1. 12 2 Wearing parts list The following list of components are related to regular wear and are therefore not subject to the warranty of the UPS Wearing part Function Article number XXXX XX XX Energy storage Depending on the Accumulator Battery assembly see acces 12 V xx Ah sories or on request For the wear part description of the accumulators please see the assembled accumulators or on contact us Adira series 77 13 Conformity Declarations 13 1 Adira 3 1 10kVA EFFEKTA EC Declaration of Conformity Address EFFEKTA Regeltechnik GmbH Rheinwaldstr 34 D 78628 Rottweil Germany Product description UNINTERRUPTIBLE POWER SYSTEMS Model ADIRA 3 1 10 kVA The above mentioned product is in delivered condition compliant with the following guidelines 2004 108 EC Council directive on the approximation of the laws of the member states relating to electromagnetic compatibility 2006 95 EC Council directive on the approximation of the laws of the member stales concerning electrical equipment for use within certain voltage limits The conformity with the guidelines is guaranteed under application of following standards Safety Electromagnetic compatibility EMC Class C3 Number Issue Number Issue EN62040 1 2008 EN62040 2 2006 Rottweil 2014 03 07 2B Mek Peter Androt Managing Director UPS Adira 10kVA 20kVA 3 1 phase Notes 13 2 Adira 3 1 20kVA EFFEKTA EC
2. EFFEKTA Regeltechnik GmbH is not liable for damage incurred or caused by staff who have not been trained or who have been insufficiently trained 1 6 Warranty Conditions The receipt of delivery is considered as the record for the initial purchase and should be kept in a safe place It will be necessary for making use of the war ranty If the product is passed on to another user he has the right to the war ranty for the remainder of the warranty period The purchase receipt as well as this declaration should also be given to the new owner if the device is passed on We guarantee that this device upon delivery is in a functional state and techni cally conforms to the descriptions in the appended documentation The warranty period for special devices corresponds to the minimum periods stipulated by law The warranty ceases to apply in the following cases In the event of defects caused by freight damage accident natural catastro phes misuse vandalism improper use defective maintenance or incorrect re pair by third parties Inthe event of changes unauthorised intervention incorrect operation an other device or accessories false installation or other modifications not ap proved by us Improper use such as plugging the device into unsuitable energy sources attempts to overload the UPS use in an unsuitable environment etc In the event of failure to follow instructions in the provided documentation
3. UPS Adira 10kVA 20kVA 3 1 phase Storage and Unpacking Fig 4 2 Unpacking step 2 sy Fig 43 Unpacking step 3 as UPS Adira 10kVA 20kVA 3 1 phase Storage and Unpacking Fig 4 4 Unpacking step 4 or dispose of them appropriately ES The shipping materials are recyclable After unpacking save them for later use Inspect the appearance of the UPS to see if there was any damage in curred during transportation Do not turn on the unit and notify the carrier and dealer immediately if there is any damage or if any parts are missing Adira series 35 UPS Adira 10kVA 20kVA 3 1 phase System Description 5 Adira series System Description The UPS runs in continuous operation according to the double converter princi ple It serves for the processing of the mains current and provides an uninterrup tible and interference free one phase voltage for operations critical appliances In addition to providing power to the appliance it also maintains the internal ac cumulators in charged condition In the case of a mains failure or interference the UPS continues to provide a clean supply voltage from the UPS output with out interruption During the backup mode power is provided from the accumula tors On line UPS 1 mains input 8 voltage inverter 2 filter 9 control and monitoring 3 rectifier 10 control panel and display 4 inverter 11 Ext battery bank optional 5 bypass switch 1
4. Use only the items listed under accessories This includes the compatible bat tery bank and the corresponding connecting cable Ensure that the output voltage of the battery bank is identical with the DC input voltage of the UPS Should this not be the case the units may not be connected with each other under any circumstances You must make sure that the UPS is switched off and that the circuit breaker of the battery bank is removed before connecting the UPS with the battery bank If the UPS is equipped with an internal battery pack this pack has to be disconnected from the DC connectors first Fig 6 2 Disconnecting battery pack and UPS e Connect the external battery pack with the UPS Re comnect the internal battery pack again e Install the circuit breakers of the battery bank e _ Switch the input breaker of the UPS to ON Now the UPS begins to charge the battery bank 42 UPS Adira 10kVA 20kVA 3 1 phase UPS Installation and Connection 6 7 Feedback protection On the customer side an additional external insulation device magnetic con tactor minimum shunt release must be provided see Fig 6 3 This insulation device must be designed to conduct the input voltage of the UPS see the corresponding table in the general UPS operating manuals The insulation device must be installed in the Bypass input line i Optionaler Magnetsch tz Main 2 Optional magnetic contactor Bypass PSDR F 2A Pl
5. Phase 3 to 1 Voltage 176 276VAC Frequency 50 60 Hz 10 Current L1 L2 L3 18 1A Max mans 36 3A Max THDI lt 5 at full load Performance factor gt 0 99 at full load Output Model 10kVA 20kVA Connected load 10kVA 9kW 20kVA 18kW Voltage 200 208 220 230 240VAC Current 45A 48 1A 45 5A 43 5A 4 90A 96 2A 90 9A 87A 83 1 7A 3A Frequency 50 60Hz 10 in line mode 50 60Hz 0 1 of the normal frequency in battery mode Wave form sine wave THDV lt 2 full linear load lt 5 full non linear load Overload In Line mode 10 min 105 125 1 min 125 150 10s gt 150 100 ms gt 170 In Battery mode 2 min 105 125 30 s 125 150 100 ms gt 150 The load capacity is limited to 90 automatically if the output voltage is set at 200 VAC 74 UPS Adira 10kVA 20kVA 3 1 phase Technical Data Battery banks Model 10kVA 20kVA Voltage 288VDC Type and number of 24x 12V 9Ah 2x24x 12V 9Ah batteries Charging rate of a 33 6A 67 2A battery pack Environment Storage temperature 15 C 50 C Operating temperature 0 40 C Operating environment ee 95 without condensation Altitude m 1000 1500 2000 2500 3000 3500 4000 4500 5000 Maximum performance 100 95 91 86 82 78 74 70 67 Standards Safety EN 62040 1 2008 EMV EN 62040 2 20
6. UPS Adira 10kVA 20kVA 3 1 phase Maintenance and Service 10 4 Service Hotline If unexpected problems occur with the photovoltaic solar inverter or you need safety information please contact our service hotline by phone or fax Phone 0049 0 741 17451 52 Fax 0049 0 741 17451 29 If you cannot reach us by phone or fax we have set up an e mail contact for you ups effekta com In addition you can contact the central area or branch office directly as listed on our website http www effekta com html kontakt html 10 5 Maintenance and service contracts EFFEKTA Regeltechnik GmbH offers the related maintenance services to en sure the highest possible reliability and availability of the UPS system In addi tion we offer maintenance contracts to support and assist you in the following areas with our qualified staff Regular testing of the equipment in particular the accumulators as well as timely replacement and proper disposal of accumulators Inspection of the UPS installation Proper disposal of defective or degenerated components Environmentally acceptable disposal of accumulators You can find the complete range of our services on line at http www effekta com html service html or contact us directly at the addresses given above Adira series 73 UPS Adira 10kVA 20kVA 3 1 phase 11 Adira series Technical Data Technical Data Input Model 10kVA leoxva
7. 1 depended on the fault warning status of other status Adira series 23 UPS Adira 10kVA 20kVA 3 1 phase UPS Device Description 3 1 3 Button e Selection Functions e Switching to the next sub menu By pushing this button for one second you switch to the sub menu of the currently active menu item Changes will not be saved e Opening of the current menu items By pushing the button for one second the currently selected menu will be opened e Saving Changes By pushing the button for more than one second you can edit the currently selected menu entry Menu down next Functions e By pushing the button for about one second you can scroll through the currently active menu Menu up back Functions e Switching to main menu Push this button for more than one second to switch from the standard display to the main menu e Back Push this button for about one second to switch to the next higher menu or to go back step by step ON OFF Functions By pushing this button you can turn the device on or off e f you push this button while you are in the main menu the display will switch to the standard display Adira series 24 UPS Adira 10kVA 20kVA 3 1 phase UPS Device Description 3 2 Elements on the back of the device The connecting terminals UPS Output and Mains Input are on mains potential when connected However there can still be a dangerously high vo
8. 6 3 1 SNMP communication port Optionally the UPS can be equipped with a SNMP communication port 6 4 Connection sequence Adira series Connect the UPS with the mains power supply both the mains and the UPS must be safely switched off during this process Before the appliances are connected to the outlet the basic configura tion must be completed Connect the appliance s with the UPS Make sure that all appliances are switched off 40 UPS Adira 10kVA 20kVA 3 1 phase UPS Installation and Connection 6 5 Configuration of the EPO port Conductor function Size of connecting wire EPO 0 5 1 mm Leave the EPO plug installed on the EPO port of the UPS even if the EPO function is not needed Fig 6 1 EPO plug Please see the information regarding the connection of the EPO contact in chapter 3 3 3 EPO port Adira series 41 UPS Adira 10kVA 20kVA 3 1 phase UPS Installation and Connection 6 6 Adira series Operating procedure for the connection with an external battery The nominal DC voltage of the external battery pack is 288VDC Each battery pack consists of 24 pieces of 12V maintenance free batteries in series To achieve a longer back up time several battery packs can be connected but the principle of same voltage same type has to be strictly observed The procedure for the installation of the battery bank must be strictly ob served to avoid the risk of an electric shock
9. advance This exemption also includes any liability that can result from the claims of third parties against the initial purchaser In some countries the exemption or the limitation of concomitant or subsequent damage is not permitted by law so that the aforementioned declaration does not enter into force 1 7 Transport and Storage The UPS may only be transported to the intended location in the original pack aging The same applies to moves or returns The packaging plays no role as fall protection so all fallen devices must be checked by EFFEKTA Regeltechnik GmbH before commissioning The device may not be transported or stored upside down Adira series 12 UPS Adira 10kVA 20kVA 3 1 phase Introduction 1 8 Adira series Positioning Do not install in an area in which combustible vapours arise e g from pet rol tanks engine compartments etc The UPS is designed for operation in ventilated rooms with an ambient tempera ture of 0 to 40 C If the UPS is exposed to severe and quick temperature changes there is danger of condensation Before you take additional steps an acclimatization period of at least 2 hours is to be observed Never place or operate the device in a moist environment Keep liquids away from the device The UPS may not be placed in the vicinity of heat sources The UPS may only be set up in a vertical position and on castors Ensure that the back side and the front side of the device are at l
10. circuit cur rent which can cause burns Unauthorized persons should not have access to the accumulators Do not place accumulators in the vicinity of heat sources and do not throw them into a fire Explosion hazard Do not open or destroy accumulators The released electrolyte presents a great danger to health and the environment chemical burns to skin and eyes toxic 17 UPS Adira 10kVA 20kVA 3 1 phase Safety Instructions ON ES Fr x 2 8 Adira series e Defective accumulators have to be disposed of in an environmentally compatible manner Never dispose of accumulators with regular household waste Local disposal regulations must be observed Maintenance Service and Malfunctions Attention Danger of electric shocks Even after switching off the supply with the power button or after discon necting the accumulator feed respectively parts of the UPS can still carry high voltages ATTENTION Only trained electricians with sufficient knowledge of the required safety regulations may perform work on accumulators or supervise such work tasks Unauthorized persons should not have access to the accumulators The following precautions must be taken when working on the UPS or the accumulators Remove wrist watches rings and other metallic objects Use only isolated tools that comply with electrotechnical regulations Wear personal protective equipment safety glasses gloves face s
11. gt 5 HE frequency low limit lt 10 45 0HZ gt lt 1 49 5HZ gt 5 HE frequency high limit lt 1 50 5HZ gt lt 10 55 0HZ gt 5 Battery quantity lt 19 gt lt 21 gt 20 Displays the number of internal integrated accumulators External battery module lt 0 gt lt 9 gt 0 Set running time Day 0000 9999 Hour 00 23 Minute 00 59 Second 00 59 Running Time LCD contrast Adira series lt 5 gt lt 5 gt The contrast of the LCD Display can be ad justed here between 5 and 5 65 UPS Adira 10kVA 20kVA 3 1 phase 8 Troubleshooting Troubleshooting If the UPS system does not operate correctly first check the operating infor mation on the LCD display Please attempt to solve the problem using the table below If the problem still persists consult your dealer 8 1 Troubleshooting according to warning indica tion Error code Name Solution Bus short Please contact your dealer or Error code 01 tl bus error short circuit the customer service Bus voltage over Please contact your dealer or Error code 02 q y bus error overvoltage the customer service BUS voltage low Please contact your dealer or Error code 03 9 y y bus error low voltage the customer service BUS voltage Unbalance Please contact your dealer or Error code 04 bus error unbalances volt y the customer service age BUS soft start Fail P
12. nana ran nnn cnn rca nana nana 73 11 Technical Data oi cisisscccsciesseccsivntitaceocecceieacesdsterseutabeoanasedseotcsdesnsntasatareseatenseanaciusndavavazcdie gt 74 12 Scope of Delivery Optional Accessories nuunennennnnnennnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn nennen 76 12 2 Wearing parts liSt oonnnncnnninicnnnonccnnoncncnananacanan cnc nana na nano cnc rn nn narran rancia narnia 77 13 Conformity Declarations uueresnsnennnnnnnnennnnnnnnnnnnnennnnnnnnnnnnnnnnnnnnnnnnnnnnnnrennennnnnsnnnnnnnnnnnn 78 131 Adira s 1 10KVYAr EHE ie ala 78 132 Adira 3 2 20KVAr nenne RR 79 Adira series 4 UPS Adira 10kVA 20kVA 3 1 phase Introduction 1 1 1 Adira series Introduction Introduction Dear Operator You are about to operate an uninterruptible power supply This operating manual should provide you with support for working responsibly and basic information about the uninterruptible power supply namely how it op erates its application and what you should do in the event of malfunctioning Furthermore this operating manual contains instructions for the transport and storage as well as the handling and installation of the uninterruptible power sup ply The plan guidelines in this operating manual only relate to special requirements for the uninterruptible power supply During installation make sure you follow the national and local requirements for electrical installations The content of this device description
13. test Press the ON OFF button for more than one second until an acoustic signal sounds The UPS is now turned on A few seconds later the UPS will switch to regular operating mode and is now ready for operation If a fault is present at the UPS it switches to battery mode and all outputs are deactivated Turning on the UPS without connected appliances Check all connections before turning on the UPS Turn on the UPS The UPS is started up as the fan turns on and the LCD display shows a welcome message The UPS conducts a self test Press the ON OFF button for more than one second until an acoustic signal sounds The UPS is turned on after this procedure Turning off the UPS Push the ON OFF button for more than three seconds The system switches into bypass mode Disconnect the UPS from the mains input to switch it off completely 51 UPS Adira 10kVA 20kVA 3 1 phase Operation 7 2 2 UPS menu structure WELCOME Battery Volt 269 V Battery floating Charge level 90 Status Line mode Para Num 1 Running time 0000 03 37 19 Fig 7 12 Menu structure Adira series 52 UPS Adira 10kVA 20kVA 3 1 phase Operation Button Description GAN The description of this button can be found in chapter 3 1 2 S Buttons A The description of this button can be found in chapter 3 1 2 af Buttons KA The description of this button can be found in cha
14. 06 Adira series 75 UPS Adira 10kVA 20kVA 3 1 phase Scope of Delivery Optional Accessories 12 Scope of Delivery Optional Accessories Below you find a list of components that have been approved and tested by EF FEKTA Regeltechnik GmbH especially for this UPS Please check the delivery for completeness immediately after receiving the goods 12 1 1 Scope of Delivery Adira No Description Function View Article number Scope of delivery 1 x UPS electronics incl internal batter ies Adira 10 kVA 3 1 ph ACX31ADS10K00000 1 x UPS electronics Adira 20 kVA 3 1 ph incl internal batter ACX31ADS20K00000 ies 1 x Battery banks for Battery Bank USV 10 8 20 kVA With 24 accumulators 3 1 ph ABADX124009XXK00 With 2 x 24 accumula tors ABADX224009XXK00 1 x Operating Manual Printed Operating Manual X English 1 x USB cable Interface connection x Adira series 76 UPS Adira 10kVA 20kVA 3 1 phase Scope of Delivery Optional Accessories Software package CD ROM network compatible LAN PowerShut x PowerShut Plus shut down and diagnosis soft ware 1 license Windows Novell 1 license UNIX LINUX MAC 1 license RCCMD network remote client 12 1 2 Communication interfaces optional accessories Description Article number Type SNMP card GE cs121 SLBdget Internal SNMP adapter budget version
15. 2 battery bank 6 filter 13 Interface 7 UPS output 14 RS232 USB Fig 5 1 Block diagram The block diagram visualizes the individual modules of the device and illustrates their interaction 36 UPS Adira 10kVA 20kVA 3 1 phase System Description Adira series If a mains failure continues beyond the backup time of the UPS the UPS shuts down to avoid a total discharge of the accumulators As soon as the mains power supply returns the UPS automatically turns on again supplies electricity to the appliance and controls the charging of the battery bank Prominent performance features of the UPS are No interruption or signal change when the primary mains supply fails Perfect sine wave voltage on the UPS output Process controlled bypass mode Power Factor correction on the input side gt 0 99 LCD Display for status and operation data display Outstanding performance factor of 0 9 Efficient and extensive communication interfaces USB standard Emergency stop contact EPO standard 37 UPS Adira 10kVA 20kVA 3 1 phase 6 6 1 Adira series UPS Installation and Connection ATTENTION The system may only be installed and connected by trained authorized elec tricians in accordance with respective safety rules and regulations All requirements listed in the technical specifications concerning ambient and operating conditions must be met to ensure proper operation of the UPS Please note the
16. 232 V gt 228 V 50 Hz 100 50 HZ 1900 W Fig 7 11 Battery fault UPS operating instructions The operator of the UPS system must always adhere to the instructions in this operating manual The operator may only carry out the following measures and must always exercise particular care e Use of the operating controls switching on starting and switching off the UPS e Reading of the display messages and interpretation of the acoustic warning signals e Triggering the test mode Using the communication interface whereby the connection to the PC or other systems must already be established for UPS devices with permanent wiring Due to the extensive protective functions the UPS system performs in re lation to the appliance s the UPS operates fully automatically The opera tor only carries out the switching on and starting or switching off of the device In addition a data exchange can take place via the communication interface or the SNMP adapter however this is not absolutely necessary for the general operation of the system 50 UPS Adira 10kVA 20kVA 3 1 phase Operation 7 2 1 Adira series Switching the UPS on off Turning on the UPS with connected appliances Before turning on the UPS make sure all appliances are connected cor rectly Turn on the UPS The UPS is started up as the fan turns on and the LCD display shows a welcome message The UPS conducts a self
17. Adira series 10 UPS Adira 10kVA 20kVA 3 1 phase Introduction Adira series Inthe event that the product is incompatible due to possible technical inno vations or regulations that occur after the purchase Inthe event of incompatibility or malfunctioning that was caused by product components we did not install Inthe event of developments that are related to the normal aging process of the product wear parts Inthe event of defects that were caused by external fixtures The warranty period for replaced and or repaired parts as part of this warranty expires together with the original warranty for the product Devices that are supplied without accessories are replaced without accessories The return of the device is only accepted if this is done in the original packaging Incurred transport costs are generally not included in the warranty You shall bear the cost of repair and exchange and the company is not liable for damage whether directly unintentionally specifically or for subsequent damage even if it was caused by negligence or other errors EFFEKTA Regeltechnik GmbH does not provide either explicit or implicit war ranties related to this device and its quality performance saleability or suitability for a certain purpose In some countries the exclusion of implicit warranties is not permitted by law In this case the validity of all explicit and implicit warran ties is limited to the warranty peri
18. Declaration of Conformity Address EFFEKTA Regeltechnik GmbH Rheinwaldstr 34 D 78628 Rottweil Germany Product description UNINTERRUPTIBLE POWER SYSTEMS Model ADIRA 3 1 20kVA The above mentioned product is in delivered condition compliant with the following guidelines 2004 108 EC Council directive on the approximation of the laws of the member states relating to electromagnetic compatibility 2006 95 EC Council directive on the approximation of the laws of the member states concerning electrical equipment for use within certain voltage limits The conformity with the guidelines is guaranteed under application of following standards Safety Electromagnetic compatibility EMC Class C3 Number Issue Number Issue EN62040 1 2008 EN62040 2 2006 Rottweil 2014 03 07 ee Peter Androt Managing Director 79 EFFEKTA EFFEKTA Regeltechnik GmbH RheinwaldstraBe 34 D 78628 Rottweil
19. EFFEKTA UPS Uninterruptible Power Supply Adira 10 kVA 20 kVA 31 phase Battery Bank Operating Manual V 1 1 Article numbers ACX31ADS10K00000 ACX31ADS20K00000 Translation of the original Operating Manual UPS Adira 10kVA 20kVA 3 1 Legal notice phase Adira series Legal notice q by EFFEKTA Regeltechnik GmbH EFFEKTA Regeltechnik GmbH 78628 Rottweil retains the copyright to this documentation This documentation is solely intended for the operator and his staff The content of this documentation texts figures drawings graphics plans etc may not be copied or distributed in part or in full without our consent in writing nor can it be used without authorisation for competitive purposes or given or made accessible to third parties EFFEKTA Regeltechnik GmbH Rheinwaldstra e 34 D 78628 Rottweil Germany Phone 49 0 74 1 1 7451 0 Fax 49 0 74 1 1 7451 22 E mail ups effekta com Internet www effekta com Manual Operating manual Language English Release date 10 2013 We reserve the right to make changes to the design and the system that will im prove the system the production process or the product UPS Adira 10kVA 20kVA 3 1 phase Table of Contents Table of Contents 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 2 1 2 2 2 3 2 4 2 5 2 6 2 7 2 8 3 1 3 2 3 3 4 1 4 2 4 3 6 1 6 2 6 3 6 4 6 5 6 6 6 7 Introduction Introduction ua ce Es T TA V
20. S Left value output voltage Right value output frequency Display Input Displays the input phases Display Battery Displays the battery voltage and the charging status of the UPS Display DC Bus Displays the DC bus voltage of the UPS Display Temperature Displays the temperature of the UPS Adira series 57 UPS Adira 10kVA 20kVA 3 1 phase Operation 7 3 4 Control Menu A UPS Status e szene 9 Single UPS battery test Start battery test no 8 Status EPO active tatus battery test Clear no Reset fault Status Status fault active Reset fault no Clear event log Total events 50 Clear event log no Restore factory Reset no settings Fig 7 16 Control menu Adira series 58 UPS Adira 10kVA 20kVA 3 1 phase Operation The keypad tones of the UPS are turned on Yes The keypad tones of the UPS are turned off Menu Parameters Settings Factory setting Buzzer mute Buzzer mute lt No gt lt Yes gt No No Single UPS battery test Status battery test The status of the latest battery tests is displayed here Start battery test lt No gt lt Yes gt No No battery test is performed Yes A battery test is performed You can configure the cycle for a battery test in the menu automatic battery test period chapter 7 3 6 Settings Menu No Clear EPO status St
21. VA 3 1 phase UPS Device Description 3 3 3 3 1 3 3 2 Adira series Components RS232 USB ports These ports serve to connect the UPS to a PC A simultaneous use of the USB and the RS232 interface is not possible EPO port The EPO port serves for an emergency shut down of the connected appliances This function can be used to shut down connected appliances in the case of an emergency This circuit has to be separated from high voltage circuits by reinforced insulation The EPO port may not be connected to circuits that are directly connected with the mains power supply Feeders must have reinforced insulation The load capacity of the EPO switch must be at least 24 V DC 20 mA and it must be designed as a special snap switch without any connection to any other circuit The EPO signal must remain active for at least 20 ms to ensure proper opera tion UPS Adira 10kVA 20kVA 3 1 phase UPS Device Description 3 3 3 Intelligent Slot After unscrewing the cover various additional expansion cards can be installed e g SNMP card Fig 3 6 Network port SNMP mini slot card 3 3 4 AS400 After unscrewing the cover the AS400 extension card can be installed 3 3 5 Parallel port This function is not supported 3 3 6 Bypass switch The manual bypass can be useful if the UPS needs to be deactivated but the connected appliances still have to be supplied with electricity e g UPS failure malfunctions
22. all iii AA A A A DEREN Storage Symbols in this Manual Information Obligation anaringa a MECA nenn Transport and Storage Rositioning sanieren Safety lnstructions 2 4244 2205 2202025002022 ste apucecnectecaereacecececuactesacerscece dai diaaa araia 14 io A CN 14 Propor Uson nia A Aa 14 Avoiding Personal Injury Property Damage ooooccccocccconoccccnnoncnonananananoncnnnnn cnc nana na nana cnn 15 Protecting the Environment c ccccsssecessscencscscseesorerenscnenaseccesonseeeedatserseseecnavstaetonseeuesucees 15 GOMES CHO soei ayes eet tet rsp actuate caste en cat ot eet ce ty ona EAA aN 16 Operati n e n 3n een gan teat ai guanidine and 17 Working with Accumulators ooooococincccnnccincncocncnonananncnnn non rn cnn cano ronn nn rra 17 Maintenance Service and MalfunctiONS cccoooccncccnnocooannnnncnonononnnnnnnnnnononnnnnncnnnnononnnnnos 18 Device description of the UPS nursansnannnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnsnnnnnnnnsnnnnnnnnnnnnnn Elements on the front of the device Elements on the back of the device CUNA a a S EE NE ences grates Storage and Unpacking i s es onnea aineen anna eaaa saaneina paaa rre 32 Storage iof the UPS cinc 32 Moving the UPS to the installation Site oonoocinnnnnnnninnnnicnonnncnnnccnorccnnnnnnranarcn narco nrnnrnncnn 32 Unpacking of the device oo eee eeeeeceeeeeeeeeeeeeceeeeeeeeeeeeeaeeseaeeseeseaeeseaeeeaeessaeeeeeseaeeseeees 32 S
23. atine Board trage siow Ausgang Relais normalerweise geschlossen normaly closed Ausgang MC coil out R ckspeisung No active backfeed Eingang MC coil in Fig 6 3 Feedback protection Adira series 43 UPS Adira 10kVA 20kVA 3 1 phase UPS Installation and Connection Adira series Operation If a bypass thyristor is defective short circuit and the UPS is operated in double conversion mode online the following steps occur The feedback relay opens and the message backfeeder appears in the LCD Display Reset To reset the feedback logic the UPS system has to be turned off for a few seconds 44 UPS Adira 10kVA 20kVA 3 1 phase Operation 7 Operation 7 1 Operation of the UPS The operation of this equipment is characterized by various operating modes and signals 7 1 1 Operating mode line mode Line mode is the regular mains power supply operating mode of the UPS The display for line mode looks as follows Input Output 230 V 269V 230 V 232 V Ps aco 50 Hz 100 50 HZ 1900 W Fig 7 1 line mode Battery mode In the event of a mains failure the UPS switches to battery mode The display for battery mode looks as follows Input Output OV 269 V 230 V 0 Hz 50 Hz 100 OW Fig 7 2 Battery mode Adira series 45 UPS Adira 10kVA 20kVA 3 1 phase Operation The battery mode is marked b
24. atus Displays the EPO status Clear lt No gt lt Yes gt No If the EPO had been triggered it will not be reset Yes If the EPO had been triggered it will be reset No Reset fault status Status Displays whether the fault mode is active or inactive Reset fault lt No gt lt Yes gt No If a fault is pending on the UPS it will not be reset Yes If a fault is pending on the UPS it will be reset No Clear event log Total events Displays the number of messages Adira series 59 UPS Adira 10kVA 20kVA 3 1 phase Operation Clear event log lt No gt lt Yes gt No The warning fault messages have not been reset Yes The warning fault messages have been deleted No Restore factory settings Reset lt No gt lt Yes gt No The UPS will not be reset to factory settings Yes The UPS will be reset to factory settings No Adira series 60 UPS Adira 10kVA 20kVA 3 1 phase Operation 7 3 5 Identification Menu Input P Output szy 269v 230v 228v oii A UPS Status 50 HZ 100 i i600 Wi e o o e Type Model Identification Tower 3 1 10000 VA Online Serial Number 130311 65920004 UPS Firmware 05570 0400 Fig 7 17 Identification Menu Parameters Description Display Type Model Displays the UPS type model Display Serial number Di
25. be carried out by professional technicians in accordance with local safety regulations and in adherence to the following in structions For safety reasons turn off the main power switch before you begin with the installation Open the panel of the terminal block at the back of the UPS Please re fer to the system diagram for this task For a 20kVA UPS we recommend to use a cable of 10 mm for the input Main1 and 25 mm for the input Main2 and for the output For a 10kVA UPS we recommend to use a cable of 6 mm for the input Main1 and 10 mm for the input Main2 and for the output UPS Input fuse Main 1 Input fuse Main 2 Bypass 10kVA 3x40A 1x63A 20kVA 3x60A 1x100A ATTENTION Do not use a wall socket as input power source for the UPS as its nominal current is below the maximal input current of the UPS The wall socket could burn and get destroyed Connect the input and output cables with the respective input and output terminals The protective earth conductor refers to the cable connection between the parts that consume electric energy and the earth wire The cable di ameter of the protective earth wire should at least have the measure ments mentioned above for cables for the individual models and a yellow and green striped wire is to be used Check after completing the installation if all the wiring is correct Please install the output circuit breaker between the output terminal and the load an
26. ckup period In this case the appliances will usually not be without power in the end To use either method you have to force the UPS into backup mode by simulat ing a mains failure e g trip the fuse of the building Do not under any circum stances remove the mains connection as that would also disconnect the pro tective earth conductor After the measurement has been carried out turn the circuit breaker back on and turn on the UPS as usual with the ON button 70 UPS Adira 10kVA 20kVA 3 1 phase Maintenance and Service 10 2 Adira series Remember that after the measuring the accumulators of the system will be dis charged l e the UPS system must operate in line mode or charging mode re spectively for several hours min 5 h before it will again be operational at about 80 capacity If the backup time is not measured due to local conditions or instructions we recommend a prophylactic replacement of the accumulators every two years to avoid any risk of insufficient backup time because of degenerated accumulators Replacing the accumulators Accumulators may only be replaced by the manufacturer 71 UPS Adira 10kVA 20kVA 3 1 phase Maintenance and Service 10 3 Service Log Please always enter all maintenance and service work conducted on the UPS into the service log Date Performed tasks Performed by Adira series 72
27. d the circuit breaker should be equipped with a fault current protective function if that is required To connect the load with the UPS first switch off all loads then establish the connections and then switch the loads on again one after the other 39 UPS Adira 10kVA 20kVA 3 1 phase UPS Installation and Connection Regardless whether the UPS is connected to the mains power supply or not the output of the UPS may still be energized The parts inside the unit may still carry dangerous voltages even after the UPS has been turned off To ensure that the UPS does not emit any electric charge turn off the UPS and disconnect it from the power supply We recommend that you charge the batteries for at least 24 hours before using the unit Turn the input breaker to ON after connecting the de vice The UPS charges the batteries automatically You can also put the UPS into operation immediately without charging the batteries first however the backup time may be below its regular value 6 3 Communication port of the UPS The UPS is equipped with a convenient communication interface to facilitate the exchange of data with the UPS ATTENTION When connected with a USB cable the software can exchange data with the UPS The software collects detailed information about the status of the power supply from the UPS In the case of a supply emergency the software en sures that all data is saved and all appliances are shut down properly
28. dira 10kVA 20kVA 3 1 phase Operation Parameters Settings Default value User password lt enable gt lt disable gt disable If this value is set to lt enable gt you have to enter the password Audio alarm lt enable gt lt disable gt enable If this value is set to lt disable gt the UPS is silent and no alarm signals will sound Output voltage lt 208 gt lt 220 gt lt 230 gt lt 240 gt 230V Output frequency lt 50HZ gt lt 60HZ gt autosensing lt Autosensing gt On lt autosensing gt the output frequency is identical to the input frequency Power strategy lt normal gt Normal lt high efficiency gt lt converter gt DC start lt enable gt lt disable gt enable cold boot Site wiring alarm lt enable gt lt disable gt enabled If this value is set to lt enable gt a warning message appears in the display when the protective earth conductor is not connected or if phase and neutral have been swapped Ambient temperature lt enable gt lt disable gt enabled warning If this value is set to lt enable gt a warning message appears in the display when the ambient temperature reaches 45 C Automatic battery tests lt 0 gt lt 31days gt 7 days period If this value is 0 the automatic battery test is turned off Auto restart lt enable gt lt disable gt enable lt enable gt means that the UPS performs an automatic restart in normal operating mode if it was shut down due to a l
29. e UPS In case the device is not being installed immediately please note the following e Always store the device and any accessories in their original packaging e The suggested ambiance temperature for the storage is between 0 C 40 C Protect the device and packaging from moisture and liquids If the storage period exceeds four months the UPS and the corresponding bat tery bank optional have to be connected with the mains power supply for ap proximately 24 hours to avoid a total discharge of the accumulators Moving the UPS to the installation site The UPS is on castors to facilitate moving the device to the installation location after unpacking However if the receiving area is far from the installation site we recommend you to move the UPS by using a pallet jack or a lifter before you start to unpack the UPS Unpacking of the device e At the installation site the utmost care shall be taken when removing the packaging in order to avoid damaging the equipment Check all packaging materials to ensure that no items are missing The shipping package contains AUPS A user manual AUSB cable 32 UPS Adira 10kVA 20kVA 3 1 phase Storage and Unpacking Remove the packaging following the sequence illustrated in Fig 4 1 to Fig 4 4 Tools Lifter Phillips screw driver of i Wrench Scissors Spanner Fig 4 1 Unpacking step 1 Adira series a
30. e fixed as quickly as possi ble The UPS continues to operate when a warning occurs If there are any warnings pending at the UPS the display looks as follows pet K Output 232 V 269 V 230 V 228 V 50 Hz 50Hz 100 ll ow Fig 7 7 Warning Fault A fault alarm signifies a fatal problem The UPS signals a fault through an alarm signal and switches either into bypass mode or shuts down depending on the configuration The background light of the LCD Display turns red The display for fault mode looks as follows Input Output 232 V 269 V OV 228 V MM 0 Hz 50 HZ 0 OW Fig 7 8 Fault 48 UPS Adira 10kVA 20kVA 3 1 phase Other signals Operation In the event of an overload the UPS emits an acoustic signal The alarm signal sounds twice per second The display in the event of an overload looks as follows Input 230 V 232 V 228 V 50 HZ Fig 7 9 Overload During a battery test the display looks as follows Output 230 V 50 Hz 6480 W Input 230 V 232 V 228 V 50 HZ Fig 7 10 Battery test Adira series Output 230 V 50 Hz 1900 W 49 UPS Adira 10kVA 20kVA 3 1 phase Operation 7 2 Adira series If a fault is detected in the battery like e g battery not connected or poor bat tery status the display looks as follows Input i Output 230 V 269 V 230 V
31. east 10 cm from other objects for ventilation in order to prevent trapped air and too much warming Make sure that the air openings cannot be covered e g through sucked in paper material etc 13 UPS Adira 10kVA 20kVA 3 1 phase 2 2 1 2 2 Adira series Safety Instructions Safety Instructions Introduction The UPS is a device that has been produced according to the rules and regula tions of technology for an uninterruptible power supply The device is safe when used properly and under consideration of the safety re quirements and instructions provided in this operating manual Proper Use The UPS and its related components may only be used for purposes in accor dance with its design to provide a short term supply for electrical devices 230 V AC with the nominal power not exceeding the total Any other use is considered improper and can lead to personal injury or damage to the device Improper Use The device is not designed for use in explosive dusty radioactive or biologically or chemically contaminated atmospheres ATTENTION This class A equipment This equipment can cause radio interference in residential areas In this case the operating company may be requested to take appropriate measures 14 UPS Adira 10kVA 20kVA 3 1 phase Safety Instructions 2 3 Avoiding Personal Injury Property Damage e Please read this operating manual carefully to familiarise yoursel
32. ed e LCD LED display information Buzzer alarm status Mains power condition load type and capacity environment tempera ture ventilation condition Information battery capacity number about the external battery pack if itis a UPS of the model series XL e Any additional information for a complete description of the problem Adira series 68 UPS Adira 6kVA 6kVA XL 10KVA Software 10kVA XL 1 phase 9 Software With a suitable software package the configurations and operating statuses of the UPS can be determined and processed via the communication interface The software packages are available from the manufacturer dealer or through the service hotline Through these channels you can receive useful information about the suitable software packages for your UPS to fit your needs See also our website http www effekta com The following basic functions are supported by all software packages Detecting and displaying the UPS s power supply status Display of the UPS output status Detecting and displaying the charging status of the battery bank Closing of open applications in the case of a mains failure Shut down of the operating system Creating log files Basic monitoring of UPS data and condition diagnostic function For more information on the individual software packages like installation op eration and range of services see the respective software manuals In the chapt
33. er Scope of Delivery Optional Accessories you will find suitable and tested software packages Adira series 69 UPS Adira 10kVA 20kVA 3 1 phase Maintenance and Service 10 10 1 Adira series Maintenance and Service You may expect a long service life and interference free operation of your UPS at a minimum of maintenance effort However the reliability of the UPS is greatly dependant on the ambient condi tions The ambient temperature and humidity must remain within the given range In addition the area around the UPS should be kept clean and free of dust At an ideal ambient temperature of about 22 C the service life of the accumula tors is typically around 4 years Through the use of special accumulators the service life can be significantly increased about 8 10 years You should check periodically every 6 12 months whether the remaining backup time is sufficient for the intended purposes Once that is no longer the case the accumulators have to be replaced Measuring the backup time Support time Before you begin this procedure please make sure to save all open data Fur thermore inform all affected employees Basically there are two different methods for measuring the back up time Method a measures the actual back up time which means that at the end of that backup time the appliances would be without a power supply Method b allows to determine the residual capacity after a defined ba
34. etc This procedure may only be carried out by a trained electrician authorized by the manufacturer 3 3 7 Port for external battery banks External battery banks can be connected to the UPS to increase backup time 30 UPS Adira 10kVA 20kVA 3 1 phase UPS Device Description 3 3 8 UPS connection terminals Connection terminals to connect appliances and the mains supply input Paseo ae s ela s aciaa L1 L2 L3 N N GND JP1 JP B B Lo o 0 le Le o o fel fe o o o te Le fol o ONoaRWD 9 Terminal supply input L1 10 Terminal supply input L2 11 Terminal supply input L3 12 Terminal supply input N 13 Terminal supply input PE 14 Terminal Main 2 L Bypass 15 Terminal Main 2 N Bypass 16 Terminal Main 2 PE Bypass Terminal supply output L Terminal supply output N Terminal supply output PE Terminal parallel jumper 1 Terminal parallel jumper 2 Terminal ext Battery Pol Terminal ext Battery Pol Terminal ext Battery PE ONO RWND Fig 3 7 Connection terminals The protective earth conductor must be connected Please always note the specified input voltage on the type plate or in the techni cal specifications in this operating manual respectively 3 3 9 Fan Fan to cool the device Adira series 31 UPS Adira 10kVA 20kVA 3 1 phase Storage and Unpacking 4 4 1 4 2 4 3 Adira series Storage and Unpacking Storage of th
35. f with the device In particular take note of the information regarding the installation and commissioning of the device Only operate the product in an appropriate and proper way and within the parameters stated in the technical data e Only perform maintenance and service work that is described in the docu mentation Observe the required steps Only use original replacement parts from EFFEKTA Regeltechnik GmbH 2 4 Protecting the Environment e Send the product back to EFFEKTA Regeltechnik GmbH after the end of its service life We will ensure environmentally friendly disposal Adira series 15 UPS Adira 10kVA 20kVA 3 1 phase Safety Instructions 2 5 Adira series Connection The UPS is connected via the connection terminals on the back of the de vice The PE protective earth conductor must be connected without fail The device may not be used without the PE under any circumstances Keep the cable length as short as possible During generator operations the pole correct connection of the UPS must be ensured For the connection of the UPS with the electricity grid only a power cable that is VDE approved and labelled CE may be used For the connection of the appliances with the UPS only a power cable that is VDE approved and labelled CE may be used The safeguarding of any appliance must always be immediately in front of an appliance and may never be done centrally in front of the UPS Never operate any
36. following during set up installation of the UPS e Avoid extreme temperatures and humidity e _ Ensure proper vertical set up as predefined e Allow adequate space for ventilation of the device Ensure a proper flow channel e Pay attention to the system layout When installing the device in su perordinate systems e g machine switchboard it has to be ensured that the UPS is operated within the specified temperature range In case ofa heat build up in the installation room it must be removed through ade quate powered ventilation e The device may only be mounted on castors and a solid weight bearing and horizontal surface Notes on the installation The UPS must be installed in a well ventilated environment far away from water flammable gas and corrosive agents Ensure that the fans on the front and back side of the UPS are not ob structed by anything There should be at least half a meter of free space on all sides Ifthe UPS is unpacked in an environment with very low temperatures there is a danger of condensation and water droplets may form In this case you have to wait for the UPS to fully dry inside and out before you continue with the installation or commission the device as there may otherwise be a risk of electric shocks UPS Installation and Connection UPS Adira 10kVA 20kVA 3 1 phase UPS Installation and Connection 6 2 Adira series Connecting the UPS The installation and wiring must
37. g mode and the hours of operation of the UPS The value Para Num shows how many devices are connected in parallel Adira series 54 UPS Adira 10kVA 20kVA 3 1 phase Operation 7 3 2 Event Log Menu Input gt Output kedd 269v 230v A 228v 50 HZ 100 Di null 1900 W 0000 03 37 19 Event Log Event 51 UPS Control Power On 1 50 o o o o 0000 03 37 19 Event 02 Utility abnormal 0000 03 37 19 Event 52 UPS On from Panel 3 50 O Fig 7 14 Event Log Menu Parameters Description Display Event Log The menu displays up to 50 warning fault messages and re sults In the event of more than 50 entries the old entries will be over written Adira series 55 UPS Adira 10kVA 20kVA 3 1 phase Operation 7 3 3 Measurements Menu Out put 850w 1130VA Input 220v 60Hz JU Output 220 Out put 60 Hz 49A 75 Out put 230 4V 50 0Hz Event log S Measurements A O Battery 54 2 V 100 Fig 7 15 Measurements Menu Adira series 56 UPS Adira 10kVA 20kVA 3 1 phase Operation Parameters Description Display Output Displays the power output of the UPS Left value active power Right value apparent power Display Output Displays the output current of the UPS Left value output current Right value output current in percent Display Output Displays the output voltage of the UP
38. hield etc The UPS may not be disassembled 18 UPS Adira 10kVA 20kVA 3 1 phase UPS Device Description 3 Device description of the UPS This manual shall provide basic information about one phase UPS system of the Adira series like the mode of operation utilization of the different functions and what to do in case of malfunctions In addition this operating manual con tains instructions for the proper transportation and storage as well as for the handling and installation of the UPS equipment The planning guidelines in this manual refer only to the specific requirements of UPS systems National and regional regulations for electrical installations have to be adhered to when installing the system The content of this device descrip tion may change due to technological developments We have made every ef fort to ensure that all content is accurate and presented in a clear and compre hensible manner In case of any errors we are grateful for advice and sugges tions We do not assume any liability for any errors in this manual or any conse quences resulting thereof The UPS system uninterruptible power supply is designed to protect sensitive electronic equipment like computers work stations electronic cash registers operations critical instruments telecommunication systems process controllers etc from interferences that can result from poor power quality or mains failures Sensitive equipment of this sort need
39. household devices or tools like e g fan heaters vac uum cleaners electric drills toasters etc with the UPS Do not connect any appliance to the UPS that could overload the device e g laser printer Keep the connecting cables as short as possible and always install them correctly Avoid hazards to the cable like tripping crushing clipping etc 16 UPS Adira 10kVA 20kVA 3 1 phase Safety Instructions 2 6 Adira series Operation Before the appliances are connected to the outlet the basic configuration must be completed Especially the output voltage is of high importance regarding the appliances The UPS system contains an energy storage accumulators This means that the outlet can be current carrying even when the UPS is not connected to the mains input terminal To completely shut down the UPS first disconnect the mains connection and then hold the OFF button pressed for more than 3 seconds Wait for the UPS to turn off before disconnecting the power connection feeder cable between the UPS and the appliance Ensure that no liquids or foreign matter enters the UPS Avoid a constant load of more than 80 on the output to protect the UPS The displayed output load should only be taken as a reference point separate measuring is necessary to determine the exact output load Working with Accumulators Attention Danger of electric shocks and burns Accumulators can cause electric shocks and have a high short
40. lease contact your dealer or Error code 05 bus soft start failure the customer service Inverter soft start fail Please contact your dealer or Error code 06 inverter soft start failure the customer service Remove all the loads Turn off the UPS Ensure that the load hast not failed and that there are Inverter short no internal UPS failures errors Error code 07 A S inverter short circuit before you turn it back on If this does not solve the issue please contact your dealer or the cus tomer service Inverter voltage low Please contact your dealer or Error code 08 y J y 0 inverter voltage low the customer service Inverter voltage high Please contact your dealer or Error code 09 J 2 4 inverter voltage high the customer service Inverter Relay short Please contact your dealer or Error code 10 O inverter relay short circuit the customer service Error code 11 Overload Fault Check the loads and remove the Adira series 66 UPS Adira 10kVA 20kVA 3 1 phase Troubleshooting non critical equipment Calculate the load current again and re duce the number of loads that are connected to the UPS Check if any of the loads failed Error code PARA Communication Line loss Fault Make sure the parallel port is correctly and fully connected If this does not solve the issue please contact your dealer or the customer service Error code Null reservation E
41. ltage on the connecting terminals even while disconnected due to device internally loaded capacities As soon as mains input voltage is present the loading unit is automatically activated l e the internal battery bank is already being charged even though the UPS has not been switched on Adira series 25 UPS Adira 10kVA 20kVA 3 1 phase UPS Device Description 3 2 1 Model 10 kVA 3 1 phase 1 USB port 2 RS 232 3 EPO port 4 Communication interface Intelligent Slot 5 Parallel port 6 AS 400 port 7 Connection terminals mains input and UPS output 8 Circuit Breaker mains input 9 Feedback protection 10 Fan 11 Bypass switch Fig 3 3 Back panel 10 kVA 3 1 phase Adira series 26 UPS Adira 10kVA 20kVA 3 1 phase UPS Device Description 3 2 2 Model 20 kVA 3 1 phase Dy A Ll M K Ey x C 1 USB port 2 RS 232 3 EPO port 4 Communication interface Intelligent Slot 5 Parallel port 6 AS 400 port 7 Connection terminals mains input and UPS output 8 Circuit Breaker mains input 9 Feedback protection 10 Fan 11 Bypass switch Fig 3 4 Back panel 20 kVA 3 1 phase Adira series 27 UPS Adira 10kVA 20kVA 3 1 phase UPS Device Description 3 2 3 External battery bank for 10 amp 20 kVA 3 1 phase 1 Fuses 2 UPS Connection Fig 3 5 Back panel external battery bank for 10 amp 20 kVA 3 1 phase Adira series 28 UPS Adira 10kVA 20k
42. may change due to technological pro gress We have tried to present the content correctly and clearly If however we have made errors we would be grateful for information about this We do not assume any liability for errors in this operating manual or any conse quences resulting thereof The uninterruptible power supply is intended to protect sensitive electronic sys tems from interferences that could occur due to bad electric quality or grid fail ures Please read this operating manual carefully and take note particularly of the safety instructions If you have questions about the device the technical supervisor in your com pany or our employees will be glad to help you Your EFFEKTA Regeltechnik GmbH UPS Adira 10kVA 20kVA 3 1 phase Introduction 1 2 Validity The descriptions in this operating manual relate solely to the uninterruptible power supply defined in the technical data as a whole or as it refers to modules components and individual parts that were developed and built by EFFEKTA Regeltechnik GmbH 11 Technical Data 1 3 Storage This operating manual for the device must be stored in the vicinity of the device at all times so it is immediately available if need be 1 4 Symbols in this Manual The abbreviation UPS in this manual stands for uninterruptible power supply e Read this documentation carefully and make yourself familiar with the product before using it e _ Store this operating man
43. ng blue normal operating mode red fault mode Adira series 21 UPS Adira 10kVA 20kVA 3 1 phase UPS Device Description Colour Name Function green Inverter LED If it is turned on constantly it shows that the load current is supplied from utility power or battery via the inverter yellow Battery LED If it is turned on constantly it shows that the UPS is in battery mode and the load current is from battery via the inverter yellow Bypass LED If it is turned on constantly it shows that the auto bypass is activated If it is flashing it shows that the auto bypass is deactivated red Fault LED If it is turned on constantly it shows that the UPS is in fault mode If it is flashing it shows that the UPS is in warning status Adira series 22 UPS Adira 10kVA 20kVA 3 1 phase UPS Device Description 3 1 2 LED action summary LED Display No Status normal LED battery LED bypass LED Fault LED green yellow yellow red 1 power on mode A A A A activation 2 bypass mode 1 without output 3 bypass mode t with output 4 line mode 1 line mode 5 battery mode 1 6 battest mode A A A A battery test mode 7 HE mode J t high efficiency mode 8 warning 1 1 1 9 fault mode ij O Remarks permanently lit A 1 4 lightened circularly x flashing
44. od With the expiration of these periods all warranties lose their validity In some countries a limitation of the validity period of implicit warranties is not permitted by law so that the aforementioned limita tion does not take effect 11 UPS Adira 10kVA 20kVA 3 1 phase Introduction 1 6 1 Limitation of liability Claims to damage compensation are excluded unless they involve intent or gross negligence by EFFEKTA Regeltechnik GmbH or its employees This does not affect liability according to the Product Liability Act Under no circum stances are we liable for Claims that third parties make against you due to losses or damage Loss or damage of your records or data or the costs of recovering this data Economic subsequent damage including lost profits or savings or con comitant damage including in the event that we were informed of the pos sibility of such damage Under no circumstances is EFFEKTA Regeltechnik GmbH responsible for any accidental indirect specific subsequent or other damage of any kind including without any limitation damage related to a loss of profits interruption of busi ness loss of business information or any other losses that result from use of the device or are connected with the device whether they are based on the con tract damage compensation negligence strict liability or other claims even if EFFEKTA Regeltechnik GmbH was informed about the possibility of such damage in
45. ow battery charge status Automatic overload lt enable gt lt disable gt enable restart lt enable gt signifies that the UPS switches from bypass to line mode after the batteries have been charged to 70 Adira series 64 UPS Adira 10kVA 20kVA 3 1 phase Operation The selected value gives the number of exter nal battery modules Auto bypass lt enable gt lt disable gt disable lt enable gt signifies that the UPS switches to bypass mode after start up lt disable gt signifies that the UPS does not start in bypass mode but switches to bypass mode if a fault is detected or the batteries are over loaded Short circuit clearance lt enable gt lt disable gt disable lt enable gt means the UPS stays in line mode and no warning message is displayed if a short circuit at the output last less than four sec onds lt disable gt means that the UPS switches to fault mode and displays a warning signal if a short circuit at the output lasts more than four seconds Bypass voltage low limit lt 167V gt lt 215V gt 176V Bypass frequency high lt 1 50 5HZ gt lt 10 55 0HZ gt 10 limit Bypass voltage high limit lt 245V gt lt 276V gt 264V Bypass frequency low lt 10 45 0HZ gt lt 1 49 5HZ gt 10 limit HE voltage low limit lt 10 207 0V gt lt 0 5 218 5V 5 HE voltage high limit lt 5 241 5V gt lt 10 253 0V
46. pter 3 1 2 NY Buttons gt The description of this button can be found in chapter 3 1 2 NR Buttons Parameters Description Display Alarm The status messages menu displays the latest error messages listed together with the count of the operating hours counter the alarm code and the plain text of the error message Display Battery voltage and Load Status The menu displays the condition of the battery Display Status and Running time The menu displays the operating mode and the hours of operation of the UPS The value Para Num shows how many devices are connected in parallel Adira series 53 UPS Adira 10kVA 20kVA 3 1 phase Operation 7 3 Menu 7 3 1 UPS status menu Input 230v 232v 228v 269V 100 sonz a Output 230V iia E UPS Status No alarm Fig 7 13 i a Battery Volt 269 V Battery floating Charge Level 90 Status Line mode Para Num 1 Running time 0000 03 37 19 UPS status menu Parameters Description Display Alarm The status messages menu displays the latest error messages listed together with the count of the operating hours counter the alarm code and the plain text of the error message For further details on fault warnings see chapter 8 Display Battery voltage and Load Status The menu displays the condition of the battery Display Status and Running time The menu displays the operatin
47. rror code Negative power Fault Please contact your dealer or the customer service Error code Over Temperature Ensure that the USP does not have an overload that the venti lation openings are not blocked and that the ambient tempera ture is not too high Wait 10 minutes to allow for the UPS to cool before restarting it If this does not solve the issue please contact your dealer or the cus tomer service Error code Model set fault Please contact your dealer or the customer service Error code Backfeeder Do not touch any of the connec tions of the device that connect the UPS with the mains power supply even after you have turned off the power supply or disconnected the device Please contact your dealer or the cus tomer service Error code Parallel Single communication Line loss Fault Make sure the parallel port is correctly and fully connected If this does not solve the issue please contact your dealer or the customer service Error code CAN Communication fault Make sure the parallel port is Adira series 67 UPS Adira 10kVA 20kVA 3 1 phase Troubleshooting correctly and fully connected If this does not solve the issue please contact your dealer or the customer service When you contact the service centre please provide the following informa tion Model number serial number Date on which the problem occurr
48. s comprehensive protection from all elec trical interference These may either be external interferences like e g light ning disruption of operations or interferences from other devices in its vicinity e g engines air conditioning processing machines welding facilities or the like Power interferences can be summarized as follows rapid or slow voltage peaks or fluctuations mains failure power overlaps or transients The UPS system monitors the above mentioned grid parameters and protects all connected appliances through appropriate countermeasures e g switching to bypass mode when temporary over or under voltage of the grid is detected to protect the end device Adira series 19 UPS Adira 10kVA 20kVA 3 1 phase UPS Device Description 3 1 Elements on the front of the device On the front side of the device are all operating and display elements necessary for the normal operation of the UPS NORMAL BATTERY BYPASS FAULT Heros Fig 3 1 Frontal view UPS Control panel Display Adira series 20 UPS Adira 10kVA 20kVA 3 1 phase UPS Device Description 3 1 1 LCD Display NORMALI BATTERY BYPASS FAULT 1 Status Display 2 LCD Display 3 Select button 4 Menu Down Next button 5 Menu Up Back button 6 ON OFF button Fig 3 2 Control panel The back lighting of the LCD Display changes its colour depending on the de vice status Colour Meani
49. splays the UPS s serial number Display UPS firmware Displays the current UPS firmware Adira series 61 UPS Adira 10kVA 20kVA 3 1 phase Operation 7 3 6 Settings Menu User password lt disabled gt Input gt Output A Ze 26v 23v 228v TR A UPS Status Audio Alarm sonz 100 A lt enabled gt Output voltage lt 230v gt Output frequency lt 50Hz gt Automatic battery tests perlod lt 7days gt Auto Restart lt enabled gt The menu structure is continued on the next page Adira series 62 UPS Adira 10kVA 20kVA 3 1 phase Operation HE voltage low limit lt 5 218 5V gt gt Automatic overload restart lt enabled gt SNS Auto bypass lt dlsabled gt S Short circult clearance HE frequency low lt disabled gt limit lt 5 47 5Hz HE voltage high limit lt 5 241 5V gt Bypass voltage low limit HE frequency high lt 184V gt limit lt 5 52 5Hz gt Bypass voltage high limit Battery quantity 4 gt SEES Bypass frequency Low limit External battery 2 lt 45 0Hz gt module lt 0 gt Set running time SEES LCD contrast lt 0 gt Bypass frequency High limit lt 55 0Hz gt Set running time Day 0001 Time 00 00 00 1 Only for models 6kVA and 10 kVA 2 Only for models 6kVA XL and 10kVA XL Fig 7 18 Settings Menu Adira series 63 UPS A
50. symbols Take note of the provided documentation and or instructions Disconnect before work Adira series 8 UPS Adira 10kVA 20kVA 3 1 phase Introduction 1 4 4 General symbols Adira series This dot marks descriptions of activities that you should carry out This dash marks specification lists This arrow marks a cross reference If a cross reference to another chapter is necessary in the text this is shortened for clarity Example gt OM 2 Safety Instructions This means See Operating Manual Chapter 2 Safety Instructions If the cross reference refers to a page figure or position number this information is added at the end of the cross reference Example gt Fig 4 4 Pos 1 This means See position number 1 in figure 4 in Chapter 4 of this manual Numbers in brackets refer to the positions in the figures Identifies instructions for recycling Identifies components that are subject to the Electronic Scrap Regulation Identifies components or parts that must be disposed of Do not throw these into the household waste Requirement that must be fulfilled V The DC circuit breaker is on OFF UPS Adira 10kVA 20kVA 3 1 phase Introduction 1 5 Information Obligation This operating manual must be read understood and all its points must be taken note of by all persons that are responsible for the Operation Cleaning and Disposal of this device
51. ual in an easily accessible place to refer to it if necessary e Please pass this operating manual on to later users of the product 1 4 1 Danger warning levels Text that is marked with DANGER provides a warning about dangers If accident prevention measures are not taken these dangers may result in serious irreversible injuries or even death Adira series 6 UPS Adira 10kVA 20kVA 3 1 phase Introduction Adira series Text that is marked with WARNING provides a warning about hazards If accident prevention measures are not taken these hazards may result in serious irreversible injuries or even death Text that is marked with CAUTION provides a warning about hazards If accident prevention measures are not taken these dangerous situations can lead to slight or medium reversible injuries ATTENTION Text that is marked with ATTENTION contains very important instructions for situations that if accident prevention measures are not taken may re sult in damage to the product and or its functions or an object in its vi cinity This symbol indicates text that contains important instructions comments or tips N UPS Adira 10kVA 20kVA 3 1 phase Introduction 1 4 2 Warning information 1 4 2 1 Warning about danger spots A General warning about danger spots 1 4 2 2 Specific warning Warning about dangerous electrical voltage A Warning about proper handling of accumulators 1 4 3 Instruction
52. y an acoustic signal in four seconds intervals Bypass mode ATTENTION The UPS has no backup function in bypass mode The UPS switches into bypass mode e g when there is an inverter problem The mains input and power output are bypassed via a relay The display for bypass mode looks as follows Input PL Output 230 V 269 V 230 V 50 Hz 50 Hz 100 1900 W Fig 7 3 Bypass mode with output Input ch Output 230 V 269 V OV 50 Hz 0 Hz 0 OW Fig 7 4 Bypass mode without output The bypass mode is marked by an acoustic signal in two minutes intervals Adira series 46 UPS Adira 10kVA 20kVA 3 1 phase Operation HE mode high efficiency In HE mode the UPS is initially in bypass mode The inverter is only activated in the event of a mains failure This results in a brief switch over time in the milli second range The display for HE mode looks as follows Input Output 230 V 269 V 230 V 50 Hz 50 Hz 1900 W Fig 7 5 HE mode Converter mode In converter mode the frequencies of the input and output can be configured The display for converter mode looks as follows Input PL Output 230 V 269 V 230 V 232 V a 228 V 50 Hz soHz gl 1900 w Fig 7 6 Converter mode Adira series 47 UPS Adira 10kVA 20kVA 3 1 phase Operation Adira series Warning In general warnings are no fatal faults but should b
53. ystem DESC 22 as sei 36 UPS Installation and Connection uu2u2u0022200222002020000000000000020000000nRnBnnnnn non nnnnnnnB naar 38 Notes on the installation z Connecting the UPS oococccciccccocanancconanononononananccnnn conca nn rar nr n nn nn Communication port of the UPS unzuessesnssnersnnnsnnnnnnnennnnnnnnnnnnnnnnnennnnnnnnnnnnnennnennnnnn nn 40 Connection sequence Configuration of the EPO port Operating procedure for the connection with an external battery 42 Feedback protection fit A asa 43 Adira series 3 UPS Adira 10kVA 20kVA 3 1 phase Table of Contents AA A E a a aaaea 45 7A Operation ofthe UPS 2 42 2 2 ee I 45 7 2 UPS operating instructions 4 2 RD 50 Peis A A A IE OT 54 8 4 TFOUDIESHOO NO dead 66 8 1 Troubleshooting according to warning indication oonnccinnnccnnnnncnnncccnnnnaancnnnanananancnnnnnoo 66 Qe SOMWANC EERRARBENBRRRERERER HE BEE ERERRER ESEL RE ET 69 10 Maintenance and Service iiis ereden adara ae aeai a daaa eaaa Ean EANES aea 70 10 1 Measuring the backup time support tiMe o oooocccinnnnnconnncnnnnnnocccnncncnrncnoncnanccnnn nono nannncns 70 10 2 Replacing the accumulators 0 cissccccescsceessiceseorsesenssonsvensceseocsseensseneuosecectorserenssorensseecers 71 10 3 Senvice Log A OO 72 104 Servico Hotline eiii iaer ain E aae aaa a a a aaie Daah ina Ea pE en aioi 73 10 5 Maintenance and service contracts oooooncinncccnnnoncconananananoncn nana n cnn