1. export kimo fr EXPORT DEPARTMENT Tel 33 1 60 06 69 25 Fax 33 1 60 06 69 29 e Connection tube e Connection fittings e Through connections Distributed by e Straight connections e Spherical coupling nut FTang transmitter_CP114 115 08 03 13 RCS 24 P rigueux 349 282 095 Non contractual document We reserve the right to modify the characteristics of our products without prior notice
2. 0 i 0 100 mbar Combinations __ Central zero x 50 mbar 0 50 mbar A gt Output setting right DIP switch CP114 115 AO and CP114 115 AN models Please follow carefully the combinations beside with the DIP switch If the combination is wrongly done the following message will appear on the display of the transmitter CONF ERROR In that case you will have to unplug the transmitter place the DIP switches correctly and then power the transmitter up To set the type of analogue output please put the on off switch of the output as shown Configurations 4 20 mA 0 10 V beside 1 E 1 i Zi 2m Combinations o Units setting right DIP switch E 4 E To set a measurement unit put the on off switches 2 3 and 4 of the units as shown in the table below Configurations mbar inWG kPa PSI mmHG mmH O daPa hPa 1 ee e Die Tee iS 1 3 Omg SHE GOE eee E ee E _ E 4 E E OHE E sE M 4 E CONFIGURATION VIA LCC S SOFTWARE option An easy and friendly configuration with the software You can configure your own intermediary ranges r r Caution the minimum difference between the high range and the low range is 20 2 m gt For example it is possible to set the instrument from 20 to 0 mbar from 0 to 20 mbar or from 10 to 10 mbar 3 m 3 e To access the configura
3. KIMO Technical Data Sheet INSTRUMENTS Pressure Temperature Humidity Air Velocity Airflow Sound level C Differential pressure transmitter my CP 14 CP 115 iti Le cr a KEY POINTS Py Ranges from 500 500 mbar to 2000 2000 mbar according to models Configurable intermediary ranges A m n 0 10 V or 4 20 mA output active power supply 24 Vac Vdc 3 4 wires or 4 20 mA output passive loop power supply from 16 to 30 Vdc 2 wires W ABS VO housing IP65 with or without display u is pua 4 turn system mounting with wall mount plate Housing with simplified mounting system FEATURES OF THE HOUSING 90 mm 46 mm Material ABS V0 as per UL94 Protection IP65 Display LCD 10 digits Size 50 x 17 mm Height of digits Value 10 mm Unit 5 mm Connections safety 6 2 mm Cable gland for cables 8 mm maximum Weight 143 g TECHNICAL FEATURES Measurement units mbar inWG mmHG PSI mmH 0 daPa hPa kPa Accuracy 1 5 of reading 3 mbar Response time 1 e 63 0 3 s Resolution 1 mbar 0 1 inWG 1 mmHG 1 mmH O 1 hPa 10 daPa 0 1 kPa 0 1 PSI Autozero Manual with push button Type of fluid Air and neutral gases Overpressure tolerated CP114 1400 mbar CP115 4100 mbar Operating temperature From 0 to 50 C Storage temperature From 10 to 70 C All the accuracies indicated in this technical datasheet were stated in laboratory conditions and can be gu
4. aranteed for measurements carried out in the same conditions or carried out with calibration compensation PART NUMBER To order just add the codes to complete the part number Example CP 114 AO Pressure transmitter measuring range 500 500 mbar 0 10 V CP1i Oo or 4 20 mA active with display Display Measuring range O with display 4 500 500 mabr N without display 5 2000 2000 mbar Power supply Output A Active 24 Vac Vde 0 10 V or 4 20 mA P Passive 16 30 Vdc 4 20 mA TECHNICAL SPECIFICATIONS Output Supply active sensor 0 10 V or 4 20 mA alim 24 Vac Vdc 10 3 4 wires passive loop 4 20 mA power supply 16 30 Vdc 2 wires maximum load 500 Ohms 4 20 mA minimum load 1 K Ohms 0 10 V Consumption 2 VA 0 10 V or max 22 mA 4 20 mA Electromagnetical compatibility EN61326 Electrical connection Screw terminal block for cables 0 05 to 2 5 mm Communication to PC Kimo USB mini Din cable Environment Air and neutral gases CONNECTIQUES Inside the front housing oo Fixed back housing Removable front face 60000 6bZ aoe wee uae oa ss ast s wae Power supply terminal block Output terminal block a a M M o d gt gt DIP Switchs Cable gland TU ces connection Pressure connections ELECTRICAL CONNECTIONS as per NFC15 100 standard A This connection must be made by a qualified technician To
5. make the connection the transmitter must not be energized To make a 3 wire connection before powering up the transmitter please connect the output ground to the input ground See drawing below For CP114 115 AO models and CP114 115 AN models with 0 10 V or 4 20 mA output active 4 wires VP GND IP g IP 123 4 5 67 3 yo 7 7 7 7rp 727 7 7 m 7 77 r 7 7 37 Regulator display or PLC BMS Power supply 24 Vdc Power supply 24 Vac class Il Power supply 24 Vdc PLC BMS active type _ 0 10 V output Regulator display or PLC BMS active type 0 10 V output Power supply 24 Vac class Il 4 wires 3 wires For CP114 115 PO models and CP114 115 PN models with 4 20 mA output passive Display regulator PLC active type Display regulator PLC passive type SETTINGS AND USE OF THE TRANSMITTER gt Autozero To perform an autozero unplug the 2 pressure connections tubes and press the Autozero key When an autozero has been performed On green light turns off then turns on and on transmitters equipped with a display autoZ is displayed gt Configuration A To configure the transmitter unscrew the 4 To configure the transmitter it must not be energized Then you can make the settings required with the DIP switches as shown on the drawing below When the transmitter is configu
6. red you can power it up On off switch 4 screws from the housing then open it DIP switches allowing the different settings are then accessible i x a Left DIP switch gt Measuring range settings left DIP switch Measuring ranges setting Standard range or central 0 setting To set a measuring range put the 1 2 and 3 on off switches as indicated in the table below Combination 1 ombination 2 ombination 3 KR WORD Output setting Units setting Right DIP switch ombination 4 1 2 c 4 Combination 5 300 400 1500 500 2000 120 0 160 0 600 0 800 0 30 0 40 0 150 0 200 0 6 0 8 0 30 0 40 0 240 800 1600 3000 10 000 20000 daPa 1 0 5 0 2 0 75 3 0 10 0 4 0 15 0 9 0 20 0 hPa 100 500 200 750 300 1000 400 1500 500 2000 e Measuring ranges of the CP114 transmitter on the 500 mbar range according to the measurement unit e Measuring ranges of the CP115 transmitter on the 2000 mbar range according to the measurement unit Example e From 0 to 750 mmH 0 measuring range is 750 mmH 0 e From 500 mbar to 500 mbar measuring range is 1000 mbar gt Standard range central zero setting left DIP switch Configurations Full scale Central zero To set the type of measuring range put the on off switch 4 as indicated beside E E Example 0 100 mbar Full scale
7. tion via software Set the DIP switches as shown beside Nota the on off switch 1 of the right DIP switch can be in 4 4 E any position selection of the analogue output 0 10 V or 4 20 mA Left DIP switch Right DIP switch Connect the cable of the LCC S to the connection of the transmitter e Please refer to the user manual of the LCC 100 to make the configuration The configuration of the parameters can be done either with the DIP switch or via software you can not combine both solutions MOUNTING To mount the transmitter mount the ABS plate on the wall drilling 6 mm screws and pins are supplied Insert the transmitter on the fixing plate see A on the drawing beside Rotate the housing in clockwise direction until you hear a click which confirms that the transmitter is correctly installed A Once the transmitter is installed and powered up please make an autozero to guarantee the correct working of the transmitter in any position MAINTENANCE 23 75 mm 75 mm Please avoid any aggressive solvent Please protect the transmitter and its probes from any cleaning product containing formalin that may be used for cleaning rooms or ducts OPTIONS AND ACCESSORIES e KIAL 100A Power supply class 2 230 Vac input 24 Vac output e LCC S configuration software with USB cable afaQ ISO 9001 Qualit AFNOR CERTIFICATION e mail