Home
        APLISENS
         Contents
1.             diaphragm seal       Fig 7a  CM30x2 type connector Fig 7b  Socket for Fig 7c  Socket for  with flush diaphragm CM30x2 type CM30x2 type connector  with M30x2 thread  connector     Sealing  teflon  Order code Socket CM30x2    The ring in Fig  7c have to be welded in place with the word TOP upwards    Fig  5  M type connector with M20x1 5 thread  Fig  6  P type connector with M20x1 5 thread  Fig  7  CM30x2 type connector with flush diaphragm with M30x2 thread    DTR APC APR ALW 02 ENG                                                                                                                       34  24 5  1  Y  N    5 Q  A  Fig 8b  Socket for G1 2 type connector   Fig 8a  G1 2  type connector  with G1 2  thread   Sealing  teflon  pie x 24 4x 1 7  AN  mm  Q  Fig 8c  CG1 2  type connector Fig 8d  Socket for  with flush diaphragm CG1 2   type connector  with G1 2  thread  Order code Socket CG1 2  21 5  Sealing  teflon  33 2 x 36 4 x 1 8  N   SI  Oj y   g  Q  o  OJ  Fig 8e  CG1 type connector Fig 8f  Socket for  with flush diaphragm CG1   type connector  Order code Socket CG1    with G1  thread     Fig  8  Process connections G1 2    and G1        B 35 DTR APC APR ALW 02 ENG           18 132 18 133                                                   91 5             FIELD TERMINALS                                   The electrical  terminals side    The electronic  circuits  and display side       packing gland  Cable 5   10                      Lock preventing    rota
2.     10mbar  ikPa    251    250bar for version compliant   10   10kPa    4mbar _ _ 0 4kPa _   50 1 with the PED pressure    0 5   7kPa    4mbar__ 0 4kPa ___ ____ 18 1   directive     50   50kPa    0 1bar__ 10kPa ___ ___  A A oktda ttt cette   8    25   25mbar   2 5   2 5kPa    2 5mbar  0 25kPa  20 1 20 bar       5 3 2  APR 2200ALW  Measurement ranges                               Nominal range   Minimum set Vertical spacing   Maximum configurable range dependent Static   FSO  range of diaphragm on the actual vertical spacing of pressure  seals  diaphragm seals   m  limit   160   160 mbar 0 1 mH20  lt 1 7m  1 6   vertical spacing of sealsx94  mH20 40bar   0 5   0 5 bar 0 5 mH20  lt 6m  5  vertical spacing of sealsx1 04  mH20 40bar   1 6   2 bar 1 5 mH20  lt  15m  20  vertical spacing of sealsx1 04  mH20 40bar   1 6   16 bar 1bar  lt  15m 16bar 40bar             B 12 DTR APC APR ALW 02 ENG     The maximum vertical diaphragm seal spacing shown in the table applies to level measurement   ensuring that it is possible to set the zero point of the transmitter when the tank is empty    For measurements of density or phase boundaries  in the sugar and chemical industries and in   refineries  the vertical spacing of the diaphragm seals can be larger     5 3 3  APR 2000ALW  APR 2200ALW Metrological parameters    Accuracy   0 075   FSO  for the APR 2000ALW nominal range  Long term stability  lt  accuracy   3 years   Error due to supply voltage changes   0 002  FSO  1V   Thermal error   0 
3.    Ro gt  2500       a Ex power supply  see p 5                    Aplisens KAP 03Ex Communicator       To measure the current in the transmitter without  disconnecting the signalling circuit  connect  a milliammeter to control sockets TEST   TEST           In hazardous areas  connections  J to the control terminals must be  made using only instruments which    are permitted to be used in such areas       The transmitter is equipped in additional communication resistor RD   2400   During normal operation terminals  lt Signal     gt  and  lt Test     gt  are shorted   RD resistor is used when you wish to communicate with the transmitter locally  from its terminals   and Ro  lt  250Q  Terminals  lt Signal   gt  and  lt Test     gt  must be opened     Transmitter electrical installation should be realised with engineering standard requirements     way  Damage and possible repair may be assessed only by the manufacturer or another    It is not allowed to repair or otherwise interfere with the transmitter   s electrical circuits in any  authorized party     B 8 DTR APC APR ALW 02 ENG     1  INTRODUCTION    1 1  This Manual is intended for users of APC 2000ALW smart pressure transmitters  APR 2000ALW  APR   2200ALW  APR 2200GALW smart differential pressure transmitters  and APR 2000YALW smart level probe  and their intrinsic safety versions  containing the data and guidelines necessary to understand the functioning of  the transmitters and how to operate them  lt includes essential
4.    The supply of power from a source with a    rectangular    characteristic means that the voltage of the Ex power  supply remains constant until current limitation activates   The protection level of power supplies with a    rectangular    characteristic is normally    ib      The transmitter powered from such a supply is also a Ex device with protection level    ib      Example of practical provision of power supply       use a stabilized power supply with Uo 24V with protection level  ib    and current limited to lo 25mA     5 4  Input inductance and capacity Ci   20nF  Li 1 1mH       for Uo  lt  1 2Uq    B 7 DTR APC APR ALW 02 ENG   Appendix Exi  5 5  Supply voltage min  13 5VDC     5 6  Load resistance   from 28V linear supply    28V     13 5V        3000    0 02A    Ro max  Q    0 0225A for transmitter without display back lighting  from a source with    trapezial    or    rectangular    characteristic supply   Usup      13 5V  Ro max  O           0 0225A       barrier resistance      16 5V for transmitter with display back lighting    6  How to connect Ex transmitters APC     APR    2    The transmitter and other devices in the measuring loop should be connected in accordance  with the intrinsic safety and explosion safety regulations and the conditions for use in  dangerous areas    Failure to observe the intrinsic safety regulations can cause explosion and the resulting hazard  to people     Hazardous area   Safe area    Ex Milliammeter                          gt  
5.  7mbar _    25   25mbar     100   100mbar_   Accuracy  lt    0 075    lt  0 16   lt  0 1   lt  0 1   lt  0 075    Set Tange  ns na mA Cee 0    25mbar weet  2 5   2 5mbar ales  7    mbar  a   25   25mbar   E i 00  wl 0Ombar    Accuracy  lt  0 4    lt  1   lt  16   lt  04   lt  0 4    Thermal error   0 1    FSO   10  C  max   0 4   aa for the whole thermal compensation  Thermal compensation range  10     70  C  5 4 3  APR 2000GALW  Construction materials  M20x1 5  6x1 adapter brass  Valve manifold ss316L  Valve manifold adapter ss316L  Ya NPT connector brass  ss316L or galvanized St3S carbon steel     Other materials as given in 5 1 3 for APR         5 4 4  APR 2000GALW  Pressure Connectors      The terminals fit adapted to    6x1 plastic tubes     Valve manifold adapter or 1   4 NPT connector   see p  8 3  and fig 17      B 13 DTR APC APR ALW 02 ENG     5 5  APR 2000YALW  Measurement ranges and metrological parameters   5 5 1  APR 2000YALW  Measurement ranges                                               N   1 2  Nominal range 0        6000 mmH20 0        1600 mmH20  Minimum set range 600 mmH20 160 mmH20  Static pressure limit 40 bar   5 5 2  APR 2000YALW  Metrological parameters   Nominal range N   1 2  Accuracy for basic range  0 16   0 2   Accuracy for minimum range  0 5    0 6    temperature error 0 4   for temperatures  25    80     Zero shift error from static pressure   0 08     10bar 0 1    10bar                     zeroing in static pressure conditions with zero diffe
6.  Ex power supply  see p 5                              Communicator       Fuse  In   0 05A  Un   250V  according to EN 60127    In case of transmitter calibration outside danger zone is possible communicator connecting to   lt SIGNAL  gt  and  lt TEST  gt  terminals  Transmitter is furnished in communication resistor  Rp   2400    closed with jumper at  lt SIGNAL  gt  and  lt TEST  gt  terminals installed by manufacturer  Rp resistor can be  use then  when it is necessary to communicate with transmitter from its terminals and the load resistance   Ro  in current loop is lover then 2500  Than  lt SIGNAL  gt  and  lt TEST  gt  terminals have to be open     Table 1  permitted packing glands                                                                                              Type Producer Screw Feature   Other marking No of certificate   501 423 HAWKE M20x1 5  Exd IIC  dimension OS  O  A   Baseefa 06 ATEX 0056X  501 421 HAWKE M20x1 5  Exd IIC  dimension OS  O  A   Baseefa 06 ATEX 0056X  ICG 623 HAWKE M20x1 5  Exd IIC  dimension OS  O  A   Baseefa 06 ATEX 0058X  501 453 HAWKE M20x1 5  Exd IIC  dimension OS  O  A   Baseefa 06 ATEX 0056X  501 453 RAC HAWKE M20x1 5  Exd IIC  dimension OS  O  A   Baseefa 06 ATEX 0056X  501 453 Universal HAWKE M20x1 5   Exd IIC dimension OS  O  A   Baseefa 06 ATEX 0057X  ICG 653 HAWKE M20x1 5   Exd IIC dimension OS  O  A   Baseefa 06 ATEX 0058X  8163 2 A2F STAHL M20x1 5   EXd IIC SIRAO6ATEX1188X  A2F  A2FRC  SS2K CMPS M20x1 5   Exd IIC SIRAO6AT
7.  Transmitters can be use in ambient temperatures  Ta  between  408     lt Ta  lt  458    for T6 class or  between  40     lt  Ta  lt  758 forT5 class     5 4  Transmitter sensor diaphragm not should be subject on damage during installation and exploitation   The diaphragm is made from 316ss or Hastelloy thin foil and cannot be subject on medium which can  entail its damage    5 5  With regard on kind of casing material   light alloy with large aluminium content   the user is obliged to  assure  that possibility of hitting casing does not step out in place of transmitter installation    5 6  In transmitter casing are two holes to assembly of packing glands from thread M20x1 5 or 1 2 NPT    5 7  Normally transmitters are delivered without installed glands but with blank plugs  corks  in the second     hole  They are at table 1 and table 2 at list of packing glands and plugs agreeable with production      documentation and accepted by certificate station  Customer should install packing glands according to   tables 1 and plugs according to tables 2  if plugs aren t installed  or other accordance with flame proof  standards    5 8  Itis necessary apply a shield cable or without shield cable with round cross section in protection from    gt   elastomer  not moisture absorbing  for example  YKSLY 2   1  YnTKSYekw 1   2  1  LIYCY 2  Incase     of need of use cable about different building customer should co ordinate this with transmitters  manufacturer to choose intakes with cable d
8.  be in danger from sedimentation    crystallization or erosion  inspections should be carried out as required    Where it is found that the signal in the transmission line is absent or its value is incorrect  a check should  be made on the line and its terminal connections    Check whether the values of the supply voltage and load resistance are correct    If a communicator is connected to the power supply line of the transmitter  a fault in the line may be   indicated by the message    No response    or    Check connection       If the line is in order  check the operation of the transmitter     B 28 DTR APC APR ALW 02 ENG   11 3  Cleaning the Diaphragm Seal  Overloading Damage  11 3 1  Sediment and dirt which have formed on the diaphragm in the course of operation must not be removed    by mechanical means  as this may damage both the diaphragm and the transmitter itself   The only permitted method is the dissolving of sediment     11 3 2  Sometimes transmitters malfunction due to damage caused by overloading  e g  in case of          application of excessive pressure     freezing or solidification of the medium     action of a hard object  such as a screwdriver  on the diaphragm     Usually in such cases the symptoms are such that the output current falls below 4mA or rises above 20mA  and  the transmitter fails to respond to input pressure     11 4  Spare parts   Parts of the transmitter which may be subject to wear or damage and require replacement  cover gasket       Ot
9.  density of liquid and phase    boundary    DTR APC APR ALW 02 ENG     To simplify the mathematical operations we introduce the density coefficient of the medium Xp     Xp     Pmecium  9 cm    Puaterat aro  g cm      Since the density of water at 4  C is 1 g em   the density coefficient Xp is numerically equal to the density of the me   dium expressed in g cm     To determine the hydrostatic pressure of a column of liquid in mm H20  it is sufficient to multiply  the height of the column h  mm  by the density coefficient of the liquid Xp  Since it is easy to determine the hydrostatic  pressure in mm H20 and the transmitter can be configured in those units  in the descriptions of measurement methods  given below we will make use of pressures expressed in mm H20 and the density coefficient Xp     Configuration of the APR 2200ALW transmitters to measure the level of liquid in a tank     The measurement task    To convert a variation in the level of a liquid with density  p   0 87 g cm  between O and hmax to a variation in the  output signal from 4 to 20 mA        H     vertical  spacing of  diaphragm  seals   0 lt h  lt  Amax   p   0 87 g cm            4 i A    1  Install the transmitter in its working position on an  empty tank    2  Make the electrical connections of the transmitter   providing for the ability to use HART communication    3  Connect the KAP 01 communicator  identify the  transmitter and select the    configuration    function     4  On the configuration menu se
10.  in 10 2 4  are used    The transmitter s output is fitted with a radio noise filter and other elements protecting against ESD     6 2  Construction     The basic units of transmitter are  measuring sensor  in which pressure signal is converted into electric signal   and electronic units  transforming signal from measuring sensor into unified output signal    APC     APR    transmitters are equipped in LCD display with LED back lighting  enabling reading two the  process variables simultaneously as well as the unit process variable reading  The electronic board is closed in  poly carbonate casing  The casing construction enables turning of display by  180 with 90  pitch    On the electronic casing the set of buttons is placed  used to local adjustment    The transmitters construction enables connecting of the separately compensated measuring sensor to  separately compensated electronic board enables fast servicing at the plant    The electronic circuit of sensor has a galvanic separation from measuring line  Thanks of that construction the  measurement susceptibility at interferences is reduced as well as the enlarged safety of work in the Ex and  flameproof applications    The sensor memory contains 8 pressure shapes data bank which can  depending on factory settings  contain  parameters describing behavior the same sensor in different pressures and or temperatures ranges     In dependence from needs we can choose a needed bank of coefficients memory for transmitter work  AP
11.  of installation    The device should be configured appropriately for the purpose for which it is to be used   Incorrect configuration may cause erroneous functioning  leading to damage to the device or  an accident    In systems with pressure transmitters there exists  in case of leakage  a danger to staff on  the side where the medium is under pressure  All safety and protection requirements must be  observed during installation  operation and inspections    If a device is not functioning correctly  disconnect it and send it for repair to the manufacturer   or to a firm authorized by the manufacturer     In order to minimize the risk of malfunction and associated risks to staff  the device is not to be  installed or used in particularly unfavourable conditions  where the following dangers occur       possibility of mechanical impacts  excessive shocks and vibration     excessive temperature fluctuation  exposure to direct sunlight     condensation of water vapour  dust  icing        Installation of intrinsic safety versions should be performed with particular care  in accordance     with the regulations and standards applicable to that type of installation        The manufacturer reserves the right to make changes  not having a negative impact on the  operational and metrological parameters of the products  without updating the contents of the  technical manual     B 1 DTR APC APR ALW 02 ENG     CONTENTS  APPENDIX E e ds  APPENDIX Exi       7  INTRODUCTION     USER MATERIAL
12.  payoed uaym 00                                                                            Stanless steel or aluminium tube  80x2       up to 6m long  by order           ea ey ee                     i       SUO SUdUIP que  jo aBue  uopesuadwog    0S       Fig  18  APR 2000YALW smart level probe for pressure tanks                                41       DTR APC APR ALW 02 ENG     L6 for M20x1 5  A L7 for 1 2NPT                                           L2                                           MINIMUM WIDTH OF JOINT AND MAXIMUM GAP FOR GROUP IIC ENCLOSURES     Ne eae sacs quantity eae H  E D za  ps etj  int PN EN 60079 1 2004 U   y  L2 12 55  3 0570  23 005 0 1 5 1 ea A  L4 13 3   15   7  215200   0 097 2  wiath of joint min 12 5 B B  L5   12 M72x1 5   M72x1 5 2 eae  L6 9 M20x1 5   M20x1 5 2 arg  in 6 thread   L7   127      1 2NPT   1 2NPT 2 mine ieee  ited joint   aoa ly 1   wiam ot joint min 10          Fig  19  The explosion   proof joints of APC    APR    transmitters     Lock the cover tight by unbolting the screw        gt  lay   Y WAANING   ZT OPEN WHEN    ACUIT IS ALIVE       Fig  20  How to lead the casing of APC    APR    transmitters    B 42    M20x1 5  or G1 2   socket    360       l  l  l  l  l        1 4 Siphon tube  T Pmaks  10 MPa      Temp maks  300     i Marerials      R 35          1 Order code   Siphon tube M20x1 5 or G1 2        DTR APC APR ALW 02 ENG     M20x1 5  or G1 2   socket    Weldable pipe stube  Pmaks  10 MPa  Marerials    ST8S galvanized  Orde
13.  range  40      85     for PED version in accordance with p  5 2 3      A Operating temperature range for intrinsic safe versions in accordance with Appendix Exi  Es Operating temperature range for flame proof versions in accordance with Appendix Exd    Medium temperature range  40      1206     for direct measurement   for PED version in accordance with p  5 2 3   over 120    measurement with a transmission  tube or diaphragm seal using    Thermal compensation range  25     80  C     40     80  C for special version APC      Relative humidity 0    98   Vibration during operation max 4g  Exposure to direct sunlight not recommended causing strong transmitter warming  5 1 3  APC     APR    Construction materials  Diaphragm seal for APC    Stainless steel 316L  00H17N14M2  PED version  or Hastelloy C276  Diaphragm seal for APR    Stainless steel 316L  00H17N14M2  PED version  or Hastelloy C276  Sensing module Stainless steel 316L  00H17N14M2     Liquid filling the interior the sensing module Silicone oil  chemically inactive liquid for measurement of  oxygen uses    Connectors for APC    Stainless steel 316L  00H17N14M2  or  Hastelloy C276 only for P  GP  CM30x2    C type vented covers and connectors for APR   Stainless steel 316L  00H17N14M2   Electronics casing High pressure cast of aluminium alloy  lacquered with  chemical resistant oxide enamel  colour yellow  RAL 1003      5 1 4  APC     APR    Rating of Case Protection IP66 according to PN EN 60529 2003     5 2  APC     Me
14.  recommendations concerning installation and  use  as well as emergency procedures  The parameters and information specified for transmitters identified  herein with the sign APC     APR    also apply to transmitters  APC 2000ALW  APR 2000ALW  APR 2200ALW   APR 2200GALW  APR 2000YALW and their explosion proof versions  as well as all the variations differing by  the type of the process terminals  Information on the transmitter sizes and the method of installation apply to  both  all versions of transmitters   1 2  Technical data for the diaphragm seals and for the APC    and APR    transmitters are contained in the  catalogue cards    DIAPHRAGM SEALS      1 3  The transmitters comply with the requirements of EU directives as shown on the plate and with the relevant  Declaration of Conformity   1 4  Additional data on APC 2000ALW  APR 2000ALW  APR 2200ALW  APR 2000GALW and   APR 2000YALW transmitters in Ex versions is contained in the appendix designed to   Ex  DTR APC APR ALW 02 ENG   Appendix Exi and in Exd versions in the appendix designed to   DTR APC APR ALW 02 ENG   Appendix Exd    During installation and use of the transmitters in Ex or Exd version  reference should be made to  DTR APC APR ALW 02 ENG  in conjunction with Appendix Exi or Exd   1 5  The pressure transmitters  APC 2000ALW  APR 2000ALW in realization for sea uses are complied with  Det Norske Veritas  DNV  Rules for Classification of Ships  High Speed 8 Light Craft and Det Norske Veritas   Offshore Standard
15.  without  disconnecting the measuring loop  connect  a milliammeter to control terminals  lt Test   gt   and  lt Test   gt      09009  9999    Oooo  000p    Communicator    Fig 2b  The link of transmitter and communicator or modem to  lt SIGNAL  gt   lt SIGNAL  gt  transmitter terminals in  case of the resistance in current loop is higher than 2500     oa                 ORR  ee tt       0008  06805    Communicator    Fig 2c  The link of transmitter and communicator or modem to  lt SIGNAL  gt   lt TEST  gt  transmitter terminals in  case of the resistance in current loop is smaller than 2500     B 31 DTR APC APR ALW 02 ENG                 A          pa   AA                            n  SIGNAL 22 E    Communicator    Fig 2d  The link of transmitter and communicator or modem to  lt SIGNAL  gt   lt SIGNAL  gt  transmitter terminals in  case of the resistance in current loop is smaller than 2500     remove jumper from  lt SIGNAL  gt  and  lt TEST  gt  terminals     f If Ro in current loop is lower than 250Q is necessary to connect 2400 resistor to current loop by  After communication jumper should cam back at its place                                                                                    18 132 18 r 133 z  j i T  ERs OVE gQ  p COVER  gt     ee E    2    amp  Ss   zZ H    LO        th     EPLISENS  a  gt    HE  E   Op    ES  E ST inos    Sa   JAQA     KS oO  E r Q   o  The electrical The electronic   9   A Qala    A fa od 1 2010  terminals side circuits  and display 
16. 08  FSO  10  C   Thermal error for the whole thermal   compensation range   0 3  FSO    Zero shift error for static pressure    0 08    FSO  10bar      0 01    FSO  10bar  for range n 4     0 03    FSO  10bar  for range nS  6   Cut off on radical characteristic curve up to10  of flow       zeroing in static pressure conditions with zero differential pressure eliminate this error   5 3 4  APR 2000ALW  Pressure Connectors    APR 2000 ALW  C type connector to mount together with a valve manifold see fig 9  available for PED version  APR 2000 ALW with single direct diaphragm seal     as in the example  fig 10  or with other diaphragm seals in  accordance with    DIAPHRAGM SEALS    catalogue cards     5 3 5  APR 2200ALW  Pressure Connectors   diaphragm seals     see    DIAPHRAGM  SEALS  catalogue cards     5 4  APR 2000GALW  Measurement ranges and metrological parameters   5 4 1 APR 2000GALW  Measurement ranges                                                                                  5 Nominal range ia Overpressure   imi  N  FSO  Minimum set range limit Static pressure limit  1   0   25mbar  0   2500Pa  1mbar  100Pa  350mbar 1bar  2    2 5   2 5mbar    250   250Pa  0 2mbar  20Pa  350mbar 1bar  3   7   7mbar   700   700Pa    imbar _  100Pa  350mbar 1bar  4   25  25mbar   2500   2500Pa    5mbar  500Pa  1bar 1bar  5   100   100mbar _   10   10Pa  20mbar   2kPa  1bar 1bar  5 4 2  APR 2000GALW  Metrological parameters   Nominal range _____    0   25mbar ___  2 5   2 5mbar    7  
17. 3  Example  how to install the APR 2000ALW transmitter with a valve manifold to a 2    pipe     B 38 DTR APC APR ALW 02 ENG     S TK type tube flanged  remote diaphragm seal    S PK type flush flanged  remote diaphragm seal S CompK P type or  S CompK GP type or  S CompK  51 type  remote diaphragm seal    gt   VA                                   S DINK type  remote diaphragm seal  50  G65  D80                 Fig  14  APR 2200ALW differential pressure  transmitter with two remote diaphragm seals   examples   Fig  15  APR 2200ALW differential pressure  transmitter with direct and remote  diaphragm seal  examples     39       Fastening  to a wall                   Fastening  on a pipe                         Fig  16  Example  how to install the APC     APR    transmitter    DTR APC APR ALW 02 ENG                                                                                                                                       18 132 18   H  RY    i      T  an  E No  IN     m  i E i L  Q  p   IB      3 The electrical oO The electronic  terminals side   I circuits  and display side        Adapter for  valve manifold or  steel impulse lines                                Weidable impulse  line connector         Valve manifold    Fig  17  APR 2000GALW smart differential pressure transmitter for low ranges     DTR APC APR ALW 02 ENG     40                                                                       gt                                asn ul uaym 0009 0  dn  Bulodsue j 10  
18. C      APR   transmitters monitor work of their equipment as well as the calculation correctness and in case of rises  of incorrigibility inform about mistakes displaying the announcement on LCD screen as well as putting out the  alarm current in current loop     B 14 DTR APC APR ALW 02 ENG     6 2 1  The pressure connectors may be fitted to the APC    sensing module as in figures 5a  6a  7a  8 and other   The APR    transmitters have the sensing modules with two P type connectors  or C type connecting covers for  installation on a valve manifold  figure 9   The sensing modules  for both types  are equipped with a diaphragm  separating the internal part of the head from the measuring medium   6 2 2  For measuring the pressure of dense  chemically reactive or hot media  the transmitter may be  additionally fitted with various types of diaphragm seal depending on the type of medium and the  conditions in which measurement is carried out  see catalogue cards    Diaphragm Seals    The diaphragm seal transmits the pressure obtained from the medium  The pressure is transmitted via a  manometric fluid which fills the space between the diaphragm of the seal and the diaphragm of the  1 sensing module  In the case of remote diaphragm seals  pressure is transmitted via a capillary linking  the transmitters sensing module to the diaphragm seal  The seals construction depends on the  medium properties and operating conditions for which they are intended   Technical data relating to the di
19. CIPLISEN 5         DTR APC APR ALW 02 ENG     APLISENS    MANUFACTURE OF PRESSURE TRANSMITTERS  AND CONTROL INSTRUMENTS    USER   S MANUAL    SMART PRESSURE TRANSMITTER  type  APC 2000ALW    SMART DIFFERENTIAL PRESSURE TRANSMITTER  type  APR 2000ALW  APR 2200ALW  APR 200GALW    SMART LEVEL PROBE  type  APR 2000YALW    Edition B    WARSAW JUNE 2010    APLISENS JSC 03 192 Warszawa  ul  Morelowa 7  tel   48 22 8140777  fax  48 22 814 07 78  www aplisens pl  e mail  aplisens aplisens pl    Symbols used    Symbol  A Warning to proceed strictly in accordance with the information contained in the  documentation in order to ensure the safety and full functionality of the device     Information particularly useful during installation and operation of the device     Information particularly useful during installation and operation of a type Ex device   Information on disposal of used equipment       BASIC REQUIREMENTS AND SAFE USE    The manufacturer will not be liable for damage resulting from incorrect installation   failure to maintain the device in a suitable technical condition  or use of the device  other than for its intended purpose     Installation should be carried out by qualified staff having the required authorizations to install  electrical and pressure measuring devices  The installer is responsible for performing the  installation in accordance with these instructions and with the electromagnetic compatibility  and safety regulations and standards applicable to the type
20. DONE   announcement or the proper number of error will notify    The parameter will be written down in units  UNIT       The setting of the end of the set URV range       change of span       lt BACK  Return to Local Menu  If you will confirm this option     you will come back to main tree of Local Menu      BY PRESsure  Setting URV across setting pressure  If you will confirm this    option  transmitter will confirm the party of command by the     DONE  announcement or the proper number of error will notify     BY VALUe  Setting the URV across inscribing of value        After confirmation will display current URV value before the passage  in mode of edition    l   l         Choose and confirm sign introduced parameter     y   00000  Introduce in sequence  digit after digit  5 digital number with point  or without point  After confirmation the last 5 digit of the parameter  transmitter will confirm the party of command by the  DONE   announcement or the proper number of error will notify   The parameter will be written down in units  UNIT      c U     DAMPING    TRANSFEr    NIT         lt BACK  l    IN_H20  IN_HG  FT_H20  MM_H20  MM_HG  PSI   BAR  MBAR  G SQCM  KG SQCM  PA   KPA  TORR  ATM  M_H20  MPA  INH20 4  MMH20 4     lt BACK    o  S   2  S   5  S   10  S   30  S   60  S         lt BACK    l   l   l   l   l   l  LINEAR  SQRT    SPECIAL  SQUARE    20 DTR APC APR ALW 02 ENG      Return to Local Menu  If you will confirm this option   you will come back to main tree of Loca
21. EX1097X   Products   E1FW  E1FX Z  CMP    E2FW  E2FX Z Products M20x1 5   Exd IIC SIRAO6ATEX1097X  T3CDS  T3CDSPB Sis M20x1 5   Exd IIC SIRAO6ATEX1283X   Products   PX2K  PXSS2K  CMP    PX2KX  PXB2KX Products M20x1 5   Exd IIC SIRAO6ATEX1097X  Table 2  permitted plugs   Type Producer   Screw Feature   Other marking No certificate   AGRO AG  M20x1 5   Exd IIC  475 HAWKE M20x1 5   Exd IIC  477 HAWKE M20x1 5   Exd IIC                for special cable only           B 5 DTR APC APR ALW 02 ENG     Appendix Exi  ll  APPENDIX Exi  APC 2000ALW PRESSURE TRANSMITTER          APR 2000ALW  APR 2200ALW  APR 2000G ALW  DIFFERENTIAL PRESSURE TRANSMITTERS   APR 2000Y ALW LEVEL PROBE     Ex VERSION  1  Introduction  1 1  This    Appendix Exi    applies to transmitters of types APC 2000ALW  APR 2000ALW     APR 2200ALW  APR 2000GALW and APR 2000YALW in Ex versions only  marked on the rating plate as  shown in 2 2 and denoted Ex in the Product Certificate     1 2  The appendix contains supplementary information relating to the Ex versions of these transmitters     During installation and use of Ex transmitters  reference should be made to DTR APC APR ALW 02 ENG  in  conjunction with    Appendix Exi        2  Use of APC    APR    transmitters in danger zones   2 1  The transmitters are produced in accordance with the requirements of the following standards  EN 60079 0 2006  EN 60079 11 2007  EN 60079 26 2004    2 2  The transmitters may operate in areas where there is a risk of explosion  in acco
22. IPE    37   IG  13  EXAMPLE  HOW TO INSTALL THE APR 2000ALW TRANSMITTER WITH A VALVE MANIFOLD TO A 2    PIPE      437  14  APR 2200ALW DIFFERENTIAL PRESSURE TRANSMITTER WITH TWO REMOTE DIAPHRAGM SEALS  EXAMPLES            38    15  APR 2200ALW DIFFERENTIAL PRESSURE TRANSMITTER WITH DIRECT AND REMOTE DIAPHRAGM SEAL  EXAMPLES  38  16  EXAMPLE  HOW TO INSTALL THE APC     APR    TRANSMITTER      ccsscssesessesseesessecsecsecsecsecssenecusescsecsecseesecseeneeneanees 39  17  APR 2000GALW SMART DIFFERENTIAL PRESSURE TRANSMITTER FOR LOW RANGES     18  APR 2000YALW SMART LEVEL PROBE FOR PRESSURE TANKS            19  THE EXPLOSION   PROOF JOINTS OF APC    APR    TRANSMITTERS   20  HOW TO LEAD THE CASING OF APC    APR    TRANSMITTERS    21  ADDITIONAL EQUIPMENT FOR FITTING OF PRESSURE TRANSMITTERS        csscssessessessessecsesseesessessesscssesecsecsecseeseeneaneess 42             jean ga a Jia Dey a s Gaa a Gaa e ma Be n abaa s Da a Da a Da a Dia a Daea a pe e a Gaa s Da a Ba s Ga          B 2 DTR APC APR ALW 02 ENG     Appendix Exd0 2  I  APPENDIX Exd    C E      APC 2000ALW XX PRESSURE TRANSMITTER   APR 2000ALW XX  APR 2200ALW XX   DIFFERENTIAL PRESSURE TRANSMITTERS   APR 2000 Y ALW XX LEVEL PROBE     Exd VERSION   1  Introduction  1 1  This    Appendix Exd 02    applies to transmitters of types APC 2000ALW XX  APR 2000ALW XX   APR 2200ALW XXand APR 2000Y ALW XX in Exd versions only  marked on the rating plate as shown in  p 3 and denoted Exd in the Product Certificate   1 2  The a
23. S             cccssssseeeeeeees  APPLICATIONS AND MAIN FEATURES                   IDENTIFYING MARKS  ORDERING PROCEDURE   TECHNICAL DATA  conooccccccconnononccnnnancannncnnnenanananens  5 1  APC     APR     COMMON PARAMETERS          c cecceseseeeseseeeeseeeeeees  5 2  APC     MEASUREMENT RANGES AND METROLOGICAL PARAMETERS         5 3  APR 2000ALW  APR 2200ALW MEASUREMENT RANGES AND METROLOGICAL PARAMETERS  5 4  APR 2000GALW  MEASUREMENT RANGES AND METROLOGICAL PARAMETERS   0oococcocccccnnons  5 5  APR 2000YALW  MEASUREMENT RANGES AND METROLOGICAL PARAMETERS     x    Me A AA A ar e A raa aa rka aana aana aE anaha iaiT  6 1  MEASUREMENT PRINCIPLES  ELECTRONIC SYSTEM     6 2  CONSTRUCTION  siai  7  PLACE OF INSTALLATION  7 1  GENERAL RECOMMENDATIONS     7 2  LOW AMBIENT TEMPERATURE   7 3  HIGH MEDIUM TEMPERATURE           7 4  MECHANICAL VIBRATION  CORROSIVE MEDIA               8  INSTALLATION AND MECHANICAL CONNECTIONS    8 1  APC    INSTALLATION AND CONNECTIONS                       8 2  APR    INSTALLATION AND CONNECTIONS                  8 3  APR 2000GALW  INSTALLATION AND CONNECTIONS  8 4  APR 2000YALW  INSTALLATION AND CONNECTIONS  9  ELECTRICAL CONNECTION              ssseeeeee  9 1  GENERAL RECOMMENDATIONS          9 2  ELECTRICAL CONNECTIONS FOR APC     APR  9 3  PROTECTION FROM EXCESS VOLTAGE     9 4  EARTHING         cccccesesesseseseeseseeeeeeees  10  SETTING AND REGULATION se  10 1  TRANSMITTER RANGE BASIC RANGE  DEFINITIONS           ccceccsceseseseeceseecesescese
24. aphragm seals    dimensions and operating conditions can be found in catalogue  cards    DIAPHRAGM SEALS      6 2 3  The APR    transmitters may be fitted with an single direct diaphragm seal  mounted on the         pressure  input of the sensing module  while the           input is a    NPT F connector  fig  10    The APR 2200ALW transmitter is fitted with two diaphragm seals and can be produced in two versions     with one direct diaphragm seal and one remote diaphragm seal  fig  15      with two remote diaphragm seals  fig 14    6 2 4  In the case of the APR 2000GALW transmitters  the sensing module is located inside the transmitter  casing  It is designed for the measurement of low pressures of non aggressive gases  with a permitted  overpressure of 1bar  or 350mbar   The basic  economy  version of this transmitter has   6x1 elastic tubes  terminals fitting  while the industrial version has adapters as shown in fig  17     6 2 5  APR 2000YALW smart level probe is equipped in diaphragm seal and flange to fixing on tank     7  PLACE OF INSTALLATION    7 1  General recommendations   7 1 1  The smart pressure transmitter and differential pressure transmitter can be installed both indoors and  outdoors  It is recommended that transmitters intended for outdoor use be placed in a box or under cover    7 1 2  The place of installation should be chosen in such a way as to allow access to the device and to protect it  from mechanical damage  In planning the installation of the tran
25. ariation in liquid density from Pmin   0 6  g cm  tO Pmax   1 2 g cm  to a variation in the output signal  from 4 to 20 mA  with the vertical spacing of the diaphragm  seals equal to H   3000 mm  The sealing system is filled  with DC 550 oil with density Poi   1 068 g cm        1  Calculate the value of the start of the range as follows   Himm    XPmin     XPoii       3000 x  0 6     1 068     1404  mm H20   2  Calculate the value of the end of the range as follows   Himmi    XPmax     XPoit       3000 x  1 2     1 068    396  mm H20   3  Set the zero point of the transmitter with the diaphragm  seals positioned at the same level     Install the transmitter in its working position     Make the electrical connections to the transmitter  pro   viding for the possibility of using HART communication     as    6  Connect the KAP  communicator  identify the  transmitter and select the    configuration    function    7  On the configuration menu select    Reranging    proce   dure    8  On the    Reranging    menu   a  change the measurement units to mm H20 at 4  C   b  enter the calculated values for the start   1404  and   end  396  of the range     When the transmitter has been configured in this way it is  ready to be used to carry out the given measurement  task     Note  If it is possible to fill the space between the seals  with a liquid whose density corresponds to the start of the  measurement range  the start of the range of the trans   mitter can be set using regulated pr
26. asurement ranges and metrological parameters   5 2 1  APC     Measurement ranges                Ne Nominal ES eee Minimum set range Rangeability Raton wees   1  _ 0   1000bar __ 0   100MPa ____  l0bar___    MPa  ad 100 1  1200bar__ 120MPa  _    Ao E A LS sean E E RT  S00KF een ESE 100 les 450bar___ 45MPa  _    3   J O16 0bar  0  16MPa  cl o O e  A EA 100 i 450bar___ 45MPa  _    4__ 9   70bar ____ 0   MPa  sd O 7bar __ _    0kPa ____        100 A  140bar___ 14MPa  _   5 _ 9  25bar ____ 0  25MPa    0 25bar   _ 25kPa  to  DOO TS Seain SObar____ 5MPa  __    6 _ 9  7bar_____ 0  0 MPaj   ds eee Ce  aaa sa 1001 eee 14bar____ 1 4MPa _     ZJ  1  6bar___   100   600kPa    300mbar _ S0kPa  te A E 14bar____ 1 4MPa _    BBs br hobar 100  TSOKP A  J  120mbar 12kPa  alle POET orrei 4bar _____ 400kPa     9  _ 0  2bar______ 0  200kPa _ J  100mbar   ONE CA E SOF A 4bar _____ 400kPa      10  0   1bar_____ 0  100kPa _____ SOmbar ___ 5kPa  o    20 1 gasi 2bar _____ 200kPa _   11     0 5   0 5bar   50   50kPa  50mbar  5kPa  20 1 2bar  200kPa     12    0   0 25bar___  0   25kPa    25mbar ___ 2 5kPa  ti  WOT eas ahi tbar _____ 100kPa _      192 J 100   100mbar   10   10kPa _ J  zombar  lt   kPa  o NETA dedos thar_____ 100kPa  _   14     15   70mbar    15   7kPa  5mbar  0 5kPa  17 1 0 5bar  50kPa    15    0   1 1bar abs  0   110kPa abs    50mbar abs  5kPa abs  22 1 2bar  200kPa              18    0   70bar abs  0   7MPa abs  0 7bar abs  70kPa abs  100 1 140bar   14MPa       only for transmitters wit
27. d  the    basic range     for specifications of basic ranges see section 5 2 1  5 3 1  5 3 2  5 4 1  5 5 1     The width of the basic range is the difference between the upper and lower limits of the basic range    The internal characteristic conversion curve for the basic range is coded in the transmitters memory    This is the reference curve used when making any adjustments which affect the transmitter s output signal     10 1 2  When the transmitter is in use the term    set range    is used  The set range is the range whose lower  end point corresponds to an output current of 4mA and whose upper end point corresponds to a current of  20mA  or 20mA and 4mA respectively when the conversion curve is inverted     The set range may cover the whole of the basic range or only a part of it    The width of the set range is the difference between its upper and lower end points    The transmitter may be set to any range within the basic range of pressure values  subject to the restrictions set  out in the table in section 5 2 1  5 3 1  5 3 2  5 4 1  and 5 5 1        B 18 DTR APC APR ALW 02 ENG     10 2  Configuration and Calibration    10 2 1  The transmitter has features which enable metrological and identification parameters to be set and  altered  The configurable metrological parameters affecting the transmitters output current include the  following    a  unit in which the measured pressure is expressed on the display   b  upper end point of the set range   c  lower end point 
28. d switched off  ERR_L09  applied_process_too_high   Error will ensue out when given parameter  pressure     exceed admissible value  Zeroing or the range setting verifying is necessary     ERR_L10  applied_process_too_low   Error will ensue out when given parameter  pressure   will too low  Zeroing or the range setting verifying is necessary     ERR_L14  span_too_small   Error will ensue out when in result of setting range executing change  the width of the range will be smaller than admissible     ERR_L16  acces_ restricted   Error will ensue out when the service of Local Menu is switched off   and the user tries to call out the Menu Local service  You should switch on the service of  Local Menu with the KAP 03 communicator     RAPORT    program  or software using  library EDDL   Warning   ERR_L16 announcement can be displayed as well by zeroing attempt of the  absolute transmitter      WNG_L14  WARNING1  new Lower Range Value Pushed    Error will ensue out when the end of  range set   the URV  change will cause the change of the range set beginning  LRV      10 2 6  Remote configuration  Remote configuration is possible with KAP XX communicator or PC software  Measuring circuit should be in  accordance with the fig  2     10 2 7  LCD display configuration    The LCD display configuration can do in dependence from needs  Changes of the display options in local  MENU are possible using buttons or remote way using communicator  or the PC software  If itis necessary the  displa
29. d to obtain IP66 protection  It is useful to form the segment of the signal wire leading  to the packing gland into a protective loop to prevent condensation from running down in the  direction of the gland     B 17 DTR APC APR ALW 02 ENG     9 2  Electrical connections for APC     APR       The APC     APR    transmitters are to be connected as shown in fig  2a     2d    In APC     APR    transmitters  a 2400 resistor is permanently fitted in series in the transmitter   s current  circuit and blocked up with jumper between  lt SIGNAL     gt  and  lt TEST     gt  as shown in fig 2a and 2b   When the resistance in the current loop is lower than 2400 it is necessary to jumper disassemble to  Hart communication        9 3  Protection from excess voltage    9 3 1  The transmitters may be in danger from excess voltage caused by connection faults or atmospheric  electrical discharge    Protection from excess voltage between the wires of the transmission line is provided by TVS diodes installed in  all types of transmitter  see the table  column 2      9 3 2  In order to protect against excess voltage between the transmission line and the casing or earth  not  prevented by the diodes connected between the transmission wires   additional protection is provided in the  form of plasma surge arresters  see the table  column 3     Also external protective devices may be used  e g  the UZ 2 Aplisens system  or others  When the transmission  ines are long  it is advantageous to use one pro
30. ect the transmitter basic versions  with two M20 x 1 5 connectors  P type connector   can use  for  example  straight connecting elements with C type nuts  If elastic impulse lines are used  the transmitter should  be additionally fastened to a pipe  panel or supporting construction     B 16 DTR APC APR ALW 02 ENG     8 2 2  The APR 2000ALW and APR 2200ALW can be installed using the  25 Fastener  fig 11  on a 925 pipe  or on a flat surface using an angle bracket     8 2 3  The APR 2000ALW with connecting cover  C type connector   fig 9  are designed for installation on  3 valve or 5 valve manifolds to a 2    pipe or to a flat surface using    C 2    holder  fig 12    fig 13      8 3  APR 2000GAL W  Installation and connections    8 3 1  The    economy    version of the APR 2000G transmitter can be mounted on a wall  panel or other stable  construction  using a clamp with  9 holes  Fig 17   The transmitter is fitted with connectors which fit to a 6x1  elastic impulse tube  When the measuring impulse is transmitted via a metal terminal with M20 x 1 5 connector   an adapter is used between the M20 x 1 5 thread and the  6x1 terminal     Transmitters should be installed in a vertical position  The way of impulse line leading should enable the  vapour flowing towards the pipeline  Where there is a significant difference between the height at which the  transmitter is mounted and the height of the impulse source  particularly if the measurement range is small  the  reading may fluct
31. ed on the corresponding counter flanges on the  facility   It is recommended that the user matches the screw joints material to the pressure  temperature  flange  material and seal to ensure tightness of the flange joint in the expected operating conditions    Screws complying with ISO 261 are to be used for flanges used in the APC     APR    transmitters   Additional data concerning the diaphragm seals are specified in the    DIAPHRAGM SEALS    catalogue cards     9  ELECTRICAL CONNECTION    9 1  General recommendations    9 1 1  It is recommended that twisted pair cabling be used for the signal lines  If the transmitter and signal line  are subject to a large amount of electromagnetic interference  then shield pair cable should be used  The signal  wires should not run alongside network power supply cables or near to large electrically powered devices    The devices used together with the transmitters should be resistant to electromagnetic interference from the  transmission line in accordance with compatibility requirements  It is also beneficial to use anti interference  filters on the primary side of the transformers  the power supplies used for the transmitters and apparatus used  in conjunction with them     9 1 2  Wet or rising damp inside transmitter can cause its damage   When the isolation of the wires in the packing gland is ineffective  for example  when single    wires are used  the opening of the gland should be carefully sealed with an elastic sealing  compoun
32. er s Manual numbered  DTR APC APR ALW 02 ENG  with Appendix Exi   User can find them at www aplisens pl    5  Permitted input parameters  based on data from the FTZU 08 ATEX 0020  certificate  and certification documentation      The transmitters should be powered via the associated power feeding and measurement devices  As provided with the relevant intrinsic safe certificates  The parameters of their outputs to the danger zone  should not exceed the limit power supply parameters for the below specified transmitters   5 1   for power supply with a    linear    characteristic  Ui  28V li 0 1A Pi 0 7W for Tas 70TiT5  Power supply with a    linear    characteristic may be e g  a typical barrier with parameters  Uo   28V lo 0 093A Rw   3000   li Rw ID                                  transmitter  pazi       Lo a  y   Fig 1  Power supply from a source with    linear    characteristic    5 2    for power supply with a    trapezial    characteristic  Ui  24V li 0 05A Pi 0 6W  forTa lt 80    and T5    Example of power supply from a source with    trapezial    characteristic  see Fig  2            Ii lo Rw ID  rao ao  l      r a     ot   S   JU Uo Ug     or     o     5 1  L  o o    Fig  2  Power supply from a source with    trapezial    characteristic    If Uo lt     a then parameters Uq  lo  Po are interrelated as follows     Uo Uq     Uo   Ug      ro   Rw   sag A Po    Rw  5 3    for power supply with    rectangular    characteristic  Ui 24V li 0 025A Pi 0 60W for Tas 808    and T5
33. essure     Measurement of phase boundary    The height of the phase boundary of liquids of different  densities is determined by measuring the average density  of the medium between the seals     Example    Calculate the measurement range start and end points  for an APR 2200 transmitter configured to measure  phase boundary height in the range 0 1000 mm between  liquids of density p4  0 7 g cm  and p2 1 0 g cm   where the vertical spacing of the seals H   1600 mm   The sealing system uses DC 550 oil with a density of  1 068 g cm        H   1600 mm  0  lt  h  lt  1000 mm  p1   0 7 g cm   p2   1 0 g cm   Poi   1 068 g cm                   4   20 mA A    To determine the start of the measurement range  calcu   late the pressure difference at the transmitter when the  tank is filled with the lighter liquid only    1600  mm  x  0 7     1 068     588 8  mm H20     To determine the end point of the range  add the increase  in pressure resulting from the appearance of a 1 metre  column of the heavier liquid    588 8  mm H20     1 0     0 7  x 1000  mm       288 8  mm H20     DTR APC APR ALW 02 ENG     Additional remarks    The settings of the transmitter can be adjusted with refer   ence to laboratory results from density measurements  carried out on samples of the liquid being measured  This  is most often necessary when the measurement takes  place in a pipeline segment where the flow velocity of the  measured liquid reaches several m s     Increasing the vertical spacing of the d
34. for the Ex or Exd version        7 4  Mechanical Vibration  Corrosive Media     7 4 1  Transmitters should correctly work with vibrations with amplitudes to 1 6 mm and accelerations to 4g   If strong vibrations are carried via the pressure line and disturb of measuring  use should be made of elastic  pulse lines or transmitters with a remote diaphragm seal      7 4 2  Transmitters should not be installed in places where the diaphragm  made of 316L steel  00H17N14M2   would be subject to corrosion by the medium being measured  If possible  transmitters   AN with diaphragms made of Hastelloy C276 should be used  or other means of protection applied  e g  in  the form of a separating liquid  or transmitters with diaphragm seals adapted for measuring aggressive  mediums according to    DIAPHRAGM SEALS    catalogue cards should be used      8  INSTALLATION AND MECHANICAL CONNECTIONS    The APC     APR    transmitters can operate in any position   When installed on an object with a high temperature medium  it is advantageous to mount the transmitter  in a horizontal position or downwards  in such a way that the transmitter is kept away from the rising hot       y   air   For the small measurement ranges  the reading can be affected by the transmitter position  and by the  impulse lines configuration  or the way in which they are filled with liquid  This error can be corrected  using the zero setting function     8 1  APC    Installation and connections    8 1 1  The APC    transmit
35. her listed parts  due to the specific features and requirements of explosion protected devices   may be replaced only by the manufacturer or by a firm authorized by the manufacturer     12  PACKING  STORAGE AND TRANSPORT     The transmitters should be packed singly or in sets  in such a way as to protect them from damage during  transportation    The transmitters should be stored in multiple packs under cover  in a place free of vapours and reactive  substances  with an air temperature between  58 and  40     and relative humidity of not more than 85    Transmitters with uncovered diaphragm or seal connectors  stored without packaging  should have covers to  prevent damage to the diaphragm    During transportation  the transmitters should be packed and secured so as to prevent them from shifting    Any means of transport may be used  provided direct atmospheric effects are eliminated     13  GUARANTEE    The manufacturer guarantees the proper operation of the transmitters for a period of 24 months from the date of  purchase and servicing provided under the guarantee and following the guarantee period  In the case of special  versions  the guarantee period shall be agreed by the manufacturer and the user  but shall not be less than 12  months     14  ADDITIONAL INFORMATION    The manufacturer reserves the right to make constructional and technological changes which do not lower the  quality of the transmitters     15  RELATED DOCUMENTS          KAP    Communicator User s Manua
36. hout diaphragm seal                       B    11    5 2 2  APC     Metrological parameters    Accuracy  Long term stability    Error due to supply voltage changes    Thermal error    Thermal error for the whole thermal    compensation range    5 2 3  APC     APR    Metrological Parameters according to PED version     DTR APC APR ALW 02 ENG     max   0 075  for the basic range   lt  accuracy for 3 years  for the nominal measuring range   max   0 002  FSO  1V   max   0 08  FSO  10  C    max   0 1  FSO 1    0  C for n13  14 ranges     max   0 25  FSO    max   0 4  FSO 10  C for n13  14 ranges     APC    transmitters  in the PED Pressure Directive versions  are produced with a measurement range in the  interval from    100 kPa to 40MPa gage  or from O to 40MPa absolute  with the overpressure up to 44 MPa   Temperature limit  40   100  C   40   150  C with S Mazut connector    APR    transmitters  in the PED Pressure Directive versions  are produced with a measurement range in the  interval from    100 kPa to 2 5MPa gage  with the static pressure 25MPa and the overpressure up to 27 5 MPa     Temperature limit  2    5   100  C     APC    pressure transmitters with the S Mazut seal pressure connection  assembled with the PED version can  be produced within the range   100 kPa to 10 MPa gage  or within the O   10 MPa absolute  and the  overpressure up to 11 MPa  Other parameters are as given in Tables 1  except that the ambient temperature error  is 0 7 kPa 10  C  The value of the p
37. iameter    5 9  The general principles of connecting and the exploitation of transmitter in Exd realization should be  compatible with principles and relating standards for Exd casing devices how in p 2 1  in this including  also   EN600079 14  EN60079 17    5 10  During service must be made a check of the tight fastening of covers and the packing glands and the  fastening of the cable in the glands  The casing and supply line must be inspected for mechanical       damage  and the transmitter rating plate for legibility  Periodic checks should also be made of the  diaphragm  which should not carry signs of damage  During maintenance it is recommended that the  threads of the covers be lubricated with non acid vaseline        Blocking cover method before unscrewing and plumbing possibility is shoved at fig 20     Because of the transmitter damage possibility  the ambient temperature should not be allowed  to become higher than 80  C  even when there is no explosion risk     It is not permitted to repair or otherwise interfere with the transmitter   s electrical circuits in any  way  Damage estimation and repair possibility may be assessed by the manufacturer or another  authorized party only     In danger zone don   t unscrew transmitter covers and don   t change the display position or its  back lighting     B 4 DTR APC APR ALW 02 ENG     Appendix Exd0 2    6  How to connect Exd transmitters APC     APR       Hazardous area      Safe area                     Ro gt  250Q      
38. iaphragm seals  widens the range and often improves measurement accu   racy     In planning the spacing of the diaphragm seals  ensure  that the pressure difference at the transmitter lies within  the basic range     The maximum vertical spacing of the diaphragm seals   H  depends on the transmitter s basic range and the  boundary values for the density of the measured liquid     Prin  Pmax      If Pmin  lt  Poi     Pmax  the seal spacing H should satisfy the  following conditions     lower boundary of range  mm H O     H  mm   lt   XP min     XP oi  H  mm   lt  upper boundary of range  mm H O   XP max 7 X Poi  Example     Determine the maximum vertical spacing of the seals for  the APR 2200    10   10 kPa transmitter when measuring  the density of liquid between 0 6 and 1 2 g cm     The  sealing system uses AK 20 silicone oil with a density of  0 945 g cm       The lower boundary of the range of the transmitter is     10 kPa    1020 mm H20     1020   Hmmz  1020  0 6  0 945   0 345    H  mm   lt  2957       H  mm   lt     The upper boundary of the range of the transmitter is   10 kPa   1020 mm H20    H  mm   lt  O   gt  H mm  lt  Jeet 020  1 2  0 945 0 255    H  mm   lt  4000    In the example  both conditions are satisfied when the  spacing of the seals is not more than 2957 mm     B 27 DTR APC APR ALW 02 ENG     10 2 9  Configuration of the APR 2200YALW smart level probes    4   20 mA Principles of operation    Measurementis carried out using an APR 2000 differential pressu
39. ignations  of certificates number     CE PED  H1D APL003 04 POL rev A for APC    transmitters  CE PED H1D APL 002 05 POL rev B for APR    transmitters     5  TECHNICAL DATA     5 1  APC     APR     Common parameters  5 1 1  APC     APR    Electrical parameters    Power supply 12    55V DC A  Power supply for intrinsic safe versions in accordance with Appendix Exi   E        Output signal 4 20mA  Communication realised via a 4 20mA signal using KAP 03 communicator  or RS Hart modem and PC computer with    Raport    software  Resistance for communication 250 11000  min 2400    _ Usup V  12V   Load resistance RLmax Q    0 0225A    Usupiy Min    12   0 0225xR_  V      15V for transmitters with display backlight     Umin   f Ro  2 podswietleniem Umin   1 Ro  bez pod  wietlenia    Vmin M       o 250 500 750 1000 1250 1500 1750  Rola  Rola     250 500 750 1000 1250 1500 1750    Safe working area  grid  upper colour area     Output updating time 500ms   Additional electronic damping 0   30s   Voltage for insulation testing 500 VAC or 750 VDC  see p 9 3   Excess voltage protection see p 9 3     Response time on pressure stroke                          pressure    switch off  ta  10   250ms  ta te  20mA te  200ms  tr  ta  te  trmin    210ms  trmax   460ms  9 89mA APC   APR   transmitter  response time on pressure stroke tr  measuring cycle 0 5s   damping   0   4mA             B 10 DTR APC APR ALW 02 ENG     5 1 2  APC     APR    Permitted environmental conditions  Operating temperature
40. itter to use the units mm H O at 4  C    4  To determine the start of the measurement range  read off via the communicator the hydrostatic pressure produced by the  manometric fluid in the capillary  e g   4250 mm H 0       To determine the end point of the measurement range  add the value  4250 mm H O and the width of the measurement range   4250 mm H O   2784 mm H O    1466 mm H O    6  Using the communicator enter the calculated start   4250 mm H O  and end point   1466 mm H O  of the measurement range   and send asa blockto the transmitter  After receiving these parameters the transmitter will perform measurementsas required     11  INSPECTIONS AND SPARE PARTS   11 1  Periodic inspections    Periodic inspections should be made in accordance with the regulations to which the user is subject  During  inspection  the pressure connectors should be checked for loose connections and leaks  the electrical  connectors should be checked with regard to tightness and the state of the gaskets  packing glands  and the  diaphragm seals should be checked for tarnishing and corrosion    Check the characteristic conversion curve by following the procedures for    Calibration    and  where appropriate     a    B    d  Nie mo  na odnale       adnych hase   indeksu 11 2  Unscheduled inspections       Configuration        If the transmitters are installed in a location where they may be exposed to mechanical damage  excess   pressure  hydraulic impulses or excess voltage  or the diaphragm may
41. l    supplied with the Aplisens communicator     Hart RS232 01 Converter information sheet         Raport    software        INTERVAL LINEARIZATION     software     B 29 DTR APC APR ALW 02 ENG     16  FIGURES          Sensing  _  Input   Converter eS en  module circuit a c poo system    Load resistance  min 250 Q       Communicator    Fig  1  APC    APR    transmitters     block diagram     Communicator or modem electrical connections to transmitter measuring lines        For successful communication with transmitter the resistance in measuring loop  behind connected  device to communication  should be higher than 2500  If necessary install the additional resistor in the  line  The communicator or modem connecting ways to the measuring loop are presented at diagrams   During increasing of resistance in the measure loop at making the good transmission  is necessary to  make sure that the tension falls at sum resistances in the loop don t lower minimum tension at transmitter  terminals   see p 5 1 1     Fig 2  Electrical connections for APC    APR    transmitters    JUMPER               a a       fF  SNA   IR SO              0098    5    eea   s onoo   5 Jopo       0000   o Switch box    S  AAA J    Fig 2a  The link of transmitter and communicator or modem to current line by the switch box   in case of the  resistance in current loop is higher than 2500      B 30 DTR APC APR ALW 02 ENG        LL JUMPER  L                  SA A  SESESEJO        To measure the transmitter current
42. l Menu      Confirm one of the following characteristics across  longer press button    After parameter confirmation  transmitter will confirm the party of command by the  DONE       Setting of the solid temporary suppression of the process variable      Return to Local Menu  If you will confirm this option   you will come back to main tree of Local Menu      Confirm one of the following values time constant across  longer press button    After parameter confirmation  transmitter will confirm the party of command by the  DONE      Setting of the current output form     Return to Local Menu  If you will confirm this option   you will come back to main tree of Local Menu     Confirm one of the following characteristics across  longer press button    After parameter confirmation  transmitter will confirm the party of command by the  DONE      Linear   square root   user s    square          SQRT     LCD1 VARiable__        l  l  l  l  l  l  l  l  l  l  l  l  l    LCD2 VARiable        lt BACK    0 0    0 2    0 4    0 6    0 8    1 0          lt BACK    l  l  l  l  CURRENT  l    PERCENT        lt BACK    PRESSURE      USER           UNIT   l    l  NO UNIT    21 DTR APC APR ALW 02 ENG    square root characteristic cut of point setting      Return to Local Menu  If you will confirm this option   you will come back to main tree of Local Menu      Confirm one of the following percent value across    longer press button    After parameter confirmation  transmitter will confirm the part
43. lect the    Reranging    pro   cedure   5  On the    Reranging    menu    a  change the units of measurement to mm H20 at 4  C    b  enter the values for the start  Xp x hmin  mm   and  end  Xp x hmas  mm   of the measurement range   namely O and  0 87 hmax  mm   respectively    c  to compensate for the hydrostatic pressure of the  manometric fluid  the start of the measurement range  should be set using regulated pressure  when sub   ject to the action of only the manometric fluid  empty  tank  the transmitter will shift the start and end points  of the range  compensating for the value of that  pressure     When the transmitter has been configured in this way it is  ready to be used to carry out the given measurement task     If it is not possible to empty the tank to configure the  transmitter  the hydrostatic pressure of the manometric  fluid should be calculated by multiplying the vertical spac   ing of the diaphragm seals by the density coefficient of the  oil in the capillaries  This pressure should be taken into  account when entering the values for the start and end of  the range   Start  mm H20     H  mm  x XPoi  End  mm H20        Amax  mm    XPmeasured liquid     H  Mm  x XPor    Poi for DC 550 oil is equal to 1 068 g cm   Poi for AK 20 oil is equal to 0 945 g cm     Configuration of the APR 2200ALW transmitters to measure density of liquids     H   300 mm  0 6  lt  p  g cm    lt  1 2  Poi   1 068 g cm     4   20 mA A         The measurement task    To convert a v
44. of the set range   d  time constant   e  type of characteristic curve  linear or radical  Parameters of an informational nature which cannot be altered include the following    f  upper limit of the basic range   g  lower limit of the basic range   h  minimum range  10 2 2  Other identification parameters  not affecting the output signal  include  device address  device type  code  factory identification code  factory device code  number of preambles  3 20   UCS  TSD  program  version  electronics version  flags  serial number  label tag  description tag  date tag  message  record number   sensing module number   The process of setting the parameters listed in 10 2 1 and 10 2 2 is called    Configuration        10 2 3  It is possible to carry out a    pressure zeroing    procedure  for example to compensate for  measurement deviation caused by a change in position during the transmitter installation    The transmitter may also be calibrated  by taking readings with the input pressure controlled using a standard  device  This process and zero point adjustment are called    Calibration        10 2 4  Configuration and Calibration of the transmitter are carried out using an Aplisens KAP communicator   certain Hart communicators or a PC with Hart RS232 converter and Aplisens    Raport    software    Together with the    RAPORT    configuration software there is a    INTERVAL LINEARIZATION    software supplied  to enable the input of 21  point nonlinear functional characteristics 
45. ppendix contains supplementary information relating to the Exd  flame proof  versions of mentioned  transmitters   During installation and use of Exd transmitters  reference should be made to DTR APC APR ALW 02 ENG  in  conjunction with    Appendix Exd        2  Use of APC    APR    transmitters in dangers zones   2 1  The transmitters are produced in accordance with the requirements of the following standards   EN 60079 0 2006  EN 60079 1  2008  EN 60079 11 2007  EN 60079 26 2004 EN 61241 0 2006   EN 61241 1 2004  EN 61241 11 2006  2 2  The transmitters may operate in areas where there is a risk of explosion  in accordance with the rating of  the explosion protection design     Il 1 2G Ex ia d IIC T5 T6        Ex  II 1 2D Ex ia D20 tDA21 T85 T100    KDB 08 ATEX 224X  KDB 08ATEX 224X 1    marking T6 and T85 applies to range  40     lt Ta  45   marking T5 and T100 applies to range  40     lt Ta  lt  758  2 3  Transmitter category and hazard areas   The category 1 2G  contained within the rating  means that the transmitter may be installed within a type 1 or  2 hazard zone  The APC     APR    process connections may connect to a O zone type  see the diagram  below for an example      Zone 0 Zone 1 or 2 Safe area                                                          Pressure transmitter    or differential  pressure transmitter                Flame proof transmitters must have a rating plate containing the information specified in paragraph 4 of  DTR APC APR ALW 02 ENG  and al
46. r code     Pipe stube M20x1 5    or G1 2         M20x1 5  G1 2            Connector to weld  Marerials   15HM   galvanized  SO   316Lss  S   Order code    RedSpaw   S  or SO   M20x1 5 or G1 2     Fig  21  Additional equipment for fitting of pressure transmitters     43    DTR APC APR ALW 02 ENG     44    DTR APC APR ALW 02 ENG     
47. rdance with the rating of  the explosion protection design        Eo Il 1 2G Ex ia IIC T5 T6    FTZ   08 ATEX 0020    T5 T6 mark means that the temperature class is T5 or T6 depending on the working temperature of the  transmitter  i e  T6 for Ta  lt  408    or T5 for 400  lt  Ta  lt  65     and with power supply with rectangular  characteristics  T6 for Ta  lt  40     T5 for 408     lt Ta  lt 80       2 3  Transmitter category and hazard areas  The category 1 2G  contained within the rating  means that the transmitter may be installed within a type 1    or 2 hazard zone  The APC     APR    process connections may connect to a 0 zone type  see the diagram  below for an example      Zone 0 Zone 1 or 2 Safe area                                                                      Pressure transmitter  or differential  pressure transmitter                3  Identifying marks     Intrinsically safe transmitters must have a rating plate containing the information specified in paragraph 4 of  DTR APC APR ALW 02 ENG  and also at least the following         CE mark and number of notified unit    E  mark       designation of explosion protection design  certificate number      values of parameters such as  Ui  li  Pi  Ci  Li       year of manufacture    B 6 DTR APC APR ALW 02 ENG   Appendix Exi    4  User information   Together with the ordered transmitters  the user will receive       Product Certificate       Declaration of conformity       Copy of certificate     on request      Us
48. re  transmitter  enabling compensation for static pressure in the tank   The value processed is just the hydrostatic pressure of the medium  measured at the level of the diaphragm of the lower seal  This  AP   Hipi   H2p2 pressure is the sum of the hydrostatic pressures of the liquid and  vapour phases of the medium  In most practical measurement  situations the density of the vapour phase is negligibly small  and  therefore the measured hydrostatic pressure relates only to the  height of the liquid phase column and can be taken as representing  the level of the surface of the liquid phase  For media where the  density of the vapour phase is significant  e g  propane  the level  found by the method described can be treated as the theoretical level  vapour phase  density p2  of the liquid level obtained by adding the actual liquid phase to the  liquid phase  density p1  condensed vapour phase          4    M   Static P          Mechanical installation  On the flange of the tank  gt     Upper equalization hole    MAM  Static P   Hip1   H2p2    Lower  equalization hol    Diaphragm  Configuration example Seal unit    To converta rise in the level of liquid with densit   0 87 from 0 to 3200 mm to a current change fron   4to 20 mA    1  Install the transmitter in working position  place the seal at the appropriate height  tank empty     2  Calculate the width of the measurement range in mm H O  4  C   3200 mm x 0 87 g cm      2784 mm H O    3  Using the communicator  set the transm
49. rential pressure eliminate this error   Medium density range     up to 1 1 g cm3      standard version       over 1 1 g cm     special version by arrangement with APLISENS     6  CONSTRUCTION  6 1  Measurement Principles  Electronic System     APC    electronic pressure transmitters and APR    electronic differential pressure transmitters work by  converting changes in the resistance of a piezoresistance bridge  which are proportional to the measured  pressure  into a standard current signal  The active sensing element is a silicon diaphragm with piezoresistors   separated from the medium by a sealing diaphragm and manometric fluid  The electronic system digitally  processes the measurement signal and generates output signals  an analogue 4 20 mA signal with a digital  communication signal    A block diagram of the transmitter is presented in Figure 1  At the circuit input two analogue signals are provide   the measured pressure reflecting and the sensing module temperature  These signals are digitalized and  provide to a microprocessor input which controls the transmitter   s operation  Using input data during the  production process adjusts for thermal errors and carries out linearization  After digital processing  the signal is  converted into an analogue 4 20mA current signal again  with a superimposed digital communication signal   For communication with the transmitter via the signal line a special Aplisens KAP communicator  or a computer  meeting the requirements given
50. ressure measurement range and related overpressure are given on rating    plate and at Product    Certificate     5 2 3  APC     Pressure Connectors    M type connector with M20x1 5 thread     see figure 5a  available for PED version  P type connector with M20x1 5 thread     see figure 6a  available for PED version    CM30x2 type connector with flush diaphragm     see figure 7a     G1 2  type connector with G1 2    thread     see figure 8a  available for PED version  GP  type connector with G1 2    thread  available for PED version   CG1 type connector with G1    thread and flush diaphragm     see figure 8e  available for PED version  RM type connector with M20x1 5 thread and radiator  RP type connector with M20x1 5 thread and radiator  G1 4 type connector with G1 4 thread  available for PED version   1 2 NPT  type connector with 1 2 NPT tread  available for PED version   R1 2 type connector with R1 2 tread  available for PED version   CG1 2 type connector with G1 2 tread and flush diaphragm  available for PED version  other connection types by arrangement     5 3  APR 2000ALW  APR 2200ALW Measurement ranges and metrological    parameters     5 3 1  APR 2000ALW  Measurement ranges                               Ne Nominal TSO range Minimum set range   Rangeability pail ence SIAS pi sSurs   1_  0   16bar  0   1 6MPa    1 6bar __ 160kPa    10 1  0   250kPa    0 25bar_ 25kPa ____ ____ 101 250  320bar   0   100kPa  __  70mbar  7kPa    des  40bar for P type connector    0   25kPa  
51. s  Certificate No  A  11308 for application in following Location Classes  Temperature C   Humidity  B  Vibrations  B  EMC  B  Enclosure  C  The pressure transmitters  PCE 28  PCE 28P  PRE 28 in  realization for sea uses are complied with Det Norske Veritas  DNV  Rules for Classification of Ships  High  Speed  amp  Light Craft and Det Norske Veritas  Offshore Standards  Certificate No  A  11308 for application in  following Location Classes  Temperature C  Humidity  B  Vibrations  B  EMC  B  Enclosure  C   1 6  The APC     APR    transmitters are also made in a version which complies with the PED pressure  directive  meet the requirements for category IV  and then carry additional markings as in 4 3     2  USER MATERIALS    Transmitters are delivered in single and or multiple packs   Together with the transmitter are delivered    a  Product certificate  which is also as the warranty card   b  Declaration of conformity   on request   c  Copy of ATEX certificate     on request    d  User s Manual numbered  DTR APC APR ALW 02 ENG    Items b   c   d  are available at  www aplisens pl    3  APPLICATIONS AND MAIN FEATURES    3 1  The APC    smart pressure transmitters are designed to measure gauge pressure  vacuum pressure and  absolute pressure of gases  vapours and liquids  including corrosive substances     Differential pressure transmitters type APR    are used to measure liquid levels in closed tanks  with static  pressure up to 25MPa  or 32MPa for special versions and to meas
52. seseesesaceeseeaesecaesecaeseeacsecasseeasseseteeeeeateees  10 2  CONFIGURATION AND GALIBRATION o e e aea a a aa aa a a aAa Aa AAAA AAA AA aA AAAA SA AAA AAA AA SAAANA  11  INSPECTIONS AND SPARE PARTS    11 1  PERIODIC INSPECTIONS                  11 2  UNSCHEDULED INSPECTIONS  11 3  CLEANING THE DIAPHRAGM SEAL  DING DAI  11 4  SPARE PARTS  aia  12  PACKING  STORAGE AND TRANSPORT     13  GUARANTEE         0  cesses  14  ADDITIONAL INFORMATION  15  RELATED DOCUMENTS          16  FIGURES Ee ep aena Ansehn cers cessancscerssaveanesens  G  1  APC    APR    TRANSMITTERS     BLOCK DIAGRAM                  iG 2  ELECTRICAL CONNECTIONS FOR APC    APR    TRANSMITTERS   3  APC 2000ALW SMART PRESSURE TRANSMITTER  4  APC     APR     DISPLAY ROTATION POSSIBILITY  CONFIGURATION BUTTONS  5  M TYPE CONNECTOR WITH M20x1 5 THREAD     6  P TYPE CONNECTOR WITH M20X1 5 THREAD   7  8                                     ANN                                                                                             CM30x2 TYPE CONNECTOR WITH FLUSH DIAPHRAGM WITH M30x2 THREAD     PROCESS CONNECTIONS G1 2    AND G1     inici    9  APR 2000ALW DIFFERENTIAL PRESSURE TRANSMITTER WITH C TYPE VENTED COVERS     IG  10  APR 2000ALW DIFFERENTIAL PRESSURE TRANSMITTER WITH A SINGLE DIRECT DIAPHRAGM SEAL  EXAMPLE            11  EXAMPLE  HOW TO INSTALL THE APR 2200ALW TRANSMITTERS WITH REMOTE DIAPHRAGM                        36  12  EXAMPLE  HOW TO INSTALL THE APR 2000ALW TRANSMITTER ON A VERTICAL OR HORIZONTAL P
53. side a  ios  2x M6                   1       Lock preventing  rotation  of the casing    Earthing terminal       E    Fig  3  APC 2000ALW smart pressure transmitter    32 DTR APC APR ALW 02 ENG      180   with 90   pitch                                                                                                                                                                                                        unscrew the  display cover buttons  and casing     display screws       ay                            Al a AY Move the electronic unit from transmitter casing  take  T TH up the upper part of the casing with display from the  catch and revolve its to left or to right to the display  setting at needed position   Rotation possibility  180   with 90  pitch   Screw on the display unit screws and display cover                                                            p             Fig  4  APC     APR     display rotation possibility  configuration buttons     Jumper in radial position   as at photo     back lighting  off  jumper in circular  position    back lighting on        Fig  4a  Back lighting jumper view at transmitter electric board  unit display back side      B 33 DTR APC APR ALW 02 ENG           M20x1 5             Fig 5a  M type connector Fig 5b  Socket for M type connector  with M20x1 5 thread                M20x1 5  O25          diaphragm seal    Fig 6a  P type connector Fig 6b  Socket for P type connector    with M20x1 5 thread  H    TOP    35 1   1    
54. smitter and configuration of the impulse lines   attention should be paid to the following requirements     The impulse lines should be as short as possible  with a sufficiently large cross section  and free of  sharp benas  in order to prevent blockages    Where the medium is a gas  the transmitters should be installed above the measuring point  so that  condensation flows down towards the site of the pressure measurement  where the medium is a liquid  or where a protective liquid is used  the transmitters should be installed below the place where the  1 pressure measurement is taken    The impulse lines should be inclined at a gradient of at least 10cm m    The levels of filling liquid in the impulse lines should be equal or kept constant difference    The configuration of the impulse lines and the valve connection system should be chosen with regard  to the measurement conditions and to requirements such as the need to reset the transmitters in  position and the need for access to the impulse lines during water or gas removal and flushing     7 1 3  Where there is a risk of heavy objects hitting the instrument  resulting  in extreme cases  in   AN a part of the system with transmitters being torn off and medium leakage   appropriate means of  protection should be applied for safety reasons and to avoid the possibility of sparkling or other   more appropriate location should be selected for the transmitter     7 1 4  Attention should also be paid to possible installation fa
55. so at least the following       CE mark and number of notified unit    Ex  mark       designation of explosion protection design  certificate number     temperature use range     year of manufacture     In place of XX letters in product rating plate will be write a pressure connection type symbols     B 3 DTR APC APR ALW 02 ENG   Appendix Exd0 2    4  User information   Together with the ordered transmitters  the user will receive   a  Product Certificate   b  Declaration of conformity   c  Copy of certificate     on request  d  User s Manual numbered  DTR APC APR ALW 02 ENG  with Appendix Exd0 2     User can find them b   c   d  at www aplisens pl  5  Power supply and exploitation of transmitters     5 1 The transmitter connecting should be made after introduction with present instruction content       Electrically transmitter should be connected according to scheme at p 6 Appendix Exd  Transmitter  electrical installation should be realised with engineering standard requirements  Electrical connections  of transmitters in danger zone should be made by people who have indispensable knowledge and  experience in this branch     5 2  Transmitters should be supplied from DC electrical source with voltage max 45V from transformer   feeders or other devices which have at least a strengthened isolation among primary and secondary  windings in which don   t appear voltage higher than 250V  The duty of power supply installation with  above mentioned requirements rests on user    5 3 
56. tective device near the transmitter  or inside it   and another near  entry points to other devices used in conjunction with it     Internal protection of transmitters              1 2 3  Type of Protection between wires  TVS Protection between wires and earth and or casing      transmitter diodes      permitted voltage type of protection  permitted voltage       Plasma surge arresters   100V DC    APC     APR      68V DC  39V DC for Exi version   Not applicable to Ex version                     9 3 3  The voltage in the protective elements must not exceed the maximum permitted values given in columns  2 and 3 of the table     The insulation test voltages  500V AC or 750V DC  given in 5 1 1 refer to transmitters plasma surge  arresters   such protection is not used in Exi versions of transmitters     9 4  Earthing    The transmitters are fitted with internal and external earth terminals     10  SETTING AND REGULATION    APC     APR    transmitters are factory calibrated to the range stated in the order or to the basic range    After installation  the transmitter   s zero point may move and require adjustment    This applies particularly in cases where the measurement range is small  where the impulse lines are filled with  a separating liquid or where APC     APR    transmitters are used with remote diaphragm seals     10 1  Transmitter Range Basic Range  Definitions    10 1 1  The maximum range of pressure  or differential pressure  which the transmitter can measure is calle
57. ters can be mounted directly on the rigid impulse lines    For used connectors as in figures 5a  6a and 7a  it is recommended that connection sockets be used as shown  in figure 5b  6b  7b or 7c  It is recommended that sockets labeled    Socket CG1    and    Socket CG1 2    Fig  8 are  used for CG1 and CG1 2 connections  respectively    Besides  there are adapters for standard DIN50   DIN40  DIN25  Clamp2     Clamp1 5     Clamp1     type connections  provided for readouts carried out in aseptic conditions using transmitters with CM30x2 connection    There are gaskets provided for every transmitter with P  CM30x2  CG1  CG1 2 and GP type connections    The gasket material is selected based on the pressure value  temperature and the type of the medium    8 1 2  If the pressure is applied via a flexible plastic tube  the transmitter should be mounted on a support with  Red  6 M reduction    The types of the impulse tubes  Fig 21  are to be selected depending on the pressure measured value and the  medium temperature    8 1 3  Tighten the transmitter in the socket with a torque suitable for the type of the gasket used and the  pressure measured    8 1 4  The APC    transmitter can be installed using a universal    AL    holder allowing to mount the transmitter in   any position on the support or a horizontal or vertical pipe  35     65  Fig  16      8 2  APR    Installation and connections    8 2 1  The APR     transmitters can be mounted directly on rigid impulse lines    To conn
58. tion    of the casing    Earthing terminal                                                                                              S T type  tube flanged  diaphragm seal    1 4NPT   i  l      l  i  i      i  i    flush flanged  diaphragm seal    Fig  10  APR 2000ALW differential pressure transmitter with a single direct diaphragm seal  example      36 DTR APC APR ALW 02 ENG     18          STWNINYAL 073134                Assembly Kit   Mounting bracket 25  made by APLISENS  for fitting differential pressure transmitters  with P type connector on a  25 pipe see catalogue cards  Fitting accessories      Fig  11  Example  how to install the APR 2200ALW transmitters with remote diaphragm     37 DTR APC APR ALW 02 ENG          7 97 161 5                                                       Ris     vy SS  A E Ny  a 5 i     lt   XA B if     x  a  Q 4  we  y                                                                      Fastener C2 for fitting differential pressure  transmitters with C type connection  to a 2    pipe or to a wall                       Fastener C2 for fitting differential pressure  transmitters with a valve manifold   to a 2    pipe   see catalogue cards    Fitting accessories                                                                                        Ma LO   AAR Me  ai  ES    2  e 2  a  o a A  o A  SS A E  Y aN g                                                                                                  E 223             j 260       Fig  1
59. to the transmitter    A description of the functions of the KAP communicator is contained in the KAP Communicator Operating  Manual  and information on the Hart RS232 converter can be found on the Hart RS232 01 Converter  information sheet    10 2 5  Local configuration of transmitters   If the option of local configuration is active  operator can change transmitter set using buttons being below  display  The access to buttons will get after unscrewing the side cover  Then we can also change the display  position turning it with 90  angle position   see fig  4     If the option of local configuration is active  operator can change transmitter set using buttons being below  display  To enter at the local set change of the work mode  you should press one button and hold its about 4s   If using buttons can t change the transmitter configuration   the local transmitter configuration is switched of and  to its switching on is necessary to use the KAP 3 Calibrator    The buttons are signed with symbols  IN  WW  sl   After pressing by 4 seconds any of buttons there will appear on display    EXIT       If we will confirm this announcement across pressing and holding button      by 1 sec  we will go out from the  local change of the MENU set  If we will not confirm  we can move in MENU and change interesting us  parameters  The time of pressing  t    1   el  has to be longer than 1s    Pressing button  f  moves up in tree s structure MENU   Pressing button     moves down in tree s str
60. uate depending on the temperature difference between the impulse lines  This effect can be  reduced by ensuring that the impulse lines run side by side     8 3 2  The APR 2000GALW transmitter can also be fitted with an adapter  Fig 17  creating a C type connector   designed for installation on a 3 valve or 5 valve manifold  Aplisens can also supply ready transmitters mounted  on valves     8 4  APR 2000YALW  Installation and connections    The APRE 2000YALW level probes installed in places where liquid levels are measured in closed tanks  with  access to medium from top of tank as fig 15 and 10 2 6  Level probes should be installed in a vertical position     Pressure may be transmitted to the installed device only after checking that it has a measurement  range which properly corresponds to the value of the measured pressure  that gaskets have been  properly selected and fitted  and the connectors have been properly screwed tight    A Attempts to undo the screws or fixing connector pipes on a transmitter under pressure may  cause the medium to leak and create hazards for the personnel   When disassembling the transmitter  it is necessary to disconnect it from the process pressure or  bring the pressure to atmospheric level  and to take particular care and precautions in case of  media which are highly reactive  caustic  explosive or otherwise hazardous to personnel   If necessary  rinse out this part of the system     Transmitters with flange diaphragm seals are to be install
61. ucture MENU   Pressing    confirms choice and leads change        EXIT  First announcement which will see after inclusion of Menu Local      If you will confirm this option  you will go out from Local Menu     and you will come back to continue of measuring    PV ZERO           lt BACK  Return to Local Menu  If you will confirm this option        you will come back to main tree of Local Menu                  PV ZERO  Pressure zeroing  If you will confirm this option      transmitter will confirm the party of command     by the  DONE  announcement or the proper number of error will    notify          B    SET LRV    SET URV__       19 DTR APC APR ALW 02 ENG      The Setting of the range of the set LRV beginning    no change of span          lt BACK  Return to Local Menu  If you will confirm this option      you will come back to main tree of Local Menu    BY PRESsure  Setting LRV across setting pressure  If you will confirm this     option  transmitter will confirm the party of command by the      DONE  announcement or the proper number of error will notify       BY VALUE  Setting the LRV across inscribing of value       After confirmation will display current LRV value before the passage  in mode of edition     y         Choose and confirm sign introduced parameter     y    00000  Introduce in sequence   digit after digit  5 digital number with point  or without point  After confirmation the last 5 digit of the parameter  transmitter will confirm the party of command by the  
62. ults which may lead to measurement errors  such  as connections which are not tight  sediment blockage in lines which are too narrow  gas bubbles in a liquid line  or liquid column in a gas line etc     7 2  Low Ambient Temperature        When the solidification point of the liquid whose pressure is being measured is higher than the  Ak ambient temperature  steps should be taken to protect the measurement apparatus from freezing  effects     B 15 DTR APC APR ALW 02 ENG     This is particularly important in the case open air installations    Protection is obtained by filling the impulse lines with a mixture of ethylene glycol and water  or another liquid  whose solidification point does not exceed the ambient temperature  Thermal insulation can protect the  transmitter casing and lines only from brief exposure to low temperatures  Where the temperature is very low   the transmitter and impulse lines should be heated     7 3  High Medium Temperature     The APC     APR    transmitters may be used to measure media with temperatures of up to 120      PED version  see p 5 2 3   To protect the sensing module from temperatures higher then 120  C  long impulse lines are used to  disperse the heat and to lower the temperature of the sensing module    Where it is not possible to use impulse lines of the required length  APC     APR    transmitters with remote  diaphragm seals should be used  see    DIAPHRAGM SEALS  catalogue cards      Data as per Appendix Exi or Appendix Exd 02 apply 
63. ure differential pressure across constrictions  such as filters and orifices     P 3 2  The transmitters may be fitted with a range of types of process connectors  which enables them to  be used in a variety of conditions such as thick or highly reactive media  high and low temperatures   etc   3 3  APC     APR    transmitters generate a 4   20mA output signal and a digital communication signal in a two   wire system  current loop   The use of smart electronics enables regulation of the zero point  the measurement  range  damping  radical conversion characteristic and other functions using an Aplisens KAP communicator or  from a PC using a Hart RS232 converter and Aplisens    Raport    configuration software     B 9 DTR APC APR ALW 02 ENG     4  IDENTIFYING MARKS  ORDERING PROCEDURE  4 1  Every transmitter carries a rating plate containing at least the following information  CE mark  manufacturer  name  transmitter type  serial number  pressure range  static pressure limit  output signal  power supply voltage   Version types and the method of specifying the desired product are described in the current    Information Cards     and the Catalogue   4 2  APC   APR   transmitters in Ex version or Exd version have additional markings as described in  DTR APC APR ALW 02 ENG  Appendix Exi or Exd     4 3  The rating plates of APC      APR    transmitters in versions compliant with the PED pressure  directive contain the notified unit number 0062 next to the CE mark  as well as the des
64. value  The decimal point position is possible to set in local MENU or remotely    In the case of display overfilling  when the displayed value will exceed the  99999     the   COMMA     displays  When the pressure value limits will exceeded the  UNDER    or  OVER    are displayed depending  on exceeding direction  The pressure unit or user   s unit can be displayed alternatingly with digital value  displaying in 10s indicate digital value cycle  or 1s indicate digital value cycle  If it is necessary the display  unit switching off in local MENU is possible  or with communicator  or PC software using    The transmitter makes possible rescale on the user s individual the pressure value  To make this is  necessary with using communicator or PC software write the corresponding to beginning and to end  values of setting range as well as write the own unit name  After activating user s mode the rescale value  will be visible on display     Local display is equipped in backlight  switching on and switching off with jumper on electronic board     After configuration it is important to protect the transducers using command HART  247    During work transmitter should be safe prior to entries  This prevents accidental or intentional  changes configurational data  The protection function is accessible in KAP03 communicator      Raport s    software  as well as  in applying DD or DMT programs libraries     B 25    10 2 8  Configuration of the APR 2200ALW transmitters to measure the level 
65. will confirm the party of command by the  DONE       Come back to factory setting      Return to Local Menu  If you will confirm this option   you will come back to main tree of Local Menu      Confirm the command as bellow across longer press  button a  After parameter confirmation transmitter will  confirm the party of command by the  DONE       The program enforcement of the transmitter restart      Return to Local Menu  If you will confirm this option   you will come back to main tree of Local Menu      Confirm the command as bellow across longer press  button    After parameter confirmation transmitter will  confirm the party of command by the  DONE      B 23 DTR APC APR ALW 02 ENG     Local Menu  error reports    During executing in Local Menu some functions  LCD2 announcement can be displayed on the screen   The error displaying evidences about no realization of command of Local Menu    The shortened description of errors announcements is showed below     ERR_L07  in_write_protected_mode   Error will ensue out when we try to change setting in Local  Menu  but transmitter is protected before recording  To to make the change of setting with  Local Menu using  transmitter has to have the included service of Local Menu as well as  switched off protection before record  These parameters modification is possible by using  KAP  03 communicator     RAPORT    program or software using library EDDL     e default setting     Local Menu service switched on  protection before recor
66. y of command by the  DONE       Type of the process variable displayed on LCD1      Return to Local Menu  If you will confirm this option   you will come back to main tree of Local Menu     Confirm one of the following option across  longer press button    After parameter confirmation  transmitter will confirm the party of command by the  DONE      On LCD1 will displayed current value in current loop     The percent value output signal will displayed on LCD1        Type of the process variable displayed on LCD2      Return to Local Menu  If you will confirm this option   you will come back to main tree of Local Menu      Confirm one of the following option across   longer press button a  After parameter confirmation  transmitter will confirm the party of command by the  DONE    The pressure value will displayed on LCD2    The user s units will displayed on LCD2     The current unit or user s unit alternately  with process variable will displayed on LCD2        The current unit or user s unit alternately  with process variable will not displayed on LCD2     LCD2 DP     SS SS ee SS eS SS    FACTORY     RESET         lt BACK    l  XXXXXe  l  XXXXeX  l  XXXeXX    l  XXeXXX    l  eXXXXX    22 DTR APC APR ALW 02 ENG      The process variable point position on LCD2      Return to Local Menu  If you will confirm this option   you will come back to main tree of Local Menu      Confirm one of the following option across  longer press button    After parameter confirmation  transmitter 
67. y switching off is also possible  The display switching of function is possible with using communicator or  PC software only     B    24 DTR APC APR ALW 02 ENG     The APC     APR    transmitter display exterior is as bellow           A  lt  gt   MEE  Sy 5 4  IM AMAIA NA                                                                                                                                                                                                                                                                         There 3 main displays are visible     Bargraf  display line      the current output grade line guidance display  At 0  output guidance  the line  units are not blacked  As the guidance is rise the next units will blacked  One unit correspond to 10   guidance  At 100  guidance all line units will blacked     LCD1   the current or guidance percent preset range display  In accordance with display configuration the  current value in 4  20 mA current loop  or percent guidance preset range is possible to display  When  current is displayed   symbol  c    before value is visible     LCD2     the measured pressure digital value display  the calibrated pressure value according to user s  units display  the process variable units or user s units display  the MENU announcement and other  information or warning announcement display    In the case the digital pressure value or the calibrated pressure value display  the sign       can be visible  before displayed 
    
Download Pdf Manuals
 
 
    
Related Search
 APLISENS  aplisens s.a  aplisens pc-28  aplisens apc-2000alw  aplisens pce-28  aplisens apr-2000alw  aplisens sge-25  aplisens gmbh  aplisens pc28  aplisens pms-920  aplisens katowice  aplisens li-24alw  aplisens warszawa  aplisens apr-2000alw manual 
    
Related Contents
Optimus F6 User Guide  do Manual  K&N Engineering 57-9004 User's Manual  Digitus Inner corner bracket    DigitalFlow™ GC868 - GE Measurement & Control  Libretto d`installazione e uso Orologio ProgrammatoreFile  TCP/IP Ethernet Communications for the Series 90 PLC    Copyright © All rights reserved. 
   Failed to retrieve file