Home
        Momentum 171 CBB 970 30 M1 Processor User
         Contents
1.             0503 ram address test error   052D P O S T BAD MPU ERROR  0402 ram data test error   0300 EXEC not loaded   0301 EXEC Checksum   8001 Kernal prom checksum error  8003 unexpected exec return  8005 Flash program   erase error  8007 Watchdog timeout event                31007547 1 2007    99       LED Patterns  Error Codes  and Diagnostic Messages       Diagnostic Message Codes                                                                                                          TCP IP The following table describes the diagnostic messages associated with the hex   Diagnostic numbers displayed in the Diag code column of the Ethernet I O Scanner dialog   Messages when the Diagnostic Block is selected in Concept  see p  64     Diagnostic Description   Code  in hex    1001 User has disabled the row in the Ethernet I O Scanner dialog    2001 not applicable   2002 not applicable   2003 Invalid value in a length field of the row in the Ethernet I O Scanner dialog    2004 Invalid value in a Ref  field of the row in the Ethernet I O Scanner dialog    2005 Invalid values in the length and Ref  fields of the Ethernet I O Scanner dialog    2006 Invalid slave device data area    2008 not applicable   3000 not applicable   30ss  Modbus slave 3001  Slave device does not support the requested operation    exception response    3992   Nonexistent slave device registers requested    3003   Invalid data value requested   3004 is reserved  3005   Slave has accepted long duration progr
2.        82    31007547 1 2007    Configuring with ProWORX 32       Selecting the  Controller Family  and the  Controller    In the Select Controller dialog  go to item 1  Pick a controller family  and select  Momentum     Then from item 2  Pick a controller  select 171 CBB 970 30    New Project  New970    Select Controller    Select a controller to see its size and performance  ratings  Click Next to select the current controller and  continue with its configuration     1  Pick a controller family  2  Pick a controller       Momentum     M1 970 30      User Memory   18k  Data Memory   512k  Discrete IO   8192 8192  Register IO   26032  Scan Speed   0 16 ms k of logic   Modbus ports   1  Ethernet ports   4    Supported IO Types          Cancel  lt Back   Next gt    Finish               31007547 1 2007    83    Configuring with ProWORX 32       Modbus  Communication  Settings    The possible communication modes for a controller type can be accessed in the  Communications Setup dialog  The dialog has four tabs   Modbus  Modbus  Plus  Gateway  or TCP IP     In the case of the 171 CBB 970 30 processor  select the Modbus tab  The following  information appears in the dialog   New Project  NewProject    Communications Setup    Select the desired communication mode   Selected Communications Type  Modbus    Modbus  ModbusPlus Gateway  TCP IP      J Modbus Communications Setup               al Modbus Address 1  Port COM 1  Baud Rate 9600  Parity Even  Stop Bits 1  Data Mode RTU  Timeout
3.        Ethernet Cable Use Ethernet CAT5E or CAT6 grade cables with EIA568 pinouts to connect devices  Selection to the Ethernet ports on the 171 CBB 970 30 processor  The maximum cable length  between devices is 100 m     In high noise environments  shielded CAT5  CAT5E  or AT6 cables must be used           31007547 1 2007 25    The Ethernet Switch       Network Design Considerations    Introduction    Concurrent  Communication    Obtaining  Network MAC  and IP  Addresses    Operating  without Battery  Back up       In a distributed control environment  the Ethernet ports on a Momentum  171 CBB 970 30 processor can connect to     e anetwork with distributed I O and control devices  e a supervisory network  e a network that combines I O and supervisory functions    The following discussion examines some network design considerations that can  make communication between related devices as effective and deterministic as  possible        A maximum of 96 devices can communicate with the Momentum 171 CBB 970 30  processor at any one time over Ethernet  The types of devices and the maximum  number of each device type are as follows     e 2 programming panels  one of which must be in monitor mode    e 14 general purpose Modbus server paths   e 16 MSTR elements  MSTR elements support Modbus Read  Modbus Write  and  Modbus Read Write commands    e 64 cyclic configured data slave paths       When installed on a new network  the Momentum171 CBB 970 30 processor  obtains the MAC addresses
4.       2 If you have not previously modified any port parameters  the default Modbus port  settings appear  If you have modified any communication port parameters  the  new values display in the dialog box                                Modbus Port Settings  X   Bridge Mode  Baud   Data bits   Stop bits   Parity  Delay ms   Address   Head slot  Mode   Protocol  7    2   9600 8  1 Even 10 1 0  RTU RS232                                  Canc Hep                                              72 31007547 1 2007    Configuring Modbus Port Parameters       Changing the Modbus Communication Protocol       The Modbus port on the Momentum 171 CBB 970 30 processor can operate using  either the RS232 or RS485 communication protocol  see p  36   The default setting    is RS232     You can change the setting to RS485 in the Modbus Port Settings dialog  In the  Protocol column  the rightmost column in the dialog box   click the down arrow and    choose RS485        Modbus Port Settings             Bridge Mode       Baud Data bits   Stop bits       Delay  ms     Address    Head slot    Protocol       2   9600 8   1                               Cancel                         Help                            31007547 1 2007    73    Configuring Modbus Port Parameters       Changing Mode and Data Bits on Modbus Port       From the Modbus Port Settings dialog box  you can configure the port to operate    in RTU or ASCII mode     e In RTU mode  the number of data bits is 8  e In ASCII mode  the nu
5.       Configuring the Time of day Clock                Time of day The Momentum 171 CBB 970 30 processor has a time of day  TOD  clock  To use  Values this feature  reserve a block of eight contiguous 4x registers  Reserving Use the following procedure to reserve these eight TOD registers   Registers for the 7  TOD Clock Step   Action  1 From the Configure menu  select Specials     The Specials dialog box appears    Specials                      31007547 1 2007 53    Configuring with Concept                                           Step   Action   2 Check the Time of Day box  the third item on the top left of the dialog    3 Type the number of the first 4x register in the series of eight  The number must be in  the range of available 4x references  and there must be at least seven more  contiguous registers after it in the available range  In the example below  a value of  100 is entered  indicating that the eight TOD registers will be 40100     40107    4 Click the OK button  The registers you have specified are displayed on the PLC    Configuration screen           54    31007547 1 2007       Configuring with Concept       The TOD  Registers    After you have reserved the block of TOD registers  you need to set the correct time   With Concept  go online and set the register bits individually  as indicated in the table  below  The CPU must be running        Register    Data Content       4x    The control register       4x 1    Day of the week  where a value of 1   Sunday  
6.    10 31007547 1 2007    Processor Overview       Ethernet Switch The four RJ45 connectors on the top of the processor are for the four 10 100BASE   Interfaces T ports provided by the built in Ethernet switch  The connectors are labeled 1 to 4  from left to right        You can connect up to four Ethernet 10 100BASE T devices or network segments  to these ports over twisted pair or shielded twisted pair cables  The network  segments may be     distributed I O modules  other Momentum processors  supervisory systems  computers   programming panels   other Ethernet products    The functionality of the 4 port Ethernet switch is described in more detail later in this  manual  see p  23            Note  The Ethernet connectors and the Modbus port connector at the bottom of the  module are female RJ45 connectors with a similar look  Do not attempt to make a  Modbus connection through an Ethernet connector                 31007547 1 2007    11    Processor Overview                                           Ethernet Port Each Ethernet port has two LED indicators  LINK ACTIVE and 100MB  Their  LED Indicators indications are described below   LED Pattern Indication  LINK  On A valid link is established on the associated Ethernet port  ACTIVE Blink A receive or transmit activity is occurring on the associated  Ethernet port   If the 100MB LED is off  the activity is ata 10BASE T speed  If  the 100MB LED is on  the activity is ata 100BASE T speed   Off No valid link established on the ass
7.    Cable for Modbus RS485 Networks Connecting Momentum Components        109  Connectors for Modbus RS485 Networks Connecting    Momentum Components             0 0  c cece eet teen eeee 111  Terminating Devices for Modbus RS485 Networks Connecting   Momentum Components             0 0 cece eee eee eee tees 112  Pinouts for Modbus RS485 Networks Connecting   Momentum Components             0 0  eee eet eens 113  a ae fia whe dase a E ahha Saab  oncayapin fe ln E aa ae caer tehi cated fateh Saeed Menara E E aterm da emake 117          Safety Information Za       Important Information    NOTICE       Read these instructions carefully  and look at the equipment to become familiar with  the device before trying to install  operate  or maintain it  The following special  messages may appear throughout this documentation or on the equipment to warn  of potential hazards or to call attention to information that clarifies or simplifies a  procedure     The addition of this symbol to a Danger or Warning safety label indicates  A that an electrical hazard exists  which will result in personal injury if the    instructions are not followed    This is the safety alert symbol  It is used to alert you to potential personal  injury hazards  Obey all safety messages that follow this symbol to avoid  possible injury or death     A DANGER    DANGER indicates an imminently hazardous situation  which  if not avoided  will  result in death or serious injury           A WARNING       WARNING indic
8.    Processor Overview       Panel Software Options    Overview       The Momentum 171 CBB 970 30 processor can be programmed and configured  with either     e Concept  version 2 6  with service release 4  patch A  or greater  e ProWORX 32  version 2 1 or greater    The processor can solve control logic written in an IEC programming language or in  the 984 Ladder Logic programming language     The processor is shipped with the IEC firmware installed  With the IEC firmware  you  can immediately use Concept to configure the device and program your control  application  Chapters 4  see p  41   5  see p  57   6  see p  67   and 7  see p  71   describe Concept   s configuration procedures and capabilities in more detail     ProWORX 32 users can download 984 Ladder Logic firmware from the Schneider  Website  www telemecanique com  Chapter 8  see p  87  describes configuration  procedures and capabilities of ProWORX 32 in more detail           31007547 1 2007    15    Processor Overview       Memory Characteristics    Introduction    Internal Memory    Flash RAM       The Momentum 171 CBB 970 30 processor is equipped with internal memory and  Flash RAM        Internal memory comprises user memory and state RAM    User memory contains the control logic program and the system overhead   processor adapter configuration  I O mapping  checksum  system diagnostics   etc      State RAM is the area in memory where all the input and output references for  program and control operations are de
9.    Processor Status LEDs    POWER OK  PLC Run  PLC LAN Status       Ethernet isolation    1500 VRMS for 1 min       Cable recommended    Twisted pair  CAT5 or better        Shielding recommended for noisy environments       Maximum cable distance       100m          Environmental protection  IP20              94    31007547 1 2007          Specifications       Serial Port    Mechanical    Performance  Specifications       Serial port types    1 port       RJ45 connector       RS232 RS485  selectable        RS232  default        Communication rates    50   19 2k baud        Protocol    Modbus       Shock       15 g peak  11ms  half sine wave       Ref  IEC 68 2 27 EA          RFI Susceptibility Immunity       Meets CE mark requirements for open equipment   Open equipment should be installed in an industry standard  enclosure  with access restricted to qualified service personnel              Weight    232 g  7 5 0z       Dimensions  HxDxW     143 8 x 43 2 x 7 42 mm  5 6 x 1 7 x 2 9 in           Enclosures Bezel Material       Lexan                                           Operating   Temperature  25     70 degrees C  Conditions   Chemical Enclosures and bezels are made of Lexan  a  Interactions polycarbonate that can be damaged by strong alkaline  solutions   Altitude  Full 2000 m  6500ft    Operation  Vibration 10    57 Hz   0 075 mm displacement amplitude  57     150 Hz   1g  Ref  IEC 68 2 6 FC  Shock    15 g peak  11 ms  half sine wave  Ref  IEC 68 2 27 EA  RFI Susceptibil
10.   Click the Copy button above the I O configuration list              Select the row where you would like to paste the data  by clicking on a new row number in the leftmost  column            31007547 1 2007    61       Ethernet Parameters and I O Scanner          Step Action       4 Click the Paste button above the I O configuration list     Ethernet   1 0 Scanner        400008 400050  7Ho aa 400001 400040 10  aNorra   400008 400050 THold Las   400001 400040 10        o  a  E  a  al  o  o  ie   a             5 Click the  lt OK gt  button when finished  Your updated Bootp parameters are displayed in the Ethernet   I O  Scanner screen                    Cut and Paste To move a row within the configuration list  follow the procedure above  using the  Cut button instead of the Copy button        Delete To delete a row from the configuration list  select the row by clicking on the row  number in the leftmost column and clicking the Delete button        Sort To sort the I O configuration list numerically or alphabetically  select a column by  clicking on the column heading you want to sort and click the Sort button           62 31007547 1 2007    Ethernet Parameters and I O Scanner                      Fill Down To copy part of any row to the next row or to a series of adjoining rows  use the Fill  Down button  following the steps in the procedure below   Step Action  1 With your mouse  select the data you want to copy and the cells where you want the data to go  You  must select 
11.   EA Knowledge Base                     Segments 01   O Words 00032                               Duplicate Coil Start 00000  Controller Details       Specials  Controller Type M1 970 30 Battery Coil  Ox  00000  Moduies   og Timer Register  4x  00000  Total Logic 17672 Time of Day Clock  4x  00000  Config Extension Used 00000  Config Extension Size 00000  Enable Skips True  Watch Dog Time   10ms  00000                   Projects Project Info   a  Bridge Mode       New970 M1 970 30   MB  1  E Nxt demo 984 A145   MB  1     amp  a3 Quantum 534   MBP  59          z  roughput    lt    30   MB  1 gt   fi Proce                   86    31007547 1 2007    Configuring with ProWORX 32       Configuration  Extensions    Monitoring  Battery Coils    Configuring a    To access the Configuration Extensions tool  you must allocate memory  Enter the  amount of memory required in the Config Extension Size field  If you do not enter  a value in this field  the Configuration Extensions tool does not open        To monitor the battery coil  you must enter an address in the Battery Coil  0x  field        To set the time of day  TOD  clock  you must have the necessary rights and you                                                                                           Time of day must configure that a starting register in the Configuration panel   Clock  Step   Action  1   Put the controller in an Online and Running state   2   In the Configuration panel  select the Time of Day Clock  4x  field 
12.  3 Seconds  Modem Type None       Change Setting    Modem Setup    Network Explorer            Use server to communicate    Cancel  lt Back Finish       If you want to change a port parameter setting  select it with your mouse and click  the Change Setting    button  A dialog appears  allowing you to enter any valid  value associated with the selected parameter  The software supports range  checking at this level  and it does not allow you to apply invalid values to the selected  parameters     Once you have changed all the settings to meet your configuration needs  click the  Next  gt  button        Note  Make sure that the Modbus tab is still selected when you click the Next  gt   button              84    31007547 1 2007    Configuring with ProWORX 32       Finishing the After you have finished viewing and changing the configuration settings displayed  Configuration by the Configuration wizard  you can close the wizard and save any changes you  have made via the Finish dialog     New Project  New970    Finish    Click Finish to complete the operation     Controller Type  M1 970 30  User Memory   18k  Data Memory   512k  Discrete IO   8192 8192  Register IO   26032  Scan Speed    0 16ms k of logic  Modbus ports   1  Ethernet ports   4    Progress           Help Cancel    lt Back   Next gt          This dialog confirms the controller type and user memory settings  If you need to  make more changes  click the  lt  Back button and make your changes     Once your project and co
13.  DTR                         E S cable 8   lt a   chassis       shield ground                                                                      1 56 in  pin 1       31007547 1 2007 39    Modbus Port       RS485 Communication Capabilities       The RS485 protocol handles messaging over long distances with higher level of  noise immunity than RS232 without the need for modems  RS485 supports two wire  or four wire cabling  A multimaster slave system must use two wire cabling  A single  master slave system may use two  or four wire cabling     Details on cabling and accessories for RS485 networks are described in an  appendix  see p  103            40    31007547 1 2007       Configuring the  Controller in Concept 4       At a Glance    Overview    What s in this  Chapter        This chapter describes how to configure the CPU functions of the Momentum  171 CBB 970 30 processor using Concept  Configuring this processor requires  Concept version 2 6  with service release 4  patch A  or greater        Note  For a full description of Concept capabilities  refer to your Concept user  manuals and the Help system              This chapter contains the following topics                                Topic Page   Selecting the Momentum 171 CBB 970 30 Processor 42  Accessing Default Configuration Parameters 45  Changing the Size of the Full Logic Area 47  Changing the Range of Discrete and Register References 48  Understanding the Number of Segments 49  Reserving and Monitoring a Batte
14.  If the slave module is an I O device attached to the specified slave module  use the  Unit ID column  item 2 above  to indicate the device number        Use the Health Timeout column  item 3 above  to specify in ms how long to try a  transaction before timing out  Valid values are 0     65 000 ms  1 min   To avoid  timing out  specify 0        Use the Rep Rate column  item 4 above  to specify how often in ms to repeat the  transaction  Valid values are 0     65 000 ms  1 min   To repeat the transaction  continually  specify 0           31007547 1 2007    65    Ethernet Parameters and I O Scanner       Read    Write    Read and Write    Description    Use a Read function to read data from the slave to the master  The Read Ref Slave  column  item 6 above  specifies the first address to be read  The Read Length  column  item 7 above  specifies the number of registers to read  The Read Ref  Master column  item 5 above  specifies the first address to read to        Use a Write function to write data from the master to the slave  The Write Ref  Master column  item 8 above  specifies the first address to write  The Write Length  column  item 10 above  specifies the number of registers to write  The Write Ref  Slave column  item 9 above  specifies the first address to write to        You may include read and write commands on the same line        You can type a brief description  up to 32 characters  of the transaction in the  Description column  item 11 above            66    31007
15.  Modbus Port  Connector    Pinouts for  Modbus Port    The Modbus port connector is a female RJ45 connector located on the bottom right  of the processor  see p  12         The pin assignments on the Modbus serial port differ depending on whether you are    using RS232 or RS485 communications                                Pin For RS232 For RS485   1 DTR RXD     2 DSR RXD     3 TXD TXD     4 RXD Not used   5 signal common signal common  6 RTS TXD     7 CTS Not used   8 cable shield cable shield                      31007547 1 2007    37       Modbus Port       Cables and Adapters for a Modbus RS232 Connection    Overview    Modbus Port       To connect a computer or other host device to the 171 CBB 970 30 processor s  Modbus port  you need a cable with an RJ45 connector on one end and a connector  suitable for host device on the other end  Schneider Electric provides pre made  Modbus cables in three lengths and two types of SUB D adapters that can be used  for an RS232 connection to most computers        Schneider Electric   s three pre made Modbus cables are standard eight position  foil                                Cables shielded  flat telephone cables with male RJ45 connectors on each end  One RJ45  connector plugs into the Modbus serial port  and the other plugs into a female SUB   D adapter that fits onto the programming station   Length Part Number  1m  3 ft  110 XCA 282 01  3 m  10 ft  110 XCA 282 02  6 m  20 ft  110 XCA 282 03  Permanently connected cables must be 
16.  and IP addresses of the other Ethernet devices on the  network  This process may require several minutes        When the processor is successfully communicating with these devices and battery  back up is not present  we recommend that you stop the processor and save your  program to Flash  using Concept  see p  67  or ProWORX 32  see p  89   This  saves the processor   s ARP cache and enables it to restore the information rapidly if  power is lost or removed  If you do not save to Flash  the processor must reacquire  the ARP cache information from the network        Note  Preserve your ARP cache information              This procedure should also be followed whenever     e anew or substitute device is installed on the network  e the IP address of a network device has been changed          26    31007547 1 2007    The Ethernet Switch       Managing  Distributed I O  over Ethernet    Supervisory  Networks    In an Ethernet I O network  the Momentum171 CBB 970 30 processor controls  distributed I O modules equipped with Ethernet interfaces and other Transparent  Ready Ethernet devices  Some examples include Advantys STB I O islands and  Momentum distributed I O modules     The Momentum171 CBB 970 30 processor provides isolation from both MIS data  traffic and unrelated communication between other control devices  Traffic from MIS  data networks can interrupt communication between control devices  causing your  control application to behave unpredictably  The high message rates 
17.  bottom of the processor  see p  12   It is a 3 pin connector with the following pin  assignments     ane       VDC VDC    24            The grounding pin  the rightmost pin on the power connector  provides protective  earth  PE            Note  The grounding pin must be used at all times           Make sure that PE    is attached before connecting or disconnecting any Ethernet  shielded cables to the device           31007547 1 2007    19    Processor Overview       Noise Immunity  Considerations    Power Cable  Recommen   dations    If the processor is operating in a noisy environment  you may insert a jumper  between the     VDC and    pins in your power cable        If you are using a grounded power supply  the jumper is not required     If any other devices in your system are connected to the same power supply as the  171 CBB 9730 processor  your power supply connection must not affect any of  these other devices     You must maintain a voltage of less than 44 VDC between the     VDC and    pins        Note  Your electrical installation must meet local or nationally applicable safety  standards and regulations                 The PE ground must be capable of supporting 30 A of current for 2 minutes with no    more than 50 mQ of resistance  The recommended wire size is 3 2 to 0 87 mm    12 to 18 AWG    The maximum wire size must not be exceeded even if your wire  contains the  VDC to PE jumper      The maximum allowable length of the cable at 18 AWG is 2 m        Note  A 
18.  configure the Ethernet address parameters of the  Momentum 171 CBB 970 30 processor and how to set I O scanner parameters with  Concept  Configuring this processor requires Concept version 2 6  with service  release 4  patch A  or greater   Note  For a full description of Concept capabilities  refer to your Concept user  manuals and the Help system    What s in this This chapter contains the following topics        Chapter  Topic Page  Accessing the Ethernet I O Configuration 58  Setting the IP Address Parameters 59  Completing the Ethernet I O Configuration 61  Configuring Ethernet I O 64                      31007547 1 2007 57    Ethernet Parameters and I O Scanner       Accessing the Ethernet I O Configuration       To access and edit the processor s Ethernet IP address and I O scanning  parameters  select the Config Extensions     Ethernet I O menu in Concept  The  Ethernet I O Scanner dialog box appears  If you have not modified any of the  Ethernet port parameter settings  this dialog box appears the default parameters  as  shown in the example below     Ethernet   1 0 Scanner    Delete   Dow  Export      Ei i       a                   b          x                      5       TI            F0       EEEE          i                          EERMEEEEEEN  PEE EE ERE    E             If you have previously modified any communication port parameters  the configured  values appear in this dialog box           58 31007547 1 2007    Ethernet Parameters and I O Scanner       Se
19.  default is 1  Do not change           76    31007547 1 2007    Configuring Modbus Port Parameters       Changing Parity on the Modbus Port    Introduction       From the Modbus Port Settings dialog  you can configure the Modbus serial port  for even  odd  or no parity checking  The default is even     To change the parity parameter  click the down arrow in the Parity column ad select    either Odd or None                                                                                                                                      Modbus Port Settings  Bridge Mode  Baud Data bits Stop bits Parity Delay  ms  Address Mode Protoco   1 vw   2  9600     a1 Even      10 Rum  7  RS232  None  Odd   Cancel Help  31007547 1 2007 77    Configuring Modbus Port Parameters       Changing the Delay on the Modbus Port    Introduction       The Delay parameter is set to 10 ms and should be left at this value for most  applications  Do not change this parameter unless your application demands it     This parameter can be any value from 10     1000 ms  in 10 ms increments     If your baud setting  see p  75  is lower than 4800 for delay timing  adjust the delay  timing as indicated                       Baud Setting Delay  in ms   2400 20   1200 30   600 50   300 100          Click in the entry field of the Delay column  The default value  10  is displayed  To  change it  enter a new value in the range 20     1000  in increments of 10                                                  x  Br
20.  document  You can reach us by e mail at  techpub   schneider electric com          31007547 1 2007       The Momentum                                  171 CBB 970 30 Processor 1  At a Glance  Overview The Momentum 171 CBB 970 30 processor  with its built in 4 port Ethernet switch   provides programmable logic control to distributed communication networks  I O   and other Modbus TCP IP compatible devices connected to an Ethernet network   This chapter gives you an overview of the processor   s features and capabilities   Installation and power wiring instructions are also provided   What s in this This chapter contains the following topics   Chapter  Topic Page  Physical Components of the 171 CBB 970 30 Processor 10  Panel Software Options 15  Memory Characteristics 16  Installation 17  Power Wiring 19  Lithium Battery 21                      31007547 1 2007 9    Processor Overview       Physical Components of the 171 CBB 970 30 Processor       Front Panel View A front panel view of the Momentum 171 CBB 970 30 processor is shown below   The interfaces and LED indicators for the Ethernet switch are on the top half of the    module  The interfaces and LED indicators for the M1 processor are on the bottom  half of the module        Connectors for each of the four Ethernet ports   LINK ACTIVE and 100MB LED indicators for each of the four Ethernet ports  POWER OK LED   PLC Run and PLC LAN Status LEDs   R232 RS485 serial port connector   24 VDC power connector    ouhwnhd           
21.  following topics    2   Chapter  Topic Page  Modbus Serial Port 36  Cables and Adapters for a Modbus RS232 Connection 38  RS485 Communication Capabilities 40                   31007547 1 2007    35       Modbus Port       Modbus Serial Port    Introduction    Modbus Port  Parameters    Auto Logout       The Modbus port is an RS232 485 asynchronous serial port that permits a host  computer to communicate with the processor for     e programming   data transfer  upload download  other host operations                                              Baud Rates  50 300 3600  75 600 4800  110 1800 7200  134 2000 9600  150 2400 19 200   Parity Settings  EVEN ODD NONE   Mode Data Bits  RTU  8 bit  ASCII  7 bit    Stop Bit  1   Modbus Address  In the range 1    247          The factory set default communication parameters for the Modbus port are     RS232   9600 baud   EVEN parity   8 bit RTU mode   1 stop bit   Modbus address 1    The Modbus port cannot support more than 1 stop bit  If you change this default  setting in the configuration software  the Momentum processor ignores the change     All other port parameters can be modified in the configuration software        If a programming panel is logged into the CPU via the serial port and its cable gets  disconnected  the CPU automatically logs out of the port  With auto logout a user  does not accidentally lock other host stations out and stop them from logging in from  other ports           36    31007547 1 2007    Modbus Port      
22. 0 processor on your  network  verify that it contains the correct IP address and program for your  application     Failure to follow this instruction can result in injury or equipment damage           31007547 1 2007    29          The Ethernet Switch       BOOTP and  DHCP Servers    Retaining The IP  Address Setting    On start up  an unconfigured processor attempts to obtain an IP address by issuing  BOOTP requests  When a response from a BOOTP or DHCP server is obtained   that IP address is used     Consult your system administrator to obtain a valid IP address and appropriate  gateway and subnet mask  if required     Each IP address on the Ethernet network must be unique  The 171 CBB 970 30  processor checks for duplicate IP addresses on the network before it actively starts  network operations     If for any reason two or more devices coexist on an Ethernet network with the same  IP address  network operations are unpredictable        A BOOTP or DHCP server is a program that manages the IP addresses assigned to  devices on the network  Your system administrator can confirm whether a BOOTP  or DHCP server exists on your network and can help you use the server to maintain  the 171 CBB 970 30 processor s IP address        If the processor has lost its battery back up capability and you want the IP address  setting to be retained after power is removed from the module  save your program  to Flash using Concept  see p  67  or ProWORX 32  see p  89   IP address retention  on r
23. 2   Monday  etc         4x 2    Month of the year  where a value of 1   Jan  2   Feb  etc         4x  3    Day of the month  a value between 1   31        4x  4    Year  a value between 00   99        4x 5    Hour in military time  a value between 0   23        4x  6    Minute  a value between 0   59        4x 7          Second  a value between 0   59        The first TOD register is the control register  Its four most significant bits report TOD  clock status                 1 2  3 4 5 6                   7                10       11       12          13       14       15       16                    __    error       1   All clock values are set  4   1   Clock values are being read  L    1   Clock values are being set          31007547 1 2007    55       Configuring with Concept       Reading the Time of Day Clock                                  Example If you reserve registers 400100   400107 as your eight TOD clock registers and set  the clock at 9 25 30 A M  on Thursday  July 16  1998  the register values are as  follows    Register   Reading  in decimal  Indication   400100 0110000000000000  All clock values are set and are being read  400101 5 Thursday   400102 7 July   400103 16 16   400104 98 1998   400105 9 9 A M    40010 6 25 25 min   40010 7 30 30 sec                      56    31007547 1 2007          Configuring Ethernet Address  Parameters and I O Scanner 5  with Concept                                        At a Glance   Overview This chapter describes how to
24. 31007547 01    a brand o  Ste    Electric    Momentum   171 CBB 970 30  M1 Processor  User Guide    1 2007    Telemecanique    www telemecanique com       Table of Contents       Safety Information5       Chapter 1    Chapter 2    Chapter 3    Chapter 4    About the  Bok  icsi nre ficken wien ace age eee ne eae Rye ae eee 7  The Momentum 171 CBB 970 30 Processor          02ee cece ee eeeeeee 9  Physical Components of the 171 CBB 970 30 Processor                 5 10  Panel Software Options          0 0 0 0 cece ete eee 15  Memory Characteristics      2 0 0 0    cect tees 16  installation ri  20 c30ceeh edb ele ie de AE eee Le eee 17  Power  WINING     2c  eu ssieck odati t ora ade eres Gee er EREE a aena aa ew alee 19  lithium Baterya ccs ee et Va ce Sek eR hE 21  The 4 port 10 100BASE T Ethernet Switch             00 cee eee eee eee 23  The Ethernet Switch  Hia ciare A ee ee ete ae eee ee va 24  The Ethernet Port Connections             00 0  cece tte 25  Network Design Considerations             00 0  cette ee 26  Network Security Firewalls         u n uaaa c eect tees 28  Assigning Ethernet Address Parameters                00  e eee e eee 29  Using BOOTP Lite to Assign Address Parameters               0 00000  31  Reading Ethernet Network Statistics      0 0 0    0    cece eee 32  Using the Modbus Port     2 0 0    c cece eee eee eee eee eens 35  Modbus Serial Port            0    ccc eee eee 36  Cables and Adapters for a Modbus RS232 Connection                    38  RS4
25. 547 1 2007       Saving to Flash in Concept       Saving to Flash in Concept       You save flash so that in the event of an unexpected loss of power the application  logic state RAM values are preserved        Note  The following conditions apply for saving to Flash   e All Momentum programs using the 984LL Exec  have the option of saving to  Flash     e The contents of memory may be retained using batteries  which are contained  in the Momentum processor     e The 171 CBB 970 30 can use either an IEC or a 984LL Exec  The minimum  984LL Exec  version that can be used is 1V 1 06  Both IEC and 984LL Execs   allow the option of saving to Flash           Note  The 171 CBB 970 30 require Concept 2 6 with service release 4  patch A                    31007547 1 2007 67    Saving to Flash       Saving to Flash                                                                                                                                                          Step Action   1 From the Online menu on the main menu bar  select Connect  The Connect to   PLC dialog box appears   Connect to PLC  x   Protocol type  e     m Protocol settings  Modbus   Modbus Plus PLC Node   Ru   Device  9600    8 1   IEC Simulator  32 bit 001    ASCII comi F Port Settings      Access Level       ___List of nodes on Modbus Plus network       Monitor only A  O Change Data      Change Program      cnan Contouraton   Host adapter   Cancel Rescan  lt  Previous Next  gt  Help  Configure the parameters you want 
26. 70 MCI 041 10  4 Modbus Plus   Modbus RS485 short interconnect cable   170 MCI 020 10  5 Modbus RS485 connector  T   RJ45 base  170 XTS 041 00             31007547 1 2007    105          RS485 on the Modbus Port       Single Master  The following illustration shows components used in a four wire single master slave   Slave Option 2 cabling scheme  In this view  the master is at one end of the network and is  connected by a single master cable   3   Terminating resistors   1  are used at both  ends of the network     Each Momentum module must include a processor adapter or option adapter with a  Modbus RS485 port                                                                                                                 Master Slave Slave Slave Slave   Legend    Label Description Part Number   1 Terminating resistor plug 170 XTS 021 00  2 Modbus RS485 connector  T   DB9 base  170 XTS 040 00  3 Modbus RS485 master communication cable 170 MCI 041 10  4 Modbus Plus   Modbus RS485 short interconnect cable 170 MCI 020 10  5 Modbus RS485 connector  T   RJ45 base  170 XTS 041 00                         106 31007547 1 2007    RS485 on the Modbus Port       Two Wire Cabling Schemes for Modbus RS485 Networks Connecting  Momentum Components    Introduction    Length    Number of  Devices    Termination    Cable       Two wire cabling schemes may be used for single master slave or multimaster   slave communications  Masters may be located anywhere in the network        A CAUTION       
27. 85 Communication Capabilities          00 0    e eee ee 40  Configuring the Controller in Concept              0c cece cece eens 41  Selecting the Momentum 171 CBB 970 30 Processor                 0005  42  Accessing Default Configuration Parameters                02000ee ee eeee 45  Changing the Size of the Full Logic Area    2 2 0 0    cece eee eee 47  Changing the Range of Discrete and Register References                  48  Understanding the Number of Segments              000 cee eee eee eee 49  Reserving and Monitoring a Battery Coil           00    cece eee 50  Configuring the Time of day Clock         0 0 0  c cece tee eee 53  Reading the Time of Day Clock            0 0  c eee e eet eee 56          Chapter 5    Chapter 6  Chapter 7    Chapter 8    Appendices  Appendix A  Appendix B    Appendix C    Configuring Ethernet Address Parameters and I O Scanner    With  CONC DE ioiai iaa dive ie etl tee ee Laa FE ee ere ake oe edie es 57  Accessing the Ethernet I O Configuration               0 00  e eee eee eee 58  Setting the IP Address Parameters             0 0000 e cece eee eee eeee 59  Completing the Ethernet I O Configuration                00 00 eee e eens 61  Configuring Ethernet I O              000 ccc eect eee ene 64  Saving to Flash in Concept         00 0 ccc e eee ee eee eee eee 67  Configuring the Modbus Port Parameters in Concept                 5 71  Accessing the Modbus Port Settings Dialog Box                0 e eee eee 72  Changing the Modbus Communicat
28. 984  171 CCC 780 10 IEC a Hoo  18 K logic   32 K state   fo   i     5 From the CPU Executive menu  click 171 CBB 970 30 984 or 171 CBB 970 30 IEC to select the  Momentum 171 CBB 970 30 processor The remaining fields fill with corresponding values   6 Click the OK button  Your PLC type and default configuration parameters are displayed in the PLC  Configuration screen   44    31007547 1 2007       Configuring with Concept       Accessing Default Configuration Parameters    The Default  Parameters    Accessing the  Configuration  Parameters in  Concept       The default configuration parameters for the 171 CBB 970 30 processor are     1536 coils in state RAM   512 discrete inputs in state RAM   48 input registers in state RAM   1872 output registers in state RAM   17649 nodes in the full logic area   144 words of user memory for the I O Map   No memory allocated for configuration extension       From the Config Extensions menu  select Select Extension     If your configuration is IEC  984 Only  the following PLC Configuration screen    appears        mj PLC Configuration    B Summary   B PLC Selection  B PLC Memory Partition    Config Extensions  Ethernet I O  B VO Map  B Segment Scheduler  B Modbus Port Settings  B ASCII             31007547 1 2007    45    Configuring with Concept       If your configuration is IEC  IEC Only  the following PLC Configuration screen  appears       fii  PLC Configuration    Config Extensions  Select Extension  B Ethernet 1 0  E 1 0 Map  E Segmen
29. Description    Part Number    Illustration       Modbus Plus or Modbus RS485  short interconnect cable  10    Can be used for Ethernet    170 MCI 020 10       Modbus Plus or Modbus RS485  3 ft  interconnect cable  Can be used for Ethernet    170 MCI 020 36          Modbus Plus or Modbus RS485  10 ft  interconnect cable  Cannot be used for Ethernet       170 MCI 021 80                   31007547 1 2007    109          RS485 on the Modbus Port       Other Premade  Cable    Custom Cable    Custom Cable  Vendors    Crimping Tool       Description    Part Number    Illustration          Modbus Plus or Modbus RS485  30 ft  interconnect cable  Cannot be used for Ethernet       170 MCI 020 80                   Interconnect and Ethernet cable in various lengths and boot colors may be obtained  from other vendors  including Amp                          Description Amp Part Number  2ft 621 894 2  5ft 621 894 4  7 ft 621 894 5  10 ft 621 894 6  14 ft 621 894 7                For custom cabling  use Cat  5 4 twisted pair Ethernet cable AWG 26  It may be  shielded or unshielded  Shielded cable is recommended for long runs and for noisy  environments  You may use stranded or unstranded cable  Keep in mind that  stranded cable is more f       Vendors include                          Vendor Part   for Shielded Cable   Part   for Unshielded Cable  Belden 1633A 1583A non plenum  1585A plenum  Berk Tek 530131 540022  Alcatel Cable Net      Hipernet Cat  5   UTP  LSZH rated cable           Schnei
30. Network statistics occupy words 0   37 in the Modbus status table    Statistics Word Data Description   00     02   MAC Address   03 Board Status   04 05   Rx Interrupt Number of frames received by this station  Only broadcast  frames pertinent to this station and individual address match  frames are received and counted    06 07   Tx Interrupt Number of frames transmitted from this station  Includes all  transmitted broadcast frames for ARP and BOOTP    08 09   Not used    10 11   Total Collisions   This field should always be 0    12 13 Rx Missed Receive frame was missed because no buffer space was   Packet Errors   available to store the frame  Indicates firmware unable to keep up  with link  The only time this should increment is during a save   user logic to Flash operation  when all interrupts are disabled for  10 sec    14 15   Not used    16 17   Chip Restart High Word  Not used  always 0    Count Low Word  Peak Collision Detector  should always be 0    18 19   Framing Errors   Counts the number of received frames addressed to this node    Giant Frame that are longer than 320 bytes  Any such large frame has no   Error  relevance to the 171 CBB 970 30 processor and is skipped  This  error should not occur    20  21 Overflow Errors   Increments whenever a received frame cannot be copied into the  frame buffer because the frame buffer is full  This situation should  never occur under legal Ethernet traffic    22 23   CRC Errors Increments when a packet is received with a
31. OOTP option  click on this radio button        The Specify IP Address option allows you to type in an IP address  gateway  and                         Address Option subnet mask of your choice  If you choose to Specify IP Address  you need to enter  parameter data in the Internet Address  Gateway  and Subnet Mask fields on the  top right side of the screen    Note  Consult your system administrator to determine the appropriate gateway  and subnet mask numbers    Disabling If you choose the Disable Ethernet option  you will no longer be able to   Ethernet communicate with the processor over any of the Ethernet ports  Your programming  and communications functions must be conducted via RS232 or RS485 over the  Modbus serial port  see p  36     60 31007547 1 2007    Ethernet Parameters and I O Scanner       Completing the Ethernet I O Configuration       Introduction You can use the Copy  Cut  Paste  Delete  Sort  and Fill Down buttons to complete    your Ethernet I O configuration        Copy and Paste To save time when typing similar read and write commands  you can copy and paste    entire rows within your configuration  Follow the steps in the procedure below        Step    Action       1    Select the row you want to copy by clicking on the row number in the leftmost column     Ethernet   I O Scanner     0 0 0 0 G     iri C86 97030       Copy   _Cut   Paste  Import   Fs00001  Delete  Toon  Export    400001 400040    E apre m aeee pa sali Ca tse  ig A es   omen              
32. POTENTIAL FOR MULTIMASTER CONFLICTS    Conflicting messages to a slave module can cause problems   e Configure a multimaster network carefully to avoid masters issuing  simultaneous or conflicting commands to the same slave module        Failure to follow this instruction can result in injury or equipment damage              The maximum length of cable from one end of network to other is 2000 ft   609 m         The maximum number of devices in a network is 64 if all are Momentum devices   Otherwise  the maximum is 32        One end of the cable run must be terminated with a terminating resistor  color code  is red     The other end of the cable must be terminated with a terminating shunt  which  connects the transmit pair to the receiver pair  color code is blue         Description Part Number       Modbus Plus or Modbus RS485 terminating RJ45 resistor plugs 170 XTS 021 00   pack of 2        Modbus RS485 terminating RJ45 shunt plugs 170 XTS 042 00                   All devices are connected with the same pin for pin cable  such as the Modbus Plus  or Modbus RS485 short interconnect cable or any Cat  5 4 twisted pair Ethernet  cable AWG 24  A master slave system using 2 wire cabling does not require the  special master communication cable        Description Part Number       Modbus Plus or Modbus RS485 short interconnect cable 170 MCI 020 10  Color code  black                      31007547 1 2007    107    RS485 on the Modbus Port       Multimaster  The following illustration 
33. RS485 Networks Connecting 104  Momentum Components  Two Wire Cabling Schemes for Modbus RS485 Networks Connecting 107  Momentum Components  Cable for Modbus RS485 Networks Connecting Momentum Components 109  Connectors for Modbus RS485 Networks Connecting Momentum 111  Components  Terminating Devices for Modbus RS485 Networks Connecting Momentum 112  Components  Pinouts for Modbus RS485 Networks Connecting Momentum Components 113                      31007547 1 2007 103    RS485 on the Modbus Port       Four Wire Cabling Schemes for Modbus RS485 Networks Connecting  Momentum Components    Introduction    Length    Number of  Devices    Termination    Master Cable    Slave Cabling       Four wire cabling schemes may be used for single master slave communications   Only one master is allowed  The master may be located anywhere in the network        The maximum length of cable from one end of network to other is 2000 ft  609 m         The maximum number of devices in a network is 64 if all are Momentum devices     Otherwise  the maximum is 32        You must terminate both ends of the cable run with special terminating resistors        Description    Part Number       Modbus Plus or Modbus RS485 terminating RJ45 resistor plugs   pack of 2   Color code  red          170 XTS 021 00          The master of this master slave cabling scheme must be connected on at least one  side to a master cable  a special cable that crosses the transmit and receive lines     The other side may be c
34. a Modbus connector              The 171 CBB 970 30 processor requires 19 2 to 42 5 VDC of power to the unit from  an external safety extra low voltage  SELV  power source  The 3 pin power  connector is located on the bottom left of the module  The connector   s pin  assignments are labeled on the front panel above the connector                 Pin Position Description   Left   24 VDC   Center  VDC   Right Protective earth  PE              Note  The PE pin must be used at all times  Make sure that PE is attached before  connecting or disconnecting any shielded cables to from the Ethernet ports              Power wiring considerations are described in more detail later in this manual   see p  19            31007547 1 2007 13    Processor Overview       M1 Processor  LED Indicators    The processor has three LED indicators  Power OK  PLC Run and PLC LAN Status   Their functions are described in the table below                                         LED Pattern Indication  POWER OK   On Internal power supply is providing normal operating  voltages to the switch circuits  Off Internal power supply is not at normal operating  voltages  PLC Run On The PLC has received power and is solving logic  Blink Flashes an error pattern  see p  98   Off CPU is not powered up or is not solving logic  PLC LAN On The PLC is in a normal run condition  Status Continuous Blink   Normal Ethernet initialization at power up  4 flashes Duplicate IP address detected             14    31007547 1 2007    
35. a block of contiguous cells  with the data to be copied in the first row  You cannot select  two separate blocks   Ethernet  1 0 Scanner  s  f  s   300001     O Normal    400008 Eo     xl    2  Ethernet 71 0 Scanner   90 UO OT  orma 4 ___ Hold Las    400     Normal     400008 400050 Hold Las     prore 400008 400050 Hold Las  3 Click the OK button  Your updated BOOTP parameters are displayed in the Ethernet   I O Scanner  dialog                    31007547 1 2007    63       Ethernet Parameters and I O Scanner       Configuring Ethernet I O    Overview    Health Block       Once the Ethernet port address parameters have been set  you can configure the  remaining parameters in the Ethernet   I O Scanner  dialog        Enter a starting reference in the window to the right of the Health Block  1x 3x   entry  The health block contains a health bit for each of the IO Scanner transactions  that you intend to configure  The reference may be either a 3x register or a 1x  discrete input reference     Ethernet   1 0 Scanner    1 Hold  400001 400040  5 Hold 400050 400055 _          l  4        f             If you designate a 3x register  as shown in the example above   the health bits for  64 transactions  maximum  are stored in 4 contiguous registers starting at the  address you specify     If you designate a 1x discrete input reference  the health bits are stored in 64  contiguous registers  using 1 bit register     A health bit is set only if the associated transaction completes succ
36. am command   3006   Function cannot be performed now  a long duration command is in  effect   3007  Slave rejected long duration program command    4001 Inconsistent MODBUS slave response    F001 Optional module not responding   F002 Module not fully initialized   5004 interrupted system call   5005   O error   5006 no such address   5009 socket descriptor is invalid   500C not enough memory   500D permission denied   5011 entry exists   5016 an argument is invalid   100    31007547 1 2007       LED Patterns  Error Codes  and Diagnostic Messages                                                                                                                      Diagnostic Description   Code  in hex    5017 an internal table has run out of space  5020 connection is broken   5028 destination address required   5029 protocol wrong type for socket  502A protocol not available   502B protocol not supported   502C socket type not supported   502D operation not supported on a socket  502E protocol family not supported   502F address family not supported   5030 address already in use   5031 cannot assign requested address  5032 socket operation on a non socket  5033 network is unreachable   5034 network dropped connection on reset  5035 network caused connection abort  5036 connection reset by peer   5037 no buffer space available   5038 socket is already connected   5039 socket is not connected   503A cannot send after socket shutdown  503B too many references  cannot splice  503C co
37. and Error Codes 98  Diagnostic Message Codes 100                      31007547 1 2007 97    LED Patterns  Error Codes  and Diagnostic Messages       Run LED Flash Pattern and Error Codes       Error Codes    The following table lists the flash pattern of the PLC Run LED on 171 CBB 970 30                                                                                              Table Momentum processor and the associated codes  in hex format     Number of Blinks Code  hex  Error   Continuous 0000 Requested Kernel mode   2 080B RAM error during sizing  080C run output active failed  082E MB command handler stack error  0835 Main loop broken  0836 Power down   Power holdup  0837 Power down reset absent  072B master config write bad  0607 modbus cmd buffer overflow  0608 modbus cmd length is zero  0609 modbus abort command error  0614 mbp bus interface error  0615 bad mbp response opcode  0616 timeout waiting for mbp  0617 mbp out of synchronization  0618 mbp invalid path  0619 page 0 not paragraph aligned  061E bad external uart hardware  061F bad external uart interrupt  0620 bad receive comm state  0621 bad transmit comm state  0622 bad comm state trn_asc  0623 bad comm state trn_rtu  0624 bad comm state rcv_rtu  0625 bad comm state rcv_asc  0626 bad modbus state tmrO_evt  0627 bad modbus state trn int  0628 bad modbus state rcv int  0631 bad interrupt                   98    31007547 1 2007       LED Patterns  Error Codes  and Diagnostic Messages                            
38. and enter a value into that field   3   Close the Configuration panel   4   Select the Logic icon in the hierarchy tree of the Projects tab   The Logic panel with the Network Navigator tree appears   Right click the Network Navigator tree  Result  A shortcut menu appears   Select Hardware Clock from the shortcut menu  Result  The Hardware Clock dialog box appears   The First Day of Week field contains a drop down list box  In the list box  select the day  Sunday through Saturday  that  the controller will use as the first day of the week   Setting the Time The time of day clock requires that you reserve eight contiguous 4x registers in your  processor   Register Content  4x Controller Information  from left to right Bit 1  Set Clock Values  Bit 2  Read Clock Values  Bit 3  Done  Bit 4  Errors  4x 1 Day of week  from 1 to 7   4x 2 Month  4x 3 Day  4x 4 Year  4x 5 Hour  in 24 hour format   4x 6 Minutes  4x 7 Seconds  You can set the date and time automatically  using Auto Set  or manually by  entering the correct values in the TOD registers   31007547 1 2007 87          Configuring with ProWORX 32       Monitoring the Health of the System    Configuring  Parameters      Health Block       Once you have established communication with the controller  you may assign  parameters for I O scanning  see p  64      Specify the starting register of the register block which will contain the health bits for  each of the I O Scanner transactions that you intend to configure     If you desi
39. ates a potentially hazardous situation  which  if not avoided  can result  in death  serious injury  or equipment damage           A CAUTION       CAUTION indicates a potentially hazardous situation  which  if not avoided  can result  in injury or equipment damage                    31007547 1 2007    Safety Information       PLEASE NOTE Electrical equipment should be installed  operated  serviced  and maintained only by  qualified personnel  No responsibility is assumed by Schneider Electric for any    consequences arising out of the use of this material      2007 Schneider Electric  All Rights Reserved           31007547 1 2007       About the Book                At a Glance    Document Scope    Validity Note    Related  Documents       This manual describes the 171 CBB 970 30 Momentum M1 processor  The  processor contains 544 Kbytes of internal memory and can be programmed with  either     e Concept  version 2 6  with service release 4  patch A  or greater  e ProWORX 32  version 2 1 or greater    The processor also contains a 4 port 10 100 Ethernet switch        The data and illustrations found in this book are not binding  We reserve the right to  modify our products in line with our policy of continuous product development  The  information in this document is subject to change without notice and should not be  construed as a commitment by Schneider Electric                       Title of Documentation Reference Number  Momentum I O Base User Guide 870 USE 002  Concept U
40. cation level firewalls reside on individual host computers   28 31007547 1 2007    The Ethernet Switch       Assigning Ethernet Address Parameters    IP and MAC  Addresses    Obtaining an IP  Address       The Momentum 171 CBB 970 30 processor is shipped from the factory without an  IP address assignment  At initial start up  the processor attempts to obtain an IP  address from a BOOTP or DHCP server     A MAC address is set for every processor at the factory     Ethernet IP address  default gateway  and subnetwork mask parameters can be  assigned with one of following applications     Concept  see p  59    ProWORX 32   The BOOTP Lite software utility  A DHCP server          A CAUTION          UNPREDICTABLE NETWORK OPERATIONS    Make sure that your Momentum 171 CBB 970 30 processor has a unique IP  address on the Ethernet network     Failure to follow this instruction can result in injury or equipment damage           A CAUTION          COMMUNICATION ERRORS    After taking the Momentum 171 CBB 970 30 processor out of service  clear the   program and IP address to prevent future conflicts    To clear the IP address    e Go to the Ethernet I O Scanner dialog in Concept  see p  58  or the  Configuration Extensions dialog in ProWORX 32  and make sure that the IP  address acquisition method is set to use a BOOTP server    e With the BOOTP method selected  save the configuration to Flash    e Then decommission the processor     Before installing a replacement Momentum 171 CBB 970 3
41. ceed the maximum  of state memory displayed at the top of the dialog    e Aminimum configuration of 16 discrete outputs  16 discrete inputs  one input  register  and one output register is required        Use the PLC Configuration screen to change the range of discrete and register  references  and follow the procedure below        Step    Action       1    From the Configure menu  select Memory Partitions  The PLC Memory  Partition dialog box appears  showing the maximum memory size and the  register allocation for the processor    PLC Memory Partition    Maximum State Memory  6144  State Memory Used  2538    State Memory Usage  41        Discretes          Coils  Oxxxx     EES  Discretes Inputs  1xxxx    512                Registers          Input Registers  3xxxx     48                Holding Registers  4xxxx     1872                                     Modify the range of your discrete and register references by changing the value  in the variable boxes  according to the guidelines above              Click the OK button              48    31007547 1 2007       Configuring with Concept       Understanding the Number of Segments       The number of segments specified in the Configuration Overview screen  determines the number of I O drops you can set up for your processor  The default  number of segments is 32           31007547 1 2007 49    Configuring with Concept       Reserving and Monitoring a Battery Coil       Introduction The Momentum 171 CBB 970 30 processor does n
42. chapter contains the following topics        Chapter  Topic Page  Configuring an Momentum Processor with ProWORX 32 82  Configuring an I O Map 86  Monitoring the Health of the System 88  Saving to Flash with ProWORX32 89                   31007547 1 2007    81          Configuring with ProWORX 32       Configuring an Momentum Processor with ProWORX 32    Introduction    Creating a New  Project       Use the ProWORX 32 Configuration wizard to configure the Momentum   171 CBB 970 30 processor  The Configuration wizard walks you through the steps  for creating a new project or modifying an existing one  Each screen in the wizard  has a caption indicating the step you are currently working on and a diagram with a  description detailing what the current step involves                 Step Action  1 Start ProWORX 32   2 Select File   New Project     The New Project   Select creation method    dialog appears     New Project  NewProject    Select creation method    If you need to immediately connect to a controller   select    Online to Controller     If you want to create a  new controller project offline  please select one of the  three offline project creation options           Online to Controller      Offline   Use as a Macro      Select Controller Type  C Base on Existing Project  C Read from Controller          Finish  3 Select Offline   Select Controller Type  and click Next   Other options are available  but Schneider Electric recommends selecting the  default                
43. der Automation provides a crimping tool  490 NAB 000 10  and an RJ45 die  set  170 XTS 023 00  to attach the 170 XTS 022 00 connector to the cable           110    31007547 1 2007       RS485 on the Modbus Port       Connectors for Modbus RS485 Networks Connecting Momentum Components    Overview    RJ45  Connector  T     DB9  Connector  T     Connectors for  Custom Cabling       This section describes the connectors which should be used in constructing an    RS485 network for Momentum components        This connector is used with the RS485 port        Description Part Number    Illustration       Modbus RS485 connector  T   RJ45 base  170 XTS 041 00                   This connector is used with the RS485 port        Description Part Number Illustration       Modbus RS485 connector  T   DB9 base    170 XTS 040 00             ey    SCHNEIDER  AUTOMATION INC    i fied          This RJ45 connector should be used when constructing custom cable for an RS485    network        Description Part Number Illustration       RJ45 connector  pack of 25  170 XTS 022 00                         31007547 1 2007    111             RS485 on the Modbus Port       Terminating Devices for Modbus RS485 Networks Connecting Momentum  Components       Overview This section describes terminating devices which should be used in constructing  Modbus RS485 networks for Momentum devices        Terminating Terminating resistor plugs are used with the RS485 connector  RJ45 base  at the  Resistor Plugs last dev
44. dit View Project Controller Server Utilities Window Help  8x  Sa LASNE 400 ALGSE o PAAT      a ezn   JEN PE INE   gt   SHAT IHRT ADO sua MULT OV ig  WZ w menok we  x Instructions El  I Direct to Online 7 7       Workspace     i   it N a  obtu  A ere N H  IF Configura Online Commands _      Start Stop  OPEN ISHAT  4 vette os Project State     2Blnitialize Controller Logic AD A00     Toga    n BE change Controller Type  Read       at i  aoe PLC Web Link write B  Write s  Date Fai z Relocate Logic and Data bee on  configura  i E   SAR        Write Extended Memory pera ow      Analyze 4  _ uetr Transfer to Flash  EEPROM e Eii    i m FOUT     knowled 01301 ed  s Ott tof  us  MSTA  ck Statu  MULT  Import Documentation        n Rat sea  Export Documentation  F    O  f0  RoT si  Logbook 00002 001305 001304 SIRES al  r Audit Trail ot of Name  Projects JF Backup Project    News7 M    NCB     SNxtdemo 99   Restore Project  Saas Q 2 Close Project 00010  MIE 87030 Trou Properties    s 1    ow pronos Pv onea  a5 omes      001304  Eran   Domens New970 M1 970 30 Offline Used 00029 17672 Views  x     l     Logic Editor    The Logic Editor is used to enter logic elements  edit register values  display input output data  and add descriptors and comments to a network  3  While online  data is gathered from the controller instead of a database  as offline does   It uses programming commands for Modbus and Modbus Plus    communication protocols to retrieve the data  Es  R         Logged in user  t
45. ector  T      DB9 Base     The illustration below shows the pinout for the 170 MCI 02x xx Modbus RS485  interconnect cables  10 in  3 ft  10 ft and 30 ft      RJ45 Connector    RJ45 Connector    RXD  1   lt    _   RXD     RXDt 2 wg p 2 RXD    TXD  3  lt q 3 TXD   TXD  6   qf     6 TXD   Notused 4 4 Not used  Signal 5 q4     p5 Signal  common common  Notused 7 7 Not used  Shield 8 q                         8 Shield       The illustration below shows the pinout for the Modbus RS485 connector  T   DB9    base      RJ45 Shielded Connector    RXD     RXD     TXD     TXD     Shield    8    Shell    RJ45 Shielded Connector                a 1 RXD   a 2 RXD   m 3 TXD   4  5 Signal  common  6  7  8 Shield  Shell             7 2 1 4 3    RXD  RXD  TXD  Signal  common          TXD     DB9 Connector          114    31007547 1 2007    RS485 on the Modbus Port       Terminating  RJ45 Resistor  Plugs    Terminating  RJ45 Shunt  Plugs    RJ45 Connector       1 1 4W    1210hm   2 1    3   4 1 4W   1210hm   5 1    6   7   8   RJ45 Connector    EE          31007547 1 2007    115    RS485 on the Modbus Port          116 31007547 1 2007       Index          Numerics  100MB indicators  12    A    adapters   Modbus host device  39  address parameters  29  ASCII mode   Modbus port  36  auto logout feature   Modbus port  36  auto MDI MDI X   on the Ethernet ports  24  auto negotiation   on the Ethernet ports  24  auto polarity   on the Ethernet ports  24    battery back up  operating without  26  batt
46. ery coil  in Concept  50  in ProWORX 32  87  baud rates  Modbus port  36  BOOTP server  for IP address management  30    C    cables   Modbus port  38  connectors   Ethernet switch ports  11   Modbus port  13  37  control register   TOD clock  55    D    data bits   Modbus port  36  DHOP server   for IP address management  30  diagnostic block   I O scanner configuration  65  diagnostic message codes   Ethernet network  100  distributed I O networks   design considerations  27  duplicate IP addresses  29    E    error codes  98  Ethernet address parameters  29  Ethernet network statistics  32  Ethernet switch   capabilities  24  Ethernet switch port connectors  11       31007547 1 2007    117    Index       F    firewalls  28  Flash  saving to  89  Flash RAM  16  front panel view  10  full duplex mode  on the Ethernet ports  24    G    grounding requirements  19    H    half duplex mode   on the Ethernet ports  24  health block   I O scanner configuration  64    I O scanner transactions  configuration  64  IP address assignment  29    L    LED  error codes  98  LEDs  Ethernet port status indicators  12  M1 processor indicators  14  LINK ACTIVE indicators  12    M    MAC address assignment  29  MDI MDI X  24  Modbus address range  36  Modbus cable   SUB D adapters  39    Modbus port  36   auto logout feature  36   cable  38   changing protocol RS485  73   pinouts  37  Modbus port connector  13  37  Modbus port parameters  36  Modbus RS485  40   cable  109   Connectors  111   f
47. essfully within the  last health time out period for that transaction  see below   When the PLC is started   the health bit for each configured transaction is preset to 1  If a transaction  subsequently fails  its health bit is cleared after the programmed health time out  period expires        64    31007547 1 2007    Ethernet Parameters and I O Scanner       Diagnostic Block    IP Address          Unit ID    Health Timeout    Rep Rate       If an you want to display Ethernet diagnostic information on your I O scanner  transactions  check the box next to the Diagnostic Block  3x 4x  entry  just below  the Health Block  3x 4x  entry  and enter a starting reference in the window  The  reference may be either a 3x or a 4x register  The system automatically reserves 64  contiguous registers starting with the reference value you enter     When the box is checked  a new column called Diag Code appears in the Ethernet  I O Scanner dialog  Whenever a diagnostic error is detected  a hexadecimal integer  code appears in this Diag Code column  The meanings of these diagnostic codes  are described in an appendix  see p  100         Type the IP address of the slave module in the IP Address column  item 1 below    This address is stored in a pull down menu so that you can use it in another row by  clicking on the down arrow and selecting it        o   8  a gt   aJ  8      Norma 400008 400050 1 ken 400001 400040 10  7 Normal 400020 _ 400050 5 Hold 400050 400055 1          Cancel  Hel      
48. estart differs depending on the way the processor is configured     If a processor without battery back up is configured to use the BOOTP server  and an IP address was previously saved to Flash  the processor issues three  BOOTP requests 5 sec apart    e  f a BOOTP response is received from the server  the new IP address is  assigned but not automatically saved to Flash  To save the new IP address to  Flash  you need to use your panel software  If a power cycle occurs on the  processor  the IP address that is currently saved to Flash is used    e  f a BOOTP response is not received from the server  the processor uses the  IP address that is saved in Flash  Three ARP broadcasts are made 5 sec apart  to check for duplicate IP addresses  Three additional ARP broadcasts are  made 2 sec apart with the station   s MAC address and IP address     If a processor without battery back up is configured for Specify an IP Address  and an IP address was previously saved to Flash  the processor listens for  any BOOTP messages but does not issue any BOOTP requests  It uses the  saved IP address  Three ARP broadcasts are made 5 sec apart to check for a  duplicate IP address  Three additional ARP broadcasts are made 2 sec apart with  the station   s MAC address and IP address           30    31007547 1 2007    The Ethernet Switch       Using BOOTP Lite to Assign Address Parameters       The BOOTP Lite Instead of a BOOTP or DHCP server  Schneider Electric s BOOTP Lite utility  Alternative softwa
49. evices       Key Features The Ethernet switch has four 10 100BASE  T ports that can operate independently  at 100 Mb s full duplex or half duplex  or at 10 Mb s full duplex or half duplex  It  supports switched Ethernet networks in accordance with IEEE standard 802 3 or  802 3u using copper technology     The switch supports     auto negotiation The switch automatically negotiates speed  10BASE T or  100BASE T  and full  or half duplex mode  Auto negotiation is managed  independently on each of the four switch ports     auto polarity The switch detects and compensates for an incorrectly wired cable   i e   cable where the RX  and RX  signal inputs need to be swapped  Auto   polarity is managed independently on each of the four switch ports     auto MDI MDI X The switch auto switches the transmit  TX  and receive  RX  wire  pairs as needed to establish communications with the end device  As a result  the  processor is able to transparently interconnect with any other 10 100BASE T  Ethernet device with either straight through or crossover cables  Auto negotiation  is managed independently on each of the four switch ports     multi addressing The switch learns the switching parameters for up to 1024 MAC  addresses  The switch deletes inactive address entries  those exceeding 300 sec  of inactivity      tagging The switch transmits data packets unchanged with the VLAN tag  in  accordance with IEEE 802 1q     store and forward The switch stores all the data it receives  checks it 
50. f the following conditions    e The original data frame was garbled  corrupted  and lost   e The target TCP IP stack is operating more slowly than the  processor retry rate    For Modbus 502 servers  the processor initiates retries after  1   1  2  2  4  8  sec    For Modbus 502 clients  the processor retry rate is the larger of   e We the health timeout for Ethernet I O Scanner data    e 4times the previous measured TCP IP round trip time for i o  Scanner MSTR block       30  31    Late Collision    Increments when the transmit frame process is aborted because  of a late collision detection  after the first 64 bytes of the frame  were transmitted collision free   This field should always be 0        32  33    Lost Carrier    Although this error is theoretically possible  it is rare   Note If you see a non zero value  please report it to your  Schneider Electric Service Representative        34  35    16 Collision Tx  Failure       Transmit frame process aborted after 16 consecutive collisions   The frame was not successfully transmitted onto the Ethernet  link  This error should never occur           36  37       IP Address             31007547 1 2007    33       The Ethernet Switch          34    31007547 1 2007       Using the Modbus Port                         At a Glance   Purpose This chapter describes the Modbus port  its communication parameters  cabling  guidelines and pinouts for R232 485 operations  and cable accessories    What s in this This chapter contains the
51. fined and returned     You can change the processor   s internal memory allocation using the PLC Memory  Partition feature that is part of your panel software        Flash RAM contains the executive firmware  which is the operating system for the  PLC  It also contains a firmware kernel  a small portion of memory that recognizes  acceptable executive firmware packages and allows them to be downloaded to the  processor  The firmware kernel cannot be changed     You can store a copy of the application program and the state RAM values in Flash  RAM     When the Momentum 171 CBB 970 30 has successfully established communication  with other devices  we recommend that you stop the processor and save the  application program to Flash  This manual describes the procedures for saving to   Flash with both Concept  see p  67  and ProWORX 32  see p  89      This procedure saves the processor   s ARP cache  enabling you to rapidly restore  communication if power is lost or removed  It is also useful when a new or substitute  device is installed on the network or when the IP address of a network device is  changed           16    31007547 1 2007    Processor Overview                                                                                  Installation  Mounting The Momentum 171 CBB 970 30 processor can be installed on a DIN rail or  Options mounted on a wall inside a panel enclosure   Note  The processor is designated as open equipment per EN61131 2  You need  to install open equip
52. for the proper  packet length  and executes a CRC validity check  Packets meeting the criteria  are forwarded to their destination  Packets that do not meet both criteria are  discarded     queuing An output port that is slow or congested never affects the transmission of  frames to ports that are non congested  Traffic will always be received on the  input port           24 31007547 1 2007    The Ethernet Switch       The Ethernet Port Connections       Introduction The Momentum 171 CBB 970 30 processor contains four 10 100BASE T ports   Four RJ45 connectors are provided on the top of the module for connectivity to each  of the four ports  see p  11         Wiring The following figure illustrates a standard pin assignment for the four Ethernet RJ45  connectors  Remember that the switch can automatically change the pin  assignments as a function of its auto MDI MDI X and auto polarity features   see p  24      Pin 8  Pin 7  TD  Pin6    TD  Pin 3  RD  Pin 2  RD  Pin 1          The TD    pair  pins 3 and 6  and the RD    pair  pins 1 and 2  are swapped when auto   MDI MDI X occurs  The switch automatically compensates for this swap    The RD  and RD  assignments on pins 1 and 2 are swapped when auto polarity occurs   The switch automatically compensates for this swap    Pins 4 and 5 are shorted together and terminated  This pin assignment is standard for  Ethernet devices    Pins 7 and 8 are shorted together and terminated  This pin assignment is standard for  Ethernet devices 
53. gnate a 3x register  the health bits for 64 transactions  maximum  will be  stored in 4 contiguous registers starting at the address you specify     If you designate a 1x register  the health bits will be stored in 64 contiguous discrete  registers     A health bit is set only if the associated transaction has completed successfully  within the last health timeout period for that transaction  When the PLC is started  all  configured transactions have their respective health bit preset to 1  If the transaction  subsequently fails  then the health bit is cleared after the programmed health  timeout period has expired     Additional health bits can be viewed by clicking on the PLC Status icon located in  the project tree           88    31007547 1 2007    Configuring with ProWORX 32       Saving to Flash with ProowORX32    Overview    Procedure for       You save to Flash so that in the event of an unexpected loss of power the application  logic and state RAM values are preserved     This topic describes how to save the application logic and state RAM values to Flash  using ProoWORX32        Follow the steps in the table below to save to Flash                                                                    Saving to Flash    Step   Action  1   Go to the Projects tab in the left panel   e Right click the project icon  a sub menu appears      Select Online Commands   Write   Transfer to Flash EEPROM       ProWORX 32    New970  Offline    Logic Editor  New970      jo  x   File E
54. ice on either end of a four wire cable network or at one end of a two wire  cable network        Description Part Number Illustration       Modbus Plus or Modbus RS485 terminating   170 XTS 021 00    RJ45 resistor plugs  pack of 2  j   Saas  Color code  red i ME                      Shunt Plugs Shunt plugs are used with the RS485 connector  RJ45 base  at one end of a two   wire cable network  The plug is used at the last device on the network        Description Part Number Illustration       Modbus RS485 terminating RJ45 shunt plugs 170 XTS 042 00  Color code  blue     at                         112 31007547 1 2007    RS485 on the Modbus Port       Pinouts for Modbus RS485 Networks Connecting Momentum Components    Overview    RJ45 Pinout    Master  Communication  Cable       The pinouts for wiring an RS485 network to a Momentum 171 CBB 970 30    processor are described below           pin 8    pin 1 RXD    pin 2 RXD    pin 3 TXD      pin 4 reserved   pin 5 signal common  pin 6 TXD     pin 7 reserved   pin 8 shield       The illustration below shows the pinout for the 170 MCI 041 10 Modbus RS485   RJ45 RJ45  master communication cable     RJ45 Connector    RXD   RXD   TXD    TXD     Not used    Signal  common    Not used  Shield    1    on oa A WO D DY    1    on o A OO Q N    RJ45 Connector    RXD   RXD   TXD    TXD     Not used    Signal  common    Not used  Shield          31007547 1 2007    113    RS485 on the Modbus Port       Interconnect    Cables    Modbus RS485  Conn
55. idge Mode  Baud Data bits   Stop bits   Parity   Delay ms  Address   Head slot   Mode   Protocol  1 l    7 AC 7                               Cancel Help                            78    31007547 1 2007       Configuring Modbus Port Parameters       Changing the Modbus Network Address of the Modbus Port       Introduction The Modbus serial port has Modbus network address in the range 1     247  That  address must be unique with respect to all other device addresses on the same  Modbus network  The default Modbus network address is 1     To change the Modbus address  go to the field in the Address column in the  Modbus Port Settings dialog  The default value 1 appears  Type a new value in the  range 2     247              x                   Bridge Mode          Baud Data bits   Stop bits Parity   Delay  ms  Address N Head slot Mode Protocol  il          L    2   9600  v  Smi Even 10 1 0 RTU RS232  Cancel Help                                                                                     31007547 1 2007 79    Configuring Modbus Port Parameters          80    31007547 1 2007       Configuring Momentum  Processor with ProWORX 32                                     At a Glance   Overview This chapter explains how to configure the Momentum 171 CBB 970 30 processor  using ProWORxX 32  Configuring this processor requires ProWORX 32 version 2 1  or greater   Note  For a full description of PPOWORX 32 capabilities  refer to the Help system  in the software    What s in this This 
56. ion Protocol                  20 00005 73  Changing Mode and Data Bits on Modbus Port                0000000eee 74  Changing the Modbus Port   s Baud Rate               2000 cece eee eeee 75  Stop Bit Should Not Be Changed            0 0 0  c eects 76  Changing Parity on the Modbus Port                000 cece eee ence eee 77  Changing the Delay on the Modbus Port                000 cece eee eee 78  Changing the Modbus Network Address of the Modbus Port                 79  Configuring Momentum Processor with ProWORX 32             2   5 81  Configuring an Momentum Processor with ProoWORX 32               25  82  Configuring an I O Map    1    eee ett 86  Monitoring the Health of the System         0 0 0 0  c cece tee eee 88  Saving to Flash with ProOWORX32         0  0 0 cece teen 89  se nice deste Gel ae ue A A E fated ays Seek a ue tes tobner A E A al tot caum aie 91  Momentum 171 CBB 970 30 Processor Specifications                   93  LED Flash Patterns  Error Codes  and   Diagnostic Messages          00 cece eee eee eee 97  Run LED Flash Pattern and Error Codes              000 000 cece eeeeeeee 98  Diagnostic Message CodesS        0 0    cece tenes 100  RS485 Accessories for the Modbus Serial Port              0 0eeeeee 103  Four Wire Cabling Schemes for Modbus RS485 Networks Connecting   Momentum Components             0 0 cece eee ett eee 104  Two Wire Cabling Schemes for Modbus RS485 Networks Connecting   Momentum Components             0 0 cece eee eet ene eee 107 
57. ity  Meets CE mark requirements for open equipment   Immunity Open equipment should be installed in an industry   standard enclosure  with access restricted to qualified  service personnel   Storage Temperature  40      85 degrees C  Conditions   Humidity 5     95   noncondensing           31007547 1 2007    95             Specifications       Electrical          Safety Degree of Protection   Unintentional access  UL 508 Type 1  NEMA250 Type    Parameters    1  IP20 conforming to IEC529        Di electric Strength    Ethernet is isolated from logic common 500 VDC       Ground Continuity    30 A test on the exposed metal connector          Agency Approvals    UL 508  CSA  CUL  CE                Power Range    19 2 to 42 5 VDC input from a safety extra low voltage   SELV  source       Operating Input Current   Typical     0 1 A at 24 VDC       0 12 A at 19 2 VDC       Maximum Inrush Current    50 A  for less than 2 ms           Overload Current Protection          Non replaceable fuse             96    31007547 1 2007          LED Flash Patterns  Error Codes                       and Diagnostic Messages 8B  At a Glance  Overview This appendix describes Run LED flash patterns and error codes on the Momentum  171 CBB 970 30 processor and the Ethernet diagnostic messages that can be  viewed when you enable the Diagnostic block in the Ethernet I O Scanner dialog   see p  64    What s in this This chapter contains the following topics   2  Chapter  Topic Page  Run LED Flash Pattern 
58. less than 3 m long  Temporary cables must  be less than 100 m long   If you are making you own Modbus cable  the maximum cable length is 9 5 m   38 31007547 1 2007       Modbus Port       Modbus Cable Two SUB D adapters are available from Schneider Electric that can be used with a  Adapters Modbus cable to enable a host device to connect to the Modbus port     e A110 XCA 203 00 9 pin adapter for 9 pin serial ports  e A110 XCA 204 00 25 pin adapter for 25 pin serial ports    These adapters have an RJ45 jack on one end that allows them to clip into your  Modbus cable     Here is the pinout for the 110 XCA 203 00 9 pin adapter              CPU     PC AT Pinouts  RJ45 Connector 9 pin SUB D       DTR1 1    TXD3   lt    _e 2 RXD  RXD4   lt     _ 3 TXD    4 40 screw RJ45 jack Dene  DIR  Vihreads  8x8  GND 5 5 GND  i E   6 DSR  BE CTS 7 a it 7 RTS       pel  RTS 6 8CTS  TAIN 9RI           cable8    4                   cable of  5 i    CST shield the connector   lt q 50 8mm    P   2in  pin 1                                                                                                                                  Here is the pinout for the 110 XCA 204 00 25 pin adapter                 CPU     PC XT Pinouts      pin 1 RJ45 Connector 25 pin SUB D             DTR 1 1  RXD4   lt        B 2 TxD  TXD3   lt        YB gt  3 RXD    CTS7 4 RTS  pin 25 RTS 6 5 CTS    ooo0oo0000000000  DOOOOO00000Q                      Z 6 DSR  GND 5 7 GND   4 40 jack RJ45 jack 8 DCD  Y screws  8x8  DSR 2 20
59. mber of data bits is 7    The default mode is RTU     To change the mode and data bit parameters from the default settings  click the    down arrow in the Mode column and select ASCII     Modbus Port Settings                Bridge Mode       Baud Data bits Stop bits Parity   Delay  ms     Address    Mode    Protocol                2 9600  v 8 1   Even    110                                  Rt Ir R5232                                          Cancel             ASCII          Help                The Modbus Port Settings dialog updates the mode type  and the value in the Data    bits column automatically changes from 8 to 7           74    31007547 1 2007    Configuring Modbus Port Parameters       Changing the Modbus Port   s Baud Rate       The Modbus serial port can be configured for one of 16 possible baud rates in the  range 50     19 200  see p  36   The default is 9600 baud     To change the baud rate  click the down arrow in the Baud column and select the    desired rate fro    m the list     Modbus Port Settings                Bridge Mode       Baud    Data bits    Stop bits    Parity    Delay  ms     Address    Mode    Protocol                2  9600ms  v                   4    Even          y  10             RTU             RS232                2000  a   2400    3600  4800  7200                               Cancel             Help                      31007547 1 2007    75    Configuring Modbus Port Parameters       Stop Bit Should Not Be Changed       The stop bit
60. ment in industry standard enclosures with access restricted to  authorized personnel   DIN Rail  Mounting    Ste Action  Procedure p  1 Put the wire lock on the back of the processor is in the down position   2 Align the mounting channel on the back of the processor to the DIN rail and  press it onto the rail until it snaps into place   3 Push the wire lock up to lock the processor onto the DIN rail   Note  The contact springs on the back of the processor may be used as the  functional ground if the DIN rail is grounded   Panel Wall Two mounting holes are provided on the front of the 171 CBB 970 30 processor   Mounting      1  213   4  10 100T Shee      RST  Momentum 171 CBB 97030  Processor  4 Port Switch  ENET  RS232 485  Mounting holes  31007547 1 2007    17          Processor Overview       Securely fasten the processor to the wall with two metal mounting screws  4 mm   0 16 in  in diameter and 25 mm  0 97 in  long with 8 mm  0 31 in  screw heads     The metal mounting screws may be used as the functional ground if the panel is             grounded   Mounting  Dimensions SS  La 74 2 mm Ji A   lt  56 2 mm  gt  mih  70 mm  KA I    approx   64 3 mm          y  143 8 mm  h d  y  A  min 137 mm  bd          18 31007547 1 2007    Processor Overview       Power Wiring    Power Wiring    Grounding  Considerations       The 171 CBB 9730 processor requires 19 2 to 42 5 VDC of power from an external  safety extra low voltage  SELV  power source  The power connector is located on  the
61. mmunication settings are complete  click the Finish button     The newly created project appears in the project navigation tree in the Projects  panel           31007547 1 2007 85    Configuring with ProWORX 32       Configuring an I O Map       Introduction As part of the configuration process  you need to set the controller properties for the    Momentum 171 CBB 970 30 processor  The controller properties set the  appropriate range and type of reference values  0x  1x  3x  or 4x  for the CPU   s state       RAM   Use the ProWORxX 32 configuration tool to edit or view your project   s current  configuration   Using the To use the Configuration tool  you need to open a project  For the examples used  Configuration below  the name of the project is New970     Tool    In the following screen  the icon for the Configuration tool is selected in the tree  hierarchy of the Projects tab  and the Configuration  New970  panel appears to  the right of the Projects tab        ProWORX 32    New970  Offline    File Edit View Project Controller Server Utilities Window Help  OSHLAR oe 1 2 AG Bee 9 8 BOD  e ervnwi og  3 2  Ht   Wi  w  2H eaw Ve i                              Direct To Online   4 Workspace       gt  New970  lt Offline gt   if  Configuration                      ontroller Properties                               Faa Traffic Cop Ranges   we Communications OXxxx 01600   FT Logic TxXxx 00256  E Data Editors 3XXXX 00099    Configuration Extensions   4 PLC Status  E  Analyze Device
62. nnection timed out  see note  below    503D connection refused   503E network is down   503F text file busy   5040 too many levels of links   5041 no route to host   5042 block device required   5043 host is down   5044 operation now in progress   5045 operation already in progress   5046 operation would block   5047 function not implemented          31007547 1 2007    101       LED Patterns  Error Codes  and Diagnostic Messages                                                       Diagnostic Description   Code  in hex    5048 hardware length is invalid   5049 route specified cannot be found   504A collision in select call  these conditions have already been selected by another task   504B task ID is invalid   5050 no network resource   5051 length error   5052 addressing error   5053 application error   5054 client in bad state for request   5055 no remote resource  may indicate no path to remote device  See note  below    5056 nonoperational TCP connection   5057 incoherent configuration   Note  Error 5055 can occur before a 503C error  No remote device takes precedence over a timeout              102    31007547 1 2007          RS485 Accessories for the  Modbus Serial Port C                                  At a Glance   Overview When you are using RS485 communication on the Modbus serial port  four wire and  two wire cabling networks are supported    What s in this This chapter contains the following topics    2   Chapter  Topic Page  Four Wire Cabling Schemes for Modbus 
63. ny of the following   e CRC error  e Extra data error  e Runt error   32 31007547 1 2007       The Ethernet Switch          24  25    Receive Buffer  Errors  Out of  Server Paths     Increments when a client attempts and fails to connect to an  Ethernet port because there is no available server path  The  Ethernet switch in the 171 CBB 970 30 processor will support 14  simultaneous data paths and 2 program paths before this counter  increments  This error indicates a poor application architecture        26  27    Transmit Buffer  Errors    Increments when the 171 CBB 970 30 processor cannot transmit  an Ethernet response frame because all frame buffers are used   For example  if all of the processor   s 16 PING buffers contain  PING replies that are ready to be transmitted but the  transmission is delayed because of collisions and back off  any  newly received PING requests are discarded and the counter is  incremented  This error can occur for PING  ARP  and  connection attempts to a server path  Although this error is  theoretically possible  it is rare        28  29    Silo Underflow   TCP retries     This field counts processor TCP IP retries  All processor clients   and servers use the TCP IP protocol  which implements   sequence numbers and time outs  Whenever TCP IP data is   pushed from the processor  the processor must receive an   acknowledgment of the receipt of data within the time out period    If not  the processor issues a retry  Retries may result from any   o
64. ociated Ethernet port  100MB On The link speed on the associated Ethernet port is 100BASE T  Off If the LINK ACTIVE LED is off  there is no link on the associated  Ethernet port  If the LINK ACTIVE LED is on or blinking  the link speed on the  associated Ethernet port is 1OBASE T  Processor Two connectors are located on the bottom of the module  a Modbus serial port  Interfaces connector and a 24 VDC power supply connector        1 Modbus port  2 24 VDC power supply connector       12    31007547 1 2007       Processor Overview       The Modbus port is an RJ45 connector on the bottom right part of the module  It is  a general purpose asynchronous serial port with dedicated RS232 485 slave  functionality  The port can also have master functionality when you use an XXMIT  or XMIT programming function block     A Modbus host device connected to the port  such as an HMI or PLC programming  panel  can be used for     e programming the M1 processor   e transferring data between the host device and the M1 processor  e uploading and downloading   e other host operations    The choice between RS232 and RS485 can be made with PLC programming  software  see p  15   RS232 is the default protocol     Modbus communication capabilities are described in more detail later in this manual   see p  35         Note  The Modbus port connector and the Ethernet connectors at the top of the  module are female RJ45 connectors with a similar look  Do not attempt to make an  Ethernet connection through 
65. onnected to a master cable  or  if the master is at one end    of the cable run  a terminating resistor        Description    Part Number       Modbus RS485  RJ45 RJ45  Master Communication Cable    170 MCI 041 10       Modbus Plus or Modbus RS485 terminating RJ45 resistor plugs   pack of 2   Color code  blue          170 XTS 021 00          The slaves use a pin for pin cable  such as the Modbus Plus   Modbus RS485 short  interconnect cable or any Cat  5 4 twisted pair Ethernet cable AWG 24        Description    Part Number       Modbus Plus   Modbus RS485 short interconnect cable  Color code  black          170 MCI 020 10             104    31007547 1 2007             RS485 on the Modbus Port       Single Master  The following illustration shows components used in a four wire single master slave  Slave Option 1 cabling scheme  In this view  a master cable   3  is used on both sides of the  master  Each Momentum module must include a processor adapter or option    adapter with a Modbus RS485 port                                                                                                                          Slave Master Slave Slave    Slave          cable   s function     Note  Each cable has different colored boots  The color of the boots signifies the                                  Legend    Label Description Part Number   1 Terminating resistor plug 170 XTS 021 00  2 Modbus RS485 connector  T   DB9 base  170 XTS 040 00  3 Modbus RS485 master communication cable 1
66. operation  a message appears on the screen confirming completion              31007547 1 2007    69       Saving to Flash          70    31007547 1 2007       Configuring the Modbus Port                                        Parameters in Concept F     At a Glance   Overview This chapter describes how to access the Modbus Port Settings dialog box and  edit the default parameters for the delay  protocol  and address  The communication  parameters on the Modbus port are set at the factory    What s in this This chapter contains the following topics    Chapter  Topic Page  Accessing the Modbus Port Settings Dialog Box 72  Changing the Modbus Communication Protocol 73  Changing Mode and Data Bits on Modbus Port 74  Changing the Modbus Port   s Baud Rate 75  Stop Bit Should Not Be Changed 76  Changing Parity on the Modbus Port 77  Changing the Delay on the Modbus Port 78  Changing the Modbus Network Address of the Modbus Port 79                      31007547 1 2007 71    Configuring Modbus Port Parameters       Accessing the Modbus Port Settings Dialog Box       Introduction Modbus port parameters can be modified using the Modbus Port Settings dialog  box in Concept        Accessing the       Modbus Port    Setting Dialog Step Action       1 From the PLC Configuration menu  select Modbus Port Settings         ii  PLC Configuration       Summary      PLC Selection       PLC Memory Partition    D Specials  Config Extensions         Segment Scheduler      S  Modbus Port Settings    
67. ot have an LED to indicate the  battery   s health  we recommend that you reserve a Ox reference to monitor the  health of the battery           Note  For a full description of and instructions for using Concept  refer to the set of  manuals shipped with the software  Your version of Concept may vary from the  sample screens shown here              Reserving a The following procedure describes how to reserve and monitor a battery coil  using  Battery Coil the Specials    dialog box in Concept   Step Action       1          From the Configure menu  select Specials     The Specials dialog box  appears                 50    31007547 1 2007          Configuring with Concept          Step Action       2 Check the Battery Coil box at the top left of the dialog     Specials             3 Type a number in the range of available 0x references in the 0x box  In the  example below  the number 1536 is used              4 Click the OK button  The dialog box closes and the register you have specified  is displayed on the PLC Configuration screen                    31007547 1 2007 51    Configuring with Concept       Monitoring the    You can monitor the battery coil in ladder logic or tie it to a lamp or alarm that turns          Battery Coil on to indicate that the battery should be changed   The state of the battery coil is either O or 1  where   e 0 indicates that the battery is healthy  e 1 indicates that the battery should be changed  52    31007547 1 2007    Configuring with Concept 
68. our wire cabling schemes  104   pinouts  113   terminating devices  112   two wire cabling schemes  107  multi addressing   on the Ethernet switch  24    P    parity   Modbus port  36  physical components of the processor  10  PLC LAN Status indicator  14  PLC Run indicator  14  POWER OK indicator  14  power supply   external source  13   grounding  19   wiring  19  protective earth  19  ProWORX32  81    Q    queuing outputs data packets  by the Ethernet switch  24    R    RS232 protocol   Modbus port  73  RS485 communications   Modbus serial port  40  RS485 protocol   Modbus port  73       118    31007547 1 2007    Index       RTU mode  Modbus port  36    S    save to Flash  16  saving to Flash with ProWORX32  89  specifications  93  state RAM  16  statistics  Ethernet  32  stop bit  Modbus port  36  supervisory networks  design considerations  27    T    tagging data packets  by the Ethernet switch  24  time of day clock  reading in Concept  56  reading in ProWORX 32  87  set up in Concept  53  set up in ProWORX 32  87  TOD clock  53  56  87    U    user memory  16       31007547 1 2007    119    Index          120 31007547 1 2007    
69. plies to a Momentum 171 CBB 970 30 processor using the  Formula for 984LL exec   984LL Exec    scan time    0 25 ms Ethernet device   0 002 ms word    0 13 ms K of logic    0 40 ms       Note  Modbus messages add from 1 to 2 ms per scan  depending on the length of  the message                 31007547 1 2007 93    Specifications          Note  The formula above presumes that all MSTR blocks and all configured  connections are set to go as fast as possible  When these conditions are true  the  Momentum processor attempts to exchange data with each device once per scan              Note  If several devices are configured to communicate on a timed basis that is  substantially larger than the scan time calculated  then the communications to  those devices will be spread out over several scans           Example You have 3 drops of Ethernet I O modules connected to one 171 CBB 970 30  processor  The processor has a configured time of 50 ms each  and a total of 4k  user logic  The scan time for all modules configured as fast as possible is    75 ms   0 12 ms   0 52 ms   1 79 ms        Ethernet Ports       Communications ports    4 ports       10 100BASE T       Half full duplex  auto negotiated       RJ45 connectors       10 100BASE T ports    Shielded RJ45       Ethernet protocols supported    All applicable IEEE 802 3 standards       Auto crossover  auto MDI MDI X     Yes       Auto negotiating    10 100BASE T or 100BASE TX       Ethernet Port Status LEDs    100MB  LINK ACTIVE    
70. re can be used to provide the IP address  subnet mask  and default gateway  to the processor        Note  BOOTP Lite and the user document are available for download at  www telemecanique com                 Using the  Correct MAC       Address A CAUTION       UNINTENDED OPERATION    e Enter the parameters of the target controller  as described in the BOOTP Lite  user manual   Otherwise  the controller runs on its old  or existing  configuration    e Verify the MAC address of the target device before invoking the BOOTP Lite  Server Software     Failure to follow this instruction can result in injury or equipment damage              An incorrect MAC address may result in an unwanted change to another device or  cause unexpected results        Specifying A response from BOOTP Lite causes the processor to enter Stopped state on  Addresses  completion of power up  if the processor has been set to Specify IP Address mode  Stopping the in Concept  This is useful when inappropriate outbound network traffic might result  Processor if the processor immediately transitioned into Run mode after power up     Refer to the BOOTP Lite user documentation for instructions           31007547 1 2007 31    The Ethernet Switch       Reading Ethernet Network Statistics                                                                      Overview Ethernet network statistics are stored in the Momentum 171 CBB 970 30 processor   They can be viewed with the processor s on board Web server    Table of 
71. rocessor is powered up and  running is typically 5 years       A circuit monitors the voltage of the lithium battery  you can set a battery monitoring  coil in the configuration with Concept  see p  50  or ProOWORX 32  see p  87   When  the battery voltage gets weak  this battery low coil turns on   i e   its value is 1  When  the battery coil turns on  you have 30 days to replace the battery           31007547 1 2007    21    Processor Overview          22    31007547 1 2007       The 4 port 10 100BASE T                                     Ethernet Switch 2   At a Glance   Overview This chapter explains the capabilities of the 10 100BASE T Ethernet switch built into  the Momentum 171 CBB 970 30 processor    What s in this This chapter contains the following topics    2   Chapter  Topic Page  The Ethernet Switch 24  The Ethernet Port Connections 25  Network Design Considerations 26  Network Security Firewalls 28  Assigning Ethernet Address Parameters 29  Using BOOTP Lite to Assign Address Parameters 31  Reading Ethernet Network Statistics 32                      31007547 1 2007 23    The Ethernet Switch       The Ethernet Switch       Introduction The Ethernet switch built into the Momentum 171 CBB 970 30 processor allows you  to connect the processor to an Ethernet network  Ethernet connectivity gives you     high speed I O servicing   high speed data transfer   remote programming   worldwide connectivity via the Internet   interfaces with a wide array of Transparent Ready d
72. ry Coil 50  Configuring the Time of day Clock 53  Reading the Time of Day Clock 56                   31007547 1 2007    41          Configuring with Concept       Selecting the Momentum 171 CBB 970 30 Processor       Introduction The following procedure describes how to select a Momentum 171 CBB 970 30    processor in Concept when you are starting a new project        Selecting a    Processor       Step    Action       1    From the File menu  select New Project   A new project is opened and the file name  untitled  appears over the menu bar        Double click PLC Selection in the left pane  The PLC Configuration screen appears         li  PLC Configuration    B PLC Selection                      42    31007547 1 2007       Configuring with Concept          Step    Action             Double click the PLC Selection folder  The PLC Selection dialog box appears  The default PLC Family  selection in the dialog is QUANTUM     m     PLC Selection          140 CPU 113 02X  140 CPU 113 03 384 Orly E  140 CPU 113 03S    140 CPU 113 03X  140 CPU 213 04    as     8 K logic   32 K state     o is  Canes    __ He               31007547 1 2007    43       Configuring with Concept                                           Step Action  4 From the PLC Family drop down list  select MOMENTUM  The CPU Executive menu changes to display  the Momentum PLC choices  PLC Selection  TEES    171 CBB 970 30 984  FQ  171 CBB 970 30 IEC  171 CCC 760 10 984 984 Only __ij  171 CCC 760 10 IEC  171 CCC 780 10 
73. ser Guide 840 USE 503  ProWORX 32 Programming Software for PLCs User Guide 372 SPU 780  Ladder Logic Block Library User Guide 870 USE 101       Momentum 170ENT11001 170ENT 11002 Ethernet Communications   870 USE 114  Adapter User Guide       Advantys STB Ethernet Modbus TCP IP Network Interface 890 USE 177  Applications Guide                      31007547 1 2007    About the Book       Product Related  Warnings    User Comments    Schneider Electric assumes no responsibility for any errors that may appear in this  document  If you have any suggestions for improvements or amendments or have  found errors in this publication  please notify us  No part of this document may be  reproduced in any form or by means  electronic or mechanical  including  photocopying  without express written permission of Schneider Electric     All pertinent state  regional  and local safety regulations must be observed when  installing and using this product  For reasons of safety and to ensure compliance  with documented system data  only the manufacturer should perform repairs to  components     When controllers are used for applications with technical safety requirements   please follow the relevant instructions     Failure to use Schneider Electric software or approved software with our hardware  products may result in injury  harm  or improper operating results     Failure to observe this product related warning can result in injury or equipment  damage        We welcome your comments about this
74. shows components used in a multimaster slave network   Slave Cabling Each Momentum module must include a processor adapter or option adapter with a  Modbus RS485 port                                                                                                              3 7 3  2  5  Master Slave Master Slave Slave  Legend   Label Description Part Number       Terminating resistor plug  Color code  red    170 XTS 021 00       Modbus RS485 connector  T   DB9 base     170 XTS 040 00       Modbus Plus   Modbus RS485 Short Interconnect Cable  Color code  black    170 MCI 020 10       Modbus RS485 connector  T   RJ45 base     170 XTS 041 00             Terminating shunt plug  Color code  blue       170 XTS 042 00             108    31007547 1 2007       RS485 on the Modbus Port       Cable for Modbus RS485 Networks Connecting Momentum Components    Overview    Master  Communication  Cable    Interconnect  Cables       This section describes the cables which should be used in constructing an RS485  network for Momentum components        This cable is required for master slave communications in a four wire cabling  scheme  This cable is 10  long and has a blue boot        Description    Part Number    Illustration       Modbus RS485  RJ45 RJ45   master communication cable          170 MCI 041 10                Cable for connecting two Modbus RS485 devices  such as Momentum modules  is  available from Schneider Automation in four lengths  These cables have a black    boot        
75. single point connection between the PE and  VDC is recommended in a   24 VDC power wiring system                    20    31007547 1 2007    Processor Overview       Lithium Battery    Introduction    Battery  Characteristics    Battery low  Threshold Level       Due to the characteristics of the lithium battery  the operating life cannot be  accurately determined  Major factors reducing battery capacity are     storage temperature  operating temperature  time in storage   e battery use    If battery backup is required  Schneider Electric recommends configuring the  battery low coil in the PLC configuration  a setting that allows monitoring of the  battery capacity level  A battery low condition exists when the configured battery low  coil goes to 1     The Momentum 171 CBB 970 30 processor contains a factory installed lithium coin  cell battery  It is shipped with the real time clock disabled  and the SRAM is not  battery backed  When the processor is powered on for the first time  it runs on the  battery and the battery backed SRAM is enabled     You can set the time of day using either Concept  see p  53  or PrOWORX 32   see p  87   If you do not set the clock  it starts running with a factory set date of  1 June 2006 at first power up        e The back up life of the lithium battery when it is supporting the processor   s  memory while the processor is powered off is typically 3 years after the real time  clock is set   e The back up life of the lithium battery when the p
76. t Scheduler  Modbus Port Settings  ASCII                46 31007547 1 2007    Configuring with Concept       Changing the Size of the Full Logic Area       Introduction The number displayed in the Available Logic Area field in the PLC Configuration  screen indicates the amount of memory available for application logic  You cannot  directly enter this field to modify the value  You can  however  change the amount of  memory available by manipulating the sizes in other fields in the PLC Configuration  screen        Example 1 For example  if you reduce the expansion size of the I O map  the number in the  Available Logic Area field automatically increases  Say you are using a 12 2K  machine and you change the size of the I O map from 512 to 256  The Available  Logic Area automatically increases by 256 words from 1198 to 1454        Example 2 If you allocate some number of words to Peer Cop expansion  you reduce the  Available Logic Area by the number of words allocated for Peer Cop           31007547 1 2007 47    Configuring with Concept       Changing the Range of Discrete and Register References    Guidelines    Procedure       If you are changing the range of discrete and register references in Concept  here  are some key guidelines     e Adjust the range of discretes in increments of 16  Sixteen discretes consume one    word     e Adjust the range of registers in increments of 1  A register consumes one word    e The total number of register and discrete references cannot ex
77. that may be  generated between the Momentum 171 CBB 970 30 processor and I O devices may  bog down an MIS network  causing loss of productivity        A CAUTION  UNPREDICTABLE NETWORK BEHAVIOR    Use switches or separate networks to isolate the Momentum 171 CBB 970 30  processor and related devices from MIS data networks     Failure to follow this instruction can result in injury or equipment damage                    In a supervisory architecture  several intelligent processing devices share system  data  Many kinds of devices may be part of the network  Be aware of each device  requirement for access to the network and of the impact each device can have on  the timing of your network communications           31007547 1 2007    27    The Ethernet Switch       Network Security Firewalls    Overview    Network level  Firewalls    Application level       To restrict access to your Momentum 171 CBB 970 30 processor and to the I O  network  you may want to consider a firewall  A firewall is a gateway that controls  access to your network  There are two types of firewalls     e network level firewalls  e application level firewalls       Network level firewalls are frequently installed between the Internet and a single  point of entry to an internal  protected network        An application level firewall acts on behalf of an application  It intercepts all traffic          Firewalls destined for that application and decides whether to forward that traffic to the  application  Appli
78. to use with your PLC    3 In the Access Level field  select the Change to Configuration radio button and  click OK The Connect to PLC dialog box disappears and Concept connects to  your PLC    4 From the Online menu on the main menu bar  select Online Control Panel The       following screen appears        Online Control Panel  Controller Executive ID is 898  Version 0200     m Time of Day clock  clock not configured          Start controller                Clear controller        Constant sweep settings  register for target scan time        target scan time  ms     free running scan time  ms           Invoke constant sweep             Invoke single sweep                      Set clock    Single sweep settings                single sweep time base  ms  0  Invoke optimized solve sweep trigger count 1                   Elash program                                                       68    31007547 1 2007          Saving to Flash                                                                                              Step Action  5 Click the Flash program    button  The Save to Flash dialog box appears   Save To Flash     Flash Type              Controller State Save To Flash    Intemal OStart After Power Up      PCMCIA  top After Power Up Clear Flash  WZ  Save State Ram  Help  6 Select the appropriate parameters in the dialog box and click Save To Flash  A  confirmation screen appears   7 Click Yes to confirm the save to Flash operation  When Concept completes the       
79. tting the IP Address Parameters    Introduction       The following Ethernet IP address parameters can be set for your controller using  Concept     e Use Bootp Server  default   e Specify IP Address  e Disable Ethernet       A WARNING       UNINTENDED OPERATION   DUPLICATE IP ADDRESS    Having two or more devices with the same IP address can cause unpredictable  operation of your network    e Obtain a valid IP address from your system administrator to avoid duplication   e Ensure that this device will receive a unique IP address     Failure to follow this instruction can result in death  serious injury  or  equipment damage                 Note  The IP address parameters need to be set in the Ethernet I O Scanner  screen before you can continue on to set I O scanner parameters              Make the IP address parameter selection by pushing one of the three radio buttons  in the top left corner of the Ethernet I O Scanner screen     Ethernet Configuration   O Specify IP Address      Use Bootp Server   o Disable Ethernet    Ethernet   1 0 Scanner    TE 08 400050 Hold Las 400001 400040 10    is        E  E  E  tel  tel  tel  ic  ic          31007547 1 2007    59    Ethernet Parameters and I O Scanner       Getting an IP  Address from the  BOOTP Sever    The Specify IP    The default configuration setting is for the processor to get its IP address is from a  BOOTP server  The Use Bootp Server button should be auto selected  as shown  above  if it is not and you want to use the B
80. vq  Administrator  PROGRAM New970   lt Mi 970 30   MB 1  gt  Offline D  SoSoWORX 32 Projects New970 pwx  2   Select Transfer when the Transfer to Flash option appears     31007547 1 2007    Configuring with ProWORX 32          90    31007547 1 2007       Appendices          At a Glance    Purpose    What s in this  Appendix        These appendixes provides Momentum 171 CBB 970 30 processor specifications   LED flash patterns and error codes  and information about RS485 cabling  accessories        The appendix contains the following chapters                          Chapter Chapter Name Page  A Momentum 171 CBB 970 30 Processor Specifications 93  B LED Flash Patterns  Error Codes  and Diagnostic Messages 97  Cc RS485 Accessories for the Modbus Serial Port 103             31007547 1 2007    91       Appendices          92    31007547 1 2007       Momentum 171 CBB 970 30                                     Processor Specifications A  Specifications  General  Specifications Memory Internal Memory 544 Kbytes  User Memory 18 Kwords 984LL Exec  200 kwords IEC Exec  Flash RAM 1 Mbyte  Clock Speed 50 MHz  984LL Input and Output References   Registers 26048  Discretes 8192 Ox references  8192 1x references  IEC Input and Output References   Registers 11200  Discretes 4096 Ox references       4096 1x references       I O Servicing Watchdog Timeout   335 ms       Logic Solve Time   See the scan time formula below  for the 984LL Exec                      Scan Time The following formula ap
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
USER MANUAL - BCH Electric Limited  Samsung MagicInfo VideoWall Author    Samsung GT-E2222 User Manual  Cobra Electronics ESD-9570 Radar Detector User Manual    2x Dual Link DVI Extender  USER MANUAL  Sencor SHB 4356 blender  フォルダ 管理表    Copyright © All rights reserved. 
   Failed to retrieve file