Contents
1. Area ot high sensitivity Technical data 6m Areaot lower sensitivity 86mm 22mm 23 5mm 86mm MWS1A PRM Supply Voltage Frequency Power consumption Load MWS1A PRM LV Supply Voltage Power consumption Load MWS1A PRM VFC Supply Voltage Frequency Power consumption Load 230VAC 10 50Hz On 1 15W Off 790mW 10A of lighting and or ventilation including incandescent fluorescent compact fluorescent low voltage switch primary of transformer Min 11 5VDC max 36VDC min 10VAC max 26 5VAC On 1 01W Off 712mW Low voltage supply with relay output rating 16A resistive 10A inductive 230VAC 10 50Hz On 1 15W Off 790mW Normally closed contact 2 Amp maximum Minimum load 100mA Normally open contact 6 Amp fluorescent lighting and resistive 3 Amp compact fluorescent lighting 3 Amp low energy lighting 3 Amp low voltage lighting switch primary of transformer All models Weight Terminal Capacity Time out period Light level Fixing method Temperature Humidity Material casing Compliance Safety Fluorescent lighting max 6 fittings recommended For fluorescent lighting total power factor correction capacitance must not exceed 4OuF 3 Amp fans and ventilation equipment Switch SON lighting loads via a contactor Minimum load 100mA 0 1kg 2 5mm Adjustable 10 seconds to 99 minutes Optional adjustment by using IR programming handsets Sur
2. SHIFT Parameter Default UHS5 Handset Graphics Description Name Value o Ol olo l amp SHIFT 1 SHIFT2 SHIFT1 SHIFT2 SHIFT1 SHIFT2 SHIFT1 SHIFT 2 Turn lights on Off Lower Time Out Time adjustment Turn lights off kk When set to On this causes a red LED to flash on the sensor when it detects movement Use this feature to check for adequate sensitivity levels _ 5 Bh Once the detector is turned on this value sets how long the lights will stay on once movement has ceased 10 mins Lux on level Switch level on Lux level setting to prevent the luminaires being switched on if the ambient light level is sufficient adjustable between 1 and 9 The luminaires will always be switched on at level 9 Lux off level Switch level off Sensitivity Presence Absence Lux level setting to switch the luminaires off during occupancy if the ambient light level goes above the setting adjustable between 1 and 9 Level 9 will always keep the lights on This setting can be used for window row switching Sensitivity level for detecting movement 1 low sensitivity 9 high sensitivity Returns the unit to the default settings Presence Presence Absence Absence mode not implemented do not use Use this button to select the settings in red and blue signified by the Shift 1 and Shift 2 LEDs Detection pattern Dimensions 30m
3. C P Electronics Ltd Brent Crescent London NW 10 7XR United Kingdom Tel 44 0 333 900 0671 Fax 44 0 333 900 0674 www cpelectronics co uk enquiry cpelectronics co uk Ref WD406 Issue 4
4. Product Guide N Priectronies MWS1A PRM Microwave Presence Detector wall mounted Overview The MWS1A series of microwave presence detector switches are designed to provide automatic control of lighting heating or ventilation loads The MWS1A detects movement using a highly sensitive microwave detector This works by emitting low power microwave signals and measuring the reflections as the signals bounce of moving objects The MWS1A is optimised for wall mounting applications to give detection over long distances When movement is detected the load is turned on When an area is no longer occupied the load will switch off after an adjustable time out period The internal light sensor provides additional energy saving in lighting applications When an area is occupied lighting is only switched on when the level of natural light is below a preset level Three variants are available MWS1A PRM Mains voltage switched live contact MWS1A PRM VFC Mains voltage isolated changeover contact MWS1A PRM LV Low voltage isolated changeover contact Fig 1 Front features Microwave Sensor Detects movement within the unit s detection range allowing load control in response to changes in occupancy IR Receiver Receives control and programming commands from an IR infrared handset Light Level Sensor An integral adjustable photocell allows the lights to be kept off if there is sufficient ambient light C amp Prese
5. face fixing 35mm deep plastic surface mount moulded box Flush fixing 25mm steel backbox or 25mm deep cavity backbox 10 C to 35 C 5 to 95 non condensing Flame retardant ABS Type Class 2 EMC 2004 108 EC LVD 2006 95 EC The microwave radiation emitted by these units is extremely low power At a distance of gt 50mm the power density is lt 6 of the ANSI IEEE C95 1 1991 recommended microwave power density At a distance of 5mm from the unit it is lt 84 of recommended power density MWS1A PRM MWS1A PRM LV MWS1A PRM VFC Microwave presence detector wall mounting Microwave presence detector wall mounting Low Voltage Microwave presence detector wall mounting Volt Free Contact Frequency compatibility The allowable frequency of operation of this product is different depending on region Please select the correct order code using the table below Region UK China India Middle East Malaysia Hong Kong Singapore Australia and all of Europe except UK France Portugal Germany Switzerland Austria Slovak Republic Republic of FM 45789 Due to our policy of continual product improvement CP Electronics reserves the right to alter the specification of this product without prior notice 4 Ireland France Portugal Switzerland Germany Austria Slovak Republic Republic of Ireland EMS 534520 energy services and technology association lectronics intelligent energy control
6. metal objects Fault finding What if the load does not turn ON Check to see if the live supply to the circuit is good For the MWS1A PRM version only strap across the L and LIVE OUT terminal to turn the load on If the supply and wiring are good check the LUX level setting Increase the LUX level setting to allow the controller to turn on at higher ambient natural light level What if the load does not turn OFF Ensure that the area is left unoccupied for a greater time period than the time out period set using the switch e Make sure that the sensor is not adjacent to vibrating surfaces or objects e g ventilation equipment The unit may pick up movement through thin partitions or walls Reduce the sensitivity 2 The functionality of the MWS1A is controlled by a number of parameters which can be changed or programmed by any of the following devices e UHS5 Infrared Handset See below for programmable functions e UN LCDHS Infrared Handset with LCD See user guide for full programming details For most basic programming operations the UHS5 handset can be used and the following procedures are based on using this device Point the handset at the Sensor and send the required programming commands to the unit as shown below Valid commands will be indicated by a red LED flash See page 1 for details of other LED responses Note other functions on the UHS5 which are not shown below are not applicable to this product
7. nce detection When movement is detected the load will automatically turn on When the area is no longer occupied the load will automatically switch off after an adjustable time period _ Status LED The LED flashes Red to indicate the following 17 Walk Test LED active Gy when movement is detected Ts I Valid setting received SRS Sensor Lens Mounting screw covers which covers IR Receiver Light Level Sensor Status LED Installation Back box Compatibility Mounting The MWS1A is designed to fit both UK and EU style backboxes Xi a Do not over tighten BS4662 square DIN standard round Mounti ack Dox back Dox ounting screw cover MWS1A PRM MWS1A PRM LV MWS1A PRM VFC Neutral Circuit protection if required Neutral Neutral Circuit protection if required Goi To switch from more than one position simply wire two or more units in parallel to achieve two way and intermediate switching The detector should be sited so that the occupants of the room fall inside the detection pattern shown overleaf at a recommended height of 1 2m to 1 5m for wall sensors Note that the higher the sensor is installed the shorter the detection range will be Do not site within 1m of any lighting or ventilation equipment Do not fix to a vibrating surface Site as far away as possible from the surface of