AVTECH Room Alert 32E/W Users Guide

image

Contents

1. Alarm Power On Loss you may leave the checkbox filled in if you wish to receive an alert when your 32E loses its main power source Otherwise you may uncheck it 3 In Alarm Profile which controls devices connected through the Light Tower amp Relay Adapter Ports you may leave the default Profile 1 or choose another Alarm Profile from the drop down menu 4 Click Accept Changes at the bottom of your screen to temporarily save your settings You may now navigate to another screen however if you close the web interface before the next step you will lose your changes 5 Click Save Settings in the navigation bar to the left of your screen Your Room Alert 32E will automatically reboot and commit your changes Advanced Sensor Configuration You may configure your Room Alert to send an alert if any of the 8 external digital sensors are disconnected from the unit This checkbox is blank by default Advanced Sensor Configuration Trigger Alarm If Sensor ls Disconnected 32 AVTECH Software Inc Room Alert 32bE 1 Check Trigger Alarm If Sensor Is Disconnected if you want to receive an alert if an external digital sensor becomes disconnected This check box 1s blank by default 2 Click Accept Changes at the bottom of your screen to temporarily save your settings You may now navigate to another screen however if you close the web interface before the next step you will lose your changes 3 Click Save Settings in the nav
2. Room Alert 32E W Temperature amp Environment Monitoring Made Easy Room Alert Xs Settings F tte hin ES AUT ESE R nt E e 510 44 Lon eh i terns Cranes R AV m TA dere mm EJ Phone 401 628 1600 User s Guide amp Fax 401 628 1601 p e Web AVTECH com ererence Manua AVT 150401 06 Don t Wait Until It s Too Late Flood 8 amp 24 Flood Spot Smoke GoToMyDevices com Wireless Sensor Hubs pes por Cloud Monitoring Service i f kA 1 4 i T y Y ka i e l l Antenna Alert To X Mobile Devices Nc a Email More NOS is Relay amp Low Voltage Ports d a e 4 1 p p mm aoe ia E E 1 a E on is T E a a i T Motion E m E X Y X PoE p Lum M ge LJ Sea RRN ns se e NONU I ess wm za a a E En My e i p p 7 Y 5 i a amp Ms pM Panic Button 1 l RS w m a D Light Tower Mc d E uar i Ee Ma RN a Lc wl E Es Relay Switch E Diu E Y m i Se s P j i ae p p 0x s E m s a 2d ie X Panic Button 2 EET Ed rud ou je n P Pd Eg Fi a fg A ae i PES LE P r d a ia j EN p s Ni hA Digital Fluid N A Sound Light amp Entry Temperature a d p p f uli D of Digital Outdoor j E Om E T d p ff Mobile Devices Digital Temp
3. except in the case of brief quotations embodied in articles and reviews Making copies of any part of this book for any purpose other than your individual use is a violation of United States copyright laws and international treaty provisions For information or additional copies contact AVTECH Software Inc as directed below Printed in the United States of America Warning and Disclaimer This publication is shipped as is without warranty of any kind either express or implied While every precaution has been taken in the preparation of this publication the publisher and authors assume no responsibility for errors or omissions Neither is any liability assumed for damages resulting from the use of the information or instructions contained herein It is further stated that the publisher and authors are not responsible for any damage or loss to your data or equipment that may result directly or indirectly from your use of this publication and the related hardware amp software Nothing on any AVTECH web site or in documentation shall be construed as conferring any license under any of the AVTECH Software AVTECH or any third party s intellectual property rights whether by estoppel implication or otherwise Trademark Acknowledgements AlertScript AVTECH the AVTECH Logo AVTECH Software the AVTECH System Manager Character AVTECH com AVTECHSoftware com Environment Alarm Environment Monitoring Made Easy EnvironmentMonitor com GoToMyDe
4. 888 220 6700 401 628 1600 Contact Us AVTECH Software Inc 16 Cutler Street Cutler Mill Warren RI 02885 2761 USA Sales 888 220 6700 Phone 401 628 1600 Fax 401 628 1601 Visit Us amp Our Store AVTECH com RoomAlert com GoToMyDevices com EnvironmentMonitor com Most Orders Ship the Same or Next Business Day Trademarks Copyright 1988 2015 AVTECH Software Inc All Rights Reserved Worldwide AVTECH AVTECH Software AVTECH com AVTECHSoftware com Device ManageR EnvironmentMonitor com Environment Monitoring Made Easy GoToMyDevices com Protect Your Facility Don t Wait Until It s Too Late Room Alert RoomAlert com WiSH WiSPR TemPageR amp TemPageR com Privacy Promise AVTECH does not sell or share your email or other contact information however AVTECH uses some email marketing because our prospects and customers consider it important and convenient When we do AVTECH provides customers with an easy means to decline further email of that type Current Versions To confirm your organization is running current software and firmware verisons or to download these versions for any licensed AVTECH product under Extended Service amp Support please visit www AVTECH com and look for the Current Versions box on the Downloads page Tell Us Your Story We truly want to know when we do well and when we miss expectations Working to provide the best products and services mea
5. Use Alarm Profile Profile 1 Sensor Label Alarm On Low Adjust Ext Sensor 1 Temperature F i 60 0 Sensor 2 Alarm Configuration Sensor Type Mot Connected Use Alarm Profile Profle 1 Sensor Label High Low Adjust Ext Sensor2 Em EE EN Sensor 3 Alarm Configuration Sensor Type Not Connected Use Alarm Profile Profile 1 Sensor Label High Low Adjust Ext Sensor3 E EE EN 1 In Sensor Label you may leave the default label Sensor 1 or rename it to something more descriptive such as Ext Temperature 2 The Alarm On fields automatically match the type of sensor you connect In this example the Alarm On setting is Temperature 3 Enter values in the High and Low field to set high and low thresholds Your Room Alert 32E will generate alerts in response to these thresholds 4 Enter a value in the Adjust field to calibrate your digital sensor if its reading differs from a known value at that location 5 In Use Alarm Profile which controls devices connected through the Light Tower amp Relay Adapter Ports you may leave the default Profile 1 or choose another Alarm Profile from the drop down menu Configure Alarm Profiles in the Alarm Options screen of your web interface Refer to the Alarm Options section in this manual for detailed instructions AVTECH Software Inc 27 Room Alert 32bE 6 Click Accept Changes at the bottom of your scr
6. likewise with a low threshold of 60 the sensor will alarm when the temperature falls below 60 and clear when it rises above 61 Internal Sensor Alarm Configuration Internal Temperature amp Humidity Sensor You may configure alert thresholds for the Internal Temperature amp Humidity Sensor in the Internal Sensor Alarm Configuration field The temperature range is 40 to 185 F 40 to 85 C and the humidity range is 5 to 95 RH Internal Sensor Alarm Configuration Sensor Type Temp Humidity Fahrenheit Use Alarm Profile Profile 1 No Alarm Sensor Label Alarm On High Low Adjust Profile 2 Profile 3 Monitor Heat Index _ Humidity RH 70 50 0 Profile 4 Profile 5 Int Temp amp Hum Temperature F 78 60 1 In Sensor Label you may leave the default label Internal Sensor or rename it to something more descriptive such as Int Temp amp Hum 2 The Alarm On field is set at the defaults of Temperature F and Humidity RH AVTECH Software Inc 25 Room Alert 32bE ex Refer to the Advanced section in this manual for instructions on KA setting the default temperature scale 3 Enter values in the High and Low field to set high and low temperature and humidity thresholds Your Room Alert will generate alerts in response to these thresholds 4 Enter a value in the Adjust field to calibrate the Internal Temperature amp Humidity Sensor if its read
7. S A or Canada please ask to speak with an International Product Specialist as they can address international shipping and customs concerns Website EnvironmentMonitor com Anytime Place your order online at anytime through the AVTECH store for immediate processing International money rates are available online to view pricing and make payment in your local currency Combination specials are available on our store Email Orders AVTECH com Anytime Send your organization s purchase order PO completed and scanned quote form or order instructions to AVTECH via email We prefer to receive POs in PDF format although can accept Word and Excel formats if necessary Other file formats are not accepted Fax 401 628 1601 Anytime Send your purchase order PO completed quote form or order instructions to AVTECH via fax at any time Faxes are received in a secure facility NOTE International orders ship when payment in U S D is received Wire transfer or credit card payment is preferred Checks must be in U S D include a U S routing code and drawn on a U S bank Thank you Extended Service amp Support GoToMyDevices is the primary online venue for customers working with Room Alert monitors and includes the services previously provided through our Maintenance Support amp Update Service MSUS program It will allow e AVTECH s 30 Day Satisfaction Guarantee on new purchases Coverage under AVTECH s hardware Limited Warranty
8. You may enter a value from 5 to 65535 The default 1s 60 seconds 1 e every minute 2 In HTTP Port you may change the port number your web browser uses to connect to your Room Alert s web interface It uses port 80 by default 3 In Temperature Scale you may choose Fahrenheit or Celsius from the drop down list Fahrenheit 1s the default 4 Click Accept Changes at the bottom of your screen to temporarily save your settings You may now navigate to another screen however if you close the web interface before the next step you will lose your changes 5 Click Save Settings in the navigation bar to the left of your screen Your Room Alert 32E will automatically reboot and commit your changes Device ManageR Push Configuration By default Device ManageR queries your Room Alert 32E for sensor values at defined intervals However you may configure your Room Alert 32E to proactively send sensor updates to Device ManageR by enabling Device ManageR Push Enabling Device ManageR Push is an advantage for two reasons e Your Room Alert 32E can communicate with Device ManageR without triggering any firewalls between the two Firewalls typically allow out going connections while blocking in coming connections e Your Room Alert 32E can immediately send an update to Device ManageR when it detects an alarm regardless of any intervals you have configured either in this section or in the Device ManageR d
9. address 1 Select Use The Following IP Configuration 2 In IP Address enter the new static IP address 3 In Subnet Mask enter the subnet mask 4 In Default Gateway enter the gateway IP address 5 In DNS Server IP enter the DNS server IP address 6 Click Accept Changes at the bottom of your screen to temporarily save your settings You may now navigate to another screen however if you close the web interface before the next step you will lose your changes 7 Click Save Settings in the navigation bar to the left of your screen Your Room Alert 32E will automatically reboot and commit your changes Make sure that you do not use an IP address that is already vr assigned to another device Also set the IP address within your current subnet range otherwise you may not be able to discover your Room Alert 32E AVTECH Software Inc 17 Room Alert 32bE Ethernet Configuration Typically you may leave the Ethernet Configuration section at the defaults which are shown below for immediate use of Room Alert 32E Ethernet Configuration MTU Size 1024 Auto Negotiate bl Speed 400Mbps 10 Mbps Duplex Full Half Gratuitous ARP Broadcasts Enabled Disabled However if you connect your Room Alert 32E to a managed switch that controls your network traffic you may need to change these settings 1 In MTU Size you may leave the default 1024 or enter a value as low as 512 2 You ma
10. for the built in humidity sensor from 5 to 95 relative humidity Monitor the on off status of the critical power source with the built in power sensor Increase your security with the bundled external Room Entry Sensor Alert multiple contacts on your team when thresholds are exceeded o 00 N80 Receive alert notifications by email email to SMS and more on a computer or mobile phone Expand your options as your needs evolve v Extend your reach by adding 7 more external digital sensors up to 100 feet away and 15 more external switch sensors up to 900 v Monitor 2 analog sensors using the built in analog input ports v Automatically turn on off electrical devices such as air conditioners or generators using the 2 built in relay output ports and or by adding Relay Switch Sensors with adapters v Use the 2 Light Tower amp Relay Adapter ports to add Light Towers or Relay Switch Sensors v Explore your options further with your AVTECH Product Specialist AVTECH Software Inc 3 Room Alert 32bE Room Alert 32E 32W Package Contents The standard Room Alert 32E package includes e One 1 Room Alert 32E ID Box e One 1 Ethernet Cable 10 e One 1 External Digital Temperature Sensor e One 1 External Room Entry Switch Sensor e One 1 Room Alert 32E User s Guide amp Reference Manual Y ou re reading it now e One 1 Package Of Literature amp Additional Information The Room Alert 32W wireless package includes all
11. in this manual for instructions on setting the default status page refresh rate and temperature scale for Room Alert 32E AVTECH Software Inc 13 Room Alert 32bE Sensor Display Area Status RA32 12345 Current Sensor Status 09 08 14 16 07 06 MAC XX XX XX XX XX XX Room Alert amp 32E W vX X X Update Every 60 secs Internal Sensors 2 Installed Relay Fahrenheit Celsius internal 1 Temperature Humidity Internal 4 Power Power State Main Power Relay Output 2 Off Digital Sensors 0 out of 8 Connected No Digital Sensors Detected Switch Sensors 16 out of 16 Enabled Channel 1 Switch Channel 2 Switch Channel 3 Switch Channel 4 Switch Switch Sen 1 Switch Sen 2 Switch Sen 3 Switch Sen 4 Circuit State Open Circuit State Open Circuit State Open Circuit State Open In the main viewing pane of the Status tab is the Sensor Display Area Here you may view the current readings for your sensors which are displayed in a grid on the screen as follows Internal Sensors Relay Output 2 Temp amp Humidity 1 Analog Input 2 when enabled in Settings Power 1 Digital Sensors 8 When enabled in Settings Switch Sensors 16 Light Tower or Relay Switch 2 Wireless Sensors Hoom Alert 32W only sensors connected to the Analog Input ports and Light Tower Relay owitch ports do not appear in Status until you enable them in the Settings screen Refer to Settings in this manual for
12. instructions 14 AVTECH Software Inc Room Alert 32bE With each sensor are displayed the status icons and labels which you may configure in Settings Sensors Status Icons Green circle with v mark Sensor is in a clear state C uel e S Sensor has no alarm threshold set Red circle with X mark Sensor is in an alarm state Settings To access your Room Alert 32E s settings click Settings in the navigation bar at the top of your screen Settings pep About MAC Address XX XX XX XX XX XX Version X X X Network Network Settings SMTP Email snmp Device Name RATS Sensors IP Adaress Configuration Alarm Options Obtain IP Address Automatically Auto Configuration Methods BOOTP 4Q Enable Disable DHCP 4Q Enable Disable AutolP Enable Disable Use The Following IP Configuration IP Address Subnetmask Default Gateway FREE DNS Server IP OE Ethernet Configuration MTU Size 1024 Auto Negotiate Speed 100 Mbps 10Mbps Duplex Full Half Gratuitous ARP Broadcast Enabled Disabled You ll see a prompt for your username and password whenever you click Settings If you have not set up a password for your Room Alert 32E simply click OK without entering anything AVTECH Software Inc 15 Room Alert 32bE Network Navigate to Settings Network to open the Network Settings screen Device Name Device Name HRA
13. leave the default 24 Hours or choose another interval as frequent as 10 minutes from the drop down list You may also disable time synchronization by selecting Disabled from the drop down list e You may manually synchronize the time by clicking Update Now Clicking this button does not affect the Auto Refresh interval 8 Click Accept Changes at the bottom of your screen to temporarily save your settings You may now navigate to another screen however if you close the web interface before the next step you will lose your changes 9 Click Save Settings in the navigation bar to the left of your screen Your Room Alert 32E will automatically reboot and commit your changes AVTECH Software Inc 47 Room Alert 32bE Trace Configuration You may configure your Room Alert 32E for trace output which is useful for troubleshooting Trace output shows the communication between your Room Alert 32E and your mail server as well as other information such as the current firmware version IP address MAC address and requests to web pages Trace Configuration Enable Tracing Trace Port 143 To configure trace output 1 Select Enable Tracing 2 In Trace Port you may leave the default port 143 or enter another port number 3 Click Accept Changes at the bottom of your screen to temporarily save your settings You may now navigate to another screen however if you close the web interface before the next step yo
14. of the above plus e One 1 Internal Wireless Assembly amp Coaxial Port e One 1 External Antenna w 13 Cable amp Magnetic Mount e One 1 External Wireless Sensor Hub WiSH The Room Alert 32E ID Box WiSH Signal Strength LEDs Alarm RA32W only LEDs Front l l A AVTECH com Room Alert Power Status Ethernet Digital PoE WLAN Light Tower amp LED Port Ports amp GSM Relay Adapter 8 LEDs Ports 2 Wireless Coaxial Port Back RA32W only Room Alert Switch Sensor Contact Sets 1 16 Relay Analog Switch Reset Power Output Input Sensor Button Port Ports Ports Ports 0 2 16 tld Button 4 AVTECH Software Inc Front Power Status LED Ethernet Port Room Alert 32bE An LED indicates the power status to Room Alert 32E Green Main or POE power Red Internal UPS power An RJ 45 PoE enabled port connects Room Alert 32E to your network via an RJ 45 network cable Eight 8 standard RJ 11 jacks connect any AVTECH digital sensor to your Room Alert 32E via a standard RJ 11 straight through telephone cord WISH Signal Strength LEDs Wireless Model Only WiSH POE WLAN amp GSM LEDs AVTECH Software Inc Three 3 LEDs indicate the signal strength of the last W1SH or WiSPR sensor to communicate with your Room Alert 32W e 3 Strong signal e Weak signal Three 3 LEDs indicate in use status of e Built in PoE e WLAN in wireless models e GSM coming in
15. service e Download access to licensed firmware software amp MIBs Access to U S based technical support services Access to your product specialist or reseller Tracking of order shipments from fulfillment to delivery location e Subscription setup and ongoing management Management of your contact and billing information During your active subscription to GoToMyDevices AVTECH will make all of the above available to the subscriber and those people they share their subscription with However GoToMyDevices is more than just a source for downloads technical support and managing your account It is AVTECH s advanced cloud solution for monitoring Room Alert devices the world s most popular IT amp facilities environment monitors GoToMyDevices enables anyone to use Room Alert monitors regardless of their skill level or technical capabilities Even better users enjoy the same look and feel from any mobile device whether they use a phone tablet laptop or desktop computer Check it out and see for yourself why many of the worlds leading corporations call it the best management platform of its class GoToMyDevices allows users to monitor alert log graph view report manage and protect Technical Support services are available 9 5 EST Monday through Friday The best way to start a support request is by opening a ticket online at GoToMyDevices Cloud GoToMyDevices com Email Support AVTECH com Website AVTECH com Support Phone
16. statistics according to a schedule or in response to alert conditions Modify according to each user s needs lt ie ka P a E r o v Log off shut down reboot and execute commands on Windows and Linux Unix systems across your network QM ERE Y Automatically text or call contacts with alerts using a eem one enn text voice or GSM satellite modem A license for Device ManageR is included FREE with the purchase of any AVTECH environment monitor Download it now from your customer account at AVTECH com Downloads 54 AVTECH Software Inc How To Purchase AVTECH Products AVTECH products are available for purchase around the world and used in 179 countries You can purchase through your favorite reseller direct from AV TECH or online through our store When ordering from AVTECH we are happy to accept your organization s purchase order PO as well as payment via credit card or wire transfer Most orders ship the same or next business day Resellers Order Through Your Favorite Reseller Ask them to contact AVTECH on your behalf AVTECH has an established and professional network of Resellers world wide and can set up new Resellers in minutes Phone 888 220 6700 401 628 1600 9 5 EST Call AVTECH direct and ask to speak with a Product Specialist They can take your order by phone for immediate processing or provide you with an immediate PDF quote by email If you are outside of the U
17. the Light Tower amp Relay Adapter For our example we ve configured Profile 1 and Profile 2 out of the 5 available profiles The alarm options available in the Feature column vary depending on the device you select Tae AVTECH Software Inc 9D Room Alert 32bE Relay 1 2 Action Configuration Here you may set the devices connected through the built in relay output ports to turn on or off in response to your Room Alert 32E rebooting or its sensors going in and out of alarm state In this example we ll configure Relay 1 Relay 1 Action Configuration Sensor Label Server Rm AC On Alarm OnClear On Alarm On Clear n Alarm OnClear OnAlarm OnClear On Alarm Mone Mone Mone Mone None Mone None Mone 1 In Sensor Label you may leave the default Relay 1 or enter something more descriptive such as Server Rm AC 2 In the On Boot column you may select what the relay output does in response to the Room Alert 12E rebooting The default is Off 3 In the Profile 1 5 columns you may create up to 3 different sets of on off actions to associate with sensors when they go in and out of an alarm state In this example we ve configured Profile 1 and left Profiles 2 through 5 at the default of None Associate Alarm Profiles With Sensors Each sensor is set at Profile 1 by default the Light Tower built in LTA Relay Relay Switch Sensor and bu
18. visit the Sensors amp Accessories sections of AVTECH com 34 AVTECH Software Inc Room Alert 32bE In this example we ll configure a Light Tower w Audio in Light Tower Relay 1 Light Tower Relay 1 Configuration Light Tower Relay Label Server Rm RYG Connected Light Tower Relay Red Y ellow Green w Audio Y Profile 1 Profile 2 Profile 3 Profile 4 Profile 5 Feature On Boot On Alarm On Clear On Alarm On Clear On Alarm On Clear On Alarm On Clear On Alarm On Clear LTA Relay or qu Off Y v Off v 1 In Light Tower Relay Label you may leave the default Light Tower 1 or enter your own such as Server Rm RYG 2 In Connected Light Tower Relay select the appropriate option from the choices in the drop down menu For this example we are choosing Red Yellow Green w Audio for the Light Tower w Audio 3 Once you choose your device the Alarm Profiles grid beneath it expands Here you may select On or Off from the drop down list for each feature of the device e Inthe On Boot column Select what each feature does response to the Room Alert 32E rebooting The default is Off e Inthe Profile 1 5 columns Create up to 5 different sets of on off actions to associate with sensors when they go in and out of an alarm state The default for each feature 1s Off 4 Above you see the grid for the Light Tower w Audio including the built in relay port on
19. 00 9 ATT txt net e Addresses separated by commas ITMgr YourCo com 1235551900 ATT txt net etc 12 Click Accept Changes at the bottom of your screen to temporarily save your settings You may now navigate to another screen however if you close the web interface before the next step you will lose your changes 13 Click Save Settings in the navigation bar to the left of your screen Your Room Alert 32E will automatically reboot and commit your changes When your Room Alert reboots return to the Email Settings screen and click Send Test Email to send a test email to the addresses you entered in Email Recipients If your test email is not received successfully check your mail server s SMTP relay settings which must allow anonymous SMTP relay messages If you entered a domain name for the Mail Server Address you may need to rename it to the IP address or assign a static IP setting and have a DNS server IP address set 20 AVTECH Software Inc Room Alert 32bE Simple Network Management Protocol SNMP Because your Room Alert 32E is fully SNMP compliant you have the option to monitor it with a 3 _party monitoring application capable of performing SNMP queries You may configure the Room Alert 32E to send SNMP Traps in response to a change in alarm states to up to three host systems running 3 party SNMP monitoring applications If you use a 39 party SNMP monitoring application e Obtain the Room Alert 32E MIB file
20. 32 12345 Device Name Server Rm RA32 To rename your Room Alert 32E l Select the automatically assigned name in Device Name and enter a new one of up to 15 alphanumeric characters Click Accept Changes at the bottom of your screen to temporarily save your settings You may now navigate to another screen however if you close the web interface before the next step you will lose your changes Click Save Settings in the navigation bar to the left of your screen Your Room Alert 32E will automatically reboot and commit your changes IP Address Configuration DHCP e Obtain IP Address Automatically Auto Configuration Methads BOOTP DHCP AutolP To obtain an IP address automatically using DHCP l 2 Select Obtain IP Address Automatically Typically leave the BOOTP DHCP and AutoIP at their default Enabled Click Accept Changes at the bottom of your screen to temporarily save your settings You may now navigate to another screen however if you close the web interface before the next step you will lose your changes Click Save Settings in the navigation bar to the left of your screen Your Room Alert 32E will automatically reboot and commit your changes AVTECH Software Inc Room Alert 32bE IP Address Configuration Static IP Use The Following IP Configuration IP Address 192 168 2 50 Subnet Mask 255 255 255 Default Gateway 192 168 2 1 DNS ServerlP 4222 To assign a static IP
21. 6 Enabled Channel 1 Switch Channel 2 Switch Channel 4 Switch Switch Sen 1 Switch Sen Switch Sen 3 Switch Sen 4 Circuit State Closed Circuit State Open Circuit State Open Circuit State Open 3 Notice the circuit state of Switch 1 It should show the normal state which in this case 1s Closed Ignore the red color coding for now We haven t configured the sensor yet so it s still set at the default alarm on closed Circuit State Closed 4 Now put the sensor into an alarm state To put a Motion Sensor into an alarm state for example wave your hand in front of it 5 Look at the circuit state at the same time You should see it switch to the opposite of normal In this example if normal 1s Closed you see the alarm state as Open Again ignore the Circuit State Open green color coding for now Now that you ve checked what Open and Closed mean on your switch sensor navigate to Settings gt Sensors to configure your options in Switch Sensor Settings 1 In Sensor Label you may leave the default Switch 1 2 3 or 4 or enter something more descriptive such as Ext Motion or Main Entry 2 In Alarm On select the alarm state Open or Closed which you determined on the Status page In our example the alarm state 1s Open 3 n Use Alarm Profile which controls devices connected through the Light Tower amp Relay Ad
22. E 14 511508 eee E E EE Se ere 15 IN CU Ol Kd code E E E E E E E E 16 SNP E ENTER ELT 19 Simple Network Management Protocol SNMP ssesssssssssseeessssssssseresssssssssseressssssseeeeees 21 IOS ccc epee mise etae EN M equ CURL I DAOFEND ees A E A 24 ZATakm CPO INS coc iodoriesse c encirse teria aes onte T uPDE Ni DNU EDU NER UR DEUU 33 WSA 0 TS OS NERO 37 BAISER ONS NE mmm 4 veta C 43 AVTECH Software Inc 1 Room Alert 32bE PUY AIC CO MENT A E TTE 44 ls 49 Lus M 50 Dpdanne Eregbleshiootia Y our Koom ATO 2E sarraie kein a DU Sq ERE AES CEP DE 2E ol How To Download Firmware amp Software Updates From AVTECH com 51 How To Update Room Alert 32E s Firmware eeessessesseeeeeeenn nn nnne enne 51 How To Discover Room Alert 32E When Your Network Blocks UDP Broadcasts 22 How To Reset Room Alert 32E To Factory Defaults sss 52 Introduction To AVTECH s Device ManageR gc ccssecnasecastascdasswedzesessencedavennsedandeandeccendzeiesseaseascouase 54 AVTECH com Protect Your Facility Don t Wait Until It s Too Late 2 AVTECH Software Inc Room Alert 32bE Introduction To Room Alert 32E The Room Alert 32E is AVTECH s flagship product that h
23. If you don t have one please visit our online store at AVTECH com 8 AVTECH Software Inc Room Alert 32bE Step 2 Open And View Your Room Alert 32E In Your Web Browser With The Built In Interface d Power Stat Main Power Wireless Sensors 0 Active Channel 12 No Wireless Sensors Detected Enter your Room Alert 32E s IP address in your web browser s address bar to access o the interface OR With Device ManageR For Advanced Functionality P a icc alhevt B Device ManageR A ANTECH Dewe Stm Discovered Devices 3 Last Discovery Dec 1 2014 405000m Temperature Scale F Dc x ul dep Duos Corona Room Alert 32WE R32 Data Center Montes Namen Qecne D 13280 g feet IP Adress Upstate Ferrwam i x MAC Adios aao g irn B Narra XXX Open Wet Rasat ghi ow Deceveed D a Ahen L Oa Time 1200954 TAMAM 2 MSUS Expire Open Seange Advanced Example QA 4E a y i j Example Mas Ex 1 v RAI2 121073 PAWE We RAVL manwe vis 9 RAXLSTHAVTECH nass RA3E 129604 RE 9132 RME QA CUSTI inr i323 4E v a Read Gragh Data RS RA24E RS RASZ cane zan I Start 120 2014 0 00 73 Ent 124 2014 16 04 ne As 5 e Aurtot aac ali tof mastery d 20 meci wdta x Off Graphed Sensors ans sanoga mema Soso AC Power Draw 7 tompenmnreiF Vots No Alerts in Progress Download and install AVTECH s Device Man
24. No Profile v Accept Changes 1 In WiSH Sensor choose the discovered WiSH you want to configure from the drop down list In this example we ve chosen WiSH Sensor 1 2 In Sensor Label you may leave the default WiSH Sensor 1 or enter something more descriptive such as Server Rm WISH 3 In Serial the interface automatically detects and displays the WiSH sensor s serial number In this example WiSH Sensor 1 s serial number is 123456789012 4 Record this number on the label on the bottom of your sensor so you ll know which physical WiSH corresponds to what you re seeing in the interface Room Alert 32W can support up to 10 WISH or WISPR hubs at one time This adds a capacity of 40 additional sensors Visit the sensors section of AVTECH com to purchase additional WISH or WISPR hubs 38 AVTECH Software Inc Room Alert 32bE AVTECH WiSH Power Sensor works with Room Alert 32W and 26W only Do NOT leave powered when not in use cupa aud aO aUa ox AVTECH com 401 628 1600 5 Onlyclick Reset This WiSH Sensor if you wish to clear your current WiSH settings and change them back to the defaults Configuring internal external digital and external switch sensors has been covered in this manual in the Sensors section please refer back to that section for instructions on configuring sensors connected to the WiSH or look specifically at the sub sections listed below Internal Sensor Alar
25. SH perform the same steps on it moving it from the Blocked WiSH Sensors box back to the Allowed WISH Sensors box 42 AVTECH Software Inc Room Alert 32bE Security By default the Room Alert 32E does not require log in credentials you may however create a password for your Room Alert 32E for extra security Status EE Pep About MAC Address XX XX XX XX XX XX Version XXX Network Security Settings SMTP Email SNMP Current Password Sensors New Password Alarm Options Confirm Password WISH Sensors WISH Options Accept Changes Advanced Save Settings Reset Defaults Navigate to Settings gt Security to open the Security Settings screen 1 In Web Password you may create a log in password of up to 15 alphanumeric characters for your Room Alert 32E Use only letters and numbers in your log in password no special characters please 2 Re enter the password in the Confirm Password field to verify Click Accept Changes at the bottom of your screen to temporarily save your settings You may now navigate to another screen however if you close the web interface before the next step you will lose your changes 4 Click Save Settings in the navigation bar to the left of your screen Your Room Alert 32E will automatically reboot and commit your changes If you forget your password you can reset your Room Alert 32E settings to the factory defaults Please see the How To Re
26. Switch Sen 3 Closed Profle 1 Switch Sen 11 Closed Profile 1 Sensor 4 Label Alarm On Alarm Profile Sensor 12 Label Alarm On Alarm Profile Switch Sen 4 Closed Profile 1 Switch Sen 12 Closed Proflel Your Room Alert 32E monitors your switch sensors for an Open or Closed circuit state Room Alert defaults to alarming on Closed as you can see above you may however need to change that depending on your sensor AVTECH s Motion Sensor for example is Open when it detects movement and Closed when it doesn t in that case you d likely want to configure the sensor to alarm on Open or when motion is detected The Alarm And Clear State Of Your Switch Sensor To determine the alarm and clear state of your sensor you may either refer to its Installation Note or see for yourself by physically connecting your sensor to your Room Alert and then observing what happens to its circuit state in the Status page After you connect your sensor and before you configure it in the Settings page follow these Steps 1 Click the Status tab at the top of your screen in the web interface 2 Scroll down to the Switch Sensors and look at the circuit state of the channel you connected your sensor to If you connected your sensor to the first switch sensor port on Room Alert look at Channel 1 if you connected it to the second look at Channel 2 etc 30 AVTECH Software Inc Room Alert 32bE Switch Sensors 16 out of 1
27. Timeout 10 254 you may enter the number of packets to allow Room Alert to miss before an alarm is generated You may enter a value between 10 and 254 the default it 10 This prevents false alerts if the wireless signal 1s temporarily interrupted 3 In WiSH Sensors Enabled 0 10 you may specify the maximum number of WiSH or WiSPR units you want to monitor You may leave the default 10 or enter a lower number WiSH Sensor Filter Configuration In this section you may block your Room Alert 32W from communicating with some or all of your WiSH sensors You may need this feature if you want only certain WiSHes recognized 1 In Enable WiSH Sensor Filter check the box to enable filtering It is disabled unchecked by default AVTECH Software Inc 41 Room Alert 32bE 2 In Allowed WiSH Sensors you see a list of WiSHes recognized by your Room Alert 32W To block a certain WiSH perform these steps e Click on the WiSH to highlight it e Select Accept Changes at the bottom of the page to move that WiSH to the Blocked WiSH Sensors box WISH Sensor Filter Configuration Enable WiSH Sensor Filter ri WISH Sensor 1 4AB10DC Allowed WISH Sensors Select to Block No Filtered WiWH Sensors Blocked WISH Sensors Select to Allow Heset All WiSH Sensors 3 Then select Save Settings in the navigation bar to the left Your Room Alert 32W will automatically reboot and commit your changes To unblock that Wi
28. ageR via your customer account at e AVTECH com Downloads e Launch it in your web browser at http localhost 8080 AVTECH Software Inc Room Alert 32bE Step 3 Install Additional Components Connect Included External Sensors Room Alert 32E and 32W Models AVTECH s Digital Temperature Sensor and Room Entry Sensor shown here come standard with the Room Alert 32E and 32W packages Digital Temperature Sensor Room Entry Sensor Proximity Room Alert 32W Model Only AVTECH s wireless model the Room Alert 32W comes with the external sensors above plus the External Antenna w 13 Cable amp Magnetic Mount and a Wireless Sensor Hub WiSH External Antenna w 13 Cable amp Magnetic Mount Wireless Sensor Hub External Sensor WiSH Wireless Sensor Hub AVTECH Software Inc o AVTECH com 4f Please install these items according to the Installation Notes that accompany them The Room Alert 32W has a capacity to monitor ten 10 Wireless Sensor Hubs WiS H and or Wireless Sensor Hub amp Powered Relays WiSPR 10 AVTECH Software Inc Room Alert 32bE Connect Other Compatible Components If you purchased additional components that are compatible install them according to the Installation Notes included with them Please refer to Status Settings and Alarm Options in this manual for instructions on viewing and configuring your external sensors AVTECH Software Inc 11 Room Alert 32
29. ame to specify who is receiving the information 3 You may leave Location sysLocation blank or enter the location of your Room Alert 32E monitor 4 You may click Use 2 digit SNMP if you prefer to receive values in 2 digit rather than 4 digit format Room Alert 32E sends values to your 3 party SNMP monitoring application in 4 digit format by default 78 55 F for example appears as 7855 In 2 digit format your values are truncated not rounded to the nearest number In this example 78 55 would appear as 78 5 Click Accept Changes at the bottom of your screen to temporarily save your settings You may now navigate to another screen however if you close the web interface before the next step you will lose your changes 6 Click Save Settings in the navigation bar to the left of your screen Your Room Alert 32E will automatically reboot and commit your changes 22 AVTECH Software Inc Room Alert 32bE SNMP Sending Configuration You may configure your Room Alert 32E to send SNMP Traps in response to a change in alarm state to up to three host systems running 3 party SNMP monitoring applications Each host system you enter in these fields will receive the same SNMP Traps simultaneously SNMP Sending Configuration Trap Send IP 1 192 168 2 100 Trap SendIP 2 192 168 2 101 Trap Send IP 3 0 0 0 0 To configure your Room Alert to send SNMP Traps 1 In Trap Send IP 1 enter the IP address of t
30. apter Ports you may leave the default Profile 1 or choose another Alarm Profile from the drop down menu If you have a Light Tower or Relay Switch Sensor connected to your Room Alert you may configure Alarm Profiles Please refer to the Alarm Options section in this manual for further information 4 Click Accept Changes at the bottom of your screen to temporarily save your settings You may now navigate to another screen however if you close the web interface before the next step you will lose your changes 5 Click Save Settings in the navigation bar to the left of your screen Your Room Alert 32E will automatically reboot and commit your changes AVTECH Software Inc 31 Room Alert 32bE For any of the switch sensor sets you leave unused on your Room Alert 32E choose Disabled from the Alarm On drop down menu to avoid confusion or false alerts Internal Power Sensor Alarm Configuration You may configure the power sensor that is built in to the Room Alert 32E here This internal power sensor triggers on loss of main power and can send a notification while the battery back up keeps the monitor powered for a short time Internal Power Sensor Alarm Configuration Sensor Type Power Sensor Label Alarm On Alarm Profile Power Sensor Alarm On Power Loss ff Profile 1 Y 1 In Sensor Label you may leave the default Power Sensor or enter something more descriptive such as RA32 Power 2 In
31. as more of everything to give you the most complete monitoring solution With the Room Alert 32E AVTECH brings you Temperature amp Facilities Environment Monitoring Made Easy In addition to its three 3 internal sensors one 1 temperature one 1 humidity and one 1 internal power the Room Alert 32E has thirty 30 external ports eight 8 external digital sixteen 16 external switch two 2 relay output two 2 analog input and two 2 Light Tower amp Relay Adapter ports Our wireless model the Room Alert 32W comes in a Room Alert 32E enclosure and has an additional external coaxial port for its antenna Install your unit with minimal planning and less hassle v Get up and running in minutes with easy Plug and Play setup V Use Power over Ethernet to install even where no DC power is available v Mount Room Alert 32E in a rack on a wall or ceiling or on a table top Get access from anywhere over the web v Configure monitor and operate Room Alert 32E with its easy to use built in web interface v Significantly expand its functionality with AVTECH s Device ManageR the powerful software bundled FREE with all Room Alert monitors v Have the flexibility to monitor with any SNMP enabled 3 party monitoring application Know immediately when physical conditions change V Set alert thresholds for the built in and bundled external temperature sensor from 40 to 185 F 40 to 85 C Set alert thresholds
32. asic information about your Room Alert 32E and make temporary adjustments to the sensor display e You may find your Room Alert 32E s name current date amp time and MAC address here RA32 12345 Current Sensor Status 09 08 14 17 48 51 MAC 00 20 4A D6 DF A8 Room Alert 32E W vX X X Update Every 60 secs Fahrenheit Celsius e To determine if your Room Alert 32E s firmware is current you may click Room Alert 32E vX X X at the right RA32 12345 Current Sensor Status 09 08 14 17 48 51 MAC 00 20 4A D6 DF A8 Room Alert amp 32E W vX X X Update Every 60 secs Fahrenheit Celsius A check firmware versions me Your Room Alert 32E must be connected to the internet to e To temporarily modify the refresh interval of the Status screen while viewing which is 60 seconds 1 e every minute by default you may enter a value in seconds in the Update Every field Click outside the field to temporarily commit the change RA32 12345 Current Sensor Status 09 08 14 17 48 51 MAC 00204A D6 DF AY Room Alert 32E W vX X X Update Every 60 secs Fahrenheit amp Celsius e To temporarily toggle the temperature scale between Fahrenheit F and Celsius C click Fahrenheit or Celsius RA32 12345 Current Sensor Status 09 08 14 17 48 51 MAC 00 220 4A D6 DF A98 Room Alert amp 32E W vX X X Update Every 60 secs Fahrenheit amp Celsius Refer to the Advanced section
33. bE How To Use Room Alert 32E s Web Interface You may configure your Room Alert 32E through its built in web interface To access the interface you may either e Select your Room Alert 32E in Device ManageR and click the Open Web button Or e Type the IP address of your Room Alert 32E monitor directly into the address bar of your web browser Your Room Alert 32E s web interface has 4 tabs e Status e Settings e Help e About Status To view your Room Alert 32E s current sensor status click Status in the navigation bar at the top of your screen TM Advanced Aus pu Room Ro O m A le rt Environment Monitoring Alerting amp Automatic Corrective Action RA32 12345 Current Sensor Status 09 08 14 16 07 06 MAC XX XX XX XX XX XX Room Alert amp 32E W vX X X Fahrenheit Celsius Update Every 60 secs Relay Status Internal Sensors 2 Installed Relay Internal 1 Temperature Humidity Internal 4 Power High Power State Main Power prd Low Output 2 High Off 32 74 RH Low 32 09 RH Digital Sensors 0 out of 8 Connected No Digital Sensors Detected Switch Sensors 16 out of 16 Enabled Channel 1 Switch Channel 2 Switch Channel 3 Switch Channel 4 Switch Switch Sen 1 Switch Sen 2 Switch Sen 3 Switch Sen 4 12 AVTECH Software Inc Room Alert 32bE Current Sensor Status Bar Below the Status tab is the Current Sensor Status Bar where you may view b
34. blocks UDP broadcast packets on port 30718 AVTECH s Device ManageR might not be able to automatically locate the Room Alert 32E monitor To manually discover your Room Alert 32E use the Advanced Discovery option in AVTECH s Device ManageR Application 1 Open AVTECH s Device ManageR If you don t already have it installed download it from your customer account at AVTECH com Downloads 2 Navigate to Advanced Discovery under the Device Status tab in the navigation bar to the left of your screen 3 In the Advanced Discovery Options dialog box click Manually Add Device s Via IP Address 4 Enter your Room Alert 32E s IP address or the range of IP addresses assigned to DHCP devices on your network 5 Click Begin Scan which initiates a TCP scan on port 30718 6 When the scan is complete click Close Window and your Room Alert 32E should be automatically added to the list of discovered devices How To Reset Room Alert 32E To Factory Defaults You may need to reset your Room Alert 32E to factory defaults if e You are moving it to a new location and it must be reconfigured e thas been assigned invalid network settings and is therefore inaccessible e You have lost your Room Alert 32E s password If your Room Alert 32E is accessible on the network to reset it to factory defaults 1 Navigate to Settings in the web interface 52 AVTECH Software Inc Room Alert 32bE 2 Click Reset Defaults in the navigation bar to t
35. default In Time Display you may select the 12 or 24 hour format from the drop down list The 24 hour setting is the default In Time Format you may select either the MM DD YY and DD MM YY date format from the drop down list Month first 1s the default Select Daylight Savings if you would like your Room Alert 32E time setting to compensate by 1 hour for daylight savings time In Time Server IP you may leave Room Alert s default Network Time Protocol NTP server IP address 198 82 1 201 or enter another time server IP address However if you d rather enter your NTP hostname such as time nist gov click Resolve hostname AVTECH Software Inc Room Alert 32bE e When the DNS Resolver dialog box opens enter the hostname of your time server and click Resolve Enter your NTP hostname and the device will attempt to resolve the IP address e g time nist gov time nist gov Resolving time nist gov e After the resolver successfully translates the hostname into an IP address click Insert to put that IP address into the Time Server IP field in the Advanced Settings screen Resolve was a success Resolved IP 216 171 120 356 Click Insert to put the resolved IP into the setup form 216 1 1 120 36 Time ServerIP 216 171 120 356 Resolve hostname 7 In Time Server Auto Refresh you may select how often Room Alert 32E automatically synchronizes with your time server e You may
36. ects Room Alert 32E to an electrical outlet with any AVTECH International Power Adapter Look for the AVTECH logo Using another power adapter could damage the Room Alert 32E s circuit board and void the warranty If you need one purchase it online at AVTECH com AVTECH has an international power adapter with a compatible plug style for each and every country AVTECH Software Inc 7 Room Alert 32bE How To Install Your Room Alert 32E Step 1 Connect Your Room Alert 32E Hardware If Your Network Is Power Over Ethernet PoE Enabled e Connect one end of a standard Ethernet cable to A AVTECH com the Room Alert 32E s Ethernet port 7 e Connect the other end to a PoE enabled network ME Jack Front That s it Your Room Alert 32E is now powered and discoverable on your network If Your Network Is Not Power Over Ethernet PoE Enabled A Connect To Your Network First O e Connect one end of a standard Ethernet cable to the Room Alert 32E s Ethernet port 4 e Connect the other end to a network jack TN Front B Then Connect To A Power Source Room Alert e Plug one end of AVTECH s International Power Adapter into the Room Alert 32E s power port e Plug the other end into a surge protected power Source Back o Your Room Alert 32E is now powered and discoverable on your network Use only AVTECH s International Power Adapter Others could damage the Room Alert 32E and void your warranty
37. een to temporarily save your settings You may now navigate to another screen however if you close the web interface before the next step you will lose your changes Click Save Settings in the navigation bar to the left of your screen Your Room Alert 32E will automatically reboot and commit your changes The options in these fields vary slightly depending on the type of digital sensor you connect Analog Sensor Settings You may configure your 0 5 VDC analog sensor in these fields In the example below we are configuring AVTECH s Current Loop Analog Sensor Settings Analog Sensor 1 Alarm Configuration Enable High Sensor Label High Low Adjust Enabled Current Loop 6 2 Scale 10 Use Alarm Profile Profile 1 Reference 5 Amp Work from right to left to configure the Analog Sensor 1 In the set of fields on the right of the screen click Enable to turn on the Reference Scale and Units fields e In Reference enter values from 5 to O that represent the High and Low points of your analog sensor s output signal range In the case of the Current Loop which outputs a signal of 0 5 VDC we ve left the default values 28 AVTECH Software Inc Room Alert 32bE e In Scale enter the High and Low points of the scale you want the Reference reading to be converted to In our Current Loop example we would like to convert 0 5 volts to 0 10 amps
38. er Access box e Your username which is the email address we have on file for you e Your organization s password Your user account information download username amp password was emailed to you when you purchased your Room Alert 32E This can be emailed to you again upon request 3 Click Login 4 Once you ve logged in you ll see which software and firmware products you are currently enabled for To download click the Download Now button next to the appropriate product How To Update Room Alert 32E s Firmware 1 Download and save the most recent firmware update for Room Alert 32E from your customer account at AVTECH com Downloads 2 Open AVTECH s Device ManageR If you don t already have it installed download it from your customer account 3 Select the Room Alert 32E option under the Device Status tab in the navigation bar to the left of your screen 4 Click the Update Firmware link shown under the product name or the Update Firmware button shown at the top of the screen 5 Then follow the on screen instructions to complete the update AVTECH Software Inc 51 Room Alert 32bE IMPORTANT Be sure that there are no web browsers accessing your Room Alert 32E monitor from anywhere on your network before uploading the firmware as this could cause the firmware update to be incomplete or become corrupted How To Discover Room Alert 32E When Your Network Blocks UDP Broadcasts If your network
39. erature Room Entry mM Ps E yf Email More Ed Temperature Pd T e i Fi T Digital i Monitor With A Web Browser 3 P4 ER Temperature amp Humidity Network Cameras Current Loop a P Fa A L7 Fuel Tank Level P Oo c Water Tank Level ES Extreme Temperature Device MaunageR SNMP Monitoring Softwa GoToMyDevices com Room Alert ED FE CE PE Install Room Alert Monitors The Most Advanced Easy To Use Reliable amp Affordable Monitors Available To MONITOR ALERT LOG GRAPH VIEW REPORT MANAGE PROTECT Digital Temperature Extreme Temperature Digital Outdoor Temperature Heat Index Feels Like Digital Fluid Temperature e Smoke Fire Digital Humidity Light Towers Relay Switches Wireless Sensor Hubs e Network Cameras Fuel Water Tank Level Analog Power amp Temp Sensors Main UPS Power e Air Flow Sound Light e Switch Sensors Flood Water e Motion Room Entry e Dry Contacts Current Loops Amperage e Panic Button Security Low Voltage Sensors On behalf of the entire team at AVTECH we say Thank You It is our privilege to serve you our valued customer Copyright Information Copyright 1988 2015 AVTECH Software Inc All Rights Reserved No part of this book may be used or reproduced for commercial benefit in any form or by any means or stored in a database or retrieval system without prior written permission of AVTECH Software Inc
40. evice ManageR is AVTECH s all in one software solution for the discovery management monitoring alerting logging graphing automatic action and more of AVTECH s physical environment monitoring hardware and Axis network cameras Manage Unlimited Room Alert amp TemPageR Montiors MAE XXX A OEE ANTEC v Control all of your Room Alert and TemPageR units amp p agire from a single web browser interface accessible from pee RA anywhere by internet i Ss FE l TAVAT Ava V N th v Take automatic corrective actions run scripts and notify unlimited contacts on the device of their choice v Use dashboard widgets to customize your interface and display the information most important to you in Tm mx real time 3 v Automatically log and graph all of your sensor data for a comprehensive history of environmental conditions Control the log file size automatically Manage Unlimited Network Cameras v View all of your Axis camera displays simultaneously and control who has access v Automatically email Axis camera snapshots in response to alert conditions v Customize your alerts with links to your Axis cameras for one click access to real time video Expand Device ManageR s Functionality With Plugins Discovered Devices 19 Last Discovery Oci 12 2012 259019m TemgeratweScale i W Scheduled Tasks conige wich taste te parinn on a space ache v Send customized reports with advanced
41. future models Room Alert 32bE Digital Switch amp Wireless LEDs Digital Switch Wireless Alerts Light Tower amp Relay Adapter Port Signal Tower Relay Back Relay Output Coaxial Port Wireless Model Only Three 3 LEDs light red or green to indicate alarm or clear status of Digital Switch or WiSH wireless model only sensors e Green Clear e Red Alarm A standard RJ 11 jack connects a Light Tower amp Relay Adapter to your Room Alert 32E via a standard RJ 11 straight through telephone cord Two 2 sets of contacts connect any low voltage device to your Room Alert 32E via standard speaker wire Two 2 set of contacts connect any low voltage analog sensor to your Room Alert 32E via standard speaker wire A coaxial jack connects your Room Alert 32W to the included wireless antenna via the antenna s built in coaxial cable AVTECH Software Inc Room Alert 32bE Switch Sensors Sixteen 16 sets of dry contacts connect Room Alert 32E to any AVTECH switch sensor or dry contact on a device e g HVAC generator pump fan etc via standard speaker wire or low voltage 2 wire cable Switch Sensor Port is shown here Reset Button A small push button resets Room Alert 32E to factory default settings Please push softly On Off Button A push button turns the Room Alert 32E s internal battery back up on and off Power Port A standard power port conn
42. he host system that runs your 3 party SNMP monitoring application 2 In Trap Sent IP 2 and Trap Send IP 3 you may enter the IP addresses of other host systems that run 3 party SNMP monitoring applications or leave the default 0 0 0 3 Click Accept Changes at the bottom of your screen to temporarily save your settings You may now navigate to another screen however if you close the web interface before the next step you will lose your changes 4 Click Save Settings in the navigation bar to the left of your screen Your Room Alert 32E will automatically reboot and commit your changes AVTECH Software Inc 23 Room Alert 32bE Sensors You may configure alert thresholds for the internal temperature external digital external analog and external switch sensors connected to your Room Alert 32E in this screen Your Room Alert 32E sends alerts based on these thresholds For more information about AVTECH sensors and accessories please refer to the Appendix at the back of this manual or visit the Sensors and Accessories sections of AVTECH com Navigate to Settings gt Sensors to open the Sensor Settings screen Status Settings About MAC Address XX XX XX XX XX XX Version XXX Network Sensor Settings SMTP Email SNMP General Alarm Configuration Sensors Degrees Within Threshold Before Alarm Is Cleared 1 between 0 1 and 25 5 Alarm Options Alarm on sensor disconnect WiSH Sensors Alarm Thresholds WISH Options In
43. he left 3 Click Yes when prompted with Are you sure you want to Reset Factory Defaults Status Settings About MAC Address XX XX XX XX XX XX Version AMX Network SMTP Email SNMP Sensors YES NO Alarm Options Security Advanced Are you sure you want to Reset Factory Defaults Save Settings Reset Defaults 4 Your Room Alert 32E will automatically reboot and attempt to obtain an IP address via DHCP 5 To automatically discover your Room Alert 32E on your network open AVTECH s Device ManageR If you don t already have it installed download it from your customer account at AVTECH com Downloads If your Room Alert 32E is not accessible on the network to reset it to factory defaults 1 With your Room Alert 32E connected to the network and powered on press and hold the reset button for at least 10 seconds until the left LED over the network jack turns off and then on again 2 Your Room Alert 32E will automatically reboot and attempt to obtain an IP address via DHCP 3 To automatically discover your Room Alert 32E on your network open AVTECH s Device ManageR If you don t already have it installed download it from your customer account at AVTECH com Downloads IMPORTANT When you reset to factory defaults you lose all of your previously configured settings including password security m AVTECH Software Inc 53 Room Alert 32bE Introduction To AVTECH s Device ManageR D
44. igation bar to the left of your screen Your Room Alert 32E will automatically reboot and commit your changes Alarm Options Navigate to Settings Alarm Options to open the Alarm Options screen Here you may configure devices connected through your 2 Light Tower amp Relay Adapter ports and your Room Alert 32E s 2 built in relay output ports Status Settings Help About MAC Address XX XX XX XX XX XX Version XXX Network Alarm Options SMTP Email SNMP Light Tower Relay 1 Configuration Sensors Light Tower Relay Label Light Tower 1 Alarm Options Connected Light Tower Relay No Light Tower Relay Connected WISH Options Feature On Boot On Alarm On Clear On Alarm On Clear On Alarm On Clear On Alarm On Clear On Alarm On Clear Light Tower Relay 2 Configuration Light Tower Relay Label Light Tower 2 Save Settings Connected Light Tower Relay No Light Tower Relay Connected Reset Defaults Feature On Boot On Alarm On Clear On Alarm On Clear On Alarm On Clear On Alarm On Clear On Alarm On Clear Relay 1 Action Configuration Sensor Label Relay ut 1 Mone None Mone None Mone None Mone None Mone None hd Relay 2 Action Configuration Sensor Label Petey 2 uM ge ee RE E putem moen ptem oc en ter ntm n Mone Mo
45. ilt in Relay Output execute Profile 1 when that sensor goes into an alarm state Once you have configured at least more profile you may associate it with a sensor When that sensor goes into an alarm state the features of those devices react by turning on or off In our example we will associate Profile 1 with our external Digital Temperature Sensor and Profile 2 with our external Room Entry sensor 1 Navigate to Settings gt Sensors 2 Find your sensor s interface and choose the profile you ve configured from the drop down list in Use Alarm Profile Note that the default for all sensors is Profile 1 36 AVTECH Software Inc Room Alert 32bE Sensor 1 Alarm Configuration Sensor Type Temperature Fahrenheit Use Alarm Profile Alarm On ies Profile 1 Sensor Label Ext Temperature Temperature F T8 60 0 Profile 5 Sensor 1 Label Alarm On Alarm Profile Profile 1 No Alarm Profile 1 Room Entry Open Sensor Label Alarm On Switch Sen 2 Closed Profile 3 Profile 4 Sensor 3 Label Alarm On Profile 5 ere Cun 7 lanl Oren d 3 Click Accept Changes at the bottom of your screen to temporarily save your settings You may now navigate to another screen however if you close the web interface before the next step you will lose your changes 4 Click Save Settings in the navigation bar to the left of your screen Your Room Alert 32E will automatically
46. ings differ from known values at that location 5 In Use Alarm Profile which controls devices connected through the Light Tower amp Relay Adapter Ports you may leave the default Profile 1 or choose another profile from the drop down menu Configure Alarm Profiles in the Alarm Options screen of your web interface Refer to the Alarm Options section in this manual for detailed instructions 6 Click Accept Changes at the bottom of your screen to temporarily save your settings You may now navigate to another screen however if you close the web interface before the next step you will lose your changes 7 Click Save Settings in the navigation bar to the left of your screen Your Room Alert 32E will automatically reboot and commit your changes Sensor 1 8 Alarm Configuration External Digital Sensors You may configure alert thresholds for the eight 8 external digital sensors in the Sensor 1 8 Alarm Configuration fields In the sample screen below you see the included external Digital Temperature Sensor in Sensor 1 which corresponds to the 1 digital sensor port Sensors 2 and 3 are shown in their default state when those digital ports are unused Sensors 4 through 8 are not shown Notice that the web interface detects the type of digital sensor automatically and enters it in Sensor Type 26 AVTECH Software Inc Room Alert 32bE Sensor 1 Alarm Configuration Sensor Type Temperature Fahrenheit
47. interface before the next step you will lose your changes 8 Click Save Settings in the navigation bar to the left of your screen Your Room Alert 32E will automatically reboot and commit your changes Repeat the steps above for each discovered WiSH A maximum of ten WiSH or WiSPR hubs can be used with each Room Alert 32W monitor Please see the next section WiSH Options for more configurable WiSH features 40 AVTECH Software Inc Room Alert 32bE WiSH Options Navigate to Settings gt WiSH Options to access advanced options and filters for each Wireless Sensor Hub WiSH or Wireless Sensor Hub amp Powered Relay WiSPR Status Settings ep About MAC Address XX XX XX XX XX XX Version XXX Network WiSH Sensor Options SMTP Email SNMP Sensors Alarm Options WISH Timeout 10 254 10 Number Of Missed WiSH Packets Advanced WISH Sensor Options Enable WISH Lost Communication Alarms f WISH Sensors WISH Sensors Enabled 0 10 10 Security Advanced WISH Sensor Filter Configuration Enable WISH Sensor Filter ANC cC mca mas di WISH Sensor 1 Save Settings Allowed WiSH Sensors Selectto Block Reset Defaults No Filtered WiSH Sensors Blocked WISH Sensors Select to Allow Reset All WISH Sensors Accept Changes Advanced WiSH Sensor Options 1 In Enable WiSH Lost Communications Alarms you may leave the box checked which is the default or disable it by unchecking the box 2 In WiSH
48. iscovery interval Device ManageR Push Configuration Enable Device ManageR Push Server IP Address 192 1682 10 Server Port 8080 Push Interval 1 Minute To enable Push to Device ManageR from your Room Alert 32E 1 Select Enable Device ManageR Push 2 In Server IP Address enter the IP address of Device ManageR s host system AVTECH Software Inc 45 Room Alert 32bE In Server Port enter the port Device ManageR uses The default 1s 8080 In Push Interval choose the number of minutes you would like between pushes from the drop down list Click Accept Changes at the bottom of your screen to temporarily save your settings You may now navigate to another screen however if you close the web interface before the next step you will lose your changes Click Save Settings in the navigation bar to the left of your screen Your Room Alert 32E will automatically reboot and commit your changes Time amp Date Configuration You may set the time and date defaults for your Room Alert 32E here 46 Time amp Date Configuration Time Zane GMT Greenwich Mean Time London Lisbon Y Time Display 24 hour Time Format MM DD Y Y Hour Minute Second Daylight Savings Adjust For Daylight Saving Time 1 hr Time Server IP 198 82 1 201 Resolve hostname Time Server Auto Refresh Disabled Update Now In Time Zone select your time zone from the drop down list Greenwich Mean Time GMT is the
49. lpful links and contact information for AVTECH sales and support resources Advanced Computer Room R O 0 m A lert Environment Monitoring Alerting amp Automatic Corrective Action Room Alert amp 32E W About Room Alert amp 32E W Firmware vX X X Released Click Here To Check For Updates Sales Order Online Quote Request Sales AVTECH com 888 220 6700 USA amp Canada 401 628 1600 International CLICK HERE FOR Support Home Users Guide amp Reference Manual Suppornt AVTECH com 888 220 6700 USA amp Canada 401 628 1600 International AVTECH com RoomAlert com EnvironmentMonitor com You may find the version number and release date of the firmware that is installed on your Room Alert 32E on this screen To check if your Room Alert 32E has the most current version click Click Here To Check For Updates Your Room Alert 32E must be connected to the internet to check for newer firmware versions Thank you 50 AVTECH Software Inc Room Alert 32bE Updating amp Troubleshooting Your Room Alert 32E How To Download Firmware amp Software Updates From AVTECH com Software and firmware updates are available to licensed customers with current Maintenance support amp Update Service MSUS To download 1 Goto AVTECH com Downloads or click Downloads on the menu bar at the top of the screen at AVTECH com 2 In the Downloads page enter the following user account information in the Custom
50. m Fax 401 628 1601 LE sad CUJICCO AVT 150401 06 Room Alert 32bE Table of Contents lirimgereto eir Co Modo 0100s cues Plac 3 RoOAIIECZELSUM Papckace t ODIGNDBL a mencdaluniadu aede at a ie Gp EOM E D nim 4 The Kom uude ID DOr sereen E E E O N 4 TOn E E E E E eee 5 Da E E E E E E E 6 How Lo malt ROm AE E espresse een eee ee qu ESE a 8 Step 1 Connect Your Room Alert 32E Hardware ceccccccccccccceeesseseeeeeeeeeeaeenseeeeeeeeeeeaas 8 If Your Network Is Power Over Ethernet PoE Enabled eene e If Your Network Is Not Power Over Ethernet PoE Enabled 3 Step 2 Open And View Your Room Alert 32E In Your Web Browser 9 Wita The DEC Hi IUe E ETC OE oeoreun doro oco eroe nne err ostrea pn ITE EOE OER 9 With Device ManageR For Advanced Functionality cesses 9 Step 3 Install Additional Components esses nennen nennen enne nns 10 Connect Included External SenSOfS c uscire ee reRs En rece Pha Feinde Eos arae Fete itr esco Po F RU Ee edu pM TE 10 Connect Other Compatible Components esee eene nnne 11 HOWIOIDEDSODnAEN SES Web IB RU eism eae eerene sari orien ne E m MA MM 12 LU CM 12 Current Sensor SPI US Dl cos sceomo D eer E iv cud ee 13 peusor D Ay FCO aa E had ade A EE E E E E
51. m Configuration e Please refer to Internal Sensor Alarm Configuration in this manual for instructions on configuring the WiSH s internal temperature sensor External Digital Sensors Sensors 1 amp 2 Alarm Configuration e Please refer to Sensor 1 8 Alarm Configuration in this manual for instructions on configuring the external switch sensor you connect to the WiSH Hefer to the Advanced section in this manual for instructions on setting the default temperature scale External Switch Sensor Alarm Configuration e Please refer to External Switch Sensor Settings 1 16 in this manual for instructions on configuring the external switch sensors you connect to the WiSH 6 In Alarm Profile which controls devices connected through the Light Tower amp Relay Adapter Ports you may leave the default Profile 1 or choose another Alarm Profile from the drop down menu The Profile you choose here applies to all sensors connected to the WiSH its internal external digital and external switch sensors AVTECH Software Inc 39 Room Alert 32bE If you have a Light Tower or Relay Switch Sensor connected to your Room Alert via a Light Tower amp Relay Adapter you may configure Alarm Profiles Please refer to the Alarm Options section in this manual for further information 7 Click Accept Changes at the bottom of your screen to temporarily save your settings You may now navigate to another screen however if you close the web
52. mail Addresses Send Test Email Accept Changes 1 Check Email Enabled 2 Leave the Email Footer Enabled checked to include AVTECH contact information with email messages 3 Check Use SMS to send a shorter email with a reduced character count 4 In Mail Server Port enter your mail server s SMTP port The default is 25 a commonly used port 5 In Timeout you may leave the default 5 seconds or enter another interval 6 In the Mail Server field enter the domain name or IP address of your mail server 7 In the Return Address From field enter an email address that resides on your mail server This 1s the address alert messages will come from 8 In Display URL you may leave the default which is the IP address and port of your AVTECH Software Inc 19 Room Alert 32bE Room Alert 32E or overwrite it with another IP address Authentication Optional 9 If your mail server requires SMTP authentication check Enable Authentication 10 In Username and Password enter a valid username and password for your mail server that will facilitate authentication Your password cannot be more than 11 alphanumeric characters v Email Recipients Separated By Comma 11 In Email Addresses enter the email and email to SMS addresses that you d like to send alerts to Separate each address with a comma e Email address ITMgrQ YourCo com e Email to 85MS address 12355519
53. mething more descriptive such as Current Loop or Cryogenic Temp 3 n Use Alarm Profile which controls devices connected through the Light Tower amp Relay Adapter Ports you may leave the default Profile 1 or choose another Alarm Profile from the drop down menu If you have a Light Tower or Relay Switch Sensor connected to your Room Alert you may configure Alarm Profiles Please refer to the Alarm Options section in this manual for further information AVTECH Software Inc 29 Room Alert 32bE 4 Click Accept Changes at the bottom of your screen to temporarily save your settings You may now navigate to another screen however if you close the web interface before the next step you will lose your changes 5 Click Save Settings in the navigation bar to the left of your screen Your Room Alert 32E will automatically reboot and commit your changes External Switch Sensor Settings 1 16 You may configure the alert state for the 16 external switch sensors in the Switch Sensor settings fields Shown below are the default settings Switch Sensor Settings Sensor 1 Label Alarm On Alarm Profile Sensor 9 Label Alarm On Alarm Profile Switch Sen 1 Closed Profle 1 Switch Sen 9 Closed Profle 1 Sensor 2 Label Alarm On Alarm Profile Sensor 10 Label Alarm On Alarm Profile Switch Sen 2 Closed Profle 1 Switch Sen 10 Closed Profle 1 Sensor 3 Label Alarm On Alarm Profile Sensor 11 Label Alarm On Alarm Profile
54. ne Mone None Mone None Mone None None None Accept Changes AVTECH Software Inc 33 Room Alert 32bE Light Tower Relay 1 2 Configuration In Light Tower Relay Configuration you may configure devices connected to your Room Alert 32E via the Light Tower amp Relay Adapter Light Tower Relay 1 Configuration Light Tower Relay Label Light Tower 1 Connected Light Tower Relay Mo Light Tower Relay Connected Feature On Boot On Alarm On Clear On Alarm On Clear On Alarm On Clear On Alarm On Clear On Alarm On Clear Light Tower Relay 2 Configuration Light Tower Relay Label Light Tower 2 Connected Light Tower Relay No Light Tower Relay Connected Feature On Boot On Alarm On Clear On Alarm On Clear On Alarm On Clear On Alarm On Clear On Alarm On Clear A Light Tower amp Relay Adapter gives you the option to add an AVTECH Light Tower Light Tower w Audio or Relay Switch Sensor You may also connect a low voltage device directly to the available relay port Shown here is a sample configuration Room Alert 32E Room Alert x RJ 11 Light Tower Light Tower Light Tower 32E Cable amp Relay Adapter Custom Cord w Audio The Light Tower w Audio in this configuration can be replaced with a standard Light Tower or Relay Switch Sensor For more information about AVI ECH sensors and accessories please refer to the Appendix at the back of this manual or
55. ns making changes that typically succeed and sometimes fall short Please email us your feedback at Feedback AVTECH com It is always appreciated Thank you AVTECH com Protect Your Facility Don t Wait Until It s Too Late
56. reboot and commit your changes Alarm Profiles do not affect email alerts WiSH Sensors Navigate to Settings gt WISH Sensors to access your wireless sensor hubs A Wireless Sensor Hub W1SH is included with Room Alert 32W AVTECH also offers a Wireless Sensor Hub amp Powered Relay WiSPR Your web interface automatically detects WiSH and or WiSPR hubs that are in range Below you see the WiSH Sensor Settings screen at defaults and detecting a W1iSH or WiSPR sensor AVTECH Software Inc 37 Room Alert 32bE Status Settings Hep J About MAC Address XX XX AX XX XX XX Version X X X WiSH Sensor Settings sNup WISH Sensor WiSH Sensor 1 v Reset This WiSH Sensor Sensors Sensor Label WiSH Sensor 1 Serial 123456789012 Alarm Options Internal Sensor Alarm Configuration Sensor Type Temperature WISH Sensors WISH Options Temperature CF Alarm On High Low Adjust External Sensors Sensor 1 Alarm Configuration SensorType Disconnected Sensor Label Alarm On High Low Adjust Temperature F Monitor Heat Index Humidity RH Sensor 2 Alarm Configuration SensorType Disconnected Save Settings Reset Defaults Sensor Label Alarm On High Low Adjust ii Temperature F La a Monitor Heat Index Humidity RH E o Switch Sensor Alarm Configuration Sensor Type Switch Switch Sensor Label Alarm On WISH 1 Switch Closed v Alarm Profile
57. s through your customer account at AVTECH com Downloads and load them into your SNMP monitoring application Otherwise your application cannot properly translate the data it receives in the SNMP Trap e Ensure that your application uses SNMPvI e Note that your Room Alert communicates with your SNMP monitoring application using the standard port for the SNMP protocol 161 Navigate to Settings gt SNMP to open the SNMP Settings screen Status Settings Hep X About MAC Address XX XX XX XX XX XX Version XXX Network SNMP Settings SMTP Email CNP Ud n nemen Sensors Community Name public Use 2 digit SNMP Alarm Options Contact sysContact WISH Sensors Location sysLocation WISH Options SRCNTI SNMP Sending Configuration Advanced Trap Send IP 1 0 0 0 0 Trap Send IP 2 0 0 0 0 Trap Send IP 3 0 0 0 0 Save Settings Reset Defaults Accept Changes AVTECH Software Inc 21 Room Alert 32bE SNMP Configuration SNMP Configuration Community Name public Use 2 digit SNMP Contact sysContact IT Manager Location sysLocation Data Center To begin configuring your Room Alert 32E for SNMP 1 In Community Name you may leave the default SNMP protocol community name public or enter a new name d The community name you assign here must match the one in your 3 party SNMP monitoring application 2 You may leave Contact sysContact blank or enter a person s n
58. set Room Alert 32E To Factory Defaults section of this manual for more information There is no other alternative AVTECH Software Inc 43 Room Alert 32bE Advanced You may configure a number of advanced options here including Status screen defaults Device ManageR Push time amp date and trace output Navigate to Settings gt Advanced to open the Advanced Settings screen Stats Settings About MAC Address XX XX XX XX XX XX Version XXX Network Advanced Settings a VUE Refresh Rate seconds AM HTTP Port 80 WiSH Sensors Temperature Scale Fahrenheit WISH Options Enable Device ManageR Push Server IP Address 0 0 0 0 Server Port s080 Save Settings Push Interval i Reset Defaults Time amp Date Configuration Time Zone GMT Greenwich Mean Time London Lisbon Time Display 24hour Time Format MM DD YY HourMinute Second Daylight Savings Adjust For Daylight Saving Time 1 hr Time Server IP 198 82 1 201 Resolve hostname Time Server Auto Refresh 24Hours Update Now Trace Configuration Enable Tracing Trace Port 143 Accept Changes Status Page Configuration You may set defaults for the Status screen here Status Page Configuration Refresh Rate seconds 60 HTTP Port 80 Temperature Scale Fahrenheit 44 AVTECH Software Inc Room Alert 32bE 1 In Refresh Rate seconds enter the number of seconds you would like the Status screen to refresh at
59. so we ve replaced the default of 5 in High with 10 and left the default of 0 in Low e In Units enter a l to 3 character label for the unit type that your readings will be measured in If you are measuring amperage as with the Current Loop you might enter A or Amp for example Note that this field is merely a label and does not affect any of the calculations The High and Low fields in Analog Sensor Settings can hold up to 6 characters total With the custom scale enabled you may enter positive and negative whole numbers With the custom scale disabled you may enter positive numbers up to 1 decimal place 2 In the set of four fields to the left of the screen click Enabled to enable the sensor on the Room Alert web interface and Device ManageR software e In High and Low you may leave the default 0 which means no alarm is configured or enter values of up to 6 characters that fall within the Scale range from the previous step In our example we entered a conversion scale of 0 to 10 amps in the previous step for the Current Loop and we ve chosen to generate alarms at the high and low thresholds of 6 and 2 amps Note that 1f you decided not to enable the Reference Scale and Units fields in the previous step you must enter numbers within the range O to 5 for 0 5 VDC e In Sensor Label you may leave the default Analog Sensor 1 or choose so
60. ternal Sensor Alarm Configuration Sensor Type Temp Humidity Fahrenheit Use Alarm Profile Profile 1 Security Advanced Sensor Label High Low Adjust Internal Sensor 0 0 0 Save Settings Reset Defaults Monitor Heat Index Sensor 1 Alarm Configuration Sensor Type Not Connected Use Alarm Profile Profle Sensor 2 Alarm Configuration Sensor Type Not Connected Use Alarm Profile Profle High Low Adjust Sensor 3 Alarm Configuration Sensor Type Not Connected Use Alarm Profile Profle 24 AVTECH Software Inc Room Alert 32bE Notice the Alarm Profile drop down menu next to each sensor If you have a Light Tower or Relay Switch Sensor connected to your Room Alert via a Light Tower amp Relay Adapter you may configure Alarm Profiles Please refer to the Alarm Options section in this manual for further information General Alarm Configuration In Degrees Within Threshold Before Alarm Is Cleared you may leave the default 1 or enter a value between 0 1 and 25 5 General Alarm Configuration Degrees Within Threshold Before Alarm Is Cleared L between 0 1 and 25 5 You may use this feature to adjust how close your digital temperature sensor readings must get to a high or low threshold before their alarms clear For example with the default setting here of 1 and a high threshold of 80 your temperature sensor will alarm when the temperature rises above 80 and clear when it falls below 79
61. u will lose your changes 4 Click Save Settings in the navigation bar to the left of your screen Your Room Alert 32E will automatically reboot and commit your changes You may then use any standard telnet or terminal application to view the trace on the configured port 48 AVTECH Software Inc Room Alert 32bE Help Click the Help tab to open the Room Alert 32E Help screen which provides helpful links and contact information for AVTECH support resources t Advanced Computer Room R e O m E e r 5 Environment Monitoring Alerting ZAE amp Automatic Corrective Action Settings O Help Room Alert amp 32E W Firmware yX X X Released Click Here To Check For Updates Support Users Guide amp Reference Manual Resources Frequently Asked Questions Support Center Downloads Live Chat Live online SUPPORT CR nere Email Support support AVTECH com Phone Support 888 220 6700 USA amp Canada 401 528 1500 International Mon Fri 9 AM 5 PM EST You may find the version number and release date of the firmware that is installed on your Room Alert 32E on this screen To check if your Room Alert 32E has the most current version select Click Here To Check For Updates Your Room Alert 32E must be connected to the internet to check for newer firmware versions Thank you AVTECH Software Inc 49 Room Alert 32bE About Click the About tab to open the Room Alert 32E About screen which provides he
62. vices com IT Environment Monitoring Made Easy MUPS Device Discovery Device ManageR Protect Your Facility Don t Wait Until It s Too Late Protect Your IT Environment Don t Wait Until It s Too Late Room Alert Room Alert Signal Tower Signal Tower RoomAlert com TemPageR TemPageR com and Temperature Monitoring Made Easy WiSH and WiSPR are trademarks or registered trademarks of AVTECH Software Inc Any other trademarks product or company names mentioned herein are the property of their respective owners and used strictly for the purpose of identifying compatibility AVTECH Software Inc cannot attest to the accuracy of any other organization s ownership claim to a trademark and use of any trademark in this publication should not be regarded as affecting the validity of any trademark or service mark Special Thanks We would like to recognize field test participants our inhouse support staff and the entire software amp hardware development teams for their contributions and assistance in completing this manual Sales Support amp Contact Information To receive further information or assistance regarding this publication or any AVTECH product or service please contact Headquarters AVTECH Software Inc Email Sales AVTECH com 16 Cutler Street Cutler Mill Support AVTECH com Warren RI 02885 2761 USA Info AVTECH com Phone 401 628 1600 Web AVTECH com Sales 888 220 6700 EnvironmentMonitor com GoToMyDevices co
63. y uncheck Auto Negotiate and choose e For Speed 100 Mpbs or 10 Mbps e For Duplex Full or Half 3 In Gratuitous ARP Broadcasts you may leave the default Enabled or choose Disabled 4 Click Accept Changes at the bottom of your screen to temporarily save your settings You may now navigate to another screen however if you close the web interface before the next step you will lose your changes 5 Click Save Settings in the navigation bar to the left of your screen Your Room Alert 32E will automatically reboot and commit your changes 18 AVTECH Software Inc Room Alert 32bE SMTP Email You may configure your Room Alert 32E to send alerts via email and email to SMS Navigate to Settings gt SMTP Email to open the Email Settings screen Status Settings Hep About MAC Address XX XX XX XX XX XX Version XXX Email Settings SMTP Email LI SNMP Email Enabled sensors mare g Al On Enabled cR Use SMS 3 WISH Options Timeout 5 Mail Server mail yourco com Damain Name or IP Advanced Return Addres Frorm RoomAlet Y ourCo com Display URL http 192 168 2 131 Save Settings Reset Defaults Authentication optional Enable F Authentication Username RoomAlert Y our C o com Password Max 11 Characters Email Recipients Separated By Comma ITMgr YourCo com 12355519008 ATT txt net FacilitiesDept YourCo com E

Download Pdf Manuals

image

Related Search

Related Contents

Trane Vertical Stack WSHP Installation and Maintenance Manual    Product User Manual - Gerling Applied Engineering, Inc.  Arria V SoC Development Kit User Guide  Samsung GT-C3300K User Manual    Samsung YP-D1V دليل المستخدم  Fiche de données de sécurité  Manual de Primux Mistral  HGM 6120U User Manual  