        User Manual for 80V/12F Modules
         Contents
1.      Mounting holes are designed for M6 hardware    2  Torque on compressive loads should not exceed 30Ncm                                                                Alternative Mounting Options  Please check with your loxus Representative if you have unique requirements  here is an example of what can  be done to meet your needs     Toll Free   1 877 751 4222 Fax  607 433 9014 http   www ioxus com sales ioxus com     2013 Ioxus  Inc  All rights reserved     oS IOXUS  INC   r 18 Stadium Circle    OX U S Oneonta  NY 13820       Environment   For best results modules should not be exposed directly to the environment  particularly the  avoidance of direct splashes should be considered  In systems with voltages greater than 60V   protection of the terminals to avoid shock and corrosion should be instituted     Modules that are expected to see significant cycling should be mounted in free air or in forced  ventilation housing  Care should be taken to protect modules in potentially corrosive environments  and direct water splash or spray is should be avoided     In all environments the best possible performance is aided by using an anti oxidation agent on the  aluminum terminals  No Al Ox or other similar products are appropriate and highly recommended  for all terminal connections     Careful design consideration should be given to the application to prevent the overheating of the  modules  Temperature monitoring is optionally available and discussed later in this document   P
2.  4  Ifthe voltage is under 2V  connect the shorting wire provided by Ioxus to the   and    connectors    5  The module is now safe for handling  Leave the shorting wire connected at all times     Accessories   Module accessories such as mating connectors and terminal hardware are available for order   Custom cables  bus bars and monitoring connections are available on request but may require an  NRE charge and will require all relevant mounting considerations in order to design your product   Please contact your Ioxus representative with questions or requests     Operation   All modules should only be operated within their prescribed voltage  constant current and  temperature  operating window  These should be monitored to ensure the safe operation and long  life of your module     NOTE  Operation of module above 65C will void the warranty    Maintenance   The modules should be kept free of dust and debris and cleaned at a regular interval  In inside  locations  that should be no more than annually however this may vary with your particular  circumstances  Outside location will be as needed  Once the modules are discharged  proceed with  cleaning with a cloth and a simple water soap solution  Avoid the use of hoses or pressurized    Toll Free   1 877 751 4222 Fax  607 433 9014 http   www ioxus com sales ioxus com     2013 Ioxus  Inc  All rights reserved     An IOXUS  INC   a 18 Stadium Circle    OX    S Oneonta  NY 13820    sprays  Once the assembly is clean check for properl
3. 80V modules can be mounted in any orientation and are qualified for shock and vibration as is    detailed on the applicable datasheet  Please review the datasheet and test specifications to  determine the appropriateness of the module for your application     The modules should not be mounted anywhere where the frame member mounted to applies any  stress torque or twisting to the module housing  All mounting holes are located on the end plates   and should be mounted to points that are in plane with each other  or parallel to each other for  Rack mount applications   Shims and spacers should be used if any of the mounting points are    more than 4imm out of plane  8mm hardware of a grade appropriate for the application should be  used for standard 80V modules     In addition it is best to avoid mounting on or near significant heat sources such as engine exhausts  or solar heated panels    Mounting Details for Preassembled Modules     8 20 THRU FOR M8 BOLT                                 290       ors  a  ed  e  I  i   i d  Doo O         a  L     Dimension   80V 12F  Dimension   80V 12F 12F   160V 6F   240V AF   320V 3F 400V 24F 2 4F 480V 2 AF   Requires center  plate in same  location as 240V   105 2   1802   255 2   330 2 405 2 483 4 module             Toll Free   1 877 751 4222 Fax  607 433 9014 http   www ioxus com sales ioxus com     2013 Ioxus  Inc  All rights reserved     SS IOXUS  INC   a 18 Stadium Circle    OX    S Oneonta  NY 13820    Mounting for Individual Modules
4. AL EE EE EA EE EE EE 14   Toll Free   1 877 751 4222 Fax  607 433 9014 http   www ioxus com sales ioxus com       2013 Ioxus  Inc  All rights reserved     oS IOXUS  INC   a 18 Stadium Circle    OX U S Oneonta  NY 13820       Never touch the power terminals as any residual voltage can  cause fatal electrical shocks  Always check with a calibrated  meter that the module is discharged prior to handling the  module  please see the step by step instructions in this manual  for the discharge procedure     Warranty Limitation    Ioxus modules are unserviceable property of the customer and  if opened or otherwise modified  are no longer covered by any  warranty written or implied    Introduction   Ioxus modules represented in this document are designed for a wide variety of applications from  stationary back up power to transportation usage  Each module is built with welded bus bars and  internal balancing circuitry  The balancing circuitry can be one of several formats based on the  options selected  The standard balancing circuitry for the large format modules is a 2 stage active  balancing that will be described later in the document  The balancing circuitry is built in and  protected by the aluminum housing allowing the entire structure to be rugged and also meet the  water resistance requirements of IEC 60529   IP54  The specifications and recommended  configurations suggested in this manual are subject to change and should be verified by checking  the most recent version of thi
5. An IOXUS  INC   a 18 Stadium Circle    OX U S Oneonta  NY 13820    User Manual for 80V 12F Modules    Models   e iMODO80V12P1M XXA       IMODO80V012 02A    IMODOSOVO12P1M OOA       Toll Free   1 877 751 4222 Fax  607 433 9014 http   www ioxus com sales ioxus com     2013 Ioxus  Inc  All rights reserved     SS IOXUS  INC   a 18 Stadium Circle    OX    S Oneonta  NY 13820    Table of Contents    Models o E EE cece    AE OIE COON EE RE NE OE EE EE AK N 3  Module Part Numbering and it s Meaning             seeccccssssssseececcccccccccsseesececeeccccccssssssesee 4  EO CUS AE EE EE E EE d  UNDA dig ie EEN DE OE RE RE EO EE EE EE EE OE EE 4  male  ale AE EE EE N 4  pies  die  OR E EE A A E 5  Orientation and ADDU CAC ORE iS edel N GE ee ERG Eg ok RR ee oe Ee RE se ee De eek bee 5  Mounting Details for Preassembled Modules    sees ee ee ee ee ee ee RR RR ek ek ee Re Reed 5  Mounting for Individual Modules    ooo ESEG ne ede ee Re oe es GO Ie Gede ed oe eed ee oe ee 6  Alternative Mounting ODtONS ees sesse se ek Re ee ee RR ee ee ee ee ee Ge RR ee ee RR GR ee Ge Ge RR Re ee ee ee ee Reggie 6  SAAGIS LEE ee OE EE EE EE 7   NI pe ie ie EE EEN EL OE EE EE EE ON EE OR EE EE EG 8  Mieta lae kie ARE ER EE EE EE EE EO N EE OE EE EE EE N 9  BaN ye N OE EN EE      Sarel AE N ER EE EE A 12  Blei gel die EE OE RR RE EE OR EET 12  PEC io     EE EE EE EE 13  Opera ON ER EE EE N E E EON E 13  Mamnte nae E ME EE N EE EE 13  FE SC OMG RNG MR EE AE EE EA EE EE 14  OS ER OE EE EE EE EE EE EE 14  DISPOS
6. ers possible    module voltage rating in Volts   three digits   M for    module     i for IOXUS       Logistics    Unpacking   Please inspect the shipping carton for signs of damage prior to unpacking the carton  Report any  damage to the carton  or the contents  to the carrier immediately  Retain all shipping materials  until the module is fully inspected and determined to be operational     The module should be lifted by the module body  The terminals should not used for hoisting  The  terminal shorting wire should remain in place     If any parts are determined to be missing or defective an RMA number must be issued prior to  returning the unit for repair or replacement  Please contact your salesperson or distributor to  request an RMA number     Handling  Ultracapacitor modules are designed for years of maintenance free operation if handled  installed  and used properly  These handling precautions should be observed     e The modules should not be stacked unless still in original packaging    Toll Free   1 877 751 4222 Fax  607 433 9014 http   www ioxus com sales ioxus com     2013 Ioxus  Inc  All rights reserved     SS IOXUS  INC   a 18 Stadium Circle    OX    S Oneonta  NY 13820    e The only tools to be used on the module should be properly sized wrenches for the terminal  and mounting bolts  hammers  chisels  files or power tools in general should not be used   e Do not drop modules  invisible internal damage mage occur    Installation    Orientation and Application  
7. lease refer to the operational temperature range on the data sheet and be sure to allow for    Toll Free   1 877 751 4222 Fax  607 433 9014 http   www ioxus com sales ioxus com     2013 Ioxus  Inc  All rights reserved     An IOXUS  INC   a 18 Stadium Circle    OX    S Oneonta  NY 13820    internal heating of the modules  If you require help with the design considerations and sizing  please contact your representative for assistance     Venting  Please note a venting hole is built into each module and a filler bolt is fitted to it  If external  venting is required remove the M5 bolt and fit with appropriate plumbing to relocate the vent     Electrical    Modules can be mounted in series and or parallel with each other  Care should be taken to insure  that similar capacitance and ESR modules are used for series chains and that if different type or  age modules are used in parallel configurations the differences in ESR are accounted for in your  design     Appropriate size bus bars or cables and terminals should be used for the application  Please note   that to minimize system loses the capacitors do not have fusing or internal circuit breakers  careful  consideration in the system design should be taken to prevent over current  With the low ESR of  the capacitors they can deliver very large amounts of current     A grounding strap should be installed on each module  The worst case fault current should be  considered when sizing the wire for this application  It is recommended 
8. nc  All rights reserved     An IOXUS  INC   a 18 Stadium Circle    OX U S Oneonta  NY 13820          Pin 4  Pin 5   Reserved Stop Col  Pin 3  Pin 6   Overtemp Emt Reserved  Pin 2  Pin 7   Reserved Stop Emt    Pin 1  Pin 8   Overtemp cal   Reserved       E  o Digital Outputs are continuously parallel able  they can be paralleled across parallel  and series module connections        x         Figure 1  Module with Monitoring Installed  Additional constraint of cabling may be required for your application    Toll Free   1 877 751 4222 Fax  607 433 9014 http   www ioxus com sales ioxus com     2013 Ioxus  Inc  All rights reserved     SS IOXUS  INC   a 18 Stadium Circle    OX    S Oneonta  NY 13820        02X Digital overvoltage and over temperature    Over Voltage Collector    Reserved   Over Voltage Emmiter  o  8 Reserved    o Over temperature caution triggered when the sensor measure greater than 60C  internal module temperature  o 2 monitoring output connectors are fully parallel  no priority    This allows several modules to be monitored with only 2  or in fact  1  monitoring circuit if you are not concerned which event causes  the warning           Digital Voltage  or  Temperature   Warning    To MCU  Low                      Pins 3 or 77    Balancing   The standard balancing for the 350F cell based modules is passive system  This is a rugged and  reliable system and accomplished by hardwiring 1200  1  resistors in parallel with each cell   This will drive the cells to conve
9. rgence on a float charged system  rapidly reduce voltage on  an overvoltage cell and discharge the module for service over about 24 hours     Toll Free   1 877 751 4222 Fax  607 433 9014 http   www ioxus com sales ioxus com     2013 Ioxus  Inc  All rights reserved     SS IOXUS  INC   a 18 Stadium Circle    OX U S Oneonta  NY 13820    Safety       Never touch the power terminals as any residual voltage can  cause fatal electrical shocks  Always check with a calibrated  meter that the module is discharged prior to handling the  module  please see the step by step instructions in this manual  for the discharge procedure     e Prior to installation or removal the module and or system of modules must be discharged  fully and shorting wires installed  procedure below    e Provide sufficient electrical isolation for operation above 50VDC   e Protect surrounding electrical and conductive components from incidental contact   e Do not operate above specified voltage or temperature range   e Do not touch terminals while charged  serious burns  shock or material fusing may occur    Discharging       A fully discharged module may    bounce back    if it is stored  without a shorting wire connected to the   and   terminals   This bounce back can be as much as 12V for an 80V module   and is enough to cause dangerous electrical shocks and other  undesirable consequences     Toll Free   1 877 751 4222 Fax  607 433 9014 http   www ioxus com sales ioxus com     2013 Ioxus  Inc  All rights reser
10. s document and the product datasheets on www IOXUS com        Please keep note of your model number when referencing this manual and note if each section  refers to your specific model number     If your model has an output connector  specifications for that connector and how to use each  connection will be detailed in the appropriate sections below     Toll Free   1 877 751 4222 Fax  607 433 9014 http   www ioxus com sales ioxus com     2013 Ioxus  Inc  All rights reserved        _       IOXUS  INC     18 Stadium Circle          OX    S Oneonta  NY 13820    Module Part Numbering and it s Meaning    Hro PPP bheg e SLEE      ra Numeric for F roto  Option Codes  Numeric for standard  Alpha for customer specials   sss   i      sSSC Alpha for customer specials   sss   i      sSSC customer specials  separator  used for readability       Cell Terminal Type Terminal Cell Terminal Type  Cell Type Cell Type  P for passive P for passive balancing w o clamping P for passive balancing w o clamping clamping  Capacitance Capacitance value rounded to the nearest Farad  three digits        rounded to the nearest Farad Capacitance value rounded to the nearest Farad  three digits        digits   V V for    voltage     for multiples of 6 cells  round down to closest multiple of 16    V for    voltage     for multiples of 6 cells  round down to closest multiple of 16     for multiples of 6 cells  round down to closest multiple of 16     B for TIT w  single stage clamping  X for no balancing  oth
11. to remove the anodizing or  coating  if applied  on the housing at one of the bolting points to allow for the ground strap to be  properly installed     Thread locking should be done with star washers or an appropriate chemical thread locker used on  threaded portion of terminal bolt not the electrical connection  in no case should flat washers be  used with lock washers     Care should be taken in cable routing to not impose undue forces  torques or tensions  on the  module terminals  Only appropriately sized ring terminals or bus bars for the expected currents  should be used     Toll Free   1 877 751 4222 Fax  607 433 9014 http   www ioxus com sales ioxus com     2013 Ioxus  Inc  All rights reserved     oS IOXUS  INC   a 18 Stadium Circle    OX U S Oneonta  NY 13820       Power Connections   Configured as 400V module     Series Connections    Monitoring  There are 2 types of available monitoring configurations noted by the suffix on the part number for  your module s      1   00X   No Monitoring  2   02X   Digital overvoltage caution  digital over temperature caution    e General Specifications for monitoring   02X   o Operating Voltage 5 24V Max 80V  o Overvoltage output  Digital  open collector    Trigger if any group of 3 cells exceeds 8 25V  2 75V cell   o Max operating current    o 3mA  o MFG part number for mating connector    RJ45    s Contacts 8  o Pin out Diagram    Toll Free   1 877 751 4222 Fax  607 433 9014 http   www ioxus com sales ioxus com     2013 Ioxus  I
12. ved     SS IOXUS  INC   a 18 Stadium Circle    OX    S Oneonta  NY 13820    Prior to any maintenance or replacement each module should be individually discharged and  shorted with a resistor or wire  Even a fully discharged module can rebound naturally to an  unsafe condition  Be sure to discharge with an appropriately sized resistor or resistor bank  not  provided  and either keep that resistor attached or replace it with a shorting wire or bus bar when  the module is depleted  Be sure to check the voltage with a calibrated meter prior to attaching the  shorting device  The voltage should be 00 25V     1  Using a voltmeter  measure the voltage between the 2 terminals    2  The pack will naturally discharge to below 5V because of the passive balancing in   lt 48hours   3  Ifthe voltage is above 2V  a resistor pack  not supplied with the module  will need to be  connected between the terminals  Proper care needs to be taken in the design and  construction of such a dissipative pack  e g  At 48V  for a 4 Ohm pack  the module will  be initially discharged with a current of 15A and will take about 15 minutes to fully  discharge  However  in this case  the heat power dissipated in the resistor pack will be    1 2kW  The resistor pack will need to be sized and provided with suitable cooling to  handle this power dissipation  Additionally  proper enclosure or other packaging is  necessary to ensure safety  In all cases  proper design of the dissipative resistor pack is  necessary   
13. y torqued fasteners and note any damage to  any of the housings or signs of internal damage and replace as necessary     In high vibration applications fasteners used for mounting as well as electrical connections should  be checked for torque every 6 months     Reconditioning  This module does not require condition because of the passive balancing system     Storage   The module can be stored in the original package discharged in a dry place  Observe the maximum  storage temperature as stated in the specifications  Discharge used module prior to stock or  shipment  The shorting wire shipped with the unit should be retained for use during storage to  prevent charge from accumulating in the module     Disposal  Please recycle according to local codes and regulations for flammable materials     Toll Free   1 877 751 4222 Fax  607 433 9014 http   www ioxus com sales ioxus com     2013 Ioxus  Inc  All rights reserved     
    