Home
        Installation, Start-Up, and Operating Instructions
         Contents
1.                             Air delivery values are without air filter and        for dry coil  See Table 10   48SD Wet Coil Pressure Drop table and Table 8 Filter Pressure Drop       Factory shipped heating cooling speed  NA   Not allowed for heating speed     Note  Deduct field supplied air filter pressure drop and wet coil pressure drop to abtain external static pressure available for ducting     d  Reassemble wheel into housing     e  Reassemble motor into housing  Be sure setscrews are  tightened on motor shaft flats and not on round part of  shaft     f  Reinstall unit access panel     3  Restore electrical power to unit  Start unit and check for  proper blower rotation and motor speeds during heating and  cooling cycles     FLUE GAS PASSAGEWAYS    To inspect the flue collector box and upper areas of the heat  exchanger        Remove the combustion blower wheel and motor assembly  according to directions in the Combustion Air Blower section     2  Remove the 3 screws holding the blower housing to the flue  collector box cover  See Fig  16 19      3  Remove the 12 screws holding the flue collector box cover   See Fig  18   19  to the heat exchanger assembly  Inspect the  heat exchangers     4  Clean all surfaces  as required  using a wire brush     INDUCED DRAFT  COMBUSTION AIR  BLOWER    Clean periodically to assure proper airflow and heating efficiency   Inspect blower wheel every fall and periodically during the heating  season  For the first heating season  inspect b
2.               24   ELECTRICAL CONTROLS AND WIRING                    24   REFRIGERANT CIRCUIT      GAS INPUT                               EVAPORATOR AIRFLOW   METERING DEVICE                                               24   LIQUID LINE STRAINER incitis 24  TROUBLESHOOTING sara niim timet       START UP CHECKLIST       NOTE TO INSTALLER     Before the installation  READ THESE  INSTRUCTIONS CAREFULLY AND COMPLETELY  Also   make sure the User s Manual and Replacement Guide are left with  the unit after installation  The furnace is NOT to be used for  temporary heating of buildings or structures under construction     SAFETY CONSIDERATIONS    Installation and servicing of air conditioning equipment can be  hazardous due to system pressure and electrical components  Only  trained and qualified personnel should install  repair  or service  air conditioning equipment        Manufacturer reserves the right to discontinue  or change at any time  specifications or designs without notice and without incurring obligations     Book  1  4 PC 101  Tab  1a 6a    Printed in U S A     Catalog       4850 15  Pg 1 8 05    Replaces  New    Untrained personnel can perform basic maintenance functions of  cleaning coils and filters  All other operations should be performed  by trained service personnel  When working on air conditioning  equipment  observe precautions in the literature  tags  and labels  attached to the unit  and other safety precautions that may apply     Follow all safety codes 
3.     Based on altitude of 0 to 2000 ft     T Required filter sizes shown are based on the larger of the ARI  Air Conditioning and Refrigeration Institute  rated cooling airflow or the heating airflow velocity of 300  ft minute for high capacity type  Air filter pressure drop for non standard filters must not exceed 0 08 in  wg           7 3  or 7 4 or Can CGA   Canadian Gas Association  B149  Installation Codes or applicable provisions of local building code     Step 5   RIG AND PLACE UNIT       CAUTION  PROPERTY DAMAGE HAZARD       CAUTION    OPERATIONAL HAZARD  Failure to follow this caution may result in unit component    Failure to follow this caution may result in property damage   When installing the unit on a rooftop  be sure the roof will  support the additional weight     damage    Do not restrict condenser airflow  An air restriction at either  the outdoor air inlet or the fan discharge can be detrimental to  compressor life        Use spreader bars or crate top when rigging the unit  The units  must be rigged for lifting  See Fig  7   Refer to Table 1 for  operating weight  Use extreme caution to prevent damage when       The condenser fan pulls air through the condenser coil and  discharges it through the top cover  Be sure that the fan discharge  does not recirculate to the condenser coil  Do not locate the unit in  either a corner or under an overhead obstruction  The minimum  clearance under a partial overhang  such as a normal house  overhang  is 48 in  above t
4.     e        E        Wood nailer            Flashing field  supplied         Flashing field  supplied             Roofcurb        La Roofcurb   Insulation  field  171 supplied           Duct wo rk  field supplied       Insulation  field  supplied                 Roofing materal    Roofing material  field supplied    field supplied                          Duct wo rk  field supplied       Cant strip    Cant strip  field supplied    field supplied                                              N                   Provided with roofcurb         Provided with roofcurb    Roof Curb for Small Cabinet Roof Curb for Large Cabinet  Note A  When unit mounting screw is used Note A  When unit mounting screw is used  retainer bracket must also be used  retainer bracket must also be used                               Tf R A S A         Gasket around     duct  P dd          Insulated   Gasket around  deck pan outer edge    Insulated  deck pan                                        Long  Support t                                  Return opening   BXC     A05165  A B D E F G  UNIT SIZE   ODS CATALOG NUMBER                 IN           IN   MM    IN   MM  IN   MM  IN   MM  IN   MM        A8SD024 030  __CPRFCURBOO6A00 8  203  11 279    161 2  419    28 3 4  730    30 3 8  771    44 5 16  1126    45 15 16  1167   CPRFCURBO007A00 14  356    11 279    161 2  419    28 3 4  730    30 3 8  771    44 5 16  1126    45 15 16  1167   4850036 06    __CPRECURB008A00 8  203    16 3 16  411    17 3 8  441   
5.    1466   1437   1387   1330   1264   1183   1093  Heating Rise    F  29 30 31 31 32 34 36 38 41  Watts   741 715 694 669 645 610 573 544  48SD   N 042060 25 55 Medium CFM   1738   1698   1653   1604   1538   1457   1362   1271  Heating Rise    F    26 27 27 28 29 31 33 35  Watts 798 772 738 700  High CFM 1720   1648   1540   1414  Heating Rise    F  26 27 29 32       20                               Table 9   Dry Coil Air Delivery      Horizontal and Downflow Discharge      Unit 48SD024 060  Deduct 10 percent for 208 Volts                                                                                                                                                                                      UNIT HEATING RISE RANGE    F    MOTOR SPEED EXTERNAL STATIC                            0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9  Watts 625 606 586 571 550 534 509   483   457  Low  CFM 1539   1496   1466   1437   1387   1330   1264   1183   1093  Heating Rise    F  44 45 46 47 49 51 53 57 62  Watts         715 694 669 645 610   573   544  48SD   N 042090 40 70 Medium CFM         1698   1653   1604   1538   1457   1362   1271  Heating Rise    F          40 41 42 44 46 50 53  Watts 772   738   700  High CFM 1648   1540   1414  Heating Rise    F  41 44 48  Watts 627 617 607 584   567   548   528   503    Low CFM 1550   1530   1493   1461   1414   1361   1320   1250      Heating Rise    F  44 44 45 46 48 50 51 54      Watts 771 755 734 711 690 665 639 607   572  48SD   N 048090 25 55 Med
6.    5 yg 91          T  L    Nya               an  4 Nu92T  AuVQNO23S  NUg8   34           1      1  WOI 34  qm            403 318 f LIA  A             aug     49 AUNTS al         134  0      134 LIM           1HM NU8      310N 339   13    Bp  870 ONY 9  14 YOSSIYdNOD    mE                    019 66M                                         134                   LLM    88M                      2  Nua 1     W3O 134  134     wg            KINO SLINN 8  0 9   0   20                                         41103             09 1 0   2 80c  JILVWN3H2S    YIMOd    AlddfiS       X18    118    HOD    01313         05125          208 230 1 60 Wiring Diagram  Units 48 0    Fig  15    14    Table 4   Heating Inputs                      GAS SUPPLY PRESSURE MANIFOLD  INPUT OF Natural Propanet  IN  WG    BTUH   ORIFICES                                  Natural Propanet   40 000 2 4 0 13 0 4 0 13 0 3 5 3 5  60 000 2 4 0 13 0 4 0 13 0 3 5 3 5  90 000 3 4 0 13 0 4 0 13 0 3 5 3 4  115 000 3 4 0 13 0 4 0 13 0 3 5 3 7  130 000 3 4 0 13 0 4 0 13 0 3 5 3 5                           When a unit is converted to propane  different size orifices must be used  See separate  natural to propane conversion kit instructions   T Based on altitudes from sea level to 2000 ft above sea level  For altitudes above 2000 ft  reduce input rating 4 percent for each additional 1000 ft above sea level   In Canada  from 2000 ft above sea level to 4500 ft above sea level  derate the unit 10 percent     Step 2   START UP H
7.    CARBON MONOXIDE POISONING HAZARD  Failure to follow this warning could result in personal injury    or death    The venting system is designed to ensure proper venting  The  flue hood assembly must be installed as indicated in this  section of the unit installation instructions        Install the flue hood as follows     1  This installation must conform with local building codes and  with the National Fuel Gas Code  NFGC   ANSI Z223 1  in  Canada  CAN CGA    149 1  and B149 2       NFPA  National  Fire Protection Association  latest revision  Refer to Provin   cial and local plumbing or wastewater codes and other  applicable local codes     2  Remove flue hood from shipping location  inside the blower  compartment   Place vent cap assembly over flue panel  Orient  screw holes in vent cap with holes in the flue panel     3  Secure flue hood to flue panel by inserting a single screw on  the right side and the left side of the hood     Table 2   Maximum Gas Flow Capacity                             NOMINAL   INTERNAL LENGTH OF PIPE  FTt  IRON RIPE    DIAMETER   ig  IN   10   20   30   40   50   60   70   80   90   100   125   150   175   200   1 2 622 175   120   97   82   73          61   57   53   50   44   40               3 4  824 360   250   200   170   151   138   125   118   110   103   93          77   72   1 1 049 680   465   375   320   285   260   240   220   205   195   175   160   145   135  1 1 4 1 380 1400   950   770   600   580   530   490   460   430   400 
8.    HEATING  amp  COOLING    48SD  Single Packaged Gas Heating   Electric Cooling Units       Visit www carrier com    Installation  Start Up  and Operating Instructions  Size 024 060    NOTE  Read the entire instruction manual before starting the  installation     TABLE OF CONTENTS         SAFETY CONSIDERATIONS    eene inrer rtt 1  INTRODUYCTION            7 rtt                     2  RECEIVING AND INSTALLATION                    eee 2  CHECK EQUIPMENT aicssscssescssssssisssssssssossssenssnssassanssnsonsossoasves 2  IDENTIFY UNIT    tte 2  INSPECT 5                               2  INSTALLATION            ttn e trenes 2  PROVIDE UNIT SUPPORT    enceinte rere 2  ROOF CURB errien ar EH ED n imer ERE  2  GROUND MOUNT                                        4  SLAB MOUNT            Van                4  FIELD FABRICATE  DUCTWORK           nnn 6       PROVIDE CLEARANCES                                 7  RIG AND PLACE           trt ren 7  CONNECT CONDENSATE                                                  7  INSTALE BE UB HOOD               erede 8  INSTALL GAS PIPING        eet cher rr ren rox sese 9  INSTALL DUCT CONNECTIONS                                        10   CONFIGURING UNITS FOR DOWNFLOW  VERTI    CAL  DISCHARGE           tete terne 10          INSTALL ELECTRICAL CONNECTIONS                           11  HIGH VOLTAGE CONNECTIONS                              11  SPECIAL PROCEDURES FOR 208 V OPERATION    12  CONTROL VOLTAGE CONNECTIONS                          12  HEAT A
9.    On a call for heating  terminal            of the thermostat is energized   starting the induced draft motor  When the hall effect sensor on  the induced draft motor senses that it has reached the required  speed  the burner sequence begins  This function is performed by  the integrated gas control  IGC   The indoor  evaporator  fan  motor is energized 45 sec  after flame is established  When the  thermostat is satisfied and        is de energized  the burners stop  firing and the indoor  evaporator  fan motor shuts off after a  45 sec  time off delay     An LED  light emitting diode  indicator is provided on the control  board to monitor operation  The control board is located by  removing the burner access panel  During normal operation  the  LED is continuously on  See Table 5 for error codes      Table 5   LED Indications  ERROR CODE LED INDICATION                                     Normal Operation On  Hardware Failure Off  Fan On Off Delay Modified 1 Flash   Limit Switch Fault 2 Flashes  Flame Sense Fault 3 Flashes  Four Consecutive Limit Switch Faults 4 Flashes  Ignition Lockout Fault 5 Flashes  Induced Draft Motor Fault 6 Flashes  Rollout Switch Fault 7 Flashes  Internal Control Fault 8 Flashes  Temporary lock out  1 hr  9 Flashes    NOTES    1  There is a 3 sec  pause between error code displays    2  If more than one error code exists  all applicable error codes will be  displayed in numerical sequence   3  This chart is on the wiring diagram located inside the 
10.   360   325   300   280  1 1 2 1 610   2100   1460   1180   990   900   810   750   690   650   620   550   500   460   430                                             Capacity of pipe in cu ft of gas per hr for gas pressure of 0 5 psig or less  Pressure drop of 0 5 in  wg  based on a 0 60 specific gravity gas   Refer to Table C 4  National    Fire Protection Association NFPA 54   T This length includes an ordinary number of fittings     Step 8   INSTALL GAS PIPING    The gas supply pipe enters the unit through the access hole  provided  The gas connection to the unit is made to the 1 2 in  FPT  gas inlet on the manual shutoff or gas valve     Install a gas supply line that runs to the heating section  Refer to  Table 2 and the NFGC for gas pipe sizing  Do not use cast iron  pipe  It is recommended that a black iron pipe is used  Check the  local utility for recommendations concerning existing lines  Size  gas supply piping for 0 5 in  wg maximum pressure drop  Never  use pipe smaller than the 1 2 in  FPT gas inlet on the unit gas  valve     For natural gas applications  the gas pressure at unit gas connection  must not be less than 4 0 in  wg or greater than 13 in  wg while the  unit is operating  For propane applications  the gas pressure must  not be less than 7 0 in  wg or greater than 13 in  wg at the unit  connection     An 1 8 in  NPT plugged tapping  accessible for test gage connec   tion  must be installed immediately upstream of the gas supply  connection to the gas
11.   550 5   249 6     9 83   21 67   9 83     REAR VIEW    CLEARANCE TO COMBUSTIBLE MATL     Refer to Maximum Operating Clearances     TOP OF UNIT  DUCT SIDE OF UNIT   SIDE OPPOSITE DUC  BOTTOM OF UNIT          NEC  REQUIRED CLEARANCES     BETWEEN UNITS  POWER ENTRY SIDE        546 1 254 0   21 501  10 001          E 042 ONLY      NAL riae               16 001             018     COND  COIL       NON BENT       INCHES  mm        INCHES  mm   42 00  1066 8     UNIT AND UNGROUNDED SURFACES  POWER ENTRY SIDE  36 00  914 0     UNIT AND BLOCK OR CONCRETE WALLS AND OTHER  GROUNDED SURFACES  POWER ENTRY SIDE    LEGEND    CG   Center of Gravity   COND   Condensor   EVAP   Evaporator   NEC   National Electrical Code  REQ D   Required    NOTE  Dimensions are in in   mm     EM           198 5                   e amp Q       FIELD ENTRY  SERVICE PORTS      42 00  1066 8          COND  COIL             EVAP  COIL     TOP VIEW    REQUIRED CLEARANCE FOR OPERATION AND SERVICING    EVAP  COIL ACCESS SIDE  POWER ENTRY SIDE    EXCEPT FOR            UNIT TOP     SIDE OPPO  DUCT PANEL        MINIMUM DISTANCES  IF UNIT IS PLACED LESS THAN 12 00  304 8  FROM  WALL SYSTEM  THEN SYSTEM PERFORMANCE MAYBE COMPROMISE     INCHES  mm   36 00  914 0   42 00  1066 8     48 00  1219 2   36 00  914 0                   31 44     1193 9   47 001          28 6  1 13  DIA  K 0                                                 POWER ENTRY    22 2  0 88  DIA  HOLE  CONTROL ENTRY                            12 7  0 50  N
12.   Clean or replace filter as necessary        Gas input to furnace too low    Check gas pressure at manifold match with that on  unit nameplate        Unit undersized for application    Replace with proper unit or add additional unit        Restricted airflow    Clean or replace filter  Remove any restriction        Blower speed too low    Use faster speed tap if available  or install alternate  motor        Limit switch cycles main burners    Check rotation of blower  thermostat heat anticipator settings   temperature rise of unit  Adjust as necessary        Poor flame characteristics        Incomplete combustion results in   Aldehyde odors  carbon monoxide  sooting  flame  floating flame    26       1 Tighten all screws around burner compartment   2  Cracked heat exchanger  Replace   3  Unit overfired  Reduce input  change orifices or  adjust gas line or manifold pressure    4  Check burner alignment   5  Inspect heat exchanger for blockage  Clean as necessary     SYMPTOM    Table 13   Troubleshooting Guide LED Error Codes    CAUSE    REMEDY       Hardware failure    LED OFF     Loss of power to control module  IGC       Check 5 amp fuse on IGC   power to unit  24   v circuit breaker  and  transformer  Units without a 24   v circuit breaker have an internal  overload in the 24   v transformer  If the overload trips  allow 10 min   utes   for automatic reset        Fan ON OFF delay modified   LED FLASH     High limit switch opens during heat  exchanger warm up period before 
13.   See Table 3 for electrical data      The field supplied disconnect switch box may be mounted on the  unit over the high voltage inlet hole when the standard power and  low voltage entry points are used  See Fig  2 and 3 for acceptable  location      See unit wiring label and Fig  11 for reference when making high  voltage connections  Proceed as follows to complete the high   voltage connections to the unit              are EIS  HIGH VOLTAGE  POWER LEADS   49977 7     SEE UNIT WIRING PONER  LABEL  a  FIELD SUPPLIED  a FUSED DISCONNECT    CONTROL BOX       WHT W1  p  LYEL Y  p  THERMOSTAT  GRN G   LOW VOLTAGE    TYPICAL   POWER LEADS   RED R       SEE UNIT  WIRING LABEL    BRN C   SPLICE BOX m    Fig  11   High  and Control Voltage Connections    Single phase units     1  Run the high voltage  L1  L2  and ground leads into the  control box     2  Connect ground lead to chassis ground connection     3  Connect L1 to pressure lug connection 11 of the compressor  contactor     4  Connect L2 to pressure lug connection 23 of the compressor  contactor     Table 3   Electrical Data   Unit 48SD                         UNIT ANGES COMPRESSOR n n MIR POWER SUPPLY  SIZE V PH HZ   48SD Min   Max RLA LRA FLA FLA MCA          024   208 230 1 60   187   253 10 9 54 0 09 20 16 5 16 5 20 20  030   208 230 1 60   187   253 140 72 5 0 9 20 20 4 20 4 25 25  036   208 230 1 60   187   253 16 0 88 0 0 9 34 24 0 24 0 30 30  042   208 230 1 60   187   253 18 4 104 0 09 44 28 0 28 0 35 35  048   208 
14.   compare outdoor air tem   perature    F db  with the suction line pressure  psig  to  determine desired system operating suction line temperature   See Table 7     6  Compare actual suction tube temperature with desired  suction tube temperature  Using a tolerance of   3  F  add  refrigerant if actual temperature is more than 3  F higher than  proper suction tube temperature  or remove refrigerant if    actual temperature is more than 3  F lower than required  suction tube temperature     NOTE  If the problem causing the inaccurate readings is a  refrigerant leak  refer to the Check for Refrigerant Leaks section     INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS    A CAUTION       UNIT OPERATION HAZARD   Failure to follow this caution may result in unit damage   For cooling operation  the recommended airflow is 350 to 450  cfm for each 12 000 Btuh of rated cooling capacity  For  heating operation  the airflow must produce a temperature rise  that falls within the range stamped on the unit rating plate        Table 9 shows the temperature rise at various airflow rates  Table  9 shows both heating and cooling airflows at various external static  pressures  Refer to these tables to determine the airflow for the  system being installed  See Table 10 for wet coil pressure drop      NOTE  Be sure that all supply  and return air grilles are open   free from obstructions  and adjusted properly     A WARNING    FIRE  EXPLOSION AND ELECTRICAL SHOCK HAZ   ARD    Failure to follow this warning
15.  0 50  12 7   NEC  REQUIRED CLEARANCES    INCHES  mm   BETWEEN UNITS  POWER ENTRY SIDE                 42 00  1066 8     UNIT AND UNGROUNDED SURFACES  POWER ENTRY SIDE  36 00  914 0   UNIT AND BLOCK OR CONCRETE WALLS AND OTHER  GROUNDED SURFACES  POWER ENTRY SIDE                          42 00  1066 8        E    EXCEPT FOR NEC REQUIREMENTS   UNIT TOP  SIDE OPPOSITE DUCTS  DUCT PANEL       48 00  1219 2   36 00  914 0      12 00  304 8                 MINIMUM DISTANCES  IF UNIT IS PLACED LESS THAN 12 00  304 8  FROM  WALL SYSTEM  THEN SYSTEM PERFORMANCE MAYBE COMPROMISE     LEGEND   CG   Center of Gravity   COND   Condensor   EVAP   Evaporator   NEC   National Electrical Code  REQ   D   Required       je    15 4 NOTE  Dimensions are in in   mm        11    1090 6    142 94        FIELD ENTRY 23 0 4     SERVICE PORT  0 911                 4 54           28 6  1 13  DIA  K              0   POWER ENTRY          22 2  0 88  DIA  HOLE   CONTROL ENTRY                      620 2   24 42                        12 951          12 4   2 85  1226 3       j 7 d   42 1 46 8         11 68  OMPRESSOR  BLOWER  GAS SECTION  1 84  12 7 10 501 N P T   329 0  amp  ELECTRICAL ACCESS PANEL      GAS ENTRY                                   FLUE HOOD          5 0   0 201           44 22       1123 1  48 281                LEFT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW A05142  CENTER OF GRAVITY  UNIT ELECTRICAL CHARACTERISTICS   UNIT WEIGHT   UNIT    IN         IN   MM   Ib kg X Y 7  48SD036060 090 208 230
16.  1 60 433 0   196 0 42 98  1092 0  21 0  533 0    20 5  520 0    16 6  422 0   48SD042060 090 208 230 1 60 460 0   209 0 46 98  1193 0  21 0  533 0    20 5  520 0    17 1  434 0   48SD048090 115 130 208 230 1 60 480 0   218 0 46 98  1193 0  21 0  533 0    20 0  508 0    17 4  442 0   48SD060090 115 130 208 230 1 60 492 0   223 0 46 98  1193 0  21 0  533 0    20 0  508 0    17 6  447 0              Fig  3   48SD036     Curb should be level to within 1 4 in  This is necessary for unit  drain to function properly  Refer to accessory roof curb installation  instructions for additional information as required     GROUND MOUNT    The unit may be installed either on a slab or placed directly on the  ground if local codes permit  Place the unit on level ground  prepared with gravel for condensate discharge                 060 Unit Dimensions    SLAB MOUNT    Place the unit on a solid  level concrete pad that is a minimum of  4 in  thick with 2 in  above grade  The slab should be flush on the  compressor end of the unit  to allow condensate drain installation   and should extend 2 in  on the three remaining sides of the unit   See Fig  6   Do not secure the unit to the slab except when  required by local codes         VACunit  base                 Gask eting  inner flange         Screw   NOTE A        Screw   NOTE A     Gasketing  inner flange            f                             Gasketing     Gasketing  outer flange    outer flange      qu                    W     Wood nailer    
17.  40 1 4  1022    41 15 16  1065    44 7 16  1129    46 1 16  1169   CPRFCURBO09A00 14  356    16 3 16  411    17 3 8  441    40 1 4  1022    41 15 16  1065    44 7 16  1129    46 1 16  1169     NOTES      Roof curb must be set up for unit being installed      Seal strip must be applied  as required  to unit being installed      Dimensions in     are in millimeters      Roof curb is made of 16 gage steel    Table lists only the dimensions  per part number  that have changed    Attach ductwork to curb  flanges of duct rest on curb       Insulated panels  1 in  thick fiberglass 1 Ib density      Dimensions are in inches      When unit mounting screw is used  see Note A   a retainer bracket must be used as well  This bracket must also be used when required by code for hurricane or    Seismic conditions  This bracket is available through Micrometl     Fig  4   Roof Curb Dimensions  5                                0 00              C00070                                  48SD                 024 030 036 042 048 060   1 69 74 87 93 97 99   2 53 57 68 72 74 76   3 83 88 104 111 116 119   4 138 147 174 184 193 198  TOTAL WEIGHT 343 366 433 460 480 492   Fig  5   48SD Unit Corner Weights  in Pounds           C99014    Fig  6   Slab Mounting Details    Step 3   FIELD FABRICATE DUCTWORK    Secure all ducts to roof curb and building structure on vertical  discharge units  Do not connect ductwork to unit  For horizontal  applications  unit is provided with flanges on the horizontal  openi
18.  CAUTION    UNIT DAMAGE HAZARD  Failure to follow this caution may result in component    damage and cause flame impingement of burners and heat  exchangers   When servicing gas train  do not hit or plug orifice spuds        Removal of Gas Train  To remove the gas train for servicing   1  Shut off main gas valve     Shut off power to unit and install lockout tag     Remove unit access panel  See Fig  17      Disconnect gas piping at unit gas valve   Remove wires connected to gas valve  Mark each wire       Remove ignitor and sensor wires at the ignitor module          t ROO P      Remove the mounting screw that attaches the burner rack to  the unit base  See Fig  16      8  Slide the burner rack out of the unit  See Fig  16 and 19     9  To reinstall  reverse the procedure outlined above   CONDENSER COIL  EVAPORATOR COIL  AND  CONDENSATE DRAIN PAN    Inspect the condenser coil  evaporator coil  and condensate drain  pan at least once each year or more often if necessary     The coils are easily cleaned when dry  therefore  inspect and clean  the coils either before or after each cooling season  Remove all  obstructions  including weeds and shrubs  that interfere with the  airflow through the condenser coil     Straighten bent fins with a fin comb  If coated with dirt or lint   clean the coils with a vacuum cleaner  using the soft brush    Table 10   48SD Wet Coil Pressure Drop                                                                                           UNIT SIZE 
19.  Heating Rise    F  32 33 34 36 37 39 40 42      Watts 1012   993 981 963 948 927 904 886      High CFM 2184   2109   2036   1963   1886   1812   1729   1647      Heating Rise    F  31 32 33 34 36 37 39 41      Watts 786 769 754 736   722   705 684 658    Low  CFM 2027   1960   1901   1821   1759   1693   1616   1513      Heating Rise    F  43 44 45 47 49 51 53 57    Watts 873 849 833 815 798 782 763 748      48SD   N 060115 35 65 Medium CFM 2095   2026   1962   1887   1817   1748   1679   1583      Heating Rise    F  41 43 44 46 47 49 51 54     Watts 1012   993 981 963 948 927 904 886    High CFM 2184   2109   2036   1963   1886   1812   1729   1647 m  Heating Rise    F  39 41 42 44 46 48 50 52                    21                               Table 9   Dry Coil Air Delivery      Horizontal and Downflow Discharge      Unit 48SD024 060  Deduct 10 percent for 208 Volts                                      EXTERNAL STATIC PRESSURE  WC   UNIT HEATING RISE RANGE   F    MOTOR SPEED   0 2 0 3 0 4 0 5 0 6 0 7 0 8   0 9  Watts 769 754 736 722 705 684 658      CFM 1960   1901   1821   1759   1693   1616   1513        Heating Rise    F  50 51 54 55 58 60 64    Watts 849 833   815 798   782   763   748        48SD   N 060130 40 70 CFM 2026   1962   1887   1817   1748   1679   1588        Heating Rise    F  48 50 52 54 56 58 62    Watts 993   981 963 948 927   904   886        CFM 2109   2036   1963   1886   1812   1729   1647        Heating Rise    F  46 48 50 52 54 56 59             
20.  P T                    12 00  304 8                   CHEESE ER enn wm         1226 3  2 08     ure  831 0  48 28  122 2     32 721  4 81   LEFT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW A05166  CENTER OF GRAVITY  UNIT WEIGHT  UNIT ELECTRICAL CHARACTERISTICS        c IN   MM  IN   MM   Ib kg X Y 7  4850024040 060 208 230 1 60 343 0 156 0 39 02  991 0  20 0  508 0    19 3  490 0    17 6  447 0   4850030040 060 208 230 1 60 366 0 166 0 41 02  1042 0  20 0  508 0    14 0  356 0    13 0  330 0                          Fig  2   48SD024 030 Unit Dimensions    3                      355 8 355 8 p    14 01   14 01                                                                      86 0       3 391  RETURN SUPPLY  n        ___  _ ________   p o   OPTIONAL optional  406 6         RETURN supply  1 406 6   16 01     AIR AIR     16 01     OPENING       OPENING            Tm    B      a                       COND  COIL T               80 5  4636 SUPPL RETURN           115 831 OPENING OPENING Y ll M  EVAP  COIL     S Jl 173 5       Ezzzzzz           2  6 83                     4 63  OND  COIL  MX  T                  TOP VIEW  REAR VIEW  REQUIRED CLEARANCE TO COMBUSTIBLE MATL  REQUIRED CLEARANCE FOR OPERATION AND SERVICING       INCHES  mm    Refer to Maximum Operating Clearances  INCHES  mm  EVAP  COIL ACCESS SIDE    36 00  914 0   TOP OF UNIT   14 00  355 6  POWER ENTRY SID    42 00  1066 8                DUCT SIDE OF UNIT  2 00  50 8   SIDE OPPOSITE DUCTS      14 00  355 6   BOTTOM OF UNIT 2
21.  Unit 48SD  Continued                                                        UNIT SIZE 48SD 048090 048115 048130 060090 060115 060130  NOMINAL CAPACITY  ton  4 4 4 5 5 5  OPERATING WEIGHT  Ib   480 480 480 492 492 492   COMPRESSORS Scroll   Quantity 1  REFRIGERANT  R 22   Quantity  Ib   12 3 12 3 12 3 12 0 12 0 12 0  REFRIGERANT METERING DEVICE Accurater  Orifice ID  in    088  088  088  101  101  101                   2   21 2   21 2   21 2   21 2   21 2   21  Face Area  sq ft  19 4 19 4 19 4 19 4 19 4 19 4  ee 3300 3300 3300 3300 3300 3300  Diameter         22 22 22 22 22 22  Motor Hp  Rpm     1100      1100  14  1100     1100     1100     1100   Bici        4   15 4   15 4   15 4   15 4   15 4   15  Face Area  sq fl  4 7 4 7 4 7 4 7 4 7 4 7                           1600 1600 1600 1750 1750 1750  Size  in   11 X 10 11 X 10 11 X 10 11 X 10 11 X 10 11 X 10  Motor Hp  Rpm  1 2  1075  1 2  1075  1 2  1075  1 0  1040  1 0  1040  1 0  1040   FURNACE SECTION   Burner Orifice No   Qty   Drill Size  3   38 3  33 3 31 3 38 3 33 3 31  Natural Gas        3   46 3   42 3   41 3   46 3   42 3   41  Burner Orifice No   Qty   Drill Size   Propane Gas  RETURN AIR FILTERS  in  t 24 X 36 X 1  Throwaway      Based on altitude of 0 to 2000 ft     T Required filter sizes shown are based on the larger of the ARI  Air Conditioning and Refrigeration Institute  rated cooling airflow or the heating airflow velocity of 300  ft minute for high capacity type  Air filter pressure drop for non standard f
22.  Wear safety glasses and work gloves  Use  quenching cloth for unbrazing operations  Have fire extinguisher  available for all brazing operations     A WARNING    FIRE  EXPLOSION  ELECTRICAL SHOCK AND CAR   BON MONOXIDE POISONING HAZARD   Improper installation  adjustment  alteration  service  mainte   nance  or use can cause carbon monoxide poisoning  fire  or  an explosion which can result in personal injury or unit  damage  Consult a qualified installer  service agency  or gas  supplier for information or assistance  The qualified installer  or agency must use only factory authorized kits or accessories  when modifying this product           A WARNING    FIRE  EXPLOSION AND ELECTRICAL SHOCK HAZ   ARD  Failure to follow this warning could result in personal injury     death and or property damage    Before performing service or maintenance operations on unit   turn off gas supply to unit  Then turn off unit main power  switch and install lockout tag  Electrical shock or explosion  could cause serious injury or death     Recognize safety information  This is the safety alert symbol A     When you see this symbol in instructions or manuals  be alert to  the potential for personal injury     Understand the signal words DANGER  WARNING  CAUTION   and NOTE  These words are used with the safety alert symbol   DANGER identifies the most serious hazards which will result in  serious injury or death  WARNING signifies a hazard which could  result in serious injury or death  CAUTION 
23.  could result in personal injury  death and or property damage    Before changing blower speed  shut off gas supply  Then  disconnect electrical power to the unit and install lockout tag        Airflow can be changed by changing the lead connections of the  indoor  evaporator  fan motor     All 48SD units are factory wired for low speed  except sizes 030  and 048 which are wired for medium speed     For 208 230V  For color coding on the 208 230V motor leads  see Table 6     Table 6 Color Coding for 208 230 V Motor Leads    BLACK   HIGH SPEED  Blue medium speed  Red   low speed       To change the speed of the indoor  evaporator  fan motor  remove  the fan motor speed leg lead from the blower relay  BR   This wire  is attached to terminal BM of the integrated gas control  IGC   board for single phase units  To change the speed  remove and  replace with lead for desired blower motor speed   nsulate the  removed lead to avoid contact with chassis parts     COOLING SEQUENCE OF OPERATION    With the room thermostat SYSTEM switch in the COOL position  and the FAN switch in the AUTO  position  the cooling sequence  of operation is as follows     1  When the room temperature rises to a point that is slightly  above the cooling control setting of the thermostat  the  thermostat completes the circuit between thermostat terminal  R to terminals Y and G  These completed circuits through the  thermostat     2  The normally open contacts of energized contactor  C  close  and complete the c
24.  must be measured to determine the input of  propane gas units     Measure Gas Flow  Natural Gas Units     Minor adjustment to the gas flow can be made by changing the  manifold pressure  The manifold pressure must be maintained  between 3 4 and 3 6 in  wg    If larger adjustments are required  change main burner orifices  following the recommendations of national and local codes   NOTE  All other appliances that use the same meter must be  turned off when gas flow is measured at the meter     NOTE  Make sure that gas supply has been purged  and that all  gas piping has been checked for leaks     CHECK HEATING CONTROL    Start and check the unit for proper heating control operation as  follows  see furnace lighting instructions located inside burner or  blower access panel      1  Place room thermostat SYSTEM switch in the HEAT position  and the fan switch is placed in AUTO position    Set the heating temperature control of the thermostat above  room temperature     3  The induced draft motor will start   Proceed as follows     4  After a call for heating  the main burner should light within 5     sec  If the burners do not light  there is a 22 sec  delay before 1  Turn off gas supply to unit   another 5 sec  try  If the burners still do not light  this 2  Remove pipe plug on manifold  See Fig  13  and connect  sequence is repeated  If the burners do not light within 15 manometer  Turn on gas supply to unit   minutes from the initial call for heat  there is a lockout  To 3  R
25.  revolution     3600   32   112 5     3  112 5 x 1 2112 5 f    of gas flow hr   4  112 5 x 1050   118 125 Btuh input     If the desired gas input is 115 000 Btuh  only a minor change in the  manifold pressure is required     Observe manifold pressure and proceed as follows to adjust gas  input      Remove cover screw over regulator adjustment screw on gas  valve     2  Turn regulator adjustment screw clockwise to increase gas  input  or turn regulator adjustment screw counterclockwise to  decrease input  Manifold pressure must be between 3 4 and  3 6 in  wg  Unsafe operation of the unit may result if manifold  pressure is outside this range  Personal injury or unit damage  may result     A WARNING       FIRE AND UNIT DAMAGE HAZARD   Failure to follow this warning couild result in personal injury   death and or property damage    Unsafe operation of the unit may result if manifold pressure  is outside this range  Serious injury   death or unit damage  may result        3  Replace cover screw cap on gas valve     4  Turn off gas supply to unit  Remove manometer from pressure  tap and replace pipe plug on gas valve  Turn on gas to unit and  check for leaks     Measure Manifold Pressure  Propane Units     The main burner orifices on a propane gas unit are sized for the  unit rated input when the manifold pressure reading matches the  level specified in Table 4     Proceed as follows to adjust gas input on a propane gas unit   1  Turn off gas to unit   2  Remove pipe plug on manif
26.  units with an outer and inner condenser coil  be sure to clean  between the coils  Be sure to flush all dirt and debris from the unit  base     Inspect the drain pan and condensate drain line when inspecting  the coils  Clean the drain pan and condensate drain by removing all  foreign matter from the pan  Flush the pan and drain tube with  clear water  Do not splash water on the insulation  motor  wiring   or air filter s   If the drain tube is restricted  clear it with a     plumbers snake  or similar probe device  Ensure that the auxiliary  drain port above the drain tube is also clear     CONDENSER FAN       CAUTION    OPERATIONAL HAZARD  Failure to follow this caution may result in unit component    damage    Keep the condenser fan free from all obstructions to ensure  proper cooling operation  Never place articles on top of the  unit  Damage to unit may result     1  Remove 6 screws holding condenser grille and motor to top  cover     2  Turn motor grille assembly upside down on top cover to  expose the fan blade     3  Inspect the fan blades for cracks or bends     4  If fan needs to be removed  loosen the setscrew and slide the  fan off the motor shaft     5  When replacing fan blade  position blade so the hub is 1 8 in   away from the motor end  1 8 in  of motor shaft will be  visible  See Fig  12      6  Ensure that setscrew engages the flat area on the motor shaft  when tightening     7  Replace grille   ELECTRICAL CONTROLS AND WIRING    Inspect and check the elect
27.  valve     When installing the gas supply line  observe local codes pertaining  to gas pipe installations  Refer to the NFGC ANSI Z223 1 1988  NFPA latest edition  in Canada  CAN CGA B149 1   2    86   In  the absence of local building codes  adhere to the following  pertinent recommendations     1  Avoid low spots in long runs of pipe  Grade all pipe 1 4 in  in  every 15 ft to prevent traps  Grade all horizontal runs  downward to risers  Use risers to connect to heating section  and to meter     2  Protect all segments of piping system against physical and  thermal damage  Support all piping with appropriate straps   hangers  etc  Use a minimum of one hanger every 6 ft  For    pipe sizes larger than 1 2 in   follow recommendations of  national codes     3  Apply joint compound  pipe dope  sparingly and only to male  threads of joint when making pipe connections  Use only pipe  dope that is resistant to action of liquefied petroleum gases as  specified by local and or national codes  Never use Teflon  tape     4  Install sediment trap in riser leading to heating section  See  Fig  9   This drip leg functions as a trap for dirt and  condensate     TEE             T NIPPLE  a iim CAP    C99020    Fig  9   Sediment Trap    5  Install an accessible  external  manual main shutoff valve in  gas supply pipe within 6 ft of heating section     6  Install ground joint union close to heating section between  unit manual shutoff and external manual main shut off valve     7  Pressure tes
28. 230 1 60   187   253 18 3 109 0 15 44 28 5 28 5 35 35  060   208 230 1 60   187   253   250 148 0 15 62 39 0 39 0 50 50                   LEGEND  FLA     Full Load Amps C UL US    LRA       Locked Rotor Amps     MCA     Minimum Circuit Amps   MOCP     Maximum Overcurrent Protection   RLA       Rated Load Amps   NOTES     1  In compliance with NEC  National Electrical Code  requirements  for multimotor and combination load equipment  refer to NEC  Articles 430 and 440   the overcurrent protective device for the  unit shall be Power Supply fuse  The CGA  Canadian Gas  Association  units may be fuse or circuit breaker    2  Minimum wire size is based on 60 C copper wire  If other than  60 C wire is used  or if length exceeds wire length in table     determine size from NEC   C99024    Table 3   Legend  SPECIAL PROCEDURES FOR 208 V OPERATION    A WARNING       FIRE  EXPLOSION AND ELECTRICAL SHOCK HAZ   ARD   Failure to follow this warning could result in personal injury   death and or property damage    Before making any wiring changes  make sure the gas supply  is switched off first  Then switch off the power supply to the  unit and install lockout tag        CONTROL VOLTAGE CONNECTIONS    Do not use any type of power stealing thermostat  Unit control  problems may result     Use no  18 American Wire Gage  AWG  color coded  insulated   35 C minimum  wires to make the control voltage connections  between the thermostat and the unit  If the thermostat is located  more than 100 ft 
29. 32 34 37 40  Watts 411 405 398 390 379 357 357      48SD   N 030040 20 50 Medium  CFM 1195   1155   1100   1028   957 868 769      Heating Rise    F  25 26 27 29 31 35 39          Watts 477 467 447 435      High CFM 1185   1088   970 853    Heating Rise    F  25 28 31 35      Watts 311 309 304 301  Low CFM 935 885 820 757  Heating Rise    F  48 51 55 59  Watts 411 405 398 390 379 357   357      48SD   N 030060 35 65 Medium  CFM 1195   1155   1100   1028   957 868 769          Heating Rise    F  38 39 41 44 47 52 59          Watts 477 467 447 435    High CFM 1185   1088   970 853    Heating Rise    F  38 41 46 53      Watts 437   433 424   417   403 391 379 362    Low  CFM 1353   1318   1283   1235   1187   1123   1059   975      Heating Rise    F  33 34 35 36 38 40 42 46    Watts             531 516   496   478   459   435  48SD   N 036060 25 55 Medium CFM         1489   1437   1362   1289   1208   1099  Heating Rise    F            30 31 33 35 37 41  Watts 629 602  High CFM 1470   1357  Heating Rise    F  31 33  Watts 437   433 424   417   403 391 379 362    Low  CFM 1353   1318   1283   1235   1187   1123   1059   975      Heating Rise    F  50 51 53 55 57 60 64 69    Watts            531 516   496   478   459   435  48SD   N 036090 40 70 Medium CFM             1489   1437   1362   1289   1208   1099  Heating Rise    F        45 47 50 52 56 61  Watts 629 602  High CFM 1470   1357  Heating Rise   F  46 50  Watts 625 606 586 571 550 534   509   483   457  Low  CFM 1539   1496
30. EATING AND MAKE ADJUST     MENTS    When the gas supply being used has a different heating value or  specific gravity  refer to national and local codes  or contact  your distributor to determine the required orifice size        CAUTION    UNIT DAMAGE HAZARD  Failure to follow this caution may result in component  damage due to flame impingement of burners and heat  exchangers    Do Not redrill an orifice  Improper drilling  burrs  out of   round holes  etc   can cause excessive burner noise and  misdirection of burner flame  If orifice hole appears damaged  or it is suspected to have been redrilled  check orifice hole  with a numbered drill bit of correct size        CAUTION             UNIT OPERATION HAZARD   Failure to follow this caution may result in improper unit  operation    Complete the required procedures given in the Pre Start Up  section before starting the unit           Do not jumper any safety devices when operating the unit     Make sure that burner orifices are properly aligned  Unstable  operation may occur when the burner orifices in the manifold are  misaligned        ADJUST GAS INPUT    Follow the lighting instructions on the heating section operation  label  located inside the burner or blower access door  to start the    The gas input to the unit is determined by measuring the gas flow  heating section     at the meter or by measuring the manifold pressure  Measuring the  gas flow at the meter is recommended for natural gas units  The  manifold pressure
31. NTICIPATOR SETTING                      eee 12  TRANSFORMER PROTECTION                          ee 12   PRESTAR T  UP saoi                                  12  START UP                 E EAE 13   CHECK FOR REFRIGERANT LEAKS                                 13   START UP HEATING AND MAKE ADJUSTMENTS       15  CHECK HEATING CONTROL                       eee 15  CHECK GAS INPUT                      ADJUST GAS INPUT   CHECK BURNER FLAME            16  AIRFLOW AND TEMPERATURE                                 16  HEATING SEQUENCE OF OPERATION                       16  LIMIT SWITCHES          16  ROLLOUT SWITCH                          ensure 16   START UP COOLING AND MAKE ADJUSTMENTS      17  CHECKING COOLING CONTROL OPERATION         17  CHECKING AND ADJUSTING REFRIGERANT  CHARGE       aea ah nen nee av 17  INDOOR AIRFLOW AND AIRFLOW ADJUST   MENTS                 M             17  COOLING SEQUENCE OF OPERATION                       18                                      nie eet einen Y eror ves be sey HEADS 18  AIR              d                          18  EVAPORATOR BLOWER AND MOTOR                      18  FLUE GAS PASSAGEWAYS                                           22    S44                A99338  Fig  1   Unit 48SD   Low NO  Model Available    COMBUSTION AIR                                                     22   LIMIT SWITCH      BURNER IGNITION     MAIN                              CONDENSER COIL  EVAPORATOR COIL  AND   CONDENSATE DRAIN PAN    22   CONDENSER            
32. OLIMS 1001108      9010              pes                                      10 3015102 5   010          8000110 W40 DE                SV9          AR  HOLIMS LIMIT  1 ONIUIM 1N3S3Hd3H 01 LON  YOLOW        YOOONT nil CAINO 191143104  YOLOW 13 80 032101 NOI NOWNOD 31V210NI 01      8311081802 SNIUIM  LINN SY9 031V89831NI 291 WNOI1dO      AYOSS3D9          3011591    ONTYIM YIMOd 01313       UINYOASNVYL                HOIH               ONINIM 108109 01313          WOSN3S 193333          SH ONIYIM AYOLIVI         Av138 3ATVA 579 YA  0392 VW  321145                  ano 32114      3514 ni  0                                     40    3  IWV14 54                 TWNINYIL CO  321145 03147  JIN  34 03931  193    02510     1123  SY9 501 SISSWHD 39897       5  410   H  24V   15     1135 N01123S  i TOULNOD        3000  1   5055399002  1011235  430        8000110             1N3439NV4UV LNANOdWOD LINN       050 NO n18                     9 21         134 LLM            9 ZIM    nua OLM            JJOONVIS NYHL    03041039                                         028                     9            9 81M  NYG 01M    OE                                                                                        NOWWO2       1  150483  1  07313                                                                     0   734  NaS 3Wv14             vag             A9W                  251  197    n18  ng 038 M  G ILON 335                             201     27   01        034 ELM       im X08 301145 Av
33. Rollout switch fault    LED 7 flashes     Rollout switch has opened     Rollout switch will automatically reset  but IGC  will continue to lock   out unit  Check gas valve operation  Ensure that induced draft  blower wheel is properly secured to motor shaft  Inspect Heat Ex   changer  Reset unit at unit disconnect        Internal control fault    LED 8 flashes     Microprocessor has sensed an error in the  software or hardware     If error code is not cleared by resetting unit power  replace the IGC         Temporary software lock out    LED 9 flashes        Electrical interference  impeding IGC software       Reset 24 v  to control board or turn thermostat off   then on again  Fault will automatically  reset itself in one  1  hour       WARNING   If the IGC must be replaced  be sure to ground yourself to dissipate any electrical charge that may be present before handling new control board  The  IGC is sensitive to static electricity and may be damaged if the necessary precautions are not taken     IMPORTANT  Refer to Table 12   Troubleshooting Guide   Heating for additional troubleshooting analysis   LEGEND    IGC     Integrated Gas Unit Controller  LED     Light Emitting Diode    277    START UP CHECKLIST   Remove and Store in Job File     I  PRELIMINARY INFORMATION    MODEL       corir e teg   SERIAL INO       dedans pde diee  DATE                  TECHNICIAN                                            JOB  LOCATION  3 8 eme eem    II  PRE START UP  insert checkmark in box 
34. STANDARD CFM  S C F M     48SD 600 700 800 900 1000   1100   1200   1300   1400   1500   1600   1700   1800   1900   2000   024  030  037  044    053  063                       030    037  044    053  063  072  081  105       036      038  044  051  059  065  072  080         042    044  051  059  065  072  080  088  095  105     048      044  050  053  059  066  072  077  086   060        079  087  095  102  113  123   IGNITION MODULE INDUCED uis i MOTOR MOUNT  E   BLOWER  HOUSING                                                                                                                   all                                                                                  Fig  16   Blower Housing and Flue Collector Box         FLUE  COLLECTOR  BOX            NS       Wee    M   SS  24   SS   SS    BLOWER  HOUSING RACK SCREW         Fig  17   Unit Access Panel               SWITCH  BURNER MOUNTING    A05119          2 SETSCREWS   HIDDEN     C99085    Fig  18   Removal of Motor and Blower Wheel         SUR     e    C99091    23    2    ST                OF           0                   Fig  19   Burner Rack Removed       C99086    attachment  Be careful not to bend the fins  If coated with oil or  grease  clean the coils with a mild detergent and water solution   Rinse coils with clear water  using a garden hose  Be careful not to  splash water on motors  insulation  wiring  or air filter s   For best  results  spray condenser coil fins from inside to outside the unit   On
35. X 30X 1       UNIT SIZE   FILTER SIZE                                                                               For longer life  operating economy  and continuing efficiency  c  On all units  remove blower assembly from unit  Remove   clean accumulated dirt and grease from the blower wheel and Screws securing blower to blower partition and slide   motor annually  assembly out  Be careful not to tear insulation in blower  compartment     A WARNING d  Ensure proper reassembly by marking blower wheel and    motor in relation to blower housing before disassembly   FIRE  EXPLOSION AND ELECTRICAL SHOCK HAZ     ARD e  Loosen setscrew s  that secures wheel to motor shaft     Remove screws that secure motor mount brackets to  housing  and slide motor and motor mount out of housing     Failure to follow this warning could result in personal injury    death and or property damage    Before cleaning the blower motor and wheel  disconnect gas   supply  Then turn off and tag electrical power to the unit  a  Ensure proper reassembly by marking wheel orientation    b  Lift wheel from housing  When handling and or cleaning  blower wheel  be sure not to disturb balance weights  clips    1  Remove and disassemble blower assembly as follows  on blower wheel vanes     2  Remove and clean blower wheel as follows        Cleaning the Blower Motor and Wheel    a  Remove unit access panel  c  Remove caked on dirt from wheel and housing with a  brush  Remove lint and or dirt accumulations from whee
36. air  Before lighting the unit for  the first time  perform the following with the gas valve in  the       OFF       position    If the gas supply pipe was not purged before connecting  the unit  it will be full of air  It is recommended that the  ground joint union be loosened  and the supply line be  allowed to purge until the odor of gas is detected  Never  purge gas lines into a combustion chamber  Immediately  upon detection of gas odor  retighten the union  Allow 5  minutes to elapse  then light unit     b  Make sure that condenser fan blade is correctly positioned  in fan orifice  Leading edge of condenser fan blade should  be 1 2 in  maximum from fan orifice venturi     c  Ensure fan hub is 1 8 in  maximum from motor housing   See Fig  12      MOTOR FAN GRILLE           12   MOTOR SHAFT    1 8  MAX BETWEEN  MOTOR AND FAN HUB    C99009    Fig  12   Fan Blade Clearance    d  Make sure that air filter s  is in place     e  Make sure that condensate drain trap is filled with water to  ensure proper drainage     f  Make sure that all tools and miscellaneous loose parts have  been removed     13                                                                                                                            MANIFOLD PIPE PLUG  C99019  Fig  13   Burner Assembly  BURNER FLAME  MANIFOLD  C99021    Fig  14   Monoport Burner    START UP  Step 1   CHECK FOR REFRIGERANT LEAKS    Proceed as follows to locate and repair a refrigerant leak and to  charge the unit     1  Locat
37. as each item is completed       VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT  ____ VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS    CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS    CHECK GAS PIPING FOR LEAKS    CHECK THAT INDOOR  EVAPORATOR  AIR FILTER IS CLEAN AND IN PLACE  VERIFY THAT UNIT INSTALLATION IS LEVEL  CHECK FAN WHEEL PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS        START UP  ELECTRICAL  SUPPLY VOLTAGE 11 12  COMPRESSOR AMPS L1  COMPRESSOR AMPS L1  INDOOR  EVAPORATOR  FAN AMPS       TEMPERATURES  OUTDOOR  CONDENSER  AIR TEMPERATURE  DB  RETURN AIR TEMPERATURE  DB WB  COOLING SUPPLY AIR  DB WB       GAS HEAT SUPPLY AIR     PRESSURES  GAS INLET PRESSURE IN  WG  GAS MANIFOLD PRESSURE IN  WG  REFRIGERANT SUCTION PSIG  REFRIGERANT DISCHARGE PSIG    SUCTION LINE TEMP   DISCHARGE LINE TEMP     VERIFY REFRIGERANT CHARGE USING CHARGING TABLES      Measured at suction inlet to compressor      Measured at liquid line leaving condenser    Copyright 2005 CARRIER Corp      7310 W  Morris St      Indianapolis  IN 46231    Manufacturer reserves the right to discontinue  or change at any time  specifications or designs without notice and without incurring obligations   Book 114      101 Printed in U S A  Catalog No  48SD 1SI Pg 28 8 05 Replaces  New  Tab  1a          
38. burner access panel     LIMIT SWITCHES    Normally closed limit switch  LS  completes the control circuit  through the thermostat R circuit  Should the leaving air tempera   ture rise above the maximum allowable temperature  the limit  switch opens and the R control circuit       breaks        Any interruption  in the R control circuit instantly closes the gas valve and stops gas  flow to the burners and pilot  The blower motor continues to run  until LS resets     When the air temperature at the limit switch drops to the  low temperature setting of the limit switch  the switch closes and  completes the R control circuit  The electric spark ignition system  cycles and the unit returns to normal heating operation     ROLLOUT SWITCH    The function of the rollout switch is to close the main gas valve in  the event of flame rollout  The switch is located above the main  burners  When the temperature at the rollout switch reaches the  maximum allowable temperature  the R control circuit trips     closing the gas valve and stopping gas flow to the burners  The  indoor  evaporator  fan motor  IFM  and induced draft motor  continue to run until switch is reset  The IGC LED will display  FAULT CODE 7     Step 3   START UP COOLING AND MAKE ADJUST   MENTS       CAUTION    UNIT DAMAGE HAZARD   Failure to follow this caution may result in unit and or  property damage    Complete the required procedures given in the Pre Start Up    section before starting the unit    Do not jumper any saf
39. ck for gas leaks at the field installed and factory installed  gas lines after all piping connections have been completed   Use soap and water solution  or method specified by local  codes and or regulations      Step 9   INSTALL DUCT CONNECTIONS    The unit has duct flanges on the supply  and return air openings on  the side and bottom of the unit  For downshot applications  the  ductwork connects to the roof curb  See Fig  2 and 3 for  connections sizes and locations      CONFIGURING UNITS FOR DOWNFLOW  VERTICAL  DIS   CHARGE       A WARNING    ELECTRICAL SHOCK HAZARD  Failure to follow this warning could result in personal injury    or death   Before performing service or maintenance operations on the  system  turn off main power to unit     1  Open all electrical disconnects before starting any service  work     2  Remove return duct cover located on duct panel by breaking  connecting tabs with screwdriver and a hammer  See Fig  10A   amp  10B      3  To remove supply duct cover  break front and right side  connecting tabs with a screwdriver and a hammer  Push louver  down to break rear and left side tabs  See Fig  10A  amp  10B      4  If unit ductwork is to be attached to vertical opening flanges  on the unit composite base  jackstand applications only   do so  at this time                                                                                            SUPPLY RETURN VENT HOOD   DUCT DUCT SHIPPING   OPENING OPENING LOCATION  A05143    Fig  10A Supply and Retur
40. e leak and make sure that refrigerant system pressure has  been relieved and reclaimed from both high  and low pressure  ports     2  Repair leak following Refrigerant Service procedures     NOTE  Install a filter drier whenever the system has been opened  for repair     3  Add a small charge of R 22 refrigerant vapor to system and  leak test unit     4  Recover refrigerant from refrigerant system and evacuate to  500 microns if additional leaks are not found     5  Charge unit with R 22 refrigerant  using a volumetric   charging cylinder or accurate scale  Refer to unit rating plate  for required charge  Be sure to add extra refrigerant to  compensate for internal volume of filter drier        AINO 151 SYH 090 9   00S8h S1300N NO  7531835 NI 0331    ZSI ONY 157 060     0058   S1300N     lt    Wil          JYIM  18 123NNO2 ONY      291           3uIM 038 123NNODSIQ 033dS WNIGIW 803                   3UIM        123NNOO ANY W8 29I MOuj 3UIM  038 1 3NNOOSIQ Mi4I 0339  HOIH 804        NOTLVTIVISNI 01313 803 SYOLINGNOD 434402 338930 SL ASN        SASVGGNS ONY LVLSOWNYIHL 803 53974 32144 335 2   IN31VAIfO3 5 11  30 341  2 338930 06          HLIM Q32v1d34 38 1      11     0331938 3uv 0                 S3UIM TVNIOIUO JHL JO ANY 3171                                     153100  0321903N3  30 032190383  ug    ug     Srl 1 S o     s       21901        9NI1V3H  0321983N3  30 037198303  9 5  0 1    0     ______  21901        9NI 1002  IN3NdINO    41103               4Y138 NOTLSNGNOD a2  H
41. eaks  repair  and recharge   Remove source of restriction        Insufficient evaporator airflow    Increase air quantity  Check filter     replace if necessary        Temperature too low in conditioned area    Reset thermostat        Outdoor ambient below 40  F    Install low ambient kit            Field installed filter drier restricted    25       Replace     SYMPTOM    Table 12   Troubleshooting Guide Heating    CAUSE    REMEDY       Burners will not ignite     Water in gas line    Drain  Install drip leg        No power to furnace    Check power supply fuses  wiring  or circuit breaker        No 24 v power supply to control circuit    Check transformer    Check fuse on ignition control    NOTE  Some transformers have internal overcurrent protection that  requires a cool down period to reset        Miswired or loose connections    Check all wiring and wirenut connections       Burned out heat anticipator in  thermostat    Replace thermostat        Broken thermostat wire    Run continuity check  Replace wire if necessary        Misaligned spark electrodes    No gas at main burners    Check flame ignition and sense electrode positioning   Adjust as necessary     1 Check gas line for air  Purge as necessary   NOTE  After purging gas line of air  wait at least 5 minutes for any  gas to dissipate before attempting to light unit    2  Check gas valve  Turn gas valve switch to  ON   Make sure wires  properly connected to gas valve        Inadequate heating     Dirty air filter  
42. ecord number of seconds for gas meter test dial to make one  reset the control  break the 24 v power to W  revolution   5  The evaporator fan will turn on 45 sec  after the flame has 4  Divide number of seconds in Step 3 into 3600  number of  been established  The evaporator fan will turn off 45 sec  after seconds in one hour    the thermostat has been           5  Multiply result of Step 4 by the number of cu ft shown for one  CHECK GAS INPUT revolution of test dial to obtain cu ft of gas flow per hour   Check gas input and manifold pressure after unit start up  See 6  Multiply result of Step 5 by Btu heating value of gas to obtain    Table 4   If adjustment is required proceed as follows     The rated gas inputs shown in Table 4 are for altitudes from sea  level to 2000 ft above sea level  These inputs are based on  natural gas with a heating value of 1050 Btu ft  at 0 65 specific  gravity  or propane gas with a heating value of 2500 Btu ft  at  1 5 specific gravity    For elevations above 2000 ft  reduce input 4 percent for each  1000 ft above sea level  For example at 2001 ft  a 1296 total  derate is required     total measured input in Btuh  Compare this value with heating  input shown in Table 4  Consult the local gas supplier if the  heating value of gas is not known      EXAMPLE  Assume that the size of test dial is 1 cu ft  one  revolution takes 32 sec   and the heating value of the gas is 1050            Proceed as follows     1  2    15      32 sec  to complete one
43. ety devices when operating the unit   Do not operate the compressor when the outdoor temperature  is below 40  F  unless accessory low ambient kit is installed    Do not rapid cycle the compressor  Allow 5 minutes between         cycles to prevent compressor damage        CHECKING COOLING CONTROL OPERATION    Start and check the unit for proper cooling control operation as  follows     1  Place room thermostat SYSTEM switch in OFF position   Observe that blower motor starts when FAN switch is placed  in ON position and shuts down when FAN switch is placed in  AUTO  position     2  Place SYSTEM switch in COOL position and FAN switch in  AUTO  position  Set cooling control below room temperature   Observe that compressor  condenser fan  and evaporator  blower motors start  Observe that cooling cycle shuts down  when control setting is satisfied  The evaporator fan will  continue to run for 30 sec     3  When using an auto changeover room thermostat  place both  SYSTEM and FAN switches in AUTO  positions  Observe  that unit operates in Heating mode when temperature control  is set to       call for heating   above room temperature  and  operates in Cooling mode when temperature control is set to    call for cooling   below room temperature      CHECKING AND ADJUSTING REFRIGERANT CHARGE    The refrigerant system is fully charged with R 22 refrigerant   tested  and factory sealed     NOTE  Adjustment of the refrigerant charge is not required  unless the unit is suspected of not ha
44. f the conditioned space  and inefficient  energy utilization  however  the required setting may be changed  slightly to provide a greater degree of comfort for a particular  installation     TRANSFORMER PROTECTION    The transformer is of the energy limiting type  It is set to  withstand a 30 sec  overload or shorted secondary condition     PRE START UP    A WARNING    FIRE  EXPLOSION AND ELECTRICAL SHOCK HAZ    ARD   Failure to follow this warning could result in personal injury    death and or property damage    1  Follow recognized safety practices and wear protective  goggles when checking or servicing refrigerant system    2  Do not operate compressor or provide any electric power to  unit unless compressor terminal cover is in place and  secured    3  Do not remove compressor terminal cover until all electri   cal sources are disconnected    4  Relieve and recover all refrigerant from system before  touching or disturbing anything inside terminal box if  refrigerant leak is suspected around compressor terminals    5  Never attempt to repair soldered connection while refrig   erant system is under pressure    6  Do not use torch to remove any component  System  contains oil and refrigerant under pressure  To remove a  component  wear protective goggles and proceed as fol   lows    a  Shut off gas supply and then electrical power to unit    b  Relieve and recover all refrigerant from system using  both high  and low pressure ports    c  Cut component connecting tubing wit
45. fan on  delay expires    Limit switch opens within three minutes    after blower off delay timing in Heating mode     Ensure unit is fired on rate  ensure temperature rise is correct   Ensure unit s external static pressure is within application guidelines        Limit switch faults    LED 2 flashes     High temperature limit switch is open     Check the operation of the indoor  evaporator  fan motor  Ensure  that the supply air temperature rise is in accordance with the range  on the unit nameplate  Clean or replace filters        Flame sense fault    LED 3 flashes     The IGC  sensed flame that should not be  present     Reset unit  If problem persists  replace control board        4 consecutive limit switch faults      LED 4 flashes     Inadequate airflow to unit    Check operation of indoor  evaporator  fan motor and that supply air  temperature rise agrees with range on unit nameplate information        Ignition lockout    LED 5 flashes     Unit unsuccessfully attempted ignition for  15 minutes     Check ignitor and flame sensor electrode spacing  gaps  etc  Ensure  that flame sense and ignition wires are properly terminated  Verify  that unit is obtaining proper amount of gas        Induced draft motor fault    LED 6 flashes     IGC does not sense that induced draft  motor is operating      Check for proper voltage  If motor is operating  check the speed  sensor plug IGC Terminal J2 connection  Proper connection   PIN 1    White   PIN 2     Red   PIN 3     Black        
46. from the unit  as measured along the control  voltage wires   use no  16 AWG color coded  insulated  35 C  minimum  wires     Standard Connection    Remove knockout hole located in the flue panel adjacent to the  control access panel  See Fig  2 and 3   Remove the rubber  grommet from the installer   s packet  included with unit  and install  grommet in the knockout opening  Provide a drip loop before  running wire through panel     Run the low voltage leads from the thermostat  through the inlet  hole  and into unit low voltage splice box     Locate five 18 gage wires leaving control box  These low voltage  connection leads can be identified by the colors red  green  yellow   brown  and white  See Fig  11   Ensure the leads are long enough  to be routed into the low voltage splice box  located below right  side of control box   Route leads through hole in bottom of control                   box and make low voltage connections  See Fig  11   Secure all  cut wires  so that they do not interfere with operation of unit     HEAT ANTICIPATOR SETTING    The room thermostat heat anticipator must be properly adjusted to  ensure proper heating performance  Set the heat anticipator  using  an ammeter between the W and R terminals to determine the exact  required setting     NOTE  For thermostat selection purposes  use 0 18 amp for the  approximate required setting  Failure to make a proper heat  anticipator adjustment will result in improper operation  discom   fort to the occupants o
47. h tubing cutter and  remove component from unit    d  Carefully unsweat remaining tubing stubs when neces   sary  Oil can ignite when exposed to torch flame     Proceed as follows to inspect and prepare the unit for initial  startup     1  Remove access panel     2  Read and follow instructions on all WARNING  CAUTION   and INFORMATION labels attached to  or shipped with  unit     3  Make the following inspections     a  Inspect for shipping and handling damages such as broken  lines  loose parts  disconnected wires  etc     b  Inspect for oil at all refrigerant tubing connections and on  unit base  Detecting oil generally indicates a refrigerant  leak     c  Leak test all refrigerant tubing connections using electronic  leak detector  halide torch  or liquid soap solution  If a  refrigerant leak is detected  see the Check for Refrigerant  Leaks section     d  Inspect all field  and factory wiring connections  Be sure  that connections are completed and tight     e  Ensure wires do not contact refrigerant tubing or sharp  sheet metal edges     f  Inspect coil fins  If damaged during shipping and handling   carefully straighten fins with a fin comb     4  Verify the following conditions     A WARNING    FIRE  EXPLOSION HAZARD  Failure to follow this warning could result in personal injury     death and or property damage   Do not purge gas supply into the combustion chamber  Do not  use a match or other open flame to check for gas leaks        a  Make sure gas line is free of 
48. he unit top  The maximum horizontal  extension of a partial overhang must not exceed 48 in     Do not place the unit where water  ice  or snow from an overhang  or roof will damage or flood the unit  Do not install the unit on  carpeting  tile  or other combustible materials  The unit may be  installed on wood flooring or on Class A  B  or C roof covering  materials     moving the unit  Unit must remain in an upright position during all  rigging and moving operations  The unit must be level within 1 4     for proper condensate drainage  therefore  the ground level pad or  accessory roof curb must be level before setting the unit in place   When a field fabricated support is used  be sure that the support is  level and properly supports the unit  Lifting point should be  directly over the center of gravity for the unit     Step 6   CONNECT CONDENSATE DRAIN    NOTE  When installing condensate drain connection be sure to  comply with local codes and restrictions     Model 48SD disposes of condensate water through a 3 4 in  NPT  fitting which exits through the compressor access panel  See Fig   2 and 3 for location      Condensate water can be drained directly onto the roof in rooftop  installations  where permitted  or onto a gravel apron in ground   level installations  Install a field supplied condensate trap at end of  condensate connection to ensure proper drainage  Make sure that  the outlet of the trap is at least 1 in  lower than the drain pan    Table 1   Physical Data  
49. ica where a Low NO  rule exists     RECEIVING AND INSTALLATION    Step 1   CHECK EQUIPMENT  IDENTIFY UNIT    The unit model number and serial number are stamped on unit  identification plate  Check this information against shipping papers  and job data  Verify unit voltage and amperage requirements listed  on unit rating plate agree with power supply provided to unit     INSPECT SHIPMENT    Inspect for shipping damage while unit is still on shipping pallet   If unit appears to be damaged or is torn loose from its anchorage   have it examined by transportation inspectors before removal   Forward claim papers directly to transportation company  Manu   facturer is not responsible for any damage incurred in transit     Check all items against shipping list  Immediately notify the  nearest distributor if any item is missing     To prevent loss or damage  leave all parts in original packages  until installation     INSTALLATION    1  Remove unit from shipping carton  Leave top shipping skid on  the unit as a spreader bar to prevent the rigging straps from  damaging the unit  If the wood skid is not available  use a  spreader bar of sufficient length to protect unit from damage     2  Position the lifting bracket assembly around the base of the  unit  Be sure the strap does not twist    3  Place each of the 4 metal lifting brackets into the rigging holds  in the composite pan    4  Thread lifting bracket strapping around bottom perimeter of  unit as follows   a  Open lever of tensio
50. ilters must not exceed 0 08 in  wg     condensate connection to prevent the pan from overflowing  See  Fig  8   Prime the trap with water  When using a gravel apron   make sure it slopes away from the unit     If the installation requires draining the condensate water away  from the unit  install a 2 in  trap at the condensate connection to  ensure proper drainage  See Fig  8   Make sure that the outlet of  the trap is at least 1 in  lower than the drainpan condensate  connection  This prevents the pan from overflowing     Prime the trap with water  Connect a drain tube     using a minimum  of 3 4 in  PVC or 3 4 in  copper pipe  all field supplied      at the  outlet end of the 2 in  trap  Do not undersize the tube  Pitch the  drain tube downward at a slope of at least 1 in  for every 10 ft of  horizontal run  Be sure to check the drain tube for leaks     TRAP    OUTLET  1  min            2  min                             C00009    Fig  8   Condensate Trap    Step 7   INSTALL FLUE HOOD    The flue assembly is secured and shipped in the return air duct   Remove duct cover to locate the assembly  See Fig  10A      NOTE  Dedicated low NO  models MUST be installed in Cali   fornia Air Quality Management Districts where a Low NO  rule  exists     These models meet the California maximum oxides of nitrogen   NO   emissions requirements of 40 nanograms joule or less as  shipped from the factory     NOTE  Low NO  requirements apply only to natural gas instal   lations     A WARNING 
51. ircuit through compressor motor  COMP   to condenser  outdoor  fan motor  OFM   Both motors start  instantly     3  The set of normally open contacts of energized relay BM close  and complete the circuit through evaporator blower  indoor   fan motor  IFM      NOTE  Once the compressor has started and then stopped  it  should not be started again until 5 minutes have elapsed  The  cooling cycle remains    on    until the room temperature drops to a  point that is slightly below the cooling control setting of the room  thermostat  At this point  the thermostat  breaks  the circuit  between thermostat terminal R to terminals Y and G  These open  circuits deenergize contactor coil C  The condenser and compres   sor motors stop  After a 30 sec  delay  the blower motor stops  The  unit is in a  standby  condition  waiting for the next  call for  cooling  from the room thermostat     MAINTENANCE  To ensure continuing high performance and to minimize the  possibility of premature equipment failure  periodic maintenance  must be performed on this equipment  This combination  heating cooling unit should be inspected at least once each year by  a qualified service person  To troubleshoot cooling or heating of  units  refer to Tables 11 13     NOTE  Consult your local dealer about the availability of a  maintenance contract     A WARNING    FIRE  EXPLOSION  ELECTRICAL SHOCK HAZARD  Failure to follow this warning could result in personal injury   death  and or property damage     The abil
52. is used to identify  unsafe practices which may result in minor personal injury or  product and property damage  NOTE is used to highlight sugges   tions which will result in enhanced installation  reliability  or  operation     These instructions cover minimum requirements and conform to  existing national standards and safety codes  In some instances   these instructions exceed certain local codes and ordinances   especially those that may not have kept up with changing residen   tial construction practices  We require these instructions as a  minimum for a safe installation     INTRODUCTION    The 48SD unit  See Fig  1  is fully self contained  combination  Category I gas heating electric cooling units designed for outdoor  installation  See Fig  2 and 3 for unit dimensions   All unit sizes  have return and discharge openings for both horizontal and  downflow configurations  and are factory shipped with all down   flow duct openings covered  Units may be installed either on a  rooftop  a cement slab  or directly on the ground if local codes  permit  See Fig  4 for roof curb dimensions      Models with an N in the fifth position of the model number are  dedicated Low      units designed for California installations     These models meet the California maximum oxides of nitrogen   NO   emissions requirements of 40 nanograms joule or less as       shipped from the factory and must be installed in California Air  Quality Management Districts or any other regions in North  Amer
53. ity to properly perform maintenance on this equip   ment requires certain expertise  mechanical skills  tools  and  equipment  If you do not possess these  do not attempt to  perform any maintenance on this equipment other than those  procedures recommended in the User   s Manual        18    A WARNING    FIRE  EXPLOSION  ELECTRICAL SHOCK  PERSONAL   INJURY HAZARD   Failure to follow these warnings could result in serious injury    1  First  turn off gas supply to the unit  Then turn off electrical  power to the unit and install lockout tag before performing  any maintenance or service on the unit      Use extreme caution when removing panels and parts  As  with any mechanical equipment  personal injury can result  from sharp edges  etc      Never place anything combustible either on  or in contact  with  the unit      Should overheating occur or the gas supply fail to shut off   turn off external main manual gas valve to the unit  Then  shut off electrical supply and install lockout tag     A CAUTION    UNIT DAMAGE HAZARD   Failure to follow this caution may result in unit damage   Errors made when reconnecting wires may cause improper  and dangerous operation  Label all wires prior to disconnec   tion when servicing        The minimum maintenance requirements for this equipment are as  follows     1  Inspect air filter s  each month  Clean or replace when  necessary  Certain geographical locations may require more  frequent inspections     N      Inspect indoor coil  outdoo
54. ium  CFM 1798   1771   1734   1687   1645   1595   1530   1449   1355  Heating Rise    F  38 38 39 40 41 42 44 47 50  Watts         908 887 858 827 804 767   748  High CFM         2000   1944   1876   1811   1735   1647   1555  Heating Rise    F          34 35 36 37 39 41 43  Watts 627   617   607 584 567 548 528      Low CFM 1550   1530   1493   1461   1414   1361   1320        Heating Rise    F  56 56 58 59 61 63 65           Watts 771 755 734 711 690 665 639 607   572  48SD   N 048115 35 65 Medium  CFM 1798   1771   1734   1687   1645   1595   1530   1449   1355  Heating Rise    F  48 49 50 51 52 54 56 60 64  Watts         908 887 858 827 804 767   748  High CFM         2000   1944   1876   1811   1735   1647   1555  Heating Rise    F          43 44 46 48 50 52 55  Watts 627 617 607 584 567  Low CFM 1550   1530   1493   1461   1414  Heating Rise    F  63 64 65 67 69  Watts 771 755 734 711 690 665 639 607    48SD   N 048130 40 70 Medium  CFM 1798   1771   1734   1687   1645   1595   1530   1449      Heating Rise    F  54 55 56 58 59 61 64 67    Watts     908 887 858 827 804 767   748  High CFM     2000   1944   1876   1811   1735   1647   1555  Heating Rise    F      49 50 52 54 56 59 63  Watts 786 769 754 736 722 705 684 658      Low  CFM 2027   1960   1901   1821   1759   1693   1616   1513      Heating Rise    F  33 34 36 37 38 40 42 45      Watts 873 849 833 815   798   782   763 748      48SD   N 060090 25 55 Medium CFM 2095   1962   1887   1817   1748   1679   1583   
55. l  and housing with vacuum cleaner  using soft brush attach   ment  Remove grease and oil with mild solvent     b  Disconnect motor lead from blower relay  BM   Discon   nect yellow lead from terminal L2 of the contactor     19    Table 9   Dry Coil Air Delivery      Horizontal and Downflow Discharge      Unit 48SD024 060  Deduct 10 percent for 208 Volts                                                                                                                                                                                                                                                                                                                                                                 UNIT HEATING RISE RANGE    F    MOTOR SPEED EXTERNAL SIATIC                           0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9  Watts 311 309 304 301 286  Low  CFM 935 885 820 757   686  Heating Rise    F  32 34 37 40 44  Watts 379 357 357 345      48SD   N 024040 20 50 Medium CFM 957   868 769 647    Heating Rise    F  31 35 39 46    Watts 447 435 421  High CFM 970 853 712  Heating Rise    F  31 35 42  Watts 311 309 304   301  Low  CFM 935 885 820 757  Heating Rise    F  48 51 55 59  Watts 411 405 398 390 379 357 357       48SD   N 024060 35 65 Medium CFM 1195   1155   1100   1028   957 868 769      Heating Rise    F  38 39 41 44 47 52 59          Watts 447 435 421  High CFM 970 853   712  Heating Rise    F  46 53 63  Watts 311 309 304 301  Low CFM 935 885 820 757  Heating Rise    F  
56. llow sections 7 2     Table 1    Physical Data   Unit 48SD             UNIT SIZE 48SD 024040 024060 030040 030060 036060 036090 042060 042090  NOMINAL CAPACITY  ton  2 2 2  2  3 3 3  3   OPERATING WEIGHT         343 343 366 366 433 433 460 460   COMPRESSORS Scroll   Quantity 1       REFRIGERANT  R 22              Quantity  Ib   7 8 7 8 8 4 8 4 10 9 10 9 10 9 10 9  REFRIGERANT METERING DEVICE Accurater  Orifice ID  in    065  065  070  070  080  080  088  088     2   21 2 2 2  21 2   21 2  21 2  21 2   21 2 21  Face Area  sq ft  11 9 11 9 13 6 13 6 15 5 15 5 19 4 19 4       2700 2700 2700 2700 2800 2800 2800 2800  22 22 22 22 22 22 22 22    Diameter  in    Motor Hp  Rpm   EVAPORATOR COIL    1 8  825    1 8  825    1 8  825    1 8  825    1 8  825    1 8  825    1 8  825    1 8  825        ip 3    17 3   17 947 3 17 3 17 3   17 9 47 3 17  Rows   Fins in   Face Area  sq ft  3 7 3 7 3 7 3 7 4 7 4 7 4 7 4 7  EVAPORATOR BLOWER 800 800 1000 1000 1200 1200 1400 1400    Nominal Airflow  Cfm   Size  in    Motor Hp  Rpm   FURNACE SECTION   Burner Orifice No   Qty   Drill Size     10X10   10X10   10X10   10X10   11X10   11X10   11X10   11X10  1 3  1050    1 3  1050    1 3  1050    1 3  1050    1 2  1000    1 2  1000    1 2  1075    1 2  1075                             2   44 2   38 2   44 2   38 2   38 3   38 2   38 3   38  Natural Gas  Burner Orifice No   Qty   Drill Size  2590 2 46 290 246   3 46 269           Propane Gas  RETURN AIR FILTERS  in  T 20 X 24 X 1 24 X 86 X 1    Throwaway
57. lower wheel bi   monthly to determine proper cleaning frequency     To inspect blower wheel  remove draft hood assembly  Shine a  flashlight into opening to inspect wheel  If cleaning is required   remove motor and wheel as follows     1  Remove unit access panel  See Fig  17      2  Remove the 7 screws that attach induced draft motor mount   ing plate to blower housing  See Fig  18      3  Slide the motor and blower wheel assembly out of the blower  housing  See Fig  18   Clean the blower wheel  If additional  cleaning is required  continue with Steps 4 and 5     4  To remove blower  remove 2 setscrews     5  To remove motor and cooling fan assembly  remove 4 screws  that hold blower housing to mounting plate     6  To reinstall  reverse the procedure outlined above     LIMIT SWITCH    Remove unit access panel  Limit switch is located on the blower  partition     22    BURNER IGNITION   Unit is equipped with a direct spark ignition 100 percent lockout  system  Ignition module is located in the control box  See Fig   16  Module contains a self diagnostic LED  During servicing   refer to label diagram for LED interpretation    If lockout occurs  unit may be reset by either momentarily  interrupting power supply to unit or by turning selector switch to  OFF position at the thermostat     MAIN BURNERS    At the beginning of each heating season  inspect for deterioration  or blockage due to corrosion or other causes  Observe the main  burner flames and adjust  if necessary       
58. mostat        Faulty condenser fan motor or capacitor    Replace        Restriction in refrigerant system    Locate restriction and remove        Compressor operates continuously     Excessive head pressure     Dirty air filter    Replace filter        Unit undersized for load    Decrease load or increase unit size        Thermostat set too low    Reset thermostat        Low refrigerant charge    Locate leak  repair  and recharge        Leaking valves in compressor    Replace compressor           Air in system Recover refrigerant  evacuate system  and recharge   Condenser coil dirty or restricted Clean coil or remove restriction    Dirty air filter Replace filter        Dirty condenser coil    Clean coil        Refrigerant overcharged    Recover excess refrigerant        Air in system    Recover refrigerant  evacuate system  and recharge        Condenser air restricted or air short cycling    Determine cause and correct        Head pressure too low     Low refrigerant charge    Check for leaks  repair  and recharge        Compressor valves leaking    Replace compressor        Restriction in liquid tube    Remove restriction        Excessive suction pressure     High heat load    Check for source and eliminate        Compressor valves leaking    Replace compressor        Refrigerant overcharged    Recover excess refrigerant        Suction pressure too low     Dirty air filter    Replace Filter        Low refrigerant charge  Metering device or low side restricted    Check for l
59. n Duct Opening                    C99012    Fig  10B   Vertical Duct Cover Removed       CAUTION    PROPERTY DAMAGE HAZARD   Failure to follow this caution may result in property damage   Collect ALL screws that were removed  Do not leave screws  on rooftop as permanent damage to the roof may occur     5  It is recommended that the unit base insulation around the  perimeter of the vertical return air opening be secured to the  unit base with aluminum tape  Applicable local codes may  require aluminum tape to prevent exposed fiberglass     6  Cover both horizontal duct openings with the duct covers from  the accessory duct cover kit  Ensure opening is air  and  watertight    7  After completing unit conversion  perform all safety checks  and power up unit     NOTE  The design and installation of the duct system must be in  accordance with the standards of the NFPA for installation of    10    nonresidence type air conditioning and ventilating systems  NFPA  90A or residence type  NFPA 90B  and or local codes and  ordinances     Adhere to the following criteria when selecting  sizing  and  installing the duct system     1  Units are shipped for horizontal duct installation  by removing  duct covers      2  Select and size ductwork  supply air registers  and return air  grilles according to American Society of Heating  Refrigera   tion and Air Conditioning Engineers  ASHRAE  recommen   dations     3  Use flexible transition between rigid ductwork and unit to  prevent transmissio
60. n buckle  ratchet type    b  Feed strapping through tension buckle as shown in Fig  7A   c  Pull strapping through tension buckle unit taut   d  Snap lever down to lock strap in tension buckle  To release    strapping  squeeze safety latch  lift lever  and pull webbing  outward     5  Tighten the tension buckle until it is taut  Lifting brackets  must be secure in the rigging holds     6  Attach field supplied clevis or hook of sufficient strength to  hole in the lifting bracket  See Fig  7B      7  Attach the 2 safety straps directly to the clevis or hook at the    4 rigging brackets  DO NOT attach the safety straps to the  lifting brackets  See Fig  7B      8  Position lifting point directly over the unit s center of gravity     9  Lift unit  When unit is directly over the roof curb  remove the  2 safety straps  Lower the equipment onto the roof curb     Step 2   PROVIDE UNIT SUPPORT  ROOF CURB    Install accessory roof curb in accordance with instructions shipped  with curb  See Fig  4 for roof curb dimensions   Install insulation   cant strips  roofing  and flashing  Ductwork must be attached to  curb     IMPORTANT  The gasketing of the unit to the roof curb is critical  for a watertight seal  Install gasketing material supplied with the  roof curb  Improperly applied gasketing can also result in air leaks  and poor unit performance     BLOCKOFF PANEL ON 018 uh      SUPPLY RETURN    REQUIRED                   DUCT DUCT  OPENING OPENING                              249 6 t
61. n of vibration  The transition may be  screwed or bolted to duct flanges  Use suitable gaskets to  ensure weathertight and airtight seal     4  All units must have field supplied filters or accessory filter  rack installed in the return air side of the unit  Recommended  sizes for filters are shown in Table 1     5  Size all ductwork for maximum required airflow  either  heating or cooling  for unit being installed  Avoid abrupt duct  size increases or decreases or performance may be affected     6  Adequately insulate and weatherproof all ductwork located  outdoors  Insulate ducts passing through unconditioned space   and use vapor barrier in accordance with latest issue of Sheet  Metal and Air Conditioning Contractors National Association   SMACNA  and Air Conditioning Contractors of America   ACCA  minimum installation standards for heating and air  conditioning systems  Secure all ducts to building structure     7  Flash  weatherproof  and vibration isolate all openings in  building structure in accordance with local codes and good  building practices     Step 10   INSTALL ELECTRICAL CONNECTIONS    A WARNING    ELECTRICAL SHOCK HAZARD   Failure to follow this warning could result in personal injury  or death    The unit cabinet must have an uninterrupted  unbroken  electrical ground to minimize the possibility of serious injury  if an electrical fault should occur  This ground may consist of    an electrical wire connected to the unit ground lug in the  control compartmen
62. ngs  Installation of flexible duct connector is recommended  to prevent transmission of vibration and  or noise to structure  All  ductwork should be secured to the flanges  Insulate and weather   proof all external ductwork  joints  and roof openings with counter  flashing and mastic in accordance with applicable codes     Ducts passing through an unconditioned space must be insulated  and covered with a vapor barrier     If a plenum return is used on a vertical unit  the return should be  ducted through the roof deck to comply with applicable fire codes     A minimum clearance is not required around ductwork  Cabinet  return air static shall not exceed   25 in  wg        MINIMUM HEIGHT  36                                                    C99015  SIZE MAXIMUM WEIGHT                kg in  mm in  mm  UNIT 48SD   024 372 169 20 0   508 0   19 3   490 2  030 395 179 20 0   508 0   14 0   355 6  036 462 210 21 0   533 4   20 5   520 7  042 489 222 21 0   533 4   20 5   520 7  048 509 231 21 0   533 4   20 0   508 0  060 521 236 21 0   583 4   20 0   508 0    Fig  7   Suggested Rigging    Step 4   PROVIDE CLEARANCES    The required minimum operating and service clearances are shown  in Fig  2 and 3  Adequate combustion  ventilation and condenser  air must be provided in accordance with section 5 3  Air for  Combustion and Ventilation  of the National Fuel Gas Code ANSI   American National Standards Institute  Z223 1 or applicable  provisions of local building code  In Canada  fo
63. not attempt to  lubricate these motors     Table 7   Cooling Checking Chart    Suction Line Temperature   F    OD Temp  Suction Line Pressure  PSIG   F    52 54 5 S 6  amp  cg 70       82 85 89 9     E CEN IC           ERES ES RC               ES   5 pepe sees                          eed    5   eT 111                                                               sp   85                                                                                                                                   0                           EN  Lm                                                                        Suction Line Temperature   C  OD Temp  Suction Line Pressure  kPa   CF   36t   370   387   405   423   442   462   482   502   523   544   566   589   612   636     17 _                                           46                                                                                                ES                          316 7                                                  ae    5            oe       L4                             Wt t    46                 pep       L9                           gt                   Table 8   Filter Pressure Drop  In  wg     CFM  500   600   700   800   900   1000   1100   1200   1300   1400   1500   1600   1700   1800   1900   2000   2100   2200   2300  024  030 20 X 20 X 1   0 05   0 07   0 08   0 10   0 12   0 13   0 14   0 15  036 20 X 24 X 1                0 09   0 10   0 11   0 13   0 14   0 15   0 16  042  048  060   24 
64. old and connect manometer  See  Fig  13    3  Turn on gas to unit     4  Remove cover screw over regulator adjustment screw on gas  valve     5  Adjust regulator adjustment screw to the correct manifold  pressure  as specified in Table 4  Turn adjusting screw  clockwise to increase manifold pressure  or turn adjusting  screw counterclockwise to decrease manifold pressure     6  Replace cover screw     7  Turn off gas to unit  Remove manometer from pressure tap   Replace pipe plug on gas valve  then turn on gas to unit  Check  for leaks     CHECK BURNER FLAME    With burner access panel removed  observe the unit heating  operation  Watch the burner flames to see if they are light blue and  soft in appearance  and that the flames are approximately the same  for each burner  Propane will have blue flame  See Fig  14   Refer  to the Maintenance section for information on burner removal     AIRFLOW AND TEMPERATURE RISE    The heating section for each size unit is designed and approved for  heating operation within the temperature rise range stamped on the  unit rating plate     16    Table 9 shows the approved temperature rise range for each  heating input  and the air delivery cfm at various temperature rises   The heating operation airflow must produce a temperature rise that  falls within the approved range     Refer to Indoor Airflow and Airflow Adjustments section to adjust  heating airflow when required     HEATING SEQUENCE OF OPERATION   See Fig  15 and unit wiring label   
65. or death  Use all service ports and open all  flow control devices  including solenoid valves        If oil is detected or if low cooling performance is suspected   leak test all refrigerant tubing using an electronic leak detector   halide torch  or liquid soap solution  If a refrigerant leak is  detected  refer to the Check for Refrigerant Leaks section     If no refrigerant leaks are found and low cooling performance is  suspected  refer to the Checking and Adjusting Refrigerant Charge  section     GAS INPUT    The gas input does not require checking unless improper heating  performance is suspected  If a problem exists  refer to the Start Up  section     EVAPORATOR AIRFLOW    The heating and or cooling airflow does not require checking  unless improper performance is suspected   f a problem exists  be  sure that all supply  and return air grilles are open and free from  obstructions  and that the air filter is clean  When necessary  refer  to the Indoor Airflow and Airflow Adjustments section to check the  system airflow     METERING DEVICE     ACCURATER    This metering device is a fixed orifice and is located in the  distributor assembly to the indoor coil     LIQUID LINE STRAINER    The liquid line strainer  to protect metering device  is made of wire  mesh and located in the liquid line on the inlet side of the metering  device     TROUBLESHOOTING  Use the Troubleshooting Guides  See Tables 11 13  if problems  occur with these units     START UP CHECKLIST  Use the Sta
66. r coil  drain pan  and condensate  drain each cooling season for cleanliness  Clean at least once  per heating   cooling season or more often if needed     3  Inspect indoor  evaporator  fan motor and wheel for cleanli   ness at the beginning of each heating and cooling season   Clean when necessary  For first heating and cooling season   inspect blower wheel bi monthly to determine proper cleaning  frequency    4  Check electrical connections for tightness and controls for  proper operation each heating and cooling season  Service  when necessary     5  Ensure wires are not contacting refrigerant tubes or sharp  sheet metal edges     6  Check and inspect heating section before each heating season   Clean and adjust when necessary     7  Check flue hood and remove any obstructions  if necessary   AIR FILTER       CAUTION    UNIT PERFORMANCE AND DAMAGE HAZARD  Failure to follow this caution may result in improper unit  operation and damage to unit components     Never operate the unit without a suitable air filter in the  return air duct system  Always replace the filter with the same  dimensional size and type as originally installed  See Table 1  for recommended filter sizes         Inspect air filter s  at least once each month and replace   throwaway type  or clean  permanent  at least twice during each  heating and cooling season or whenever the filter s  becomes  clogged with dust and or lint     INDOOR  EVAPORATOR  MOTOR  NOTE  All motors are permanently lubricated  Do 
67. rical controls and wiring annually  Be  sure to turn off the gas supply  and then the electrical power to the  unit     Remove access panel to locate all the electrical controls and  wiring  Check all electrical connections for tightness  Tighten all  screw connections  If any smoky or burned connections are  noticed  disassemble the connection  clean all the parts  restrip the  wire end and reassemble the connection properly and securely     After inspecting the electrical controls and wiring  replace the  access panel  Start the unit  and observe at least one complete  heating cycle and one complete cooling cycle to ensure proper  operation  If discrepancies are observed in either or both operating       24    cycles  or if a suspected malfunction has occurred  check each  electrical component with the proper electrical instrumentation   Refer to the unit wiring label when making these checkouts   NOTE  Refer to the heating and or cooling sequence of operation  in this publication as an aid in determining proper control  operation    REFRIGERANT CIRCUIT    Annually inspect all refrigerant tubing connections and the unit  base for oil accumulations  Detecting oil generally indicates a  refrigerant leak     A WARNING    FIRE  EXPLOSION HAZARD  Failure to follow this warning could result in personal injury   death and or property damage     System under pressure  Relieve pressure and recover all  refrigerant before system repair or final unit disposal to avoid  serious injury 
68. rt Up Checklist to ensure proper start up procedures are  followed     SYMPTOM    Table 11   Troubleshooting Guide   Cooling    CAUSE    REMEDY       Compressor and condenser fan  will not start     Compressor will not  start but condenser  fan runs     Power Failure    Call power company        Fuse blown or circuit breaker tripped    Replace fuse or reset circuit breaker        Defective thermostat  contactor  transformer  or control relay    Replace component        Insufficient line voltage    Determine cause and correct        Incorrect or faulty wiring    Check wiring diagram and rewire correctly        Thermostat setting too high  Faulty wiring or loose connections in compressor circuit    Lower thermostat setting below room temperature   Check wiring and repair or replace        Compressor motor burned out  seized  or internal  overload open    Determine cause  Replace compressor        Defective run start capacitor  overload  start relay    Determine cause and replace        Compressor cycles  other than  normally satisfying thermostat      Refrigerant overcharge or undercharge    Recover refrigerant  evacuate system  and recharge to  capacities shown on nameplate        Defective compressor  Insufficient line voltage    Replace and determine cause   Determine cause and correct        Blocked condenser    Determine cause and correct        Defective run start capacitor  overload or start relay    Determine cause and replace        Defective thermostat    Replace ther
69. t  or conduit approved for electrical  ground when installed in accordance with NEC  National  Electrical Code  ANSI NFPA  latest edition  and local elec   trical codes  In Canada  follow Canadian Electrical Code  CSA  Canadian Standards Association  C22 1 and local  electrical codes        11       A CAUTION    UNIT DAMAGE HAZARD   Failure to follow these precautions may result in damage to   the unit being installed    1  Make all electrical connections in accordance with NEC  ANSI NFPA  latest edition  and local electrical codes  governing such wiring  In Canada  all electrical connec   tions must be in accordance with CSA standard C22 1  Canadian Electrical Code Part 1 and applicable local  codes  Refer to unit wiring diagram    2  Use only copper conductor for connections between  field supplied electrical disconnect switch and unit  DO  NOT USE ALUMINUM WIRE    3  Be sure that high voltage power to unit is within operating  voltage range indicated on unit rating plate    4  Do not damage internal components when drilling through  any panel to mount electrical hardware  conduit  etc   Consult local power company for correction of improper  voltage and or phase imbalance        HIGH VOLTAGE CONNECTIONS    The unit must have a separate electrical service with a field   supplied  waterproof  disconnect switch mounted at  or within  sight from  the unit  Refer to the unit rating plate for maximum  fuse circuit breaker size and minimum circuit amps  ampacity  for  wire sizing
70. t all gas piping in accordance with local and  national plumbing and gas codes before connecting piping to  unit     NOTE  Pressure test the gas supply system after the gas supply  piping is connected to the gas valve  The supply piping must be  disconnected from the gas valve during the testing of the piping  systems when test pressure is in excess of 0 5 psig  Pressure test  the gas supply piping system at pressures equal to or less than 0 5  psig  The unit heating section must be isolated from the gas piping  system by closing the external main manual shutoff valve and  slightly opening the ground joint union     A WARNING    FIRE OR EXPLOSION HAZARD   Failure to follow this warning could result in fire  explosion   personal injury  death and or property damage     Connect gas pipe to unit using a backup wrench to avoid  damaging gas controls     Never purge a gas line into a combustion chamber  Never  test for gas leaks with an open flame  Use a commercially  available soap solution made specifically for the detection of  leaks to check all connections     Use proper length of pipe to avoid stress on gas control  manifold     If a flexible connector is required or allowed by authority  having jurisdiction  black iron pipe shall be installed at  furnace gas valve and extend a minimum of 2 in  outside  furnace casing     If codes allow a flexible connector  always use a new  connector  Do not use a connector which has previously  serviced another gas appliance        8  Che
71. ving the proper R 22 charge     A superheat charging chart is attached to the outside of the service  access panel  The chart includes the required suction line tempera   ture at given suction line pressures and outdoor ambient tempera   tures     An accurate superheat  thermocouple  or thermistor type ther   mometer  and a gauge manifold are required when using the  superheat charging method for evaluating the unit charge  Do not  use mercury or small dial type thermometers because they are not  adequate for this type of measurement     17       CAUTION    UNIT DAMAGE HAZARD  Failure to follow this caution may result in unit damage    When evaluating the refrigerant charge  an indicated adjust   ment to the specified factory charge must always be very  minimal  If a substantial adjustment is indicated  an abnormal  condition exists somewhere in the cooling system  such as  insufficient airflow across either coil or both coils                   Proceed as follows     1  Remove caps from low  and high pressure service fittings     2  Using hoses with valve core depressors  attach low  and  high pressure gauge hoses to low  and high pressure service  fittings  respectively    3  Start unit in Cooling mode and let unit run until system  pressures stabilize     4  Measure and record the following   a  Outdoor ambient air temperature   F db    b  Suction tube temperature    F  at low side service fitting   c  Suction  low side  pressure  psig     5  Using  Cooling Charging Charts 
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Consumo Consciente  Oregon Scientific BA2000 User's Manual  Sommaire - Centre Hospitalier du Rouvray  MANUAL DE INSTALACIÓNY OPERACIÓN Typ S601  XGK EX™ MANUALE DI ISTRUZIONI  00. Initial Installation Manual AF INTEGRA.book  Template BA B168xH238  Black & Decker 398178-00 Instruction Manual  Manual de usuario  SERIE FASTOP S.TEC.    Copyright © All rights reserved. 
   Failed to retrieve file