Home
        User Manual - Metrix Electronics Ltd
         Contents
1.        HYSt     e  d       OFFS          SEnS       e       t on          toFF                unit       36    threshold is accessible when    modE    parameter is set to    in    or    out    value   Threshold is the medium value of relay hysteresis       hysteresis of relay  range 0   999   Full hysteresis of the relay is equal to 2 times     HYSt    parameter  The relay state can change when an input signal is out of  threshold hysteresis to threshold hysteresis zone     Presented parameters should be set to ensure that    SEtP         HYSt         SEt2         HYSt        SEtP        HYSt    or    SEt2        HYSt    does not exceed the  measure range  Additionally  in two threshold mode     modE        in    or    out       the hysteresis for both thresholds must not cover each other  in other case relay  can t change his state        LEDs light when relays are closed  independently of relays  mode     When power supply fail  unit do not store relays state selected by RS 485  interface       this parameter specifies the difference between the setpoint value to the controller  and the signal measured by the device  which will cause an output response to that  signal       this parameter specifies what percentage of the controller s output status must be  achieved in order for the output to react to the status of the controller     In a situation where the parameters  OFFS  and  SEnS  are other than zero  the  controller only responds to the signal when the conditions desc
2.       User manual   CONTROLLER PUR 94       4  DEVICE INSTALLATION    The unit has been designed and manufactured in a way assuring a high level of user  safety and resistance to interference occurring in a typical industrial environment  In order to  take full advantage of these characteristics installation of the unit must be conducted correctly  and according to the local regulations     AY   Read the basic safety requirements on page 3 prior to starting the installation       Ensure that the power supply network voltage corresponds to the nominal  voltage stated on the unit   s identification label       The load must correspond to the requirements listed in the technical data     All installation works must be conducted with a disconnected power supply       Protecting the power supply connections against unauthorized persons must be  taken into consideration        4 1  UNPACKING    After removing the unit from the protective packaging  check for transportation damage  Any  transportation damage must be immediately reported to the carrier  Also  write down the unit  serial number located on the housing and report the damage to the manufacturer     Attached with the unit please find     users manual      warranty      assembly brackets   2 pieces     4 2  ASSEMBLY       AN   The unit is designed for mounting inside housings  control panel  switchboard   insuring appropriate protection against surges and interference  Metal housings  must be connected to ground in a way t
3.      current output enabled with 4   20 mA mode    modb    current output controlled via RS 485 interface     For active voltage output      oFF    voltage output disabled    0 5    voltage output enabled with 0   5V mode    1 5    voltage output enabled with 1   5V mode    0 10    voltage output enabled with 0   10V mode      2 10      voltage output enabled with 2   10 V mode    modb   voltage output controlled via RS 485 interface    OUtL     this parameter determines the input value for which the output signal is minimal     depend of output mode    Omod          OUtH     this parameter determines the input value for which the output signal is maximal   depend of output mode  Omod       The analogue output value is calculated due to formula given below       1  W  OUtL   Qut TOU     OUL  X  B 4   A       where  W   displayed value   Out     analogue output value   B   higher range limit  20mA   5V   10V    A     lower range limit  OmA   4mA   OV   1V   2v         OutL    parameter can be greater than  OutH   In this case the conversion  characteristic is reversed  it means that if input value raises the output value falls      Lor   Hir   this parameters define the output value range  If calculated output value Out  exceeds defined range then analogue output generates signal equal to upper  or lower border of the defined range  These parameters defines the percentage  extension of nominal analogue range  with 0 1  resolution      Parameter  Lo r  defines lower border of t
4.   63    User manual   CONTROLLER PUR 94                                                                                                    Register   Write Range Register description  a Re er   A e  5Dh Yes 022 NURSE  only when rEL3 is relay output   0  5Eh Yes    999   9999      SEt2    parameter in  rEL3  menu  no decimal point included  5Fh Yes    999   9999      InLo    parameter in  rEL3  menu  no decimal point included  60h Yes    999   9999      InHi    parameter in    rEL3    menu  no decimal point included  61h Yes 0 9999    PEri  parameter in    rEL3    menu  no decimal point included  62h Yes 079999     H on    parameter in    rEL3    menu  no decimal point included  63h Yes 0  9999    HoFF    parameter in    rEL3    menu  no decimal point included  64h Yes 0 1 o ru aaa   d rEL3 is OC type output    65h Yes 0 1000    duty    parameter in    AL    menu  only when rEL3 is OC type output   66h   Yes   0  1000 _   the decimal point  only where FEL3 isthe OC ype output  o  67h Yes    999   9999      OFFS    parameter in    rEL3    menu  no decimal point included  68h Yes 0 1000      SEnS    parameter in   rEL3    menu  no decimal point included   Sour  parameter in    rEL4    menu   8h  xem 0 3 0  InPU  option  1      modb    option  2    PidH  option  3    PidC   option    modE  parameter in    rEL4    menu   6Ah Yes 0 5 0      noAC    mode  1      on    mode  2      oF F    mode  3      in    mode   4      out    mode  5      PULS    mode  6Bh Yes    999   9999      S
5.   80h Yes 021  modE  parameter in  HOLd  menu  type of detected changes    0   peaks  1   drops  81h Yes 0   9999  PEA  parameter in  HOLd  menu  minimum detectable change  no  decimal point included   82h Yes 0  199  timE  parameter in  HOLd  menu  maximum peaks   or drops    display time expressed in seconds     HdiS  parameter in    HOLd    menu   E AC 0 1   Q0  rEAL  mode   1      HOLd    mode  R  H r1  parameter in  HOLd  menu      W    Yes 0 1   g  rEAL  mode   1      HOLd    mode  B  H r2  parameter in  HOLd  menu   en 0 1   0  rEAL    mode   1      HOLd    mode     H r3  parameter in  HOLd  menu     w pres 0 1   0  rEAL  mode   1      HOLd    mode     H r4  parameter in  HOLd  menu   M  0 1   Q0 rEAL  mode   1      HOLd    mode  A    HOUt    parameter in    HOLd    menu   EA R  0 1   0  rEAL  mode   1      HOLd    mode  Ah Yes    999   1999 The value of X coordinate of point no  1 of the user defined  characteristic  expressed in 0 196  A1h5 Yes    999   9999 The value of   Y    coordinate of point no  1 of the user defined  characteristic  no decimal point included  A2h     C5h5 Further pairs of    X         Y    coordinates of points no  2   19 of the    user defined characteristic  C6h5 Yes    999   1999 The value of X coordinate of point no  20 of the user defined  characteristic  expressed in 0 1   C7h5 Yes    999   9999 The value of S   coordinate of point no  20 of the user defined  characteristic  no decimal point included   OSou  parameter in    OutP    menu 
6.   DOh Tak 0 3 0    InPU  option  1      modb    option  2    PidH  option  3    PidC   option                   65    User manual   CONTROLLER PUR 94                                                                                     Register   Write Range Register description   Omod  parameter in    OUtP    menu  active current output mode   Yes 0 3 0   current output disabled  1   current output enabled with 4 20mA  mode  2   current output enabled with 0 20mA mode      Omod    parameter in  OUtP  menu  passive current output mode   Yes 0 2 0   current output disabled  1   current output enabled with 4 20mA  D1h  mode    Omod  parameter in    OUtP    menu  active voltege output mode   0   voltage output disabled  1   voltage output enabled with 0 5V  Yes 0 5 mode  2   voltage output enabled with 1 5V mode  3   voltage  output enabled with 0 10V mode  4   voltage output enabled with  2 10V mode   D2h  Yes    999   9999      OUtL    parameter in    OUtP    menu  no decimal point included  D3h  Yes    999   9999      OUtH    parameter in  OUtP  menu  no decimal point included  i    Lo r    parameter in    OUtP    menu  for active current output and  Yes 0   999     e  Bini active voltage output  expressed in 0 196  z  Lo r    parameter in    OUtP    menu for passive current output   YES iius expressed in 0 196  Yes 0   199  Hi r  parameter n M menu for active and passive current  output  expressed in 0 1   ER H OUtP f    R  Hi r    parameter in       menu for active voltage ou
7.   as a percentage  that is to be forced on  the output at the time of an alarm  regardless of the state of the source value     31    User manual   CONTROLLER PUR 94       Minimal  Output D  50  on and off  plato 4 time                gt  Time  s        PEri   200    Figure 6 14  An example of the progress of an OC type PWM output signal in PULS mode    7  DEVICE PROGRAMMING    The device menu allow user to set all parameters connected to operation of  measurement input  control modes  critical situations behaviour  communication via RS 485  and access settings  The meaning of the particular parameters is described in paragraph  MENU DESCRIPTION    Some of the parameters can be accessed without menu entering  quick view mode    After pressing     or  v  button  name of the threshold  e g  rEL1   and his value will be  displayed on the display in alternating mode  If     or  v  will be pressed in 5 sec again  the  next threshold will be displayed  else the device comes back to the measurement mode  If a  free access is enabled  see description of  SECu  menu   user can change the value of  particular threshold pressing button  ENTER   see  PARAMETERS EDITION      If particular parameter has been changed and confirmed in quick view mode  its   Gi  new value is displayed in alternating mode with parameter name by few seconds   Confirmed changes may be checked or user can switch viewed parameter pressing   4  or  v  button     7 1  PROGRAMMING MENU       To enter main menu  being
8.   modE   in E MEME  Ir  pi ny LG  ton   0     closed   ioi i   I   id      toFF  0  L fon EX  H  ER i RB J bd BEEN time  c  relay state 4 m   WE   a   E        modE   out   I GC         ton   0    toFF   0  em  relay state 4 5d bod I E T bord  d   mek n        P 1 IRE   ton  gt  0 I   i closed po   I   I  toFF  gt  0  i       E met KASKA  ve tein ame  e  relay state 4    t on    parameter G        toFF    parameter    t on  parameter       modE   out bd   paf   i   closed   i a  ton  gt  0            pn Fi        toFF  gt  0        i   Y   Ld   I vt i E wr  time   toFF  parameter    t on  parameter    toFF    parameter  Obja  nienie   A B C D E   points where measured signal exceeds border values  expected value   allowed deviation   Bon    Borr    Con    Corr    Eon  Eorr   relays state changes moments   for    t on     gt  0     toFF     gt  0   ta  ts  te   to  te   time periods while input signal is in zone A or zone B    Figure 6 12  Principle of LED relay output operation for two thresholds mode    29    User manual   CONTROLLER PUR 94       Figure 6 12 presents the principle of relay outputs operation for two thresholds mode   and an example values of other parameters  In this mode parameter    SEt2    is accessible in  common with    SEtP     this parameter describes a second threshold of the relay output  The  parameters    HYSt        modE        ton        toFF        unit    and    AL    are connected with both     SEtP    and    SEt2    thresholds  While the cont
9.  OFF       one threshold mode  the relay is turned OFF when input signal exceeds  SEtP   HYSt value  and is turned on back when the input signal became  lower than SEtP     HYSt       in      two threshold mode  the relay is turned ON when the input signal is  bigger than    lower threshold   HYSt    and lower than    bigger threshold      HYSt     and turned off when the input signal is contained in the second  zone  The bigger threshold means bigger one of    SEtP    and    SEt2     thresholds  the lower threshold    means lower one of    SEtP    and     SEt2    thresholds       out      two threshold mode  relay is turned ON when the input value is bigger  than  bigger threshold   HYSt  and lower than  lower threshold      HYSt     and turned on when the input signal is contained in the second  zone  The bigger threshold means bigger one of    SEtP    and    SEt2     thresholds  the lower threshold means lower one of    SEtP    and    SEt2     thresholds       PULS      available only for OC type output  Turns on PWM mode for OC type  output       first threshold of the relay  range  999   9999   Negative values can be input by  selecting a  7 sign on first digit  to change value use     and  v  buttons    Threshold is the medium value of relay hysteresis       second threshold of the relay  range  999   9999   Negative values can be input  by selecting a         sign on first digit   to change value use     and  v  buttons   This    35    User manual   CONTROLLER PUR 94  
10.  PH  Y  PL            W    1  x  X  PH   x PL     100  Y PL    8  80   30  T       0 375   0 3  x  40 30  100   302 67    b  lin   2 5 mA and I     0 0938  because of the normalized    value is lower than O  the  segment defined by X1 and X2 will be selected  X1 PL    0  Y1 PL     50  X2 PH    10   Y2 PH     30 and      0  For these values the displayed value W    69     C  lin   20 5 mA and      1 0313    because of the normalized    value is higher than 1  the  segment defined by X10 and X11 will be selected  and X10 PL    90  Y10 PL    900   X11 PH    100  Y11 PH    820 and l    0 9 for these values the displayed value W   795     Example 7  Current output value calculation   Lets assume that we have active current output and its parameters are       modE         4 20      OUtL    100   OUtH  2 200     Lor    5 0   Hir    5 0  Parameters  Lo r    and  Hi r    define working range of current output to 3 8   21 mA   Output current will be calculated for three displayed values    D        a  D      17 5       According to formula from page 42   lout    17 5 10 0     20 0 10 0  x 16 mA   4 mA   0 75  16   4   16 mA    58    User manual   CONTROLLER PUR 94       Calculated l   do not exceeds the output working range  3 8   21 mA      b  D  20 5     According to formula from page 42    lout    20 5 10 0     20 0 10 0  x 16 mA   4 mA   1 05  16   4   20 08 mA  Calculated Lu do not exceeds the output working range  3 8   21 mA      c  D     30 0     According to formula from page 
11.  around the setpoint is a natural behaviour     Auto tuning   If the user does not know the dynamic parameters of the controlled system  and is unable  to select the suitable controller coefficients or simply doesn   t have the time or patience  the  controller auto tuning system included in the device can be used instead    Thanks to auto tuning  the controlled system is identified and controller settings are  selected using the Ziegler Nichols method  which involves measuring the set oscillation  parameters of the system  The auto tuning process is divided into three phases  during which  no device settings can be changed  and after their completion the device automatically  switches to operation in the Pid mode  The duration of the auto tuning process depends on the  properties of the controlled system     processes  because auto tuning may damage the products manufactured in the    During auto tuning  the user is warned against regulating the actual technological  process     25    User manual   CONTROLLER PUR 94       There are 3 auto tuning modes available  as a result of which the settings of one of the  controllers will be selected     The At F mode    Auto tuning using both the controller s control loops  At F mode   during which two  outputs of the device are controlled by two controller loops  In this process  the device  determines  based on the setpoint and the measured value   which loop is to be tuned  The  second loop receives the same settings  When the setpo
12.  automatically sets up in the PiD operating mode   the modE parameter in the CtrL menu  and the calculated settings of the PID H controller s  loop will be stored in the appropriate parameters     59    User manual   CONTROLLER PUR 94       11  THE MODBUS PROTOCOL HANDLING    Transmission parameters  1 start bit  8 data bits  1 or 2 stop bit  2 bits are send  1 and 2 bits  are accepted when receive   no parity control  selectable from  1200 to 115200 bits second    Baud rate   Transmission protocol     MODBUS RTU compatible    The device parameters and display value are available via RS 485 interface  as HOLDING   type registers  numeric values are given in U2 code  of Modbus RTU protocol  The registers   or groups of the registers  can be read by 03h function  and wrote by 06h  single registers  or  10h  group of the registers  accordingly to Modbus RTU specification  Maximum group size for  03h and 10h functions can not exceeds 16 registers  for single frame      a The device interprets the broadcast messages  but then do not sends the answers     11 1  LIST OF REGISTERS                                              Register   Write Range Register description  01h No    999  9999  Measurement value  no decimal point   Oh  AOh  60h The status of the measurement  Oh   data valid  AOh   top border of    i     the measurement range is exceeded  60h   bottom border of the  02h No COh  10h      RAA  20h measurement range is exceeded  COh   sensor failure  10h   error  of user char
13.  current number of points of the user defined   characteristic is displayed for about approx  1 5 sec  After that device waits for  selection of point being deleted  by       v  buttons   The short pressing of  ENTER   button causes by switching between X and Y value of the displayed point  The long  press  press and hold at least 2 sec  of  ENTER  button causes by displaying      dEL     ask  If  ENTER  button is pressed again  current point is deleted and new   updated number of points of the user defined characteristic is displayed       this option allows user to modify of particular point of the user defined  characteristic  After selection current number of points of the user defined  characteristic is displayed for about approx  1 5 sec  After that device waits for  selection of point being edited  by       v  buttons   The short pressing of  ENTER   button causes by switching between X and Y value of the displayed point  The long  press  press and hold at least 2 sec  of  ENTER  button causes by entering to edit  the selected coordinate of the point  Modification of the coordinates is done  accordingly to numerical parameters edition      AddP    dELP  and  EdtP  options are available only if the user defined  characteristic is used  it means when parameter  CHA    USEr        Lo r    Hi r    these parameters define the expansion of nominal range in percent  They    40    determine the permissible range of input signal  Figure 7 1      The permissible range allow user
14.  delay of relay R1 0 0 36  unit Unit of    t on        toFF    parameters of relay R1 SEC 36  InLo The lower limit of the PWM range of relay R1 0 0 37  InHi The upper limit of the PWM range of relay R1 100 0 37  PEri Relay R1 output signal period 1 0 37  Hon Low state minimal time of relay R1 PWM signal 0 0 37  HoFF High state minimal time of relay R1 PWM signal 0 0 37  AL Reaction for critical situation of relay R1 oFF 37  OFFS Relay R1 output offset 0 0 36  SEnS Relay R1 output sensitivity 100 0 36  Parameters of relay R2 operation     rEL2    menu   Sour Relay R2 signal source InPU 35  modE Operation mode of relay R2 on 35  SEtP Relay R2 threshold 20 0 35  SEt2 Relay R2 second threshold 40 0 35  HYSt Hysteresis of relay R2 0 0 36  ton Turn on delay of relay R2 0 0 36  toFF Turn off delay of relay R2 0 0 36  unit Unit of  t on    toFF  parameters of relay R2 SEC 36  InLo The lower limit of the PWM range of relay R2 0 0 37  InHi The upper limit of the PWM range of relay R2 100 0 37  PEri Relay R2 output signal period 1 0 37  H on Low state minimal time of relay R2 PWM signal 0 0 37  HoFF High state minimal time of relay R2 PWM signal 0 0 37  AL Reaction for critical situation of relay R2 oFF 37       70       User manual   CONTROLLER PUR 94                                                                                                                   Parameter Description Default value User s value pecs  OFFS Relay R2 output offset 0 0 36  SEnS Relay R2 output sensitivity 
15.  error check  Hi and Lo byte     ADDR  FUNC   REG H L  COUNT H L  BYTE C  DATA H L  CRC LH    1  Read of the displayed value  measurement   PUR 94 device address   01h        ADDR   FUNC    REG H L    COUNT HL    CRC LH       01 03             00 01    00 01       D5 CA          a  The answer  we assume that the measure result is not out of range         ADDR   FUNC    BYTE C    DATA H L    CRC L H                01 03    02       00 FF          F8 04          DATA H  L   displayed value   255  no decimal point     Decimal point position can be read from reg  03h     b  The answer  if an error occur         ADDR   FUNC    ERROR    CRC L H       01 83             60    41 18                ERROR   error code   60h  bottom border of the measurement range is exceeded    2  Read of device ID code                                           ADDR   FUNC REG H L COUNT HL CRC L H  01 03 00 21 00 01 D4 00  The answer   ADDR   FUNC   BYTEC DATA H L CRC L H  01 03 02 22 DC 18 89                            DATA   identification code  22DCh     68                User manual   CONTROLLER PUR 94       3  Change of the device address from 1 to 2  write to reg  20h                                         ADDR   FUNC REG H L DATA H L CRC LH  01 06 00 20 00 02 09 C1  DATA H   0    DATA L   new device address  2     The answer  the same as the message         ADDR   FUNC REG H L DATA H L CRC LH  01 06 00 20 00 02 09 C1                                     4  Change of baud rate of all devices conne
16.  in the measurement mode  operator must to press and hold  at least 2 sec   ESC MENU  button     If the user password is defined  see parameter    Scod     menu    SECU      operator have  to enter correct one before proceeding to menu options   Entering of the passwords is similar  to the edition of numeric parameters  see  PARAMETERS EDITION    however presently editing  digit is showed only on the display  other digits are replaced by         sign     After entering of last digit of the password first menu position will be displayed  if the  password is correct  or warning    Err    in other case     32    User manual   CONTROLLER PUR 94       A Pay attention when device parameters are being changed  If it is possible  turn off  controlled installation  machine      Functions of the buttons while sub menu and parameters choice     Selection of sub menu or parameter for editing  Name of selected item  sub    menu or parameter  is displayed    Operation of  ENTER  button depend on present menu position      if the name of some sub menu is displayed   enter this sub menu  name  of the first parameter  or next level sub menu  is displayed      if the name of some parameter is displayed   enter the edition of this  parameter  present value of the parameter is displayed     ENTER      ESC MENU  button allow user to exit present menu level and goes to upper  MENU level menu  or measurement mode      ED After about 1 min  since last use of the buttons  device exits the menu mode a
17.  of parameters available         Conn    I         Hon    II   in  inPt  menu depends on value i i  of  tYPE  parameter        CHar    II    ol HoFF    I     E D        FiLt I    AL  I        toFS    I     oi Pnt    I           ES  l   bei HiC    I     I lt      AddP    I           dELP    I          EdtP B   Y   Lor     See next page E        Hir    I                Parameter  edition    User manual   CONTROLLER PUR 94       See previous page                                                                            _      Parameter                                                    v    See next page                                                                                                                   OutP CG OSou              Ge  ry   Z5 edition i  ipae peli dum once d Omod        i      OUtL     I       i    D OUtH      I    i  i    Lor                    Hir    I         t    AL 1    option    M eR I A a Se sa           CL   lt  modE L    r Ga  SEtP    I       e  Y a i  EL      99 Parameter  bri edition PArH    lam z      mc A J  H        Hold    modE E id    za    u     D   Esc  PEA     I  es    II   H  timE    II  FuZL    II   t  zs Hdis    II   t  Hr         Hr2    I   H  Hr3    II   t  H r4  ll     E  HOUt     I     Parameter  edition    51    User manual   CONTROLLER PUR 94       See previous page    A       52    4                                gt   Addr                                  i  bAud    EE mh    mbAc  t  mbtO         rESP                   4 
18.  of relay R4 OFF 37                      71    User manual   CONTROLLER PUR 94                                                                                                                         Parameter Description Default value User s value pena  OFFS Relay R4 output offset 0 0 36  SEnS Relay R4 output sensitivity 100 0 36  Activation of acoustic signal  menu  bEEP    AL Activation of acoustic signal by critical situation oFF 38  r1 Activation of acoustic signal by relay R1 oFF 38  r2 Activation of acoustic signal by relay R2 oFF 38  r3 Activation of acoustic signal by relay R3 oFF 38  r4 Activation of acoustic signal by relay R4 oFF 38  Configuration of measurement input     inPt    menu   tYPE Input mode    4 20    38  Conn Connection method  A in  39  FiLt Filtering time constant  in seconds  0 39  toFS Shifting of measurement scale 0 0 39  CHAr Conversion characteristic mode Lin 39  Pnt Decimal point position 0 0 39  LoC Minimum displayed value  for nominal range  000 0 39  Hi C Maximum displayed value  for nominal range  100 0 39  Lor Extension of the bottom of the nominal input range 5 0  96  40  Hir Extension of the top of the nominal input range 5 0  96  40  Active current output configuration     OUtP    menu   OSou Active current output signal source    InPU    41  Omod Active current output mode    0 20     mA  42  OUtL Display value for 0 mA or 4 mA current output 0 0 42  OUtH Display value for 20 mA current output 100 0 42  Lo r Extension of the bottom of 
19.  offsetting of a scale is realised independently of cold ends automatic  compensation     7 3 5     inPt    menu  parameters of current and voltage inputs         CHAr    this option presets type of the conversion characteristic  and can be set to    Lin  m li   Sgr    ee When one of those characteristics is chosen display     Sqrt     square root range is defined by    Lo C  and    Hi C       USEr     user defined characteristic  Maximal length 20 points  Every point is  defined by user  Adding  Editing and Deleting of points is done by options     AddP        EdtP      dELP        InPt    menu  respectively     a If user defined characteristic is selected  and if number of defined points is lower  than 2 then warning  Errc  is displayed in measurement mode     The process of displayed result calculation is described in details in DISPLAY VALUES  CALCULATION paragraph      Pnt    decimal point position  It can be set to one of   Di 0     Di 0 0     Di 0 00        0 000     Decimal point position is changed by  4    v  buttons        LoC    These parameters describe the values displayed for minimum and maximum input      Hi C    current  For example  if input type is set to 4 20 mA    Lo C  parameter defines the  value displayed when input current is equal 4 mA  and    Hi C    parameter defines  the value displayed for 20 mA of input current  Available range for these  parameters   999   9999  Negative values can be set by entering     sign on the first  position  by use of  
20.  on the load  In consequence of using the suppression circuit  the level of    generated electromagnetic disturbances is lower  and the life of relay contacts  rises     User manual   CONTROLLER PUR 94       a        N  Figure 4 18  Examples of suppression circuit connection   a  to relay terminals  b  to the inductive load         Logic controller       voltage input  24V             Figure 4 19  Example of OC type outputs connection   for device with OC type output only     17    User manual   CONTROLLER PUR 94       ACTIVE  current output         DD    Logic controller          current input  0 20 mA             Figure 4 20  Example of active current outputs connection   for device with active current output only     PASSIVE  current output Uo        Logic controller         Isolation loss    current input  4 20 mA             Figure 4 21  Example of passive current outputs connection   for device with passive current output only     ACTIVE  voltage output         DD    Logic controller          voltage input  0   10V             Figure 4 22  Example of active voltage outputs connection   for device with active voltage output only     18    User manual   CONTROLLER PUR 94       4 4  MAINTENANCE    The unit does not have any internal replaceable or adjustable components available to  the user  Pay attention to the ambient temperature in the room where the unit is operating   Excessively high temperatures cause faster ageing of the internal components and shorten the  fault 
21.  parameter in  rEL1  menu  no decimal point included  R    Acti    parameter in    AL    menu   only when rEL1 is OC type output    a ves SFA 0      noCH    option  1    USdu  option   3Fh Yes 0 1000    duty    parameter in    AL    menu  only when rEL1 is OC type output   M Current OC type output fill factor expressed as a percentage without  gon ES PSZ the decimal point  only where rEL1 is the OC type output   41h Yes    999   9999      OFFS    parameter in    rEL1    menu  no decimal point included  42h Yes 0 1000      SEnS    parameter in   rEL1    menu  no decimal point included     Sour    parameter in    rEL2    menu   43h Yes 0 3   Q    InPU    option  1      modb    option  2    PidH  option  3    PidC   option        62       User manual   CONTROLLER PUR 94                                                                                     Register   Write Range Register description   modE  parameter in    rEL2    menu   44h Yes 0 5 0      noAC    mode  1      on    mode  2      oFF    mode  3      in    mode   4      out    mode  5      PULS    mode  45h Yes    999   9999     SEtP    parameter in    rEL2    menu  no decimal point included  46h Yes  999  999     HySt    parameter in    rEL2    menu  no decimal point included  TE a mM  48h   Yes   0 989 1 tenth ot minutes depend on  unit  parameter   register no  47h   MEN d  4Ah Yes 0 2 See ide SE  only when rEL2 is relay output   0  4Bh Yes    999   9999      SEt2    parameter in    rEL2    menu  no decimal point i
22.  particular  wires  Ra   Rd  MUST BE IDENTICAL to enable proper compensation of it s resistance  The  resistance of particular wire should not be greater than 20 Q              15    User manual   CONTROLLER PUR 94       16                                                             i 9  prfsz ss 34  n c  n c    Ra Rb Rc Rd   Ra   pel Rd gel   Re    V M A  T    RTD RTD RTD  Ra  Rb  Rc  Rd can be different Ra Rc Rd Ra  Rc can be different    Figure 4 16  Connection of RTD sensors   a  4 wires circuit  b  3 wires circuit  c  2 wires circuit    The connection circuit should not be changed while unit is powered  While using  TC  RTD or voltage inputs  0 150mV  the device is able to detect wire breaks  Wire  breaks are detected within about 2 seconds  For connectors number 32 and 33 of  RTD input it may take up to about 7 seconds  During detection measurements will  be incorrect  If wire break is detected  S Err   sensor error  message is displayed        Depending on version   85   230   260V AC DC or  19   24   50V DC  16   24   35V AC    L N    Figure 4 17  Connection of power supply and relays    Contacts of relay outputs are not equipped with spark suppressors  While use  the relay outputs for switching of inductive loads  coils  contactors  power  relays  electromagnets  motors etc   it is required     to use additional  suppression circuit  typically capacitor 47nF  min  250VAC in series with  100R 5W resistor   connected in parallel to relay terminals or  better  directly 
23.  therefore are suitable for  constant value regulating of the object or technological processes that contain such elements  as furnaces  boilers  etc    The PUR 94 device includes a proportional integral derivative  PID  controller with two  independent control loops  one for controlling the heating process and the second for the  cooling system  a general diagram of the controller is shown in Figure 6 5   Hereafter these  loops are called PID H loop and PID C loop respectively  as shown in Figure 6 5  Each of  these loops is composed of the following blocks  P proportional  I integral and D derivative   whose proper summing up gives the output signal controlling the object Figure 6 6    The controller s signal may be redirected to any output of the device  which means that  the PUR 94 may be used to control most objects used in the industry    The PID controller can be used to adjust such values as temperature  humidity  pressure   force  speed  flow rate  or level of a liquid or loose material etc  Note  however  that the  controllers included in the device have a common setpoint  SEtP parameter   and so should  be used in applications where one of the controllers  e g  PID H  is used to control actuators  that increase the state of the regulated object  e g  heating   and the other controller  e g  PID  C  is used to control actuators reducing the state of the regulated object  e g  cooling     Additional controller parameters such as  dead zone  fuzzy logic block or inert
24.  to exceed the nominal range of input signal   If input value is contained in the permissible range a proper result is displayed   If input signal exceeds this range  defined by    Lo r    and  Hi r        Lo   or       Hi   warning is displayed depend on input signal value     User manual   CONTROLLER PUR 94              Lo r      75 0   3 mA   Hi r      5 0    1 mA   RE nominal measurement range  4 20mA   d   min   rid mie i La   em e Yt tt ima  0 1 4 20 21 22  permissible measurement range    pt  gt  4   LN measurement result is displayed 4  display regardless on nominal range exceeding display  message   Lo   message   Hi      Figure 7 1 Example of definition of permissible range of input signal     Lo r    and    Hi r    parameters     4 20    mode     The    Lo r    parameter is important if input is set to    4 20        1 5    or    2 10    mode  only  and determines lower border of the permissible range  In the other cases  for  current and voltage ranges   lower border of the permissible range is always 0    For example if input is set to    4 20    mode  then lower border is calculated due to  expression  Imn   4 mA   4 mA x    Lor    95    The  Lo r  value can be set from 0 to 99 996    Parameter  Hi r  determines the upper border of the permissible range accordingly  to the expression  for all modes     For example if input is set to    4 20    mode  then upper border is calculated due to  expression  Imax   20 mA   20 mA x  Hi r    96    The value of  Hi r    ca
25.  will linearly vary the percentage share of the high status over the entire period of the  signal in accordance with fill factor D  In those cases where the source value is less than the  value of the  InLo  parameter  the fill is equal to 096  i e  the output signal will always in low  level state   and when the source value is greater than the value of the  INHi  parameter the  fill will be equal to 100   i e  the output signal will always in high level state     Factor D is defined by the following formula        p    T    where   t     the duration of the high status for a single pulse   T   the duration of the signal     30    User manual   CONTROLLER PUR 94          Di 33         Sour  0 2 4 6 8 10 12 14 16 parameter             InLo     Ini   parameter parameter    Figure 6 13  Example characteristics of an input   output signal in the  PULS  mode for  parameters   InLo    4   InHi    14    There is also a possibility of protecting the signal from too high or too low fill factor  by  inserting the parameters  H on  and  HoFF   These specify the minimum duration of the high  signal and low signal respectively  When setting the output status  the parameters  H on  and   HoFF  have a higher priority than the fill factor     does not exceed the value of the parameter  Peri   since this will cause the OC output    Gi  It should be noted that the sum of the values of the parameters  H on  and  HoFF   to move to a low status     The  AL  parameter specifies the permanent fill
26. 100 0 36  Parameters of relay R3 operation     rEL3    menu   Sour Relay R3 signal source InPU 35  modE Operation mode of relay R3 on 35  SEtP Relay R3 threshold 20 0 35  SEt2 Relay R3 second threshold 40 0 35  HYSt Hysteresis of relay R3 0 0 36  ton Turn on delay of relay R3 0 0 36  toFF Turn off delay of relay R3 0 0 36  unit Unit of    t on        toFF    parameters of relay R3 SEC 36  InLo The lower limit of the PWM range of relay R3 0 0 37  InHi The upper limit of the PWM range of relay R3 100 0 37  PEri Relay R3 output signal period 1 0 37  Hon Low state minimal time of relay R3 PWM signal 0 0 37  HoFF High state minimal time of relay R3 PWM signal 0 0 37  AL Reaction for critical situation of relay R3 OFF 37  OFFS Relay R3 output offset 0 0 36  SEnS Relay R3 output sensitivity 100 0 36  Parameters of relay R4 operation     rEL4    menu   Sour Relay R4 signal source InPU 35  modE Operation mode of relay R4 on 35  SEtP Relay R4 threshold 20 0 35  SEt2 Relay R4 second threshold 40 0 35  HYSt Hysteresis of relay R4 0 0 36  ton Turn on delay of relay R4 0 0 36  toFF Turn off delay of relay R4 0 0 36  unit Unit of    t on        toFF    parameters of relay R4 SEC 36  InLo The lower limit of the PWM range of relay R4 0 0 37  InHi The upper limit of the PWM range of relay R4 100 0 37  PEri Relay R4 output signal period 1 0 37  Hon Low state minimal time of relay R4 PWM signal 0 0 37  HoFF High state minimal time of relay R4 PWM signal 0 0 37  AL Reaction for critical situation
27. 2 5 mA then In    2 5   4  16    0 0938  and if input current is  equal 20 5 mA then I     20 5   4  16   1 0313    Example 3  The linear characteristic    Let the input mode   4 20 mA  and parameters    Lo C    and  Hi C    equal to  300 and 1200  respectively  The calculations will be done for three different input currents from example 2     36    User manual   CONTROLLER PUR 94       a  ln 210 mA and I    0 375  Accordingly to expression on page 54 for linear characteristic   0 375 x  1200     300     562 and next  the    Lo C    value is added to the result   so the  displayed value   W  562     300    262    b  ln   2 5 mA and I     0 0938   W   441     c  ln   20 5 mA and h   1 0313   W   1247     Example 4  The square characteristic    Let the input mode   4 20 mA  and parameters    Lo C    and    Hi C    equal to  300 and 1200  respectively  The calculations will be done for there different input currents from example 2     a  lin  10 mA and h   0 375  Accordingly to expression on page 54 for square characteristic   0 375  x  1200     300      211   and next  the    Lo C    value is added to the result   so the displayed value   W   211     300     89    b  lin   2 5 mA and       0 0938   W   287     C  ln   20 5 mA and      1 0313   W   1295     Example 5  The square root characteristic    Let the input mode   4 20 mA  and parameters  Lo C    and  Hi C    equal to  300 and 1200  respectively  The calculations will be done for there different input currents from exam
28. 4    v  buttons      39    User manual   CONTROLLER PUR 94                AddP       e       dELP          EdtP             If user defined characteristic is selected  parameter  CHAr     USEr   the  parameters  Lo C  and  Hi C  are not available for modification  due to their values  are calculated from defined characteristic       this menu allow user to add single point to the user defined characteristic    After selection of this option device waits for    X    and  Y    coordinates of new point   Modification of the coordinates is done accordingly to numerical parameters edition   Coordinate  X    defines the percentage ratio of input current to selected current  range  The    X    range   99 9   199 9  Coordinate    Y    defines displayed value for  particular  X  value  The    Y    value can be changed in range   999   9999  decimal  point position depend on    Pnt    parameter  menu  inPt        e User can not enter two points with the same value of    X    coordinate  If user trays  to do it   Err  warning is displayed  To modify any defined point use  EdtP   option      To distinguish    X    and  Y  coordinates  if  X  coordinate is displayed an  additional decimal point on utmost right position is displayed      If user defined characteristic is selected  and if number of defined points is lower  than 2 then warning  Errc  is displayed in measurement mode      this option allows user to delete any of the points of the user defined   characteristic  After selection
29. 42    Lu    30 0 10 0     20 0 10 0  x 16 MA   4 mA   2 16   4   36 mA   Calculated l  exceeds the output working range  3   21 mA   so current output will generate  current equal to the upper border of range defined by parameter  Lo r  and  Hi r   it means  21 mA      Example 8  Connecting and preparing the system for the auto tuning process       Let s assume that we want to carry out the auto tuning process of the PID H controller s  loop connected to an OC type output in the PULS mode  In such an arrangement the device is  to control the temperature of an oven  in a free state of 20  C  using a high power SSR relay   and the feedback concerning the temperature is obtained using a Pt100 sensor     230V    AR       F                 SSR                         OC type output             PUR 94    Pt100          Measurement input    l    Figure  10 5 Example arrangement of connections for auto tuning                               Preparatory steps to launch the auto tuning process     a  Connect the system in accordance to the diagram in Figure  10 5   b  In the selected OC type output set   parameter Sour as PidH   parameter modE as PULS   parameter Peri at 6 0   c  Set the tYPE parameter  in the inPt menu  as Pt 1   d  Set the setpoint to 120  C  the SEtP parameter in the CtrL menu    e  Set the modE parameter  in the CtrL menu  as At H   f  Wait until the device carries out auto tuning  at which time the display will blink    g  Once the display stops blinking  the device
30. 5    voltage input   range 0  5 V    1 5    voltage input   range 1  5 V    0 10    voltage input   range 0  10 V    2 10    voltage input   range 2  10 V    60    voltage input   range 0  60 mV    75    voltage input   range 0  75 mV    100    voltage input   range 0  100 mV      150      voltage input   range 0  150 mV    Pt 1      Pt 100 input     Pt 5    Pt 500 input       Pt10      Pt 1000 input     tc k      thermocouple input  type K    tc S    thermocouple input  type S    tc J      thermocouple input  type J    tc t    thermocouple input  type T    tc n      thermocouple input  type N    tc r    thermocouple input  type R    tc b      thermocouple input  type B    tc E      thermocouple input  type E     38    User manual   CONTROLLER PUR 94       For current and voltage inputs displayed values are defined by parameters     Lo C   Hi C   or by user defined characteristic points  and parameter  Pnt       FiLt    option allows to change the filtration time constant  Expressed in seconds   Acceptable values range from O  no filtration   to 255     7 3 4   inPt  menu  parameters of temperature inputs         Conn   connection method of RTD input  This parameter can be set to values    4 in    4 wire method    3 in    3 wire method    2 in      2 wire method        toFS     offset expressed in   C  range   9 9  C  for RTD input  or   99  C  for TC input   This  parameter allows shifting of measurement scale  and express value added to  calculated  measured  result     The
31. 6 1  MEASUREMENT MODE    In the measure mode  the measurement results  converted over selected characteristic   are displayed on the LED display  The measurement range equal to the nominal range is  called  nominal measurement range  and the measurement range equal to the extended  nominal range is called  permissible measurement range  Figure 6 1  6 2         For temperature inputs  TC and RTD  there is linear characteristic available only   For this kind of inputs nominal measurement range  and permissible  measurement range are the same  no range extension available  Figure 6 3             Lo r    parameter  Hi r  parameter  Ki nominal measurement range PA    Ka  gt  gt      4 mA 20mA      permissible measurement range       Figure 6 1  Definitions of measurement ranges in mode 4   20mA    If the result of measurement exceeds the permissible measurement range  warning    Hi   or   Lo   is displayed rather than input signal  depending on exceeded value  see  description of    Lo r    and  Hi r    parameters  paragraph  inPt  menu   The warning can be  effect of measurement circuit malfunction  In that case     Lo     means shortcut and     Hi      means break of measurement circuit  If sensor failure will be detected  e g  broken wires   then   S Err  warning will be displayed      Hi r  parameter       nominal measurement range   Pd       OmV 150 mV      permissible measurement range       Figure 6 2  Definitions of measurement ranges in mode 0   150mV  If the measurement 
32. Assisting the automation    rz simex industry since 1986    User manual  CONTROLLER    PUR 94      Firmware  v 1 00 or higher    Inputtype  universal    4x20 mm display       CE    Read the user s manual carefully before starting to use the unit or software   Producer reserves the right to implement changes without prior notice     2015 10 01 PUR 94_INSSXEN_v 1 01 003    User manual   CONTROLLER PUR 94       CONTENTS  1  BASIC REQUIREMENTS AND USER SAFETN  EEN 3    2  GENERAL CHARACTERISTICS                itii esce srtae sica spain te ratae os add Adik st eaa  W awa ao aS PR      asas 4  3  TECHNICAL                                                                                   5  4  DEVICE  INSTALLATION                                      8  41 o EE 8  Lcd  az ana nd Salesian DW AO R   NZOZ T  4 3  CONNECTION METLIOD        ierit ia AO A A EA TN DR n ea araa ERE  Nigri                           5  FRONT PANEL DESCRIPTION   6  PRINCIPLE OF OPERATION         20  6 1  MEASUREMENT MODE             initi tate tpa i ip A HE TA a EAR HIE ERA ARV Pen 20  6 1 1  detection OF THE PEAK VALUES                sisse awa a EA  21  6 2  DIDREGULATORS  6 3  CONTROL OF THE RELAY OUTPUTS     6 3 1  One threshold mode                       6 3 2  Two thresholds mode     6 3 3  PWM Controlling         7  DEVICE PROGRAMMING         7 1  PROGRAMMING MENU     7 2  PARAMETERS EDITION  7 2 1  Numeric parameters  digit change model 383  7 2 2  Numeric parameters  slide change model 33  7 2 3  Swi
33. EN i EE  toFF   0  EEEE i      m rfl rz   b ime  d  relay state 4 e f EM R i MES   modE   on   i i losed  ton  gt  0 rt   lee ba Popei  toFF  gt  0      open i i   i Fog     rn  teal     gt    GH ES ime  e  relay state 4 bog   m    ton  E    toFF    A it   modE   oFF E Sos dosed       parameter     Parameter   BE  ton  gt  0           es i    7  torr 0     1          Loser   E  Te i r  z AE ime  s    toFF     t on     parameter parameter  Description   A  B  C D   points where measured signal exceeds border values  expected value   allowed deviation   Bon    Borr Don Dor   relays state changes moments   for    t on     gt  0     toFF     gt  0   ta  te   tc   to   time periods while input signal is in zone A or zone B    Figure 6 11  Principle of LED relay output operation for one threshold mode    Parameter    SEtP    sets a threshold of the relay  and parameter    HYSt    sets a  hysteresis of the relay  Figure 6 11 a   The relay can change his state only when input value  exceeds  over or under  border value and tA  tB  tC  tD times  Figure 6 11  are bigger than the  time defined by parameters  t on    toFF  and    unit     Border values means values equal  threshold hysteresis and threshold hysteresis respectively    If    ton    and    toFF    parameters are set to    0     then the relay state will be changed  as soon as input value exceeds any of the border values  see points A and C  Figure 6 11 a   b  c     If values of    ton    or and  toFF  are positive  then rela
34. EtP    parameter in    rEL4    menu  no decimal point included  6Ch Yes  999   999   HySt  parameter in  rEL4  menu  no decimal point included    en ee i  Gen   Yes  ng    ofe orminules depend on    unit parameter eer EOR   m  ve   dedo  e ire nee men  70h Yes 0 2 o e  only when rEL4 is relay output   0  71h Yes    999   9999     SEt2    parameter in    rEL4    menu  no decimal point included  72h Yes    999   9999     InLo    parameter in    rEL4    menu  no decimal point included  73h Yes    999   9999     InHi    parameter in    rEL4    menu  no decimal point included  74h Yes 0   9999  PEri  parameter in    rEL4    menu  no decimal point included  75h Yes 079999     H on    parameter in  rEL4  menu  no decimal point included       64       User manual   CONTROLLER PUR 94                                                                            Register   Write Range Register description  76h Yes 0   9999  HoFF  parameter in    rEL4    menu  no decimal point included  77h Ves 021  Acti  parameter in  AL  menu   only when rEL4 is OC type output    0    hoCH  option  1    USdu  option   78h Yes 071000      duty    parameter in  AL  menu  only when rEL4 is OC type output   S Current OC type output fill factor expressed as a percentage without  M Gs da the decimal point  only where rEL4 is the OC type output   7Ah Yes    999   9999      OFFS    parameter in    rEL4    menu  no decimal point included  7Bh Yes 0   1000  SEnS  parameter in rEL4    menu  no decimal point included
35. H regulator 0 0 44  tl H integral gain factor I of PID H regulator 0 0 44  td H derivative gain factor D of PID H regulator 0 0 44  OF H Offset of PID H regulator 0 0 44  Lo H The lower characteristic limit of PID H 00 44  regulator  Hi H The upper characteristic limit of PID H 100 0 44  regulator  PID C regulator configuration     ParC    menu  44  P  C proportional gain factor P of PID C regulator 0 0 44  tl c integral gain factor I of PID C regulator 0 0 44  td c derivative gain factor D of PID C regulator 0 0 44  OF C Offset of PID C regulator 0 0 44  Lo C The lower characteristic limit of PID C 0 0 44  regulator  Hi C The upper characteristic limit of PID C 100 0 44  regulator  PID regulators configuration     ConF    menu  45  dEAd Dead zone 0 0 45                      73    User manual   CONTROLLER PUR 94                                                                                                                SE   Desc   Parameter Description Default value User s value page  StAr Start state of the regulators 0 0 45  dsrC Feedback of the regulators LooP 45  InEr Inertial block OFF 45  PID regulators configuration     FuZL    menu  46  SLOP Incline of the characteristics of the fuzzy logic 46  0 0  block  FuZL menu parameter  unit Time unit of incline of the characteristics of the 46    SEC  fuzzy logic block  FuZL menu parameter  HySt Hysteresis of incline of the characteristics of the 0 0 46  fuzzy logic block  FuZL menu parameter    Display parameters  bri Displ
36. K    are used to make it more readable  example   modE     tc K         34    User manual   CONTROLLER PUR 94       7 3 1     rEL1    menu    This menu allows to configure the operation mode of relays and LEDs marked    R     e g   R1       If there are few relay outputs available  then every output has its own configuration menu   e g  menu  rEL2  for relay  LED     R2      Principle of the relays operation is described in  paragraph CONTROL OF THE RELAY OUTPUTS     e     Sour        modE          SEtP          SEt2         The relay outputs and LEDs  named R  can be controlled depend on both   the  current value and the peak value  when peak detection is active  of the input  signal       f device is not equipped with one or more relay outputs  menus refer to this  relays are available  but apply to LED indicators only  In such case LEDs  indicates exceeding of particular thresholds       this parameter specifies the source of the signal controlling the output    InPU      output is controlled using signals from the measurement input    modb     control via Modbus registers       PidH        control via the control loop of the PidH controller     PidC     control via the control loop of the PidC controller       relay operation mode      noAC    the relay is not active  permanent turned off       on      one threshold mode  the relay is turned ON when input signal exceeds  SEtP   HYSt value  and is turned off back when the input signal became  lower than SEtP     HYSt      
37. ONTROLLER PUR 94       Communication interface  Baud rate    Display   depending on version     Data memory    Front panel protection    Terminals protection    Housing type  Housing material  Housing dimensions  Mounting hole  Assembly depth  Panel thickness    Operating temperature   depending on version     Storage temperature   depending on version     Humidity  Altitude    Screws tightening max  torque  Max  connection leads cross section    Safety requirements    EMC    RS 485  8N1 and 8N2  Modbus RTU  not separated  1200 bit s   115200 bit s    LED  4 digit  20mm height  red or  LED  4 digit  20mm height  green    non volatile memory  EEPROM type    IP 65  optional version with panel cut out sealing available    IP 20    panel   NORYL   GFN2S E1  96 x 48 x 100 mm  90 5 x 43 mm   102 mm   max  5mm    0  C to  50  C  or  20  C to  50  C     10  C to  70  C  or  20  C to  70  C    5 to 90  no condensation  up to 2000 meters above sea level    0 5 Nm  2 5 mm     according to  PN EN 61010 1  installation category  II   pollution degree  2   voltage in relation to ground  300V AC    insulation resistance   gt 20MQ   insulation strength between power supply and  input output terminal  1min     2300V  insulation strength between relays terminal   1min  Q 1350V    according to  PN EN 61326 1    This is a class A unit  In a residential or a similar area it can cause radio    frequency interference  In such cases the user can be requested to use  appropriate preventive measures  
38. acteristic  20h   waiting for the first measure  B  Pnt   parameter in  InPt  menu  decimal point position   osh ves SS 0   0 1   0 0     2      0 00     3      0 000     State of the relays and alarm LED  binary format    1   on  0   off   00000000 000edcba  04h Yes see descr   a  relay R1  b   relay R2  c   relay R3  d   relay R2  e   alarm LED   If written  only a  b  c  d bits are important  others are ignored   these bits allows user to control the relays via RS 485 interface  State of active current output  expressed in 1 256 mA units     it  Yes   Oh   1800h   means that high byte express integer part  and low byte fractional  part of desired output current   State of passive current output  expressed in 1 256 mA units     it  05h  Yes   2CCh 1800h   means that high byte express integer part  and low byte fractional  part of desired output current   State of active voltage output  expressed in 1 512 V units     it means  Yes Oh   1600h   that high byte express integer part  and low byte fractional part of  desired output voltage   06h No  999   9999   Peak  drop  value  no decimal point   08h No 0  50 Temperature inside device housing expressed by 1  C       60       User manual   CONTROLLER PUR 94                                                                         Register   Write Range Register description   tyPE  parameter in  InPt  menu  nominal input range    0   0 20 mA range  1   4 20 mA range  2   0 5 V range   3   1 5 V range  4   0 10 V range  5   2 10 V 
39. ay brightness bri6 47  Configuration of peaks detection function     HOLd    menu   modE Kind of detected changes norm 47  PEA Minimum detected change 0 0 47  timE Maximum time of peak displaying 0 0 47  HdiS The type of displayed value HOLd 47  Hr Source of relay R1  and LED R1 control rEAL 48  H r2 Source of relay R2  and LED R2 control rEAL 48  H r3 Source of relay R3  and LED R3 control rEAL 48  H r4 Source of relay R4  and LED R4 control rEAL 48  HOUt Source of current output control rEAL 48  Settings of access to the configuration parameters     SECu    menu   Art Permission to changes of relay R1 threshold on 48  without of the user password knowledge  Ar2 Permission to changes of relay R2 threshold on 48  without of the user password knowledge  A r3 Permission to changes of relay R3 threshold on 48  without of the user password knowledge  Au Permission to changes of relay R4 threshold n 48  without of the user password knowledge  APid Permission to changes of regulator s setpoint   n 48  without of the user password knowledge  RS 485 interface configuration  menu    rS      Addr Device address 0 48  bAud Baud rate 9 6 48  mbAc Permission to changes of configuration registers on 48       74       User manual   CONTROLLER PUR 94                         Parameter Description Default value User s value pec   mbtO Maximum delay between received messages 0 49   rESP Additional delay of answer transmission Std 49  Configuration of numerical parameters edition   Edit Numerica
40. can lead to unit damage or  an accident       If in the case of a unit malfunction there is a risk of a serious threat to the  safety of people or property additional  independent systems and  solutions to prevent such a threat must be used       The unit uses dangerous voltage that can cause a lethal accident  The unit  must be switched off and disconnected from the power supply prior to  starting installation of troubleshooting  in the case of malfunction        Neighbouring and connected equipment must meet the appropriate standards  and regulations concerning safety and be equipped with adequate overvoltage  and interference filters       Do not attempt to disassemble  repair or modify the unit yourself  The unit  has no user serviceable parts  Defective units must be disconnected and  submitted for repairs at an authorized service centre        User manual   CONTROLLER PUR 94         In order to minimize fire or electric shock hazard  the unit must be protected  against atmospheric precipitation and excessive humidity       Do not use the unit in areas threatened with excessive shocks  vibrations  dust   humidity  corrosive gasses and oils       Do not use the unit in areas where there is risk of explosions       Do not use the unit in areas with significant temperature variations  exposure to  condensation or ice       Do not use the unit in areas exposed to direct sunlight       Make sure that the ambient temperature  e g  inside the control box  does not  exceed the r
41. cted to the net  BROADCAST message         ADDR   FUNC REG H L COUNT H L CRC LH  00 06 00 22 00 04 29 D2                                     DATA H   0  DATA L   4  new baud rate 19200 baud    a Device do not reply to BROADCAST type messages     5  Read of the registers 1  2 and 3 in one message  example of reading a number of  registries in one frame         ADDR   FUNC REGH L COUNT H L CRC LH  01 03 00 01 00 03 54 OB                                     COUNTL  the count of being read registers  max 16     The answer        ADDR   FUNC  BYTEC   DATA H1 L1   DATA H2 L2   DATA H3 L3   CRC LH  01 03 06 00 0A 00 00 00 01 78   B4                                              DATAH1 L1  reg  01h  10   displayed value  1 0     DATAH2 L2  reg  02h  0   no errors    DATA H3  L3  reg  03h  1   decimal point position   0 0         E There is no full implementation of the Modbus Protocol in the device  The  functions presented above are available only     69    User manual   CONTROLLER PUR 94       12  DEFAULT AND USER S SETTINGS LIST                                                                                                                      Parameter Description Default value User s value pania  Parameters of relay R1 operation     rEL1    menu   Sour Relay R1 signal source InPU 35  modE Operation mode of relay R1 on 35  SEtP Relay R1 threshold 20 0 35  SEt2 Relay R1 second threshold 40 0 35  HYSt Hysteresis of relay R1 0 0 36  ton Turn on delay of relay R1 0 0 36  toFF Turn off
42. d PL points     If the normalized result exceeds the user defined characteristic values  then specific  aD utmost segment  defined by two next points  is used for calculations  If characteristic   from figure below is used  and if I gt 1 then segment defined by points   X PL     90 0    X PH       100 0     will be used     55    User manual   CONTROLLER PUR 94       Normalized measurement In  for 0 20 mA range   0 0 2 0 35 0 5 0 7 0 9 1          5 elements characteristic           i   X  PH       70 0                       Displayed value                                  0 4 8 12 16 20  Input current  mA     Figure  10 4 Example of user defined characteristic    10 2  EXAMPLES OF CALCULATIONS       Example 1  Selection of the permissible input range     4 20    mode    If in  4 20  mode the user sets  Lo r      20 0  and    Hi r      10 0   then permissible  input currents range will be equal  3 2 mA   22 mA  Lower border of the range is the result of  calculations  4 mA   4 mA x 20   and the higher   20 mA   20 mA x 10     Example 2  The normalized I  result calculation  Let the input mode   4 20 mA  The normalized    result is calculated accordingly to the  expression on page 53  so if lin   10 mA then 10 mA   4 mA   6 mA  and this result should be    divided by the width of input range  16 mA   Finally the normalized result       6 16   0 375     In case when input current exceeds nominal measurement range  calculations are similar  For  example if input current is equal 
43. d calculations are similar  be sure of  particular ranges and units     The first step to compute the result of measure is the calculation of the normalized result   it means result of 0 1 range   To do it  the begin of the input range  0 mA for 0 20mA range   and 4mA for 4 20mA range  must be subtracted from measured value  Next  received result  must be divided by the width of the input range   it means 20mA for 0 20mA range  and 16mA  for 4 20mA range   So normalized result can be expressed by expressions           Ti     4   Jee for 4  20mA range  Tp    I     20 for 0 20mA range    where li  Means input current  in mA   and lIn  normalized result     If measured value exceeds the nominal input range  0 20mA or 4 20mA   and do   aD not exceed the permissible input range  then received normalized    result will  exceed 0 1 range  e g  input range 4 20 mA  input current   3 mA   the normalized  result is equal  0 0625  and for input current   22 mA  the normalized result is equal  1 125  In such cases presented expressions are still correct     10 1  ADDITIONAL CALCULATIONS  USED CONVERSION CHARACTERISTIC    The manner of the additional computation of the displayed result depends on selected  conversion characteristic  All presented charts are connected with the input range 4   20 mA        53    User manual   CONTROLLER PUR 94       10 1 1  Linear characteristic    The normalized result is converted by fixed coefficients determined by    Lo C    and    Hi C     parameters  
44. d its setting will not change following the  rocess   The process of auto tuning in this mode may commence subject to the following conditions   1  The value measured by the device must be greater than six fifths of the setpoint  2  The source of at least one of the device   s outputs must be PID C  Additionally  those  outputs cannot be set in the noAC mode     Auto tuning that is already underway is a very sensitive process  So the user should pay  attention to events that could interrupt the tuning of the settings  These events include    1  Loss of power to the device    2  Time for auto tuning exceeded  24 h     3  When the PID controller   s operating mode is switched over    4  Measurement error  e g  sensor failure     5  Change in the parameters of the device     26    User manual   CONTROLLER PUR 94       6 3  CONTROL OF THE RELAY OUTPUTS    The control of the object  measured signal  is realized via relay outputs  Front panel  LEDs named    R    indicates the state of particular relay output     If device is not equipped with one or more relay outputs  menus refer to this relays  are available  but apply to LED indicators only  In such case LEDs indicates  exceeding of particular thresholds     Modes of the control can be changed depend on the values of parameters    SEtP         SEt2      HYSt      modE        t on      toFF        unit    and    AL     Depend on    modE    parameter   relays can be not used or controlled over one or two thresholds values    If on
45. digit special      SZ   Parameter  SG edition    password entering           gt  0                      ESC Y   M        SECu 3  A  m   Y  C c E  n  mo  kend  L  I za L   Dn  7 S  e  Y bel  bei dEFS  amp   7 S  fe  3  SEE                 gt     SEt                    ESC        gt                                               Default settings  restoring    i  gt   Scod Le  T        lt     An    I      i   I     An    I     t   bi AB kl  E  i   bei Ar    II   i        APid    I       Parameter  edition    User manual   CONTROLLER PUR 94       8  THE ALARM LED    Alarm LED  AL  lights in cases     exceeding of permissible measurement range    detection of sensor malfunction  shortcut or break of measurement circuit        9  OVER CURRENT PROTECTION    The current input of the device is equipped with over current protection circuit  This circuit  protects the standard resistor to damage  Maximum input current is set to 50mA  typical    When temperature of the standard resistor falls  the protection circuit will turn off himself  automatically  and the device will measure the input current again  Due to thermal  phenomenon in the standard resistor  precision of the measurement may be lower  during few  minutes  up to the standard resistor temperature will falls to the environment temperature      10  DISPLAYED VALUES CALCULATION    For simplicity of examples it s assumed that current input is selected  and all calculations  are related to this input  When voltage input is selecte
46. e device  To get the access to this  option special password is required   5465     next the device displays acknowledge question     SEt      Press  ENTER  to acknowledge the restoring of factory settings or  ESC  to cancel        7 3 14   SErv  menu    This menu contains the parameters for authorized service only  To enter this menu  proper service password must be entered  Improper settings can causes of damage of the  device     49    User manual   CONTROLLER PUR 94       7 4  MENU STRUCTURE    50    ESC    r          Measurement mode    Press and hold at least 2 seconds       SS                        4 digit user password entering  if it is different from  0000                                                                                                                                                                                                                                                                                       fe      5 ES     A rEL1 ja 1    Sour L          D Ed  5129 s   WS      Options similar dE         a to    rEL1    menu m z    te  E e WAM Options similar r   SEP Zb   2 a Io EL  menu    z JAZ Sle sev      u   pen    Options similar  a   to    rEL1    menu na    MENU   La y       a M  CL z z i   CJ    I      _  Parameter  PEER  t n T edition       ton  I      i 1    u     lt      toFF    u     GE Ee 2 ES e i  I   F     Ss ol InLo    Iu         M Sie GJ mHi    u    E  Y 2 2 t  inet E SE erg GJ Peri    u   i D 26 edition  Notice  D D  Quantity
47. e device is available in two power supply versions    Exact description of functions is provided in further section of the instruction    The PUR 94 is designed to regulate such processes as heating   cooling temperatures  with adjustable delay times for the operation of the output relays and controlling of valve levels     User manual   CONTROLLER PUR 94       3  TECHNICAL DATA    Power supply voltage   depending on version   External fuse  required   Power consumption    85   230   260V AC DC  50   60 Hz  separated    or 19   24   50V DC and 16   24   35V AC  separated   T   type  max  2A   max  6 5 VA Q 85   260V AC DC   max  6 5 VA Q 16V   35V AC   max  6 5 W   19V   50V DC       Current input  20 mA     Current measurement accuracy  Current input resistance    Accepted prolonged input overload    0720 mA  4 20 mA overload protected   input current is limited to 50 mA  typically       0 196    25  C    one digit  for 0 20 mA range      65 Q  typical 30 Q   20        Voltage input  10V range   Voltage measurement accuracy  Voltage input resistance    Accepted prolonged input overload    0 5 V  1 5 V  0 10 V  2 10 V     0 196    25 C    one digit  for 0 10 V range     gt  100 kW  while maintaining correct polarization   20        Voltage input  150mV range   Voltage measurement accuracy  Voltage input resistance    Accepted prolonged input overload    0 60 mV  0 75 mV  0 100 mV  0 150 mV     0 1     25 C    one digit  for 0 150 mV range    gt  1 5 MQ   20        RTD input  
48. e fill factor equal to 096       the upper limit of the range within which a change in the signal source causes a  change in the PWM output signal fill factor  Above this limit the PWM output signal  will have the fill factor equal to 10096     the duration of one cycle of the PWM output signal in the range 0   999 9 s      low state minimal time       high state minimal time     To ensure proper operation  the sum of the values of the  H on  and  HoFF   parameters should not exceed the value of the  Peri  parameter     The duration of the high and low status  parameters  H on  and  HoFF   are  calculated for each period  the  Peri  parameter  separately       this parameter defines how the relay reacts to an alarm state   The following options are available      noCH    relay do not change his state        on      relay will be turned on      OFF       relay will be turned off    Acti   this occurs only when the  modE  parameter is set to  PULS   it turns    on and disables responses to alarm state for the OC type output      noCH     the output status does not change during alarm state    USdu   in an alarm state  the output sets itself to the fill factor as set in  the  duty  parameter     duty     this occurs only when the  modE  parameter is set to  PULS   it  specifies the fill factor in the event of an alarm state     If parameter  modE  is set to    on         oFF      in      Out    or    PULS    the    critical  situation  means that allowable measurement range is e
49. e of displaying of the peak  drop  value  can be set from 0 0 to 19 9    sec  with 0 1 sec  resolution  If  HdiS    HOLD  then setting parameter  timE  0 0  causes holding peak value until  ESC  button is pressed  If    HdiS     rEAL  then  value  timE  0 0 means no holding        HdiS     type of displayed values      rEAL   current value is displayed    HOLd    peak  drop  value is displayed     47    User manual   CONTROLLER PUR 94          H r1       H r4     relay LED outputs  R1 R4  operation mode      rEAL     relay LED operates depend on the current value    HOLd    relay LED operates depend on the peak  drop  value      HOUt    current output operation mode      rEAL    current output operates depend on the current value    HOLd    current output operates depend on the peak  drop  value     7 3 10   SECu  menu  This menu contains presets connected with availability of other parameters         Scod     user password  4 digits number   If this parameter is set at value  0000   user  password is turned off     If the user do not remember his password  the access to the menu is possible  by the    one use password   To get this password please contact with  Marketing Division   Single use password  can be used only one time  after  that it is destroyed  Entering this password causes in clearing of user  password  it means sets the user password to   0000        The    one use password    can be used ONE TIME ONLY  it is impossible to use it  aD again  The    one use pass
50. e threshold is used  Figure 6 9  the relay can be turned on     modE       on   or off      modE       oFF   when the input signal value is contained in zone A  If two thresholds are  used  Figure 6 10  the relay will be turned on when value of input signal is contained in zone  A     modE       in   or zone B     modE       out   and turned off if the signal is contained in  the second one     state of  relay LED     SEtP  parameter          measure    U HYSt parameter  Figure 6 9  One threshold control of the relay LED outputs    state of  relay LED    SEEN    or GET SB        measure     HYSt         Figure 6 10  Two threshold control of the relay LED outputs    The relay outputs and LEDs  named R  can be controlled depend on both   the  current value and the peak value  when peak detection is active  of the input signal     27    User manual   CONTROLLER PUR 94       6 3 1  One threshold mode    Figure 6 11 presents the principle of relay outputs operation for one threshold mode  and  an example values of other parameters                                measured  displayed value A t  t t signal ty  SEtP  parameter  LE  CES ZS     lt   gt   expected signal value   a  zone A   NE   B it l  zone B i EN I M    allowed signal  bug NEEDLE E MENOR deviation   b  relay state 4 ME Dd EN NE ue   modE   on a E vz N MESE  ton  0      closed   NEN WW I riot  toFF   0     SEM M   oen i 11i      EEE g WR ime  c  relay state 4 bog i mE L4 i Lpd   modE oFF          ZEN    oil  ton   0   R 
51. e to unblock writes via RS 485 interface  The unblocking of the writes is possible from menu level only      the pairs of    X  Y  coordinates may be defined for any free point  The pair is  free   it means that particular point is  not defined  if    X    coordinate of this point is equal 8000h  After writing both X and Y coordinate the point is defined  and used in calculation of result  The coordinates of any point can be changed at any time     WON    a    11 2  TRANSMISSION ERRORS DESCRIPTION    If an error occurs while write or read of single register  then the device sends an error  code according to Modbus RTU specifications  example message no 1      Error codes    01h   illegal function  only functions 03h  06h and 10h are available    02h  illegal register address   03h   illegal data value   08h   no write permission  see   mbAc    parameter    A0h   exceed of upper border of input range   60h   exceed of lower border of input range    AOh and 60h codes can appear only during reg  01h is reading by 03h function  read of  a single register      67    User manual   CONTROLLER PUR 94       11 3  EXAMPLES OF QUERY ANSWER FRAMES    Examples apply for device with address 1  All values are represent hexadecimal     Field description    Device address on modbus network  Function code  Starting address  address of first register to read write  Hi and Lo byte   No  of registers to read write  Hi and Lo byte   Data byte count in answer frame  Data byte  Hi and Lo byte    CRC
52. ecifies the change in the setpoint fuzzy logic block  for  every unit specified in the parameter as  unit   Setting a  0  value disables  the fuzzy logic block        unit      this parameter specifies the unit of time in which the setpoint of the fuzzy  logic block will increase        HySt       the difference between setpoint specified for the controller  specified in the   SETP  parameter  and the setpoint of the fuzzy logic block  to which the  setpoint of the fuzzy logic block will seamlessly progress     User manual   CONTROLLER PUR 94       120    100    fuzzy value       80  60   SLOP  0      SLOP   1  40     SLOP  5      SLOP   10  20  0  unit    0 20 40 60 80 100 120 140    Figure 7 4  Change in the fuzzy setpoint depending on the setting of the SLOP parameter    7 3 8   bri  parameter       This parameter allows user to set bright of the LED display  bright can be set to  conventional values from 1 to 8     7 3 9   HOLd  menu    This menu contains parameters connected with peak detection function  See also full  description of the peak detection function in paragraph  DETECTION OF THE PEAK VALUES        modE   the type of detected changes of the input signal  can be set to values      norm   peaks  peak and next drop of the input signal of value equal at least  PEA       inv    drops  drop and next peak of the input signal of value equal at least  PEA         PEA     minimal detected signal change classified as peak or drop  see Figure 6 4    timE      maximum tim
53. ecommended values  In such cases forced cooling of the unit must  be considered  e g  by using a ventilator      The unit is designed for operation in an industrial environment and must  not be used in a household environment or similar        2  GENERAL CHARACTERISTICS    The PUR 94 device has a universal input that can be configured to work as  a current  input  in the range 0   20mA   as a voltage input  in the range 0 10V and 0 150 mV   as an  RTD input  operating with Pt 100 500 1000 sensors  and as a TC input  operating K  S  J  T  N   R  B and E type thermocouples   The device automatically compensates the temperature of  cold junction of thermocouple sensor  RTD and TC inputs feature full linearization of  characteristics  Only one input type can be used at a time  The exact measurement ranges of  the inputs are quoted in the next chapter  The measurement is shown on a 4 digit LED display    The device can be equipped with 1  2 or 4 relay outputs and one OC type output  not  available in the 4 relay output version   which can be controlled from the measuring inputs via  Modbus protocol or a PID controller implemented in the device with two control loops and an  auto tuning option  Optionally  the device  in version with two relays and OC type output  can  be equipped with  an active current output  a passive isolated current output or an active  voltage output  An RS 485 communication interface and a sensor transducer power supply  output are available as standard  Th
54. ending on version    uo       JS    R1 R2   optional   optional                                   DCH  Umax   30V DC   Imax  30mA  Pmax   100mW    Figure 4 11  Terminals description  two relay  one OC type and one passive current outputs     Power  24V  5    10  RS   485  supply active Imax 100mA GND   DATA      depending on version  Voltage output   Uo   DATA   A       optional       A   s  e 7  s  e      optional                                   optional   optional        OC3  Umax   30V DC   Imax  30mA  Pmax   100mw       24V DC                                                         Figure 4 13  Connection of 2 wire current transducer    14    User manual   CONTROLLER PUR 94             24V DC                                                                                                                   Figure 4 15  Connection of voltage transducer    Temperature sensor can be connected to the device in typical 4 wire circuit  Figure 4 16a  or  3 wire circuit  Figure 4 16b   Due to precision of measurement 4 wire circuit is recommended     If 2 wire circuit is used  the resistance of wires should be as small as possible  to  avoid of measurement errors  Measured value can be corrected  constant  correction  using  toFS  parameter from menu    inPt     Due to low precision 2 wire  connection is not recommended     When 4 wires or 2 wires connection is used  the resistance of particular wires   Ra   Rd  CAN BE DIFFERENT  When 3 wires connection is used  the resistance of
55. eter in   PArC    menu  no decimal point included  FBh Yes    999   9999   OF C    parameter in   PArC    menu  no decimal point included          FCh Yes 0   999  Lo C  parameter in PArC  menu  no decimal point included       FDh Yes 1 1000    Hi C    parameter in  PArC  menu  no decimal point included       FEh Yes 0  9999      dEAd    parameter in ConF  menu  no decimal point included       FFh Yes 0  9999    StAr  parameter in   ConF    menu  no decimal point included        dSrC  parameter in  ConF  menu     Tm Yes 1502 0    Err  option  1    LooP  option         InEr  parameter in  ConF  menu   101h Yes 0 3 0      OFF    option  1      HArd    option  2      mEdi    option   3   SoFt  option     102h Yes 0   9999    SLOP    parameter in    FuZL    menu  no decimal point included             unit    parameter in    FuZL    menu     d yes BPE 0    SEC  option  1      min    option  2    hour  option        104h Yes 0   9999  HySt  parameter in  FuZL  menu  no decimal point included                      105h No   1000   1000   Value of regulator s output  in percentage          these registers are active only if device is equipped with current or voltage output     after writing to register no 20h the device responds with an  old  address in the message      after writing to register no 22h the device responds with the new baud rate      the value of the    mbAc       parameter is also connected to write to this register  so it is possible to block a writes  but  impossibl
56. eturning to menu        Functions of buttons when editing numeric and switching parameters     While editing numeric parameter      change of current  flashing  digit    Slide change of value  acceleration  deceleration  direction change   While editing switch parameter   selection of switch parameter     If numerical parameter is being edited  a short press of  ENTER  button  change edited position  A long press of  ENTER  button  at lest 2 sec    causes of display a  SEt   ask  which allow user to make sure if change of  the parameter value is correct  If switch parameter is being edited  a short  press of  ENTER  button causes of display a  SEt   ask  When  ENTER   button is pressed again  while  SEt   is displayed  the new value of the  parameter is stored in EEPROM memory     ENTERI    Pressing this button operator can cancel the changes done up to now  if they  MENU were not approved by  ENTER  button after the    SEt     ask  and come back  to menu    7 3  MENU DESCRIPTION    M       WEI   password checking  If some password different from    0000    is set  then every  enter to main menu follows the entering of password  If entered password is  correct then first menu position will be displayed else warning  Err   and unit  returns to measurement mode        Due to problem with direct displaying of  m  and    K    letters  they are exchanged   aD with special signs    jm    for  m  and    F     for    K    respectively  However  in user  manual letters    m    and    
57. free time of the unit s operation    In cases where the unit gets dirty do not clean with solvents  For cleaning use warm water with  small amount of detergent or in the case of more significant contamination ethyl or isopropyl  alcohol     A Using any other agents can cause permanent damage to the housing        RZ   Product marked with this symbol should not be placed in municipal waste  Please  f X   check local regulations for disposal of electronic products              5  FRONT PANEL DESCRIPTION       alarm LED indicator  AL  ML display  Rie  R26  R3       Thresholds exceeding A bot    LED indicators  R  res              programming  pushbuttons    Symbols and functions of push buttons     Symbol used in the manual   ESC MENU   MENU Functions       Enter to main menu   press and hold by at least 2 sec      Exit the current level and Enter to previous menu  or measure mode     Cancel the changes made in parameter being edited    Symbol used in the manual   ENTER    Functions      Start to edit the parameter     Enter to the sub menu      Confirmation of changes made in parameter being edited    Symbol used in the manual       v   Functions       Change of the present menu     Modification of the parameter value     Change of the display mode     ENTER    19    User manual   CONTROLLER PUR 94       6  PRINCIPLE OF OPERATION    After turning the power supply on  device ID and software version are showed on the  display  next the controller goes to the measurement mode     
58. hat complies with the governing  regulations       Disconnect the power supply prior to starting assembly          Check the connections are wired correctly prior to switching the unit on     prepared  The thickness of the material of which the panel is made must not exceed  5mm  When preparing the mounting hole take the grooves for catches located on  both sides of the housing into consideration  Figure 4 1  4 2   Place the unit in the  mounting hole inserting it from the front side of the panel  and then fix it using the  brackets  Figure 4 3   The minimum distances between the centre points of multiple  units   due to the thermal and mechanical conditions of operation   are 115 mm x  67mm  Figure 4 4      i In order to install the unit  a 90 5 x 43 mm mounting hole  Figure 4 1  4 2  must be    User manual   CONTROLLER PUR 94       90 5 mm    YMA                      43 mm    8             mm  Wf    mm max  5 mm    1mm   gt                 iL  7    Figure 4 1  Recommended mounting hole dimensions    92 mm    YW    7    2 max  5 mm     gt     lt           43 mm                Figure 4 2  Allowable mounting hole dimensions                                           5mm       eg  e    Figure 4 3  Installing of brackets  and dimensions of connectors     User manual   CONTROLLER PUR 94       115 mm    EE  Ex          67 mm             Figure 4 4  Minimum distances when assembly of a number of units    4 3  CONNECTION METHOD    Caution    A     10         Installation should be co
59. he range due to formula     Out    A    A x    Lo r    96   where   A     lower signal value range limit     42    User manual   CONTROLLER PUR 94       This parameter can be set from 0 to 99 9   for active current output and active  voltage output  or from O to 29 9   for passive current output      Parameter  Hi r    defines higher border of the range due to formula    Out    B    B x    Hi r        where    B     higher signal value range limit    This parameter can be set from 0 to 19 9   for active and passive current  output  or from O to 9 9   for active voltage output      In example on page 58 of the DISPLAY VALUES CALCULATION paragraph  the procedure of the analogue outputs determining is presented in details      AL    this parameter determines the behaviour of analogue output if any critical situation  occurs  According to version of the device  this parameter can be set     For active current output      noCH     current will not change      22 1      current will be set to 22 1 mA      3 4      current will be set to 3 4 mA      0 0      current will be set to 0 mA     For passive current output    noCH   current will not change   22 1      current will be set to 22 1 mA      3 4      current will be set to 3 4 mA     For active voltage output    noCH   voltage will not change      11 0      voltage will be set to 11 V        5 5      voltage will be set to 5 5 V   1 2      voltage will be set to 1 2 V      0 6      voltage will be set to 0 6 V      0 0      vol
60. held while button     is still pressed the increasing slow  down and will be kept on lower speed    To decrease edited value press  or press and hold    v  button only  The decreasing  became quickest as long as button  v  is pressed  To slow down the decreasing  button  4     33    User manual   CONTROLLER PUR 94       can be used  If     is pressed shortly  and button  v  is still pressed   decreasing slow down for  a moment only  if     is pressed and held while button  v  is still pressed the decreasing slow  down and will be kept on lower speed     Press  ENTER  at least 2 seconds to accept the changes  after that question    Set     is  displayed  and user must to confirm  or cancel  the changes  To conform changes  and story it  in EEPROM  press  ENTER  button shortly after    SEt     is displayed  To cancel the changes  press  ESC  button shortly after    SEt     is displayed  After that device returns to the menu     7 2 3  Switch parameters     LIST    type     Switch parameters can be described as a sets of values  a lists  out of which only one of  the options available on the list can be selected for the given parameter  Options of switching  parameter are selected using       v  keys    Short pressing of  ENTER  causes in displaying of the acknowledge question   SEt     If  key  ENTER  is pressed again  the changes are accepted  stored in EEPROM end the edition  process finished  Pressing the key  ESC  after    SEt     causes in cancelling of made changes  and r
61. i Wa A e cta pared NOA AA PY aaa AAA 60  11 2  TRANSMISSION ERRORS DESCRIPTION      11 3  EXAMPLES OF QUERY ANSWER FRAMES    12  DEFAULT AND USER S SETTINGS LIST                         User manual   CONTROLLER PUR 94          Explanation of symbols used in the manual     This symbol denotes especially important guidelines concerning the installation and  operation of the device  Not complying with the guidelines denoted by this symbol  may cause an accident  damage or equipment destruction     IF THE DEVICE IS NOT USED ACCORDING TO THE MANUAL THE USER IS  RESPONSIBLE FOR POSSIBLE DAMAGES       This symbol denotes especially important characteristics of the unit   Read any information regarding this symbol carefully    1  BASIC REQUIREMENTS AND USER SAFETY       A   The manufacturer is not responsible for any damages caused by  inappropriate installation  not maintaining the proper environmental  conditions and using the unit contrary to its assignment       Installation should be conducted by qualified personnel   During installation all  available safety requirements should be considered  The fitter is responsible for  executing the installation according to this manual  local safety and EMC  regulations       If the device is equipped with PE connector  it should be connected to PE wire   Otherwise PE wire should be connected to GND connector       The unit must be properly set up  according to the application  Incorrect  configuration can cause defective operation  which 
62. ial block   enables even more precise control over the physical object  optimizing  but also protecting the  object against over regulation or an excessive rise of the control value        22    User manual   CONTROLLER PUR 94       Setpoint  SEtP             Fuzzy logic block                   Modbus  Master                                       Sour  Qut  rELWOCx    1    I  Fuzzy 4  gt    x  gt  modE      setpoint    PID H      ihe    e    I    d ecc ME VR APTE un Controlled    nds  Analogue     object     i e Sou output CS     A N  gt   Omod       gt           PID C i       Measurement  input  Feedback  Z   inPt   lt                                                                                                     Figure 6 5  The general structure of the PUR 94 device                                                                               Upper limit  Hi H  Offset HiG   gt   1 OF H  orc Output  Proportional Integral limits  Setpoint Dead zona block block    SEIP A      PH tI H idl  or  gt    gt  gt   dEAd  gt   gt   gt   gt    Fuzzy   P C LC  setpoint  lt    Err Derivative Inertial  block block  LooP  Feedback  gt   gt e N  gt   ee  gt   InEr  Lower limit  Lo H  Lo C    Figure 6 6  General scheme of the PID controller implemented in the PUR 94 device    Configuring the PID controller   The PID controller can be configured in two ways  manually and automatically    In manual mode  the user defines all factors and additional elements of the controllers   fuzzy logic  
63. inertia  output limiting and dead zone  at their own discretion  The settings chosen  by the device in automatic mode can also be improved and fine tuned  The user can disable  each block of the PID controller as well as additional blocks  This is done by setting the zero  value or OFF option in the selected parameter    In automatic mode  in the auto tuning process using the Ziegler Nichols method  the  device calculates and tunes the parameters P  I and D of one of the controllers loops   Additional blocks  fuzzy logic  inertia  output limiting and dead zone  are not configured in this  mode and the user must choose them himself according to respective applications  The auto   tuning process is described later in this chapter     23    User manual   CONTROLLER PUR 94       Fuzzy logic block  FuZL submenu    Step changes in the setpoint can be mitigated by the use of the fuzzy logic block  which  inserts speed control of the setpoint change  Thanks to its application the user may dictate  how quickly a fuzzy value approximates the target value in the process  SEtP     This feature is particularly useful in systems where too rapid change in the setpoint and   as it is possible in such a situation  the control signal  could lead to unwanted behaviour on the  part of a object  for instance destruction of the product being manufactured  It is also possible  to set the minimum difference between the setpoint  SEtP   and the fuzzy setpoint  beyond  which the controller step change
64. int is greater than the measured  value  the PID H controller s loop will be tuned  and when the setpoint is less than the  measured value  the PID C controller s loop will be tuned    The process of auto tuning in this mode may commence subject to the following  conditions    1  The value measured by the device must be greater than six fifths of the setpoint  when   the PID H controller is tuned  or the value measured by the device must be greater than   six fifths of the setpoint  when the PID C controller will be tuned    2  The source of at least one of the device s outputs must be PidH if the loop of the   PID H controller will be tuned  or the source of at least one of the outputs must be PidC    if the loop of the PID C controller will be tuned  In addition  these outputs can not be set   in the noAC mode     The At H mode    Auto tuning of the PID H loop  the At H mode   during which the device uses and adjusts  only that loop  The second loop remains idle and its setting will not change following the  process    The process of auto tuning in this mode may commence subject to the following conditions    1  The value measured by the device must be less than four fifths of the setpoint    2  The source of at least one of the device s outputs must be Pid H  Additionally  those   outputs cannot be set in the noAC mode     The At C mode   Auto tuning of the PID C loop  the At C mode   during which the device uses and adjusts  only that loop  The second loop remains idle an
65. l parameters edit mode dig 49                      75       fj simex  SIMEX Sp  z 0 0   ul  Wielopole 11    80 556 Gda  sk  Poland    tel     48 58  762 07 77  fax    48 58  762 07 70    http   www simex pl  e mail  infoQsimex pl    
66. menu   The detection of the peak can be done if  the measured signal raises and drops of value at least equal to parameter  PEA   Detected  peaks are displayed during the time defined by parameter  timE   If a new peak will be  detected while one is displayed  this new peak will be displayed and display time counter will  be cleared  Figure 6 4     If no peaks are detected while time  timE  elapses  device starts to show the current  value of input signal again  If  HdiS   HOLD  then setting parameter  timE  0 0 causes  holding peak value until  ESC  button is pressed  If    HdiS     rEAL  then value  timE  0 0  means no holding  Displaying peak value is signalized by flashing most right decimal point    The relays LEDs can be controlled depend on the current value of input signal or the  peak value  see  HOLd  menu         21    User manual   CONTROLLER PUR 94       a measure     timE         timE                 time    real measurement result  display value    Figure 6 4  Process of peaks detection    6 2  PID REGULATORS    Operation of the PID controller involves calculating the error value ensuing from the  difference between the setpoint and the measured value and responding in such a way as to  minimize the calculated error by appropriately adjusting the signal connected to the input of  the regulated object    Controllers are mainly used in industrial control systems that have large time constants  vulnerable to interference from the input of the regulated object  and
67. mode    Enn  e SS  0    dig  mode  1      SLid    mode     Sour    parameter in    rEL1    menu   AP   ONES 0 3   0     nPU    option  1      modb    option  2    PidH  option  3    PidC   option    modE  parameter in  rEL1  menu   31h Yes 0 5 0      noAC    mode  1      on    mode  2      oF F    mode  3      in    mode   4      out    mode  5      PULS    mode  32h Yes    999   9999     SEtP    parameter in    rEL1    menu  no decimal point included  33h Yes  999   999   HySt  parameter in    rEL1    menu  no decimal point included       t on    parameter in    rEL1    menu  expressed in tenth of seconds or  M Ke eee tenth of minutes depend on    unit    parameter   register no  36h   R    toFF    parameter in    rEL1    menu  expressed in tenth of seconds  SS   e 0 2933 or tenth of minutes depend on    unit    parameter   register no  36h   36h Yes 0 1    unit    parameter in    rEL1    menu   0   seconds  1   minutes  37h Yes 022    AL    parameter in    rEL1    menu  only when rEL 1 is relay output   0    no changes  1   on  2   off  38h Yes    999   9999      SEt2    parameter in  rEL1  menu  no decimal point included  39h Yes    999   9999    InLo  parameter in  rEL1  menu  no decimal point included  3Ah Yes    999   9999      InHi    parameter in  rEL1  menu  no decimal point included  3Bh Yes 079999     PEri    parameter in  rEL1  menu  no decimal point included  3Ch Yes 079999      Hon    parameter in  rEL1  menu  no decimal point included  3Dh Yes 079999    HoFF   
68. n be set from 0 to 19 9     In example no 1 of the DISPLAY VALUES CALCULATION paragraph the  procedure of the permissible input range determining is presented in details     If the measurement value do not exceeds permissible measurement range but  displayed value exceeds range  999   9999  the warning     Ov     is displayed rather  than the calculated result     7 3 6   OutP  menu       This menu contains parameters of analogue output control  Menu is available if the    device is equipped witch analogue output     Analogue output can be controlled depend on both present measured value and  peak value  if peak detection is enabled       OSou   the source for the analogue output        InPU       the output is controlled using signals from the measurement input     modb   the output is controlled using Modbus registers       PidH     the output is controlled by the positive part of the PID controller s  characteristics     PidC   the output is controlled by the negative part of the PID controllers  characteristics     41    User manual   CONTROLLER PUR 94          Omod      analogue output mode  Depending on version of the device there are following  options     For active current output        OFF      current output disabled     0 20    current output enabled with 0   20 mA mode      4 20      current output enabled with 4   20 mA mode    modb    current output controlled via RS 485 interface     For passive current output        OFF      current output disabled      4 20 
69. nal                                   OC2  Umax   30V DC   Imax  30mA  Pmax   100mW    Figure 4 7  Terminals description  one relay and one OC type outputs     R4  Power  optional   24V  5    10  RS   485  DATA     supply Imax   100mA GND   depending on version  B H Uo      DATA     Cl  Gi Gere    31 34         EJ Lo  od Y     R1   optional   optional   optional  RTD TC                                  Figure 4 8  Terminals description  four relay outputs     12    User manual   CONTROLLER PUR 94       Power  24V  5    10  RS   485  supply Imax   100mA GND DATA      depending on version    uo    DATA       Z n c  n c  4 A      omei    Pis  M a oo o E PO dM  RI R2 Al Fl UJ    OC3  Umax   30V DC   Imax   30mA  Pmax   100mW     1 2  BI  EiT Tefel                                optional   optional        Figure 4 9  Terminals description  two relay and one OC type outputs     Power  24V  5    1096 RS   485  supply active Imax 100mA GND   DATA      depending on version  Current output   Uo     DATA      optional  A A      GA be  Bere    10  11 12 13 14 15       31 32 33 34 35      pe 31 34 y mA     optional                     R2   optional   optional  RTD                      OC3  Umax   30V DC   Imax  30mA  Pmax   100mW    Figure 4 10  Terminals description  two relay  one OC type and one active current outputs     13    User manual   CONTROLLER PUR 94       Power puma  24V  5    10  RS 485  supply  a  Imax   100mA GND DATA     DATA        a   1 2   s e 7 s o     optional    dep
70. ncluded  4Ch Yes    999   9999      InLo    parameter in    rEL2    menu  no decimal point included  4Dh Yes    999   9999   InHi  parameter in    rEL2    menu  no decimal point included  4Eh Yes 0 9999      PEri    parameter in    rEL2    menu  no decimal point included  4Fh Yes 0   9999  H on    parameter in    rEL2    menu  no decimal point included  50h Yes 0   9999  HoFF  parameter in  rEL2  menu  no decimal point included  51h Yes 021  Acti  parameter in  AL  menu   only when rEL2 is OC type output    0    hoCH  option  1    USdu  option   52h Yes 0   1000    duty    parameter in    AL    menu  only when rEL2 is OC type output   e  54h Yes    999   9999     OFFS    parameter in    rEL2    menu  no decimal point included  55h Yes O   1000  SEnS  parameter in   rEL2    menu  no decimal point included     Sour    parameter in    rEL3    menu   56h Yes 0 3  0     InPU    option  1      modb    option  2      PidH    option  3    PidC   option      modE    parameter in    rEL3    menu   57h Yes 0 5 0      noAC    mode  1      on    mode  2      oF F    mode  3      in    mode   4      out    mode  5      PULS    mode  58h Yes    999   9999     SEtP    parameter in    rEL3    menu  no decimal point included  59h Yes  999   999     HySt    parameter in    rEL3    menu  no decimal point included  TOEA EE a  5Bh Yes 0   999    toFF    parameter in    rEL3    menu  expressed in tenth of seconds          or tenth of minutes depend on  unit  parameter   register no  58h            
71. nd  returns to the measurement mode  only if no parameters are in editing mode      7 2  PARAMETERS EDITION    To start edition of any parameter user should select name of desired one using      v   buttons and then press  ENTER         7 2 1  Numeric parameters  digit change mode        Numerical parameters are displayed as decimal numbers  The mode of its new value  entering depends on chosen edit method   see parameter    Edit        In mode    by digit    Edit   dig   pressing one of the keys     or  v  causes change of  current position  flashing digit  or the sign        Short pressing of the  ENTER  button causes  change of the position  digit     Press  ENTER  at least 2 seconds to accept the changes  after that question    SEt     is  displayed  and user must to confirm  or cancel  the changes  To conform changes  and story it  in EEPROM  press  ENTER  button shortly after    SEt     is displayed  To cancel the changes  press  ESC  button shortly after  SEt   is displayed  After that device returns to the menu        7 2 2  Numeric parameters  slide change mode     In    slide change    mode     Edit     Slid      buttons     and  v  has different functions    To increase edited value press  or press and hold      button only  the increasing  became quickest as long as button     is pressed  To slow down the increasing  button  v  can  be used  If  v  is pressed shortly  and button     is still pressed   increasing slow down for  a moment only  if  v  is pressed and 
72. nducted by qualified personnel   During installation all  available safety requirements should be considered  The fitter is responsible for  executing the installation according to this manual  local safety and EMC  regulations       The unit is not equipped with an internal fuse or power supply circuit breaker   Because of this an external time delay cut out fuse with a small nominal current  value must be used  recommended bipolar  max  2A  and a power supply circuit   breaker located near the unit  In the case of using a monopolar fuse it must be  mounted on the phase cable  L        The power supply network cable diameter must be selected in such a way that in  the case of a short circuit of the cable from the side of the unit the cable shall be  protected against destruction with an electrical installation fuse       Wiring must meet appropriate standards and local regulations and laws       In order to secure against accidental short circuit the connection cables must be  terminated with appropriate insulated cable tips       Tighten the clamping screws  The recommended tightening torque is 0 5 Nm   Loose screws can cause fire or defective operation  Over tightening can lead to  damaging the connections inside the units and breaking the thread       In the case of the unit being fitted with separable clamps they should be inserted  into appropriate connectors in the unit  even if they are not used for any  connections       Unused terminals  marked as n c   must not be 
73. ple 2     a  lin  10 mA and      0 375  Accordingly to expression on page 55 for square root characteristic   40 375 x  1200     300     919   and next  the    Lo C    value is added to the result   so the displayed value   W   919     300    619       b  lin   2 5 mA and h    0 0938   normalized result is negative   so the displayed value is equal  to    Lo C    parameter  W      Lo C       300     c  ln   20 5 mA and I    1 0313   W   1223     57    User manual   CONTROLLER PUR 94       Example 6  The user defined characteristic    Let the input mode   4 20 mA  and the user selected the 10 segment characteristic  To do this  it is necessary to enter X and Y coordinates of 11 points  see Menu  inPt      The calculations will be done for three different input currents from example 2  so in  calculations some of the segments will be used only     Let the following points will be given   X1      00 0      Y1       50 0      X2     10 0      Y2       30 0        X6    30 0    Y6      30 0      X7      40 0     Y7      80 0        X10      90 0      Y10      900 0      X11   400 0    Y11      820 0        Additionally all other points must to be defined and stored in the device memory     a  ln 210 mA and      0 375   The segment defined by X6      30 0     and X7      40 0     for this    will be selected  Accordingly  to expressions given for user defined characteristic  see page 55  X6 PL    30  Y6 PL    30   X7 PH    40  Y7 PH    80 and l    0 3   the displayed value       Y 
74. r than the value of  mbtO  parameter  the  relays which are controlled via RS 485 interface  will set to alert state  see  OUtP   menu  and    rEL1    menu description   Parameter    mbtO    can be set to values  from 0 to 99 seconds  The value 0 means that the time will be not controlled      rESP    this parameter defines minimal  additional  delay between the Modbus message  and the answer of the device  received and sent via RS 485 interface   This  additional delay allows the device to work with poor RS converters which do not  works properly on baud rates higher than 19200  This parameter can be set to one  of values      Std    answer as quick as possible  no additional delay  5 10c     20c   answer delayed of 10  20  50  100 of 200 chars respectively  where    bod one character time depends on selected baud rate     200c     In the most cases parameter  rESP  should be set to  Std   no additional delay    aD Unfortunately for some third party RS converters  rESP  should be adjusted  experimentally  Table 7 1 contains most frequently used values         bAud  parameter  38 4   57 6     115 2      rESP  parameter    10c        20c       500                         Tab 7 1  Settings of    rESP    parameter    7 3 12   Edit  parameter   This parameter allows to change the edition mode of numerical parameters    dig    the change to    by digit    mode    Slid      slide change mode        7 3 13   dEFS  parameter   This setting allows to restore the factory settings of th
75. range   6   0 60 mV range  7   0 75 mV range  8   0 100 mV range   10h Yes 0    20 9   0 150 mV range  10   Pt 100  11   Pt 500  12   Pt 1000  13   thermocouple input K  14   thermocouple input S   15   thermocouple input J  16   thermocouple input T   17   thermocouple input N  18   thermocouple input R   19   thermocouple input B  20   thermocouple input E   i  CHAr  parameter in  InPt  menu  characteristic type   11h Yes 0 3     F   d  0   linear   1   square  2   square root  3   user defined  12h Yes 0   255  FiLt  parameter in    InPt    menu  time constant in seconds   13h Yes 0 3    Pnt  parameter in    InPt    menu  the copy of 03h register  decimal    point position   0     0     1   0 0     2       0 00   3      0 000     14h Yes    999   9999      Lo C  parameter in  InPt  menu  no decimal point included  15h Yes    999   9999      Hi C  parameter in  InPt  menu  no decimal point included  16h Yes 0   999  Lo r    parameter in    InPt    menu  in 0 1   17h Yes 0   199  Hi r    parameter in  InPt  menu  in 0 1   sca z   toFS  parameter in  InPt  menu  shift of measurement scale    18h Ma 99  99   expressed by 0 1  C  for RTD input  or by 1 0  C  for TC input   19h Yes 022    Conn    parameter in    InP  menu  RTD input connection method    0      4 in     1      3 in     2      2 in  20h  Yes 0  199 Device address  21h No 22DCh Device identification code  ID      bAud    parameter in    rS    menu  baud rate    22h  Yes 0 7 0   1200 baud  1   2400 baud  2   4800 ba
76. resistive   Measurement range  Measurement accuracy    Measurement wires resistance    Pt 100  Pt 500 Pt 1000   100  C    600  C   0 1    25  C    one digit    max  20 Q  every wire     User manual   CONTROLLER PUR 94          Thermocouple input    Thermocouple input range    Measurement accuracy    Accuracy of cold ends temperature  compensation    K  S  J  T  N  R  B  E     200  C    1370  C   50  C    1768  C   210  C    1200  C   200  C     400  C     200  C    1300  C     50  C    1768  C   250  C    1820  C   200  C    1000  C      J  E  0 1    25  C    one digit        0 296   25  C    one digit    T  R  B    0 5    25  C    one digit    1  C      OZA MBDZACHA       Sensor power supply output    24V  5    10    max  100 mA  stabilized       Relay output    0  1  2 or 4 NO  1A 250V AC  cos 9   1        OC type output    0  1  2 or 4  30mA   30VDC   100mW       Active current output   optional  for two relays and one  OC type output version only     Load resistance max     range max  0   24 mA    700 Q       Passive isolated current output   optional  for two relays and one  OC type output version only     Supply voltage    Load resistance max     range max  2 8   24 mA    Us   9 5   36V   Us     9 5V   24mA  kQ        Active voltage output   optional  for two relays and one  OC type output version only     Load resistance min     range max  0   11V    2000 Q       Temperature stability  Display range  6    50 ppm     C   999   9999  plus decimal point    User manual   C
77. ribed for both of  these parameters are met simultaneously       turn on delay time  the relay is turned on with delay equal  t on  if the input value  exceeds appropriate border value  defined with threshold and hysteresis   at  least  t on  time   t on  range 0   99 9  defined with 0 1 sec  resolution  Unit of  this parameter is set by  unit  parameter       turn off delay time  the relay is turned off with delay equal    toFF    if the input value  exceeds appropriate border value  defined with threshold and hysteresis   at  least    toFF    time     toFF    range 0   99 9  defined with 0 1 sec  resolution  Unit of  this parameter is set by  unit  parameter     If time when the input signal exceeds some border value is shorter than  t on  or   toFF  time  the relay do not change its state  see paragraph  6 3  CONTROL  OF THE RELAY OUTPUTS        unit of time for    t on  and    toFF    parameters  Can be set on one of two values    min    minutes    SEC    seconds     User manual   CONTROLLER PUR 94       d       InLo      InHi      PEri          H on          HOFF       e           AL       The above mentioned parameters do not occur when the    modE  parameter is  set to  PULS   In such a configuration the user has at his disposal the  parameters   InLo    INHI    Peri    H on  and  HoFF        the lower limit of the range within which a change in the signal source causes a  change in the PWM output signal fill factor  Below this limit the PWM output signal  will have th
78. rolling process  the relay output changes his  state depends of both  SEtP    and    SEt2    thresholds in similar way as it was described in one  threshold mode    If two threshold mode is used     modE    parameter defines state of the relay output when  the input value occurs in a particular zone defined by border values of both thresholds  The  relay can be turned on if the input value is contained in zone A     modE       in   or zone B      modE       out   and turned off if it is contained in the second one  Figure 6 12      The sequence of thresholds    SEtP    and  SEt2  can be set in any order  due to the  control of relay outputs is done depend on difference between thresholds values   zone A   and outside of threshold values  zone B      6 3 3  PWM Controlling    In devices equipped with the OC type output  the user can switch this output to the  special    PULS    mode  This mode allows the user to adjust the output pulse width  Pulse  Width Modulation or   by means of a source signal defined in the parameter  Sour  and the  parameter settings  InLo    InHi    PE      Hon      HoFF  and  AL   for the exact  description of these parameters  see chapter 7 3 1     rEL1    menu     PWM allows the user to change the width  duration  of high and low levels by defining the  range of the input signal  in  InLo  and  INHi  parameters   the duration of this signal    PEri   parameter  and the source value   Sour    parameter   The input signal  changing within this  range 
79. s the fuzzy setpoint to the setpoint  SEtP   This is defined by  the HYST parameter  Both controllers use the same settings of the fuzzy logic block     PID H controll loop    120    100 CE    Histeresis    setpoint       60    FuZL on  40     FuZL off  20  0  0 20 40 60 80 100 120 140 160 180 200    time    Figure 6 7  Comparison of the PID H controller s response to a change in the setpoint using  and without the use of fuzzy logic    24    User manual   CONTROLLER PUR 94       PID C controll loop    160  140    120           FuZL on     FuZL off    100    setpoint    80  60  40    20   NA    0 20 40 60 80 100 120 140 160 180 200  time    Figure 6 8  Comparison of the PID C controller s response to a change in the setpoint using  and without the use of fuzzy logic    The inertial block   This is used to smooth the progress of the derivative block response  in other words to  eliminate overly dynamic changes in the output signal   s value caused by the presence of  measurement process noise  The use of the inertial block lengthens response time  but  provides protection against over regulation that could lead to failures in the controlled system     Dead zone   The insertion of this parameter provides the possibility of  anesthetising  the control  system to small deviations in the measured value from the setpoint  The dEAd parameter  specifies the minimum deviations to which the controller should react  The use of the dead  zone is justified in systems for which oscillation
80. shielded  must be used with RS 485 serial  transmission connections          n the case of measurement or control signals are longer than 30m or go outside of the  building then additional safety circuits are required         Inthe case of interference from the power supply side the use of appropriate interference  filters is recommended  Bear in mind that the connection between the filter and the unit  should be as short as possible and the metal housing of the filter must be connected to  the earth with the largest possible surface  The cables connected to the filter output must  not be run with cables with interference  e g  circuits controlling relays or contactors      Connections of power supply voltage and measurement signals are executed using the  screw connections on the back of the unit   s housing           Figure 4 5  Method of cable insulation replacing and cable terminals    AN All connections must be made while power supply is disconnected      11    User manual   CONTROLLER PUR 94       Power  24V  5    10  RS   485  supply Imax   100mA GND   DATA      depending on version    uUo    DATA             n c  n c  4 A   1 2   s e 7 e 9     AC    R1   optional   optional                                   Figure 4 6  Terminals description  two relay outputs     Power  24V  5    10  RS   485  supply Imax   100mA GND DATA   DATA      depending on version    Uo     n c  n c  A 4    Ce  G4  Gere        Nc  nc  EE    H      a OC2   m U     optional  p   S   lol     optio
81. single  actuator element  Once completed  the device automatically switches to PiD  mode      the auto tuning procedure for the PID C loop in an arrangement with a single  actuator element  Once completed  the device automatically switches to PiD  mode       the setpoint of the controllers  The initial state of the controlled object to which the    controllers will progress        PATH         p  H        tH        td H        OF H        Lo H        Hi H          PArC         p  C        tlc        td C        OF C        Lo C        Hi C       44      PID H control loop coefficients       proportional gain factor P      integral gain factor I      derivative gain factor D      value by which control loop limitations are shifted     lower limit of the control loop s characteristics      upper limit of the control loop s characteristics        PID C control loop coefficients       proportional gain factor P      integral gain factor I      derivative gain factor D      value by which control loop limitations are shifted     lower limit of the control loop s characteristics      upper limit of the control loop s characteristics     User manual   CONTROLLER PUR 94        ConF   input settings of the controller       dEAd      width of the dead zone  For the definition of the dead zone  see chapter  B    d  Nie znaleziono   r  d  a odwo  aniaB    d  Nie znaleziono   r  d  a  odwo  ania     StAr   the parameter  expressed in 96  allowing to set the controller s output status    a
82. t the time of launch  depending on the controller s output parameters        dSrC       this parameter defines how to interpret the feedback used to calculate the  controller s response        Err      used for calculations is the output of the controlled object following prior  calculation of the error at the controllers input and a check on the  condition of the controllers operation as a result of dead zone range  being exceeded       LooP       used for calculations is the object s output without calculating the error  on the controller s input or taking into account the dead zone      InEr   the settings of the inertial block  For the definition of the inertial element refer  to chapter B    d  Nie znaleziono   r  d  a odwo  aniaB    d  Nie znaleziono    r  d  a odwo  ania     27 where  Iner     response of the inertial block   Iner    T t     successive moments in time   T   the inertia factor specified by the parameters        OFF     inertia is disabled  The Iner block   1      HArd      factor T   0 07      mEdi     factor T   0 14    SoFt   factor T   0 21     45    User manual   CONTROLLER PUR 94          A       N    innertial block  response       CH       hard  6    medi      soft    0 02 04 06 08 1 12 14 16 18 2    seconds    Figure 7 3  Responses of the inertial block depending on factor T          FUZL      an additional fuzzy logic block  It enables a smooth change of the setpoint for the    46    soft control of the object        SLOP      this parameter sp
83. tage will be set to 0 V     When the critical situation goes  the output signal will be set to value calculated due to  formulas given above     7 3 7     CtrL    Menu    The menu includes configuration options for the control loops of the PID controller  featured in the device        43    User manual   CONTROLLER PUR 94       Setpoint  SEIP    setpoint                                                                                           Upper limit  Hi H  Offset Hi C   gt  1 OF H  OF C Output  Proportional Integral limits  Dead zone ea Me Y      P H tl H Ap  or  gt   dEAd  gt    gt   gt   gt  y k  Fuzzy   P C LC Z  Err Derivative Inertial S  block block  LooP    Feedback  gt   N      Hl ner  td C  Lower limit    Lo H  Lo C    Figure 7 2  General diagram of the PID controller featured in the PUR 94 device       modE          OFF          Pid        At F          At H          At C          SEtP         operating mode of the controllers       the controller is switched off  Outputs of control loops are set at idle  but all  their parameters are available for configuration      normal operating mode of the controller      the auto tuning procedure for one of the control loops of the controller in an  arrangement with two actuator elements  Selection of the control loop to be  tuned depends on the setting of the SetP parameter  Following this procedure   the device automatically switches to PiD mode      the auto tuning procedure for the PiD H loop in an arrangement with a 
84. tch parameters CLUISTTtvpel eee aaa aaa aaa aaa aaa aaa aaa tnn eene nnn entes nennen 34  7 3  MENU DESCRIPTIONY             4 11211211221     7 3 1     rEL1    menu        iD  TEE  7 3 3   inPt  menu  common Garameterg  eee aaa aaa aaa awake nennt nnns nennt nna 38  7 3 4   inPt  menu  parameters of temperature inputs                 7 3 5   inPt  menu  parameters of current and voltage inputs    E   ERGO NUT m                                          M  Posts OUE Ip                                  M  7 3 8   bri  parameter   7 3 9   HOLd  menu        7 3 10   SECu  menu      7 3 11   rS  menu           7 3 12   Edit  parameter        7 3 13  HEES  parameter     7 3 14   SErv  menu       7 4  MENU STRUCTURE    0  8  THE ALARM LED              111111112112  53  9  OVER CURRENT PROTECTION             53  10  DISPLAYED VALUES CAL CULATION     1 s ccsesecseeseessensessenseeseeseanenssesseesenseasensensenses 53  10 1  ADDITIONAL CALCULATIONS  USED CONVERSION CHARACTERISTIC  53  10 1 1  Linear characteristic    eee nitent nth than    94  10 1 2  Square Characleristic            octies O DRE Ro LE DARE UR ABEL ERA   A PKW EAU PEEP 54  10 1 3  Square root character  55     SB  56  60  60  67  68  70                                       10 1 4  User defined characteristic        10 2  EXAMPLES OF CALCULATIONS    s   11  THE MODBUS PROTOCOL HANDLING      s1scssssccsssscssssscsssesssssssensssssnscennsnsssnsessnsssnsssssansnsnsansasenenseseess 60  14 1  LIST OF REGISTERS       iniret 
85. the nominal output 5 0     42  range  Hi r Extension of the top of the nominal output range 5 0     42  AL Current output value on critical exception 22 1  mA  43  Passive current output configuration     OUtP    menu   OSou Passive current output signal source    InPU    41  Omod Passive current output mode  4 20   mA  42  OUtL Display value for 4 mA current output 0 0 42  OUtH Display value for 20 mA current output 100 0 42       72       User manual   CONTROLLER PUR 94                                                                                                       Parameter Description Default value User s value pe  Lor Extension of the bottom of the nominal output 5 0     42  range  Hi r Extension of the top of the nominal output range 5 0     42  AL Current output value on critical exception 22 1  mA  43  Active voltage output configuration     OUtP    menu   OSou Active voltage output signal source    InPU    41  Omod Active voltage output mode  0 10   V  42  OUtL Display value for 0 V  1 V or 2 V voltage output 0 0 42  OUtH Display value for 5 V or 10 V voltage output 100 0 42  Lor Extension of the bottom of the nominal output 5 0     42  range  Hir Extension of the top of the nominal output range 5 0     42  AL Voltage output value on critical exception 11 0  V  43  PID regulators configuration     CtrL    menu   modE Operation mode OFF 44  SetP Regulators setpoint 0 0 44  PID H regulator configuration     ParH    menu  44  P  H proportional gain factor P of PID 
86. tput   Yes R expressed in 0 1   Yes 023  AL  parameter in    OUtP    menu  active current output value on    critical exception   0   no change  1   22 1 mA  2   3 4 mA  3 0 mA  Yes 022  AL  parameter in    OUtP    menu  passive current output value on  D6h  i critical exception   0   no change  1   22 1 mA  2   3 4 mA     AL    parameter in    OUtP    menu  active voltage output value on  Yes 0 5 critical exception   0   no change  1   11 V  2   5 5  3   1 2 V   4 0 6V 5 0V     modE    parameter in CtrL  menu   FOh Yes 0 4 0      oFF    option  1   opcja Pid  option  2    At F  option   3   opcja At H    option  4    At C  option   F1h Yes    999   9999   SEtP  parameter in CtrL  menu  no decimal point included  F2h Yes 0  9999     P  H  parameter in PArH  menu  no decimal point included  F3h Yes 0  9999     tl H    parameter in PArH  menu  no decimal point included  F4h Yes 0 9999    td H    parameter in PArH  menu  no decimal point included  F5h Yes    999   9999      OF H    parameter in PArH  menu  no decimal point included  F6h Yes 0   999  Lo H  parameter in   PArH    menu  no decimal point included  F7h Yes 171000    Hi H    parameter in PArH  menu  no decimal point included  F8h Yes 079999     P  C  parameter in PArC    menu  no decimal point included  F9h Yes 0  9999      tl C    parameter in PArC  menu  no decimal point included          66       User manual   CONTROLLER PUR 94          Register   Write Range Register description       FAh Yes 0   9999  td C  param
87. ud  3   9600 baud   4   19200 baud  5   38400 baud  6   57600 baud  7   115200 baud  23h  Yes 021    mbAc    parameter in    rS    menu  permission to write registers via  RS 485 interface   0   write denied   1   write allowed  Parameters of    SECU    menu  binary format  0      oFF     1      on       bit 0    A r1  parameter  bit 1    A r2  parameter  24h Yes see descr  bit 2      A r3    parameter  bit 3      A r4    parameter  bit 4      A Pid     parameter      rESP    parameter in    rS    menu  additional response delay    25h Yes 0 5 0   no additional delay  1     10c    option  2    20c  option   3    50c  option  4    100c    option  5    200c  option      mbtO    parameter in  rS  menu  maximum delay between  27h Yes 0    99 received frames   0   no delay checking   1   99   maximum delay expressed in seconds  28h Yes 0 71  AL  parameter in    bEEP    menu  0   off  1   on  29h Yes 0 71  R1  parameter in    bEEP    menu  0   off  1   on  2Ah Yes 0 1  R2  parameter in    bEEP    menu  0   off  1   on                   61    User manual   CONTROLLER PUR 94                                                                                              Register   Write Range Register description  2Bh Yes 0 1    R3    parameter in  bEEP  menu  0   off  1   on  2Ch Yes 0 1  R4  parameter in  bEEP  menu  0   off  1   on  B  bri  parameter  display brightness    2Dh Yes TER 1   the lowest brightness  8   the highest brightness  E  Edit  parameter  numerical parameters edit 
88. used for connecting any  connecting cables  e g  as bridges   because this can cause damage to the  equipment or electric shock     User manual   CONTROLLER PUR 94       AN   If the unit is equipped with housing  covers and sealing to  protecting against  water intrusion  pay special attention to their correct tightening or clamping  In the  case of any doubt consider using additional preventive measures  covers  roofing   seals  etc    Carelessly executed assembly can increase the risk of electric shock       After the installation is completed do not touch the unit s connections when it is  switched on  because it carries the risk of electrical shock        Due to possible significant interference in industrial installations appropriate measures  assuring correct operation of the unit must be applied  To avoid the unit of improper  indications keep recommendations listed below         Avoid running signal cables and transmission cables together with power supply cables  and cables controlling inductive loads  e g  contactors   Such cables should cross at  a right angle         Contactor coils and inductive loads should be equipped with interference protection  systems  e g  RC type         Use of screened signal cables is recommended  Signal cable screens should be  connected to the earthing only at one of the ends of the screened cable         _ ln the case of magnetically induced interference the use of twisted pair of signal cables is  recommended  Twisted pair  best if 
89. value do not exceeds permissible measurement range but    displayed value exceeds range  999   9999  the warning   Ov   is displayed rather  than the calculated result     20    User manual   CONTROLLER PUR 94           100  C  600  C    permissible measurement range i   gt a  gt a  A i     Lo  message   Hi   message  displayed displayed    Figure 6 3  Definitions of measurement ranges in mode Pt100    In the measurement mode and PID mode user can check main thresholds values  After  pressing     or  v  button  name of the threshold  e g   rEL1   and his value will be displayed  on the display in alternating mode  If     or  v  will be pressed in 5 sec again  the next  threshold will be displayed  else the device comes back to the measurement mode  If a free  access is enabled  see description of  SECu  menu   user can change the value of particular  threshold pressing button  ENTER   see  PARAMETERS EDITION      All accessible parameters can be changed by entering the menu  see  DEVICE  PROGRAMMING   Use the local keyboard or the remote controller to do it   Note  all  parameters can be remote changed via RS 485 interface      aD Configuration of the device  via menu or RS 485 interface  does not stop  measures     6 1 1  detection OF THE PEAK VALUES    The PUR 94 controller is equipped with peaks detection function  It can detect a peaks of  the input signal and display their values  Presets connected with this function are placed in   HOLd  menu  see description of  HOLd  
90. version is done as for linear characteristic   Conversion is made accordingly with the expression     WI  x   Hi C     Lo C      Lo C      where W means the displayed value     possible for 4 20 mode only  In this case  1  lt 0  the displayed result is equal    Lo C     a Showed above expression is not valid when normalized result is negative  It is   see graphs below         Hi C LoC       Displayed  value  Displayed  value             LoC HiC                        0 4 8 12 16 20 0 4 8 12 16 20  Input current  mA  Input current  mA           Figure  10 3 Normal     Lo C   lt   Hi C  and inverted     Lo C   gt   Hi C  characteristic    10 1 4  User defined characteristic       User defined characteristic is defined as set of X Y points  Number of the points is variable and  may be set from 2 to 20 points which make linear segments  see graph and see Menu  inPt     Due to the normalized result In  the device computes specific segment  e g  for characteristic  from figure below  and      0 65 the segment between points X    50 0   and X    70 0   will  be chosen    Let s mark those points as PL  point low  and PH  point high    in this example PL     50 0      and PH    70 0    and the normalized result I for the point PL as I   in this example I    I    PL     0 5   The displayed result is calculated accordingly to the expression      Y  PH   Y PL     X  PH   X  PL         W    1  Xx x 100   Y PL     where Y PH   X PH   Y PL   X PL  mean values of X and Y coordinates of PH an
91. when the normalized results is equal 0  then value    Lo C    is displayed  and when    the normalized results is equal 1  then value    Hi C    is displayed   Expression presented below  shows the manner of result calculation     W I x  Hi C     Lo C      Lo C    where W means the displayed value     a The value of the    Lo C  parameter can be higher than the value of    Hi C     parameter  In such a case  for an increasing value of input current the displayed  value decreases     p            r      T      T       3         cL       r  o  a       Displayed  value  Displayed  value    Lo C Hi C                            I l l l l  0 4 8 12 16 20 0 4 8 12 16 20  Input current  mA              Input current  mA     Figure  10 1 Normal     Lo C     lt   Hi C  and inverted     Lo C     gt   Hi C  characteristic    10 1 2  Square characteristic       The normalized result is squared and further conversion is done as for linear characteristic   Conversion is made accordingly with the expression     WI  x   Hi C     Lo C      Lo C      where W means the displayed value                 Displayed  value  Displayed  value                         LoC       Hi C       o i    Ro    0 4 8 12 4146 20 0 4 8 12 16 20    Input current  mA           Input current  mA     Figure  10 2 Normal     Lo C   lt   Hi C  and inverted     Lo C   gt   Hi C  characteristic    54    User manual   CONTROLLER PUR 94       10 1 3  Square root characteristic    The normalized result is rooted and further con
92. word    can be restored by Service Division only        Ar1 Ar4     this option permits user   on   or prohibits   oFF   to modify the thresholds  of the relays LEDs R1   R4 without knowledge about user password       APid      this option enables one to permit   on   or prohibit   oFF   modification of the  controller s setpoint in measurement mode without knowing the user password    7 3 11   rS  menu       This menu is connected with RS 485 interface  and sets his properties      Addr    this parameter defines the address of the device  accordingly to Modbus protocol   It can be set in range from 0 to 199  If the value O is set then device  responds to  frames with address 255  FFh       bAud    this parameter determines RS 485 interface baud rate  It can be set to one of 8  possible values   1 2    2 4    4 8    9 6    19 2    38 4   57 6   115 2   which  respond to the baud rates of 1200  2400  4800  9600  19200  38400  57600 and  115200 bit s respectively      mbAc   this parameter sets the access to the configuration registers of the device   Possible values    on    configuration registers can be set via RS 485 interface    oFF     configuration registers can not be set via RS 485 interface     48    User manual   CONTROLLER PUR 94       The access to registers no 04h and 05h cant be denied by  mbAc  parameter  see   D LIST OF REGISTERS      mbtO     this parameter defines maximal time  sec  between following frames received by  the device  If the delay will be greate
93. xceeded     37    User manual   CONTROLLER PUR 94         H option    noCH    is selected for    AL    parameter  behaviour of the relay may  aD depend on  FiLt  parameter in some cases  If    FiLt    is set to big value and the  input signal drops  result value of the measure will change slow  causes of  turning on or off relay due to thresholds values  The critical situation is slowly  detected  so it is impossible to predict the relay state in that situations      f parameter  AL     on   the relay will be turned on in the critical situations   even if his parameter  modE     noAC      7 3 2   bEEP  menu    This menu contains options connected with acoustic signal          AL    if this parameter is set to  on   any critical situation causes by acoustic signal    r1    if this parameter is set to    on     activation of relay R1 causes by acoustic signal   r2    if this parameter is set to    on     activation of relay R2 causes by acoustic signal   r3    if this parameter is set to    on     activation of relay R3 causes by acoustic signal   r4    if this parameter is set to    on     activation of relay R4 causes by acoustic signal    Acoustic signal  turned on by e g  relay   can be turned off by pressing of any  button    7 3 3   inPt  menu  common parameters        This menu presets the measurement input      tYPE    type of the input   sensor  This parameter can be set to values    0 20    current input   range 0  20 mA    4 20    current input   range 4  20 mA    0 
94. y state will be turned on if the  input value exceeds the border values and stay bigger  or lower  during at least   t on   see points Bon  Don  Figure 6 11 a  d  e   Similarly  the relay will be turned off if time     toFF    elapse since the input signal value exceeds any of the border values  see points  Borr  Dorr  Figure 6 11 a  d  e     If tA  tB  tC or tD  when input signal stay in zone A or zone B  are lower than parameters     t on  or    toFF     the relay will not change his state  see points A and C  Figure 6 11 a  d  e      28    User manual   CONTROLLER PUR 94       The state of relay output while the input value exceeds the border values  points A  B  C   D  is described by parameter    modE     The relay can be turned on     modE       on    or  turned off     modE       oFF   when input signal value is contained in zone A  Figure 6 11 a     The parameter    AL    allow user to set the relay output behaviour in critical situations   e  g  input values exceeds permissible measurement range   User can select that the  relays will be turned on  turned off or not changed in critical situations     All parameters connected with relay outputs are described in paragraph  rEL1  menu     6 3 2  Two thresholds mode                                         displayed value t t t t t  4 i  zone B  a  Zona    SEtP    or    SEt2     parameter  NAN  Y    HYSt    parameter  zone B l                i Li MEE E bod  RE rom NECI EE   NEN  ime  b  relay state     E MEM I d i    poi 
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
KitchenAid KAWE460W User's Manual  User`s Manual - Grating Solver Development Company  Xbox 360 Component HD AV Cable Cabo de vídeo HD  231 User`s Manual - Lake Shore Cryotronics, Inc.  メジャーポートⅡ Rタイプワイド  Avaya Voice Announcement Manager Reference User's Manual  AixConcept NoteCart Flex 16 Laptops    Copyright © All rights reserved. 
   Failed to retrieve file