1. locking the lid closed 20 Safety Instr v2 CSA CliDv1 RN_Sultan Sonar Glad doc Page 3 of 11 Hawk Measurement Systems Pty Ltd www hawklevel com b Change of output configuration The only other hardware adjustment that may be desired by the user is converting from the Sultan 234 output configuration to the Sultan 2 output configuration Refer to Assembling and Dismantling above c Software Adjustment For software adjustment of Sultan unit parameter adjustment and data entry refer to instructions in Entering Data and all of the Setup sections If GosHawk II software is to be used for parameter adjustment and data entering from a lap top computer read and fully understand the information in the GosHawk IT Manual either supplied with the equipment or downloaded free from the Hawk web site http www hawklevel com 8 Application Conditions a Voltage Supply Must be according to the voltage supplies given in Specifications b Temperature Must not exceed the operating temperature range stated in Putting Into Service above To prevent inaccuracies due to extremes in temperature and the effect of long term UV exposure it is recommended that transducers constructed with grey beige polypropylene housing material be protected from direct sunlight This does not apply to the blue green and dark grey plastic enclosure parts These parts have better UV stability c Cable Connection Cables must only be replaced by th
2. possible to reconfigure a Sultan 2 model eg AWI2 or AWR2 as a Sultan 234 model Only Sultan 234 models can be reconfigured to operate as Sultan 2 models and this modification is reversible b Disconnect the power to the Sultan 234 Unit c To do the modification follow the instructions in Wiring Change Sultan 234 lt gt Sultan 2 d Modify the wiring to suit the new output configuration as shown in Wiring Diagrams The sonar transducer cleaning system may require careful assembly Refer to the user manual for details of the various cleaning systems Eg Floating Sonar Assembly Sonar Bracket Nozzle Assembly etc 6 Installation and Wiring Carefully follow Typical Installations Installation Guide and Wiring Diagram sections Follow all points listed in Putting Into Service above Wiring should be in accordance with relevant installation standards for hazardous area equipment eg NFPA 70 or other local codes of practice 7 Adjustment a Sultan Remote Electronics AWR series models To access the user controls unlock the clear cover using the lever on the right hand side of the clear lid Press this lever in the direction of the arrow towards the lid to release the catch The lid can then be swung open to gain access to the user control push buttons Close the lid when finished To lock the lid press on the lower part of the lever which moves the arrow symbol in reverse slightly away from the lid
3. to 75 C REMOTE TRANSDUCER Related Drawing No modifications permitted without the approval of the Engineering Manager DOC NO NOT TO SCALE ALL DIMENSIONS IN MM HAWK MEASUREMENT SYSTEMS HAW_RD_WIR CSA F3 A0 15 17 MAURICE COURT NUNAWADING VICTORIA AUSTRALIA 3131 Wiring for CSA Class 1 Div 1 2 Group D Sultan 34 wire Remote Amplifier in Safe Area A4 amp Transducer s in Zone 0 Hazardous Area REVISION SHEET A01 1 1 Hawk Measurement Systems Pty Ltd www hawklevel com F4 Wiring for AWRT Transducers in Class 1 Division 1 2 Group D Hazardous Area and Gladiator Remote Amplifier in Safe Area l S Barriers connected between Transducers amp Remote Amplifier Note All equipment in Hazardous area must have appropriate certification CSA Certificate No 2137731 External Environment Rating Safe Area Class 1 Div 1 2 Hazardous Area Internal Vessel Rating AEx Ex ia IIA T4 Ta 20 C to 70 C eg MTL 7758 AC DC Power A Black Shield Optional Bo o gt i Black Shield PLC Comms Shed Relay 1 eg MTL 7761 ac Relay 2 Failsafe GLADIATOR REMOTE AMPLIFIER I or Stahl 9002 22 158 200 001 L White White Blue Barrier Ground Acoustic Switch Application ips GG Note1 Wiring to conform to NFPA 70 Note 2 Transducer Power from Remote Amplifier Amplifier Output 6 5V Transducer Input Uo 12 6 Volts Ui 12 6 Volts lo 2 41 Amps li 333 mA AWRT AWRT Po 1 2W
4. A higher level of performance HAWK Safety instructions Ly HAWK SULTAN SERIES C US Smart Universal Level Transmitter And Network CSA Class I Division 1 2 Class I Div 1 2 Group D Equipment types Zone 0 AEx Ex ia IIA T4 20 C to 75 C AWR series Remote Electronics Lustaliation Dre AWRT series Remote Transducer we WARNING Static Hazard GR AWRT Sonar series Transducer HAW KJ Do Not Rub using dry cloth teat as OSIRT Sonar series Transducer T amb 1 General This document provides instructions for the installation of Intrinsically Safe equipment for Class I Division 1 amp 2 hazardous locations according to CSA Certificate Of Conformity 2137731 CSA Product Classes are relevant in Canada and North America Class I Div 1 is similar to Zone 0 The Hawk Sultan Series Acoustic Wave equipment uses high frequency acoustic waves to measure the distance from the sensor face to the material product surface The equipment is available as an Integral Transmitter or as a Remote system with various levels of Ex rating The Remote Sultan system is one where an AWRT or OSIRT Sonar series Remote Transducer is mounted at the level measurement point and an OSIR series Remote Electronics unit is installed in a safe area OSIRT Sonar series are identical to AWRT Sonar series transducers Sonar transducers are rated to 1 metre submersion depth A Equipment Identification The CSA Class I Division 1 2 mar
5. B1 A0_ jpg HAW_RD_WIR CSA B2 A0_ jpg HAW_RD_WIR CSA B3 A0_ jpg HAW_RD_WIR CSA F2 A0_ jpg HAW_RD_WIR CSA F3 A0_ jpg HAW_RD_WIR CSA F4 A0_ jpg 20 Safety Instr v2 CSA CliDv1 RN_Sultan Sonar Glad doc Page 5 of 11 Hawk Measurement Systems Pty Ltd www hawklevel com B1 Wiring for CSA Class 1 Division 1 2 Group D Sultan 2 Wire Remote Amplifier in Zone 0 Hazardous Area amp Tranducer in Zone 0 Hazardous Area l S Isolator connected between Transmitter amp Control System Note All equipment in Hazardous area must have appropriate certification Class 1 Div 1 2 Hazardous Area External Environment Rating Safe Area Internal Vessel Rating AEx Ex ia IIA T4 Ta 20 C to 75 C 24Vde 70mA eg MTL 5041 Isolator or MTL 5042 for HART GND not required 4 20mA a Current Loop to Safe Area Load eg 2500 ee es ee SULTAN REMOTE AMPLIFIER SULTAN REMOTE TRANSDUCER Note 1 Wiring to conform to NFPA 70 Note 2 Current Loop Input Ui 28 Volts li 93 mA Pi 0 66 W Ci 0 Li 0 Related Drawing No modifications permitted without the approval of the Engineering Manager DOC NO NOTTO SCALE ALLDIMENSIONSINMM COMPANY A HAWK MEASUREMENT SYSTEMS 15 17 MAURICE COURT NUNAWADING DATE 19 12 2011 VICTORIA AUSTRALIA 3131 REF TITLE Wiring for CSA Class 1 Div 1 2 Group D Sultan 2 wire Remote Amplifier in Zone 0 Hazardous A4 Area amp Transducer in Zone 0 Hazardous Area ARE THE PROPRIETARY PR
6. EMS shoviirbiep et On DWG NO REVISION SHEET WRITTEN AUTHORISATION FROM HAWK HAW_RD_WIR CSA B2 A0 A01 1 1 MEASUREMENT IS PROHIBITED 20 Safety Instr v2 CSA CliDv1 RN_Sultan Sonar Glad doc Page 7 of 11 Hawk Measurement Systems Pty Ltd www hawklevel com B3 Wiring for CSA Class 1 Division 1 2 Group D Sultan 2 Wire Remote Amplifier in Zone 0 Hazardous Area amp Tranducer in Zone 0 Hazardous Area l S Isolator amp Barrier connected between Amplifier amp Control System Note All equipment in Hazardous area must have appropriate certification External Environment Rating Safe Area 4 20mA Current Loop to Safe Area Load eg 2500 eg MTL 7761ac or Stahl 9002 22 1 58 200 001 Modbus Comms Note1 Wiring to conform to NFPA 70 Note 2 Current Loop Input Ui 28 Volts li 93 mA Pi 0 66 W Ci 0 Li 0 Note 3 Modbus Communication to PLC DCS Ui 9 Volts li 120 mA Pi 0 54 W Ci 0 Li 0 Uo 5 9 Volts lo 1 13 Amps Po 0 66 W Co 1000 uF Lo 223 pH L R Ratio 170 uH Q 20 Safety Instr v2 CSA CliDv1 RN_Sultan Sonar Glad doc Page 8 of 11 24Vde 70mA eg MTL 5041 Isolator or MTL 5042 for HART GND not required A Class 1 Div 1 2 Hazardous Area Internal Vessel Rating AEx Ex ia IIA T4 Ta 20 C to 75 C e Black Shield SULTAN REMOTE AMPLIFIER SULTAN REMOTE TRANSDUCER Related Drawing No modifications permitted without the approval of the
7. Engineering Manager DOC NO NOT TO SCALE ALL DIMENSIONS IN MM LY COMPANY ar HAWK MEASUREMENT SYSTEMS 15 17 MAURICE COURT NUNAWADING DATE 49 42 2011 VICTORIA AUSTRALIA 3131 REF TITLE Wiring for CSA Class1 Div 1 2 Group D Sultan 2 wire Remote Amplifier in Zone 0 Hazardous Area A4 amp Transducer s in Zone 0 Hazardous Area THIS DRAWING AND THE CONTENTS THEREOF ARE THE PROPRIETARY PROPERTY OF HAWK DWG NO REVISION SHEET HAW_RD_WIR CSA B3 A0 A01 1 1 MEASUREMENT SYSTEMS REPRODUCTION OR USE OF THIS INFORMATION WITHOUT PRIOR WRITTEN AUTHORISATION FROM HAWK MEASUREMENT IS PROHIBITED Hawk Measurement Systems Pty Ltd www hawklevel com F2 Wiring for CSA Class 1 Division 1 2 Group D Sultan 3 amp 4 Wire Remote Amplifier in Safe Zone amp Remote Transducer in Zone 0 Hazardous Area l S Barriers connected between Transducer amp Remote Amplifier Note All equipment in Hazardous area must have appropriate certification External Environment Rating Safe Area AC DC Power 4 20mA Current Loop Isolated A Optional Bo o PLC Comms Shield SULTAN ORCA or Panel Mount REMOTE AMPLIFIER Note 1 Wiring to conform to NFPA 70 Note 2 Transducer Power from Remote Amplifier Amplifier Output Transducer Input Uo 12 6 Volts Ui 12 6 Volts lo 2 41 Amps li 333 mA Po 1 2W Pi 0 66 W Co 13 5 uF ci 0 Lo 25 H Li 0 L R Ratio 37 5 pH Q Note 3 Essential Communication To Transducer Ui 9 V
8. OPERTY OF HAWK MEASUREMENT SYSTEMS MRPO an DWG NO REVISION SHEET WRITTEN AUTHORISATION FROM HAWK HAW_RD_WIR CSA B1 A0 A01 1 1 MEASUREMENT IS PROHIBITED 20 Safety Instr v2 CSA CliDv1 RN_Sultan Sonar Glad doc Page 6 of 11 Hawk Measurement Systems Pty Ltd www hawklevel com B2 Wiring for CSA Class 1 Division 1 2 Group D Sultan 2 Wire Remote Amplifier in Zone 0 Hazardous Area amp Tranducer in Zone 0 Hazardous Area l S Barrier connected between Transmitter amp Control System Note All equipment in Hazardous area must have appropriate certification Class 1 Div 1 2 Hazardous Area External Environment Rating Safe Area Internal Vessel Rating AEx Ex ia IIA T4 Ta 20 C to 75 C eg MTL 7787 ne e 4 20mA Current Loop SULTAN REMOTE AMPLIFIER SULTAN REMOTE TRANSDUCER Note 1 Wiring to conform to NFPA 70 Note 2 Current Loop Input Ui 28 Volts li 93 mA Pi 0 66 W Ci 0 Li 0 Related Drawing No modifications permitted without the approval of the Engineering Manager DOC NO NOTTO SCALE ALLDIMENSIONSINMM COMPANY HAWK MEASUREMENT SYSTEMS 15 12 2011 15 17 MAURICE COURT NUNAWADING DATE 49 42 2011 VICTORIA AUSTRALIA 3131 DATE 20 12 2011 HAWI REF TITLE Wiring for ATEX Class 1 Div 1 2 Group D Sultan 2 wire Remote Amplifier in Zone 0 Hazardous A4 Area amp Transducer s in Zone 0 Hazardous Area ARE THE PROPRIETARY PROPERTY OF HAWK MEASUREMENT SYST
9. Pi 0 66 W IE Apakan Co 13 5 uF Ci TRANSDUCER TRANSDUCER Lo 25 pH Li 0 s hd a a Mee Te eas OAS ual L R Ratio 37 5 pH Q Note 3 Essential Communication To Transducer Ui 9 Volts li 120mA Pi 0 54W Ci Li 0 Related Drawing Uo 5 9 Volts No modifications permitted lo 1 13 Amps wi Engineering Manager Po 0 66 W Cos 1000 pF DOC NO NOTTOSCALE ALLDIMENSIONSINMM Lo 223 H L R Ratio 170 pH Q COMPANY a ee ee 15 17 MAURICE COURT NUNAWADING REF TITLE Wiring for AWRT Transducers in Class 1 Div 1 2 Grp D Hazardous Area ant na Gladiator Remote Amplifier in Safe Area THIS DRAWING AND THE CONTENTS THEREOF MEASUREMENT SYSTEMS REPRODUCTION OR DWG NO REVISION SHEET WRITTEN AUTHORISATION FROM HAWK HAW_RD_WIR CSA F4 A0 1 1 MEASUREMENT IS PROHIBITED 20 Safety Instr v2 CSA CliDv1 RN_Sultan Sonar Glad doc Page 11 of 11 Hawk Measurement Systems Pty Ltd www hawklevel com
10. e same cable type If extending the cable it must be protected in a junction box and terminated in an enclosure suitable for the environment Refer to Wiring Diagrams Transducer d Earthing Hawk Sultan Acoustic Wave equipment must be earthed to ensure that shielded cabling is effective e Electrostatic Discharge Hawk Sultan Acoustic Wave equipment has been certified safe to use in hazardous dust locations The marking label warns not to rub the surface with a dry cloth if equipment is installed in hazardous gas locations f Industrial Conditions This equipment is designed for use in normal industrial conditions relating to humidity vibration etc If the user intends to operate the equipment in more severe environmental conditions the manufacturer or local distributor should be consulted for advice 20 Safety Instr v2 CSA CliDv1 RN_Sultan Sonar Glad doc Page 4 of 11 Hawk Measurement Systems Pty Ltd www hawklevel com 9 List of CSA certified equipment types Sultan Acoustic Wave Remote Electronics AWR series Sultan Acoustic Wave Remote Transducer AWRT series Sultan Acoustic Wave Remote Sonar Transducer AWRT Sonar Series Sultan Sonar Wave Remote Transducer OSIRT Sonar series Identical to AWRT Sonar series Flange Cone and Accessory selection in any combination 10 Intrinsic Safe configuration drawings Note All equipment in Hazardous Areas must have appropriate certification HAW_RD_WIR CSA
11. instructions for safe use of the Sultan Unit is as follows a The Sultan equipment must put into service safely see Putting Into Service above b This User Manual must be read and understood by any person involved with the unit c Environment and installation conditions should be checked regularly d When opening the cover of the any Sultan unit prevent dust liquids or chemical substances from getting inside the unit Do not leave any cover open in rain or snow conditions 20 Safety Instr v2 CSA CliDv1 RN_Sultan Sonar Glad doc Page 2 of 11 Hawk Measurement Systems Pty Ltd www hawklevel com e The LCD display is visible through the clear lid of the AWR series Sultan Remote Electronics enclosure To view the LCD display on the AWI series Sultan Integral Transmitter open the visor by lifting up the front edge with a finger Close and click into place again after viewing so that the display is protected from environmental effects f Before making any wiring or hardware configuration changes it is important to disconnect power from the equipment S Assembling and dismantling The user is able to reconfigure a Sultan 234 unit 2 3 4 wire operation to that of a Sultan 2 unit 2 wire operation This flexibility is unique to Sultan equipment To safely reconfigure a Sultan 234 model to that of a Sultan 2 model a Make sure that the original unit is a Sultan 234 model eg AWI234 or AWR234 It is not
12. king label is shown above If Hawk Sultan Acoustic Wave equipment is installed and mounted in Class I hazardous areas these User Manual Safety and Operating Instructions the general Ex installation regulations and the general installation regulations for electrical equipment must all be observed The installation of Ex instruments should only be made by trained personnel a Putting Into Service To put a Hawk Sultan Unit safely into service the following steps must be taken 20 Safety Instr v2 CSA CliDv1 RN_Sultan Sonar Glad doc Page 1 of 11 Hawk Measurement Systems Pty Ltd www hawklevel com a To be compliant the equipment must be installed with Intrinsic Barrier devices as described in Intrinsic Safe Installation Cables from both hazardous and safe areas must be segregated from each other according to the appropriate Intrinsic Safe installation standards b Follow the instructions in Typical Installations and Installation Guide as well as the relevant conditions on the CSA Certificate Of Conformity e On units supplied with a permanently connected factory fitted cable the free end of the cable shall be appropriately connected e For installations rigid conduit and fittings or cables approved for the hazardous location shall be used together with appropriate size adaptors to terminate the cable e The units shall not be installed where they are subject to direct sunlight or concentrated light The equipment must not be instal
13. led in an acetic acid environment e The equipment supply cable must be connected to a maximum voltage of 30V in a safe area or to an intrinsically safe supply c Remote Electronics enclosure conduit entry locations for AWR series models are shown in Dimensions Remote Enclosure Remove the terminal cover by loosening the two captive screws Use a flat blade screwdriver and a slight tap to remove the selected conduit entry openings in the front of the enclosure Follow the installation instructions in the Installation Guide and Wiring Diagram sections Be careful to seal any unused cable glands When wiring is complete ensure the cable glands are securely sealed against the enclosure and the cable then seal the terminal cover by tightening the two screws d Correct wiring Follow the instructions in the Wiring Diagram sections Wiring should be in accordance with relevant installation standards for hazardous area equipment or other local codes of practice e Safe temperature Temperature must not exceed the operating range of the Sultan unit In particular Ex rated equipment must not exceed the temperature limits shown on the marking label f Safe power supply Power supply values must be according to the Specifications g It is advised to provide a cover for the unit to prevent damage that could happen due to environmental conditions h Do not put into service where there is a possibility of contact with acetic acid 4 Use The
14. olts li 120mA Pi 0 54W ci 0 Li 0 Uo 5 9 Volts lo 1 13 Amps Po 0 66 W Co 1000 pF Lo 223 uH L R Ratio 170 pH Q 20 Safety Instr v2 CSA CliDv1 RN_Sultan Sonar Glad doc Class 1 Div 1 2 Hazardous Area Internal Vessel Rating AEX Ex ia IIA T4 eg MTL 7766 Pac 1 channel spare Ta 20 C to 75 C Black Shield Barrier Ground eg MTL 7761 ac or Stahl 9002 22 158 200 001 White Blue SULTAN ORCA REMOTE TRANSDUCER Ground Drs ets say tees gate ES ero ee ne ee et Sees el et a Related Drawing No modifications permitted without the approval of the Engineering Manager DOC NO NOT TO SCALE ALL DIMENSIONS IN MM COMPANY ee BE i 15 12 2011 15 17 MAURICE COURT NUNAWADING DATE 49 12 2011 VICTORIA AUSTRALIA 3131 REF TITLE Wiring for CSA Class 1 Div 1 2 Group D Sultan 34 wire Remote Amplifier in Safe Area A4 amp Remote Transducer in Zone 0 Hazardous Area THIS DRAWING AND THE CONTENTS THEREOF ARE THE PROPRIETARY PROPERTY OF HAWK DWG NO REVISION SHEET HAW_RD_WIR CSA F2 A0 A01 1 1 MEASUREMENT SYSTEMS REPRODUCTION OR Hawk Measurement Systems Pty Ltd www hawklevel com USE OF THIS INFORMATION WITHOUT PRIOR WRITTEN AUTHORISATION FROM HAWK MEASUREMENT IS PROHIBITED Page 9 of 11 F3 Wiring for CSA Class 1 Division 1 2 Group D Sultan 3 amp 4 Wire Remote Amplifier in Safe Zone amp Remote Transducer s in Zone 0 Hazardous Area l S Barrie
15. rs connected between Transducers amp Remote Amplifier Note All equipment in Hazardous area must have appropriate certification External Environment Rating Safe Area AC DC Power 4 20mA Current Loop Isolated A Optional PLC Comms O SULTAN ORCA or Panel Mount REMOTE AMPLIFIER Note 1 Wiring to conform to IEC 61241 14 Barrier Ground eg MTL 7766 Pac A Red Black Shield eg MTL 7761 ac or Stahl 9002 22 158 200 001 White White Blue e g 50mm separation between hazardous and safe area cables Note 2 Transducer Power from Remote Amplifier Amplifier Output Transducer Input Uo 12 6 Volts Ui 12 6 Volts lo 2 41 Amps li 333 mA Po 1 2 W Pi 0 66 W Co 13 5 uF Ci 0 Lo 25 pH Li 0 L R Ratio 37 5 pH Q Note 3 Essential Communication To Transducer Ui 9 Volts li 120 mA Pi 0 54 W ci 0 Li 0 Uo 5 9 Volts lo 1 13 Amps Po 0 66 W Co 1000 uF Lo 223 uH L R Ratio 170 pH Q 20 Safety Instr v2 CSA CliDv1 RN_Sultan Sonar Glad doc COMPANY THIS DRAWING AND THE CONTENTS THEREOF ARE THE PROPRIETARY PROPERTY OF HAWK MEASUREMENT SYSTEMS REPRODUCTION OR USE OF THIS INFORMATION WITHOUT PRIOR WRITTEN AUTHORISATION FROM HAWK MEASUREMENT IS PROHIBITED Page 10 of 11 teri C 12 12 2014 L BRAN Class 1 Div 1 2 Hazardous Area Black Shield m SULTAN SULTAN i REMOTE TRANSDUCER Internal Vessel Rating AEx Ex ia IIA T4 Ta 20 C
Download Pdf Manuals
Related Search
File filezilla files file explorer file manager filevine login filecr filevine filehippo filemaker file converter files folder file transfer file sharing filezilla download file compressor filet mignon file explorer options file associations settings files app filezilla server filehorse filezilla client file upload file explorer this pc file explorer windows 10