Home
1756-TD005 - Rockwell Automation
Contents
1. Overcurrent protection max User supplied 15 Ae Fusing Non replaceable fuse is soldered in place Isolation voltage 250V continuous Reinforced Insulation Type Power Input to Backplane Power Input to Annunciator Annunciator to Backplane Type tested at 3250V DC for 60 s Dimensions HxWxD approx 17 5x 14 5 x 13 7 cm 6 9 x 5 7x 5 4 in Weight approx 1 45 kg 3 2 Ib Chassis 1756 A4 1756 A7 1756 A10 1756 A13 1756 A17 Wire size Power 2 5 mm 14 AWG solid or stranded copper wire rated at 90 C 194 F or greater 1 2 mm 3 64 in insulation max Annunciator 0 25 2 5 mm 22 14 AWG solid or stranded copper wire rated at 90 C 194 F or greater 1 2 mm 3 64 in insulation max Wire category 6 1 on power ports 3 on annunciator ports 3 on 1756 CPR2 connections Pilot duty rating Annunciator not rated Conductor screw torque 0 79 Nem 7 Ibein Solid state relay contact 240V AC DC North American temperature code T4A IEC temperature code T4 Enclosure type rating None open style 1 UL certification for 120 240V AC 50 60 Hz nominal Rockwell Automation specified 85 265V AC 47 63 Hz Do not exceed 50 mA resistive only The hold up time is the time between input voltage removal and DC power failure Use time delay type overcurrent protection in all ungrounded conductors This fuse is intended to guard against fire hazard due
2. IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 1756 PAXT 25 70 C 13 158 F 1756 PBXT Temperature surrounding air max 70 C 158 F Temperature nonoperating IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Vibration 2g 10 500 Hz IEC 60068 2 6 Test Fc Operating Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 50g IEC 60068 2 27 Test Ea Unpackaged Shock Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity 6 kV contact discharges IEC 61000 4 2 8 KV air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 50 Pulse 100 AM at 900 MHz 10V m with 200 Hz 50 Pulse 100 AM at 1890 MHz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC 61000 4 4 4 kV at 5 kHz on power ports Surge transient immunity IEC 61000 4 5 1kV line line DM and 2 KV line earth CM on power ports Conducted RF immunity IEC 61000 4 6 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz Rockwell Automation Publication 1756 TDOOSE EN E Apri
3. when used with FLEX I O XT products provide a complete control system solution that you can use in environments where temperatures range from 20 70 C 4 158 F When used independently the ControlLogix XT system can withstand environments where the temperature ranges from 25 70 C 13 158 F 1756 PAXT and 1756 PBXT Mounting Dimensions 14 0 5 51 11 2 4 41 42669 Dimensions are in cm in Table 7 Technical Specifications ControlLogix XT Power Supplies Attribute 1756 PAXT 1756 PBXT E Input voltage range 85 265V AC 18 32V DC Input voltage nom 120 240V AC 24V DC Input frequency range 47 63 Hz N A Input power max 82VA 64 W 54W Output power max 42 W 25 70 C 13 158 F Power consumption 22W 12W Power dissipation 75 1 BTU hr 40 9 BTU hr Hold up time 6 cycles 85V AV 50 60 Hz 35 ms 18V DC 6 cycles 120V AV 50 60 Hz 40 ms 24V DC 6 cycles 200V AV 50 60 Hz 40 ms 32V DC 6 cycles 240V AV 50 60 Hz Inrush current max 20A 30A Current capacity at 1 2V 1 5A Current capacity at 3 3V 4A Current capacity at 5 1V 8A Current capacity at 24V 1 75A Overcurrent protection max User supplied 15 Ae Fusing Non replaceable fuse is soldered in place Isolation voltage 250V continuous reinforced insulation type power input to backplane Type tested 3260V DC for 60 s Rockwell Automatio
4. 3 3V 4A Current capacity at 5 1V 10A 13A Current capacity at 24V 2 8A Overcurrent protection max User supplied 15 Al Fusing Non replaceable fuse is soldered in place Isolation voltage 250V continuous reinforced insulation type power input to backplane Type tested 3500V DC for 60 s Weight approx 0 95 kg 2 10 Ib Dimensions 14 0 x 11 2 x 14 5 cm 5 51 x 4 41 x 5 71 in Module location Left side of 1756 chassis Chassis 1756 A4 1756 A7 1756 A10 1756 A13 1756 A17 Chassis compatibility Series A Series B Series B Wire size 2 5 mm 14 AWG solid or stranded copper wire rated at 90 C 194 F or greater 1 2 mm 3 64 in insulation max Wire category 1 on power ports Rockwell Automation Publication 1756 TDOOSE EN E April 2014 5 1756 ControlLogix Power Supplies Specifications Table 4 Technical Specifications Standard DC Power Supplies Attribute 1756 PB72 C 1756 PH75 B Conductor screw torque 0 8 Nem 7 bein North American temperature code T4 IEC temperature code T4 N A Enclosure type rating None open style 1 The hold up time is the time between input voltage removal and DC power failure I UL certification for 24V DC nominal Rockwell Automation specified 18 32V DC EW Use time delay type overcurrent protection in all ungrounded conductors This fuse is intended to guard against fire hazard due to short circuit conditions An publication 1770 4 1 7 UL Certification for 48V DC
5. 6 kV contact discharges IEC 61000 4 2 8 KV air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 50 Pulse 100 AM 900 MHz 10V m with 200 Hz 50 Pulse 100 AM 1890 MHz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity 4 kV at 5 kHz on power ports IEC 61000 4 4 Surge transient immunity 1 kV line line DM and 2 KV line earth CM on power ports IEC 61000 4 5 Conducted RF immunity 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz IEC 61000 4 6 Oscillatory surge withstand N A 3kV IEEE 37 90 1 Voltage variation 60 dips for 100 ms on DC supply ports IEC 61000 4 29 100 dips for 50 ms on DC supply ports 20 fluctuations for 15 min on DC supply ports 5 s interruptions on DC supply ports 10 ms interruption on DC supply ports 6 Rockwell Automation Publication 1756 TDOOSE EN E April 2014 1756 ControlLogix Power Supplies Specifications Table 6 Certifications Standard DC Power Supplies Certification 1756 PB72 C 1756 PB75 B 1756 PC75 B 1756 PH75 B UL N A UL Listed Industrial Control Equipment See UL File 65584 c UL us UL Listed Industrial Control Equipment certified for US and N A Canada See UL File 65584 UL Listed for Class I Division 2 Group A B C D Hazardous Locations certified for US and Canada See UL File E194810 CSA CSA Certified Proces
6. at 3 3V DC 4A Current capacity at 5 1V DC 10A 13A Current capacity at 24V DC 2 8A Overcurrent protection max User supplied 15 Al Fusing Non replaceable fuse is soldered in place Transformer load max 100VA Isolation voltage 250V continuous reinforced insulation type Type tested 3500V DC for 60 s power input to backplaneapprox Weight approx 0 95 kg 2 10 Ib Dimensions 14 0 x 11 2 x 14 5 cm 5 51 x 4 41 x 5 71 in Module location Left side of 1756 chassis Chassis 1756 A4 1756 A7 1756 A10 1756 A13 1756 A17 Chassis compatibility Series A Series B Series B Wire size 2 5 mm 14 AWG solid or stranded copper wire rated at 90 C 194 F or greater 1 2 mm 3 64 in insulation max Wire category 1 on power ports Conductor screw torque 0 8 Nem 7 Ibein orth American temperature code T4 Enclosure type rating SESS DQ publication 1770 4 1 None open style UL certification for 120 240V AC 50 60 Hz nominal Rockwell Automation specified 85 265V AC 47 63 Hz The hold up time is the time between input voltage removal and DC power failure The combination of all output power 5 1V backplane 24V backplane 3 3V backplane and 1 2V backplane cannot exceed 75 W Use time delay type overcurrent protection in all ungrounded conductors This fuse is intended to guard against fire hazard due to short circuit condition
7. immunity 10V m with 1 kHz sine wave 80 AM from 80 1000 MHz IEC 61000 4 3 10V m with 200 Hz 50 Pulse 100 AM 900 MHz 10V m with 200 Hz 50 Pulse 100 AM at 1890 MHz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity 4 kV at 5 kHz on power ports IEC 61000 4 4 4kV at 5 kHz on annunciator ports Surge transient immunity 1 kV line line DM and 2 KV line earth CM on power ports IEC 61000 4 5 Conducted RF immunity 15V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz IEC 61000 4 6 Voltage variation 30 dips for 1 period at 0 and 180 on AC supply ports N A IEC 61000 4 11 60 dips for 5 and 50 periods on AC supply ports 10 fluctuations for 15 min on AC supply ports gt 95 interruptions for 250 periods on AC supply ports Voltage variation IEC 61000 4 29 N A Table 15 Certifications XT Redundant Power Supplies Certification c UL us 1756 PAXTR 10 ms interruption on DC supply ports 60 dips for 100 ms on DC supply ports 100 dips for 50 ms on DC supply ports 20 fluctuations for 15 min on DC supply ports 5 s interruptions on DC supply ports 1756 PBXTR UL Listed Industrial Control Equipment certified for US and Canada See UL File 65584 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E194810 CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial
8. nominal Rockwell Automation specified 30 60V DC 8 UL certification for 125V DC nominal Rockwell Automation specified 90 143V DC Table 5 Environmental Specifications Standard DC Power Supplies The combination of all output power 5 1V backplane 24V backplane 3 3V backplane and 1 2V backplane cannot exceed 75 W Use this conductor category information for planning conductor routing as described in the system level installation manual See the Industrial Automation Wiring and Grounding Guidelines Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 1756 PB72 C 1756 PB75 B 1756 PC75 B 1756 PH75 B 0 60 C 32 140 F Temperature surrounding air max 60 C 140 F Temperature nonoperating IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Vibration 29 10 500 Hz IEC 60068 2 6 Test Fc Operating Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 50g IEC 60068 2 27 Test Ea Unpackaged Shock Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity
9. with EN 61131 2 Programmable Controllers Clause 11 RCM Australian Radiocommunications Act compliant with EN 61000 6 4 Industrial Emissions Ex Europ s Union 94 9 EC ATEX Directive compliant with EN 60079 15 Potentially Explosive Atmospheres Protection n EN 60079 0 General Requirements 113 G Ex nA IIC T4 Gc KC Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 1 When marked See the Product Certification link at http www ab com for Declarations of Conformity Certificates and other certification details Table 13 Technical Specifications ControlLogix XT Redundant Power Supplies Attribute 1756 PAXTR 1756 PBXTR Input voltage range 85 265V acl 18 32V DC Input voltage 120V 240V AC 24V DC Input frequency range 47 63 Hz DC Input power max 75VA 65 W 75W Output power max 42W 0 60 C 32 140 F Hold up time 2 cycles 60 Hz 20 ms 2 cycles 50 Hz Inrush current max 20A 30A Current capacity at 1 2V 1 5A Current capacity at 3 3V 4A Current capacity at 5 1V 8A Rockwell Automation Publication 1756 TDOOSE EN E April 2014 15 1756 ControlLogix Power Supplies Specifications Table 13 Technical Specifications ControlLogix XT Redundant Power Supplies Attribute 1756 PAXTR 1756 PBXTR Current capacity at 24V 175A Annunciator power 240V AC 50 60 Hz 240V DC 50 mA resistive only
10. 0 F 1756 PB75R Temperature surrounding air max 60 C 140 F Temperature nonoperating IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Vibration IEC 60068 2 6 Test Fc Operating 29 10 500 Hz Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 50g IEC 60068 2 27 Test Ea Unpackaged Shock Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity 6 kV contact discharges IEC 61000 4 2 8 kV air discharges Radiated RF immunity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 50 Pulse 100 AM 900 MHz 10V m with 200 Hz 50 Pulse 100 AM at 1890 MHz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity IEC 61000 4 4 4 kV at 5 kHz on power ports 4kV at 5 kHz on annunciator ports 14 Rockwell Automation Publication 1756 TDOOSE EN E April 2014 1756 ControlLogix Power Supplies Specifications Table 11 Environmental Specifications Redundant Power Supplies Attribute 1756 PA75R 1756 PB75R Surge transient immunity 1 kV line line DM and 2 KV line earth CM on power ports IEC 61000 4 5 Conducted RF immunity 15V
11. Automation Resource Description ControlLogix Selection Guide publication 1756 SG001 Provides overview of the ControlLogix system and its products ControlLogix Chassis Specifications Technical Data publication 1756 TD006 Provides technical specifications for ControlLogix chassis ControlLogix Chassis and Power Supplies Installation Instructions publication 1756 IN005 Provides planning and installation information for the ControlLogix chassis and power supplies ControlLogix System User Manual publication 1756 UM001 Provides information on how to install configure program and use ControlLogix systems Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Provides general guidelines for installing a Rockwell Automation industrial system Product Certifications website http www ab com Provides declarations of conformity certificates and other certification details You can view or download publications at http www rockwellautomation com literature To order paper copies of technical documentation contact your local Allen Bradley distributor or Rockwell Automation sales representative 22 Rockwell Automation Publication 1756 TDOOSE EN E April 2014 1756 ControlLogix Power Supplies Specifications Notes Rockwell Automation Publication 1756 TDOOSE EN E April 2014 23 Important User Information Read this document and the documents listed in the additional resources section about inst
12. IC T5 Gc X KC Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 1 When marked See the Product Certification link at http www ab com for Declarations of Conformity Certificates and other certification details Rockwell Automation Publication 1756 TD005E EN E April 2014 19 1756 ControlLogix Power Supplies Specifications Power Load and Transformer Sizing The following graphs show the input power requirements for the power supplies given the power they are providing to the modules in the chassis Follow these steps to determine the power requirements for your chassis 1 Calculate the Backplane Power Load by adding the power draw in Watts for all of the planned modules For module power draws refer to the module specification tables in the ControlLogix Selection Guide publication 1756 SG001 2 Locate the Backplane Power Load on the graph s vertical y axis and determine the corresponding Real Power input power rating on the horizontal x axis The Real Power value is the amount of power consumed by the power supply 20 Rockwell Automation Publication 1756 TDOOSE EN E April 2014 Power Supply Power Requirements 1756 PA72 C 1756 PA75 B AC 75 100 60 Backplane Power 45 Load Watts 30 15 0 0 20 40 60 80 100 120 Real Power Watts 43895 1756 PB72 C 1756 PB75 B DC 75 95 60 Backplane Powe
13. Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A amp B European Union 2006 95 EC LVD compliant with EN 61131 2 Programmable Controllers Clause 11 RCM Australian Radiocommunications Act compliant with EN 61000 6 4 Industrial Emissions European Union 94 9 EC ATEX Directive compliant with EN 60079 0 General Requirements I3GExnAlICT4 GcX EN 60079 15 Potentially Explosive Atmospheres Protection n KC Article 58 2 of Radio Waves Act Clause 3 Korean Registration of Broadcasting and Communications Equipment compliant with 1 When marked See the Product Certification link at http www ab com for Declarations of Conformity Certificates and other certification details Redundant Power Supply Chassis Adapter Module Table 16 Technical Specifications Redundant Power Supplies Chassis Adapter Module Attribute 1756 PSCA2 1756 PSCA2XT Current capacity at 1 2V DC 1 5A Current capacity at 3 3V DC 4A Current capacity at 5 1V DC 15A Current capacity at 24V DC 2 8A Wire category M 3 on 1756 CPR2 connections Rockwell Automation Publication 1756 TD005E EN E April 2014 1756 ControlLogix Power Supplies Specifications Table 16 Technical Specifications Redundant Power Supplies Chassis Adapter Module Attribute 1756 PSCA2 1756 PSCA2XT North American tem
14. Technical Data Allen Bradley 1756 ControlLogix Power Supplies Specifications Standard Chassis Catalog Numbers 1756 A4 1756 A10 1756 A13 1756 A17 ControlLogix XT Chassis Catalog Numbers 1756 A4LXT 1756 A5XT 1756 A7XLT 1756 A7XT Standard Power Supplies Catalog Numbers 1756 PA72 1756 PA75 1756 PB72 1756 PB75 1756 PC75 1756 PH75 ControlLogix XT Power Supplies Catalog Numbers 1756 PAXT 1756 PBXT Redundant Power Supplies Catalog Numbers 1756 PA75R 1756 PB75R Redundant Power Supplies Chassis Adapter Module Catalog Number 1756 PSCA2 ControlLogix XT Redundant Power Supplies Catalog Numbers 1756 PAXTR 1756 PBXTR ControlLogix XT Redundant Power Supplies Chassis Adapter Module Catalog Number 1756 PSCA2XT Topic Page Standard AC power supplies 2 Standard DC Power Supplies 5 1756 ControlLogix XT Power Supplies 8 Redundant Power Supplies 11 ControlLogix power supplies are used with the 1756 chassis to provide 1 2 V 3 3V SV and 24V DC power directly to the chassis backplane Standard ControlLogix XT and redundant power supplies are available LISTEN JADE Rockwell SOME Allen Bradley Rockwell Software Automation 1756 ControlLogix Power Supplies Specifications Summary of Changes This manual contains new and updated information Changes throughout this revision are marked by change bars as shown to the left of this paragraph Added Technical Specifications Environmental Specifications and Cer
15. allation configuration and operation of this equipment before you install configure operate or maintain this product Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes laws and standards Activities including installation adjustments putting into service use assembly disassembly and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice If this equipment is used in a manner not specified by the manufacturer the protection provided by the equipment may be impaired In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited Documentation Feedback Your comments will help us serve your document
16. ammable Controllers Clause 8 Zone A amp B European Union 2006 95 EC LVD compliant with EN 61131 2 Programmable Controllers Clause 11 C Tick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions KC Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 1 When marked See the Product Certification link at http www ab com for Declarations of Conformity Certificates and other certification details 4 Rockwell Automation Publication 1756 TDOOSE EN E April 2014 1756 ControlLogix Power Supplies Specifications Standard DC Power Supplies 1756 PB72 1756 PB75 1756 PC75 and 1756 PH75 Mounting Dimensions t 14 0 5 51 11 2 4 4 41 gt 42669 Dimensions are in cm in Table 4 Technical Specifications Standard DC Power Supplies Attribute 1756 PB72 C 1756 PB75 B 1756 PC75 B 1756 PH75 B Input voltage range 18 32V DC 30 60V DC 90 143V DC Input voltage nom 24V DC 48V DC 125V DC Input power max 95 W Output power max 75 W 0 60 C 32 140 Fy Power consumption 20W 0 60 C 32 140 F Power dissipation 68 2 BTU hr Hold up time 35 ms 18V DC 50 ms 30 60VDCnom 50 ms amp 90 143V DC nom 40 ms 24V DC 40 ms 32V DC Inrush current max 30A 20A Current capacity at 1 2V 15A Current capacity at
17. ation needs better If you have any suggestions on how to improve this document complete this form publication RA DU002 available at http www rockwellautomation com literature Allen Bradley Rockwell Software Rockwell Automation ControlLogix ControlLogix XT FLEX I O XT and LISTEN THINK SOLVE are trademarks of Rockwell Automation Inc Trademarks not belonging to Rockwell Automation are property of their respective companies Rockwell Otomasyon Ticaret A Kar Plaza Is Merkezi E Blok Kat 6 34752 erenk y stanbul Tel 90 216 5698400 www rockwellautomation com Power Control and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Automation NV Pegasus Park De Kleetlaan 12a 1831 Diegem Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Publication 1756 TDOOSE EN E April 2014 Supersedes Publication 1756 TD005D EN E March 2013 Copyright 2014 Rockwell Automation Inc All rights reserved Printed in the U S A
18. e 100 AM at 900 MHz 10V m with 200 Hz 50 Pulse 100 AM at 1890 MHz 3V m with 1 kHz sine wave 80 AM from 2000 2700 MHz Table 18 Certifications Redundant Power Supplies Chassis Adapter Module Certification 1756 PSCA2 1756 PSCA2XT c UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File 65584 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E194810 CSA CSA Certified Process Control Equipment See CSA File N A LR54689 CSA Certified Process Control Equipment for Class Division 2 Group A B C D Hazardous Locations See CSA File LR69960C FM FM Approved Equipment for use in Class Division 2 Group N A A B C D Hazardous Locations CE European Union 2004 108 EC EMC Directive compliant with 18 Rockwell Automation Publication 1756 TD005E EN E April 2014 EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A amp B 1756 ControlLogix Power Supplies Specifications Table 18 Certifications Redundant Power Supplies Chassis Adapter Module RCM Australian Radiocommunications Act compliant with EN 61000 6 4 Industrial Emissions Ex European Union 94 9 EC ATEX Directive compliant with EN 60079 15 Potentially Explosive Atmospheres Protection n EN 60079 0 General Requirements 113 G Ex nA I
19. er 1 2 mm 3 64 in insulation max Annunciator 0 25 2 5 mm 22 14 AWG solid or stranded copper wire rated at 90 C 194 F or greater 1 2 mm 3 64 in insulation max Wire category 6 3 on annunciator ports 1 on power ports 3 on 1756 CPR2 connections Pilot duty rating Annunciator not rated Conductor screw torque 0 79 Nem 7 Ibin Solid state relay contact 240V AC DC North American temperature code T3C T4 IEC temperature code TB T4 Enclosure type rating None open style 1 UL certification for 120 240V AC 50 60 Hz nominal Rockwell Automation specified 85 265V AC 47 63 Hz 2 UL certification for 24V DC nominal Rockwell Automation specified 18 32V DC 3 The hold up time is the time between input voltage removal and DC power failure 4 Use time delay type overcurrent protection in all ungrounded conductors 5 This fuse is intended to guard against fire hazard due to short circuit conditions 6 Use this conductor category information for planning conductor routing See the Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 7 Do not exceed 50 mA resistive only Table 11 Environmental Specifications Redundant Power Supplies Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 1756 PA75R 0 60 C 32 14
20. l 2014 1756 ControlLogix Power Supplies Specifications Table 8 Environmental Specifications ControlLogix XTPower Supplies Attribute 1756 PAXT 1756 PBXT Oscillatory surge withstand 3kV N A IEEE 37 90 1 Voltage variation 30 dips for 1 period at 0 and 180 on AC supply ports N A IEC 61000 4 11 60 dips for 5 and 50 periods on AC supply ports 10 fluctuations for 15 min on AC supply ports gt 95 interruptions for 250 periods on AC supply ports Voltage variation IEC 61000 4 29 N A Table 9 Certifications ControlLogix XPowerT Supplies Certification 1756 PAXT 1756 PBXT 60 dips for 100 ms on DC supply ports 100 dips for 50 ms on DC supply ports 20 fluctuations for 15 min on DC supply ports 5 s interruptions on DC supply ports 10 ms interruption on DC supply ports c UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File 65584 UL Listed for Class I Division 2 Group A B C D Hazardous Locations certified for US and Canada See UL File E194810 CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions European Union 2006 95 EC LVD compliant with EN 61131 2 Programmable Controllers Clause 11 EN 61131 2 Programmable Controllers Clause 8 Zone A amp B CTick Australian Radiocommunications Ac
21. n Publication 1756 TDOOSE EN E April 2014 1756 ControlLogix Power Supplies Specifications Table 7 Technical Specifications ControlLogix XT Power Supplies Attribute Weight approx 1756 PAXT 0 95 kg 2 10 Ib 1756 PBXT Dimensions 14 0 x 11 2 x 14 5 cm 5 51 x 4 41 x 5 71 in Module location Left side of 1756 chassis Chassis 1756 A4LXT 1756 A5XT 1756 A7LXT 1756 A7XT Wire size 2 5 mm 14 AWG solid or stranded copper wire rated at 90 C 194 F or greater 1 2 mm 3 64 in insulation max Wire category 1 on power ports Conductor screw torque 0 8 Nem 7 Ibein North American temperature code T4 T4A IEC temperature code T4 Enclosure type rating None open style 1 The hold up time is the time between input voltage removal and DC power failure 2 UL certification for 120 240V AC 50 60 Hz nominal Rockwell Automation specified 85 265V AC 47 63 Hz 3 Use time delay type overcurrent protection in all ungrounded conductors 4 This fuse is intended to guard against fire hazard due to short circuit conditions 5 Use this conductor category information for planning conductor routing as described in the system level installation manual See the Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Table 8 Environmental Specifications ControlLogix XTPower Supplies Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold
22. oses Rockwell Automation Publication 1756 TDOOSE EN E April 2014 11 1756 ControlLogix Power Supplies Specifications System Configuration Recommendations We recommend that you use one of these methods to configure your redundant power supply system Recommended Configurations for a System That Uses One Chassis oo oo oo oo 2 42655 42657 Recommended Configurations for a System That Uses Two Chassis BI 8 te gg dog q oa s HEEE Tal Is Le de aa a a a ad Ica 42658 42655 12 Rockwell Automation Publication 1756 TDOOSE EN E April 2014 1756 ControlLogix Power Supplies Specifications 1756 PA75R 1756 PAXTR 1756 PB75R and 1756 PBXTR Mounting Dimensions Dimensions are in cm in Redundant Power Supply Features The redundant power supplies offer the same features as the standard power supplies in addition to the following Top Mounting Hole Diameter os 1 1 0 433 e Automatic chassis load sharing between the redundant power supplies e Status indicators for visual operating status of the pair e Solid state relay for system recognition of supply status when wired to an input module Table 10 Technical S
23. pecifications ControlLogix Redundant Power Supplies Bottom Mounting Hole Diameter 0 55 om O 45829 Attribute 1756 PA75R 1756 PB75R Input voltage range 85 265V AC 18 32V DC Input voltage 120V 240V AC 50 60 Hz 24V DC Input frequency range 47 63Hz DC Input power max 120VA 115 W 110W Output power max 75 W 0 60 C 32 140 F Hold up time 2 cycles 60 Hz 20 ms 2 cycles 50 Hz Inrush current max 20A 30A Current capacity at 1 2V 1 5A Current capacity at 3 3V 4A Current capacity at 5 1V BA Current capacity at 24V 28A Annunciator power 240V AC 50 60 Hz 240V DC 50 mA resistive only Overcurrent protection max User supplied 15 A Fusing Non replaceable fuse is soldered in place Isolation voltage 250V continuous Reinforced Insulation Type Power Input to Backplane Power Input to Annunciator Annunciator to Backplane Type tested at 3250V DC for 60 s Rockwell Automation Publication 1756 TDOOSE EN E April 2014 13 1756 ControlLogix Power Supplies Specifications Table 10 Technical Specifications ControlLogix Redundant Power Supplies Attribute Dimensions HxWxD approx 1756 PA75R 1756 PB75R 17 5x 14 5 x 13 7 cm 6 9 x 5 7 x 5 4 in Weight approx 1 45 kg 3 2 Ib Chassis 1756 A4 1756 A7 1756 A10 1756 A13 1756 A17 Wire size Power 2 5 mm 14 AWG solid or stranded copper wire rated at 90 C 194 F or great
24. perature code T5 T4A IEC temperature code T5 T4 Enclosure type rating None open style 1 Use this conductor category information for planning conductor routing See the Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Table 17 Environmental Specifications Redundant Power Supplies Chassis Adapter Module Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 1756 PSCA2 0 60 C 32 140 F 1756 PSCA2XT 25 70 C 13 158 F Temperature surrounding air max 60 C 140 F 70 C 158 F Temperature nonoperating 40 85 C 40 185 F IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock Relative humidity 5 95 noncondensing IEC 60068 2 30 Test Db Unpackaged Damp Heat Vibration 2g 10 500 Hz IEC 60068 2 6 Test Fc Operating Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 50g IEC 60068 2 27 Test Ea Unpackaged Shock Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity 6 kV contact discharges IEC 61000 4 2 8 KV air discharges Radiated RF immunity 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz IEC 61000 4 3 10V m with 200 Hz 50 Puls
25. r 45 Load Watts 30 15 0 4 0 20 40 60 80 100 120 Real Power Watts 43896 1756 PH75 B 1756 PC75 B DC 75 95 60 Backplane Power 45 Load Watts 30 15 o Lf 0 20 40 60 80 100 120 Real Power Watts 43618 1756 PAXT AC 42 64 35 28 Backplane Power 21 Load Watts 14 7 0 0 10 20 30 40 50 60 70 Real Power Watts 45008 1756 PAXTR AC 42 2 35 28 Backplane Power 21 Load Watts 14 7 0 0 10 30 40 50 60 70 20 80 Real Power Watts 5897 1756 ControlLogix Power Supplies Specifications 1756 PBXT DC 42 54 35 28 Backplane Power 21 Load Watts 14 7 o Z 0 10 20 30 40 50 60 Real Power Watts 45809 1756 PBXTR DC 42 75 35 28 Backplane Power 2 Load Watts 14 0 10 20 30 40 50 60 70 80 Real Power Watts jae 1756 PA75R A AC 60 Backplane Power 45 Load Watts 30 15 0 20 40 60 80 100 120 Real Power Watts 43588 1756 PB75R A DC Backplane Power 45 Load Watts 30 0 20 40 60 80 100 120 Real Power Watts 43589 Apparent Power Watts Transformer Load VA Real Power Watts Rockwell Automation Publication 1756 TD005E EN E April 2014 21 1756 ControlLogix Power Supplies Specifications Additional Resources These documents contain additional information concerning related products from Rockwell
26. rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz IEC 61000 4 6 Voltage variation 30 dips for 1 period at 0 and 180 on AC supply ports N A IEC 61000 4 11 60 dips for 5 and 50 periods on AC supply ports 10 fluctuations for 15 min on AC supply ports gt 95 interruptions for 250 periods on AC supply ports Voltage variation N A 10 ms interruption on DC supply ports IEC 61000 4 29 60 dips for 100 ms on DC supply ports 100 dips for 50 ms on DC supply ports 20 fluctuations for 15 min on DC supply ports 5 s interruptions on DC supply ports Table 12 Certifications Redundant Power Supplies Certification 1756 PA75R 1756 PB75R c UL us UL Listed Industrial Control Equipment certified for US and Canada See UL File 65584 UL Listed for Class Division 2 Group A B C D Hazardous Locations certified for U S and Canada See UL File E194810 CSA CSA Certified Process Control Equipment See CSA File LR54689C CSA Certified Process Control Equipment for Class Division 2 Group A B C D Hazardous Locations See CSA File LR69960C FM FM Approved Equipment for use in Class Division 2 Group A B C D Hazardous Locations CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A amp B European Union 2006 95 EC LVD compliant
27. s Use this conductor category information for planning conductor routing as described in the system level installation manual See the Industrial Automation Wiring and Grounding Guidelines Table 2 Environmental Specifications Standard AC Power Supplies Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 1756 PA72 C 1756 PA75 B 0 60 C 32 140 F Temperature surrounding air max 60 C 140 F Temperature non operating IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Vibration IEC 60068 2 6 Test Fc Operating 29 10 500 Hz Shock operating IEC 60068 2 27 Test Ea Unpackaged Shock 30g Rockwell Automation Publication 1756 TDOOSE EN E April 2014 1756 ControlLogix Power Supplies Specifications Table 2 Environmental Specifications Standard AC Power Supplies Attribute 1756 PA72 C 1756 PA75 B Shock nonoperating 50g IEC 60068 2 27 Test Ea Unpackaged Shock Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity 6 kV contact discharges IEC 61000 4 2 8 KV air discharges Radiated RF imm
28. s Control Equipment See CSA File LR54689C CSA Certified Process Control Equipment for Class I Division 2 Group A B C D Hazardous Locations See CSA File LR69960C FM FM Approved Equipment for use in Class Division 2 Group N A A B C D Hazardous Locations CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN61000 6 4 Industrial Emissions EN 61131 2 Programmable Controllers Clause 8 Zone A amp B European Union 2006 95 EC LVD compliant with EN 61131 2 Programmable Controllers Clause 11 CTick Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions Ex European Union 94 9 EC ATEX Directive compliant with N A EN 60079 15 Potentially Explosive Atmospheres Protection n EN 60079 0 General Requirements I3GExnAIICT4 GcX KC Korean Registration of Broadcasting and Communications Equipment compliant with Article 58 2 of Radio Waves Act Clause 3 1 When marked See the Product Certification link at http www ab com for Declarations of Conformity Certificates and other certification details Rockwell Automation Publication 1756 TDOOSE EN E April 2014 1756 ControlLogix Power Supplies Specifications 1756 ControlLogix XT Power Supplies The ControlLogix XT products include control and communication system components that
29. t compliant with AS NZS CISPR 11 Industrial Emissions Ex European Union 94 9 EC ATEX Directive compliant with EN 60079 0 General Requirements 113 GExnAlICT4 GcX EN 60079 15 Potentially Explosive Atmospheres Protection n KC Article 58 2 of Radio Waves Act Clause 3 Korean Registration of Broadcasting and Communications Equipment compliant with 1 When marked See the Product Certification link at http www ab com for Declarations of Conformity Certificates and other certification details 10 Rockwell Automation Publication 1756 TDOOSE EN E April 2014 1756 ControlLogix Power Supplies Specifications Redundant Power Supplies To build a redundant power supply system you need the following Cat No Description Amount 1756 PA75R A 1756 PAXTR Redundant power supply 2 1756 PB75R A or 1756 PBXTR 1756 CPR2 Redundant power supply cable Length 0 9 1m 3 ft 2 1756 PSCA2 or 1756 PSCA2XT Redundant power supply chassis adapter module 1 User supplied Annunciator wiring Max length 10 m 32 8 ft 2 1 Cable bend radius is 12 7 cm 5 0 in 2 The 1756 PSCA2 or 1756 PSCA 2XT chassis adapter module is a passive device that funnels power from the redundant power supplies to the single power connector on the ControlLogix series B chassis backplane 3 Optional user provided annunciator wiring can be connected to the solid state relay for status and troubleshooting purp
30. tifications tables for of Tables for ControlLogix XT Redundant Power Supplies Updated the tables to include the ControlLogix XT Redundant Power Supply Chassis Adapter 17 The following components were added to this technical data e ControlLogix XT Redundant Power Supply catalog number1756 PAXTR e ControlLogix XT Redundant Power Supply catalog number 1756 PBXTR e ControlLogix XT Redundant Power Supply Chassis Adapter Module catalog number1756 PSCA2XT e Standard AC power supplies Standard AC Power Supplies 1756 PA72 and 1756 PB75 Mounting Dimensions f 14 0 5 51 11 2 ae 42669 Dimensions are in cm in Table 1 Technical Specifications Standard AC Power Supplies Attribute 1756 PA72 C 1756 PA75 B Input voltage range 85 265V AC Input voltage nom 120V 240V AC Input frequency range 47 63 Hz Input power max 100VA 100 W Output power max 75W 0 60 C 32 140 oe Power consumption 25 W 0 60 C 32 140 F Power dissipation 85 3 BTU hr 2 Rockwell Automation Publication 1756 TDOOSE EN E April 2014 1756 ControlLogix Power Supplies Specifications Table 1 Technical Specifications Standard AC Power Supplies Attribute 1756 PA72 C 1756 PA75 B Hold up time 5 cycles 85V AC 50 60 Hz 6 cycles 120V AC 50 60 Hz 6 cycles 200V AC 50 60 Hz 6 cycles 240V AC 50 60 Hz Inrush current max 20A Current capacity at 1 2V DC 1 5A Current capacity
31. to short circuit conditions Use this conductor category information for planning conductor routing See Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Table 14 Environmental Specifications XT Redundant Power Supplies Attribute Temperature operating IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Operating Thermal Shock 1756 PAXTR 1756 PBXTR 25 70 C 13 158 F Temperature surrounding air max 70 C 158 F Temperature nonoperating IEC 60068 2 1 Test Ab Unpackaged Nonoperating Cold IEC 60068 2 2 Test Bb Unpackaged Nonoperating Dry Heat IEC 60068 2 14 Test Na Unpackaged Nonoperating Thermal Shock 40 85 C 40 185 F Relative humidity IEC 60068 2 30 Test Db Unpackaged Damp Heat 5 95 noncondensing Vibration IEC 60068 2 6 Test Fc Operating 29010 500 Hz Shock operating 30g IEC 60068 2 27 Test Ea Unpackaged Shock Shock nonoperating 50g IEC 60068 2 27 Test Ea Unpackaged Shock Emissions Class A CISPR 11 IEC 61000 6 4 ESD immunity 6 kV contact discharges IEC 61000 4 2 8 KV air discharges 16 Rockwell Automation Publication 1756 TDOOSE EN E April 2014 Table 14 Environmental Specifications XT Redundant Power Supplies 1756 ControlLogix Power Supplies Specifications Attribute 1756 PAXTR 1756 PBXTR Radiated RF
32. unity IEC 61000 4 3 10V m with 1 kHz sine wave 80 AM from 80 2000 MHz 10V m with 200 Hz 50 Pulse 100 AM 900 MHz 10V m with 200 Hz 50 Pulse 100 AM 1890 MHz 3V m with 1kHz sine wave 80 AM from 2000 2700 MHz EFT B immunity 4 kV at 5 kHz on power ports IEC 61000 4 4 Surge transient immunity 1 KV line line DM and 2 kV line earth CM on power ports IEC 61000 4 5 Conducted RF immunity 10V rms with 1 kHz sine wave 80 AM from 150 kHz 80 MHz IEC 61000 4 6 Oscillatory surge withstand 3kV IEEE 37 90 1 Voltage variation 30 dips for 1 period at 0 and 180 on AC supply ports IEC 61000 4 11 60 dips for 5 and 50 periods on AC supply ports Table 3 Certifications Standard AC Power Supplies 10 fluctuations for 15 min on AC supply ports gt 95 interruptions for 250 periods on AC supply ports Certification 1756 PA72 C 1756 PA75 B UL UL Listed Industrial Control Equipment See UL File 65584 CSA CSA Certified Process Control Equipment See CSA File LR54689C CSA Certified Process Control Equipment for Class I Division 2 Group A B C D Hazardous Locations See CSA File LR69960C FM FM Approved Equipment for use in Class Division 2 Group A B C D Hazardous Locations CE European Union 2004 108 EC EMC Directive compliant with EN 61326 1 Meas Control Lab Industrial Requirements EN 61000 6 2 Industrial Immunity EN 61000 6 4 Industrial Emissions EN 61131 2 Progr
Download Pdf Manuals
Related Search
Related Contents
Usermanual - SchunkNet Netviewer Internet Version 取扱説明書 スライド扉付埋込収納 スライド鏡扉付埋込収納 RIDGID R82230SB Use and Care Manual Elektronische Kommutiereinheit EKE Electronic Manuale utente Superlight 125/150 cc HP Deskjet 9800 Survivor35 multi-manual3.qxd New Buck Corporation 94NC User's Manual VSP 112W User Manual Copyright © All rights reserved.