Home

(GMR) Phase IV Software v2.00 Information, GFK

image

Contents

1. The normal state can be configured on a point by point basis or with the Select All and Clear All buttons can be configured uniformly for all points in that output group Important Product Information GMR Phase IV Software GFK 1287F February 2006 Output Autotest Faults When Outputs are Rapidly Changing State In addition to the output discrepancy faults that can occur as a result of non steady state outputs in redundant output groups it is also possible that Output Autotest faults could occur This may happen under very narrow timing conditions when the output block s state has been overridden to the de energized state during the Autotest sequence and the output value changes This would cause the Autotest to fail resulting in a Output Autotest fault message A second side effect is that the output would remain overridden in the de energized safe state consistent with TUV requirements Note that this TUV requirement applies only to outputs which are normally energized as determined by the setting in the GMR Configuration Utility Those outputs configured as normally de energized will not see this particular fault under these conditions Because of the asynchronous operation of CPUs in a GMR system it is possible that output blocks while voting the output from three separate CPUs could see a discrepancy when an output is simply changing states Earlier versions of GMR dealt with this situation by filtering discrepancies that occ
2. channel must be set to its safe state The value chosen here should match the default value chosen for this channel in the GMR configuration see item 2b Important Product Information GMR Phase IV Software GFK 1287F February 2006 c On the Network tab of the GBIO01 the Report Faults parameter must be set to Enabled and if the NIU is part of a duplex or triplex input group the CPU Redundancy parameter must be set to Hot Standby Using the GMR Configuration Utility configure each voted VersaMax input channel as follows a The Engineering Units Max and Min values must represent the full range of input values that the module can report to the PLC b The Default State must be set to the safe state Use and configuration of Field Control Modules in GMR systems There are certain failures of Field Control modules that the GMR software does not recognize If such a failure does occur instead of discarding the associated inputs and adapting the voting the GMR software will include the values from the faulted Genius Bus Interface Unit BIU in the voting The net result can be that the voted input value becomes set to the BIU s default value which can only be configured for 0 or Hold Last State Therefore the use of Field Control modules in a GMR system must be limited to cases where 0 is the safe state for the associated input channels When Field Control modules are included in a GMR system configure the system ac
3. Important Product Information GFK 1287F February 2006 READ THIS INFORMATION FIRST Product Genius Modular Redundancy Phase IV Software v2 00 1C641SWP745B Compact Disk GMR System Software Release 4 04 GMR Configuration Utility Release 8 06 General Description This is an upgraded version of Genius Modular Redundancy GMR software that provides Windows 2000 support for the Configuration Utility It also addresses several issues with the Configuration Utility and System Software This version replaces version 8 05a of the Configuration Utility and 4 02c System software provided in IC641SWP745A Software upgrades may be purchased from a distributor This version of Genius Modular Redundancy GMR software has the features and functionality described in the GMR User s Manual GFK 1277D A copy of the manual is provided on the CD with the Configuration Utility Compatibility Logicmaster and CPU This release requires Logicmaster 90 70 release 6 02 or later This new software is only compatible with the IC697CPM790 CPU release 6 02 or later Firmware release 6 03 or later is required to enable the Ethernet interface for programming This new software is NOT compatible with the IC697CPU788 or IC697CPU789 Series 90 70 Genius Bus Controller Release 5 4 or later Genius Bus Controller IC697BEM731 firmware is required Genius Hand Held Monitor Hand Held Monitor IC660HHMS501H version 4 5 or later is required Genius Blocks Versi
4. ant outputs from the second PLC This misconfiguration will not be indicated with a system fault message and the GMR PLCs will appear to operate normally To assure that there is no such misconfiguration GE Fanuc advises the use of appropriate verification procedures as well as careful configuration practices as identified in the Genius Modular Redundancy User s Manual GFK 1277 Important Product Information GMR Phase IV Software GFK 1287F February 2006 Specific verification procedures include Ensuring that the current GMR Configuration printout indicates the actual number of active PLCs Using the Logicmaster 90 Programming package to toggle the M12262 REPORT control reference so that the system will report the current GMR checksum in the PLC Fault table Verifying this checksum with the one listed in the GMR Configuration printout Any inconsistencies indicate improper GMR Configuration settings that should be corrected at the earliest opportunity 2 Normal State Must be Configured Appropriately for Critical Outputs in Fire and Gas Application Critical outputs in a Fire and Gas application must be configured such that the normal state is the opposite of the safe or demand state as appropriate so that the GMR diagnostics will perform correctly For example normally energized on outputs will be forced to the safe or de energized state in the event of failure whereas normally de en
5. cording to the following rules l Using a Genius Hand held monitor configure each Field Control Genius BIU as follows a For each module attached to the BIU fault reporting should be enabled for every channel that is used and the Hld Lst State parameter should be set to NO b The BIU s Report Faults parameter must be set to YES c Ifthe BIU is part of a duplex or triplex input group its CPU Redundancy parameter must be set to Hot Stdby Mode Using the GMR Configuration Utility configure each voted Field Control input channel as follows a The Engineering Units Max and Min values must represent the full range of input values that the module can report to the PLC b The Default State must be set to the safe state which should correspond to the value 0 Special Operating Notes if Misconfiguring the Number of PLCs in the Series 90 70 GMR System may result in Unreported Output Discrepancy Faults The GMR Configuration Utility is used to select the operational and hardware parameters fora GMR system Should the user fail to configure the GMR system with the actual number of PLCs the GMR software could fail to report some Output Discrepancy faults For example a Triplex system configured with only two PLCs could result in a failure to report some discrepant outputs from the third PLC Likewise a Duplex system configured with only one PLC could result in a failure to report some discrep
6. ergized off outputs will be forced to the energized state as in a Fire and Gas application To configure outputs in this manner bring up the GMR Configuration Utility and select the output group as shown GMR Configurator C LMS0 GMR folders 486 Phase4_AC_1VM1 P4AC1VM1 gct _ alx Bile Edit View Insert Tools window Help E ETET EA MB S Se SS E Be GBC Group 1 View 1 af Group 1 gt Channels be 16 Channel ipti Redundant Output Group 1 32 Channel H Block Output Discrep b 16 Enabled Btart Address 1 C Disabled ut Discrepency Enabled Group No f1 z k1 BusA SBAT BusB SBA1 D E BusC SBAT Siaran E BusB SBA2 Description Redundant Output Group 1 CPU Type IC697CPM790 Revision 1 Select mouse click the Normal State tab for the associated output group to display the following screen GMR Configurator C LM9S0 GMR folders 486 Phase4_AC_1 M1 P4AC1VM1_gcf Ele Edt View Insert Tools Window Help D SOS s ela Xml AO EEE rete ae Ge Se a ompi omp2 Sompa ap General Bus AutoTest Neintal State y Normal State gt Pi hs Pees M260 Pr E Murer z pie Mier ami Redundant Output Group 1 w iber of Channels 16 M13 E24 Btart Address 1 Kurzer a AR eA i Kr ar 32 BusA SBAT BusB SBAT BusC SBAT BusB SBA2 put Discrepency Enabled aaa wonsa CPU Type IC697CPM730 Revision 1
7. ill cause the system to act just as earlier versions of the GMR Software now operate with the filtering algorithm described in the User s Manual This is the default value Important Product Information GMR Phase IV Software GFK 1287F February 2006 Fault Table Contents When a GMR CPU is in Stop Mode If a GMR CPU has been in Run mode and on line then subsequently is put in Stop mode some faults may be reported incorrectly or may not be reported at all When the CPU is returned to Run mode the fault table resumes normal operation Each time a CPU is put into Run mode and on line an I O fault table reset should be performed by using the GMR IORES control bit M12258 as described in the GMR User s Manual GFK 1277C This operation will ensure that the I O fault table is updated with the current and correct fault information An I O Shutdown Canceled Message is logged in the PLC Fault Table following a Supervised Output Shutdown If a fault condition exists for an output group that results in a supervised output shutdown the shutdown occurs as it should but then an erroneous Shutdown canceled message is erroneously entered in the fault table Slow response to ORES and FRCLOG after power cycle is to be expected Following a power cycle of multiple CPUs the actions performed by GMR control bits IORES M12258 and FRCLOG M12263 can take several minutes to complete The GMR status bit IORESIP M 12238 can be m
8. includes the input value from that module in the voting until the Genius device re reports the fault This can cause the voted input to be set to an unrealistic value during the time between the I O reset and the time the fault is received Be sure that all faults are corrected prior to issuing an I O reset or design the application logic to hold the outputs in their current state long enough to allow all standing faults to be re reported after an I O reset Configuration of VersaMax modules in GMR systems There are certain failures of VersaMax modules that the GMR software does not recognize If such a failure does occur instead of discarding the associated inputs and adapting the voting the GMR software includes the values from the faulted Genius NIU in the voting The result can be that the voted input value becomes set to the GNIU s default input value Therefore the GNIU s default input values must be configured for their safe states When VersaMax modules are included in a GMR system configure the system according to the following rules 1 Using the NIU Configuration Tool within Machine Edition configure each Genius NIU as follows a On the Module Parameters tab of every input module the Default Hold Last State parameter must be set to Default and the Report Faults parameter must be set to Enabled b On the Input Parameters tab of every input module the default input value for every input
9. ode 11501 is correctly reported if a certain section of GMR code is improperly accessed A diagnostic reset occurs on the rising edge of a DIAGRES This behavior which triggers a diagnostic reset on the rising edge of a DIAGRES in any PLC is consistent with the other GMR to USER functions Starting PLCs simultaneously does not cause a nuisance Program Changed to be logged by one of the PLCs Changing ALG block fault reporting for analog block BBA026 does not cause GMR Fault Handler message 10899 Changing the configuration of ALG block fault reporting does not unexpectedly cause an INVALID CONFIG error message If there is no I O present in a duplex or triplex system the PLC identity is not assumed to be PLCA A system that has communications between PLCs without I O groups will not have erroneous Loss of Device 0 faults Ifa M discrepancy exists the third PLC will synchronize correctly PLCB and PLC C can be started when PLCA is autotesting the last output group without causing PLC C to report error GMR1 ST2 10h Non discrepant analog inputs are voted correctly in Duplex mode If an I O reset is initiated while there are standing faults on duplex groups the inputs are voted correctly Loading a Simplex configuration into PLCB or PLCC or loading a duplex configuration into PLCC will correctly generate a mismatch error message Important Product Information GMR Phase IV Software GFK 1287F February 2006 Du
10. on 4 02 GMR software supports the following Genius blocks in GMR groups All Genius analog input blocks The following discrete Genius block versions are compatible with version 4 02 GMR software IC660BBD020U IC660BBD021U IC660BBD024V IC660BBD025U Other types of Genius blocks can be used as non redundant blocks in the same system Field Control Products The following Field Control devices are supported Field Control Bus Interface Unit version IC670GBIO02E 8 Channel Current Source Analog Input module version IC670ALG230A RTD module IC670ALG620 Thermocouple module IC670ALG630 Important Product Information GMR Phase IV Software GFK 1287F February 2006 16 Channel Current Source Analog Input module IC670ALG240 VersaMax Products The following VersaMax devices are supported Any Versa Max Power Supply Network Interface Unit IC200GBI001 Any 4 Channel Analog Input Module Any 8 Channel Analog Input Module These Field Control and VersaMax modules may be used as voted input devices however they are not included in the list of TUV approved devices Incompatible Devices GMR is incompatible with the Series 90 70 GDS module The Series 90 70 GMR CPU 790 release 6 02 is incompatible with CIMPLICITY 70 Problems Resolved by This Release This release of GMR addresses the following issues of previous release of GMR 4 02c System Software and 8 05a Configuration Utility System Software v4 04 Error c
11. onitored to transition to the off state to verify that the IORES request completed Subsequent use of these control bits result in normal response times Field Control BIUs and Versa Max NIUs must be configured in Hot Standby mode for proper fault contact behavior Otherwise fault contacts may not be consistent in all CPUs Hot Standby mode should be used for all input blocks and modules when GMR mode is not an available selection Also the appropriate CPU firmware 6 02 must be used with this release in order for fault contacts to be cleared properly following an IORESET Note The Versa Max NIU Configuration Utility must be used in order to place Versa Max NIU in Hot Standby mode For more information contact GE Fanuc Technical Support at 1 800 GE FANUC CPU Memory areas should be cleared as a standard procedure step when storing application code and re starting the system Otherwise the redundant PLCs may not synchronize correctly
12. ring an I O shutdown performing an I O reset does not cause outputs to change state from their set defaults During an I O reset premature or spurious inputs will not be incorrectly interpreted as discrepant inputs During an autotest sweep the output group shutdown timers are triggered consistently Configuration Software v8 06 Inserting redundant output groups and changing busses in the configuration does not cause an overlap in the groups resulting in an invalid configuration The About Form reads the owner organization for Windows NT systems correctly VersaMax and Field Control non voted inputs are not labeled as voted on printouts of the system configuration The printer settings will be remembered during a current configuration session The configuration utility limits the insertion of GBC groups to 31 GBCs The configuration utility will not try to reuse Serial Bus Addresses that have already been used The Rack Memory Error dialogs inactivate the GMR I O Groups section of the toolbar The M Sync data cannot be configured to overlap the reserved M system status data area The maximum watchdog timer setting of 2250ms is correctly reported if a higher setting is attempted Restrictions and Open Problems All standing faults should be corrected prior to issuing an I O reset If an input point has a standing fault when an I O reset is initiated the GMR software clears that fault and
13. urred during state changes However under some circumstances this default filter may be inadequate A field has been added to the GMR Configuration Utility revision 7 00 and later that allows the user to adjust the filter by adding a configurable number of seconds between 0 and 65535 In effect an output discrepancy would have to exist for the configured number of seconds before being reported as a fault For more information on GMR Output Discrepancy reporting see the GMR User s Manual To access the parameter in the GMR Configuration Utility select View from the menu bar followed by System Configuration Then select the Options tab to reveal a screen similar to the one below GMR Configurator C LM90 GMR folders 486 Phase4_AC_1VM1 P4AC1 M1 gcf Ele Edit View Insert Tools Window Help 0 calal telka xin wes EEEE e e System Configuration me General Gptions p Test Interval r Discrepancy Filters Period minutes B Input seconds 1 0 Continuous Output seconds 0 A T Register R f 170 Shutdown Timer Period minutes 1 440 r Online Prog Simplex Shutdown o Enabled C Enabled Tinecut ndes poz C Disabled Disabled Astan Norton Syste 4 Exploring 2 S smr Con BY Microsot w 2ySent Items Calendar M 3 Command Pf GM 1 45PM In the Discrepancy Filter area a value can be entered for Output A value of 0 w

Download Pdf Manuals

image

Related Search

Related Contents

USER`S MANUAL - Smith-Root  SendIgence User`s Manual in PDF  「ペネロペオリジナルポーチ」プレゼントキャンペーンを実施  Pro4700 Entertainment Kit, Assembly and Operations  Christian Lassure La pierre sèche, mode d`emploi  MODE D`EMPLOI - Reproductive Health Technologies Project  Release Notes Change Series C to D  FDCX(XP40,XP45,XP50,XP56,XP63)  Integral INFD8GBFUS3.0 USB flash drive  JVC KV-DV7 Portable DVD Player without Screen  

Copyright © All rights reserved.
Failed to retrieve file