Home

Metasys® System Extended Architecture Overview Technical Bulletin

image

Contents

1. 13 Alarm and Event WMAMAQGSING HU siasSicctetinatsmstatmtiundsantaanddiaradeeiGaetnetsbiedddtetiatitiiuacalabinlaaneidneniaa elds 13 557610112101 1000 E ener mee Hee ere enor Ber he PR ren eee E Parr DOLENS 14 Historical Data Management Trend 2 22 c ccceeseeceeetceeeee ceeeeseeneceetae cenneseaaeeeeeeeeesenseenseeetenseeensennes 14 Export Utility SONWALE ieira CM 14 Metasys Advanced Reporting Sysbelti is iemaacipesshuisa ata pete cuta ae ah de ttsaas er tub seertoceteneannadecsmmeceublignsss 14 Energy Essentials Asarnie eni Pain Dues nte ua desst apices bia iude x sess e Maul rac addet ee bites uaa adt lau ced ede 15 User Graphics8 iisecee ener nere kx ve D C C X ER YR KE RR X c FP E X v a i 15 Advanced Graphics Application Software s sssessssssssssssssesee nennen nnn nns 15 Graphic Generation Tool seesessssssssssessseseene nere enne nenne en nnn nennen ense nennen nnn sn nenne enne nsn nens 15 System SECUN PRO sea odesasenes auaiendatestatc 15 MS TP Communications zu 15 N2 Rield BUS ioo E URINE E DE UU EN 16 Bani mE 7e r 16 ull inizio rz ios etr TERT RRDNERUS 16 P2000 Security Management System Integration esee een 16 Wels om Connector Tool CIR ronroni n aA EEE E EEA TEETE AAEE 16 Interlocking Programs EVE doa ctctind disci ania ptuachicdch pente pna aa b
2. accessing data for example Site Director Maximum number of simultaneous Site Management Portal users per NAE45 NAE35 NCE25 Maximum number of simultaneous Site Management Portal users per NAE55 NIE55 before ADS as Site Director is required 4 Includes browsers or other devices accessing data for example Site Director Maximum number of simultaneous Site 1 Includes browsers or other devices Management Portal users per accessing data for example Site NAE85 NIE85 Director Maximum number of simultaneous Site Management Portal users per ADS Maximum number of connections per ADX 10 to 25 ADX has two versions with 10 and 25 connections maximum Maximum number of simultaneous Mix of online SCT simulation browsers per client computer Maximum number of users per Site gt Limited only by the number of users Director Metasys System Extended Architecture Overview Technical Bulletin 30 3 2 5 2 Table 3 Performance Guidelines and Limitations Maximum number of user views per Site Limited only by memory capacity Director or NAE NIE Maximum number of nesting levels for 7 item object creation Maximum number of extensions per object 10 Includes Metasys Alarm Totalization Trend Averaging and Load Does not include BACnet Intrinsic Alarm Maximum number of dynamic values per 100 graphic Maximum number of characters in the 4 Readable display up to 40 before name of an item object tru
3. IP Ethernet BACnet Communication Network Y Y Y mE m w N30 N30 BACnet BACnet Bus D Third Party Third Party Device Device Site Management FC Portal or Ready BACnet MS TP Access Portal Client Bus Metasys System Extended Architecture Overview Technical Bulletin 25 Smoke Control Application Configuration Figure 11 shows a configuration that complies with the UL 864 UUKL Ninth Edition listing incorporating smoke control and non smoke control systems Figure 11 is only an example the number and arrangement of components in your system may differ Ensure that your system complies with all device and communication requirements and restrictions Figure 11 Metasys System Extended Architecture UL864 UUKL Ninth Edition Smoke Control System Existing Building Network Ethernet Site Management Computer Portal UI g z l oe M l Sy aban EENEN EREE n US INS Smoke Control Asante Switch 1 HERD Ethernet _ icm N Smoke Control Ethernet 77 S Asante Switch 2 5 Port ERE Sw UPC CoD a ii Ethernet 100 Mbps to Fiber NAE Fiber Media Converter Fiber to 100 Mbps Ethernet 100 Mbps 100 Mbps MultiState or Life Safety BACnet Gateway Seo Ethernet Ak Crossover Cable Smoke Control FiberOptic Switch Smoke Control to Field Asante Switch x N 5 Port SW FC 1 5 Port LONWoRKS sw p Smoke Con
4. This configuration supports up to four simultaneous users Note The Site Director must contain the modem for a dial up site Note This configuration only provides long term storage of data through the use of the Export Utility installed on a computer Note The NAE45 Lite can be partnered with only other NAE45 Lite devices Additionally the NAE45 Lite requires an ADS Lite A Site Director Figure 4 Multiple NAE System Configuration with One NAE Designated as the Site Director Site Management Portal Site Management Portal Site Management Portal Client Client Client on a Laptop rm J Em pL Internet og Ethernet IP Network Site Director Inputs Outputs BACnet Inputs Outputs MS TP FIG msea tech overview stedir LONWORKS Chiller Plant Air Handler Metasys System Extended Architecture Overview Technical Bulletin 20 Ready Access Portal Configuration The Ready Access Portal software provides a natural complementary extension of the Metasys Site Management Portal Ul The Ready Access Portal configuration includes a computer running the Ready Access Portal software a Metasys Site Director and a computer and or handheld device for browsing to the Ready Access Portal UI The example configuration in Figure 5 shows a configuration with the Ready Access Portal Software installed on an ADS ADS Site Director with Multiple NAEs System Configuration Sites that require more than four simultaneou
5. and any other software or service packs required for your ADS Lite configuration Recommended Memory 2 GB RAM minimum Supported Operating Microsoft amp Windows 7 OS Professional Enterprise and Ultimate Editions 32 bit with SP1 2 Systems and Database includes Microsoft IIS Version 7 5 Software Supports Microsoft SQL Server 2008 Express R2 software SQL Server 2008 Express software with SP2 or SQL Server 2005 Express software with SP3 Microsoft Windows XP OS Professional Edition 32 bit with SP3 Includes Microsoft IIS Version 5 1 Supports Microsoft SQL Server 2008 Express R2 software or SQL Server 2008 Express software with SP2 or SQL Server 2005 Express software with SP3 Required Web Browser Microsoft Internet Explorer amp Version 6 x 7 0 or 8 0 Software for Metasys Client Computers Java Runtime Environment JRE 1 6 0 23 Note When browsing to the UI of a Metasys system device the OS on the client computer must be supported by the Metasys release loaded on the device You may be unable to browse to Metasys system devices if the client OS is not supported See Computer Requirements for Site Management Portal Client Computer for more information Network Communication Ethernet network interface card 10 100 1000 Mbps 100 Mbps or better recommended Additional Software CCT software Er ADS Export Utility software Metasys Database Manager software Microsoft NET Framework Version 3 5 1 Microsoft SQ
6. American National NAE NCE Protocol Implementation LIT 1201532 Standards Institute ANSI American Conformance Statement Technical Bulletin Society of Heating Refrigerating and Air Conditioning Engineers ASHRAE Standard 135 2004 BACnet Protocol NIE Compliance with ANSI ASHRAE NIE Series Protocol Implementation LIT 1201672 Standard 135 2004 BACnet Protocol Conformance Statement Technical Bulletin How to Install and Use the Metasys Metasys System Extended Architecture LIT 1201691 System Remote Access Application for Remote Access Technical Bulletin Dial Up Connections to Shorten the UI Access Time How to Use Web Service Technology for Metasys System Extended Architecture LIT 1201663 Secure Access to the Metasys System Secure Data Access DLL Technical Extended Architecture Bulletin How to Create and Modify Users and Security Administrator System Technical LIT 1201528 Roles Configure User Profiles Assign Bulletin System Access Permissions Assign All Items Navigation View Permissions and Unlock User Accounts How to Set Up an MS TP Communications MS TP Communications Bus Technical LIT 12011034 Bus Bulletin How to Set Up an NAE as a BACnet IP or BACnet Controller Integration with LIT 1201531 BACnet MS TP System Integrator in a NAE NCE Technical Bulletin Metasys Network How to Set Up an NAE or LCS85 as a LoNWonks Network Integration with NAE LIT 1201668 LonWorks Network Integrator and LCS Technical Bulletin Dir
7. BBMDs Metasys System Extended Architecture Overview Technical Bulletin 22 N1 Integration System Configuration The NIE NIE55 and NIE85 provides a means of migrating your existing Metasys N1 network to the Metasys system Figure 7 N1 Integration with NIE85 Engineering Workstation ADS ADX OWS legacy JR IP Ethernet N1 Communication o p _ lt FIG msea tech overview NIE85 NI Site Management Portal or Ready Access Portal N2 N2 Metasys System Extended Architecture Overview Technical Bulletin 23 Multi Location Configuration Remote sites may be single or multiple NAE configurations with or without a local ADS ADX The remote site may also be a Metasys N1 installation with one or more NIEs to integrate the site into the Metasys system The operations center for the multiple sites would normally have an ADS connected to the enterprise IP network and be part of the Virtual Private Network VPN for access to the sites that are linked by a WAN It would also have modems to receive messages from small sites that only have telephone line access The application server receives and displays alarm and event messages to the operators and records their response actions The server retrieves and stores all operational data from the remote buildings for review by management personnel Enterprise business systems can access the data for further analysis The building where the Operations Center is locate
8. Metasys system engines and servers but is the primary mode of access for stand alone NAE3514 NAE3515 NAE3524 and NAE3525 models Microsoft Active Directory accounts can be used with the Site Management Portal and Ready Access Portal In addition to making it easier for system administrators to manage Metasys account access this feature also provides the ability to use Single Sign On to access Metasys together with other supported applications on the enterprise network All user activities are recorded in the Audit Log which allows the System Administrator to monitor user actions MS TP Communications Bus The MS TP Bus is a local network that connects some NAE NCEs and field controllers using BACnet MS TP protocol Two tiers of MS TP Buses exist in the Metasys system architecture The Field Controller Bus FC Bus consists of BACnet controllers and point interfaces supervised by an NAE NCE The Sensor Actuator SA Bus consists of point interfaces and networked sensors supervised by a field controller Metasys System Extended Architecture Overview Technical Bulletin 15 N2 Field Bus The N2 Field Bus is a local network that links controllers and point interfaces to some NAE NCE The N2 Bus uses a master slave protocol in which the master device the NAE NCE initiates the communication with the N2 Bus devices LonWorks Devices The LonWorks network links LonWorks devices to some NAE NCE The NAE acts as a supervisory controller and com
9. OS settings that may be required for your Metasys system configuration 9 You must purchase a SQL Server software license for each individual processor you have You do not need to purchase multiple licenses if you have a single processor divided into multiple cores For example if you have a single processor with dual cores purchase one license for SQL Server software Metasys System Extended Architecture Overview Technical Bulletin 38 SCT System Requirements Table 10 describes the recommended and minimum computer requirements for a computer on which you are installing a stand alone SCT Table 10 System Configuration Tool System Requirements Recommended Intel Core 2 Duo E6700 or better Intel Core 2 Duo E4300 minimum Computer Server Platform 20 GB free hard disk space available 600 MB minimum DVD drive Recommended Computer Platforms 2 GB RAM 1 GB RAM minimum Server Platforms 4 GB RAM 2 GB RAM minimum Supported Operating Microsoft Windows 7 OS Professional Enterprise and Ultimate Editions 32 bit with SP1 Systems and Database Software Includes Microsoft IIS Version 7 5 Supports SQL Server 2008 R2 Express software SQL Server 2008 Express software with SP2 or Microsoft SQL Server 2005 Express software with SP3 Microsoft Windows XP OS Professional Edition 32 bit with SP3 Includes Microsoft IIS Version 5 1 Supports SQL Server 2008 R2 Express software SQL Server 2008 Express softwar
10. Recommended Processor 2 8 GHz or higher Pentium 4 processor 2 0 GHz Pentium 4 processor minimum Recommended Random Access Memory RAM 1 GB 256 MB minimum Hard Disk Capacity 40 GB hard disk minimum Supported Operating System Microsoft amp Windows 7 OS 32 bit with SP1 Microsoft Windows XP OS 32 bit Required Web Browser Software for Metasys Client Computers Microsoft Internet Explorer Version 6 x 7 0 or 8 0 1 6 Java Runtime Environment JRE 1 6 0 23 1024 x 768 or higher resolution and 16 bit or higher color depth 1 Our computer platform and memory recommendations are not meant to imply that older or slower machines are not usable Refer to the Network and IT Guidance for the BAS Professional Technical Bulletin LIT 12011279 for more information regarding computer server recommendations A graphics intensive user may experience better performance with additional RAM Table 5 Site Management Portal Laptop Client Computer Requirements Recommended Processor 1 8 GHz or higher Pentium 4 processor 800 MHz Pentium 4 processor minimum Recommended Random Access Memory RAM 1 GB 256 MB minimum Hard Disk Capacity 40 GB hard disk minimum Supported Operating System Microsoft Windows 7 OS 32 bit with SP1 Microsoft Windows XP OS 32 bit Required Web Browser Software for Metasys Client Computers Microsoft Internet Explorer Version 6 x 7 0 or 8 0 Java Runtime Environment JRE 1 6 0_23 3 Ou
11. event history The Metasys system allows alarms and events to be configured using either a Metasys alarm extension or a BACnet alarm intrinsic or algorithmic Metasys alarm extensions generally provide more feature capability and ease of setup whereas the BACnet alarms provide better interoperability with other BACnet systems Note An eventis a notification of a status change in the Metasys system An alarm occurs when a value defined in an engine goes outside of a user defined range changes to a user defined contact condition or fails to respond to a command within a user specified time When an alarm occurs an event is generated Events can be generated by any Metasys platform For example if the NAE detects that a network node is offline it can generate an event If an error occurs in the server platform an event can also be generated Once an event is generated it is stored in an Event Repository file located on the device that generated the event You can retrieve and examine events stored in the Event Repository Destination Delivery Agents DDA DDAs are the method used for routing and delivering Metasys alarm extension event messages to destinations such as pagers printers e mail and Network Management systems The Metasys system uses an e mail DDA Pager DDA Printer DDA and Simple Network Management Protocol SNMP DDA The e mail DDA supports standard Simple Mail Transfer Protocol SMTP Post Office Protocol POP and Interne
12. restore the network database offline is installed on a separate computer in split configuration The Metasys Advanced Reporting System is also available in a split configuration if the SQL Server database components are installed on the Database server and the SQL Server Reporting Services are installed on the Web Application server In a split configuration you can place your database server behind a firewall for an added layer of data protection NAE The NAE is a Web enabled Ethernet based supervisory controller that monitors and supervises networks of field level building automation devices that typically control Heating Ventilating and Air Conditioning HVAC equipment lighting security fire and building access The NAE provides features including alarm and event management trending archiving energy management scheduling and password protection through its embedded Site Management Portal UI Different models and options support various communications protocols including BACnet over Internet Protocol IP BACnet amp Master Slave Token Passing MS TP N2 Bus N2 over Ethernet and LonWorks protocol The following models are available The NAE55 Series supports a comprehensive set of supervisory features and functions for large facilities and technically advanced buildings and complexes The NAE35 and NAE45 Series extend the power of the NAE to the smaller buildings or small areas of larger buildings and enable the wider distri
13. the maximum number is 10 engines servers With 1 concurrent connection the maximum number is 14 engines servers Maximum number of engines on a site with 5 ADS Lite E supports up to 5 of the an ADS Lite E Site Director following engines NAE35 NAE45 Maximum number of engines on a site with 4 ADS Lite A supports up to 3 NAE Lites an ADS Lite A Site Director Maximum number of engines on a site with 500 to 1000 Depends on computer hardware see an ADX Site Director Large ADX Site Configuration plus up to 1 NIE NIE29 39 49 Maximum number of engines on a site If an NxE55 or NxE85 is the Site Director supported by an NxE55 NxE85 as Site it can supervise up to three additional Director supervisory devices on the site NAE35s NAE45s excluding NAE45 Lite or NxE55s or NxE85s Maximum number of engines on a site supported by an LCS85 as Site Director With an LCS85 as a Site Director Maximum number of engines on a site If an NAE45 is the Site Director it can supported by an NAE35 NAE45 as Site supervise up to two additional supervisory Director devices on the site NAE45s NAE35s or NCE25s excluding NAE45 Lite If an NAE35 is the Site Director it can supervise up to two additional NAE35s or NCE25s on the site The NAE45 Lite cannot be a Site Director 0 Maximum number of engines on a site An NCE25 can only act as the Site Director for itself supported by an NCE25 as Site Director Includes browsers or other devices
14. 250 Add ADS ADX for more each NAE45 NAE35 NCE25 Maximum number of alarms events f Supports one daily burst of 25 000 received by ADX per hour alarms events in one hour This number applies to alarms events originating from devices at Release 5 2 or later Maximum number of alarms events Within a 24 hour period This number received by ADX per day applies to alarms events originating from devices at Release 5 2 or later Maximum number of trend samples 22 500 for ADS This number applies to trends originating received by ADS ADX per hour from devices at Release 5 0 or later 100 000 for ADX Supports one daily burst of 300 000 trends in one hour This number applies to trends originating from devices at Release 5 0 or later Maximum number of trend samples 540 000 for ADS Within a 24 hour period for samples received by ADS ADX per day originating from devices at Release 5 0 or later 2 600 000 for ADX Within a 24 hour period for samples originating from devices at Release 5 0 or later Metasys System Extended Architecture Overview Technical Bulletin 29 Table 3 Performance Guidelines and Limitations Maximum number of trend samples per 8 000 000 This is a hard limit in the NxE85 and NAE85 NIE85 cannot be exceeded Maximum number of engines servers on 10 to 14 Varies with the number of concurrent a site with an ADS Site Director connections users devices browsing to the system For example with 5 concurrent connections
15. Director with SCT Access Portal Client Or Ready Access Portal Clients Site Management Portal and Site Management Portal Ready Access Portal Software or Ready Access Portal Client l X m Hm BO d Lapop 27 Wes Computer 72 7 Desktop s Wireless Computer Access Point IP Ethemet i c P ja L Vd WRZ EE AU VMA TE 7800 Sensor One to one Receiver 1 wrz Sensor 7 ZFR1810 Coordinator 4 n Mu FEC Router AN ensor T cg ut m UN N i n VMA16 TEC Coordinator Metasys System Extended Architecture Overview Technical Bulletin 27 Performance Guidelines and Limitations Table 3 describes performance guidelines and limitations of the Metasys system extended architecture Table 3 Performance Guidelines and Limitations NAENIE NCEADS ADX Bereit 500 to 1 000 ADX depends on computer hardware see Large ADX Site Configuration Maximum number of Metasys only Metasys MS TP devices include FECs MS TP Devices on an FC Bus on an VMAs and IOMs NAE55 NAE45 or NAE45 Lite Maximum number of Metasys and or third party MS TP devices that can be connected to an FC Bus on an NAE45 or NAE55 when one or more TEC26 Thermostat Controller variable speed drive or third party MS TP device is connected to the FC bus Maximum number of Metasys MS TP Metasys MS TP devices include FECs devices on an FC Bus on an NAE35 VMAs and IOMs Performance varies based on mix N2 O
16. Generation Tool Help LIT 12011697 Metasys System Extended Architecture Overview Technical Bulletin 3 Table 1 Related Documentation For Information On LIT or Part Number How to Configure an ADS ADX to be Site ADS ADX Commissioning Guide LIT 1201645 Director Use ADS Repositories Synchronize Time Use a Network Printer Accept Dial Up Connections and More How to Apply Mount Wire Set Up and NAE35 NAE45 Installation Instructions Part No 24 10050 6 Start the NAE35 and the NAE45 Including Technical Specifications and Ordering Information How to Apply Mount Wire Set Up and NAE55 NIES55 Installation Instructions Part No 24 10051 0 Start the NAE55 and NIE55 Including Technical Specifications and Ordering Information How to Apply Mount Wire Set Up and NCE25 Installation Instructions Part No 24 10143 63 Start the NCE25 Including Technical Specifications and Ordering Information How to Set Up an NAE35 NAE45 and NAE Commissioning Guide LIT 1201519 NAE55 for Network Connectivity and Access the NAE User Interface to Set the Basic Parameters How to Set Up an NAE85 NIE85 for NxE85 Commissioning Guide LIT 12011044 Network Connectivity and Access the NAE85 User Interface to Set the Basic NAE85 Parameters How to Set Up a LonWorks Control LCS85 Commissioning Guide LIT 12011568 Server LCS 85 for Operation on the Metasys Network How to Use the SCT Including Setting Up SCT Technical Bullet
17. L Server 2008 Express R2 software Microsoft SQL Server 2008 Express software with SP2 Microsoft SQL Server 2005 Express software with SP3 Ready Access Portal software SCT software SCT Manager software Optional Hardware Any network or local printer supported by the qualified Windows operating system Metasys System Extended Architecture Overview Technical Bulletin 35 1 Our computer platform and memory recommendations are not meant to imply that older or slower machines are not usable Refer to the Network and IT Guidance for the BAS Professional Technical Bulletin LIT 12011279 for more information regarding computer server recommendations 2 Refer to the Network and IT Guidance for the BAS Professional Technical Bulletin LIT 1201279 for specific Microsoft Windows OS settings that may be required for your Metasys system configuration ADX System Requirements Table 8 describes the recommended and minimum computer requirements for the computer on which you are installing a unified ADX Table 9 describes the recommended and minimum computer requirements for the computers on which you are installing a split ADX Table 8 Extended Application and Data Server System Requirements Unified ADX Systems MS ADX10SQL 0 New ADX project software for up to 10 concurrent users MS ADXSWOSQL 0 New ADX project software for up to 25 concurrent users Recommended Server 2 8 GHz Pentium 4 processor with 160 GB hard disk Platform 2 0 GHz Pentium 4
18. Metasys System Extended Architecture Overview Technical Bulletin Code No LIT 1201527 Software Release 5 2 Issued May 13 2011 Supersedes October 4 2010 Refer to the QuickLIT Web site for the most up to date version of this document Bhietnrindainiete me 3 eiui Me 3 Metasys System Extended Architecture cessent 7 Metasys System Extended Architecture Components eeeeeeeeeeseeeeeeeeeeeeeeee 9 B CEPI COE e t eme 9 ADX T H 9 Ll HM T CT D 10 NGE 11 NIE en I UR I EUMD IE UEM M EEUU LEE EN d 11 Ee v s 11 s n A 11 ee 11 Metasys Database Manage MM rts 12 Lamia evo Ao aia aaao eta ia RAAE aAa 12 Metasys System Capabilities xciaciccaccacaeinuniecdenascuiandecandasansdvencdoeaexnenstdauasieunineacesauadudeniniaeuuiciudodacaundense 12 SMS DPS RU E iE 12 MUTT INA a oem e ES 12 wr UN Ucar secre OR 13 Monitoring and COMINMANNOING ccccticcsdsastdatectnceesxedenttece E ES 13 PYG ENCES e
19. NIE55 NIE59 NCE25 on Windows 7 OS Windows XP Windows Server 2008 R2 OS Windows Server 2008 OS or Windows Server 2003 OS NAE85 NIE85 on Windows Web Server 2008 R2 OS Windows Web Server 2008 OS or Windows Server 2003 Web Edition OS ADX 10 on Windows Server 2008 R2 OS Windows Server 2008 OS or Windows Server 2003 OS ADX 25 on Windows Server 2008 R2 OS Windows Server 2008 OS or Windows Server 2003 OS or on Windows 7 OS or Windows XP Maximum number of load extensions Limited only by memory capacity If you used for DLLR plan to attach a large number of load extensions to a single DLLR object consider the memory limitation For load extensions attached to one DLLR object there is a 64 KB text limit for the list of the Loads fully qualified references Load Limit 64 x 1024 average number of characters per load Note 1024 Bytes equals 1 KB For example if your DLLR object is configured with Loads that have fully qualified references that average 100 characters including dots in length then you can Maximum number of concurrent users on the Ready Access Portal UI where the software is installed on a Site Director ADS ADX support approximately 650 loads 64 x 1024 100 for that DLLR If you reach the memory limit you may need to combine loads For example if a site has multiple physical meters split the meters across multiple controllers and apply appropriate DLLR loads if possible Otherwise
20. Ready Access Portal software SCT software SCT Manager software Optional Hardware Any network or local printer supported by the qualified Windows operating system 1 Our computer platform and memory recommendations are not meant to imply that older or slower machines are not usable Refer to the Network and IT Guidance for the BAS Professional Technical Bulletin LIT 12011279 for more information regarding computer server recommendations Metasys System Extended Architecture Overview Technical Bulletin 34 2 Refer to the Network and IT Guidance for the BAS Professional Technical Bulletin LIT 1201279 for specific Microsoft Windows OS settings that may be required for your Metasys system configuration ADS Lite System Requirements Table 7 describes the recommended and mimum computer requirements for the computer on which you are installing an ADS Lite Table 7 Application and Data Server Lite System Requirements Product Code MS ADSLESU 0 New ADS Lite E project software for up to 5 concurrent users MS ADSLASU 0 New ADS Lite A project software for up to 5 concurrent users Recommended 2 8 GHz Pentium 4 processor with 80 GB hard disk Computer Platform 2 0 GHz Pentium 4 processor with 40 GB hard disk minimum 20 GB free space on the hard disk after installing all prerequisite software and before installing the ADS Lite software DVD drive Note Prerequisite software includes the supported OS database software NET Framework
21. Site Management Portal Ul or more recent historical data can be displayed as a graph or table on the Ready Access Portal Ul Trend data can also be copied to the browser computer s clipboard allowing the data to be transferred to spreadsheets databases and Microsoft Word documents Using the Site Management Portal Ul multiple point trends can be shown on a single graph or table making it easier to detect system level performance These multiple trends can either be predefined in a Trend Study or the user can dynamically select various point trends to display on a single graph using the Trend Viewer The Site Management Portal UI also offers information on the rate of events rate of samples and number of samples that are lost Refer to the Metasys system Help LIT 1201793 Export Utility Software The Export Utility software provides facility managers with the ability to easily build custom reports using historical data from the Metasys system This data can be used to manage daily building operations Export Utility software extracts historical trends alarms and audit data from an engine or server This data can be collected from the system and stored in up to six different formats desired by the operator for analysis including Microsoft Word or Microsoft Excel A scheduling feature is also provided to retrieve and save data based upon user configurable time intervals The Export Utility provides the user with the ability to create runtime stu
22. abet risbA irc uisus ktadkiaeneplautonamiaalds 16 Optimal Stan soe ss ccakoss vestre quere te nia Fo Fe Le EXN SERE a este svaceheatedievaads ea e 17 Demand Limiting and Load Foll te eina PE Era Run RR XR Han R ERAT cu ER ERRR M Y Un ICE EDAR ERA E MRSDEE 17 Audit Trails Transaction Data Managemenn 222 cccccesesssssecceeeeeeesessceceeeneeeeesessenenseseeenenestennenees 17 System Diagnostics and ServiBgabiliy ssiusencuutio cocido ausucu smipkbuti asa usc cp basis bcp Ran v tram dede eth ok Aaa 17 UL 864 UUKL Ninth Edition Smoke Control Listing and Fire Panel Integration 17 Metasys for Validated Environmeaents ieeeeeisiieeeeeeeee eene annee nn tnhnnhu nk nu inna memes ka ka aa si nnnc 18 Metasys System Extended Architecture Overview Technical Bulletin 1 Johnson Y Controls Metasys System Configuration Examples cesses enne nennen nennt 19 Single NAE System COPfIQUE Sors outs ria so ostoct usa eadeni aptae tla JAEN NAKKEN aAA tnatidber te Senais 19 Multiple NAE System Configuration with One NAE Designated as the Site Director 20 Ready Access Portal Config ration eiie ro ener intet Re peer Re ORE Dra E RRIA RE EORCEREQRR eaten 21 ADS Site Director with Multiple NAEs System Configuration eseeee 21 ADX Split GonltgurdatOr sspe na ed ate toes petente P EI eeu Oise n udi ertet qum 22 Large ADA Si
23. ance and other areas UL 864 UUKL Ninth Edition Smoke Control Listing and Fire Panel Integration Components of the Metasys system running Release 4 1 software are Underwriter Laboratories UL 864 UUKL Ninth Edition listed for smoke control In applications requiring smoke control this offering provides the protection of a UL 864 UUKL listed smoke control system that has a lower installed cost and leverages the operational efficiencies of using a single system to provide HVAC and Fire Alarm smoke control Earlier versions of the Metasys system also support UL 864 UUKL Eighth Edition Eighth Edition and Ninth Edition hardware must be isolated from each other via an Ethernet switch to coexist in a building The Metasys Smoke Control System consists of a set of hardware components specifically UL Listed for smoke control applications and a smoke control application running in an NAE specifically UL Listed for UL 864 UUKL Ninth Edition smoke control The smoke control offering provides a configurable yet straightforward application for receiving fire alarm and smoke control inputs from various systems and allows for the automatic triggering of smoke control schemes The system also enables a designated operator to execute real time control from an annunciator panel the Automation Displays Incorporated ADI UL Listed Firefighter s Smoke Control Station FSCS or its primary user interface based on the specific dynamics of a fire smoke control event i
24. bution of supervisory functions in larger facilities Metasys System Extended Architecture Overview Technical Bulletin 10 The NAE45 Lite available only in specific markets is a functionally limited NAE45 that cannot be used as a Site Director and functions only with a corresponding ADS Lite The NAE85 supports large BACnet IP integrations NCE The NCE combines the network supervisor capabilities and IP network connectivity of an NAE with the Input Output I O point connectivity and direct digital control capabilities of a Metasys Field Equipment Controller FEC The NCE provides a cost effective solution designed for central plants and large built up air handler applications All NCE models provide IP Ethernet network connectivity the Site Management Portal Ul and the network supervisory functions featured on network automation engines including the BACnet IP integration Depending on the model an NCE supports either a BACnet MS TP trunk an N2 Bus trunk or a LonWorks network trunk NIE The NIE is a Web enabled supervisory controller for integration of Metasys N1 networks The NIE is a specialized version of the NAE and is designed to provide for the migration of existing N1 networks into the Metasys system extended architecture The NIE provides the same Site Management Portal UI as the NAE Unlike the NAE the NIE does not support integration of BACnet MS TP or BACnet IP N2 or LonWorks networks Two models of the NIE are availab
25. d 10 100 Mbps 100 Mbps network recommended Additional Software Microsoft NET Framework Version 3 5 with SP1 A o SOPE iS System Configuration Tool SCT software for Ethernet Passthru Disks Note You must install CCT on the same computer as the SCT software to use the Ethernet Passthru option in SCT otherwise CCT may run on a stand alone computer Additional Requirements Wireless Commissioning Converter MS BTCVT 1 Order Separately Laptop with Bluetooth wireless communications or a computer with a Universal Serial Bus USB Bluetooth converter Universal Serial Bus USB Dongle with ZigBee Driver IA OEM DAUB1 2400 provides a wireless connection through the CCT to allow wireless commissioning of the wirelessly enabled FEC and VMA16 field controllers Also allows use of the ZCT in CCT Adobe Acrobat Reader Note Adobe Acrobat Reader is required for the Print function in CCT Optional Hardware Any network or local printer supported by the qualified Windows operating system 1 Our computer platform and memory recommendations are not meant to imply that older or slower machines are not usable Refer to the Network and IT Guidance for the BAS Professional Technical Bulletin LIT 12011279 for more information regarding computer server recommendations Metasys System Extended Architecture Overview Technical Bulletin 40 NxE85 System Requirements Table 12 describes the recommended and minimum computer requirements for a co
26. d may have its own BAS with a single or multiple NAEs Figure 8 Multi Location Configuration Site Management Portal Enterprise Operations or Ready Access Portal UI System Center Remote ADS Site Management Portal or Ready Access Portal UI 7 NAE55 NAE55 IP Ethernet g NAE45 gt MS TP Bus MS TP Bus 3 N2 Bus LONWORKS N2 Bus LONWORKS MS TP Bus Network MS TP Bus Network Metasys System Extended Architecture Overview Technical Bulletin 24 BACnet IP Network System Configuration BACnet IP devices are connected directly to the IP Ethernet network The NAE NCE communicates with the devices using the BACnet protocol and presents the BACnet data to the system in the same way as the other data in the Metasys system Figure 9 shows the N30 supervisory controller integrated into the Metasys network Other BACnet IP devices are integrated in the same way Figure 9 BACnet IP Network Integration System Configuration ADS with SCT Site Management Portal and Ready Access Portal Site Management Portal or Ready Access Portal JR Client Printer 8 5 c IP Ethernet BACnet Communication Third Party ER BACnet Device TEC Third Party N2 BACnet Device FIG msea tech overview bnet int The NAE85 allows integration of larger BACnet integration projects Figure 10 NAE85 BACnet Integration ADS ADX Printer z BACnet i Workstation g NAE85 7 m i 3 3 p
27. d statements and False command statements Through these statements the user specifies a set of conditional checks using one or more points for which a series of commands is used to control a collection of one or more other objects Metasys System Extended Architecture Overview Technical Bulletin 16 Optimal Start Optimal Start automatically determines the correct time to start HVAC systems to ensure the facility is ready for occupants at the scheduled time It adjusts to seasonal variations and minimizes the energy used The generic standard object screens handle the Optimal Start Stop object configuration and focus views The object defines views for configuration and focus and the generic screens interpret the views to display the proper fields to the user No custom screens or handlers are needed Demand Limiting and Load Rolling The Demand Limiting DL feature reduces utility bills by limiting peak energy usage DL electively turns off sheds equipment such as fans and lights or adjusts setpoints to limit energy use during peak times The Load Rolling LR feature helps save money by reducing overall energy consumption LR acts continuously to maintain a specified energy reduction by shedding unnecessary loads A facility can implement either one or both of these features Audit Trails Transaction Data Management The Audit Trail feature records events generated either by user actions or system activity Examples of user actions i
28. dies and discover root cause analysis of system changes and mechanical equipment failures You can also use it to collect trended runtime data for use by a Computerized Maintenance Management System CMMS to schedule mechanical maintenance of HVAC systems Metasys Advanced Reporting System The Metasys Advanced Reporting System is a standard capability for all ADXs when using SQL Server 2008 R2 software SQL Server 2008 software or SQL Server 2005 software with SQL Server Reporting Services SSRS installed The Web based reporting interface provides standard report sets to allow users to review the alarm and trend configuration of their site run summary and detail reports to monitor alarm and event information view offline information combine alarm and audit information in a single report and provide summary and detailed trend aggregations The report information is filtered by the site s All Items or User View navigation tree Users can customize the date range and data type desired for each report Once a report is created in the user interface the option to export the data into common applications such as Microsoft Excel spreadsheet or Adobe PDF formats is available Metasys System Extended Architecture Overview Technical Bulletin 14 Energy Essentials Energy Essentials is an optional software feature that can be added to the Metasys Advanced Reporting System It offers seven types of energy reports that provide a high level view of normal
29. e Metasys Database Manager provides both database management and database monitoring functions handled in two separate windows Database management includes summarized information on and methods for backing up purging and restoring Metasys system ADS ADX trend alarm event and audit databases Monitoring includes an indication of database status compared to three levels of defined database sizes Wireless Solutions Several wireless Metasys solutions are available for integrating wireless connectivity in desired portions of a Metasys network These solutions provide wireless communication between controllers thermostat controllers coordinators routers and room sensors e ZFR1800 Series Wireless Field Bus System TEC Wireless Thermostat Controller System e WRS Series Many to One Wireless Room Temperature Sensing System e TE 7800 Series One to One Wireless Room Temperature Sensing System e WRZ 7850 One to One Wireless Room Temperature Sensing System These wireless solutions reduce costs by minimizing wiring provide application mobility and flexibility and simplify the challenges of difficult or cost prohibitive installations or renovations The wireless solutions can coexist with each other and offer the flexibility of coexisting with hard wired Metasys solutions Metasys System Capabilities Site Director When a user accesses any engine or server directly through a Web browser only the information local to that device is access
30. e SCT supports commissioning of N2 devices by allowing HVAC PRO software GX Tool software and XTM Configurator software to access the devices on the N2 Bus of an engine The SCT also supports commissioning of FECs by using Controller Configuration Tool CCT software to access the devices on the Field Bus of an engine The SCT Manager is a software tool that allows you to use multiple versions of SCT on your computer This tool is useful when supporting different Metasys sites that have different revisions of installed Metasys software or a single site that has multiple engines at different software revisions CCT The Controller Configuration Tool CCT is used in conjunction with the Metasys system extended architecture user interface to configure simulate and commission FECs Input Output Modules IOMs NCEs Variable Air Volume VAV Modular Assembly VMA 16s and DIS1710 Local Controller Displays on a BACnet MS TP Bus You must install CCT on the same computer as SCT software to use the Ethernet Passthru option in SCT The CCT includes the ZFR Checkout Tool ZCT The ZCT allows you to validate the wireless connectivity and health of wireless devices within a ZFR1800 Series Wireless Field Bus System to help ensure a reliable wireless mesh network is in place The CCT is a separate software installation included on the SCT product disk Metasys System Extended Architecture Overview Technical Bulletin 11 Metasys Database Manager Th
31. e time and date consistently for all system operations Because the Site Director is the master time keeper for all engines and servers on a single site all of these devices are assumed to use the same time zone for all time rated functions For network wide time synchronization the engine or server acting as Site Director is the time server for the entire site All other devices are time clients because they receive the time from the Site Director The Site Director can be configured to use three different methods of time synchronization Unicast Simple Network Time Protocol SNTP also known as Microsoft Windows time synch Multicast SNTP or BACnet time synch The Site Director can also be configured to synch its time from an external Web site Metasys System Extended Architecture Overview Technical Bulletin 12 System Navigation Users can create customized system navigation schemes in the form of User Views a hierarchical method of organizing and displaying some or all of the items within a system A Metasys system administrator can limit a user s access to the Metasys system by creating User Views and assigning them to specific users User views provide organizational structure and data filtering for the information displayed in the Metasys Advanced Reporting System UI and the Ready Access Portal Ul Monitoring and Commanding Monitoring and commanding allows you to efficiently navigate through items associated with your building operati
32. e with SP2 or Microsoft SQL Server 2005 Express software with SP3 Microsoft Windows Server 2008 R2 OS 64 bit Includes Microsoft IIS Version 7 5 Supports Microsoft SQL Server 2008 R2 Standard and Enterprise software 64 bit Microsoft Windows Server 2008 OS 32 bit with SP2 Includes Microsoft IIS Version 7 0 Supports Microsoft SQL Server 2008 R2 Standard and Enterprise software 32 bit or SQL Server 2008 Standard and Enterprise software with SP2 or SQL Server 2005 Standard and Enterprise software with SP3 Microsoft Windows Server 2003 R2 OS 32 bit with SP2 Includes Microsoft IIS Version 6 0 Supports Microsoft SQL Server 2008 R2 Standard and Enterprise software 32 bit or SQL Server 2008 Standard and Enterprise software with SP2 or SQL Server 2005 Standard and Enterprise software with SP3 Required Web Browser Microsoft Internet Explorer Version 6 x 7 0 or 8 0 Software for Metasys i Client Computers Java Runtime Environment JRE 1 6 0 23 Network Ethernet network interface card 10 100 Mbps 100 Mbps network recommended Communication Additional Software Controller Configuration Tool CCT software C Tools software SCT Manager software Included on the SCT Product Disks Optional Software The ADS and ADX software packages include the SCT software Packaging 1 Our computer platform and memory recommendations are not meant to imply that older or slower machines are not usable Refer to the Network and IT Gu
33. eature which is an extension of the Metasys Advanced Reporting System Metasys System Extended Architecture Overview Technical Bulletin 9 Figure 2 Unified and Split ADX Configurations Unified ADX Configuration Computer A Oo OG dX ADX Application Server SCT on Advanced Reporting Ready Access Portal Application Server Server Historical Databases SCT Database Advanced Reporting Database Split ADX Configuration Computer B Computer C ADX Application Server e Advanced Reporting SCT Server Database Advanced Reporting Application Server C3 SCT Database Historical Databases Ready Access Portal Server ADX Web Application ADX Database SCT Server Computer Computer Note All three computers used in a split ADX configuration require the same version of SQL Server software Note You can install the Ready Access Portal software on a stand alone computer as well but you cannot install the Ready Access Portal software on an SCT computer with simulation Also we do not support installing Ready Access Portal software on any ADS ADX that is not a Site Director or on any NxE85 engine The ADX can be installed in a split configuration with the ADX software Site Management Portal Ul on one computer the Web Application server computer and the historical trend audit and event data on another computer the Database server running Microsoft SQL Server software Figure 2 The SCT which is used to generate back up and
34. ect Serial Connections and Dial up Metasys System Extended Architecture LIT 1201639 Modem Connections between NAE NIEs Direct Connection and Dial Up Connection and a Computer Running Microsoft amp Application Note Windows 7 Operating System OS or Windows XP amp OS How to Change a Non Tunneling ToggleTunnel and ChangeModel LIT 12011531 NAE55 NIE55 into an NAE55 with N2 Technical Bulletin Tunneling Capabilities and Vice Versa How to Convert an NAE55 to an NIE55 Toggle Tunnel and ChangeModel LIT 12011531 and Vice Versa Using ChangeModel Technical Bulletin How to Configure and Enable the Demand DLLR Technical Bulletin LIT 12011288 Limiting and Load Rolling DLLR Features on the System How to Use CCT Software CCT Help LIT 12011147 Features Benefits and Specifications of Ready Access Portal Software Catalog LIT 1900538 the Ready Access Portal Software Page How to Use the Ready Access Portal UI Ready Access Portal Help LIT 12011342 ZFR1800 Series Wireless Field Bus ZFR1800 Series Wireless Field Bus LIT 12011295 System System Technical Bulletin TEC Wireless Thermostat Controller TEC Series Wireless Thermostat LIT 12011414 System Controller System Technical Bulletin WRS Series Many to One Wireless Room WRS Series Many to One Wireless Room LIT 12011095 Temperature Sensing System Temperature Sensing System Technical Bulletin Metasys System Extended Architecture Overview Technical Bulletin 5 Table 1 Related Docume
35. ended Memory 4 GB RAM minimum Metasys System Extended Architecture Overview Technical Bulletin 37 Table 9 Extended Application and Data Server System Requirements Split ADX Systems Supported Operating Microsoft Windows Server 2008 R2 OS 64 bit Systems and Database Includes Microsoft IIS Version 7 5 Software Supports Microsoft SQL Server 2008 R2 Standard and Enterprise software 64 bit Microsoft Windows Server 2008 OS 32 bit with SP2 Includes Microsoft IIS Version 7 0 Supports Microsoft SQL Server 2008 R2 Standard and Enterprise software SQL Server 2008 Standard and Enterprise software with SP2 or SQL Server 2005 Standard and Enterprise software with SP3 32 bit Microsoft Windows Server 2003 R2 OS 32 bit with SP2 Includes Microsoft IIS Version 6 0 Supports Microsoft SQL Server 2008 R2 Standard and Enterprise software SQL Server 2008 Standard and Enterprise software with SP2 or SQL Server 2005 Standard and Enterprise software with SP3 32 bit Required Web Browser Microsoft Internet Explorer Version 6 x 7 0 or 8 0 Software for Metasys Client Computers Java Runtime Environment JRE 1 6 0 23 Note When browsing to the Ul of a Metasys system device the OS on the client computer must be supported by the Metasys release loaded on the device You may be unable to browse to Metasys system devices if the client OS is not supported See Computer Requirements for Site Management Portal Cl
36. events are scheduled to occur Scheduling automates routine functions such as transferring a room from occupied mode to unoccupied mode for heating and cooling needs and energy optimization Each schedule consists of a weekly schedule an exception schedule a list of items in the schedule and an effective period Exception schedules take precedence over the daily schedule only for their configured length and then return the schedule to its typical weekly schedule Exceptions can include references to Calendars that can for example reflect a holiday schedule for the entire facility or show selected tenant spaces in the building Another view within the schedule called Today s Schedule shows the current day s schedule including how each exception schedule affects the current day s schedule Historical Data Management Trend The Metasys Historical Data Management capability allows you to collect store and view historical samples of object data With the information generated by this feature you can manage energy usage prove compliance to standards and diagnose problems in your facility Each engine has a local buffer where it stores trend samples The size of this buffer in number of samples is configurable by the user If a server exists on the site you can send the trend samples to its database This database supports backup restore and archival of data to long term storage You can display trend data as a graph or table of values on the
37. evices on a continuously connected IP network A site s primary network consists of one or more engines The engines also provide the Site Management Portal UI that allows for the configuration of the primary network and user monitoring of all devices on the network Engines can be Network Automation Engines NAEs Network Integration Engines NIEs Network Control Engines NCEs or LonWorks Control Servers LCSs These engines are described in further detail in this document A site can optionally have one or more Metasys servers computer based devices that add long term data storage and support for larger Metasys networks Metasys servers can be either Application and Data Servers ADSs ADS Lites or Extended Application and Data Servers ADXs which are described in further detail in this document Servers provide the same Site Management Portal UI as the engines Additionally you can install Ready Access Portal software on an ADS ADX Each Metasys site has one device engine or server that is designated at the Site Director Typically the Site Director is the single point of access for all Site Management Portal UI users because the Site Director includes a view of all Metasys devices on the site If a server is connected to a site it must be designated as the Site Director For more information see Site Director Figure 1 shows an example Metasys system configuration The Metasys System Configuration Examples section shows a variety of c
38. h overview adx sj IP Ethernet NAE55 NAE55 Firewall Optional Optional pa MS TP Bus e Nee LONWORKS Ready Access Portal MS TP Bus Network Ready Access Portal Server Large ADX Site Configuration For a customer site that requires from 200 to 1 000 NxEs we recommend an ADX configuration with a minimum of two separate servers one serving as ADX Site Director and repository and a second for use with configuration tools such as SCT and the NAE NIE Update Tool If the Ready Access Portal software is required a third server is recommended to run the Ready Access Portal software See Table 2 Table 2 Recommendations for Large ADX Systems Hard Disk 584 GB at 15 000 RPM with 400 GB free GB at 15 000 RPM with 400 GB free Processor Type 2x Sroa oo REM wi 10 CE fee NN Xeon Processor E5530 2 4 GHz 4 MB Cache RAID Level 5 configuration Operating System Microsoft Windows Server 2008 Standard R2 64 bit SQL Server Software Microsoft SQL Server 2008 Standard R2 64 bit Poll Rate Set to slow Time Sync Method Select Multicast with heartbeat interval of 60 seconds Note To allow multicast packets to reach all NxEs configure network routers to allow multicast packet passthru This setting is usually not the default Dynamic Broadcast Depending on the number of network segments and data sharing needs Management set Dynamic Broadcast Management to False and manually set up BACnet Broadcast Management Devices
39. he marks of their respective owners 2011 Johnson Controls Inc Published in U S A www johnsoncontrols com Metasys System Extended Architecture Overview Technical Bulletin 41
40. ible To make all information in the facility accessible from a single point the Metasys system uses a Site Director The Site Director is the device designated to maintain the site information including the logical organization of data about your facility called User Views user password administrative information and overall master time and date This function resides in an engine or on large installations a server For networks that do not have a server one of the engines is designated as the Site Director When one or more servers are part of the network one server must be designated as the Site Director The Site Director provides a uniform point of entry and supports functions such as user logon user administration time synchronization and traffic management Consider a server as the Site Director if you require support of multiple international languages repository for trend and alarm data and operator transactions along with annotations for MVE systems agreater number of simultaneous users than an engine allows additional storage space for graphics Time Management The time and date used by all devices connected to a site are synchronized automatically preventing errors from manual time entry and clocks that become inaccurate over time Network wide time management ensures that scheduling trending audit trailing data collecting time stamping of alarms and other functions requiring accurate time management use the sam
41. idance for the BAS Professional Technical Bulletin LIT 12011279 for more information regarding computer server recommendations Metasys System Extended Architecture Overview Technical Bulletin 39 CCT System Requirements Table 11 describes the recommended and minimum computer requirements for a computer on which you are installing a stand alone CCT Table 11 Controller Configuration Tool System Requirements Recommended Intel Core 2 Duo E6700 or better Intel Core 2 Duo E4300 minimum bain dod 20 GB free hard disk available 600 MB minimum Platform DVD drive Recommended Memory Computer Platforms 2 GB RAM recommended 1 GB RAM minimum t Pa efecto oman Supported Operating Microsoft Windows 7 OS Professional Enterprise and Ultimate Editions 32 bit with SP1 HS and Database Includes Microsoft IIS Version 7 5 Supports SQL Server 2008 Express software with SP1 or Microsoft SQL Server 2005 Express software with SP3 Microsoft Windows XP OS Professional Edition 32 bit with SP2 or SP3 Includes Microsoft IIS Version 5 1 Supports SQL Server 2008 Express software with SP1 or Microsoft SQL Server 2005 Express software with SP3 Required Web Browser Microsoft Internet Explorer Version 6 x 7 0 or 8 0 Software for Metasys Client Computers Java Runtime Environment JRE 1 6 0 23 The Internet Explorer Web browser is required to use the CCT Help Network Communication Ethernet network interface car
42. ient Computer for more information Network Communication Ethernet network interface card 10 100 1000 Mbps 100 Mbps or better recommended Additional Software CCT software ce ee nus Export Utility software Metasys Advanced Reporting System Metasys Database Manager software Microsoft NET Framework Version 3 5 SP1 or 3 5 1 Windows Server 2008 R2 software Ready Access Portal software SCT software SCT Manager software Optional Hardware Any network or local printer supported by the qualified Windows operating system This product cannot be used in the following situations due to SQL Server software licensing restrictions a split ADX with the Metasys Advanced Reporting System and computers with more than one processor Order the ADX software and the appropriate SQL Server software separately 5 Our computer platform and memory recommendations are not meant to imply that older or slower machines are not usable Refer to the Network and IT Guidance for the BAS Professional Technical Bulletin LIT 12011279 for more information regarding computer server recommendations 6 ADX prerequisite software includes the Windows OS and SQL Server software Windows NET Framework and any other software or service packs required for your ADX configuration 7 The Web Application and Database servers must have the same OS installed 8 Refer to the Network and IT Guidance for the BAS Professional Technical Bulletin LIT 1201279 for specific Microsoft Windows
43. in LIT 1201534 Archive Databases Offline and Basic N2 Online Network Setup N1 Migration with an NIE N1 Migration with the NIE Technical LIT 1201535 Bulletin How to Integrate an N2 Network into the N2 Integration with the NAE Technical LIT 1201683 Metasys System Bulletin How to Install the NAE NIE Update Tool NAE NIE Update Tool Technical Bulletin LIT 12011524 and Update NxEs From One Release to Another Network Information Including Security Network and IT Guidance for the BAS LIT 12011279 Risks Professional Technical Bulletin Network and IT Considerations for the IT LIT 1201578 Professional Technical Bulletin How to Apply and Engineer a Metasys Metasys System UL 864 UUKL Ninth LIT 12011252 Smoke Control System that Complies with Edition Smoke Control System Technical the Metasys System UL 864 UUKL Ninth Bulletin Edition Smoke Control Listing Devices and Logic Used to Implement a Metasys System UL 864 UUKL Ninth LIT 12011308 Ninth Edition Smoke Control System for Edition Standard Smoke Control Single Story Mall Warehouse and Applications Application Note Multistory Building How to Integrate a Fire System into the Metasys System Extended Architecture LIT 1201993 Metasys Network Fire System Integration Using the IFC BACnet Gateway Application Note Metasys System Extended Architecture Overview Technical Bulletin 4 Table 1 Related Documentation For Information On LIT or Part Number NAE Compliance with
44. ized energy use across your site and presents your daily electrical demand graphically User Graphics User interaction with the Metasys system can be done using a graphic presentation on the Site Management Portal UI or the Ready Access Portal Ul The User Graphics Tool UGT is used to view create and edit user graphics This application provides a way to monitor and control a facility through a graphic representation presented in a functional format Advanced Graphics Application Software The Advanced Graphics Application is an enhanced graphics creation package that provides additional dynamic capabilities such as custom animation color changing and flashing for the Metasys system which are not supported by Standard Graphics The package includes a dynamic example stencil library and is an add on to Microsoft Visio amp software With a more comprehensive representation of facility support systems building operators can easily monitor the health of the system on a more intuitive interface Advanced graphics are viewed from the Metasys system Site Management Portal UI Graphic Generation Tool The Graphic Generation Tool GGT is the newest graphic creation package for Metasys that takes building control from graphical displays to the next level This stand alone application runs on any supported Windows OS computer to deliver an ideal platform for creating sophisticated graphics for your entire facility A Metasys Graphics Package is inc
45. le The NIE55 supports smaller N1 networks while the NIE85 supports large N1 integrations LCS The LCS85 is a computer based server that is used to communicate with LonWorks devices over an IP network The LonWorks field devices are normally connected to an IP router This arrangement allows the Metasys system to be used in a flat LonWorks configuration SCT The System Configuration Tool SCT assists in all phases of engineering installing and commissioning engines and servers in a Metasys system The SCT can be used offline to create archive databases that can be downloaded to an engine or server The SCT also allows you to upload and archive databases that were created or modified online from an engine or server Using the SCT you can view and configure multiple sites in one archive The SCT has the same look and feel as the Site Management Portal Ul Two diagnostic reports are available that provide helpful system statistics and list any unbound references found in the database The SCT also provides a Simulation feature which allows you to simulate a functioning engine and test database control logic prior to downloading it Simulation allows you to perform commissioning and configuring tasks on simulated devices when the Metasys system is offline In Simulation mode you can test commands and see how a real system reacts if commanded to perform the same action The same features are used to commission both simulated and online devices Th
46. luded to provide an extensive library of pre built templates symbols controls and dynamics that you can freely use and customize Graphics built with the tool are saved to the Site Director or engine as Graphics objects and viewed from and interacted with the Site Management Portal UI or Ready Access Portal UI For best results we recommend graphic authors use a computer system with two monitors System Security User access to the Metasys system is controlled by user accounts An account defines which portions of the Metasys data a user can access for example all HVAC data or all lighting data from a particular area of the building and which functions the user can perform on that data from view only access to configuring new databases The Metasys system provides the ability to divide the data into 25 unique categories including HVAC fire and security and has 10 different levels of user functionality User accounts can be further limited to operate only at specified times on specified days of the week All account settings are created by a System Administrator Each account can also have associated preferences such as which graphic or trend to display when a user logs on to the Site Management Portal UI or which User Views appear in the Navigation Tree Basic Access offers limited operator access to Site Management Portal features based on the user s assigned permissions in the Security Administrator Basic Access is offered on all the
47. m Supported Operating Systems Microsoft Windows 7 OS Professional Enterprise and Ultimate Editions 32 bit with SP1 Includes Microsoft IIS Version 7 5 Supports Microsoft SQL Server 2008 Express R2 software SQL Server 2008 Express software with SP2 or SQL Server 2005 Express software with SP3 Microsoft Windows XP OS Professional Edition 32 bit with SP3 Includes Microsoft IIS Version 5 1 Supports Microsoft SQL Server 2008 Express R2 software or SQL Server 2008 Express software with SP2 or SQL Server 2005 Express software with SP3 Required Web Browser Software for Microsoft Internet Explorer amp Version 6 x 7 0 or 8 0 i y eat ror BPIes Java Runtime Environment JRE 1 6 0_23 Note When browsing to the UI of a Metasys system device the OS on the client computer must be supported by the Metasys release loaded on the device You may be unable to browse to Metasys system devices if the client OS is not supported See Computer Requirements for Site Management Portal Client Computer for more information Network Communication Ethernet network interface card 10 100 1000 Mbps 100 Mbps or better recommended Additional Software Included on the CCT software ADS duet Piss Export Utility software Metasys Database Manager software Microsoft NET Framework Version 3 5 1 Microsoft SQL Server 2008 Express R2 software Microsoft SQL Server 2008 Express software with SP2 Microsoft SQL Server 2005 Express software with SP3
48. mputer on which you are installing an NxE85 Table 12 NxE85 Software System Requirements Product Code MS NxE85SW 0 NxE85 software for 10 000 objects new projects only software Recommended Computer Platform Intel Xeon E5506 2 13 GHz 4 MB Cache 2 x 160 GB 7 2K RPM Serial Advanced Technology Attachment SATA 8 9 cm 3 5 in Cabled 3 Gbps RAID 1 configuration with add in SAS6 IR SATA SAS Controller DVD ROM SATA Recommended Memory 1 GB RAM minimum Hard Disk 160 GB minimum Supported Operating Systems and Microsoft Windows Web Server R2 2008 OS 64 bit Software Microsoft IIS Version 7 5 Microsoft NET Framework Version 3 5 1 Microsoft Windows Web Server 2008 OS with SP2 32 bit Microsoft IIS Version 7 0 Microsoft NET Framework Version 3 5 with SP1 Microsoft Windows 2003 Web Edition OS with SP2 32 bit Microsoft IIS Version 6 0 Microsoft NET Framework Version 3 5 with SP1 Network Communication Network Interface Single 1 Gbps Ethernet network interface card 10 100 1000 Mbps 100 Mbps or better recommended Recommended Data Protection Uninterruptible Power Supply UPS American Power Conversion APC Smart UPS SC 450 VA 280 W 120 VAC input output NEMA 5 15R output connections OEM Part No SC450RM1U Building Efficiency 507 E Michigan Street Milwaukee WI 53202 h Jo nson Metasys and Johnson Controls are registered trademarks of Johnson Controls Inc Controls All other marks herein are t
49. munication path to the Metasys system for a network of LonWorks devices The NAE supports any LonWorks device if the network interface follows the current LoNMARKO guidelines and uses the Free Topology Transceiver FTT10 including all current LonMark certified devices from Johnson Controls such as e LN Series Controllers including programmable controllers application specific controllers and displays and schedulers Terminal Control Units TCUs Programmable NexSys Flexible System Controllers FSCs An LNS plug in tool such as LN Builder 3 x can be configured to work concurrently with the SCT for commissioning a LonWorks trunk and creating import files for the NAE to map the LonWorks objects to NAE objects N1 Integration The N1 integration is based on the NIE A single NIE or a network of multiple NIE devices are configured to map point objects of all or selected Network Control Module NCM devices on one or multiple existing Ethernet N1 networks The NIE to which an N1 object is mapped provides alarm and event management trending energy management and scheduling capabilities P2000 Security Management System Integration The Metasys system provides integration with the P2000 Security Management System The P2000 integration offers the following features View and interact with all aspects of HVAC facility operation For example floor plan graphics can contain dynamic information about environmental conditions and security sta
50. n a building The system ships with a set of pre configured standard applications Metasys System Extended Architecture Overview Technical Bulletin 17 Metasys for Validated Environments Metasys for Validated Environments MVE extended architecture is a feature designed for facilities that require regulatory compliance for their environmental systems The MVE feature operates on an ADX NAE55 NCE25 and NIE55 which are all supported as validated devices MVE is specifically designed to help customers address United States Food and Drug Administration USFDA Title 21 Code of Federal Regulation CFR Part 11 compliance MVE is also compliant with other similar agencies around the world that deal with electronic records and electronic signature requirements such as Annex 11 of the European Union Good Manufacturing Practice EU GMP regulations European Medicines Agency EMEA 1998 The ADX with MVE software provides secure data management and reporting capabilities traceable electronic records and signatures and time stamped audit trails for facilities subject to Part 11 compliance It manages and protects the long term storage of trend data audit data event alarm messages annotations and system configuration data In addition complex passwords and message encryption secure the system from unauthorized access and data tampering Metasys System Extended Architecture Overview Technical Bulletin 18 Metasys System Configuration Example
51. n the Metasys System Including Technical Specifications and Ordering Information Features Functions and Applications of Network Control Engine NCE Product LIT 12011283 the Network Control Engine NCE 25 in Bulletin the Metasys System Including Technical Specifications and Ordering Information Features Benefits and Specifications of System Configuration Tool Product LIT 1201536 the System Configuration Tool SCT Bulletin How to Install and Upgrade the ADS ADX ADS ADX and SCT Installation and LIT 12011521 and SCT Software How to Maintain SCT Upgrade Instructions Wizard Databases from Multiple Releases How to Install the Metasys Advanced Reporting System How to Install the ADS Lite ADS Lite Installation and Upgrade LIT 12011688 Instructions Wizard How to Use the Metasys Database Metasys Database Manager Help LIT 12011202 Manager to Manage Historical Data on an ADS How to License Metasys System Extended Software License Activator Technical LIT 1201654 Architecture Software ADS ADX NxE85 Bulletin and Others How to Install the CCT Software CCT Installation Instructions LIT 12011529 How to Install the Graphic Generation Tool Graphic Generation Tool Installation LIT 12011685 Instructions How to Use the Advanced Reporting Metasys Advanced Reporting System Help LIT 12011312 System How to Use Ready Access Portal UI Ready Access Portal Help LIT 12011342 How to Use Graphic Generation Tool Graphic
52. ncation Maximum number of characters in the 4 description of an item object Maximum number of results displayed in 2 000 With an ADX as the Site Director third party BACnet states text With an NAE as the Site Director Maximum number of members for a 5 multi value third party BACnet states text Number of Users for SCT 1 user per database at a time Refers to active users Maximum number of concurrently active 10 Databases can be archived and restored archives in SCT Maximum size of an Active Database or 4 GB Using supported SQL Server 2008 Project in SCT Express software or SQL Server 2005 Express software 10 GB Using supported SQL Server 2008 Express R2 software a global search 5 Maximum number of sets for third party 1 000 BACnet states text Maximum number of characters for a 00 0 00 00 Maximum number of languages per 1 Any one language NAE NIE NCE Maximum number of languages per 4 Allows dynamic switching ADS ADX Metasys System Extended Architecture Overview Technical Bulletin 31 Table 3 Performance Guidelines and Limitations Maximum number of concurrent users on 100 ADX on Windows Server 2008 R2 OS the Ready Access Portal UI where the Windows Server 2008 OS or Windows software is installed on a stand alone Server 2003 OS computer ADS on Windows Server 2008 R2 OS Windows Server 2008 OS or Windows Server 2003 OS ADS on Windows 7 OS or Windows XP OS NAE35 NAE45 NAE55
53. nclude logging into the Ul or issuing commands to a point Examples of system activity include device restart initialization settings or internal security changes An audit message consists of the information that describes a significant event on the Building Automation System BAS For each significant event a new audit message is generated and appears in the Audit Viewer Once an eventis sent to the Audit Trails subsystem an audit message is generated and stored in an Audit Repository file located on the server or engine that detected the condition Audit messages may be forwarded from the Local Audit Repository to a user specified ADS Audit Repository for permanent storage on a server ADS ADX based on user defined rules The Site Management Portal UI contains the Audit Viewer that allows the user to view audit messages Once a user logs on to the Site Director the user can view all audit messages from the server or any device that contains a Local Audit Repository When a user directly logs on to a device not designated as the Site Director the user can only view audit messages in that device s Local Audit Repository Any audit messages generated on a server are placed directly into the ADS ADX Audit Repository System Diagnostics and Serviceability The engine provides collection and storage of diagnostic data The Diagnostic view of the engine device retrieves and displays diagnostic data related to communications internal component perform
54. nt Portal Client Computer for more information Network Communication Ethernet network interface card 10 100 1000 Mbps 100 Mbps or better recommended Metasys System Extended Architecture Overview Technical Bulletin 36 Table 8 Extended Application and Data Server System Requirements Unified ADX Systems Additional Software CCT software Included on the ADX x Product Disks Export Utility software Metasys Advanced Reporting System Metasys Database Manager software Microsoft NET Framework Version 3 5 SP1 or 3 5 1 Windows Server 2008 R2 software Ready Access Portal software SCT software SCT Manager software Optional Hardware Any network or local printer supported by the qualified Windows operating system 1 Our computer platform and memory recommendations are not meant to imply that older or slower machines are not usable Refer to the Network and IT Guidance for the BAS Professional Technical Bulletin LIT 12011279 for more information regarding computer server recommendations 2 Refer to the Network and IT Guidance for the BAS Professional Technical Bulletin LIT 1201279 for specific Microsoft Windows OS settings that may be required for your Metasys system configuration 3 You must purchase a SQL Server software license for each individual processor you have You do not need to purchase multiple licenses if you have a single processor divided into multiple cores For example if you have a single processor with dual cores
55. ntation For Information On LIT or Part Number TE 7800 Series One to One Wireless Room Temperature Sensing System TE 7800 Series One to One Wireless LIT 12011097 Room Temperature Sensing System Technical Bulletin WRZ 7850 One to One Wireless Room WRZ Series One to One Wireless Room LIT 12011641 Temperature Sensing System Sensing System Technical Bulletin Metasys System Extended Architecture Overview Technical Bulletin Metasys System Extended Architecture The Metasys system extended architecture is a Web based system that allows day to day building operators using a Web browser to access the system s User Interface UI The Metasys system user experience is a portal into a site It can be tailored to fit the needs of all potential system users The user experience provided by the Metasys system can evolve and scale to match the needs of any single facility or campus of multiple buildings Two variations of the UI are available Site Management Portal and Ready Access Portal The Site Management Portal provides real time and historical data views extensive alarm management capabilities and system configuration functions for system administrators or dedicated building operators The Site Management Portal transforms the raw data from the site and organizes it into a comprehensive set of information management tools and reports This portal is accessed using Microsoft Internet Explorer Web browser through an Internet or intrane
56. onfiguration examples Metasys System Extended Architecture Overview Technical Bulletin 7 Figure 1 Example Metasys System Configuration ADS Site Director with SCT Site Management Portal and Ready Access Portal Ready Access Portal Software Handheld Device Site Management Portal Site Management Portal or Ready Access Portal or Ready Access Portal A Bn x wm sat I e jose i z Printer rr Firewall Wireless Access Point IP Ethernet Wide Area Network WAN or Internet Hardwire Input Output Points FC Bus amp BACnet MS TP I MEME Field Bus 3 N2 posa etworl BACnet MS TP N2 or LONWORKS Field Bus Metasys System Extended Architecture Overview Technical Bulletin FlG msea tech overview msea rch Metasys System Extended Architecture Components ADS and ADS Lite The ADS is a Metasys server running on a computer that has a supported Microsoft Windows operating system and two specific components The first component is the relational database management system using a supported edition of Microsoft SQL Server Express software to store collected trend data audit trail messages and alarm and event messages with operator annotations The second component is the Web server software that provides Site Management Portal UI and optionally Ready Access Portal Ul access to data and routes commands to the Metasys system The ADS also Supports a greater of numbe
57. ons as well as view analyze and modify these items After creating items with wizards use these features to access view and modify item data send commands to items run reports to analyze item information Preferences The Metasys system provides customized preferences for the Site Management Portal The preferences allow you to configure how the UI behaves including the sounds and colors the startup views alarm priorities and links from within the UI to external applications Preferences are divided into two categories system preferences and user preferences System preferences apply to all users who log on to the site or device and affect the performance and operation of the system User preferences apply to a specific Metasys system user and define how information is displayed in the UI User preferences do not affect the operation of the system Alarm and Event Management The alarm and event feature provides event management for the system and allows you to configure the routing of event messages to destinations such as the server for permanent storage The Metasys Site Management Portal UI features a pop up alarms window which alerts the operator to potential problems whenever the operator is logged on to the system and an event viewer which provides for greater analysis or a history of alarms and events in the system The Ready Access Portal UI features an Alert Summary view which allows the user to view and acknowledge recent
58. pen Sys91 VMA Maximum number of N2 devices on the Performance varies based on mix N2 N2 trunk on an NAE35 Open Sys91 VMA Maximum number of N2 devices per N2 trunk on an NCE25 Maximum number of mapped N2 points 1 000 Performance varies based on mix N2 per N2 trunk Open Sys91 VMA Recommended maximum for best performance is 1 000 points The software definition limit is 3 200 points with no guarantee of acceptable performance Maximum number of LonWorks devices 255 Single subnet LonWorks network does per NAE55 not support routers supports physical repeaters Maximum number of LonWorks devices Single subnet LonWorks network does per NAE45 not support routers supports physical repeaters Maximum number of LonWorks devices 6 Single subnet LonWorks network does per NAE35 not support routers supports physical repeaters Maximum number of LonWorks devices 32 per NCE25 Maximum number of Metasys MS TP devices on an FC Bus on an NCE25 100 64 50 32 Maximum number of N2 devices per N2 100 trunk on an NAE55 NAE45 50 32 128 4 Maximum number of LonWorks network 2 000 variables per NAE55 Maximum number of LonWorks network 1 500 variables per NAE45 NAE35 NCE25 Maximum number of BACnet IP devices 100 Includes N30s third party devices per NAE55 NAE45 NCE25 Metasys System Extended Architecture Overview Technical Bulletin 28 Table Porrormance Guidelines and Limitations Maximum number of Excel 5000 C B
59. processor with 80 GB hard disk minimum 40 GB free space on the hard disk installing the prerequisite software and before installing the ADX software DVD drive Recommended Memory 4 GB RAM minimum Supported Operating Microsoft Windows Server 2008 R2 OS 64 bit 2 Systems and Database Includes Microsoft IIS Version 7 5 Software Supports Microsoft SQL Server 2008 R2 Standard and Enterprise software 64 bit Microsoft Windows Server 2008 OS 32 bit with SP2 Includes Microsoft IIS Version 7 0 Supports Microsoft SQL Server 2008 R2 Standard and Enterprise software SQL Server 2008 Standard and Enterprise software with SP2 or SQL Server 2005 Standard and Enterprise software with SP3 32 bit Microsoft Windows Server 2003 R2 OS 32 bit with SP2 Includes Microsoft IIS Version 6 0 Supports Microsoft SQL Server 2008 R2 Standard and Enterprise software SQL Server 2008 Standard and Enterprise software with SP2 or SQL Server 2005 Standard and Enterprise software with SP3 32 bit Required Web Browser Microsoft Internet Explorer amp Version 6 x 7 0 or 8 0 Software for Metasys Client Computers Java amp Runtime Environment JRE 1 6 0 23 Note When browsing to the UI of a Metasys system device the OS on the client computer must be supported by the Metasys release loaded on the device You may be unable to browse to Metasys system devices if the client OS is not supported See Computer Requirements for Site Manageme
60. purchase one license for SQL Server software Table 9 Extended Application and Data Server System Requirements Split ADX Systems Product Codes MS ADX10U 0 New ADX project software for up to 10 concurrent users MS ADX10SQL 0 New ADX project software for up to 10 concurrent users Includes Microsoft SQL Server 2008 software with a Processor License for unlimited users devices MS ADXSWO 0 New ADX project software for up to 25 concurrent users MS ADXSWOSQL 0 New ADX project software for up to 25 concurrent users Includes Microsoft SQL Server 2008 software with a Processor License for unlimited users devices Recommended Server Web Application Server Computer Platform 2 8 GHz Pentium 4 processor with 160 GB hard disk 2 0 GHz Pentium 4 processor with 80 GB hard disk minimum DVD drive 200 MB free space on the hard disk after installing the prerequisite software and before installing the ADX software Database Server Computer 2 8 GHz Pentium 4 processor with 160 GB hard disk 2 0 GHz Pentium 4 processor with 80 GB hard disk minimum DVD drive 40 GB free space on the hard disk after installing the prerequisite software and before installing the ADX software SCT Manager In a split configuration you cannot install the SCT on either the Web Application Server computer or the Database Server computer Refer to the System Configuration Tool Catalog Page LIT 1900198 for current SCT computer requirements Recomm
61. r computer platform and memory recommendations are not meant to imply that older or slower machines are not usable Refer to the Network and IT Guidance for the BAS Professional Technical Bulletin LIT 12011279 for more information regarding computer server recommendations A graphics intensive user may experience better performance with additional RAM The Microsoft Windows 7 Operating System OS does not support browsing to applications with Java Runtime Environment JRE version 1 6 0 15 or earlier If the client computer you use to browse to Metasys systems has a Windows 7 OS you may not be able to connect directly and browse to some of the older Metasys devices on your Metasys systems Metasys System Extended Architecture Overview Technical Bulletin 33 ADS System Requirements Table 6 describes the recommended and minimum computer requirements for a computer on which you are installing an ADS Table 6 Application and Data Server System Requirements Product Code MS ADSO05U 0 New ADS project software for up to 5 concurrent users 2 0 GHz Pentium 4 processor with 40 GB hard disk minimum 20 GB free space on the hard disk C drive after installing all prerequisite software and before installing the ADS software DVD drive Note Prerequisite software includes the supported OS database software NET Framework and any other software or service packs required for your ADS configuration Recommended Memory 2 GB RAM minimu
62. r engines as a Site Director than an engine supports supports multiple simultaneous international languages at the user interfaces allows a greater number of simultaneous users than is supported by an engine provides added storage for memory intensive Metasys features such as User Graphics The ADS Lite is a specialized offering that enforces specific localized market connection limitations to other Metasys devices like ADSs and engines See ADS Lite System Requirements for details ADX The ADX is a version of the ADS with extended capabilities for historical data archiving that expand the multi user Web access capabilities of the system The ADX supports the relational database management system that uses a supported edition of Microsoft SQL Server software to store collected trend data audit trail messages and alarm and event messages with user annotations This relational database also stores configuration information for site security trend studies and other features The ADX supports the Metasys Advanced Reporting System which has a Web based reporting interface and standard report sets that allow users to review the alarm and trend configuration of their site run summary and detail reports to monitor alarm and event information view offline information combine alarm and audit information in a single report and aggregate trend data at a summary or detailed level An ADX can also support the optional Energy Essentials reporting f
63. s Single NAE System Configuration Figure 3 shows a single NAE55 device attached to one N2 trunk and one LonWorks trunk Once you complete the automated discovery process for both the N2 and LonWorks trunks your system is ready to provide supervisory control and Web access to a maximum of four simultaneous users Graphics access is included however it is limited to available storage on the NAE The Site Management Portal UI can be accessed by connecting the NAE to an Ethernet network and adding a computer with a suitable browser on the network Note This configuration only provides long term storage of data through the use of the Export Utility installed on a computer Note The NAE45 Lite cannot be a stand alone engine on a network Figure 3 Single NAE Metasys Site Example Site Management Portal Site Management Portal ent Client m Firewall Internet 2 IP Ethernet ri Site Director Ready Access Portal T on Handheld Device M Wireless s Fo Bus Na Bus s Access Point FEC VMA14 VMA14 v t ds Chiller Plant E VMA16 i Air Handler Boiler Metasys System Extended Architecture Overview Technical Bulletin 19 Multiple NAE System Configuration with One NAE Designated as the Site Director To extend the capabilities of your system add one or more additional NAEs In Figure 4 one NAE designated as the Site Director provides the Site Management Portal to all devices on the site
64. s users must add an ADS or ADX Figure 5 If a large number of graphics are required to navigate through a site the addition of the ADS ADX allows access to a disk drive or network drive for graphic file storage The ADS ADX provide permanent storage of collected trend data samples event messages and audit trail messages routed from the NAE NCE devices Note The ADS Lite is available in select markets and supports a subset of available Metasys system devices Figure 5 Multiple NAE System Configuration with ADS and Ready Access Portal ADS with SCT Site Management Portal and Ready Access Portal Site Management Portal Software Site Management Portal or Ready Access Portal or Ready Access Portal Client JR Client al Printer Internet IP Ethernet Firewall FIG msea tech overview ads intwk Metasys System Extended Architecture Overview Technical Bulletin 21 ADX Split Configuration The ADX split configuration provides the ADX software user interface on one computer the Web Application server computer and the alarm audit annotations and historical trend data on another computer with Microsoft SQL Server software the Database server computer Figure 6 ADX Split Configuration SCT ADX Web Application Server Computer ADX Database with Site Management Portal Site Management Portal Server or Ready Access Portal Printer Firewall r Internet Firewall splintwk FIG msea tec
65. t Message Access Protocol IMAP SNMP provides IP standard SNMP functionality in the Metasys system enabling network administrators to manage Metasys network performance find and resolve Metasys system related issues and plan for future growth of the Metasys system SNMP functionality uses standard SNMP Versions 1 2C and 3 excluding SNMP encryption and authentication support Metasys system allows delivery of unsecured SNMP traps for Metasys alarm events from all engines and servers to the facility owners s Network Management System NMS and allows the NMS to execute SNMP Gets against engines This version of SNMP support does not include the SNMP set commands Metasys System Extended Architecture Overview Technical Bulletin 13 Johnson Controls has developed a downloadable custom dynamic Management Information Base MIB that allows the NMS to monitor Metasys point objects display attributes and control sequence objects The MIB is constructed to accurately reflect the additions and deletions of objects in the supervisory devices as the changes occur The custom MIB defines explicit traps and associated attributes that align with Metasys alarm messages making data correlation parsing sorting at the NMS straightforward and seamless Alarm Printer Alarms from supervisory devices can be sent automatically to an alarm printer if one is configured and online Scheduling Scheduling provides a graphical user interface that illustrates when
66. t connection to a Metasys server or engine The Site Management Portal has all the features one expects from a full function traditional workstation including pop up alarm windows navigation tree multiple custom trees can be created to best represent the logical layout of the facility dynamic graphics of systems and floor plans that can be zoomed in on to show fine details multiple display areas that can be individually sized and controlled global search function and sorting capability that helps you find system information within seconds the entire user manual available in the Help system The Ready Access Portal software provides a natural complementary extension of the Metasys Site Management Portal Ul The Ready Access Portal UI provides an intuitive task based interface that can be tailored to meet the needs of building tenants and other specialized users When using a computer or handheld device you need only a Web browser to connect to the computer running the Ready Access Portal software Information Management is an inherent capability of the overall user experience and reporting capabilities Whether you are logged into the Site Management Portal UI running online reports using the Metasys Advanced Reporting System or retrieving data from an engine with the Export Utility you are transforming the data collected by the system into information you can use to manage your site A Metasys site comprises one or more Metasys d
67. te Configuration dace inito tai aa reet bared eta thee stand aa Taia ioe aaiae 22 N1 Integration System Configuration eret ee e etre ERE ERE EAR CH NY De tradu RE AE aunt 23 Mu lti Eocation Configurati n arine satan pe A es eed olore ou een de a asada Qu expe Sapa Poeta peau eee 24 BACnet IP Network System Comnfiguration 22 c cccececseccceeeeeteeeesenceceedethedensstenneeeetenenesneeeceseneteeseens 25 Smoke Control Application Configuration ssssssse eee 26 Wireless Metasys System Configurations cccecccceeeeeeeeeeeneeeeeeeeeeeeeeaaaeeeeeeeeeeeaaaeeeeeeeeeeeeneeeeneeeees 27 Performance Guidelines and Limitations eeeeeeeeeeeeeeeeeeeeeeeeneen nennen nnn 28 Technical Specifications and Requirements cccccccccccccceceeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeneeeneeeneeeneenes 33 Hardware Configuration Requirement 22 ccccesessesccceeeeeeeesseeeceneeneeeeesesccenseseeeesenerseneneenstnenseneneees 33 Computer Requirements for Site Management Portal Client Computer ueeeesusssssse 33 ADS System REQUISITIONS x oiu ote oec cere re cede pene iita eue esau Suse densa clu sar ie Le RR a 34 ADS Lite System RequireMentS c eas ttadesetu otto iet etd eder paene eoa mde sertl sut crisp t oder lesu deus 35 ADX System Requirements 5 35 teca aec sede on ida cte tasas d teda rette aaide bta 36 SCT System Redgquiremierits er rete coe er a
68. te EE RA ERR ened ede E GR RR EHE RO cR EINE RARO 39 CGT System Requirerieribs room e eter eec aa Dee esu i tete sud ie emi estadio eder Aa 40 NXEGS System Requirements seu citt oret Pos c tuat tede es 41 Metasys System Extended Architecture Overview Technical Bulletin 2 Document Introduction This document introduces the components and capabilities of the Metasys amp system extended architecture It also describes how the system operates and provides an overview of the various configurations Related Documentation The documents in Table 1 contain information related to the features installation operation configuration and troubleshooting of the Metasys system extended architecture Important user information is located in the Metasys system Help LIT 1201793 Table 1 Related Documentation For Information On LIT or Part Number Features Benefits and Specifications of Application and Data Server ADS ADX LIT 1201525 the Application and Data Server Product Bulletin ADS Extended Application and Data Server ADX Features Functions and Applications of Network Automation Engine NAE LIT 1201160 the Network Automation Engine NAE 35 Product Bulletin NAE45 NAE55 and NAE85 in the Metasys System Including Technical Specifications and Ordering Information Features Functions and Applications of Network Integration Engine NIE Product LIT 1201537 the Network Integration Engine NIE 55 Bulletin and NIE85 i
69. trol NAE LONWORKS NAE 5 Port SW LEUR Ethernet Smoke Smoke Control LONWORKS Control NAE d NAE 5 Port SW n LonWorks 2 Smoke Control pe NAE 2 2 LONWORKS v 2x 1 MS TP FC Bus Connections 2 LON Bus Connections 1100 Mbps Site Management Portal UI Smoke Control Equipment r 10 Mbps Fiber Non Smoke Control Equipment Ethernet NAE I 10 100 Mbps 55 pem e I 5 Port SW E ER 10 Mbps thernet edia V 1 SM Converte Spot sw NAE35 45 Smoke Fiberto 2 2 2 2 2 Control 10 Mbps Media I NAE I Converter I Smoke Fiber to 100 Mbps l 10Mbps Control l Ethernet NAE Media I to Field Converter i 100 Mbps l Media Fiber to 100 MPS Ethernet to Field Converter E I Fiber to 100 Mbps I 10 Mbps Ethernet to Field l Lo i l e T gt Ethernet I 5 Port SW l 10 Mbps Smoke I Ethernet Control i to Field NAE55 5 Port SW __ l E i A 5 Port SW I FC 1 is I Sue s Smoke N Control 4 Pont sw NAESS to Smoke iy FC l 5 Control Mi A NAE f z C 114 1 E Ee i 2 Metasys System Extended Architecture Overview Technical Bulletin 26 Wireless Metasys System Configurations Figure 12 shows the various wireless Metasys system offerings and illustrates how the systems can coexist with each other within the Metasys system Figure 12 Wireless Metasys Systems Site Management Portal ADS Site
70. tus in a common display e View P2000 objects in the navigation tree leveraging the use of a common user browser user interface Control output points and doors e View P2000 events in the Metasys system Event Viewer Initiate actions on the Metasys system from P2000 Events You can define functional interlocks between the P2000 and other systems managed by the Metasys system For example employee identification cards can be set to turn on the air conditioning system serving their work areas when they arrive in the building For information refer to the P2000 P2000LE Metasys System Extended Architecture Integration Option Manual Part No 09 9300 01 Logic Connector Tool LCT The Logic Connector Tool LCT is used to create custom application programs that execute in any engine The programs are created using a drag and drop editor that allows the programmer to connect real time point data in the engine with logic blocks that perform mathematical logical and various specialized control functions LCT programs can be created edited and viewed online through the Metasys Site Management Portal UI or offline using the SCT When viewed through the SCT the finished programs can be simulated to verify proper operation before being downloaded to the engine Interlocking Programs Event The Interlock object provides a means to establish conditional control over one or more other objects It consists of an If conditional statement True comman
71. us The NIE counts as one of the 30 devices devices on the C Bus trunk on an NIE55 E Bus devices do not count as one of the with UXB 30 devices Maximum number of points per C Bus 2 500 The total point count of the E Bus devices trunk counts toward the 2 500 point limit Maximum number of items objects in 3 000 000 Without Metasys Advanced Reporting entire system system and Metasys Energy Essentials 750 000 With Metasys Advanced Reporting system and Metasys Energy Essentials Maximum number of items objects in one 25 000 Includes all points extensions graphics NAE85 NIE85 LCS85 background image trend study and other objects schedules and interlock for example Maximum number of items objects in one 5 000 Includes all points extensions graphics NAE55 NIE55 background image trend study and other objects schedules and interlock for example Maximum number of items objects in one 2 500 Includes all points extensions graphics NAE45 NAE35 NCE25 background image trend study and other objects schedules and interlock for example Maximum number of items objects within 700 a single folder per NIE85 NAE55 NIE55 Maximum number of items objects within 300 a single folder per NAE45 NAE35 NCE25 Maximum number of audits per hour for 500 Add ADS ADX for more each NAE85 NIE85 Maximum number of audits per hour for 500 Add ADS ADX for more each NAE55 NIE55 Maximum number of audits per hour for
72. use Interlock or Multiple Command objects to reduce the number of loads added to the DLLR Limited only by memory capacity Maximum number of DLLR objects Metasys System Extended Architecture Overview Technical Bulletin 32 Technical Specifications and Requirements Hardware Configuration Requirements Our suggested minimum hardware configuration is based upon experience and testing for both client and server platforms These configurations are only suggestions and are not meant to imply that older or slower machines are not usable Systems with less memory smaller hard disks or that are generally slower may have acceptable performance for basic operations These systems may also be acceptable when not called upon to operate simultaneous tasks that require hardware or network resources Memory intensive applications may require additional memory for proper performance Examples of these optional or advanced features of the Metasys system include navigation and support for complex graphics operation with the maximum number of users complex and extended queries with the Export Utility support for large network integrations and large numbers of concurrent open windows Computer Requirements for Site Management Portal Client Computer Table 4 and Table 5 describe the recommended and minimum computer requirements for the computer used for Site Management Portal access Table 4 Site Management Portal Desktop Client Computer Requirements

Download Pdf Manuals

image

Related Search

Related Contents

Lexmark P350 Portable Photo Printer  ASSMANN Electronic AK-300306-002-S  MOD. ELSA MOD. ELSA MOD. ELSA MOD. ELSA MOD. ELSA  空気圧機器 取扱説明書 (小形タイプ)  Ropox Shower & Changing Bed  このリリースのPDFファイル  Schlüter®-RENO-T - Schlüter  Product Information for Item 0009546, WP 1550AW with  ManualsLib - Makes it easy to find manuals online!  MANUEL D`INSTRUCTIONS - MRC  