Home
        GB National Standard of the People`s Republic of China
         Contents
1.   35 3 5 3 0  4 0 3 5  e 35                Remarks  The water pressure of water storage tank  burning chamber and heat transfer tube should be greater       than 0 3MPa   smaller than or equal to 0 6MPa        6 2 6 The material plate numbers  thickness and execution standards of the main parts  of burning appliances  Table 2 and Table 3  should be publicized in the product  manual   6 3 Safety devices  6 3 1 Burning appliances for domestic use should be equipped with the safety devices  specified in Table 5  The performance of the safety devices should meet the  requirements of the related standards    Table5 Safety devices of burning appliances for domestic use                               Serial  Safety Devices Scope of Application  No  1 Automatic ignition Different kinds of burning appliances   2 Fire observation Different kinds of burning appliances   3 Fire extinguishment protection Different kinds of burning appliances   Indoor atmospheric environmental Vertically placed water heaters  air heater  drying machine  4  protection and heater inside the room           Overheat protection    Shell of closed type water heater inside bathroom        Water systems  like rice pot  water heater  and the                                     6 Excessive temperature protection  heating hot water combination  combi  boiler  and so on   7 Air current supervision and control Compulsorily arrayed burning appliances   Gas burning system of portable burning stove  portable  8 Overpressur
2.   7 2 2 4 The hot water production rate of water heaters should adopt the requirements  of CJ 164    7 2 3 Gas fired volumetric water heaters   a  The type  structure and safety control devices of water heater should meet the  requirements of GB 18111    b  The heat storage of water heater should satisfy the bathing need for once   and the heat storing time should not be less than 30 min    Remarks  Heat storing time refers to the interval that the volumetric water   heater stops heating   7 2 4 Gas fired heating hot water combi boilers   a  The type  structure and safety control devices of water heater should meet  the requirements set out in CJ T 228    b  The selected type  fume design  system design  installation  troubleshooting   operation and maintenance of water heater should meet the requirements of  CECS 215     7 2 5 Other burning appliances for domestic use  a  Portable butane gas stoves should meet the requirements of GB 16691   b  Portable butane gas bottles for stove use should meet the requirements of  GB 16692   c  Gas heating appliances for domestic use should meet the requirements of  CJ T 113   7 2 6 Other burning appliances for business use  a  Gas fired large cooking stoves should meet the requirements of CJ T 3030   b  Chinese gas cooking stoves should meet the requirements of CJ T 28   c  Gas water boilers should meet the requirements of CJ T 29     d  Gas steamers should meet the requirements of CJ T 187     8 Installation of equipments    8 1 Install
3.   released to the market within the nation or province and through different means     10 Requirements of the limits of hazardous and toxic substances as well as the  pollution control for the electronic information products and materials in    gas burning appliance products    10 1 The electronic information products and materials of gas burning appliances   simply called GBA  have to meet the requirements of the limits of hazardous and  toxic substances and the requirements of identification for pollution control specified  in this Standard    10 2 The toxic and hazardous substances or elements in the electronic information  products and materials of gas burning appliances refer to the substances or elements   like lead  mercury  cadmium  sexavalent chrome  polybrominated biphenyls  PBB   and polybrominated ether  PBDE   and so on    10 3 The classification for the basic composing units of burning appliance products is  shown in Table 10 3 1  and the related terms and definitions are shown in  SJ T 11363 2006    Table 10 3 1 Classification of composing units                   Kinds of Composing Units Definition of Composing Unit  GBA A Different homogeneous materials that compose the burning appliance  products  GBA B Metal coated materials of different parts in burning appliance products  GBA C Small parts or materials that cannot be further dismantled from    burning appliance products under the current conditions  generally  referring to the products with specifications 
4.   st  4 Gas flue There should be no leakage on the gas flue   Note 1  For the installation location  fume exhaust and ventilation  please refer to the requirements set out in    CJJ12                 Note 2  The balanced type burning appliances can be installed inside the bathroom   Note 3  For the burning appliances using AC power  inspect the electrical environment conditions of the  building installed with burning appliances  and whether the electrical grounding of burning appliances    is safe           Annex B   Normative Annex     Use and maintenance of gas burning appliances    B 1 Inspect the user   s correct use situation of burning appliances according to the  requirements set out in the user manual of the burning appliance product   B 2 Inspect the maintenance situation of burning appliances according to the  requirements set out in the user manual of the burning appliance product     B 3 Inspect the qualifications of the maintenance staff     Annex C                                                  Normative Annex   Quality of gas supply  Table C 1 Kinds of Gas  i Wobbe Burning i  Item Kinds of Gas f Conclusion  No behaviour Cp  Artificial gas SR 6R 7R  4T 6T 10T 12T  Natural gas  13T  Liquefied petroleum gas   19Y 20Y 22Y  Remarks  For gas quality  please refer to GB T 16411   Table C 2 Pressure of Supplied Gas  Fluctuation f  Item Rated Pressure p  Pa Conclusion  Range  Artificial gas 1000   0 75 1 5 pn  AT 6T 1000   0 75 1 5 pn  Natural gas  10T 12T 13T 2000  B
5.  0 5m    b  When testing gas that is heavier than air  liquefied petroleum gas LPG   LPG air mixture  and so on  and fume  the horizontal distance between the  detection alarm and burning appliances or valve should be within the range  of 0 5 4m  The height of installation should be within the range of 0 3m  from the floor  The distance between the alarm and the door or window  hole should be greater than 0 5m    c  The technical indicators of the gas CO complex detector  including the  independent detector  should meet the requirements of the related national  standards    8 9 2 The installation of the emergency automatic gas cut off valve should meet the  following requirements    a  The automatic cut off valve should be installed in front of the gas meter   with the exception of smart gas meters with automatic cut off function     b  There should be a hand operated cut off valve in front of the automatic  cut off valve     8 9 3 The emergency automatic cut off valve should adopt the product of low voltage        24V   pulse switch  on the spot manual switch type  Its technical indicators should  meet the requirements of the related national standards  When an air exhaust device is  installed  after the emergency automatic cut off valve is turned off  the air exhaust    device should be turned on automatically        GB xxxx 2 200X    Safety Management Regulations of Gas Burning Appliances    1 Scope    This Standard sets the safety requirements for gas burning appliances a
6.  GB xxxx 2 200X   This Standard replaces GB 17905 1999     Safety management regulation of  gas burning appliances for domestic use       Compared with GB 17905 1999  the major changes made to this Standard are  as follows        the risks for the use of product and the requirements of control for hazardous  and toxic substances has been added to Subsection 3 of the original Standard        a clause about the responsibility of producers and sellers to retrieve the  scraped products has been added to Subsection 4 of the original Standard        the concrete requirements and limitations of product suitability test have  been added to Subsection 5 of the original Standard        the inspection requirements of the controller and cut off valve of product  have been added to Subsection 7 of the original Standard        the content that the gaseity condition during inspection of accidents related  to the product has been revised as the most unfavourable gaseity condition  the    requirements for CO content in fumes have been revised and requirements regarding    the shutdown function of the safe cut off valve have been revised according to the  European standards        information has been added to Subsection 9 about the handling  recycling   reuse and recirculation requirements of scraped gas burning appliances        information has been added to Subsection 10 about the requirements of the  limits of hazardous and toxic substances as well as pollution control for electronic  info
7.  The gas  discharge and resistance loss while running through the pipe should meet the designed  requirements    8 4 2 Below the pressure relief  spillway  etc  of furnace body  there should be  drainage facility  When the drainage is overheated  effective temperature reduction  measures should be taken  There should be no valve on the connecting pipe    8 4 3 The lowest part of the heating system should be equipped with drainage valve   whereas its highest part and the upper part of the radiator should be equipped with gas  exhaust valve  In the system  there should be at least an automatic gas exhaust  valve    8 4 4 The water tank of the open type heating appliances should be installed at the  highest place of the heating system  There should be no valve equipped on the  expansion pipe    8 4 5 A filter should be installed on the water return pipe of heating system    8 4 6 There should be valves equipped at the warm water inlet and outlet as well as  the cold water inlet of the furnace body    8 4 7 When the pressure of the supplied domestic cold water exceeds 0 6MPa  a  depressurising valve should be provided  When it is lower than the lowest working  pressure of equipment  a pressure pump should be additionally provided    8 4 8 The surface of the domestic hot water pipe should be winded by heat retaining  material to retain its temperature  The thickness of the heat retaining material should  not be less than 20mm    8 4 9 Water saving appliances should be selected for
8.  age limit  The environment friendly age limit is expressed by  the unit of years  The environmentally friendly age limit of products is specified by  the manufacturers themselves    10 10 When the complete appliance is inspected to be not complying with the  regulations of    Administration on the Control of Pollution Caused by Electronic  Information Products     the producer of the complete appliance shall be responsible for  the non conformance  and the responsibility of the elements and parts factory shall be  traced by the factory of the complete appliance  If the products independently sold  by the factory of elements and parts are inspected to be not complying with the  regulations of    Administration on the Control of Pollution Caused by Electronic  Information Products     the producer of the elements and parts should be responsible  for the non conformance    10 11 All the electronic information products and materials have to be stuck with a  label with name  contents and the related information of the toxic and hazardous  substances or elements  When marks are to be stuck on products  tests of products  can be made  If the producer is very clear about the contents and the related  information of the toxic and hazardous substances or elements  it is not required to  perform any tests  The test reports on the contents and the related information of the  toxic and hazardous substances or elements can either be the report made by the local  test laboratory  or the re
9.  compatibility  safety devices  control devices and    regulating devices should meet the specified requirements              5 3 1 7    Safety of AC power    The parts using AC power must meet the related standard code for    low pressure electric appliances        5 3 1 8    Pressurised parts    The design  assembling and strength of the pressurised parts have    to meet the standard code        5 3 1 9    Malfunction of safety    devices    Safety  regulation and control devices  including flame detection  device  gas regulator  discharge regulator  cooling fan  water gas  linkage device  atmospheric environmental sensor  of CO    overheat protection device  series valves of gas system  automatic  cut off valve  air supply device  Type C burning appliances    gas air proportional control device  and so on  should be ensured    to be safe under normal and abnormal use        5 3 1 10    Safety regulation    The functions of safety devices should not be affected by    regulating and control devices        5 3 1 11    Protection of parts specified    by manufacturer    The gas pressure regulator  the nozzle of burning appliances or  discharge regulator  the air sensor  CO  for environmental  protection  and so on should be regulated and preset by the  manufacturer when the products are delivered from the factory   and should take the protection measures of fixing or sealing   They shall not be dismantled and regulated by non professional    people        5 3 1 12    Marking a
10.  on and off  air Inspection  10 pressure 5kPa  no pressure Same as the left  gas system reduction for 1 min  report  Leakage specified in the Inspection  5 Same as the left  current standards report  Safety  Inspection  20 1 1 gas  0 05        1  Same as the left  report  CO content in Inspection  10 1 1 gas  0 10        1  Same as the left  fume report  Content specified in the Inspection  5 Same as the left  current standards report                                                    Fast water discharge  3 Heat load of main fire rate Ge 9L min  Inspection  enesfeauing  Q     3 5kW Volumetric heat load report  Qe 18kW  water saving Fast water discharge  Economi  sa i Heat load of main fire rate Ge 11L min  Inspection  cality Q     4 0kW Volumetric heat load report  environmental Qe 22kW  ee Fast water discharge  Protecnon i Heat load of main fire rate Ge 13L min  Inspection  Q     4 5kW Volumetric heat load report  Qe 26kW  Inspection  30 20 years 20 years  report  s    2 P Inspection  years years  Durability Age limit report  Age limit of scrap judgement  Inspection  10 specified in the current Same as the left  report  standards                         6 5 2 According to the total scores per item acquired from Table 11  the burning  appliances for domestic use can have their quality grades confirmed based on the  following gradation in terms of scores  full score is 100 scores    a  Grade A  1    class product   The total scores per item are greater than or  equal to 90 sc
11.  products  It is not required to indicate the elements  components or    materials of the non toxic and non hazardous substances or elements     Annex A     Normative Annex     Installation  fume exhaust and ventilation of gas burning appliances  and    Table A 1    airtightness of pipeline    and airtightness of pipeline    Installation  fume exhaust and ventilation of gas burning appliances                                                                             Product Name Model No Producer Production date  Serial No  Item Contents Conclusion  Certification of installation unit  1 Quality  Recognition of training of fixer  Permitted Kitchen  external corridor  balcony  outdoors  Not Bedroom  basement   Installation Area of gas inlet is  2 permitted bathroom  the  location greater than the area  inflammable  explosive  of gas exhaust funnel  and corrosive room  Stove  etc  Possess natural gas fume  exhaust hood  or Area of gas inlet is  compulsory fume exhaust   above 9 5cm    kW  hood or air exchange fan  Natural gas The wind cap of gas fume  exhaust exhaust pipe is out of the  positive pressure zone of  Indoor type building  3 burning Compulsory The gas funnel or fume exhaust hood has linkage  appliances   gas exhaust action with the gas exhaust fan   Natural gas The gas supply  exhaust funnel is connected to the  supply  outdoors or the public flue   exhaust  Compulsory The gas supply  exhaust funnel is connected to the  gas outdoors or the public flue   supply exhau
12.  related  requirements of GB4706           Remarks  The definition for the condition of gas quality test is shown in the requirements of GB T 16411           
13.  resistant material above the equivalent standard should be used   The minimum nominal thickness of material should meet the requirements  set out in Tables 2   4  The actual thickness of parts should be greater than  0 8 time of the nominal thickness    b  The metallic material for performing electric plating of the surface should  take a 24 hour test according to the requirements of GB T 16411  and  should be confirmed corrosion free    c  The metallic material for surface coating should take a 24 hour test according  to the requirements of GB T 16411  and should be confirmed to have no  rusting  bubbling and shedding phenomena    d  The metallic material for surface enamelling should perform ballistic impact  test according to the requirements of GB T 16411  and should be confirmed  to have no shedding phenomenon    e  Steel glass materials should perform impact resistance test according to the  related standard code  and should be confirmed to have no breaking  phenomenon    6 2 3 Sealed objects  sealing materials and other non metallic sealing materials used    where gas passes through should meet the following requirements     a  Rubber  plastic and other materials of the sealed object should be tested  under the gas resistant performance test according to the requirements of  GB T 16411  and the quality change rate should be less than 20   without  any softening and brittling phenomena to affect their use   b  Rubber product should perform gas resistant performance tes
14.  scraped and old gas appliances and  fittings    4 3 Responsibilities and obligations of the gas suppliers   4 3 1 The quality of gas provided by the gas suppliers should meet the related  regulations  requirements and commitments    4 3 2 The gas suppliers are obliged to instil in consumers the knowledge of the safe  use of gas    4 4 Responsibilities and obligations of the fixers and maintenance staff of burning  appliances   4 4 1 The installation unit and maintenance unit of burning appliances have to acquire  certification    4 4 2 The fixers and maintenance staff of burning appliances have to be trained  and  acquire certification    4 4 3 The installation and maintenance of burning appliances have to meet the  requirements of the related standards and codes    4 4 4 The fixers and maintenance staff should be responsible for the quality of the  burning appliances installed and maintained    4 4 5 The fixers and maintenance staff are obliged to provide consumers with safety  information    4 5 Responsibilities and obligations of the consumers   4 5 1 After consumers have purchased a burning appliance  they should carefully read  the installation manual and user manual  and use the product correctly according to  the related requirements set out in the manuals    4 5 2 The consumers should provide a location for the installation of the product  which should meet the installation requirements and should guarantee the normal use  of burning appliances    4 5 3 The consumers
15.  should regularly perform routine  simple and operable cleaning  and maintenance of burning appliances according to the requirements of the user   s  manual    4 5 4 If a consumer finds any abnormal phenomena with regard to the burning  appliances  they should immediately stop using them and promptly contact the seller  or producer to achieve technical support and protection     4 5 5 If an accident occurs  the scene must be well retained and the related authorities    should be reported   4 5 6 The consumers should consider the possible risks that may happen to children     the aged and the handicapped during use of the product     5 Inspection of burning appliances and fittings   5 1 The type test of burning appliances and fittings should be performed according to  the related standards of burning appliances and fittings  The inspection units should  be the inspection institutions of burning appliances authorized by the nation    5 2 The inspection of the burning appliances and fittings that belongs to compulsory  product management should be conducted according to Directive No 5 of General  Administration of Quality Supervision  Inspection and Quarantine  AQSIQ   The  People   s Republic of China     China Compulsory Certification  CCC      The  inspection of burning appliances and fittings that belongs to application for product  license should be conducted according to Directive No  19 of AQSIQ     Measures for  the Administration of Manufacturing License for Industrial 
16.  specified by the design   8 7 6 When the coaxial pipe is horizontally installed on the external wall  the  downward inclination should not be less than 3mm m  and the effective length of its  external pipe section should not be less than 50mm   8 7 7 The installation of detachable pipe should meet the following requirements   a  When Type 1 and Type 3 burning appliances are detachable pipes  they  should be installed in a zone with a perimeter of 50cm   b  The gas supply inlet of Type 5 burning appliances should not be installed on  the wall with buildings on the opposite side   Comment  The types of burning appliances should adopt the requirements of  CJ T 228   8 7 8 The connection of burning appliances with gas supply exhaust pipe should have  guaranteed good airtightness  The connection length should not be less than 20mm   8 7 9 When the naturally ventilated common flue and the independent flue are to be  connected to the gas supply exhaust pipe  the following requirements should be met   a  The naturally ventilated common flue and the independent flue are  applicable to the closed type compulsory gas supply exhaust burning  appliances     b  The structure and dimensions of flue can be confirmed according to the    requirements of the related standards    c  The flue has good airtightness  no leakage of fume  and good performance in  fume resistance and heat resistance  Its heat retaining performance should  be good  and no condensation will be caused    d  The cross se
17.  system should meet  the specified requirements   b  Flame stability  When adopting limit gas to test the corresponding pressure 0 5Pn or 1 5Pn   the flame should be stable   c  Carbon monoxide  CO  content in fume   1  For open type  vertically placed  burning appliances  it should not be  greater than 0 1   a   1       2  For semi closed type and closed type burning appliances  it should not    be greater than 0 2   a  1    The testing condition  both are tested by adopting limit gas and 1 5Pn or  the maximum pressure   d  Electrical performance  The grounding  insulation  and so on should meet the specified  requirements   6 4 2 Energy efficiency and energy consumption of burning appliances  The energy efficiency of burning appliances should meet the related standard  and the    heating hot water combi boilers for domestic use as well as the Chinese cooking stove    code     The energy consumption of the gas stoves  water heaters    and large cooking stove for public use should meet the requirements of Subsections  6 4 3   6 4 5   6 4 3 Energy consumption gradation of gas stoves for domestic use  a  The rated heat load of the main fire of gas stoves for domestic use should  be 3 0   3 5kW  The energy consumption of the gas stoves for domestic  use should meet the requirements set out in Table 6     Table 6 Energy consumption gradation of gas stoves for domestic use                      Heat load Energy Identification of Energy  Serial No of Burner consumption index   energ
18.  the airtightness of the gas pipe and the pipe connecting with the  gas appliances    c  Accident of AC power shock  inspect the installation environment and  grounding conditions of burning appliances  and inspect the voltage  resistance strength of burning appliances according to the related  regulations of GB4706     8 6 For damage and loss of property caused by the violation of regulations  the  responsibilities and compensation should be implemented according to the related  regulations of    Product Quality Law  the People   s Republic of China        9 Handling  recycling  reuse and recirculation requirements of scraped gas  burning appliances    9 1 According to the requirements of    Cleaner Production Promotion Law  the  People   s Republic of China    and    Law on the Prevention and Control of  Environmental Pollution by Solid Wastes  the People   s Republic of China     the  environmental pollution by scraped burning appliance products should be controlled  and decreased  The purpose of stipulating the handling  recycling  reuse and material  recirculation of the scraped gas appliance is to maintain  protect and improve the  quality of the environment  protect the health of human beings and cautiously use the  natural resources    9 2 Pollution control of gas appliance products refers that the following measures  should be taken to decrease or eliminate the toxic and harmful substances or elements  in gas appliance products  such as lead  mercury  cadmium  sexava
19.  the domestic hot water system   8 4 10 The water filling pressure of the heating water system should not be smaller  than 0 1MPa    8 5 Connection of wire  restricted to the burning appliances using commercial power   8 5 1 Burning appliances should use the 220V    10     50H2 single phase AC  power    8 5 2 All connecting pipes of burning appliances shall not serve as the grounding  wires of electrical appliances     8 5 3 Burning appliances using Type I anti shock protection grade should have    reliable electrical grounding  The grounding measures should meet the requirements  set out in the existing related national standards  Type I burning appliances should  also be inspected to determine whether grounding wire is reliable and effective    8 5 4 The cross section area of power wire should satisfy the electrical need of  maximum power of burning appliances  and should not be small that 3 x 0 75mm      Inspection can be made according to the specifications and dimensions of the power  wire specified on the manual    8 5 5 The connection of power wire has to pay attention to the polarity of power wire   Live wire  L      brown wire  naught wire  N      blue wire  and earth wire  E       yellowish green wire  Type I burning appliances have to adopt the single phase  three hole socket  When facing the socket  the right hole connects with the live wire   the left hole connects with the naught wire  and the upper hole connects with the  ground wire  The installation way shoul
20.  the parts of burning appliances located close to the floor or other surfaces   the temperature rise of the floor and surfaces of the surrounding substances should  meet the requirements set out in the related standards  Its temperature is restricted  from reaching the extent that endangers the surrounding buildings   5 3 6 2 The rise in the surface temperature of operating parts of burning appliances   such as the button and handle  shall cause no harm to users   5 3 6 3 With the exception of surfaces and parts relating to heat transfer  the surface  temperature of the external parts of burning appliances for domestic use under normal  conditions shall not cause any harm to users  especially children  Appropriate  response time must be considered for users   5 3 7 Food and domestic water   Under the prerequisite that the related requirements are not violated  the  materials and parts for manufacturing burning appliances shall not contain heavy  metals  such as cadmium  lead  mercury  etc  If they happen to come into contact with  food and domestic water  their quality shall not be damaged   5 4 Comparison of the basic requirements  topical contents and requirements of  different standards for burning appliances   A list of the comparison of the basic requirements  topical contents and  requirements of different standards for burning appliances is shown in Table 1    Table 1 Comparison of the basic requirements  topical contents and   requirements of different standards for b
21.  when applying the sealing stamp  sealing wax or  adopting the unusual bolt connection    4 1 3 Because burning appliances and fittings are unsafe products  in case of harm  caused to the human body or loss of properties  the producers should bear the related  responsibilities    4 1 4 If the burning appliances and fittings are confirmed to be safe products  and the  harm and loss are confirmed to be caused at the fault of the victim  or by the fault of  another person deemed responsible for the victim  then the producer concerned may  be exempt from or may reject the related compensation responsibility    4 1 5 The producer is obliged to take part in the safety promotion activity held in  times of the release of products to the market  and should especially provide the  information of hazards of the burning appliances and fittings  enabling the consumers  to know the possibly foreseen hazards during the installation and use of the products   even if some of them are very small hazards    4 1 6 The producers should bear the responsibilities of the recycling  handling   recirculation and reuse of the scraped burning appliances    4 2 Responsibilities and obligations of the sellers   4 2 1 The sellers should be responsible and obliged to sell safety conditions and safe  fittings on the market    4 2 2 After a seller selling and importing burning appliances and fittings has been  recognised by a foreign enterprise  it immediately becomes the representative of the  foreign enterp
22. 0016 and GB 50045   8 2 Installation of furnace body  8 2 1 The installation of furnace body should meet the following requirements    a  The furnace body should be installed on the fire resistant wall  furnace  platform or floor that can bear the weight of furnace body    b  The installation of furnace body should be firm  kept vertical  and cannot be  slanted    c  When the furnace body is installed above other burning appliances  the net  horizontal distance between the furnace body and other burning appliances  shall not be less than 30cm    d  There should be necessary operation and maintenance space around the  furnace body  and the space should satisfy the requirements of the manual    8 2 2 The place installed with furnace body should be available for easy connection  with gas supply exhaust pipe  heating water supply return pipe  and the domestic  hot cold water pipe    8 2 3 The lowest point of the place installed with furnace body should be floor drained   restricted to the burning appliances with heating water supply return pipe     8 3 Connection of gas pipe   8 3 1 The gas type and the pressure of power supply have to be consistent with the  indication shown on the plate of burning appliances  When they are inconsistent  they  must be changed or re regulated by the suppliers of burning appliances   8 3 2 The gas pipe and the furnace body should be connected to a metallic pipe with  threaded adaptor  or the aluminium plastic composite pipe especially for gas  The
23. GB    National Standard of the People   s Republic of China    GB xxxx     200X  Replaces GB16914 2003 and GB17905 2004    Safety Code for Gas Burning Appliances    Date of Issue  200x xx xx Implementation Date  200x xx xx       Issued General Administration of Quality Supervision  Inspection  by and Quarantine of The People   s Republic of China    Contents    Foreword    GB xxxx 1 200X   Scope   Normative references   Release to the market and free circulation   Judgement procedures of conformance and inspection rules  Basic requirements   Technical measures    Conditions of selected type    ON DND NN FW NY    Installation of equipment    GB xxxx 2 200X   1 Scope   2 Normative references   3 Safety and environmental requirements of gas burning appliances and fittings   4 Responsibilities and obligations   4 1 Responsibilities and obligations of producers   4 2 Responsibilities and obligations of sellers   4 3 Responsibilities and obligations of gas suppliers   5 Inspection of gas burning appliances and fittings   6 Safety and maintenance supervision of gas burning appliances   7 Maintenance and scrap judgement of gas burning appliances   8 Handling of accident   9 Handling  recycling  reuse and recirculation requirements of scraped gas burning   appliances   10 Requirements for the limits of hazardous and toxic substances as well as  pollution control for electronic information products and materials in gas  burning appliance products   Annex A  Normative Annex  Installatio
24. Products       5 3 The market supervision and sampling inspection of burning appliances and fittings  should be conducted according to Directive No 13 of AQSIQ     Administration  Methods of National Supervision and Spot Check on Product Quality       5 4 The producers and sellers of burning appliances should apply for gas suitability  inspection of the burning appliances using artificial gas from the inspection institution  appointed by the local technical quality supervision authorities  For the suitability  inspection  it is only required to undergo the inspection of the most unfavourable gas  conditions of burning appliances  including incomplete burning  staying away from  flame  yellow flame  tempering and CO content in fume  Only if the suitability  inspection of the burning appliances is passed     it is not allowed to restrict the  enterprises and individuals of other districts from engaging in the production  operation and services  and it is not allowed to restrict the products of other districts    99 66    from entering the market of the district       according to the regulations of Clause 15 of       Administration Permit Law  The People   s Republic of China        6 Supervision during the installation and maintenance of burning appliances    Supervision during the installation and maintenance of burning appliances  should meet the regulations of Article 5 of Directive No 73 of the Ministry of Housing  and Urban Rural Development  MOHURD   the People   s Repub
25. abnormal situation found  the user should ask the  maintenance unit for reparation immediately  The maintenance stations and gas  suppliers having signed contracts with the producers of burning appliances should  regularly perform or be authorized by users to conduct safety inspection of burning  appliances and safety propaganda  and keep the inspection records  For the  problematic burning appliances  written comments on inspection and reparation  should be proposed  and the records should be filed  The inspection contents are as  follows   a  The functions of different operation parts of burning appliances  and the age  limit of burning appliances   b  The flame stability during the burning of burner   c  The function of controller  the normal switch off function of safety valve   and the safe switch off function during malfunctioning   d  The airtightness and draft of the flue  and the airtightness of the connecting  pipes of burning appliances   e  Whether the flue and the gas supply funnel are blocked  and whether the gas  exhaust system is smooth   f  Safety inspection of AC power  and the inspection of the installation  environment and grounding conditions of burning appliances   g  The airtightness and safety of the steel bottle  angle valve  pressure regulator    and rubber connecting pipe of liquefied petroleum gas  LPG      h  Records of maintenance or the replacement of damaged parts   7 3 Scrap judgement of burning appliances  7 3 1 As from the day the burning ap
26. aked flames should be                                        5 3 3 Ignition  stable and safe   5 3 4 Burning  Working conditions of The flame should be stable  The CO content in fumes should meet  5 3 4 1  burning the standard code   The gas supply exhaust funnel of the enclosed  Type C  burning  appliances as well as the gas exhaust funnel of semi closed type  5 3 4 2 Fume exhaust   Type B  burning appliances should be mechanically sealed well   and meet the specified requirements   The semi closed type  Type B  burning appliances should be  Fume exhaust into a room  installed according to the balanced type partition room  or   referring that the burning  established with a safety device that cuts the gas supply before the  5 3 4 3 appliances equipped with  burning product installed in the room has reached the dangerous  flue are under abnormal  volume  and a fume block safety device that prevents the  ventilation condition   backflow of fume   Limits of CO and CO   The indoor hygiene conditions should be ensured  The CO and  concentration inside the  CO  concentration in the air indoors shall not exceed the standard  room  referring to the Type A  5 3 4 4 code  The burning appliances should be equipped with a reliable  burning appliances  such as  cut off device for the excessive CO and CO  concentration  the flue free water heater and  indoors   heating appliances  etc    The energy effect and energy consumption of burning appliances  should meet the standard code  The con
27. ation Location  8 1 1 The following rooms and parts of a building may be installed with burning  appliances    a  Kitchen    b  Special room    c  Outdoors  external corridor  and unenclosed balcony  all of them should be  equipped with facilities sheltering from wind  rain and snow     8 1 2 The following rooms and parts of a building cannot be installed with burning  appliances    a  Rooms such as bedroom  living room and bathroom    b  Around stairs and safety exits  not restricted to the places beyond 5m     c  Places piled up with inflammable and explosive objects    d  Places with wires and electrical appliances    e  Liquefied petroleum gas  LPG  and LPG air mixture burning appliances  shall not be placed underground or partially underground    8 1 3 It is not suitable to install the burning appliances underground and in the  semi underground of a building  Conditionally restricted  the burning appliances  installed in the underground or semi underground of a building should meet the  following requirements    a  There should be hand operated and automatic mechanical anti explosion  ventilation devices underground or in the semi underground  There  should also be the installation of automatic alarm and cut off device for the  leakage of anti explosion gas and carbon monoxide  and the device should    interlock with the mechanical ventilation device     b  Safety measures underground  like anti explosion  pressure relief  and so on   should meet the requirements of GB 5
28. burning appliance products  The handling and  recycling charges for the scraped gas appliances historically left behind shall be  proportionally shared independently or through the joining of united fund plan by all  the producers during the happening of costs  The united fund plan should not  exclude the small output producers  importers and new producers  The handling  guarantee fund of the producers of burning appliance products should be a transparent  loan plan with a safe bank account   9 7 The third party reuse centre for the handling and recycling of the scraped gas  appliances refers to the approved and professional enterprise particularly engaging in  the handling  recycling  reuse and material recirculation of the scraped gas appliances   Within one year after each kind of new burning appliance product is released to the  market  the producer of the burning appliance product has to provide to the reuse  centre with the information of reuse and handling methods of the gas appliance  The  required information includes the environment friendly handling methods   maintenance  upgrading  renovation  reuse  etc  Meanwhile  the identification methods  of electronic  electrical components and materials  and the electronic and electrical  parts with hazardous and toxic substances or elements should be provided   9 8 Every year the industry association should make statistics on the kinds and    quantity of the collected  reused  recycled and recycled scraped gas appliances  
29. ctional shape of flue should be circular  square or rectangular   It should be in vertical direction  and has no narrow contracted mouth    e  Appropriate separation or heat insulation measures should be taken for the  flue and the inflammable material    f  When the common flue is adopted  only one heating hot water combi boiler  can be installed on each floor  and the total number of combi boilers shall  not exceed 6    g  In the main flue  there should be no mechanical air supply system installed    h  Under stable working conditions  the entire flue should be situated at a  negative pressure situation    i  At the bottom of the flue  there should be a collection chamber of solid  objects and condensed objects at a height below 0 5m with a sealed  metallic door    j  The wind cap of flue should meet the following requirements     1  The effective area of the wind cap outlet should be greater than the  cross section area of the flue    2  The wind cap outlet should avoid the wind pressure belt  positive  pressure zone     3  The wind cap outlet should avoid the entry of rain and snow   8 8 The indoor air exchange equipment  restricted to the open type and  semi closed type burning appliances only   8 8 1 General requirements  8 8 1 1 The fume produced during the burning of gas should be exhausted out of the  room through the natural air exchange or the mechanical air exchange  When the  natural air exchange cannot meet the requirements  mechanical air exchange should  be us
30. d  standard code    b  The burning chamber and the heat exchanger are seriously burned  or flame  leaks out of them    c  Water leakage  gas leakage  and the insulation is broken  causing power leak    d  After the electronic controller is inspected and repaired  malfunctions still    occur     8 Handling of accident    8 1 The handling of accidents related to burning appliances should be carried out  according to the regulations set out in Article 29 of Directive No 73 of the MOHURD      Measures for the Administration of Installation and Maintenance of Gas Burning  Appliances        When any units and individuals have found an accident of burning  appliances  they should immediately cut off the power  take the measures of  ventilation and fire prevention  and report the situation to the related authorities   According to the regulations of Directive No 10 of MOHURD     City Gas Safety  Administration Measures    and Directive 62 of MOHURD     City Gas Administration    Methods     the related authorities should investigate the accident  If the cause of the  accident is confirmed to be the installation and maintenance problems of the gas  burning appliances  the related authorities should ask the installation and maintenance  firms of the gas burning appliances to take handling measures according to the related  regulations       8 2 The first witness should retain the scene well  and immediately report the situation  to the related authorities for making on the spot investi
31. d be    nought for the left  live for the right  and  earth for the upper       Comments  The protective grounding can also be indicated by the sign in this   pattern      k   8 5 6 When the indoor temperature controller uses a 220V power source  the control  circuit should be separated from the power system  The temperature controller   whether shutdown or under working conditions  shall not affect the turning on of the  anti freezing function of the heating hot water combi boiler    8 6 Installation of indoor temperature controller  restricted to heating hot water combi  boilers only    8 6 1 The heating hot water combi boilers should be equipped with indoor  temperature time sequence controller    8 6 2 The installation location should meet the following requirements    a  In an area with a stable indoor temperature requiring concentrated heating   Indoor temperature controller can be installed on a well ventilated wall at a  distance of 1 2   1 5m from the floor  or the signal output box of  temperature controller can be placed in the area with temperature for  concentrated heating    b  It should not be installed around the door or window  where it might be  affected by a cold wind  or in a place affected by radiator or sunlight  radiation  or any area reachable by children    8 7 Connection of gas supply exhaust pipe  restricted to the closed type burning  appliances only    8 7 1 The connection and installation of gas supply exhaust pipe should meet the  requirements o
32. densed burning appliances  5 3 5 Reliable energy use  should fully avoid damage to the flue and other parts by the  condensed fluid   5 3 6 Temperature  Floor and neighbouring The surface temperature rise of the installed parts of burning  5 3 6 1  surfaces appliances should meet the standard code   The surface temperature rise of the control handle of burning  5 3 6 2 Control handle  appliances should meet the standard code   External surface of burning The temperature rise on the external surface of burning appliances  5 3 6 3  appliances has to meet the standard code   Safety of food and domestic   Materials that come into contact with food and domestic water  S3        water       shall not affect their quality  The temperature rise of water heater                in times of the stoppage of water supply  as well as the    temperature rise of the oven with ignitor during the ignition             period of ignitor should meet the standard code        6 Technical measures    6 1 Structure   6 1 1 The structure of burning appliances and their parts should consider safety and  durability requirements  such as the prevention of gas leaks  prevention of fire  etc   Under ordinary conditions for transportation  installation and use  the appliances  should not be damaged or deformed in a manner that would obstruct their use    6 1 2 The different parts should be accurate and flexible    6 1 3 When burning appliances are used after normal installation  there should be no  mobility 
33. der normal use must be  guaranteed  There should be no instabilities  deformations  leakages  wearing  cutting   or any other aspect endangering the safety of the overall structure and fittings    5 3 1 2 Condensed water produced in fumes when burning appliances are started or  are being used shall not affect the safety of burning appliances    5 3 1 3 In the case of fire occurring to the external part of the burning appliance  it    should be ensured that the structure  materials and sealing performance of the burning    appliances provide the most minimised risk of explosion    5 3 1 4 It must be guaranteed that the materials  structure and sealing performance of  which the burning appliances are made meet the requirements  and that water and air  do not enter into the appliances    5 3 1 5 When the auxiliary power is normally fluctuated  the safety work of burning  appliances should be ensured    5 3 1 6 When the auxiliary power is abnormally fluctuated  invalid or resumed  it  should be ensured that the burning appliances are under safe conditions    5 3 1 7 The burning appliances should have the necessary protection measures against  the potential harm of alternating current  AC  power  Burning appliances and fittings  using AC power should meet the safety requirements for low pressure electric  appliances    5 3 1 8 The design  assembling and strength of all burning appliance parts containing  pressure must meet the requirements  should be able to bear mechanical and th
34. e protection of gas system  cooker    Overpressure protection of hot water Enclosed type volumetric water heater and closed type  9  system heating system   10 Anti frozen protection Water systems  like water heater and heating appliances   Fume exhaust outlet of semi closed type water heater and  11 Flue block protection  heating appliances   12 Fume backflow protection of flue Semi closed type water heater and heating appliances   Burning appliances with anti shock protection grades being  13 Electrical grounding protection  Types I  II and MI   Anti explosion protection for flue of Semi closed type and closed type water heater and heating  14  firebox appliances   The air exchange fan and range hood attached to the  15 Fume lead out device  vertically placed stove and water heater  Installation place of burning appliances with nobody   s  16 Gas alarm and cut off device       supervision and the place with poor ventilation              6 3 2 Burning appliances for public use  commercial use  should be installed with    safety devices according to the technical needs of heating  The performance of    safety device should be able to meet the requirements of the related standards     6 4 Performance    6 4 1 Safety performance of burning appliances    a  Pressure resistance and airtightness   1  The airtightness and airtight force of gas system  restricted to automatic  valves only  should meet the specified requirements    2  The pressure resistance and airtightness of water
35. ed   8 8 1 2 The air exchange equipment inside a building should be selected according to  the type of burning appliance  type of building  and other conditions  The  performance and structural type of the air exchange equipment should satisfy the need  of gas exhaust  and meet the requirements of the related standards   8 8 2 Gas supply exhaust facility  8 8 2 1 The gas supply exhaust facility of the gas burning appliances for domestic use  should meet the following requirements     a  The mechanical air exchange facilities  such as air exchange fan  range hood     and so on  should be adopted  The wind pressure  static pressure  and   wind volume of air exchange facility should meet the following   requirements     1  The wind pressure  static pressure  should be greater than 80Pa     2  The wind volume should be confirmed according to the heat discharge  of the cooking appliances  When using the air exchange fan  the  wind volume should not be smaller than 40m   1kW  When using the  range hood  the wind volume should not be smaller than 30m   1kW    b  The installation of mechanical air exchange facilities  such as air exchange   fan  range hood  and so on  should meet the following requirements     1  The position of the gas exhaust outlet of air exchange fan should be  within 0 8m below the ceiling indoors  The gas supply inlet should  be at a suitable position indoors     2  The fume exhaust hood of the range hood should be installed at a  distance of less than 1m from 
36. embled as burning appliances  and these fitting  should simultaneously meet the corresponding standard codes of products    1 2 This Standard does not apply to industrial burning appliances designed for the  implementation of industrial procedures in an industrial site    1 3 The gaseous fuel indicated in this Standard refers to any gas state fuel under  the air pressure 101 3kPa and temperature 15  C  and the quality and type of fuel  should meet the requirements set out in GB 50028 and GB T 13611    1 4 Burning appliances indicated in this Standard as    under normal use    refer to  burning appliances that are used in the following situations    a  They are correctly installed according to the installation manual  and  correct maintenance is performed regularly    b  They are used in circumstances in which there is normal change in gas  quality and normal pressure fluctuation of the supplied gas    c  They are used correctly in accordance with the predetermined purposes of  burning appliances  or can be reasonably used correctly according to the    intended methods     2 Normative references    The provisions of the following documents become provisions of this Standard  after being referenced  For dated reference documents  all later amendments   excluding corrigenda  and versions do not apply to this Part  however  the parties to  the agreement are encouraged to study whether the latest versions of these documents  are applicable  For undated reference documents  the lat
37. equirements  specified in Subsection 5 of this Standard    3 3 Release onto the market and offer for use of burning appliances and fittings that  meet the requirements of Subsections 4 7 of this Standard should not be forbidden   restricted or obstructed    3 4 Burning appliances and fittings should meet the requirements of the related    national product standards  Only burning appliances and fittings that have been  inspected and meet the related national standards may be released onto the market and  circulated freely   3 5 When appliances and fittings endanger the safety of people  domestic animals and  properties under normal use  or if the safety performance of the appliances and fittings  is damaged  the related institutions should perform corresponding tests  Meanwhile   appropriate measures should be taken by recalling any problematic appliances and  fittings from the market  forbidding them and restricting them from being released  onto the market and offered for use  especially when the above problems are caused  by the following reasons    a  the appliances and fittings do not meet the requirements of the related   national standards   b  improper implementation of the related national standards     c  there are defects in the related national standards     4 Judgement procedures of conformance and inspection rules    The judgement procedures of conformance and inspection rules should be    implemented according to the regulations of CJ T 222     5 Basic requireme
38. ermal  stress  and should guarantee that no deformations shall happen to them to affect their  safety within their life cycle limit    5 3 1 9 When the safety  control and regulating devices of burning appliances  malfunction  it must be ensured that the burning appliances are turned off or running  under safe conditions    5 3 1 10 When the burning appliances are equipped with safety devices and control  devices  said devices must meet the corresponding product standards  and the  functions of the safety devices should not be affected by control and regulating  devices    5 3 1 11 The burning appliances should be positioned or regulated at the  manufacturing stage  Any parts that are not suitable for operation by user and fitter  must be locked or lacquer sealed  and identified by marks  Other protection measures  may also be taken  Non professionals shall not dismantle and regulate these parts   5 3 1 12 Clear markings and appropriate explanations for the handling and other  safety  regulating  control and positioning devices should be made  Avoid making any  error during this operation  The devices should be designed in a manner that prevents  the occurrence of faulty operation    5 3 2 Accidental release of gas   5 3 2 1 The airtightness  leakage  of the gas system of burning appliances should meet  the requirements  and the safety of burning appliances should be ensured    5 3 2 2 With regard to the procedures and structural design of burning appliances  it  should be en
39. est versions apply to this  Standard    GB T 13611 Classification and essential property of city gas   GB T 16411 Universal test methods of gas burning appliances for domestic use   GB 16691 Portable butane cookers   GB 16692 Butane cylinders for portable butane cookers   GB 18111 Gas storage water heaters   GB 50016 Code of Design on Building Fire Protection and Prevention   GB 50028 Code for design of city gas engineering   GB 50045 Code for fire protection design of tall buildings   CJ T 28 Chinese cooking gas appliances   CJ T 29 Water boiling gas appliances   CJ T 113 Gas fired space heaters for domestic use   CJ T 164 Domestic water saving devices   CJ T 187 Steaming gas appliances   CJ T 3030 Large gas cooker for cooking   CECS 215 Technical rules for application of gas fired heating hot water combi  boilers   CJ T 222 Quality assessment procedures and test rules for gas burning  appliances for domestic use   CJ T 228 Gas fired heating hot water combi boilers    3 Release on the market and free circulation   3 1 Burning appliances and fittings that meet the requirements of Subsection 1 of this  Standard should take all necessary measures to ensure that they will not endanger the  safety of people  domestic animals and properties under normal use  otherwise  they  cannot be released onto the market and offered for use    3 2 The standards of burning appliances and fittings that meet the requirements of  Subsection 1 of this Standard should support the applicable basic r
40. f product manual and the related national standards  The gas    supply exhaust pipe and its associated parts should be the original manufacturer   s    fittings  The coaxial pipe  detachable pipe  double head pipe   and its adaptor should  be applicable to the installation of equipment   8 7 2 The establishment of fume clear blade should meet the following requirements   a  The fume clear blade should be established according to the type and  maximum length of gas supply exhaust pipe as well as the requirements set  out in the manual   b  The specifications  dimensions and place of establishment of the fume clear  blade should be correct   8 7 3 The gas absorption fume exhaust outlet of gas supply exhaust pipe can be  installed on the wall  roof or flue  It is forbidden to insert the flue into the common  flue dedicated for the non closed type burning appliances   8 7 4 The length and resistance coefficient of gas supply exhaust pipe shall not be  greater than any one of the following numerical values indicated in the manual   a  Actual length  applicable to coaxial pipe    b  Equivalent length  applicable to detachable pipe    c  Resistance coefficient  applicable to coaxial pipe and detachable pipe    8 7 5 When the length of the selected gas supply exhaust pipe exceeds the allowed  maximum length  certain pipe sections should be changed to be the gas  supply exhaust pipe of larger diameter  The resistance of the pipe should be  guaranteed as not exceeding the maximum value
41. gation and sealing the burning  appliances    8 3 The handling of serious accident should be according to the related regulations   The related authorities should form an accident investigation team to carry out the  investigation and handling    8 4 When handling the accidents of burning appliances  there should be 4 technical  appraisement certificates issued for the accident according to the related regulations  and standards of burning appliances        Installation of burning appliances  ventilation for fume exhaust  and  airtightness of pipeline  please refer to normative Annex A         Use and maintenance of burning appliances  please refer to normative  Annex B         Supply quality of burning appliances  please refer to normative Annex C         Quality of burning appliances  please refer to normative Annex D     8 5 When inspecting the burning appliances of an accident  after the inspection  institution has removed the foreign matters from the burning appliances of the  accident  the following tests should be performed according to different accident  types    a  CO intoxication related accidents  the following performance should meet  the requirements clearly stated on the related standards of products         Airtightness of burning appliances       Flame stability       CO content in fume    b  Accident caused by gas leaks        When the gas inlet of burning appliances is under the air pressure of  4 2kPa  the leakage should be less than 0 07L h        Inspect
42. lent chrome   polybrominated biphenyls  PBB  and polybrominated ether  PBDE   etc         In the design and production processes  technical measures can be made  e g   change and study the design plan of product  adjust the technical  procedures  change the materials used  renovate the manufacturing  methods  etc  Provided that the requirements of product performance are  met  adopt harmless  non toxic or low harm  low toxic  easily degradable   recyclable and reusable materials  and fully consider the production  techniques that are favourable to the maintenance  possible upgrading   easy dismantling  easy reuse and recirculation of products        In the design  production  sale and import processes  indicate the names and  contents of harmful and toxic substances  and mark the environment  friendly age limit of products        In the sale and import processes  reject any sale and import of gas appliance  products and parts that are not meeting the requirements of this Standard   The producer should provide in the product manual the identification  information of the components and materials of the product  provide users  with the recycling and collection system of the useable scraped gas  appliances  tell users not to handle the scraped gas appliances as the  unclassified urban scraped objects  propagate to users their helpful action    in the handling  recycling  reuse and material recirculation of the scraped    gas appliances  and promote to users the existence of the p
43. lic of China      Measures for the Administration of Installation and Maintenance of Gas Burning  Appliances        The construction and administration supervisory departments of the    State Council are responsible for the supervisory management work of the installation    and maintenance of the gas burning appliances of the whole nation      The installation  maintenance  inspection and acceptance of the burning    appliances should meet the requirements of standard CJJ 12     7 Maintenance and scrap judgement of burning appliances    7 1 The maintenance company of burning appliances should meet the regulations of  Article 23 of Directive No 73 of the MOHURD     Measures for the Administration of  Installation and Maintenance of Gas Burning Appliances        The enterprises engaging  in the maintenance of gas burning appliances should be established by the producers  of gas burning appliances  or by the maintenance firms of gas burning appliances  established under the authorization of gas burning appliances producers     The  maintenance work should meet the regulations of Article 26 of    Measures for the  Administration of Installation and Maintenance of Gas Burning Appliances        The  firms engaging in the installation and maintenance of gas burning appliances should  establish a sound management system and a normalized service standard      7 2 When using the burning appliances  users should always observe and pay attention  to the situation of use  If there is any 
44. mercury  sexavalent chrome     GBA C polybrominated biphenyls  PBB  and polybrominated ether  PBDE  should not          exceed 0 1   and the content of cadmium should not exceed 0 01         10 5 The test methods for testing the toxic and hazardous substances in burning  appliances should be implemented according to SJ T 11365 2006    10 6 The identification requirements for the electronic information products in  burning appliance products and the pollution control of material as well as the  identification requirements for the environment friendly age limit should be  implemented according to SJ T 11364 2006    10 6 1 The pollution control marks of burning appliance products should be identified  according to the requirements of this Standard  The marks should be clear   identifiable and visible  cannot be easily faded  and cannot be easily removed    10 7 According to the regulations of    Measures for the Control of Pollution from  Electronic Information Products     the producers of electronic information products  and materials should clearly indicate the products with toxic and hazardous  substances or elements having entered the market of China  They should adopt the  ways of sticking labels and giving explanation on the product manual  telling users or  consumers the names  contents  environmental friendly age limit of the toxic and  hazardous substances or elements  whether they can be recycled when being discarded   the names of the packaging materials  and other i
45. n  fume exhaust and ventilation of gas burning   appliances  and airtightness of pipeline   Annex B  Normative Annex  Use and maintenance of gas burning appliances   Annex C  Normative Annex  Quality of gas supply    Annex D  Normative Annex  Quality of gas burning appliances    Foreword    This Standard is divided into GB xxxx 1 200X and GB xxxx 2 200X    All of the contents of this Standard are mandatory   GB xxxx 1 200X   This Standard is formulated according to the foreign regulations and standards  of the European Council Directive 90 396 EEC     Approximation of the Laws of the  Member States Relating to Appliances Burning Gaseous Fuels     English Version   and  the actual situation of gas burning appliances in China    This Standard replaces GB 16914 2003    Compared with GB 16914 2003  the major changes made to this Standard are  as follows        the stipulation    the conformance judgement procedures and inspection rules  should be implemented according to the requirements of CJ T 222    has been added       Table 1     Basic requirements  topical contents and the various corresponding  standard requirements     has been increased        Subsection 6     Technical measures    has been increased        Subsection 7     Conditions of selected type    has been increased        Subsection 8     Installation of equipments    has been increased        the    Corresponding subsection numbers of 90 396 EEC and technical  differences and their reasons    Have been deleted  
46. nd identification    of    The cock and temperature controller of burning appliances that  regulate and control the turning on and off and regulating of the    parts should be clearly identified and marked        9 3 2    Accidental gas release       5 3 2 1    Danger of gas leakage    The airtightness  leakage  of the gas system should meet the    related standard code        5 3 2 2    Danger of gas accumulation    inside burning appliances    The gas release after ignition  re ignition and flame    extinguishment should be restricted  There should be  fire extinguishment protection device installed  The installation  of valves for burning appliances should meet the requirements   and the structure of burning appliances should guarantee the  immediate dispersion of the released gas  For example  fire  cannot be ignited until the burner is exposed outside  the  ventilation hole is attached to the burner  and the door of oven is    opened           5 3 2 3       Danger of gas accumulation    inside a room       Indoor burning appliances should be equipped with    fire extinguishment protection device  For the burning    appliances equipped with no fire extinguishment protection             device  the place where they are installed should be equipped with  a gas alarm and cut off device  and kept sufficiently ventilated   After the sudden fire extinguishment of burning appliances     accidents should be prevented from occurring        The ignition  re ignition and long term n
47. nd the  fittings of gas burning appliances for domestic use  simply called burning appliances  and fittings   the responsibilities and obligations for the producers of burning  appliances  sellers of burning appliances  suppliers of gas  fixers of burning  appliances  and consumers of burning appliances  the installation  inspection and  acceptance of burning appliances  the use  upkeep  maintenance  scrap judgement and  accident handling of burning appliances  the handling  recycling  reuse and  recirculation requirements of the scraped gas appliances  and the limits of hazardous  and toxic substances as well as the pollution control for the electronic information  products and materials in burning appliance products    This Standard applies to the safety management of local and foreign burning  appliances and fittings using city gas as well as the judgement of responsibilities in    the cases of accidents   2  Normative references    The provisions of the following documents become provisions of this Standard  after being referenced  For dated reference documents  all later amendments   excluding corrigenda  and versions do not apply to this Part  however  the parties to  the agreement are encouraged to study whether the latest versions of these documents  are applicable  For undated reference documents  the latest versions apply to this  Standard    GB T 16411 2006 Classification of city gas   GB T 20000 4 2003 Guide for standardization     Part 4  Safety aspects for  thei
48. nformation relating to environmental  protection    10 8 The scope of electronic information products and materials required for  identification and explanation are shown in    Classified Commentary of Electronic  Information Products    edited by the classified index of electronic information  industries  which are confirmed by National Bureau of Statistics of China  The  burning appliances    controller  electromagnetic valve  electronic ignitor  piezoelectric  ceramic ignitor  switch of wind pressure  switch of micro drive  temperature and flow  sensor  relay  liquid crystal display  circuit board  microprocessor  integrated circuit   discrete component  wire  packaging material  and heat exchanger with lead  etc  must  clearly indicate any toxic and hazardous substances or elements     10 9 The environment friendly age limit of electronic information products refers to    the safe age limit of environmental quality  It only refers to the age limit in which the  electronic information products and materials containing toxic and hazardous  substances or elements would not cause any leakage or mutation  and would not  produce environmental pollution or bring serious damage to human body or properties   The environment friendly age limit is not equivalent to the age limit of safe operation   However  the environment friendly age limit can be the same age limit for the scrap  judgement of product  The production day of product is just the first day of the  environment friendly
49. nts    5 1 General conditions  5 1 1 The design and manufacturing of burning appliances should ensure that  when  they are under normal use according to Subsection 1 4 of this Standard  the operation  is safe and does not bring any danger to people  domestic animals and properties   5 1 2 The following manuals and warnings expressed in standard Chinese should be  enclosed with burning appliances that are to be released onto the market    a  Technical manual for fitters    b  User and maintenance manual for users    c  Special caution symbols  which should appear on both the burning appliances   and package    5 1 3 The technical manual for the fitter must include all explanations required for the  installation  troubleshooting and maintenance of the product  Such explanations  should ensure the correct installation  troubleshooting  maintenance  and safe  operation and use of the burning appliances    The manual should include the following contents     a  Type of gas used     b  Pressure of gas source used    c  Circulated fresh air required    1  Air supply required for burning    2  When the device specified in Subsection 5 3 2 3 of this Standard is not  provided with the burning appliance  the accumulation of any  dangerous unburned gas mixtures should be avoided    d  Dissipation conditions of the burning product    e  The performance and assembling of mechanical air blast burners and the  heating device installed with such burners should meet the applicable basic  requi
50. on grade   34 9kw   1  grades  colour   letters   1 23 3 0 67 Green A  2 29 1 0 83 Yellowish green B                                              3 34 9 1 00 Yellow C  4 40 7 1 17 Orange D  5 46 5 1 33 Red E             b  The rated heat load for the main fire of the large cooking stoves should be    52 3   58 1kW  and the energy consumption gradation should meet the    requirements of Table 10     Table 10 Energy consumption gradation of large cooking stoves                                  Energy Identification of Energy     Heat load Seer       Serial No  kw  consumption index   energy consumption   consumption grade    34 9kw   1  grades  colour   letters    1 46 5 0 80 Green A   2 52 3 0 90 Yellowish green B   3 58 1 1 00 Yellow C   4 64 0 1 10 Orange D   5 69 8 1 20 Red E             6 5 Quality evaluation of burning appliances for domestic use    6 5 1 Burning appliances that meet the quality standards of burning appliances for    domestic use can perform itemised scoring of burning appliances according to the    different performance indicators specified in Table 11     Table 11    the corresponding itemized scoring    Performance indicators of burning appliances for domestic use and                         Performance indicator  Itemized Way of  Evaluation item Water heater   scoring Stove verification  two purpose stove  Valve turned on and off  air Inspection  20 pressure 10kPa  no pressure Same as the left  reduction for   min  report  Airtightness of Valve turned
51. or direct access to outdoor space and with poor ventilation   there should be a compound alarm and cut off device in case of gas and  fume leakage    7 2 Conditions of burning appliances  7 2 1 Gas stoves for domestic use   a  The required wind volume  wind pressure  structural type and outlook  dimensions of stoves should be able to match with their range hoods    b  The embedded stove should match with the stove cabinet  which should  guarantee the air supply for once  The opening and closing of the door of  the stove cabinet shall not affect the stability of flame    c  Stoves should be equipped with ignition and fire extinguishment protection  device  Rice pots should be equipped with temperature control device   Portable stoves should be equipped with overpressure protection device    d  The heat load of the main fire of stove  including oven and baking apparatus   should be controlled within a range of 3 0   4 0kW    e  Each burner should be able to be ignited by matches and ignition rod    f  The status of burner should be easy for observation    g  The supporting frame of stove should be able to adapt to pan and wok  One  of the burners should be able to adapt to a pan at a diameter of 100mm   The strength of the supporting frame of stove should not affect its normal  use  When a net load of 100N is placed on the supporting frame of stove   no deformation or damage should be caused  When 500N horizontal  component force  canting pull at 40    is placed in the front pa
52. or inclination    6 1 4 The gas interface of burning appliances should be connected by the taper pipe  thread  which should be attached to a location available for easy connection    6 1 5 The specified valves of burning appliances should be possessed    6 1 6 The gas path should meet the following requirements    a  The airtightness of the gas path must meet the related standards  During  ordinary transportation  installation and use  its airtightness shall not be  damaged    b  The gas pipe should be installed in a location that will not overheat or  become corroded  otherwise  protection measures should be taken    c  The connections should be firmly connected by welding  thread  bolt  nut   screw  etc     6 1 7 The burners should be assembled according to the following requirements    a  Kindling burners  ignition burners   small fire burners  long term naked fire   and main fire burners should be firmly installed at the specified position   Ensure that they and the nozzle  burning chamber  electric ignition device   safety device  and so on are fixed at correct positions  and would not be  moved or fall down during ordinary use    b  With the exception of special parts of burning appliances  it is not suitable to  install them in overheated or damaged locations    6 1 8 Burning appliances should be confirmed as available for ignition in the  operation site of ignition through visual measurement  mirror  voltmeter  indicating  light  etc  Burning appliances with ignition 
53. ores   b  Grade B  2    class product   The total scores per item are greater than or  equal to 75 scores  and less than 90 scores   c  Grade C  3    class product   The total scores per item are greater than or  equal to 60 scores  and less than 75 scores   d  Grade D  passed product   The total scores per item are greater than or    equal to 30 scores  and less than 60 scores   7 Conditions of selected type    7 1 Supporting conditions  7 1 1 City gas  a  The types and basic properties of city gas should meet the requirements set  out in GB T 13611   b  The quality of city gas and the pressure fluctuation range of the supplied gas  should meet the requirements set out in GB 50028   7 1 2 Water supply and drainage    a  The quality  volume and pressure of the supplied water should satisfy the    need for the running of burning appliances   b  The drainage should satisfy the need for the running of burning appliances   7 1 3 Electrical conditions   a  The voltage  frequency and power should satisfy the need for the running of  burning appliances    b  There should be good grounding    7 1 4 Installation Location   a  The installation location of burning appliances should have gas  supply exhaust facilities that match the burning appliances and meet the  specified requirements  Gas and fume leaks in the running process of  burning appliances should not cause any harm to the environment    b  In the basement  semi basement  or the closed typed room without any door  or window f
54. otential threats   of hazardous and toxic substances in the scraped gas appliances against the   environment and health of human beings   9 4 When buying new burning appliance products  the users of the burning appliance  products are encouraged to return the scraped gas appliances to the burning appliance  producer free of charge on one to one foundation  The burning appliance producers  are liable to the charges for the handling  recycling  reuse and material recirculation of  the scraped gas appliances  The producers should be able to fulfil this obligation  independently or through the joining of united plan   9 5 If the producers of burning appliance products are able to be responsible for the  work of handling  recycling  reuse and material recirculation of the scraped gas  appliances independently  they are not required to join the united fund plan  As to  the producers of burning appliance products without these abilities  when they release  their burning appliance products to the market  they should provide a handling  guarantee fund of products  preventing the scraped gas appliances from being left  behind and passed over to other producers to take over the handling responsibility   9 6 The united fund plan of the handling  recycling  reuse and material recirculation of  the scraped gas appliances should be implemented by a third party reuse centre  organized by the industry association  or by a third party reuse centre after signing  contract with the producers of 
55. ottled liquefied petroleum gas 2800    0 5kPa                   Note 1  The liquefied petroleum gas pressure of flue is 0 75 1 5 pn     Note 2  Whether the liquefied petroleum gas pressure regulator is passed  please    refer to the requirements of the related standards              Annex D   Normative Annex     Quality of gas burning appliances    Table D 1 Quality of burning appliances                                                             Product Model Date or  Producer  Name No production  Conditions  Serial  Test Item Requirements of gas Conclusion  No   quality test  1 Meeting the requirements 2 3  Tempering of the related standards of  product   Meeting the requirements 1 2  Flame  Yellow flame of the related standards of  stability  product   Meeting the requirements 3 1  Staying away from flame of the related standards of  product   2 Flue free burning The CO content in fume 1 1  appliances  e g  stove  etc    should be less than 0 15    CO content in   Burning appliances with The CO content in fume 1 1  fume and safe   flue  e g  gas fired fast should be less than 0 20    cut off device   water heater  volumetric When the CO content in 0 2  water heater  two purpose   fume is less than 0 20   the  stove  etc  safety cut off device is cut   3 When the inlet of burning Air  appliances is under air  Airtightness pressure 4 2kPa  the  leakage should be less than  0 07L h   The accident of AC power  shock is investigated  Accident of AC power shock  according to the
56. pliances are sold  the age limit for the scrap  judgement of artificial gas water heaters is 6 years  whereas the age limit for the scrap  judgement of LPG and natural gas water heaters is 8 years  The age limit for the scrap  judgement of the burning appliances like stoves  steamers  Chinese cooking stoves   etc  is 8 years  The age limit for the scrap judgement of volumetric water heaters   two purpose stoves  condensed water heaters  etc  is 8 years  If the age limit for the  scrap judgement of products or fittings is specified by the related firms  the scrap  judgement is based on the statement of the firms  If the burning appliances or  fittings  such as the gas operated air conditioners  electromagnetic stoves  LPG steel  bottles  angle valves  LPG pressure regulators  burning appliances controllers   automatic electromagnetic valves  and so on  do not have any age limit of scrap  judgement specified  the age limit of scrap judgement is 10 years based on the related  regulations of Article 45 of    Product Quality Law  the People   s Republic of China      7 3 2 For burning appliances such as gas water heaters etc   when one of the following  malfunctions continues to occur after inspection and reparation  even if the age limit  of scrap judgement is not due  the burning appliances should be still be judged as  scrapped    a  The working conditions of the burner seriously deteriorate  After inspection  and reparation  the CO content in fume still cannot reach the relate
57. port made by the foreign test laboratory  provided that the  report  identification and the related environmental protection information are correct  and complying with the facts    10 12 Principally  the suppliers of the elements  components or materials purchased  locally or from foreign countries for production should undergo the marking and  identification of the related environmental protection information  If there is an  agreement or contract signed between the suppliers of the elements  components or  materials and the downstream producers  the suppliers of the elements  components or  materials need not perform the indication  However  the related environmental  protection information has to be transmitted to the downstream producers  The  downstream producers have to stick the labels on the final products  and give clear    indication on the manual of the final products     10 13 The parts or fixings of burning appliance products are composed of multiple  elements  components or materials  It is a combination of elements and components  with relatively independent functions  There is a great variety of the kinds of  electronic information products  so it is impossible to list out all the parts or fixings of  products  Hence  the producers are only required to make a concrete division by  following the habitual practice of the industry  It is only required to indicate the  contents of the toxic and hazardous substances or elements  and the related  information of the
58. r inclusion in standards   CJJ 12 2000 Rules for installation  inspection and acceptance of gas burning  appliances for domestic use   SJ T11363 2006 Requirements for Concentration Limits for Hazardous  Substances in Electronic Information Products   SJ T11364 2006 Marking for Control of Pollution Caused by Electronic  Information Products   SJ T11365 2006 Testing Methods for Regulated Substances in Electrical and    Electronic Products    3 Safety and environmental requirements of burning appliances and fittings    3 1 Under normal conditions of use  the burning appliances and fittings shall not  cause any hazard to the life and health of consumers  shall not create any loss to  properties  and shall not pollute the environment    3 2 Burning appliances and fittings should meet the safety performance and  environmental performance requirements of the related standards    3 3 The following aspects of safety of burning appliances and fittings should also be  noted        The gas quality used by burning appliances should be stable  The burning  appliances should be correctly installed and correctly used        When burning appliances and another kind of product are used together   hazards may arise        It should be made clear that the burning appliances are suitable to which  kind of consumers  The danger and dangerous nature of such products  should be particularly made aware with regard to children  the aged and the  disabled        The possible risks and the expected risk
59. re  should be a valve attached to the front part of the furnace    8 3 3 The gas pipe should meet the requirements of maximum input power  load  of  burning appliances    8 3 4 When the pressure of supplied gas is greater than 5kPa  independent pressure  regulator should be placed in front of the gas meter    8 3 5 The gas supply pipe of burning appliances is connected with the main pipe   The dimensions of the main pipe should be greater than the dimensions of the branch  pipe of burning appliances  The diameter of the connecting pipe between burning  appliances and gas meter should not be less than the diameter of the gas input pipe on  burning appliances  and should be confirmed according to the maximum discharge   length and allowed pressure loss of pipe    8 3 6 When using artificial gas  a filter or filtering net should be installed at the gas  inlet     8 3 7 The airtightness of gas pipe and valve should go through the 5kPa pressure test     During the inspection  the gas valve of burning appliances should be turned off  It is  prohibited to make an overpressure test that may possibly damage the gas valve of  burning appliances    8 4 Connection of water pipe  restricted to heating hot water combi boilers and water  heaters only    8 4 1 The diameter of pipe should not be smaller than the diameter of the connecting  pipe of the furnace body  The dimensions of the main pipe should be greater than  the dimensions of the branch pipes of the heating hot water combi boiler 
60. rements  A recommended assembling list should be provided at the  appropriate places by the production unit    f  Installation and troubleshooting methods for burning appliances    5 1 4 The user and maintenance manual should include all explanations required for  the safe use of the product  in particular explanations on the restrictions of its use   installation environment and ventilation requirements    5 1 5 The warning marks printed on burning appliances and their packaging must  clearly indicate the type of gas to be used  the pressure of the gas source and the  restrictions of use  in particular the installation environment and ventilation  requirements    5 1 6 In general  the designed and manufactured fittings of burning appliances must  be able to fulfil the predetermined purposes after they are assembled in burning  appliances according to the installation manual    The producers of the fittings of burning appliances must provide explanations   concerning installation  troubleshooting  operation and maintenance    5 2 Materials   5 2 1 The materials must be suitable for their intended purposes  and must be able to  sustain anticipated technical  chemical and high temperature conditions    5 2 2 The properties of the safety related major materials must be guaranteed by the  company that produced the burning appliances and the suppliers of materials    5 3 Design and manufacturing   5 3 1 General rules   5 3 1 1 The stability and reliability of burning appliances un
61. rise  Both the foreign enterprise and the seller should be responsible for  the safety of the burning appliances and fittings    4 2 3 During the selling process  the behaviours of the seller may affect the safety  performance of products  Hence  measures have to be taken to guarantee the safety  performance of products  The seller is obliged to tell the consumers which measures  they should take during the installation and use of the burning appliances and fittings   If necessary  the seller  together with the producer  should offer training  and make  investigation and interviews  so as to track  inspect and test the products  and study  the complaints about the safety of the products    4 2 4 If the burning appliances and fittings are confirmed to be safe products  and any  harm and loss is confirmed to be caused by the fault of the victim  or the fault of  another person deemed responsible for the victim  then the seller concerned can be    exempt from or may reject the related compensation responsibility     4 2 5 The seller is obliged to provide any relevant information to consumers  and  should especially provide information pertaining to hazards of the burning appliances  and fittings  enabling consumers to know of any possible foreseeable hazards during  the installation and use of the products  even if some are very small hazards    4 2 6 The sellers are obliged to assist the producers of burning appliances in the  recycling  handling  reuse and recirculation of the
62. rmation products and materials in gas burning appliance products    Annexes A  B  C and D of the Standard are normative annexes    This Standard was proposed by the Ministry of Housing and Urban Rural  Development of the People   s Republic of China    This Standard is under the central management of the North China Municipal  Engineering Design  amp  Research Institute  the residing unit of Urban Rural Gas  Standard Techniques under the Ministry of Housing and Urban Rural Development    The main drafting units of this Standard are  North China Municipal    Engineering Design  amp  Research Institute              The main drafters of this Standard are     GB xxxx 1 200X    Safety Technical Conditions for Gas Burning Appliances    1 Scope    This Standard sets the safety technical requirements for the release to market   free circulation  conformance judgement and basic requirements of gas burning  appliances  hereinafter referred to simply as burning appliances     1 1 This Standard applies to    a  Burning appliances that burn gaseous fuel for cooking  heating  producing  hot water  refrigeration  lighting or washing  and are required to have their  normal water temperature not exceeding 105  C  They also include  mechanical air blast burners and heating equipment installed with this kind  of burner    b  Safety devices  control devices  regulating devices and other components   simply called fittings  independently sold on the market  installed in  burning appliances or ass
63. rposes   5 2 Materials  No pollution shall be caused to water and food  The quality and  5 2 1 Properties of materials  thickness of materials should meet the requirements for its use   Certificates of guarantee for   The properties of the important safety related major materials  5 2 2  materials have to be guaranteed   53 Design and manufacturing  5 3 1 General rules  The materials  structure  strength  connection and fixing ways   5 3 1 1 Reliability and durability valves  flame detection device  etc  of burning appliances should  meet the related requirements   Condensation of fume The condensed water for fume exhaust shall not affect the safety  5 3 1 2  exhaust of burning appliances   The materials  structure and airtightness should meet the  5 3 1 3 Risk of explosion  requirements   The materials  structure and airtightness should meet the  5 3 1 4 Leaking water and air  requirements   When the auxiliary energy is under the conditions of normal  fluctuation  disconnection and resumption  the safety of burning  Normal fluctuation of  5 3 1 5 appliances should be guaranteed  and the functions of the safety  auxiliary energy  devices  control devices and regulating devices should meet the  specified requirements   When the auxiliary energy is under the conditions of normal  fluctuation  disconnection and resumption  the safety of burning  Abnormal fluctuation of  5 3 1 6 appliances should be guaranteed  and the functions of the       auxiliary energy       electromagnetic
64. rt of the shell  for 15 min   there should be no transient deformation of above 2 5mm  caused on the stove shell     h  Other requirements of the related standards     7 2 2 Gas fired fast water heaters for domestic use  7 2 2 1 Vertically placed  Type A  water heaters should meet the following  requirements    a  The rated heat load shall not be greater than 12kW    b  There should be an atmospheric environmental sensing device  When the CO  content in the air at the height 1 5m in a room installed with water heater is  greater than 0 01  and the CO   content is greater than 2 5   the gas  supply should be able to be reliably cut off    c  The fume exhaust temperature should be higher than the dew point  temperature by 15  C    d  There should be a 20 minute timer device    e  It should only apply to kitchen cleaning for a short while and intermittently   7 2 2 2 Semi closed type  Type B  water heaters should meet the following  requirements    a  There should be the installation of a gas cut off device in the case of  backflow fumes during working conditions as well as a flue block device  in case of disuse condition    b  When using air exchange fan and range hood for fume exhaust  the water  heater should be equipped with a linkage device interlocking with the fume  exhaust device  Its fume exhaust temperature should be higher than the  dew point temperature by 15  C    7 2 2 3 The closed type  Type C  water heaters should meet the requirements of the  related standards  
65. s out of wrong operation during the  use of burning appliances should be considered according to the  requirements of the standard  GB T 20000 4 2003        For burning appliance products as well as electronic information products  and materials in the products produced  sold and imported in the territory of  China  pollution and other hazards caused by such products to the  environment should be controlled and decreased  The contents of lead   mercury  cadmium  sexavalent chrome  polybrominated biphenyls  PBB   and polybrominated ether  PBDE  should be controlled  and the marking and  identification requirements should meet the requirements of this Standard        The handling  recycling  reuse and recirculation requirements of the burning  appliance products produced  sold and imported in the territory of China    should meet the requirements set out in this Standard   4 Responsibilities and obligations  4 1 Responsibilities and obligations of producers    4 1 1 The producers of burning appliances and fittings should comply with the related    safety requirements over the design  production and sale of burning appliances and    fittings  The products released to the market should be the safe products    4 1 2 Towards the foreseen behaviours that may affect the safety of products during  the sale  installation and use of products  protection measures have to be taken to  protect the safety performance of products from being damaged during the  abovementioned processes  e g  
66. smaller than or equal to    1 2mm                 10 4 Requirements for the limits of toxic and hazardous substances   The producers of burning appliance products should carry out the classification  of composing units for the parts and materials used by them according to Table 10 3 1   and should control the contents of toxic and hazardous substances according to the  requirements of limits indicated in Table 10 4 1  When performing supervisory  inspection  the supervisory inspection institution of burning appliance products should  dismantle the products to an extent that they meet the requirements of classification  specified in Table 10 3 1  and then perform the supervisory test to see if they meet the  requirements set out in Table 10 4 1     Table 10 4 1 Requirements of limits of toxic and hazardous substances          Requirements of limits  for those with the limit of quantity value   Kinds of Units          all units are expressed in weight percentage  wt              In this kind of composing unit  the contents of lead  mercury  sexavalent chrome   GBA A polybrominated biphenyls  PBB  and polybrominated ether  PBDE  should not    exceed 0 1   and the content of cadmium should not exceed 0 01         In this kind of composing unit  the hazardous substances of lead  mercury   GBA B cadmium  sexavalent chrome  polybrominated biphenyls  PBB  and  polybrominated ether  PBDE  should not be deliberately added           In this kind of composing unit  the contents of lead  
67. st shall not be less than 80 Pa  semi closed type compulsory  gas exhaust water heater   The position of the flue outlet in the case of  horizontal exhaust should meet the requirements of GB 50028     2  When using a common flue for the vertical exhaust  the structure of the  flue should ensure the juxtaposition of the main and branch flues  At  the interchange of the main and branch flues  there should be the  installation of an anti backflow fume device with reliable  performance  It is suggested to select the jet plate with eradiation  function  Venturi absorption device  and the reliable non return  one way valve  check valve  non return valve     With regard to the fume inlet  at the interchange of the main and branch flues   of the flue co used by several water heaters  the static pressure value when the water  heater is not used should be less than or equal to 0    8 9 Installation of the alarm and automatic cut off valve  8 9 1 The installation of the gas and CO concentration detection alarm should meet  the following requirements    a  When testing gas that is lighter than air  artificial gas  natural gas  and so on   and fume  the horizontal distance between the detection alarm and burning  appliances or valve should be within the range of 1 8m  The height of  installation should be within the range of 0 3m from the ceiling  The alarm  should not be installed above burning appliances  The distance between the  alarm and the door or window hole should be greater than
68. sured that following ignition  re ignition and flame extinguishment  the  release of gas is controlled and safely exhausted promptly  Avoid any risks that may    be caused by the accumulation of unburned gas inside the burning appliances     5 3 2 3 Indoor burning appliances should be equipped with fire extinguishing  protection devices  For burning appliances that are equipped without a  fire extinguishing protection device  the location in which they are installed should be  equipped with a gas alarm and cut off device  and kept sufficiently ventilated  so as to  prevent the accumulation of any unburned gases    The size and ventilation conditions of the location in which the burning  appliances are installed should be confirmed according to the properties of burning  appliances    5 3 3 Ignition   The ignition device of the burning appliances should belong to electric pulse  ignition  piezoelectric ceramic ignition  or equivalent  It should also be ensured that   under normal conditions  the ignition device should meet the following requirements    a  Ignition and re ignition are stable and safe    b  Cross ignition should be stable and safe    c  The safety of the burning appliances should be ensured if there is any   unsuccessful or accidental fire extinguishing    5 3 4 Burning  5 3 4 1 Ensure that the flame is burning stably when the burning appliances are in  normal use  Hazardous substances in the burning product shall not exceed the limit of  its concentration  For 
69. surface treatment  Aluminium and  1 0 1 0 1 0 3 0 1 0 1 0 1 5     aluminium alloy  Copper and copper  1 0 1 0 0 8 1 5 1 0 1 0 1 5     aluminium                                  Remarks  1  The water pressure of water storage tank  burning chamber and heat transfer tube should be smaller  than or equal to 0 3MPa   2  The steel material for surface treatment refers to the steel material having gone through    anti corrosion treatment  e g  enamelling           Table 3  Minimum nominal thickness of the water storage milling parts              0 3MPae Pe 0 6 MPa  mm  Carbon steel  aluminium Protective steel  stainless steel  copper  a b c a b c  4 0 3 0 2 9 2 0 2 0 1 0                         Remarks  1  The water pressure of water storage tank  burning chamber and heat transfer tube should be  greater than 0 3MPa   smaller than or equal to 0 6MPa   2  a  The wall of the burning chamber that has contact with water and fire  and the horizontal wall  on the surface of heat transmitter  water fire heat exchange  and so on    b  The rigid surface r that has contact with water  e g  the surface of the heat transmitter outside  the burning chamber  water water heat exchange  and so on      c  The pipeline of heat transmitter  cold  hot water pipes  and so on            Table 4 Minimum nominal thickness of the milled water storage parts   0 3MPae Pe 0 6 MPa  mm             Thin graphite cast iron  Spheroidal graphite cast  Rated heat load  kW          aluminium iron  cast iron  copper  
70. t according to  GB T 16411  and the pentane penetration per hour should be less than 5mg   c  Grease sealed material should perform gas resistant performance test  according to GB T 16411  and the quality change rate should be less than  10  at 20  C  and less than 25  at 4  C   6 2 4 The conduction material should be copper and the material possessing the  electrical performance  thermal stability performance and mechanical stability  performance should be copper alloy  stainless steel or above  With regard to the  necessary materials to be used at the portion requiring elasticity and at other portions   such restriction is inapplicable when there is no danger   6 2 5 The heat retaining and heat insulating materials of the gas path  burner and  electrical parts should perform gas resistant performance test according to GB T  16411  and should not be burned or should be extinguished within 10 seconds   However  such a restriction does not apply to the burning of heat retaining and    heat insulating materials if they will not cause the danger of shock or fire     Table 2 Minimum nominal thickness of the parts of burning appliances                            Water path Burning Heat Support   Panel and  Material Burner   Gas path transfer and  Pipe   Container   chamber tube frame shell  Cast parts 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0  Die cast parts 1 5 1 5 1 5 1 5 1 5 1 5 1 5 1 5  Stainless steel 0 5 0 5 1 0 1 0 0 5 0 5 1 0 0 5  Steel material for  1 0 1 0    1 5 1 0 1 0 1 5 0 8  
71. that are not confirmed must be installed  with the fire extinguishment protection device that meets the requirements     6 1 9 Burners  heat exchangers and other main parts should be able to be regulated or    changed    6 1 10 When in use or being cleaned  the sides and ends of the parts that may be  touched by the hands should be smooth    6 1 11 When cleaning or dismantling parts  the operation should be principally carried  out using common tools    6 1 12 The screws for assembling different parts should be firmly installed  Parts that  are dismantled during maintenance and inspection should be available for repeated  use    6 1 13 Burning appliances installed on walls  erected columns or on the floor should  be available for easy installation and dismantling  Ordinary piping operations shall not  cause any abnormal phenomenon  and should be installed firmly    6 2 Materials   6 2 1 The materials used on burning appliances should be able to bear mechanical   chemical and thermal actions under ordinary use and maintenance    6 2 2 With the exception of sealed objects  including the diaphragm  rubber valve  body  and grease sealed materials  the gas path and burner should be made of metallic  materials with a melting point greater than 500  C  the fume path should be made of a  non burning material with a melting point greater than 350  C  and should meet the  following requirements    a  Corrosion resistant metallic materials meeting the related standard code or  corrosion
72. the stove surface  with an ideal  distance of 0 8 0 9m  The gas supply inlet should be at a suitable  position indoors    The fume of the range hood can be horizontally exhausted through the external  wall  and can also be vertically exhausted through the building  The air shaft should  be equipped with a device preventing the backflow of fume and the tainting of odour   voltage change device or non return device  etc     8 8 2 2 The gas supply exhaust facilities of gas fired water heaters for domestic use  should meet the following requirements    a  The flue for natural fume exhaust should meet the following requirements     1  The draft  surplus pressure  should not be below 3 Pa     2  The fume temperature of the fume exhaust outlet should be greater than  180  C  and should be smaller than 260  C     3  The fume exhaust temperature of the chimney outlet should be higher  than the dew point of fume by above 15  C     4  When using the common flue  the structure of the flue should be in a  way that the main and branch flues are juxtaposed  The height of the  branch flue should be at floor height  and its net cross section area  should not be less than 0 015m     The net cross section area of the  main flue should be confirmed through calculation under the  prerequisite that the draft of flue is guaranteed    b  The flue for mechanical fume exhaust should meet the following   requirements      1  The static pressure at the wind machine outlet of the mechanical fume    exhau
73. ts     energy consumption gradation should meet following   1  The energy consumption gradation of the fast water heaters and the  heating hot water combi boilers for domestic use should meet the  requirements of Table 8    Table 8 Energy consumption gradation of gas fired water heaters    and heating hot water combi boilers for domestic use                                     f Water Heat Eneigy Identification of Energy  Serial A consumption consumption  discharge rate load   energy consumption  Ne  L min    kw  index rades  colour  grade  i OLmin 1    8  letters   1 5 and below 10 0 56 Green A  2 7 and below 14 0 78 Yellowish green B  3 9 and below 18 1 00 Yellow C  4 11 and 22 1 22 Orange D  below    5 13 and 26 1 44 Red E  below                2  The energy consumption gradation of the volumetric gas fired water  heaters and the heating hot water combi boilers for domestic use  should be confirmed according to the converted water discharge rate   L min   of heat load and the requirements set out in Table 8    6 4 5 Energy consumption gradation of Chinese cooking stoves and large cooking  stoves for public use  a  The rated heat load for the main fire of Chinese cooking stoves should be   29 1   34 9kW  and the energy consumption gradation should meet the   requirements of Table 9    Table 9 Energy consumption gradation of Chinese cooking stoves             Energy Identification of Energy    Heat load ae      Serial No kw  consumption index   energy consumption   consumpti
74. unsupervised burning appliances that are running continuously   there supervisory control should be established for its fume exhaust and the  concentration of its hazardous substances   5 3 4 2 For burning appliances equipped with flues  it must be ensured that  under  normal use  the structure  design and airtightness of the fume exhaust system should  meet the requirements and shall not leak   5 3 4 3 For burning appliances equipped with flues  necessary protection measures  must be taken to ensure that no backflow of fume appears under abnormal fume  exhaust conditions   5 3 4 4 Ensure that in the room using independent flue free heating appliances for  domestic use and flue free fast water heaters  the concentration of carbon monoxide   CO  should not exceed the related indoor environmental hygiene standard code   The burning appliances must have the supervisory control device of indoor CO  concentration and the corresponding gas cut off device  Ensure that within the  predetermined period of use of burning appliances  the health of people shall not be  endangered   5 3 5 Synthetic use of energy   Under the prerequisites that the technical level is fully reflected and the safety    factors are considered  the energy effect and energy consumption of burning    appliances should meet the related standards  Condensed burning appliances should  fully consider the avoidance of corrosion caused to the flue and other parts by the  condensed fluid   5 3 6 Temperature  5 3 6 1 For
75. urning appliances                Basic  Require  Topical Contents Requirements of Different Standards  ments  5 1 General conditions  When the burning appliances are under normal use  no danger  should be brought to people  domestic animals and properties   The burning appliances    adaptability to gas  the gas supply and  exhaust of burning appliances  the regulation  control and safety  5 1 1 Operation safety devices of burning appliances  the fixing and connection of  burning appliances  the materials and thickness of burning  appliances  the operability of burning appliances  the airtightness   heat flow volume  burning condition  etc  of burning appliances  should meet the requirements set out in the related standards                    Manual and special warning    a  Technical manual for fitters                                                     5 1 2 b  User   s and maintenance manual for users   marks  c  Dedicated warning marks  on burning appliances and package    Manual of installation Gas type  pressure  gas supply and exhaust  installation  5 1 3  techniques requirements  etc   Knowledge about the use and maintenances of burning  5 1 4 User manual  appliances   Warning contents on burning appliances and package  such as the  5 1 5 Special warning marks must read manual  gas type  pressure  gas supply and exhaust  and  so on   Fittings of burning The regulation  control and safety devices of burning appliances  5 1 6  appliances should reach the predetermined pu
76. y consumption   consumption grade   kw   3 5kw   1  grades  colour   letters   1 2 5 0 71 Green A  2 3 0 0 86 Yellowish green B  3 3 5 1 00 Yellow C  4 4 0 1 14 Orange D  5 4 5 1 29 Red E                         b  The energy consumption gradation of gas ovens should be confirmed  according to the effective capacity of ovens  The energy consumption  gradation of gas ovens for domestic use should meet the requirements set  out in Table 7     Table 7 Energy consumption gradation of gas ovens for domestic use                                           Energy Identification of Energy       Heat load ae      Serial No  kw  consumption index   energy consumption   consumption grade    3 0kw   1  grades  colour   letters   1 2 0 0 67 Green A  2 2 5 0 83 Yellowish green B  3 3 0 1 00 Yellow C  4 3 5 1 17 Orange D  5 4 0 1 33 Red E   6 4 4 Energy consumption gradation of gas fired water heaters and the    heating hot water combi boilers for domestic use  a  Water discharge limit of the water saving domestic water apparatus for civil  use  CJ 164 2002    Water saving domestic water apparatus        1  The water discharge of the water saving shower for bathing should not  be greater than 0 15L s  9L min      2  The water discharge of the water saving nozzle for cleaning should not  be greater than 0 15L s  9L min     b  The water discharge rate of the gas fired water heaters for domestic use and  the heating hot water combi boilers for bathing should be 7   9L min   The the    requiremen
    