1. DESCRIPTION a MBPF 1001 ee APRIL 4 2013 MBPF 1008 MB 600PF MBPF 200 MBPF 202S Sensor Modules SAL US APPROVED The MBPF 100S MB 600PF MBPF 200S and MBPF 202S modules provide visual indication and electrical output that signal the user regarding flame presence in a combustion chamber The module uses Fireye optical ultra violet scanners and or flame rod to sense flame presence independently or as components in a burner man agement system Many operational characteristics are provided including e UL recognized and FM approved MBPF 100S MB 600PF e FM approved MBPF 200S MBPF 202S e Self contained 120 VAC 50 60 MBPF 100S MB 600PF 220 VAC 50 60 MBPF 200S MBPF 202S e UV detection or flame rod or both e Flame ON LED e User controlled Flame Fail LED e Analog output test points permits direct reading of flame signal e Uses standard 11 pin relay base e Panel surface or DIN rail mounting e Remote testing of contacts available e Self check scanner available for MBPF 100S and MB 600PF Check with Fireye for more details by contacting your local distributor or by check ing the Fireye home page at www fireye com NOTE When the MBPF modules are used additional means must be furnished to provide those func tions usually provided by flame safeguard control systems to meet local regulations i e safe start check valve closure starting and running interlocks safety timings etc NOTICE When Fireye product
2. in its own shielded cable Multiple shielded cables can be run in a common conduit Flame rods should be used only on gas burners They accumulate soot on oil burners causing nui sance shutdowns and unsafe operating conditions See the burner manufacturer s literature for flame rod mounting location Use only Fireye scanner models UV7A4 UV7R4 amp UV7SC Consult the burner manufacturer s instructions for mounting location FIGURE 2 TYPICAL APPLICATION MBPF 100S CD an r 7 WH 120VAC B n this application the programmable RD NEUTRAL _A controller PLC can test the flame relay UV Scanner pj LE USC ue BK SIGNAL eis for proper function by applying voltage oo i to Pin 10 and monitoring the contact yellow D action on Pins 4 5 and 6 Pin 4 Flame Rod opens and Pin 6 closes MBPF 100S p ae and GN RETURN MB 600PF NC ONLY Zz ie FLAME ROD RETURN WHERE APPLICABLE 60 2726 NOTE WIRING TERMINALS 1 amp 8 ARE BASE INTERNALLY CONNECTED Programmable 12 120 VAC DC Test Signal Controller Analog Signal 8 12 VDC Signal Return N 6IL 120VAC NOTE f Pin 10 is not used for remote testing it should be jumpered to Pin 1 neutral 50 60Hz SPECIAL CONDITIONS OF USE The equipment shall be installed in compliance with the enclosure mounting spacing and segregation requirements of the ultimate application Line voltage and extra low voltage wiring to and from this device is i
3. self check applications NEMA 4 1 2 NPT mount 4 lead with insulating SC 107 coupling UV7R4 Ultra violet scanner non self check applications 1 2 NPT 90 lead with insulating coupling SC 107 UV7SC Ultraviolet scanner self check applications 120VAC 1 NPT mount MBPF 100S only SC 107 59 504 010 Cable connector for self check scanner 10 foot SC 107 Flame Rods SC 103 SC 103 SC 103 69ND1 1000K4 Flame rod 1 2 NPT mount 12 length 69ND1 1000K6 Flame rod 1 2 NPT mount 18 length 69ND1 1000K8 Flame rod 1 2 NPT mount 21 length PRODUCT SPECIFICATIONS Supply Voltage MBPF 100S MB 600PF 120 VAC 10 15 50 60 Hz 0 1 Amp consumption MBPF 200S MBPF 202S 220 VAC 10 15 50 60 Hz 0 1 Amp consumption Flame Relay Output SPDT 2 Amp Resistive 240VAC 3Amp 24VDC Flame Fail Response Time Operating Temperature Storage Temperature Humidity Agency Approvals MBPEF 100S MBPE 200S MBPE 202S Shipping Weight Scanner Voltage Ultra Violet Terminals 7 amp 8 Flame Rod Terminals 9 amp 8 Sensitivity 3 seconds MBPF 100S MB 600PF MBPF 200S 2 seconds MBPF 202S 40 F to 140 F 40 C to 60 C 40 F to 176 F 40 C to 80 C 85 RH max non condensing Underwriters Laboratories UR Factory Mutual FM Factory Mutual FM Factory Mutual FM 1 lb 5 Kg 460 VDC 530VDC 120 1ISOVAC Note Measured with d
4. igital VOM Terminals 1 and 8 are internally connected Flame Rod 3uAmps 80 Meg ohms Vmeter 3 0 VDC Ultra Violet 50 pW cm 210nm Vmeter 8 0 VDC FIGURE 1 DIMENSIONS OF DIN RAILS WIRING BASES AND FLAME SWITCH MODULES SHOWN IN INCHES MM 0 165 4 2mm 2 Holes FIREYE DERRY NEW HAMPSHIRE OURCE 230VAC 50 60HZ OUTPUT LOAD 1A 250VAC RESISTIVE LOAD 40 e UV to 60 C 40 to 149 F OFO n 340 0700 0 164 oe E Cim p ann Fr 858 1 299 22mm j Deaamm T Panel Cutout for Surface Mounting arl TEST MODULE a STYLE 11 pin octal snap mount surface mount TAL M gt TERMINAL M3 5 screws with captive wire clamp WIRE SIZE Maximum up to 2 12 AWG each terminal ELECTRICAL RATING 300V 10A Iil To secure MBPF to socket use retaining kit P N 129 172 MBPF 100S DIN RAIL MOUNT 120VAG PART NO LENGTH 60 2539 12 L 12 305 60 2539 24 L 24 610 60 2539 36 L 36 914 DIMENSIONS IN INCHES MM SENSOR INSTALLATION WARNING Incorrect sensor installation may cause the sensor to generate a false flame sig nal causing unburned fuel to collect in the combustion chamber The result can be explo sions injuries and property damage Be certain that the flame sensor detects only pilot and main flames not glowing refractory burner or ign
5. ition parts Route sensor wiring a sufficient distance from ignition and other high voltage or high current wiring to avoid electrical interference Interference from ground currents nearby conductors radio fre quency emitters wireless devices and inverter drives can induce false flame signals Shielded cables can help reduce interference with the shield connected to ground at the control end only The wire type and its capacitance picofarads or microfarads to ground may cause low signal problems so a grounded shield may decrease the signal due to the cable s internal capacitance Multiple UV tube type sensor leads run together without shielding may interfere or cross talk so the shield or flexible armor must be grounded to prevent this situation For flame rod sensor runs approximately 100 feet 30 meters or greater use Belden P N 8254 RG62 coax cable To achieve the maximum wiring distance the shield should not be grounded keep in mind that an underground shield pro vides less protection against electrical interference Depending on field connections sensor wiring can be up to 200 feet 61 meters Do not ground the shield to terminal GND Unshielded sensor wiring must not be run in common with other wires it must be run in separate conduit Multiple flame sensor wiring must not be run together in a common conduit or wireway Use 14 to 18 AWG wire suitable for 90 C 194 F and 600 volt insulation and run each pair of leads
6. ntended to be wired in the field to become part of a Class 1 circuit only Test Signal Flame Condition RF Relay FLAME ON LED FLAME FAIL LED Terminal 10 o Je J J o fo fo o oe WARRANTIES FIREYE guarantees for one year from the date of installation or 18 months from date of manufacture of its products to replace or at its option to repair any product or part thereof except lamps electronic tubes and photocells which is found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND FIREYE MAKES NO WARRANTY OF MERCHANTABILITY OR ANY OTHER WARRANTY EXPRESS OR IMPLIED Except as specifically stated in these general terms and conditions of sale remedies with respect to any product or part number manufactured or sold by Fireye shall be limited exclusively to the right to replacement or repair as above provided In no event shall Fireye be liable for consequential or special damages of any nature that may arise in connection with such product or part FIREYE MBPF 1001 3 Manchester Road APRIL 4 2013 Derry New Hampshire 03038 USA Supersedes September 12 2011 www fireye com
7. s are combined with equipment manufactured by others and or integrated into systems designed or manufactured by others the Fireye warranty as stated in its General Terms and Conditions of Sale pertains only to the Fireye products and not to any other equipment or to the combined system or it s overall performance ORDERING INFORMATION PART NUMBER DESCRIPTION Flame Sensor Single channel module 120VAC 50 60 Hz use with UV detection or flame rod or both single channel module 120VAC 50 60 Hz use with UV detection or flame rod or both Mounting ears provided for use with MB 600S multiburner programming module single channel module 220VAC 50 60 Hz use with UV detection or flame rod or both Single channel module 220VAC 50 60 Hz use with UV detection or flame rod or both 2 sec FFRT Wiring Base 60 2726 socket 11 pin DIN rail or panel surface mounting Kit retaining secures module on socket 60 2627 129 172 Mounting Rails 60 2539 12 DIN style mounting rail 12 inches mounts up to 4 modules ae BULLETIN MBPF 1008 MB 600PF MBPF 2008 MBPF 2028 MBPF 1001 MB 6001 MBPF 1001 MBPF 1001 133 647 133 658 60 2539 24 DIN style mounting rail 24 inches mounts up to 8 modules ns 60 2539 36 DIN style mounting rail 36 inches mounts up to 12 modules a UV7A4 UV7A4W Ultra violet scanner non self check applications 1 2 NPT mount 4 lead with insulating coupling SC 107 Ultra violet scanner non