Home
        User Manual - RainHarvest Systems
         Contents
1.     DEVICE  ADJUSTMENT          LANGUAGE  ENGLISH          Jm  UNITS    INCH   CM                          MEASURING LENGTH  30 600cm 200       I       OPERATION TERM  1  REFILL NO       Tr       OPERATION TERM  2  BACKUP NC             Tr     Main menu level       key  ENTER      A 20 feet Sensor may be ordered      Output 1 has been configured for the  Refill   function and NO   normally open  Therefore the  valve  or the pump  for the function  Refill   should be attached at terminal 1     Output 2 has been configured for the  Backup   function and NC   normally closed     Page 14       OPERATION TERM  3  PUMP NO       Tw        OPERATION TERM  4  DRAIN NO                  OPERATION TERM  5  ERROR NC                   Output 3 has been configured for the  Pump   function and NO  normally open     Output 4 has been configured for the  Drain   function and NO  normally open     Output 5 has been configured for the  Error   function and NC  normally closed     Figure 12  Sub menu  General device description     For each terminal the selection between the following functions exists     BOOSTER PUMP NO  BOOSTER PUMP NC  CLEANER NO  CLEANER NC  BACKUP NO  BACKUP NC  TRANSFER NO  TRANSFER NC  REFILL NO   REFILL NC   PUMP NO   PUMP NC   DRAIN NO   DRAIN NC    Note     Please configure each output according the requirements of your rainwater    system requirements     Page 15    The function of the output can be specified for each terminal separately  normally  open or normally clo
2.     REFILL ON  0 100                     Flush the drinking water supply pipes for 30  seconds     Cleaning the rainwater filter every 14 days  The value 0 switches the cleaning process off     Cleaning the rainwater filter for 5 seconds    Cleaning the rainwater filter when the fill level  has increased by 2  after rainfall  If the fill level  continues to increase  the rinsing will be repeated  every 3 hours     6699    Cleaning the drain tank every    x    days     TAE     Cleaning the drain tank for    x    minutes     This enables water to be pumped out of the main  tank  The chosen numeric value    Transfer from   should always be greater than the numeric   value    BACKUP OFF       The water will be pumped off when it rises above  the set value  To prevent constant switching on  and off of this function  it is pumped off to 2   under the opposed value     Numeric value is always greater than the value     BACKUP ON    and less than the value for     REFILL OFF        Page 13       REFILL OFF  0   100                Ter    Numeric value is always greater than the value  for    REFILL ON        Figure 11  Sub menu    Switching points       Press the    ENTER button to alter the respective switching points The value to be  altered will begin to blink  The value may then be adjusted by using the      and the      buttons  Press the    ENTER    button again when the displayed value should be    accepted     The following is an introduction to the general device settings    
3.    Figure 7  Display during the equipment check    The equipment type is shown on the first line and the software check in progress is  shown in the second line    If after the initial installation check all 15 correct  the LCD indicator will display the  fill level  in 9o      Figure 8 shows the LCD display in the operation mode  The display shows the  filling level and the operating modes as abbreviations   FV  and  P   These abbre   viations correspond as follows       FV   filter cleaning valve opened     FV   filter cleaning valve closed     P    pump on  house waterworks in operation     Pe  pump off  no water currently being withdrawn    Status of rain water  filter flushing valve      0    Status house waterworks     pump   on     off   Tank  FV  P   50              Fill level in     Visual display of the fill level    Figure 8  Display in the operation mode    Page 10    4  Set up of the system control     After putting into operation  the system control must be adjusted and programmed  according to the conditions and requirements of the individual user s system  The  required settings are easily programmed  There are four buttons for this purpose   All necessary programming data entries follow a menu displayed by the LCD  For  the set up  follow all the points listed in table 1 in the sequence shown  Should any  error in the sequence occur then it is necessary to begin the set up again from the  beginning starting with the tank height  Begin the programming of the s
4.  entries have been received for approximately 30 seconds     Page 11       23                  TANK  FV  P                    key                 255              SWITCHING POINTS       e DEVICE e MANUAL OPERATION       ADJUSTMENT                      T                     Figure 10  Main menu level    Press the    ENTER    button to arrive at each of the listed sub menu functions   Through pressing the    MENU    button again the display changes back to the opera     tion mode        SWITCHING POINTS                   PUMP ON  0 100  8        Ir       PUMP OFF  0 100  6                                       0 100  10         Ter       BACKUP OFF    0 100  12                 BACKUP INTERVAL  0 14 DAYS 14             Main menu level        key    ENTER       Pump ON  The numerical value is always smaller  than with BACKUP ON      Pump OFF  The numerical value is always smaller  than with PUMP ON      Supply with municipal drinking water   ON  The  numerical value is always smaller than with  BACKUP OFF      Supply with municipal drinking water   OFF    Flush the drinking water supply piping every 14  days  The value    0    switches the flushing off     Page 12             BACKUP  0 60 SEC 30       I          CLEANER INTERVAL             0 14 DAYS 14         CLEANER DURATION   0 60 SEC 5                   CLEANER RINSE AT  INCREMENT 2         Ter       DRAIN DELAY          0   60 DAYS  iti   DRAIN TIME   0 60 MIN       em          TRANSFER FROM  0     100                      
5. User Manual    AquaControl    Rainwater System Controller    Item no   351027          TANK  tis EME  23                            e                       e     MENU       e       Aqua Control      Serial       AS AQ RH 5000    Otto Graf GmbH Carl Zeiss Str  2 6 Tel     49 0  7641 5890  Kunststofferzeugnisse D 79 331 Teningen Fax   49 0 7641 58950    Page 1                RC          Aqua Control       gt  24VAC          e      wsa  3    Serial No   AS AQ RH 5000       Figure 1  View of equipment    qug DM EC UI ET    LED for power supply   Information Display   LED for drinking water operation   LED for faults and malfunction   Operating buttons   Lower cover of the System Control   The main fuse for the rainwater system controller is under this  cover     Page 2                         Figure 2  Sensor assembly    12  Data cable  13  Wire seal 3    14  Connection of the data cable is polarity protected   15  connect white wire here   16  connect red wire here   17  data cable terminal    18  Wire seal 2  19  Wire seal 1    Page 3    20  active measuring length    21  When assembling be sure that the cable spacers are equally dis   tributed over the cable length    22  Stainless steel probe   23  Tank floor   24  Screws must be blunted    danger of injury    25  overflow   26  Tank or riser wall   27  Sensor   28  Sensor control box    Important notes on safety     Please read and follow safety instructions carefully  before assembly or using the device     Equipment using 
6. a 120 V   supply may only be installed and commissioned by a  qualified tradesman  The assembly place must allow all possible safety precautions  when laying the attached cables    Power supply cables and data cables mast not be damaged or pinched in any way   Plan the assembly place so that you can reach the transformer easily and unplug it  from the electrical outlet in dangerous situations    Choose the assembly place so that children cannot play or be near the device and  its connections without supervision    Before opening the device  disconnect it from the main supply  unplug  otherwise  there is a serious danger of an electrical shock    Fuses may only be replaced with standard compliant parts with the same nominal  value    All liability is excluded for damages which result from non compliance of these in   structions or from improper handling of the device  At chosen intervals in this hand  book we will give directions for safety precautions  These safety precautions have  been specially marked     STOP STOP Before opening the equipment    unplug the transformer from the outlet     Page 4    1  Description    The AquaControl   is an electronic water management control system    It has been developed especially for rainwater usage systems  It can be used with a  wide variety of tank systems    Tanks made from metal or steel reinforced cement may only be used when the fol   lowing conditions have been correctly followed    Metal tanks lead to faulty readings  It is op
7. and tighten this  lightly  then connect the red wire to the terminal  16   The free white wire  is now passed through the wire seal 2  18  and tightened lightly  then  connect the white wire to the terminal  15      6  Now pass the end of the data cable  12  through the wire seal 3  13    Lightly tighten the wire seal and connect the cable wire cores of the data  cable  12  to the double terminal  14   The connection of the data cable is  reverse polarity protected  Attention  The screws should be tightened  with care to ensure that they are not damaged through over  tightening     7  Now recheck that all the connections and the sensor components have  been fitted correctly  Replace the cover ofthe sensor control box and  secure this with the appropriate fastening screws     8  Atthe main system control unit  remove the jacket from the ends of the  sensor data cables  strip about 4  of insulation from the wires  and insert  each wire into the appropriate terminal   Tighten the terminal screws  securely              Lo                                     GGGGG 24V 60Hz 1    2 3   4    Input   Sensor    Figure 5  Connection of the sensor system at the System Control    Page 8    Note     The red and the white wires going down to the probe should be straight and  smooth to be drawn taught      the weight of the stainless steel probe  The stainless _  steel probe must hang just above the tank floor  When setting the spacers please be  sure to distribute them equally over the comp
8. ettings by  pressing the button marked    MENU       With the buttons         or         the menu may be scrolled backwards and forwards   With the respective menu point shown the values may be altered  For this the  button    ENTER    must be used  The value begins to flash  With the         or         the  desired value may now be entered according to individual requirements  When the  desired value has been entered this must be confirmed by pressing the  ENTER   button  The value is only then taken over and stored in the programming of the unit   Through pressing the    MENU    button again the display changes back to the  operation mode    It is possible to reset the unit to the factory setting standard values at any time   The resetting can only be carried out in the operation mode  Display see Figure 7    To do this press the    ENTER    button and hold it pressed  Now simultaneously in  addition press the    MENU    button  After a short wait the following display will be  shown        DEFAULT VALUES  23                   Figure 9  Message reset to standard factory settings    As soon as this message is displayed the buttons may be released    The menu structure integrated in the system control is outlined in Figure 9  To  bring up the menu  press and hold the   MENU    button for longer than 5 seconds        outputs are inactive when the menu level has been activated and operation of  the device is suspended  The system automatically returns to operating mode when  no
9. le        The sensor electronics comprise of a stainless steel probe  22  with red and white  connecting wires  27  and the sensor control box  28            Figure 4  Sensor technology    l     N    Now the sensor control box  28   cover removed  should be installed on  the tank wall  preferably in the man hole shaft of the Graf synthetic tank    The location of the mounted sensor control box should be between 4    and  6    above the overflow  25   The enclosed screws should be used to secure  the device  After fully tightening the screws  the points that are showing  themselves on the outside of the tank must be blunted to avoid injury  24      Measure the height from the bottom of the tank  23  to the end of the  terminals  15  and  16  on the  28        Shorten the connection cable to suit the measured height       After shortening the cable  the distance between the cable fastening    spacers  21  should be set equally along the entire length  The cable  fastening spacers prevent the red and white wires of the sensor from  crossing over and thereby causing a slight distortion of the measurement    Page 7    readings  If for any reason the cable fastening spacers cannot be mounted   an additional distortion of the measurement reading of approximately 196  may result     5  Connect the sensor cable to the sensor as described in the following  instructions  Remove approximately 1 4  of insulation from both of the  wires  Next  pass the red wire through the wire seal 1 19  
10. lete length as shown in Figure 2        2 3  Electrical wiring diagram       The AquaControl  offers the rain water system a dry run protection for the pump  or the house water system when equipped with an external pump relay  In order for  the dry run protection will function properly the rain water system must be wired  according to the following diagram     j                                                    Fuse 500mA  Sensor  au               Vs Output   GGGGG 24V 60Hz 1lPl2l3l4       0   10V    NO c  24V AC     Function Relay 5  1  Terminal 1 G  Ground  grounding conductor   2  Terminal 2 24V 60Hz  Input 24V AC  3  Terminal 3 P  Input 24V AC    4  Terminal 4  NO COM NC  Terminal 5    For the supply of 24V AC to operate valves and other accessories  external power  must be supplied to the 24V AC input terminals using a transformer sufficient for  the needs of the attached devices     Figure 6  electrical wiring diagram    Page 9    3  Activation and calibration process   Before the energizing the equipment  be sure that all electrical connections are cor   rectly insulated and all covers are properly closed    Now open the transparent cover of the system controls  Plug the transformer into  the outlet  this outlet must be exclusively for the equipment and be on its own  breaker   The system runs a self test automatically    For the duration of the system check  approx  10 seconds  the following signal will  be displayed in the window                       02 0          
11. mmed to original setting        ips    Figure 14  Sub menu    Manual functions       Page 17    5  Error messages and fault correction        The operation of the system control should be checked at regular intervals  at  least every 4 weeks      The error messages provide an indication of general symptoms  Additional  troubleshooting will be required to determine the underlying cause and necessary  actions     Please also take note that the system control device cannot sense any malfunc   tion of the municipal water supply or house water system   No malfunction signal    is supplied by external water supplies or devices to the system control device      If faults are recognized by the tank level sensor  the system control cannot continue  to work properly     The following faults are shown in the plain text on the display        ERROR The reason for this error is that the white  SENSOR sensor wire has been damaged           Error possibilities    The data cable of the sensor control box  is not connected to the data cable terminal   14  but has been connected to the sensor  terminal    Wires of the data cable have been damaged    ERROR  DL SHORT CIRCUIT                ERROR The sensor control box delivers no signal  SENSOR CONTROL and must be replaced              For further diagnosis  remove the stainless steel  weight  22  out of the water  If the error indication  has now stopped  then the sensor itself was the  cause of the fault  If the error indication continues   thi
12. oltage   24V AC  Maximum Current   SAmps Maximum Current               Terminal 5   Operating voltage   120V AC DC   Maximum Current   3Amps    Analogue outlet     Minimal apparent ohmic resistance   20K Ohm   Short circuit protection   Yes   Short circuit current   Approx 15mA   Cable length   650 feet  maximum   shielded  Note     Only the control electronics in the device are protected by the fuse  Valves and  pump connections are not protected  These are protected only by the mains supply  via the circuit breaker     The yellow LED indicating    Drinking water operation     3  is lit as soon as the  valve switches over to the mains supply  The user is made aware that the system  now uses water from the mains supply  The red LED for    Faults and  malfunctions     4  is lit as soon as the system identifies a fault  The display will  then show a warning that describes the cause of the fault in plain text     2  Assembly  2 1 Control system    The mains plug of the transformer serves as an on   off switch   STOP Before opening the equipment  unplug the transformer from the outlet       Loosen the fastening screws of the lower cover  6  and remove the cover    Mark out drilling points and drill according to sketch    Page 6      Fasten the device with the enclosed installation hardware  screw anchor and  Screws             75 5mm   75 5 mm   2 97    2 9 7      120 mm     4 72      4         Figure 3  Drilling outline for housing outline    2  2 Connection sensors and data cab
13. s implies that the sensor control box 15 defective        ERROR  SENSOR SYSTEM             Page 18                      ERROR The communication between the system   NO SIGNAL control to the sensor control box is  interrupted    ERROR First try re setting the system control to the   MEMORY factory default settings   If the error message  continues to be displayed then it is necessary    to contact your service partner    Note  After resetting to the factory  default settings all the newly  programmed setting values will  have been overwritten and must be    re programmed   Figure 15  Error messages    If the device shows no function at all then check whether the main electrical supply  provides current and also check the house breakers     STOP STOP Before opening the equipment    unplug the transformer from the outlet     If the electrical outlet is working properly  then unplug the transformer from the  system control  Once the system has been de energized open the lower cover of the  system control  see Figure 1  and check the rainwater system controller main fuse     6  Analog outlet      Your device has been fitted with an analogue terminal  This terminal shows the per   cent values from the system control  0   100   by a voltage range from      to  10V DC  The following connection values apply     Minimal apparent ohmic resistance   20K Ohm   Short circuit protection   Yes   Short circuit current   Approx 15mA   Cable length   650 feet  maximum  shielded    Page 19    No
14. sed   Please consider the maximum current values for each in   dividual terminal     Terminal 1  5Amps  Terminal 2  lAmps  Terminal 3  lAmps  Terminal 4  lAmps  Terminal 5  3Amps                ES  EB         1                                        GGGGG 24V 60Hz         w     gt              2 02  S                       Terminal 5             B eee  NO   normally open  COM   common  NC   normally closed    Figure 13  Allocation of the relay outputs    Page 16    The last part of the operation level covers the manual functions        MANUAL OPERATION  Main menu level          Key    ENTER       LAST FLUSH  BACKUP 0    m       Time scale in days  elapsed since the last flush  using municipal drinking water                Activation of the flushing process for the municipal                         prc  me NO drinking water inlet pipe  The switch over valve  remains permanently switched on until reprogrammed  il ma to original setting   LAST RINSE Time scale in days  elapsed since the last filter  CLEANER 1 rinse   e       HAND RINSE Activation of the filter rinse  The RINSE valve  CLEANER NO remains permanently switched on until reprogrammed  to original setting           The refill function may also be regulated by hand The                HAND        REFILL REFILL valve remains permanently switched on until  reprogrammed to original setting   Eds  Activation of the drain tank cleaning  The DRAIN  HAND         DRAIN TANK valve remains permanently switched on until    reprogra
15. te     The system control is only capable of displaying whole percent values  no frac   tions   These are shown on the analogue signal display                       EN              GGGGG 24V eOHz 1     21314                         Output        10V    Figure 16  Allocation of the analogue terminal    Page 20    Attachment A     Symbols used        Attention  Pull out the mains plug from the socket before  opening the device     Attention  An error has occurred     Mains drinking water operation    Page down    Page up    Only for use in a dry areas        Room for your notes     Page 21             22             23    Purchase date    Device serial number   Type   AS AQ                        Tank height                     Software level       REV   U2 0    Design and specifications are subject to change without notice  Dated  September 2011   Version        U2 0    Page 24    
16. timal to install the device so that the  sensor is as far as possible from the metal sides so  for example  in the center of a  cylindrical tank  The system controls offer an easy to use guide for the switch pro   gramming  Using an LCD display the fill measurement is shown in 1   stages  in  relation to the height of the tank   The sensor operates with 12 volts DC  supplied  from the main control unit    All programmed values such as the tank height are retained after disconnection  of the power supply or after loss of power     Performance features       Fill level measurement display in 1  steps with a bar type indicator     Freely variable switching points in 1  steps for drinking water refill     Automatic flushing of the system intervals in days  and duration in  minutes are programmable     Dialogue oriented user guidance  choice of language      Equipment indication using 3 additional LED        Supervision of the sensor control box and the sensor     Error indications in simple text     Analog output for connection to external systems  0 10V DC    Technical data     Control electronics Measurement sensors   Operating current  224VAC Measurement voltage  12   DC   Fused  T500mA Measuring frequency       0 2 20 kHz   Power consumption         Data cable length  165 feet   maximum   Tank height  9 8 feet  optional 20feet    Measurements  6 1 7x6 5 x3 5  Measurements   3 6     3 2     2                5    Terminal 1 Terminal 2 4    Operating voltage   24V AC Operating v
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Eglo OROTELLI  COCINA POR INDUCCIÓN Modelo: CIJ  SYSTEM 3000 BASIC 3000 SET F3 Funkalarmanlage  ATVisionPro - Advanced Technology Video  ESPAÑOL INSTRUCCIONES DE USO  BANKSCHLEIFMASCHINE BEDIENUNGSANLEITUNG - BM  DPG10A - Chamois Metrology  Philips SWS4686W 4-Way Automatic Scart switcher  Sony XM-ZR604 User's Manual  Water Analysis - Pacific Laboratory Products    Copyright © All rights reserved. 
   Failed to retrieve file