1. oe D f oI T Li LOS f 1 VL 37 5 UPS Working Principle 5 1 UPS System Block Diagram AC INPUT EMI FILTER DGAC CHARGER PUSH PULL BATTERY fig 5 1 Figure 5 1 above illustrates the True On Line Double Conversion architecture of the UPS system The major modules consist of 1 An AC to DC power converter Rectifier with PFC control circuit 2 A DC to AC power high frequency inverter 3 An Intelligent Battery Charger 4 A bank of stationary maintenance free batteries 5 A DC to DC push pull converter control circuit 6 A Static Bypass Loop 7 Input amp Output EMI Filter The table below provide a summery guide to the UPS operating modes against the Utility AC Power Source conditions 38 Utility LEDs Display Rectifier convert AC to DC battery charging Inverter convert to G4 892 LEDs and supply to loads with clean amp stable illuminated power Rectifier and charger stop operating Battery discharge via DC DC boost circuit and supply to Inverter Loads m LED off LED continue to receive supply from illuminated Inverter Alarm buzzer beeps UPS now on battery mode Rectifier and charger stop operating Battery discharge via DC DC boost circuit and supply to Inverter Alarm m LED off amp buzzer beeps with quick amp short LED i
2. 41 5 5 Jriverter Falur G Danie eats 42 5 6 Inverter Internal Over 43 Inverter VOL sso Ge ratte LE 5 43 es 44 ou asa ale oS 44 6 2 Error Codes and Their 46 0 3 IMaIDIe DalIC G 47 Bundle Software Installation Guide 48 x Hardware Installation iu etate iude tutu 48 kes SOWAS ALON 48 Optional Communication 49 Sa 49 49 9 9 DCE Diy Gontacl ca 50 8A NMP Gir RC X ee ee 51 na 821211 Lef 11 0 keen re emis Renn OS ni ee 52 1 1 1 10 11 12 13 Important Safety Instruction An Important Notice Do not open the case as there are no serviceable parts inside Your Warranty will be void Do not try to repair the unit yourself contact your local supplier or your warranty will be void If liquids are split onto the UPS or foreign objects dropped into the unit the warranty will be null and void Do not install the UPS in an environment with spa
3. 230V 10A IEC 320 14 10A IEC 320 C14 16A IEC 320 C20 54 55 56 97 58 192321142010000
4. 1Hz 6 Drawing T means the acceptable Inverter Output Voltage of which voltage is 200V 208V 220V 230V or 240V for 220Vac system or 100V 110V 115V 120V and 127V 7 Drawing U1 U2 and U3 mean the operation modes of the UPS of which alternative is Online fixed 50Hz Output or fixed 60Hz Output 8 Drawing V means the adjustments of the Inverter Output which may be calibrated as 096 1 1 2 2 3 Or 3 9 When all the setting changes are done you have to press enter pad to save all the changes when the LCD screen shows as drawing All those changes will be activated only when the UPS 15 re turned on The LCD screen will be back to the original screen before setting 31 10 Turn off the UPS and the input breaker of the Utility 11 Your Setting changes are complete 4 4 2 6 UPS Is Off Due to Unknown Reason and Its Trouble Shooting 1 If there is a serious abnormal condition occurred the UPS will lock itself in OFF position as shown in the drawing Y and a abnormal message will show in the LCD screen 2 For some special conditions the UPS will lock itself however it is still allowed to have bypass output in most of conditions and the LCD screens will show as drawing Z and error message will be shown on the screen 2 gt LINE UPS LOAD lt gt 3 release the UPS lock please proceed the followings a Check tho
5. 10 Cooling Fans 11 Output circuit breaker for two outlets 12 Output circuit breaker for two programmable outlets 10 3 3 Operating Modes amp Voltage System Configurations Download and open the UPS Setting Tool Software to see the screen as below 3 3 1 p UPS Setting Tool Yer X100725 cystem Voltage Selection 220v Voltage Configuration 220 LIPS Mode Normal mode Output Voltage Fine Tuning oz Bypass Voltage vvindow Sensitivity Low gt oyn Frequency window THe Serial port open Nannected oystem Configuration Settings System Voltage Selection Select Input Voltage 110V or 220V Voltage Configurations Select UPS Output Voltage 200V 208V 220V 230V 240V or 100V 110V 115V 120V 127V UPS Modes Select Normal CF50 CF60 Mode Output Voltage Fine Tuning Output Voltage Regulation from 0 3 11 5 Bypass Voltage Windows Sensitivity Select Sensitivity Low Sensitivity 3 3 2 Programmable outlet setting High Sensitivity Low Sensitivity High The UPS is equipped with 2 programmable outlets for use to supply to less 110V System 92V 130V 97V 130V critical loads These outlets can be disabled to shed the less critical loads during 220V System 184V 260V 194V 260V back up modes or overload conditions to maintain quality power supply to the more critical loads connected to the UPS 6 Syn Frequency Window Select 3Hz 1Hz Inverter Freq synchronizing range
6. 7 Com Port Select the Com Port of PC 8 Click on Write to confirm the configuration settings The UPS will beep twice to acknowledge setting is successful 9 Turn off the UPS after setting is complete to make sure that all the new Click on the Programmable outlet setting bar to enter to the setting screen as shown below Outlet Scheme setting values are written into EEPROM successfully then re start the Programmable Outlet Settings UPS to enable the new settings r Programmable Outlet 1 Outlet Turn On_Atter UPS On Q Second 0 2600 Outlet Turn Off After AC Failure Q Second 0 3600 Note 1 zi CF50 CF60 z Frequency Converter mode 50 to 60Hz or vice versa ele 2 Sensitivity Low 184 260V High 194 260V Outlet Turn DCf when Battery Low BH 22120 80 Outlet Turn Off When UPS Overload Setting Programmable Outlet 2 Outlet Turn On After UPS On Second 0 3600 Outlet Turn Of After AC Failure Second 10 26001 Outlet Turn On After AC Recovery Second 0 3600 Outlet Turn Off hen Battery Low 26120 80 Outlet Turn UPS Overload Manual Control Switch Programmable Outlet 1 Frogrammable Outlet 2 pep 471 Eo Bar 12 13 Outlet Turn On After Turn on UPS select the time to automatically enable this outlet within the specified time when the UPS is powered on If 0 se
7. Ablerex MP RT Intelligent True On Line UPS For Corporate amp IT User User manual 1K 2K 3KVA Table of Contents Important Safety Instruction a cessere 2 AI Impottarnt NOLO oca dic ovas iu Wr 2 2a 211216216124 INS UIC HO deseo oai ce e iae 3 e m 4 1 General CharacteriSlleS e eis 4 2 2 x9 peclal Peat les acid oan 5 UPS Functional aaia 6 UPS Front Panel Display 6 3 2 Heal Panel Descriptions OSEE ERE a Y ya RU Bu rade 10 3 3 Operating Modes amp Voltage System Configurations 11 3 4 Communication Port 15 Installation and Operati nnn 17 NO AG IMG DE 17 4 2 Selecting Installation 18 NEC NU en 19 AA OPEO iocos specu Eti S CRM TA 23 UPS Working e ada ves ee in 38 UPS System Block Diagt aiias ut 38 9 2 Wher Utility 1s Normal ot Econo cus 39 5 3 When Utility is 40 5 4
8. The USB communication protocol definition as below 1 Comply with USB version 1 0 1 5Mbps 2 Comply with USB HID Version 1 0 3 The Pin Assignments of the USB port 1 gt VCC 45V 2 gt D 32 D 4 gt Ground 3 4 3 EPO The Pin assignments of the EPO Input port are 112 1 5 EPO 2 Ground To enable the EPO function please short Pin 1 amp 2 16 4 Installation and Operation Read the Safety Instruction guide page 2 to 3 before installing the UPS 4 1 Unpacking Inspect the UPS upon receipt The manufacturer designed robust packaging for your product However accidents and damage may occur during shipment Notify the forwarder and dealer if there is damage The packaging is recyclable save it for reuse or dispose of it properly Hemove the UPS from the carton box Check the package contents Standard content shall includes 1 set of User s Manual 2 pcs of IEC output cables for UPS with IEC sockets only 1 pc of AC Input Power Cord 1 set of UPS communication software with RS232 cable 1 set of Tower Rack Accessories Kit as below Optional 17 4 3 Setup 4 2 Selecting Installation Position Tower Configuration Setup The UPS is heavy Select a location sturdy enough to handle the UPS weight To ensure proper operation and long operating life always position the UPS according to the following requirement Step 1 1 Keep minimum 20cm 8 inches distance clearance f
9. capacity is illustrated by the graph amp table below sec Load Delay Time Sec 5 5 Inverter Failure Output Load short circuit when supply via inverter If output load is short circuited while supply via Inverter the UPS will shutdown Inverter automatically and stop supply to the loads The Fault LED lights up and the buzzer will beep continuously The UPS will not switch on automatically after short circuit condition is eliminated The UPS has to be re start manually refer to 4 5 1 Start Up in Normal AC Mode 42 5 7 Inverter Internal Over temperature If the UPS experiences internal over temperature when Utility is normal it will switch to bypass loop The UPS will switch back to inverter mode when the over temperature situation is eliminated If over temperature occurs when Utility is abnormal the buzzer will beep continuously and the Fault LED A will light up The UPS will cut off supply to the loads Inverter Over current and Inverter Output Voltage Out of tolerance If the UPS inverter delivers over current and out of tolerance voltage to its outlets the UPS is out of order The UPS will switch to bypass loop when Utility is normal The Utility LED Bypass 7 LED and Fault A LED will light up If these two fault conditions occur when Utility is abnormal the UPS will cut off the supply to its outlets and the Fault A LED will light up 43 6 Maintenance Guide 6 1 Troubl
10. 14 3 4 Communication Port Explanation The UPS is equip with EPO dry contacts input true RS232 amp USB Communication port as standard to provide communication with bundled UPS monitoring software for remote monitoring of UPS status via PC There are 4 other optional interface cards available to meet various communication needs i e DCE dry contact relay card R2E USE and SNMP WEB card Please consult Ch8 The bundled software of the UPS is compatible with many operating systems such as Windows 98 amp 2000 ME NT and XP For other applications such as Novell NetWare Unix Linux please contact your local dealer for suitable software All the communication ports including optional cards can be active amp use simultaneously to monitor the UPS status However only 1 communication interface at any one time with the highest priority has the ability to command amp control the UPS The priority of these communication interfaces are as follow Highest Priority in descending order EPO input port 2 Optional Interface card 3 USB 4 RS232 3 4 1 True RS232 Port Descriptions The RS232 interface shall be set as follows Baud Rate 2400bps Bbits w Data Length Stop Bit Tbit Parity 15 Pin Assignments of the true RS232 port are illustrated as follows Pin 3 RS232 Rx Pin 2 RS232 Tx Pin 5 Ground ON a NUO AA 3 4 2 USB Port Descriptions
11. international standards for Electromagnetic Interference amp protection EMC 3 UPS Functional Descriptions 3 1 UPS Front Panel Display Descriptions 3 1 1 LED Panel Standard 13 12 1110 9 8 7 Battery Load Level 10 25 3 2 1 4 5 6 Control Keypads Symbols Functional Descriptions Ro 2 OFF Rom UPS Power Off Switch a Command the UPS to perform self testing 3 Self Test Alarm b Alarm Silence Silence To mute the alarm buzzer Do not press amp hold for gt 1 sec Press OFF key and Self Test key simultaneously for approx 3 seconds to transfer from Inverter to Bypass the bypass led continuously blink and the buzzer will beep intermediate or Bypass to Inverter when the UPS is on Line Mode and the Bypass Voltage Window is Normal O Manual Bypass LED Indicators Functional Descri Symb LED illuminated indicates utility voltage within sr NOI Mal MUSEI tolerance 120Vac 288 Vac 5 Battery Mode LED LED illuminated indicates utility outage or out of tolerance loads supply by battery power 6 Bypass Mode LED LED illuminated indicates bypass supply is normal 7 Overload LED Red LED illuminated indicates UPS is overloaded 8 Fault LED Red LED illuminated indicates fault or abnormal conditions 9 Site wiring fault Red LED illuminated indicates Live amp Neutral lines are LED connected wrongly or High Neutral Ground voltage 10 Battery Bad Weak Red LED illuminated indicates low bat
12. seconds till the LCD display illustrates from drawing G to drawing H then the UPS will be in self test Mode The UPS may offer energy to the output in a minute and the LCD display illustrates as drawing I In case of failure in pushing the UPS On Switch in 10 seconds the UPS will automatically turn off LINE UPS LOAD LOW LINE UPS LOAD A 26 4 4 2 3 Check Measured Values amp Figures detected by UPS 1 If you would like to check the measured values amp messages please use scroll up and scroll down Q key pads When you use scroll down key pad the LCD display will illustrate in sequence from Drawing E Input Voltage gt Drawing J Input Frequency Drawing K UPS Output Voltage gt Drawing L UPS Output Frequency Drawing M UPS Output Load percentage Drawing N UPS Battery Voltage Drawing O UPS inner temperature LINE UPS LOAD A LINE UPS LOAD LINE UPS LOAD A 2 LINE UPS LOAD LINE UPS LOAD 4 4 2 4 UPS Default Data and Special Function Execution 1 After UPS is turned on successfully use key pad to change the LCD Display screen to drawing P1 P1 2 2 Press key pad to scroll down the LCD screen then check the UPS settings The LCD display will show in sequence Drawing P1 buzzer gt Drawing Q1 self test Drawing R1 Bypass Voltage gt Drawing S Output Frequency Synchronized Window Drawing T
13. the UPS 0 To re confirm the change of UPS Setting Manual Bypass Press QON KEY and QD Up KEY key simultaneously for approx 3 seconds to transfer from Inverter to Bypass the bypass led continuously blink and the buzzer will beep intermediatel or Bypass to Inverter when the UPS is on Line Mode and the Bypass Voltage Window is Normal 3 1 2 1 Symbols on the LCD Display Panel Symbol LINE Utility or Bypass Source Battery Low 4 Digits Measurement Display Indicate the desired to be measured Battery Weak or Dead 2 Output Short Circuit 24 0 Inverter Over current UPS Overheat 9 En2 UPS Output Overloading Er Other Error Code 3 2 Real Panel Descriptions 891 KETON a LO 9 e 8 rex ea e G zJ TH A B 4 D 58 OUTI O CC CC T 2 A B INPUT HREAKER d OUTPUTBREAKER USB Port RS232 Port Emergency Power Off EPO Dry Contact Signal inputs Communication Card Options Slot External Battery Connector AC power connection socket AC Outlets Two programmable outlets Utility Input circuit breaker
14. 6 6 3 Maintenance uu 100 bar LEDs Each bar LED represents a number as shown Clean the dust from the ventilation openings and intakes on the rear panel 1 Turn off the UPS and wipe the casing with a damp cloth the figure below For example the fig below showed the 25 bar LED 75 bar LED amp 2 Periodically unplug the power cord of the UPS from the wall Receptacle to test the batteries condition 100 bar LED illuminated when the LD key is pressed The error code 3 RE shall be 8 2 1 11 or Er11 which indicate that the UPS is over go add sid y Saved your applicati you p battery discharging capability test temperature y ging cap y 168 4 2 1 j 1 f i Te mE c Ge bk GS 7 A 50 M Level 405 255 50 100 a 1 OO s VA __ i 6 2 Error Codes and Their Descriptions Er05 Battery weak or faulty E06 Output short circuited UPS over temperature En2 Inverter overload Fans out of order EEPROM s data error Er24 Utility Low 85 170V amp Battery Disconnect E28 Bypass overload Er31 EEPROM s data not conform to the Jumper Setting 46 47 T Bundle Software Installation Guide 7 1 Hardware Installation 1 Connect the male connector of RS232 USB cable to the UPS communication port 2 Connect the female connector of the RS232 USB cable to a dedicated RS232 port of the Computer 3 For optional interfa
15. Contact your local dealer for replacement Consult your local dealer for assistance UPS fails to provide battery backup or its back up time is shorter than its intended performance UPS is normal but no Check if all power Output to load codes are properly connected UPS switches to battery mode then back to Utility mode when connected device is turned on 1 if any power strip is connected to the UPS 2 Verify if there is any damage to the utility Or the UPS Wall Receptacle or if switches back and the cable cord plug is forth between battery faulty and Utility Strange noise and smell UPS is unable to provide backup power source 45 If the backup time remains non satisfactory after 8 hours of charging please contact your local dealer for battery replacement If problem persist consult your local dealer for technical assistance 1 Do not use power strip 2 Replace the wall receptacle cable cord plug Immediately shut down the whole System Disconnect the power from the UPS and call for service Check that the battery connectors are fully engaged Allow the battery to recharge if the batter is weak If problem persist after recharging replace the battery If problem persist consult your local dealer for technical assistance Note When the Fault LED is illuminated press and hold the D key to check the error code The error code is represented by the five 109
16. Inverter Output Voltage Drawing U1 UPS Operation Drawing V Output Voltage Fine Tuning 28 Q1 Q2 R1 R2 20 U1 U2 U3 30 3 Press scroll TO key pad you may execute special functions The functions include Buzzer ON as drawing Q1 or buzzer OFF as drawing Q2 Alarm silence for UPS warning and self test OFF as Drawing R2 UPS will execute battery test for 10 seconds if the self test is successful it show as Drawing W otherwise it will show as Drawing D amp error message at the same time W LINE UPS LOAD 4 4 2 5 UPS Default Settings and Their Alternatives 1 Make sure the UPS is not ON yet which means it is not in Line Mode or Backup Mode Press on ON Switch and scroll down key pads simultaneously for approx 3 seconds the buzzer will sound twice the LCD display screen shows as drawing P1 then the UPS is under setting mode now 2 To scroll down the LCD screen you may refer to Chapter 4 4 1 3 point 1 3 Except Buzzer as Drawing P1 amp P2 and self test Q1 amp Q2 all the rest default settings may be changed by pressing scroll up 4 key pad 4 Drawing S1 and S2 mean the bypass input acceptable window it can be 176Vac 264Vac for 220Vac system 88Vac 132Vac for 110Vac system or 187Vac 264Vac for 220Vac system 93 5Vac 132Vac for 110Vac system 5 Drawing S means the bypass frequency window of the inverter output the acceptable setting values are 3Hz and
17. c is selected the outlet will be enabled once the UPS is powered on Outlet Turn Off After AC Failure select this option to automatically disable the outlet within the specified time after utility outage to shed the less critical loads to provide longer battery back up time for the other more critical loads connected to the UPS Outlet Turn On After AC Recovered select this option to automatically enable the outlet within the specified time after the utility is restored Outlet Turn Off When Battery Lower than select this option to automatically disable the outlet at the specified remaining battery power capacity during battery mode to shed the less critical loads to prolong battery back up time for the other more critical loads connected to the UPS Outlet Turn Off When Overload select this option to automatically disable the outlet during overload condition bypass mode to possibly allow the more critical loads a be continually supplied via Bypass without shut down You have to select the Setting menu to configure new parameters The calibration is confirmed successfully after the UPS beeps twice Turn off the UPS and remove the input source to make sure that those new parameters are written into EEPROM successfully then re start the UPS to enable the new settings Manual Control Switch Click On or to manually enabled or disabled the programmable outlets overriding all previous settings
18. ce cards please refer to Chapter 8 for more details Note Only RS232 cable is provided with the UPS USB cable is optional 7 2 Software Installation Please refer to the user s manual of the bundled software CD ROM for installation guide 48 8 Optional Communication Cards 8 1 R2E 2nd RS 232 card 8 1 1 is for RS232 DB9 8 1 2 For communication protocol please refer to Chapter 3 4 1 8 1 3 Installation Position Optional Slot 8 2 USE USB card 8 2 1 CN1 is for USB 8 2 2 For communicaiton protocol please refer to Chapter 3 4 2 8 2 3 Installation Position Optional Slot 49 8 3 DCE Dry Contact card 8 3 1 The pin assignments of 10 Pin Terminal 1 gt UPS on Bypass mode Bypass 2 gt Utility Normal Normal close contact 3 Utility Normal Normal open contact 4 Inverter On 5 gt Battery Low 6 Battery Bad or abnormal 7 gt UPS Alarm 8 gt Common 9 gt Shutdown UPS positive signal 10 Shutdown UPS negative signal 8 3 2 shutdown function will be activeated after a 6 25Vdc is put between pin 9 and pin 10 for 5 seconds 8 3 3 The capacity of each relay contact is 40Vdc 25mA 8 3 4 Installation Position Optional Slot 8 3 5 Flexible signal output for N C Normal Close or N O Normal Open contact by shorting pin1 2 or pin2 3 form JP1 5 8 3 6 shutdown function will be enabled in 1 minute after blackout occurs
19. ds except 891 72 which will remain illuminated Green At the same time the fan at the rear of the UPS will start operating Press the LO Switch for approximately 3 seconds to start the UPS the buzzer will beep and the LED display of 594 We will light up after 30 seconds The start up procedure is completed and the UPS outlets are ready to supply to load It is advisable to perform a battery mode test before connecting the loads to the UPS to ensure the batteries are working properly Switch Off the AC power source when the UPS had been switched on The LED on the front panel display will light off while the LED will be illuminated and the buzzer alarm will beep intermediately indicating the UPS is in Battery Mode Connect a non critical load to the UPS outlets to confirm if the Battery is supplying power Repeat the test by switching on amp off the AC power source to ensure the UPS is functioning properly 4 4 1 2 Start up in Battery Mode Cold Start This UPS is able to be Switch On for operation without the presence of an AC power source Press and hold the LO owitch until the buzzer beep within the next 10 sec press and hold the LO Switch for 2 time The UPS shall perform its start up procedure The LED display and 894 892 will light up after 30 seconds the buzzer will beep intermediately to indicate successful power on Note Ensure the UPS Battery is pre charge for minimum 4 hours by si
20. e Shooting When the UPS becomes faulty or malfunctions during operation you may check the fault lists below for respective solutions Should the problem persists please contact your local dealer for assistance Check Items Situation UPS Fault N LED Read the error code see 1 Er05 Er25 next page for readings displayed by the combinations of the LEDs and verify the fault as follow 3 Er11 UPS Over Temperature 4 Site wiring Ground fault Tt 5 Er14 Fans out of order 6 Other error codes 44 Solution Check battery connection if is properly done Measure Battery voltage to ensure batteries are charged or healthy Recharge batteries for 8 hours if necessary Simulate Utility outage to verify if UPS is able to provide DC back up Otherwise consult your local dealer right away Disconnect some non critical loads form the UPS output until overload ceases Check if there is any short circuit between cables due to broken cable insulator Replace the cables in necessary Remove any objects obstructing the ventilation louvers Verify if the cooling fans are working properly Contacts your local dealer to replace the fans if necessary Verify if the L amp N phase of the Utility AC source has been wrongly wired or if the Ground Neutral Voltage exceeded the limits Verify if the ventilating fans are functioning properly Do not attempt to replace the fans by yourself
21. ect plugs and sockets for the appropriate voltage system 1 2 Storage Instruction For extended storage in moderate climate the batteries should be charged for 12 hours every 3 months interval by connecting the UPS to the utility supply and switch on input breaker located at UPS rear panel Repeat this procedure every 2 months if the storage ambient temperature is above 30 C 2 Product Introduction 2 1 General Characteristics True online technology continuously supplies your critical device with a stable regulated transient free pure sine wave AC Power 1 High efficiency PWM sine wave topology yields an excellent overall performance The high crest factor of the inverter handles all high in rush current loads without the need to upgrade the power rating User friendly Plug and Play design allows hassle free installation All units up to 3Kva are supplied with input cables and output sockets as standard Built in Maintenance free sealed type battery minimises the need for frequent after sales service To protect the unit from overloading the UPS will automatically switch to bypass mode in 30 seconds if loading is at 105 120 of rated capacity It will automatically switch back to inverter mode once overload condition ceases Should the output becomes short circuited the UPS puts the system on stand by mode provide visual amp audible alarm and cuts the output supply automatically till the short circuit situation
22. equency Synchronized Range 3Hz or 1Hz setting by software Frequency Battery Mode 0 1 0 05 0 06Hz unless synchronized to line 52 Without 3 1 Current transformer Crest Factor With 25 transformer Harmonic Distortion lt 3 THD Linear Load x 7 THD Non Linear Load Transient Response ms lt 60ms 596 AC Mode transformer Battery Mode o o AC Mode transformer Battery Mode B o o Battery System Type 12V 7 2Ah 12V 9Ah Numbers of Batteries 3 Charging Voltage 41 0Vdc 0 5V 82 0Vdc 0 5V 82 0Vdc 0 5V Yes Hot Swappable Battery Internal battery lt 30uA 10UA with no AC applied and the unit in the off position Battery type Sealed non spillage maintenance free lead acid Transfer Time AC to DC Zero Inverter to Bypass 2 5ms Typical DC leakage current Self Diagnostics ront Panel By button of the panel or Software Control Load Level Battery Level Battery Mode Normal Mode Bypass Mode Self Test Weak Bad Battery Site Wiring Fault Fault Overload Programmable Outlet1 Programmable Outlet2 LED ON Button OFF Button Test Alarm Reset Button Protection 53 Mode ee lt 105 continuous Output Connection 4 10A IEC 320 C13 gt 106 120 for 30 seconds transfer to bypass 1 16A IEC 320 19 gt 12196 15096 for 10 seconds transfer to bypass Environmental gt 1509 for immediately transfer to bypass Buzzer nia Operatio
23. high as 6 times its rated capacity while others the Inverter without delay and turn off the charger and AC DC converter The produce negligible inrush To prevent severe damage to its Inverter cause by inverter revert DC to AC to supply energy to the output load connected without the inrush produce by the loads the UPS is equipped with electronics overload interruption The amp LED will be illuminated protection feature as standard If the UPS loading is 105 12096 of its capacity it will switch to bypass mode in 30 seconds to protect the Inverter If overload 2 When Utility is back to Normal the UPS will turn on the AC DC converter turn condition is eliminated by reducing the load to 10576 the UPS will switch back off DC DC converter and switch the charger to charging mode It has the same to Inverter mode automatically If the UPS is over 150 loading it inverter will working principle as figure 5 2 shutdown immediately 3 During a utility outage the UPS will work as illustrated in figure 5 2 When Battery is low buzzer will beep continuously till battery is completely cut off The battery low protection of the UPS will cut off battery supply after a preset threshold to avoid the battery from over drain The lt 8 Battery Low LEDs will light up till the UPS is completely cut off The UPS will re start automatically when Utility is available 40 41 2 The UPS Bypass loop is also equipped with overload protection Its overload 5 6
24. if the pin1 2 of both CN1 and CN6 are shorted by cap Or the shutdown function can only be enabled by pin9 10 of CN3 if the pin2 3 of both CN1 and CN6 are shorted by cap 50 8 4 SNMP Cards 8 4 1 SNMP WEB card 8 4 1 1 For installation please refer to the user s manual attached with the card 8 4 1 2 Installation Position Optional Slot 8 4 2 SNMP card of Megatec 8 4 2 1 For installation please refer to the user s manual attached with the card 8 4 2 2 Installation Position Optional Slot 51 9 Specifications 1KVA 2KVA 3KVA 1000VA 2000VA 3000VA 700Watts 1400Watts 2100Watts lt JJ Power Factor Topology Type Double conversion On Line Rack Tower 230V Models CE lt gt gt gt 10 5 lt D Q O qim lt gt 9a 5 5 5 cys m Q 9 a o oO o gt lt 120 140 160 288 Base load percentage 0 33 33 66 66 100 Low Line Transfer Low Line Comeback 170Vac High Line Transfer 230V 288Vac High Line Comeback 278Vac Frequency 50 60 Hz auto select 5Hz AC Leakage current TATE 115V 230V 300 joules Voltage 230V 230V adjustable to 200 208 220 230 240 Without Transformer lt 1 until low battery warning 120 140 160Vac M d 2280 00 Voltage Regulation With Transformer lt 2 5 until low battery warning Fr
25. is resolved manually 2 2 Special Features 1 High Frequency Transformer less technology with rack tower convertible enclosure enables the UPS for integration even in the most difficult of environment with space constraints This UPS is equipped with fully digitalized control logic for greater functionality and enhanced high level of power protection Digital signal processing DSP also provides the UPS with powerful communication capability which enhances the flexibility for easy remote control and monitoring Wide input voltage tolerance from 120V 288V 220V version allows under voltage or over voltage correction without unnecessary battery drain and helps extend the battery life span DC start function ensures the start up of UPS even during power outages Revolutionary battery management circuit analyzes battery discharging status to adjust battery cut off point and extend the batteries life span Active Power Factor Correction PFC control function constantly maintains the UPS Input Power Factor PF at 0 99 for superb energy efficiency Selectable Bypass input voltage tolerance Sensitivity low high to prevent under or over voltage being supply to the loads at Bypass mode The selectable Voltage ranges are i Sensitivity Low 184 260V amp ii Sensitivity High 194 260V Vast Selectable Output Voltages 200 208 220 230 240 to meet various voltage systems The UPS is designed to comply with various stringent
26. lluminated succession indicating battery power low and Inverter may stop supply soon Utility Normal Utility Abnormal under or over voltage Absent Utility Abnormal Absent Battery low voltage Paragraph 5 2 5 7 below provide detailed descriptions of the UPS operating principle 5 2 When Utility is Normal The working principle of the UPS under Utility normal condition is illustrated as follows RECTIFIER N STATI ACIDC CONVERTER INVERTER EBU CIE CONVERTER When Utility is normal the AC source is rectified to DC partially fed into the charger to charge battery and partially fed into irter The inverter revert the DC to a cleaned and pure AC to supply energy to the load connected The rv G4 72 LEDs illuminated 39 5 3 When Utility is Abnormal Absent 5 4 Overload Condition The working principle of the UPS under Utility abnormal condition is illustrated The working principle of the UPS when overloading is illustrated as follows as follows ACIDC CONVERTER STATIC bobs CONVERTER CONVERTER STATE SWITCH CONVERTER ETER 80 CHARGER CHARGER BATTERY 1 Generally modern day electronics amp IT equipment generate an inrush current when switching on The amount of inrush current varies from equipment to 1 When Utility is abnormal the UPS will direct the battery energy automatically to equipment some can be as
27. mply 22 connecting the AC power cord to the Utility receptacle 23 4 4 1 3 Shutdown 1 Shutdown in AC Mode Press the Switch for approximate 5 seconds until the buzzer beeps the UPS will stop power supply to the outlets UIt G2 LEDs shall remains illuminated and the ventilating fans shall continue to operate Switch Off the power source after 10 sec the Wr UIZ LEDs will light off and the ventilating fans stop operating The UPS is now completely shutdown 2 Shutdown in DC Mode Press the Switch for approximate 5 seconds until the buzzer beeps UPS will stop power supply to the outlets Ir 4 72 LEDs light off and the ventilating fans shall stop to operate after 10 sec The UPS is now completely shutdown 4 4 1 4 Self Testing during AC mode After the UPS has been successfully start up in AC mode press the Switch for approximately 5 seconds until the buzzer beeps The v LED will blink to indicate self test in progress The LED will stop blinking and remains illuminated when the self test is completed without finding any faults or abnormal conditions The k1 LED will automatically lights off 30 sec after the successful self test 4 4 2 LCD panel Optional 4 4 2 1 Start Up In Normal Mode 1 Make sure the voltage of Utility matches with the input voltage window of the UPS 2 Connect the UPS to the wall Receptacle of the Utility Turn on the ON switch to start
28. n Temperature continuously alarms Battery Mode lt 50dBA lt 105 continuous Relative Humidity 0 to 90 Without condensation Interface 00 gt 121 150 for 10 seconds shuts down gt 150 forimmediately shuts down Interface Type Overload Buzzer continuously alarms SNMP option Power management from SNMP manager and Web Bypass Mode browser lt 105 continuous Compatible platforms Windows 95 98 NT 2000 XP Novell NetWare Linux etc gt 106 120 for 250 seconds shuts down Standards and Certification gt 121 130 for 125 seconds shuts down gt 131 135 for 50 seconds shuts down IEC EN 62040 1 1 gt 136 145 for 20 seconds shuts down Performance IEC EN 62040 3 14696 14896 for 5 seconds shuts down IEC EN62040 2 Class A FCC Part 15 Subpart B Class A gt 149 15796 for 2 seconds shuts down IEC EN5501 1 CISPR11 IEC61000 4 2 3 4 5 61000 715896 17696 for 1 seconds shuts down 2 2 IEC61000 3 2 3 gt 1779 187 for 0 32 seconds shuts down gt 18896 for 0 16 seconds shuts down Buzzer continuously alarms Bypass mode Input Fuse Input Breaker Short Circuit Normal Mode Output Breaker Electronic Circuit Battery Mode Output Breaker Electronic Circuit Over Normal Mode Transfer to Bypass Mode Continuously Sounding or Sounding once every 3 second Fault Physical Dimensions HxWxD in mm 132x440x405 176x440x520 176x440x520 Without transformer 15 5kg 32kg 33kg Weights 115V
29. rks smoke or gas This UPS is equipped with an EMI filter To prevent potential leakage current hazard ensure that the AC main supply is securely grounded This UPS is designed to be installed and commissioned in a sheltered controlled environment as follows Operating temperature 0 40 C and 30 90 non condensing humidity Always avoid contact with direct sunlight Installing the UPS in inflammable or hazardous environment Dusty corrosive and salty environments can do damage to any UPS Install the UPS indoors as it is not designed for installation outdoors To prevent any overheating of the UPS keep all ventilation openings free from obstruction and do not place anything on top of the UPS Keep the UPS rear panel 20 cm away from the wall or other obstructions The battery will discharge naturally if the system is unused for any length of time Install the UPS away from objects that give off excessive heat and areas that are excessively wet Always switch off the UPS and disconnect the batteries when relocating the UPS It should be recharged every 2 3 months if unused If this is not done then the warranty will be null and void When installed and being used the batteries will be automatically recharged and kept in top condition Make sure that the AC Utility outlet is correctly grounded Please ensure that the input voltage of the UPS matches the utility supply voltage Use a certified input power cable with the corr
30. rom the rear panel of the UPS to avoid any obstructions 2 Do not block the air flow to the ventilation louvers of the unit 3 Please ensure the installation site is free from excessive dust and the ambient temperature and humidity should be within the specified limits 4 Do not place the UPS in a dusty or corrosive environment or near any flammable objects 5 This UPS is not designed for outdoor use Relative humidity non condensation 0 90 18 Rack Mount Configuration Setup Power Module Battery Module Step 1 Step 1 Step 2 N zr CD Step 3 21 Step 4 Step 5 E ME tdt Bae Be Boe Be Qu Be Be ww Be Be BoB BR Be BH 566 Eo 66 1 6 4 4 Operation 4 4 1 LED panel Standard 4 4 1 1 Start Up in Normal AC Mode Before commencing the installation please ensure the grounding is connected properly Ensure the voltage of Utility matches with the input voltage window of the UPS Connect UPS main power cord into Utility AC power source receptacle Switch on the AC power source all the LEDs on the front panel display will flash once after 3 secon
31. se error messages recorded b Check to see Chapter 6 2 to trouble shoot the problem of the UPS otherwise consult your local distributor for service c Press key pad for 5 seconds and buzzer will sound twice d Turn off the Breaker of the Utility Input e The UPS lock problem is solved now 22 4 4 2 7 Shut Off 1 Press w key pad for about 5 seconds the Inverter output will be turned off then the output load is supplied by Bypass loop and the LCD screen shows as drawing B 2 Turn off the input of the UPS 3 The UPS is turned off completely 4 4 3 Status amp Alarm Buzzer The following table helps to define some of the common UPS statuses with respect to their buzzer beep descriptions Status Definitions Buzzer Beep Descriptions UPS faulty Inverter shutdown Lona Continuous Ree All functions inhabited g UPS faulty loads continue to l l i Single successive beep with 2 sec be supplied via Inverter or interval Bypass battery mode Single short successive beep with 1 sec interval battery low Very quick and short successive beep confirm RS232 port receiving 2 quick amp short beeps 1 quick amp short beep UPS initial starts up with self 2 successive quick amp short beeps test repeating per 2 sec interval 33 4 4 4 Battery Replacement Step 2 otep 1 1Kva Ta 2K 3Kva 34 35 Step 3 2K 3Kva 36 Step 4
32. tery power or LED faulty battery bank Green LED illuminated indicates successful self test 11 Self Test LED and no abnormal conditions or faults were found Green LED illuminated indicates UPS Outlets 2 are enabled and ready to supply loads Green LED illuminated indicates UPS Outlets 1 are enabled and ready supply loads a During Normal Mode Press and hold for 1 sec the 7 11 LEDs will function as Load Rate indicators showing 100 75 50 25 or 10 of UPS capacity used These LEDs will stop 7 11 LEDs illuminating after 10 sec During Battery Mode Press and hold for 1 sec the 7 11 LEDs will function as Battery Power indicators showing 100 75 50 25 or 10 Battery Power remaining These LEDs will stop illuminating after 10 sec 3 1 2 LCD panel Optional OQ OQ oO amp 0 d 0 LCD Display Green LED steadily lights up to indicate that the Utility input voltage is within the window 160Vac 288Vac the LED flashes flickeringly to indicate that the Utility input voltage is within the acceptable window 120Vac 159Vac 4 Green LED lights up to indicate there is an output available at the Programmable Outlet 1 amp Programmable Outlet 2 Amber LED lights up to indicate the Bypass Input is normal UPs Fault LED 2 UPS On Alarm Silence UPS OFF Switch 9 Special functions log in out Go to next page Go to previous page or change the setting of
33. the UPS LED and light up to indicate the Utility and the Bypass are normal The LCD will illustrate from drawing A to drawing B LINE UPS LOAD LINE En LOAD L 3 Then the UPS is on Bypass Mode now and it will proceed self test automatically If there is no abnormal message occurred it means the pre startup of the UPS is successful and the charger starts to charge the batteries 4 Press the UPS Switch for approx 3 seconds then the Buzzer sounds twice If the UPS start up is successful the LCD display changes from drawing B to drawing C LINE UPS LOAD l D Inr E LOW im 5 In case of failure in self test the LCD display will illustrate as drawing D then an error code or error status will be shown on the screen D LINE UPS LOAD LINE UPS LOAD A 25 6 Your start up operation of the UPS is completely now as illustrated as drawing E Make sure the UPS is plugged onto the wall receptacle for charging at least 8 hours and the batteries of the UPS are fully charged 4 4 2 2 Start up in Battery Mode Cold Start 1 Make sure the UPS has already been installed with batteries 2 Press the UPS On switch to awake the UPS for approx 3 seconds and then the buzzer sounds twice The LCD display will illustrate from Drawing A to drawing G LINE UPS LOAD 3 Press the UPS On switch of the UPS again for approx 3

Download Pdf Manuals

image

Related Search

Related Contents

  Quadro Elettrico Tipo ABS CP 112/212 IT Manuale dell`utente  LC87F7932B - ON Semiconductor  Bedienungsanleitung testo 905-T1 22.1°C On On On On On On  User Manual - Projector Central  User Manual  Kramer Control Software  Geotech Sipper Pump & Skimmer Assembly Installation and  Sony RDH-SK8iP User's Manual    