives the defective Product from the End User n any case Company will provide shipping instructions and will pay its designated carrier for all shipping charges for eturn of defective equipment and replacement of Warranted Item
39. battery circuit breakers are in the OFF position see Figure 13 2 Plug the EBM cable s into the battery connector s as shown in Figure 13 Up to four EBMs may be connected to the UPS 3 If you are installing an optional REPO switch continue to the following section Remote Emergency Power off Installation Otherwise continue to Plug Receptacle UPS Installation on page 32 or Hardwired UPS Installation on page 34 NOTE After UPS installation ensure maximum battery runtime by configuring the UPS for the correct number of EBMs see page 43 Battery Circuit m e Breaker I FI UPS Battery EE e Connector EBM Cable EBM Battery Connectors EBM Battery Circuit Breakers 1 Figure 13 Typical Installation PW5125 5000 UPS Model Shown Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 29 www eaton com powerquality INSTALLATION Remote Emergency Power off Installation P 30 The Eaton 5125 includes a REPO port that allows power to be switched off at the UPS output from a customer supplied switch in a remote location The REPO feature shuts down the protected equipment immediately and does not follow the orderly shutdown proc
40. be transferred This Guaranty applies even in the event that the Product is initially sold by Company for resale to an End User WHAT THIS GUARANTY COVERS For the lifetime of the Product Guarantor promises to repair or replace at Guarantor s option the equipment valued up to the limits shown below that is damaged by an AC power line surge spike or other transient when properly connected to Guarantor s uninterruptible power system UPS Reimbursement for or restoration of data loss excluded This Guaranty applies only if all of the following circumstances arise 1 The UPS is plugged into properly grounded and wired outlets using no extension cords adapters other ground wires or other electrical connectors 2 The installation of the UPS complies with all applicable electrical and safety codes described by the National Electrical Code NEC 3 The UPS was used under normal operating conditions and in accordance with all labels and instructions and 4 The UPS was not damaged by accident other than AC power line transient misuse or abuse Cumulative Limits to be paid by Guarantor under this Load Protection Guaranty e 25 000 for Eaton UPS Model 3105 e 150 000 for Eaton UPS Models 5110 5115 5125 and 5130 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 73 www eaton com powerguality WARRANTY WHAT THIS GUARANTY DOES NOT COVER Any reimbursement or repair to End User s equipment does not
41. d or the ground connection is missing 79 O 0 EBMs On Zero EBMs are configured 10096 O default O O Flashing One of the other EBM configurations is selected 25 O w O 1EBM On One EBM is configured 100 O O nes e Flashing One of the other EBM configurations is selected 25 0 0 O 2 EBMs On Two EBMs are configured 100 O O Flashing One of the other EBM configurations is selected 25 O 2 0 3 EBMs On Three EBMs are configured 100 0 O PRESSE O Flashing One of the other EBM configurations is selected 25 O 4 5 Four 5 are configured 100 O iui O Flashing One of the other EBM configurations is selected 25 6 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 45 www eaton com powerquality CONFIGURATION 46 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality Chapter 6 USB Port Additional UPS Features This section describes the USB port DB 9 communication port e X Slot cards e Load segments The Eaton 5125 UPS includes a USB port a DB 9 communication port and an X Slot communication bay or card Only one communication option may be used to monitor the UPS they cannot operate simultaneously The UPS can communicate with a USB compliant computer using LanSafee Power Management Software v5 0 1 or higher To establish communication between the UPS and a computer 1 Connect the USB cable to
42. de Sine wave lt 7 THD with typical PFC load and no more than 15 atthe end of battery discharge Table 6 Weights and Dimensions UPS Extended Battery Module EBM Dimensions 44 2 x 66 x 13 cm 44 2 x 68 3 x 13 cm WxDxH 17 4 x 26 x 5 1 3U 17 4 x 26 9 x 5 1 3U Weights 73 kg 161 Ib 69 9 kg 154 Ib 62 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality Table 7 Environmental and Safety SPECIFICATIONS PW5125 5000 PW5125 6000i PW5125 6000 HW Operating 10 C to 40 C 50 F to 104 F Temperature Optimal battery performance 25 C 77 F Storage Temperature 0 C to 25 C 32 F to 77 F Transit Temperature 25 C to 55 C 13 F to 131 F Relative Humidity 5 95 noncondensing Operating Altitude Up to 2 000 meters above sea level Transit Altitude Up to 15 000 meters above sea level Audible Noise Less than 45 dBA Normal mode typical load Less than 50 dBA Battery mode Surge Suppression ANSI C62 41 Category B3 EN 61000 4 5 Level 3 Criteria B Safety Conformance UL 1778 CSA C22 2 No 107 3 IEC 62040 1 1 and IEC 60950 1 Agency Markings cULus cUL GS CE GOST EMC Class A IEC 62040 2 FCC Part 15 IEC 62040 2 FCC Part 15 ICES 003 ICES 003 VCCI Table 8 Battery UPS Configuration 20 12V 7 2 Ah internal batteries EBM Configuration EBM 240 20 12V 9 Ah Type Sealed maintenance free valve regulated
43. e liable in contract in tort including negligence or strict liability or otherwise for damage to property or equipment other than the Products including loss of profits or revenue loss of use of Products loss of data cost of capital claims of customers of the End User or any special indirect incidental or consequential damages whatsoever The total cumulative liability of Company hereunder whether the claims are based in contract including indemnity in tort including negligence or strict liability or otherwise shall not exceed the price of the Product on which such liability is based Company shall not be responsible for failure to provide service or parts due to causes beyond Company s reasonable control END USER S OBLIGATIONS In order to receive the benefits of this Warranty the End User must use the Product in a normal way follow the Product s user s guide and protect against further damage to the Product if there is a covered defect OTHER LIMITATIONS Company s obligations under this Warranty are expressly conditioned upon receipt by Company of all payments due to it including interest charges if any During such time as Company has not received payment of any amount due to it for the Product in accordance with the contract terms under which the Product is sold Company shall have no obligation under this Warranty Also during such time the period of this Warranty shall continue to run and the expiration of this Wa
44. edure initiated by any power management software Any devices that are operating on battery power are also shut down immediately The UPS does not automatically restart when the REPO switch is reset the UPS must be manually restarted If the Off 1 button is pressed after the REPO is activated the UPS remains in Standby mode when restarted until the On button is pressed The REPO circuit is an IEC 60950 safety extra low voltage SELV circuit This circuit must be separated from any hazardous voltage circuits by reinforced insulation CAUTION To ensure the UPS stops supplying power to the load during any mode of operation the input power must be disconnected from the UPS when the emergency power off function is activated NOTE The REPO function activates when the REPO contacts close NOTE If the REPO function is not needed the REPO connector must remain installed in the REPO port on the UPS rear panel NOTE For Europe the emergency switch requirements are detailed in Harmonized document HD 384 48 S1 Electrical Installation of the Buildings Part 4 Protection for Safety Chapter 46 Isolation and Switching Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality INSTALLATION To install the REPO switch 1 Verify that the UPS is off and disconnected from utility power 2 Remove the REPO connector from the REPO port on the UPS rear panel see Figure 14 3
45. ee as stalling the Ball hit is o LO ERAS EO A SENAT nstalling the UPS Internal Batteries Extended Battery Module Installation Remote Emergency Power off Installation Pl gcReceptacle UPS Installation rea une mE eee TE Hardwired UPS Installation nem ie ac RE Se Aaah EEG mrd need 4 Operation akar adel Firing He UPS On 1 22 2300 s vante Wiener dad Pet LAS ated bib deidad Starting the UPS on Battery vereert herde a aa E O AE Turning ei ie s cR NR RES Initiating ten ne Mot et RAUS Operating Modes it risiede ren gd Normal Modes 2 a n LAST PANNI Dit N eis ts Battery Mode 4 0 2 2 Ad t dec MSN ce Oed hen ee Bypass IM Ode jm iter emen ate Aen ah at a DT ae ANT lene ae O a EE Standby redet oe ee lid ali Ed eid 5 6 Additional UPS Features USB ORE so ice end ed Ee etu Rr ed hen teu ec las alal DB 9 Communication Portes resosi e Beet 7 Cards aart idea dd aio e te The ConnectUPS X Web SNMP Card SA
46. ence in which case the user may be required to take additional measures VCCI Notice LORIE 810 8655 VCC oR 2 5 gt 2 5 lt CT CORE 8 cim 5 4 EK RE 25 1 5 2 3 5 Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information X PB Pb pal RISK OF ELECTRIC SHOCK Observe the warning associated with the risk of electric shock symbol CAUTION REFER TO OPERATOR S MANUAL Refer to your operator s manual for additional information such as important operating and maintenance instructions This symbol indicates that you should not discard the UPS or the UPS batteries in the trash This product contains sealed lead acid batteries and must be disposed of properly For more information contact your local recycling reuse or hazardous waste center This symbol indicates that you should not discard waste electrical or electronic equipment WEEE in the trash For proper disposal contact your local recycling reuse or hazardous waste center Table of Contents Te Introd ction encender eins tod 2 Safety Warnings 3 Installation vnm tele note ce be E q eese ette eel IAN fispecting the Equipment na e Belse Date EA A AE nstallation OVerVIeWe tue ie interes Out Xe S REDE S Sa d
47. ery capability for powering up the UPS even if utility power is not available Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 1 www eaton com powerquality INTRODUCTION Hot swappable electronics module and batteries that simplify maintenance by allowing you to replace them safely without powering down the critical load Emergency shutdown control through the remote emergency power off REPO port Two standard communication options with a USB port and a DB 9 serial port Optional X Slote cards with enhanced communication capabilities for increased power protection and control Advanced power management with the Software Suite CD for graceful shutdowns and power monitoring Sequential shutdown and load management through separate receptacle groups called load segments Backed by worldwide agency approvals Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality Chapter 2 Safety Warnings IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries Please read all instructions before operating the equipment and save this manual for future reference This UPS contains LETHAL VOLTAGES All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY There are NO USER SERVICEABLE PARTS inside the UPS This UPS conta
48. esenza di umidit eccessiva 95 max Nei sistemi UPS provvisti di uscite cablate i dispositivi di protezione da sovracorrente per il i circuito i a corrente alternata in uscita devono essere forniti da terzi Nei sistemi UPS prowisti di uscite cablate i sezionatori di corrente nominale adeguata per il i circuito i a corrente alternata in uscita devono essere forniti da terzi ATTENZIONE Le batterie possono comportare un rischio di scossa elettrica o di ustione in seguito a un elevata corrente di corto circuito Osservare le dovute precauzioni L assistenza deve essere eseguita da personale qualificato esperto di batterie e delle necessarie precauzioni Tenere il personale non autorizzato lontano dalle batterie Le batterie devono essere smaltite in modo corretto Per i requisiti di smaltimento fare riferimento alle disposizioni locali Non gettare mai le batterie nel fuoco poich potrebbero esplodere se esposte alle fiamme Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 11 www eaton com powerguality SAFETY WARNINGS Viktig Sikkerhetsinformasion VIKTIGE SIKKERHETSINSTRUKSJONER GJEM DISSE INSTRUKSJONENE Denne h ndboken inneholder viktige instruksjoner som du bgr overholde ved montering og vedlikehold av UPS enheten og batteriene Les alle instruksjoner fgr utstyret tas i bruk og gjem h ndboken til fremtidig referanse Denne UPS en inneholder LIVSFARLIGE SPENNINGER All reparasjon og
49. ge the batteries see Turning the UPS Off on page 40 Consider all warnings cautions and notes before replacing batteries Batteries can present a risk of electrical shock or burn from high short circuit current The following precautions should be observed 1 Remove watches rings or other metal objects 2 Use tools with insulated handles 3 Do not lay tools or metal parts on top of batteries e ELECTRIC ENERGY HAZARD Do not attempt to alter any battery wiring or connectors Attempting to alter wiring can cause injury Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 55 www eaton com powerquality UPS MAINTENANCE How to Replace UPS Internal Batteries CAUTION Pull the battery trays out onto a flat stable surface The battery trays are unsupported when you pull them out of the UPS e The UPS battery trays are heavy A minimum of two people are required to lift the battery trays into the UPS chassis To replace the UPS internal batteries 1 Remove the UPS front cover by pulling on both ends pull harder on the left side and lift the front cover off the right retaining hook Figure 28 Removing the UPS Front Cover 2 Unscrew and set aside the battery retaining bracket see Figure 29 Battery Retaining Bracket Figure 29 Removing the Battery Retaining Bracket 56 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality UPS MAINTENANC
50. ificado com conhecimento sobre baterias e ciente das precau es exigidas Mantenha o pessoal n o autorizado afastado das baterias e Siga as instru es apropriadas ao desfazer se das baterias Consulte os c digos do local para maiores informa es sobre os regulamentos de descarte de produtos e Nunca jogue as baterias no fogo porque h risco de explos o Mepbi 14 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton
51. ilding Management System BMS Multi Server Card has six serial communication ports that can communicate simultaneously with other computers using LanSafe Power Management Software provided on the Software Suite CD USB Card connects to a USB port on your computer Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 49 www eaton com powerquality ADDITIONAL UPS FEATURES ConnectUPS X Web SNMP Cari Eg Mil Relay Interface Card emme Modbus Card Relay Interface Adapter 5 o Ze Ee 9 Multi Server Card o Do QE qmm USB Card X Slot Communication Bay Figure 24 Optional X Slot Cards The ConnectUPS X Web SNMP Card With the ConnectUPS you can monitor the UPS several different ways Using a Web browser such as Microsofte Internet Explorer to monitor and manage the connected UPS Using your Internet ready cell phone or PDA personal digital assistant Using SNMP compatible network management software user supplied that monitors the UPS in a method similar to that of other network devices Refer to the ConnectUPS Web SNMP Card User s Guide for more information 10 Mb Network LEDs yellow Uplink Ethernet Connector LED green Network LEDs green 100 Mb Jm 5 5 I OO OO
52. ins its own energy source batteries The output receptacles may carry live voltage even when the UPS is not connected to an AC supply For 200 240V models the output receptacles may remain electrically live If the input power source in your application is wired line to neutral as in most European applications the voltage to the output receptacles is OV With line to line input wiring the voltage to the output receptacles is 100 120V measured from line to ground or line to neutral depending on the UPS wiring e Do not remove or unplug the input cord when the UPS is turned on This removes the safety ground from the UPS and the equipment connected to the UPS e To reduce the risk of fire or electric shock install this UPS in a temperature and humidity controlled indoor environment free of conductive contaminants Ambient temperature must not exceed 40 C 104 F Do not operate near water or excessive humidity 95 maximum e For UPS models with hardwired outputs overcurrent protection for the output AC circuit s is to be provided by others For UPS models with hardwired outputs suitably rated disconnect switches for the output AC circuit s are to be provided by others Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality SAFETY WARNINGS CAUTION e Batteries can present a risk of electrical shock or burn from high short circuit current Obse
53. interno del gruppo statico di continuit NON vi sono PARTI RIPARABILI DALL UTENTE 10 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality SAFETY WARNINGS AVVERTENZA L UPS contiene la propria fonte di energia batterie Le prese d uscita possono essere sotto tensione anche quando l UPS non collegato all alimentazione elettrica CA Nei modelli da 200 240 V amp possibile che le prese d uscita rimangano sotto tensione Se la fonte di alimentazione in entrata dell installazione costituita da un collegamento linea neutro come accade nella maggior parte delle installazioni europee la tensione delle prese d uscita pari a 0 V Con un cablaggio in entrata del tipo linea linea la tensione sulle prese d uscita 100 120 V con misurazione effettuata da linea a terra o da linea a neutro in base al cablaggio dell UPS Non rimuovere n scollegare il cavo di ingresso quando il gruppo statico di continuit acceso poich in tal modo si disattiverebbe il collegamento a terra di sicurezza del gruppo statico di continuit e dell apparecchiatura ad esso collegata Per ridurre il rischio di incendio o di scossa elettrica installare il gruppo statico di continuit in un ambiente interno a temperatura ed umidit controllata privo di agenti contaminanti conduttivi La temperatura ambiente non deve superare i 40 C Non utilizzare l unit in prossimit di acqua o in pr
54. ja huollon yhteydess Lue kaikki ohjeet ennen laitteiston k ytt ja s ilyt ohje my hemp tarvetta varten VAARA T m UPS sis lt HENGENVAARALLISIA J NNITTEIT Kaikki korjaukset ja huollot on j tett v VAIN VALTUUTETUN HUOLTOHENKIL N TOIMEKSI UPS ei sis ll MIT N K YTT J N HUOLLETTAVIA OSIA 6 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality SAFETY WARNINGS VAROITUS T ss UPS virtal hteess on oma energianl hde akut L ht vastakkeissa voi olla j nnite vaikka UPS virtal hdett ei ole kytketty verkkovirtaan 200 240V malleissa l ht vastakkeissa voi s ily j nnite Jos sovelluksen tulovirtal hde on johdotettu linjasta neutraaliin kuten useimmissa eurooppalaisissa sovelluksissa laht vastakkeiden j nnite on 0 V Linjasta linjaan tulojohdotuksessa l ht vastakkeiden j nnite on 100 120V mitataan linjasta maahan tai linjasta neutraaliin UPS virtal hteen johdotuksesta riippuen l poista tai irrota sis ntulojohtoa kun UPS on kytkettyn T m poistaa turvamaadoituksen UPS laitteesta ja siihen liitetyst laitteistosta V hent ksesi tulipalon ja s hk iskun vaaraa asenna t m UPS sis tiloihin joissa l mp tila ja kosteus on s dett viss ja joissa ei ole virtaa johtavia ep puhtauksia Ymp rist n l mp tila ei saa ylitt 40 C l k yt l hell vett ja v lt kosteita til
55. l common tied to chassis 6 DSR To external device tied to Pin 4 Out 7 No Connection 8 AC Fail AC Fail relay contact 20 mA 30 Vdc contact rating Out 9 Power Source V 8 to 24 volts DC power Out 48 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality X Slot Cards ADDITIONAL UPS FEATURES X Slot cards allow the UPS to communicate in a variety of networking environments and with different types of devices NOTE If your UPS part number ends with 5507 your UPS includes the factory installed ConnectUPS X Web SNMP Card continue to the following section The ConnectUPS X Web SNMP Card The Eaton 5125 has an available communication bay for one of the following X Slot cards ConnectUPS X Web SNMP Card has SNMP and HTTP capabilities as well as monitoring through a Web browser interface connects to a twisted pair Ethernet 10 100BaseT network It has a built in switching hub that allows three additional network devices to be connected to the network without the requirement of additional network drops In addition a Environmental Monitoring Probe can be attached to obtain humidity temperature smoke alarm and security information Relay Interface Card has isolated dry contact Form C relay outputs for UPS status Utility failure Low battery UPS alarm OK or On bypass Modbuse Card allows you to continuously and reliably monitor the UPSs in your Bu
56. le and removes power from your equipment 3 Unplug or remove utility power from the UPS the UPS shuts down in 30 seconds The load level and battery indicators flash briefly prior to shutdown If you do not unplug or remove utility power from the UPS it remains in Standby mode Initiating the Self Test Press and hold the button for three seconds to initiate the self test The indicators cycle through slowly during the test If the alarm beeps or a UPS alarm indicator stays on see Table 10 on page 66 40 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality OPERATION Operating Modes Eaton 5125 s front panel indicates the UPS status through the UPS indicators Figure 19 shows the UPS front panel indicators and controls Indicator Legend o Unlit o Green Normal Mode Indicator solid green Red Standby Mode Indicator flashing green Bypass Mode Indicator solid red 205 Flashing On Button Off Button Test Alarm Reset Button Battery Mode Indicator Load Level Indicators Figure 19 UPS Front Panel Normal Mode During Normal mode the indicator illuminates and the front panel displays the percentage of UPS load capacity being used by the protected equipment see Figure 20 The UPS monitors and charges the batteries as needed and provides power protection to your equipment 20 gt 100 100 76 100
57. les The UPS detects a fault in the UPS electronics Standby Mode When the UPS is turned off and remains connected to utility power the UPS is in Standby mode The indicator flashes and the load level indicators are off indicating that power is not available to your equipment The battery recharges when necessary NOTE For 200 240V models the output receptacles may remain electrically live up to 100 120V Unplug the UPS to ensure power is not available to the output receptacles Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality Chapter 5 Configuration When the UPS is in Configuration mode the front panel LEDs represent the configuration options Use the control buttons On button Off 1 button and 4 button to modify the UPS configuration Figure 21 shows the LEDs and Table 2 explains the corresponding options To reconfigure the UPS default settings 1 Press and hold the On button and the button simultaneously for three seconds The UPS transfers to Configuration mode The LEDs flash briefly and then display the enabled options NOTE If the LEDs start cycling automatically from left to right repeat Step 1 and be sure to press both buttons 2 Press the On button to scroll through the options Each time you press the button the UPS beeps The LED for the selected option indicates the current setting flashing represents disabled
58. ment ratings do not exceed the UPS capacity to prevent an overload alarm 4 Verify that all load segment circuit breakers are in the ON position 5 Remove the breaker tie from all battery circuit breakers 6 Switch all battery circuit breakers to the ON position 7 If an emergency power off disconnect switch is required by local 10 11 codes see Remote Emergency Power off Installation on page 30 to install the REPO switch before powering on the UPS Plug the UPS power cord into a power outlet The cv indicator flashes indicating the UPS is in Standby mode with the equipment offline Press and hold the On button for approximately three seconds The indicator illuminates solid and the load level indicators display the percentage of load being applied to the UPS The UPS is now in Normal mode and supplying power to your equipment If the alarm beeps or a UPS alarm indicator stays on see Table 10 on page 66 To change the factory set defaults see Configuration on page 43 If you installed an optional REPO test the REPO function Activate the external REPO switch De activate the external REPO switch and restart the UPS If optional EBMs are installed continue to Configuration on page 43 to specify the number of 5 installed NOTE The batteries charge to 80 capacity in approximately 3 hours However it is recommended that the batteries charge for 48 hours after installation or long term st
59. n energik lla batterier Uttagen kan vara sp nningsf rande ven d UPS enheten inte r ansluten till sp nningsn tet e modellerna 200 240 V kan de utg ende uttagen fortfarande vara str mf rande Om den ing ende str mk llan i din applikation r kopplad ledare till nolla det vanligaste i Europa r sp nningen till de utg ende uttagen O V r den ing ende str mk llan kopplad ledare till ledare r sp nningen i de utg ende uttagen 100 120 V uppm tt fr n ledare till jord eller ledare till nolla beroende p UPS ens anslutning e Ta aldrig bort n tsladden n r UPS enheten r p slagen Detta tar bort skyddsjordningen fr n b de UPS enheten och den anslutna utrustningen Minska risken f r brand eller elektriska st tar genom att installera denna UPS enhet inomhus d r temperatur och luftfuktighet r kontrollerade och d r inga ledande f roreningar f rekommer Omgivande temperatur f r ej verstiga 40 C Anv nd inte utrustningen n ra vatten eller vid h g luftfuktighet max 95 96 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 17 www eaton com powerquality SAFETY WARNINGS e verstr msskydd f r de utg ende v xelstr mskretsarna ska tillhandah llas av andra f r UPS system med fasta utg ngar e Bortkopplingsswitchar med passande dimensionering f r de utg ende v xelstr mskretsarna ska tillhandah llas av andra f r UPS system med fasta utg
60. ngar VIKTIGT e Batterierna kan inneb ra en risk f r elektrisk st t eller br nnskada fran kortsluten starkstr m lakttag l mpliga f rsiktighets tg rder Service ska utf ras av utbildad servicepersonal med kunskap om batterierna och n dv ndiga f rsiktighets tg rder H ll ej beh rig personal borta fr n batterierna e Batterierna m ste avyttras enligt anvisningarna i lokal lagstiftning e Anv nda batterier f r aldrig br nnas upp De kan explodera 18 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality Chapter 3 Installation This section explains Equipment inspection Rail kit installation UPS installation including internal batteries Extended Battery Module EBM installation Remote emergency power off REPO installation Inspecting the Equipment If any equipment has been damaged during shipment keep the shipping cartons and packing materials for the carrier or place of purchase and file a claim for shipping damage If you discover damage after acceptance file a claim for concealed damage To file a claim for shipping damage or concealed damage 1 File with the carrier within 15 days of receipt of the equipment 2 Send a copy of the damage claim within 15 days to your service representative NOTE Check the battery recharge date on the shipping carton label If the date has expired and the batteries were never recharged do not use the UPS
61. oja 95 maksimi UPS j rjestelmiss kiintealla asennuksella kuormana olevien laitteiden ylivirtasuojaus ja erotuskytkimet tulee toteuttaa kuormapiireissa Akut voivat aiheuttaa s hk iskun tai palovammojen vaaran johtuen suuresta oikosulkuvirrasta Noudata kaikkia asianmukaisia varotoimia Laitteen saa huoltaa vain ammattitaitoinen huoltohenkil kunta joka tuntee akut ja niihin liittyv t varotoimet l p st valtuuttamatonta henkil st l helle akkuja Akusto t ytyy h vitt s d sten mukaisella tavalla Noudata paikallisia m r yksi l koskaan heit akkuja tuleen Ne voivat r j ht Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 7 www eaton com powerguality SAFETY WARNINGS Consignes de s curit CONSIGNES DE S CURIT IMPORTANTES CONSERVER CES INSTRUCTIONS Ce manuel comporte des instructions importantes que vous tes invit suivre lors de toute proc dure d installation et de maintenance des batteries et de l onduleur Veuillez consulter enti rement ces instructions avant de faire fonctionner l quipement et conserver ce manuel afin de pouvoir vous y reporter ult rieurement A Cet onduleur contient des TENSIONS MORTELLES Toute op ration d entretien et de r paration doit tre EXCLUSIVEMENT CONFI E A UN PERSONNEL QUALIFI AGR AUCUNE PIECE R PARABLE PAR L UTILISATEUR ne se trouve dans l onduleur AVERTISSEMENT e Cet onduleur poss de
62. only to the original End User the End User of any Eaton 3105 5110 5115 5125 and 5130 Products individually and collectively the Product purchased on or after August 19 2009 and cannot be transferred This Warranty applies even in the event that the Product is initially sold by Company for resale to an End User LIMITED WARRANTY PERIOD The period covered by this Warranty for Product installed and currently located in the fifty 50 United States the District of Columbia and Canada is twenty four 24 months from the date of purchase or thirty 30 months from the date of shipment For units which are registered online at www eaton com PQ Register the warranty is extended to thirty six 36 months from the date of purchase forty two 42 months from the date of shipment WHAT THIS LIMITED WARRANTY COVERS The warrantor warrants that the Product and battery individually and collectively the Warranted Items are free from defects in material and workmanship If in the opinion of Company a Warranted Item is defective and the defect is within the terms of this Warranty Company s sole obligation will be to repair or replace such defective Warranted Item including by providing service parts and labor as applicable at the option of Company PROCEDURES FOR REPAIR OR REPLACEMENT OF WARRANTED ITEMS The Warranted Item will be repaired or eplaced at a Company site or such other location as determined by Company f the Warr
63. or the load is defective Turn off and remove utility power from the UPS Remove some of the equipment from the UPS Wait at least 5 seconds until all LEDs are off and restart the UPS You may need to obtain a larger capacity UPS 1 4 ZIN Continuous audible alarm The UPS internal temperature is too high The UPS transfers to Bypass mode allowing the UPS to cool Turn off and remove utility power from the UPS Clear the vents and remove any heat sources Ensure the airflow around the UPS is not restricted Wait at least 5 minutes and restart the UPS If the condition persists contact your service representative Momentary overload The UPS transfers to Bypass mode Repetitive overloads will lock on bypass for one hour press the On button for immediate return IA V UPS fault condition Save your work and turn off your eguipment Turn off Mw Nw NW sw and remove utility power from the UPS Contact your KAAAA service representative The alarm cannot be silenced 68 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality TROUBLESHOOTING Service and Support If you have any questions or problems with the UPS call your Local Distributor or the Help Desk at one of the following telephone numbers and ask for a UPS technical representative United States 1 800 356 5737 Canada 1 800 461 9166 ext 260 All other countries Call your local
64. orage Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 33 www eaton com powerquality INSTALLATION Hardwired UPS Installation Only qualified service personnel such as a licensed electrician shall perform the electrical installation Risk of electrical shock CAUTION For UPS models with hardwired outputs overcurrent protection for the output AC circuit s is to be provided by others For UPS models with hardwired outputs suitably rated disconnect switches for the output AC circuit s are to be provided by others NOTE Do not make unauthorized changes to the UPS or accessories otherwise damage may occur to your equipment and void your warranty The Eaton 5125 hardwired models require a dedicated branch circuit that meets the following requirements 40A minimum circuit with short circuit and overcurrent protection 200 240 Vac Single phase 50 60 Hz The breaker must be wall mounted and readily accessible to the operator Flexible metal conduit recommended for ease of service and maintenance 34 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality X Slot Communication Bay Ground Bonding Screw INSTALLATION
65. port Audible Alarms and UPS Conditions The UPS has an audible alarm feature to alert you of potential power problems Use Table 10 to determine and resolve the UPS alarms and conditions Indicator Legend Unlit Battery Service o Green On Battery Site Wiring Fault e Red General Alarm Power On S Flashing 1 On Button Off Button Alarm Reset Button Load Level Indicators Figure 32 Alarm Indicators Silencing an Audible Alarm Before silencing an alarm check the alarm condition and perform the applicable action to resolve the condition see Table 10 To silence the alarm for an existing fault press the button If UPS status changes the alarm beeps overriding the previous alarm silencing Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 65 www eaton com powerquality TROUBLESHOOTING Table 10 Troubleshooting Guide Alarm or Condition Possible Cause Action The indicator is not on the The power cord is not connected correctly UPS does not start Check the power cord connections The wall outlet is faulty Have a qualified electrician test and repair the outlet The main utility breaker is off Verify that the main utility breaker is on The remote emergency power off REPO switch is active Reset the REPO switch and restart the UPS The REPO connector is missing Verif
66. requency of usage and ambient temperature Batteries used beyond expected service life will often have severely reduced runtimes Replace batteries at least every 5 years to keep units running at peak efficiency Storing the UPS and Batteries If you store the UPS for a long period recharge the batteries every 6 months by connecting the UPS to utility power The batteries charge to 8096 capacity in approximately 3 hours However it is recommended that the batteries charge for 48 hours after long term storage Check the battery recharge date on the shipping carton label If the date has expired and the batteries were never recharged do not use the UPS Contact your service representative Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 53 www eaton com powerquality UPS MAINTENANCE Replacing the Electronics Module 54 The electronics module can be hot swapped for easy replacement without losing power to your equipment The UPS automatically switches to Bypass mode Battery mode is not available however the utility power continues to be passively filtered by the UPS If you prefer to remove input power to change the electronics module see Turning the UPS Off on page 40 To replace the electronics module 1 Disconnect the communication cable if installed 2 Remove the X Slot card if installed 3 Remove the UPS front cover by pulling on both ends pull harder on the left side and lift the front co
67. rranty shall not be extended upon payment of any overdue or unpaid amounts 72 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality WARRANTY COSTS NOT RELATED TO WARRANTY The End User shall be invoiced for and shall pay for all services not expressly provided for by the terms of this Warranty including without limitation site calls involving an inspection that determines no corrective maintenance is required Any costs for replacement equipment installation materials freight charges travel expenses or labor of Company representatives outside the terms of this Warranty will be borne by the End User OBTAINING WARRANTY SERVICE In the USA call the Customer Reliability Center 7x24 at 800 356 5737 Outside of the USA call your local Eaton product sales or service representative For comments or questions about this Warranty write to the Customer Quality Representative 3301 Spring Forest Road Raleigh North Carolina 27616 USA Load Protection Guarantee US and Canada Eaton UPS Models 3105 5110 5115 5125 and 5130 GUARANTOR The Guarantor for the load protection guaranty set forth herein is Eaton Corporation an Ohio Corporation company Company LIMITED GUARANTY This load protection guaranty this Guaranty applies only to the original End User the End User of any Eaton 3105 5110 5115 5125 and 5130 Products individually and collectively the Product and cannot
68. rtenden Komponenten ACHTUNG Diese USV Unterbrechungsfreies Stromversorgung enth lt eine eigene Fnergiequelle Batterien Die Ausgangssteckdosen k nnen Spannung f hren auch wenn die USV nicht an eine Wechselstromquelle angeschlossen ist Bei Modellen mi bleiben Wenn d wie in den meis ie Eingangsstromquelle in Ihrer Anlage mi ten europ ischen Anlagen betr gt die Sp 220 240 Volt k nnen die Ausgangssteckverbinder stromf hrend Masseleitung verkabelt ist annung an den Ausgangssteckverbindern 0 Volt Bei einer Verkabelung mit AuRenleitern betr gt die Spannung an de Masse oder Leit n Ausgangssteckverbindern 110 120 Volt ung zu Masseleiter abh ngig von der USV gemessen von Leitung zu Verkabelung Das Eingangskabel nicht entfernen oder abziehen w hrend die USV eingeschaltet ist weil hierdurch d ie Sicherheitserdung von der USV und den Ger ten entfern Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D wird daran angeschlossenen www eaton com powerquality SAFETY WARNINGS e Um die Brand oder Elektroschockgefahr zu verringern diese USV nur in Geb uden mit kontrollierter Temperatur und Luftfeuchtigkeit installieren in denen keine leitenden Schmutzstoffe vorhanden sind Die Umgebungstemperatur darf 40 C nicht bersteigen Die USV nicht in der N he von Wasser oder in extrem hoher Luftfeuchtigkeit max 95 96 betreiben e F r USV Systeme mi
69. rve proper precautions Servicing should be performed by qualified service personnel knowledgeable of batteries and required precautions Keep unauthorized personnel away from batteries e Proper disposal of batteries is required Refer to your local codes for disposal requirements Never dispose of batteries in a fire Batteries may explode when exposed to flame Sikkerhedsanvisninger VIGTIGE SIKKERHEDSANVISNINGER GEM DISSE ANVISNINGER Denne manual indeholder vigtige instruktioner som skal fglges under installation og vedligeholdelse af UPS en og batterierne L s venligst alle instruktioner inden betjening af udstyret og gem denne manual mhp fremtidige opslag Denne UPS indeholder LIVSFARLIG H JSP NDING Alle reparationer og vedligeholdelse b r kun udfgres af en AUTORISERET SERVICETEKNIKER Ingen af UPS ens indvendige dele kan repareres af brugeren ADVARSEL A e Denne UPS indeholder sin egen energikilde batterier Udgangsstikkene kan endog v re str mf rende n r UPS en ikke er koblet til en vekselstr msforsyning e Pa 200 240V modeller kan udgangsstikkene v re str mf rende Hvis ledningsf ringen til indgangsstr mkilden p din enhed er fase til neutral som p de fleste europ iske enheder er sp ndingen til udgangsstikkene OV Med en fase til fase indgangsledningsf ring er sp ndingen til udgangsstikkene 100 120V m lt fra fase til jord eller fase til neutral afh ngig af UPS ledningsfgringen
70. s Any returned Warranted Item or parts that are eplaced may be new or reconditioned All Warranted Items returned to Company and all parts replaced by Company shall become the property of Company Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 71 www eaton com powerquality WARRANTY WHAT THIS LIMITED WARRANTY DOES NOT COVER This Warranty does not cover any defects or damages caused by a failure to properly store the Product before installation including the charge of batteries no later than the date indicated on the packaging b shipping and delivery of the Product if shipping is FOB Factory c neglect accident abuse misuse misapplication or incorrect installation d repair or alteration not authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or Agent e improper testing operation maintenance adjustment or modification of any kind not authorized in writing by Company personnel or performed by an authorized Company Customer Service Engineer or Agent or f use of the Product under other than normal operating conditions or in a manner inconsistent with the Product s labels or instructions This Warranty is not valid if the Product s serial numbers have been removed or are illegible Any Warranted Items repaired or replaced pursuant to this Warranty will be warranted for the remaining portion of the original Warranty subject to all the terms thereof
71. s Guaranty COSTS NOT RELATED TO GUARANTY The End User shall be invoiced for and shall pay for all services not expressly provided for by the terms of this Guaranty including without limitation site calls involving an inspection that determines no corrective maintenance is required Any costs for replacement equipment installation materials freight charges travel expenses or labor of Company representatives outside the terms of this Guaranty will be borne by the End User TO MAKE A CLAIM In the USA call the Customer Reliability Center 7x24 at 800 356 5737 Outside of the USA contact your local Eaton product sales or service representative For comments or questions about this Load Protection Guaranty write to the Customer Quality Representative 3301 Spring Forest Road Raleigh North Carolina 27616 USA 74 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality
72. s interrupteurs de d connexion convenables pour le s circuit s de sortie de courant alternatif doivent tre fournie par un autre fournisseur 8 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality SAFETY WARNINGS ATTENTION e Les batteries peuvent pr senter un risque de choc lectrique ou de br lure provenant d un courant de court circuit haute intensit Observez les pr cautions appropri es L entretien doit tre r alis par du personnel qualifi connaissant bien les batteries et les pr cautions n cessaires N autorisez aucun personnel non qualifi manipuler les batteries Une mise au rebut r glementaire des batteries est obligatoire Consulter les r glements en vigueur dans votre localit e Ne jamais jeter les batteries au feu L exposition aux flammes risque de les faire exploser Sicherheitswarnungen WICHTIGE SICHERHEITSANWEISUNGEN AUFBEWAREN Dieses Handbuch enth lt wichtige Anweisungen die Sie w hrend der Installation und Wartung des USV Unterbrechungsfreies Stromversorgungssystem und der Batterien befolgen m ssen Bitte lesen Sie alle Anweisungen des Handbuches bevor Sie mit dem Ger t arbeiten Bewahren Sie das Handbuch zum Nachlesen auf Die USV f hrt lebensgef hrliche Spannungen Alle Reparatur und Wartungsarbeiten sollten nur von Kundendienstfachleuten durchgef hrt werden Die USV enth lt keine vom Benutzer zu wa
73. t breaker on the UPS rear panel is in the OFF position see Figure 13 on page 29 2 Unscrew and set aside the battery retaining bracket see Figure 10 Battery Retaining Bracket Figure 10 Battery Retaining Bracket 3 Slide the left battery tray into the chassis Repeat for the right battery tray Figure 11 Installing the Battery Trays 4 Secure the battery trays to the chassis with the battery retaining bracket and screws removed in Step 2 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 27 www eaton com powerguality INSTALLATION 5 Align the UPS front cover provided in the accessory kit with the right retaining hook and front cover holes on the UPS cabinet Insert the UPS front cover Figure 12 Installing the UPS Front Cover 6 If you are installing an optional Extended Battery Module continue to the following section Extended Battery Module Installation otherwise continue to Plug Receptacle UPS Installation on page 32 or Hardwired UPS Installation on page 34 28 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality INSTALLATION Extended Battery Module Installation CAUTION A small amount of arcing may occur when connecting an EBM to the UPS This is normal and will not harm personnel Insert the EBM cable into the UPS battery connector quickly and firmly To install the optional EBM s 1 Verify that all
74. t festverdrahteten Eing ngen mu der berstromschutz f r die Ausgangswechselstromkreise anderweitig bereitgestellt werden e F r USV Systeme mit festverdrahteten Ausg ngen m ssen Trennschalter f r die Ausgangswechselstromkreise mit passendem Nennwert anderweitig bereitgestellt werden VORSICHT e Batterien k nnen das Risiko eines elektrischen Schlags bergen oder durch hohen Kurzschlussstrom in Brand geraten Die richtigen VorsichtsmaRnahmen beachten Wartungsarbeiten m ssen von qualifizierten Kundendienstfachleuten durchgef hrt werden die Kenntnisse ber Akkus besitzen und die erforderlichen VorsichtsmaRnahmen beachten Unberechtigtes Personal von den Akkus fern halten e Ordnungsgem Re Entsorgung der Akkus ist erforderlich Lesen Sie hierf r Ihre rtlichen Entsorgungsbestimmungen e Die Akkus nicht in einem Feuer entsorgen In Feuer k nnen Akkus explodieren Avvisi di sicurezza IMPORTANTI ISTRUZIONI DI SICUREZZA CONSERVARE QUESTE ISTRUZIONI presente manuale contiene importanti istruzioni da seguire durante l installazione e la manutenzione dell UPS e delle batterie Leggere integralmente le istruzioni prima di utilizzare l apparecchiatura e conservare il presente manuale per futuro riferimento PERICOLO A La TENSIONE contenuta in questo gruppo statico di continuita 6 LETALE Tutte le operazioni di riparazione e di manutenzione devono essere effettuate ESCLUSIVAMENTE DA PERSONALE TECNICO AUTORIZZATO All
75. tem in the bottom of the rack See page 62 for UPS and EBM weights To install the rail kit 1 Loosen the assembly wing nuts on both rail assemblies and adjust the rail size for the depth of your rack see Figure 2 Assembly Wing gt Front Rail Figure 2 Adjusting the Rail Depth 2 Select the proper holes in the rail for positioning the UPS and any optional cabinets in the rack see Figure 3 The first rail should be placed at the bottom using positions 1 and 6 for the front rail hex head screws If you are installing additional rails the next rail should be placed 4 holes above the last installed screw Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 21 www eaton com powerquality INSTALLATION o 0 0 Position 15 O Second Rail O O po Position 10 0 O J Position 6 0 First Rail 0 Position 1 Figure 3 Front Rail Screw Positions 3 Secure the rail to the front of the rack with two hex head screws see Figure 4 Front Rail Hex Head Screws Figure 4 Securing the Front Rail 22 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality INSTALLATION Using two clip nuts and two hex head screws attach the rail to the rear of the rack see Figure 5 and Figure 6 The bottom rail uses positions 2 and 4
76. the UPS and any optional EBMs into the rack 11 Secure the front of the cabinet to the rack using two hex head screws in the top and bottom positions of each mounting bracket see Figure 8 Repeat for each cabinet UPS Optional EBM Figure 8 Securing the Mounting Brackets Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 25 www eaton com powerquality INSTALLATION 26 12 Attach the rear hold down bracket to the rail and slide the bracket into the slots on the UPS rear panel Repeat for the other side Verify each rear hold down bracket is fully seated and then tighten the wing nut The UPS is now secured in the rack 13 If installing optional EBMs repeat Step 12 for each cabinet Rear Hold Down Bracket Lr x Figure 9 Securing the Back of the UPS 14 Continue to the following section Installing the UPS Internal Batteries Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality INSTALLATION Installing the UPS Internal Batteries To install the battery trays into the UPS chassis 1 Verify that the battery circui
77. v D www eaton com powerquality Chapter 4 Operation This section describes Turning the UPS on and off e Starting the UPS on battery e Initiating the self test Operating modes Turning the UPS On After the UPS is connected to utility power it enters Standby mode the indicator flashes and the load level indicators are off To turn on the UPS press and hold the On button for approximately three seconds The indicator illuminates solid and the load level indicators display the percentage of load being applied to the UPS Starting the UPS on Battery NOTE Before using this feature the UPS must have been powered by utility power at least Once To turn on the UPS without using utility power press and hold the On button for approximately five seconds until you hear the second beep The UPS starts up in Battery mode and supplies battery power to your equipment The indicator flashes and the indicator illuminates solid Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 39 www eaton com powerquality OPERATION Turning the UPS Off NOTE Pressing the Off b button while the UPS is in Battery mode causes the UPS to shut down immediately To turn off the UPS 1 Prepare your equipment for shutdown 2 Press and hold the Off 1 button for approximately three seconds The indicator begins to flash The UPS transfers to Standby mode if utility power is availab
78. ver off the right retaining hook 4 Remove the screw on the left of the electronics module Remove the electronics module and retain the screw NOTE To prevent power loss to your equipment follow Step 5 closely 5 While inserting the new electronics module press and hold the 4 button for approximately five seconds or until the front panel indicators illuminate individually NOTE If the five load level indicators are flashing the module may not be properly seated Remove and reinsert the module as described in Step 5 6 Secure the electronics module to the UPS chassis with the screw removed in Step 4 7 Replace the UPS front cover 8 Replace the X Slot card if removed in Step 2 9 Reconnect the communication cable if removed in Step 1 10 See Recycling the Used Battery or UPS on page 59 for proper disposal Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerquality UPS MAINTENANCE When to Replace Batteries When the 4 indicator flashes and the audible alarm beeps intermittently the batteries may need replacing Contact your service representative to order new batteries Replacing Batteries 1 NOTE DO NOT DISCONNECT the batteries while the UPS is in Battery mode With the hot swappable battery feature UPS batteries can be replaced easily without turning the UPS off or disconnecting the load If you prefer to remove input power to chan
79. when the UPS starts up or returns from a utility failure The UPS is recharging the batteries The indicator turns off when the batteries have reached an acceptable charge level If the or 4 indicator is still on after 48 hours contact your service representative NM ZIN Intermittent audible alarm Ground wire connection does not exist or the line and neutral wires are reversed in the wall outlet Have a qualified electrician correct the wiring To disable this alarm see Configuration on page 43 Mo RI AN Intermittent audible alarm Bypass is out of tolerance Input voltage is not within 10 of nominal The UPS is receiving utility power that may be unstable or in brownout conditions The UPS continues to supply power to your equipment If conditions worsen the UPS may switch to battery power Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D 67 www eaton com powerquality TROUBLESHOOTING Alarm or Condition Possible Cause Action The UPS is in Bypass mode The equipment is transferred to utility power Battery mode is not available however the utility power continues to be passively filtered by the UPS Check for one of the following alarms Overtemperature Overload UPS Failure or Battery Service 9 100 O O 25 Power requirements exceed UPS capacity 102 to 110 for 2 minutes or gt 110 for 12 cycles
80. y Alarm or Condition Possible Cause TROUBLESHOOTING Action ur X NU ZIN Intermittent audible alarm The UPS is on battery due to a utility failure The UPS is powering the equipment with battery power Prepare your equipment for shutdown The UPS is running on battery power because the input voltage is too high or too low The UPS continues to operate on battery until the condition is corrected or the batteries are completely discharged If the condition persists the input voltage in your area may differ from the UPS nominal Change the UPS input voltage to match your local voltage see Configuration on page 43 The utility line voltage and frequency are out of specification Have a qualified electrician check the wiring un NZ 1 4 AIN Continuous audible alarm The batteries are running low Three minutes or less of battery power remains depending on load configuration and battery charge Save your work and turn off your equipment 7 I ZIN Intermittent audible alarm The batteries are not connected correctly Check the battery connections Call your service representative if the problem persists The batteries need to be replaced Contact your service representative to order new batteries See Replacing Batteries on page 55 D NI AN Intermittent audible alarm The batteries are low
81. y that the REPO connector is installed on the rear panel The indicator is flashing The UPS is in Standby mode power is not available at the UPS output Press and hold the On button for approximately three seconds to supply power to the connected equipment The UPS operates normally but The equipment is not connected to the UPS some or all of the protected equipment is not on correctly Verify that the equipment is plugged into the UPS receptacles For hardwired models contact a qualified electrician to check connections to the power source Load segment circuit breakers are in the OFF position Switch load segment circuit breakers to the ON position Load segments have been turned off by power management software or a communication card Modify the settings for Load Segment Control in the LanSafe software or the ConnectUPS X Web SNMP Card refer to the individual user s guide The UPS does not provide the The batteries need charging expected backup time or service Plug the UPS into a power outlet apply utility power on hardwired models for 48 hours to charge the batteries If the 4 indicator is on see Replacing Batteries on page 55 Battery circuit breakers are in the OFF position Switch all the battery circuit breakers to the ON position 66 Eaton 5125 Rack Mount UPS 5000 6000 VA User s Guide 164201541 Rev D www eaton com powerqualit
Download Pdf Manuals
Related Search
Related Contents
User Manual - Association of Public Health Laboratories ABB ACS350 VFD Inverters LG LC-1000 Air Conditioner M2N32-SLI Premium Vista Edition Spezifikationsübersicht Samsung L210 Kasutusjuhend SPAN-SE user manual 入力すると下記の画面が表示されます。 ー (入力の方法は、 ご Sea Gull Lighting 4135-962 Installation Guide Copyright © All rights reserved.