        RXT20.1 Service terminal
         Contents
1.   EN 61000 6 2  EN 61000 6 3    89 336 EWG    NCS 0502 Y14R                                                             Operator controls RAL 7035  Excluding packaging 0 13 kg  R1  R1 RXT20 1 service terminal    A Connection to DESIGO RXB    A RXC controller or QAX     room unit  Bus PPS2 L B Bus connection   B 1 A RXC for RXT10 commission   Bus 7 ing and service tool  ca A5 orm RJ45 RXB for KNX   EIB bus    RXT20 1     Service terminal    CA2N3851en_02   12 01 2007  5 6    Pin layout of RJ45 12345678 1 LONWOoRKS    Bus  DESIGO RXC   CLA  EIB Bus  DESIGO RCB   CE   connector 2 LONWORKS    Bus  DESIGO RXC   CLB  EIB Bus  DESIGO RCB   CE   3  Notused  A 4     Not used  8 5 Not used  6     Not used  7 CP  PPS2 data  8 CP  PPS2 data    The same pin layout applies to the tool socket     Connection diagram The built in connecting cable with an RJ45 connector is used to connect the service  terminal to the tool socket of a DESIGO RXB   RXC controller  or to a QAX    room unit   The service terminal communicates with the controller via the PPS2 interface  Addition   ally  the bus is looped through the service terminal  RXC  this enables a PC for the  RXT10 service tool to be connected to the tool socket of the service terminal     A Caution  For correct operation of the service terminal  there must always be a room unit  connected to the controller  PPS2 communication is not possible without a room  unit        Options for connecting the RXT20 1 service terminal   1 To QAX    room un
2.  pin     Varies according to the DESIGO RX application  3 Controller ready for operation     run    and cycling cursor   Display Description  Normal operation between controller and room unit  run ican  e Display reads    run      The room unit with the set address  see Address switch  communi   Rie ease cates with the controller  The    run    display can be overwritten by  other displays  see Additional information    e Cycling cursor  1 s pulse  The controller communicates  or tries to communicate    no communication  or controller not ready  e Static display in all cursor fields  ll There is no room unit connected or the controller is not ready for  operation  but the power supply is working  controller in start up  phase  or no application loaded  or controller not configured    Faulty controller   e No display  The power supply is not connected or the controller is faulty   Additional information Display Description       r  J    Wink command    e Controller type displayed for 64 s  e g  RXC30 1     r 30     or RXB21 1   r 21    Press the right key  Function key 2  to switch back to the original  display before expiry of the 64 s  The display of the wink command  takes priority over all other display options on the service terminal     The wink command can be used during commissioning to identify  the currently addressed controller        RXC  see RXT10 user manual  document CA110338       RXB  see ETS user manual          ees                   Room temperature  operati
3. Interfaces  Cable connections    Housing protection standard  Protection class    Environmental conditions    Industry standards    Dimensions    Colour    Weight    Internal diagram    Building Technologies    Operating voltage  The service terminal receives its supply from the  connected controller via the PPS2 interface   SELV low voltage in accordance with HD 384   Power consumption  controller     Display  Type  Functions displayed    Function keys    Interface between controller and service terminal  Baud rate    Cable for connection to controller or room unit  Cable length    Protection standard to EN 60529  Insulation protection class    Operation  Climatic conditions  Temperature  Humidity  Mechanical conditions  Transport  Climatic conditions  Temperature  Humidity  Mechanical conditions    Electromagnetic compatibility  Interference immunity  Emitted interference   Meets the requirements for CE marking   EMC Directive    see    Dimensions       Housing cover    DC 12   15V  Max  0 10 VA  LCD        Controller and room unit status       Wink function       Additional information of the room unit       Function key 1  Error message display       Function key 2  Remote operation of service  pin and display of additional information of  the room unit    PPS2  point to point interface  Version 2   4 8 kBit s    Built in  Approx  15 cm    IP 30  Il    IEC 721  Class 3K5  0   50   C    lt  85  rh  Class 3M1  IEC 721  Class 2K3       25     70   C   lt  95  rh  Class 2M2  
4. SIEMENS 3      DESIGO    RX    Service terminal RXT20 1    Bu   er    Services d  Pin i    Hand held service terminal with built in connecting cable   Controller and room unit status display   Remote operation of DESIGO RXB and RXC room controller service pins  NOT SUITABLE FOR RXB VERSION 2 36 AND HIGHER   e Error message display   e Room temperature display  operating mode and temperature setpoint  adjustment   PPS2 interface to controller   Socket for commissioning and service too    Use The RXT20 1 service terminal is used for simple diagnostics of room controllers and  room units  and for remote operation of the DESIGO RXB and RXC controller service  pins  The built in connecting cable of the service terminal is plugged directly into the  roomcontroller to be interrogated  or into the room unit of the controller concerned     The service terminal displays the status of the controller and room unit  the    wink    func   tion  error messages or additional information of the room unit     The service pin of the connected DESIGO RXB   RXC controller can be operated re   motely with the function keys on the service terminal  This function is especially useful  for addressing controllers installed in concealed locations     The service terminal also incorporates a RJ45 socket for the bus      RXC  for RXT10 commissioning and service tool  LONWORKS   bus connection       RXB  for KNX   EIB bus connection  not for Version 2 36 and higher      Ordering When placing an order  ple
5. ase specify the quantity  product name and type code   Example   1 Service terminal RXT20 1   Mechanical design Essentially  the service terminal consists of the housing  the base plate and the cable for    connection to the controller or room unit  The housing and the base plate are connected  by a snap fitting mechanism     Building Technologies RXT20 1     Service terminal CA2N3851en_02   12 01 2007  1 6    Elements for operation  and display    Function key 1     Function key 2     CA2N3851en_02   12 01 2007  2 6    The housing accommodates a printed circuit board  the function keys  LCD and a socket  for the commissioning and service tool     Connecting cable    Base plate    Housing    SIEMENS    Service    Pin    Lands  amp  Staota       Action  Press   or     key    Action  Press left key    Service  pin    Press right key             K j    Socket for RXT10 commis   sioning and service tool                                  90044 A    Displays room unit status     wink    function  error messages or additional  information of the room unit    Function key 1  Error message display    Cursor  Controller status indication    Function key 2  Displays remote operation of service pin and additional  information of the room unit    Description   Press once to display any existing error messages   The error with the highest priority is displayed for 5 s   For error codes see    LCD display       Description    The service pin is used to address the controllers when commis   s
6. ioning the system        RXC  refer to the RXT10 user manual  document CA2110338      RXB  refer to the ETS manual    This function of the service terminal is especially useful for ad   dressing controllers in concealed locations where direct access to  the service pin is difficult  For this purpose  the service terminal is  connected to the room unit of the controller concerned    Press this key on the left side for at least 1 5 s for remote opera   tion of the service pin of the connected DESIGO RXB   RXC con   troller    While service pin operation is in progress  the LCD display is  blank  The controller  room unit and service terminal will then re   start  ready for operation after approx  3     5 minutes       Varies according to the DESIGO RX application    1  key press Room temperature display in   C   2    key press Room temperature display in   F   3  key press Setpoint adjustment display in   C  4  key press Setpoint adjustment display in   F  5  key press Return to original display  e g     run        RXT20 1     Service terminal Building Technologies    LCD display If the service terminal is connected to a DESIGO RXB   RXC controller  the start up rou                                                                             Response at start up tine is as follows   Step Description  1 All segments activated for approximately 5 s   2 Cursor fields may be activated for max  10 s    approx   3    5 minutes   on controller power up  e g  after operation of  service
7. it  2 To RXC    room controller  3 Not possible without QAX         Dimensions All dimensions in mm                                                 Q  2  y  32   lt    _   34   lt  gt      2000   2007 Siemens Switzerland Ltd  Subject to change  CA2N3851en_02   12 01 2007 RXT20 1     Service terminal Building Technologies    6 6    
8. on mode  e Room temperature in   C or   F  see  Function key 2         OMESESES The displayed operation mode  Stand by  Auto  fan speed  comes  from the room unit   The same applies to the displayed room temperature  there is no tem   perature sensor in the service terminal itself   Building Technologies RXT20 1     Service terminal CA2N3851en_02   12 01 2007    3 6    Static error messages    Dynamic error mes   sages    Room temperature    Address switch    Note    Disposal    psd    CA2N3851en_02   12 01 2007       z T g   Temperature setpoint  cee e Temperature setpoint in   C or   F  see  Function key 2         The displayed temperature setpoint comes from the room unit        Display Description    The address of the service terminal has not been set correctly  see     Hex switch            Dynamic error messages are displayed for 5 s when they occur  The error message  remains in memory while the error persists  The message can be re displayed for 5 s  using Function key 1  If there is more than one error  the error with the highest priority  will be displayed  The table below shows the error messages in order of priority     Display Description       F IS There has not yet been any communication between the room unit and  the controller  e g  during the controller power up phase             l    The controller does not recognise the room unit type        ra  oo    C  Communication between controller and room unit is interrupted   02  Firmware version of the service te
9. rminal  e g  Version 2 0     ca  mo       Error  open circuit or short circuit  affecting the potentiometer or tem   perature sensor of the connected room unit     om          Display Description    elas    Room temperature in   C or   F  see    Function key 2        The displayed room temperature is the temperature measured by the  room unit  there is no temperature sensor in the service terminal itself        The service terminal must have the same PPS2 address as the room unit  address  1    12  in order to display any of the information described above  The QAX3    room  units are all factory set to Address 1  The service terminal is also factory set to Ad   dress 1     The address can be changed if necessary       Service terminal  hex switch on the back of the housing  remove base plate for access      Room unit  Address plugs     If an invalid address is set  e g     O      the error message    E16    will be displayed     If the address of the service terminal and the room unit are not the same  or if several  devices are communicating  the  normal operation    display will show 12 extra points   one for each possible address   The points that stand for actively communicating de   vices are flashing     The device includes electrical and electronic components and must not be disposed    of as domestic waste     Current local legislation must be observed     RXT20 1     Service terminal Building Technologies    4 6    Technical data    Power supply    Function data    
    