1. BD Eindhoven The Netherlands Tel 020 7942 0700 Fax 020 7942 0701 E mail industrial uk fluke nl In Canada 905 890 7600 or Fax 905 890 6866 From other countries 1 425 446 5500 or Fax 1 425 446 5116 Visit us on the worldwide web at Visit us on the worldwide web at www fluke co uk www fluke com Copyright 2006 Fluke Corporation All rights reserved Printed in the Netherlands 04 06 Data subject to alteration without notice Pub_ID 11097 eng 430 Series Three phase Power Quality Analyzers EZM b Vi funa 229 7 Vo fung 223 0 Us tuna 221 0 Hz 50 00 OU tis 0 Woe 122 Uas 239 OMIS 16 41 08 VEA Liu L N score Ee EEn Enma Fluke 435 Fluke 434 True Ams Volts Amps Hertz On all inputs 4 15 04 95 mi L1 L2 L3 N Urms 230 80 223 86 222 38 9 74 V pk 324 8 326 0 316 0 17 3 CF 1 41 1 46 1 42 1 78 Hz 49 994 L1 L2 L3 N Arms 286 e75 282 2 2 A pk 427 421 424 40 CF 1 49 1 53 1 50 1 79 04713706 11 02 05 Tu 2300 50Hz38 WYE 06 29 04 02 38 22 Tu 230u 50Hz 38 WYE CUnoun ZOOM 2 gt ON OFF HRSEH lt gt PREU NEXT 7 AutoTrend automatically records all displayed parameters in the background EN50160 Pinpoint power quality problems faster safer and in greater detail The Fluke 435 and 434 three phase power quality analyzers help you locate predict prevent and troubleshoot problems in power distribution systems Th
2. bars clearly indicating which parameters fall outside the limits MONITO 230 PEI MN 3 60 9 230 840 9 230 82U 21 55 09 lt Limit NAllowed MONITOR EVENTS URMS 047 START 08712704 19 55 17 191 22 59 DATE TIME TYPE LEVEL DURATION 08 13 04 12 06 08 433 08 13 04 12 06 08 433 ARI CHER Unt te Red 08 13 04 12 06 18 433 08 13 04 12 06 18 433 08 13 04 12 06 18 433 08 13 04 12 06 18 433 08 13 04 12 06 18 433 08 13 04 12 06 18 433 08 13 04 12 06 18 433 gt i Hote Sh hi neoinein in a ANS i o EN50160 TREND BACK 08 23 04 20 10 37 230V 50Hz38 WYE SELECTED NORMAL ALL DETAIL The System Monitor overview screen gives instant insight into whether the voltage harmonics flicker frequency and the number of dips and swells fall outside the set limits A detailed list is given of all events falling outside the set limits 430 Series Three phase Power Quality Analyzers 744 28 40 o lt a Li Le ia N Urms 230 83 223 86 222 38 9 76 Li Le L3 N Arms 286 e75 28e 22 L1 Le L3 N Hz 50 004 Li Le L3 kW 64 7 58 9 62 1 04 13 06 14 38 05 185 6 230U SOHZ3G8 WYE EN50160 EVENTS OPEN TREND 31 MENU Logging function allows you to customize measurement selections and provides instantaneous analysis of user selectable parameters Fluke 435 with flex clamps Included Accessories Hard carrying case C430 434 Water tight hard case with r
3. 30 4 7 4 15 compliance Class A Class B 5 Built in general purpose Scope and DMM Memory screens data 50 10 50 10 20 for ji and ata Memory size 16MB 8 MB FlukeView software and interface cable oO Depending on configuration Power Log Software Optional EN61010 safety rating 600 V CAT IV 1000 V CAT III 600 V CAT III Current clamps included 4 x 1430 Flex 4 x 1400S 1400S Optional functionality can be added with Logger upgrade kit For details see ordering information Logger uses user configurable shared memory Fluke 43B A choice of three configurations 43Basic 43B 43Kit i400s Current Clamp SW43W FlukeView Software OC4USB Serial Interface Adapter Cable USB C120 Hard Case 4 VPS40 Voltage Probe Fluke 61 IR Thermometer VR101S Voltage Event Recorder All configurations are delivered with test leads probes clips battery pack banana to BNC adapter and line voltage adapter battery charger Check the Fluke web site for Technical Specifications and Application Notes with the Fluke power quality analyzers Fluke Keeping your world up and running Fluke UK Ltd Fluke Corporation For more information call 52 Hurricane Way P O Box 9090 In the U S A 800 443 5853 Norwich Everett WA USA 98206 or Fax 425 446 5116 Norfolk In Europe M East Africa NR6 6JB Fluke Europe B V 31 0 40 2 675 200 United Kingdom P O Box 1186 or Fax 31 0 40 2 675 222 5602
4. Power Quality Analyzers In industry healthcare and business in fact wherever electrical and electronic equipment is indispensable power quality plays a critical role in maintaining continuity Non linear loads switching load changes and equipment problems can result in poor power quality Poor power quality is not only costly in terms of wasted energy and unnecessary downtime it s also dangerous and increases risk of equipment failure Fluke has an unrivalled range of power quality analyzers to help you maintain high quality power systems The tools give you the power to analyze every parameter power related event or anomaly faster safer and in more detail than ever before Analyze your power network quickly FLUKE o Features 435 434 43B Application Three phase Single phase Inputs 4 voltage and 4 current 1 voltage and for 3 phases and neutral 1 current Measurements Vrms Arms Hz W VAR VA PF Cos DPF Crest Factors Harmonics and THD V A W k factor Inter harmonics kWh and KVARh kVAh demand interval Flicker Plt Pst PF5 O amp Unbalance O Mains signaling 8 Optional Recorder AutoTrend 0 0 0 0 e Logger Optional System Monitor EN50160 compliance Real time scope Phasor diagrams 0 0 0 0 e Dips and swells Half cycle based e e 0 0 e Transient display Inrush current O IEC61000 4
5. al voltage Vpk 1 1400 V 5 of Vnom Crest factor voltage 1 0 gt 2 8 5 Arms AC DC 0 20 000 A 0 5 5 counts Apeak O 5500 A 5 Crest factor A 1 10 5 Hz 50Hz nominal 42 50 57 50 Hz 0 01Hz Dips and swells Vrms AC DC 0 0 100 of Vnom 0 2 of nominal voltage Arms AC DC O 20 000 A 1 5 counts Harmonics Harmonic interharmonic n DC 1 50 Off 1 49 measured according to IEC 61000 4 7 Vrms 0 0 1000 V 0 05 of nominal voltage Arms 0 0 4000 mV x clamp scaling 5 5 counts Watts depends clamp scaling and voltage 5 n x 2 or reading 10 counts DC voltage 0 0 1000 V 0 2 of nominal voltage THD 0 0 100 0 2 5 V and A 5 Watt Hz O 3500 Hz 1Hz Phase angle 360 360 nx 1 5 Power and Energy Watt VA VAR 1 0 20 00 MVA 1 counts kWh kVAh kVARh 00 00 200 0 GVAh 1 5 10 counts Power Factor Cos DPF 0 1 0 03 Flicker Pst 1min Pst Plt PFS 0 00 20 00 5 Unbalance Volts 0 0 5 0 0 5 Current 0 0 20 1 Transient capture Volts 6000 V 2 5 of Vrms Minimum detect duration 5 ps 200 kS s sampling Inrush mode Arms AC DC 0 000 20 00 kA 1 of meas 5 counts Inrush duration selectable 7 5 s 30 min 20 ms Fnom 50 Hz AutoTrend recording Sampling 5 readings sec continous sampling per channel Memory 1800 min max and avg
6. ese easy to use handheld tools have many innovative features to give you the details to pinpoint problems faster and safer e Complete three phase troubleshooting tool measures virtually every power system parameter voltage current frequency power power consumption energy unbalance and flicker harmonics and inter harmonics Captures events like dips and swells transients interruptions and rapid voltage changes e The Fluke 435 features 0 1 percent voltage accuracy making it fully compliant with the IEC 61000 4 30 Class A standard e Logger record the detail you need Detailed user configurable long time recording gives you the MIN MAX and AVG readings of up to 100 parameters on all 4 phases with selectable averaging time down to 0 5 seconds Enough memory is available to record 400 parameters with 1 minute resolution for up to a month e Four channels simultaneously measures voltage and current on all three phases and neutral e Autoscaling easier trend analysis with automatic scaling of the vertical axis you will always use the full display to view the waveforms e Automatic transient display captures up to 40 dips swells interruptions or transients automatically e Meets the stringent 600 V CAT IV 1000 V CAT II safety standard required for measurements at the service entrance e Rugged handheld instrument operates for more than 7 hours on included rechargeable NiMH battery pack Menu driven interface si
7. mplifies operation e Extensive data analysis possibilities Cursors and zoom can be used live while taking the measurements or offline on stored measurement data The stored measurements can also be transferred to a PC with FlukeView software included with Fluke 435 and 434 e The Fluke 435 comes with Power log software to analyse recorded data and to create reports e Complete package includes everything to get started 4 current clamps 4 flex clamps with Fluke 435 5 voltage test leads and clips line adapter battery charger and hard case e Complies with IEC 61000 4 30 measurement standards AutoTrend Quickly see the trend Unique AutoTrend gives you fast insight into changes over time Every displayed reading is automatically and continuously recorded without having to set up threshold levels or interval times or having to manually start the process You can quickly view trends in voltage current frequency power harmonics or flicker on all three phases plus neutral And you can analyze the trends using the cursors and zoom function even while background recording continues SystemMonitor Check performance against EN50160 with ease With a single push of a button the unique system Monitor gives you an overview of power system performance and checks the compliance of incoming power to EN50160 limits or to your own custom specifications The overview is shown on a single screen with color coded
8. ollers C435 435 4 current clamps i400s CAT IV 600 V 4 current clamps 1430 Flex 4pk CAT IV 600 V 435 5 Test leads 4black 1 green Battery Charger Eliminator BC430 FlukeView Software SW43W Power Log Software 435 Optical Cable for USB OC4USB Color localization set WC 100 Getting Started printed User Manual CD ROM Ordering information POWER amp ENERGY FULL d LI kl 8 65 KVA 8 79 KVAR 160 PF 0 98 Cosi 0 99 kWh 0 285 kVAh 0 293 kVARh 0 053 START 08 19 04 15 44 24 PULSE CHT On OFF CLOSE EHERGY 0 08 15 Le L3 22 93 22 60 1 75 1 00 1 00 0 751 0 753 1 776 0 058 0 310 b 0 01 59 RESET EHERGY 1 749 Measure and record power W VA and VARs The 434 adds the ability to record energy HARMONIC DEEE 1 HS 23 2 r E Hz 5 105 0 02 19 Lis THODC 1 08 17 04 14 05 49 Li L L3 tl AL ma Il 1 fm il ma lli 1 fma jl T 3 11 13 15 i 2300 SOHZz38 WUYE EH5S0160 I HARH HOLD TABLE OH OFF RUH oe 3 5 Track harmonics up to the 50th and measure and record THD in accordance with IEC 61000 consumption 4 7 requirements Specifications Check the Fluke web for detailed specifications Inputs Number of inputs 4 voltage and current 3 phases neutral Maximum input voltage 1000 Vrms 6kV Peak Maximum sampling speed 200 kS s on each channel simultaneously Volt Amps Hertz Vrms AC DC 1 1000 V 0 1 of nomin
9. points for each reading Recording time Up to 450 days Zoom Up to 12x horizontal zoom Memory Screens amp data 50 shared memory divided between logging screens and data sets Standards Measurement methods used TEC61000 4 30 class A EN50160 IEC 61000 4 15 IEC 61000 4 7 Fluke 435 Power Quality Analyzer three phase with Logger Function Fluke 434 Power Quality Analyzer Fluke 434Kit three phase Logger Upgrade Kit Adds the Logger Function of the 435 to the 434 OC4USB Serial Interface Adapter Cable USB I5SPQ3 Set of 3 5A AC 1430 flex 4pk current clamp set of 4 3000 A flexclamps PM9080 Serial Interface Adapter Cable RS232 SW43W FlukeView Software GPS430 GPS sync module for 430 Series The advanced functions Interharmonics Energy Transients and Inrush are optional for the Fluke 433 and standard available on the Fluke 434 depending clamp scaling Value is measured over 1 cycle commencing at a fundamental zero crossing and refreshed each half cycle Battery life gt 7 hours with rechargeable NiMH installed Battery charging time 4 hours typical Safety EN61010 1 2nd edition pollution degree 2 1000 V CAT III 600 V CAT IV Case Rugged shock proof with integrated protective holster IP51 drip and dust proof Shock 30 g Vibration 3g according to MIL PRF 28800F Class 2 Operating temperature 0 C to 50 C Size HxWxD 256 mm x 169 mm x 64 mm Weight 1 1 kg Three Years Warranty