Home
        FGC 211 User Manual
         Contents
1.                                               4 3  Display                                                      4 4  Push Buttons                                            4 5  Menus                                                       4 5 1  Using the Menus                                          4 6  Pump Control                                             4    4  4  4  4  4    5    5  6  8    9    9  9  9  9  10  10  10  10  11  11    12  12  12  12  13  13  13  13  13  13  13  13  14  14    14  14  14  14  14  15  16    17    17  17  17  17  17  18  18    4 7  Reset Function                                          4 8  Display Language                                       5  Configuration                                           5 1  Introduction                                               5 2  Startup                                                       5 3  Configuring Level Switches                      5 3 1  Using a Stop Level Switch                         5 3 2  Stopping a Pump After a Time                  5 4  Configuring a Level Sensor                      5 4 1  Start  Stop and High Levels                       5 5  Pump Configuration                                  5 5 1  Maximum Motor Current                            5 6  Restoring Default Values                            6  Additional Configuration                         6 1  Introduction                                               6 2  Level Configuration                                   6 
2.            3 3 5  Pressure Switch                                           3 3 6  Flush timer or similar start blocking  relay                                                             3 4  Connecting Thermal Contact                   3 5  Connecting Alarm Output                         3 6  Internal Buzzer                                          3 7  Installing Power Supply                            3 7 1  Cabling                                                        3 7 2  Power Supply                                              3 7 3  Earthing  Grounding                                   3 7 4  Overvoltage Protection                                3 7 6  FGC 24 VDC Supply  3 8  FGC 211 in a LPSS application               3 8 1  Background                                                 3 8 2  Preventing over pressure in system            3 8 3  Avoiding simultaneous pump starts            3 8 4  Handling pressure increases during  operation                                                      3 8 5  Preventing over flow at high pressure         3 8 6  Resetting over current protection                3 8 7  Flushing sewage from the system              3 8 8  System overview                                          3 9  Wiring Diagram                                        3 10  Controller Specification                             4 Operator Panel                                           4 1  Introduction                                              4 2  Front Panel 
3.         Any open menu is closed     4 4  Push Buttons    Available push buttons are listed below     4 5  Menus    You use the menus to configure the FGC  and view  relevant information  such as runtime data and alarms     The following information is generally shown in a menu          Menu name  for example Pump Control          Menu indicator  for example  5_  or  5_1   It is shown  for 3 seconds only  If the indicator ends with an  underscore  there are submenus          Parameter value     For a complete list of menus  see also    Menu  Descriptions    on page 31     FGC 211    Reset  Esc  OK    1    0    Push buttons to  navigate menus    Display  Power  LED  High level  LED  Pump status  LED    Relay status  LED    Alarm status  LED    Reset  push button  Push button to change  between automatic and  manual pump control    Push button to block  pump operation    Escape    Left arrow    Right arrow    Up arrow    Down arrow    OK    Reset    Manual pump stop and block    Automatic mode and manual pump start    Esc    OK    Reset    0    1    4  Operator Panel    28     30     Issued  Supersedes     18    4 12    4 5 1  Using the Menus    1  Display the desired menu          Press the  button to browse forwards one  menu at a time          Press the  button to browse backwards one  menu at a time          Press the  button to show the first menu in a  group of submenus          Press the  button to exit a group of  submenus     2  You can now view the parameter value in t
4.     Safety instruction    Personal safety    Safety instruction    Personal safety   dangerous voltage    Special attention value    Apparatus or component damage    Special information    Special information about a function     Special information    Special information about alarms     1 1  Introduction    Before starting to use the FGC 211  read this chapter  carefully  It contains general information on  documentation  safety and guarantee     1 2  Safety Regulations for Owner   Operator        All government regulations  local health and safety  codes shall be complied with         All danger due to electricity must be avoided   1 3  Guarantee        Modifications or changes to the unit installation  should be carried out only after consulting Xylem Inc         Original spare parts and accessories authorized by  the manufacturer are essential for compliance with  the terms of the guarantee  The use of other parts  may invalidate any claims for warranty or  compensation     1 4  Used Symbols    Observe all precautions for handling  electrostatic sensitive devices before opening  the unit     The FGC has a high degree of protection  against moist and dirt  but should always be  installed so that it will not be unnecessarily  exposed to water or the risk of external  physical damage     A FGC may be used only in the manner  specified by the manufacturer     The manufacturer does not allow any internal  modifications to be made in the unit     Always keep this manual with t
5.    12  13  14  0  2  9  1  8  1  7  1  6  1  5  1  1  1  0  1  9    Issued  Supersedes     12    4 12    3 3 6  Flush timer or similar start blocking  relay    A flush timer allows the sewage level to rise in the well  above the normal start level  The increased sewage  volume is then used for purging the sewage system          If used  connect to terminals 14 and 15   Switch  open    blocking  closed    not blocking           For more information  refer to the installation  instruction of the flush timer     3 4  Connecting Thermal Contact    If the thermal contact for the pump is          used  connect the wires from the thermal contact to  terminal 12 and 13 in the FGC          not used  make sure a jumper lead is placed between  terminal 12 and 13 in the FGC     The thermal contact in the pump is normally closed       3 5  Connecting Alarm Output    The common alarm output is a potential free  alternating  relay with a maximum rating of 250 VAC  5 A   The output  can be used to activate an audible or visual alarm device   for example a lamp or a siren     The common alarm output does not supply power for the  external device  It must be must be supplied from another  source     Connect the external device to terminals 9 and 10     When the common alarm output is          passive  the relay closes between terminals  9 and 11          activated  or the power supply is off  the relay closes  between terminals 9 and 10     3 6  Internal Buzzer    When an alarm is generated  t
6.    Analogue level 4 20 mA3    3 The supply from the FGC can carry max 12 VDC     Terminals    Signal  1 5 mm2    Power  6 mm2    Earth Terminal  6 mm    Type of level sensors to be used    Pneumatic sensor LTU 301  4 20 mA  with 0 2 5 m  sensor range     External level sensor  4 20 mA   ENM 10 external level regulator    Options and Accessories    Level control accessories         Level regulators ENM 10  Different level switches   start  stop and high level  that provide digital input  signals         Open bell system  and pneumatic sensor LTU 301   The open bell system includes a cast bell and a  tube that can be connected to a pneumatic sensor   It transforms the generated pressure to an analogue  signal  4 20 mA          Pressure sensor  It transforms the measured pressure  to an analogue signal  4 20 mA          High water module  It is used to detect a high level in  the pump sump     3 10  Controller Specification    Issued  Supersedes     17    4 12    4 1  Introduction    FGC 211 is a pump controller designed for single pump  installations and household usage     4 2  Front Panel    The figure below shows the front panel of FGC 211     The panel contains          Display to show the different menus          Push buttons to navigate menus and change  values          A set of LED indications  see also    LED  Descriptions    on page 29     4 3  Display    The display shows the current menu  When the display  has been idle for 10 minutes          Light is switched off  
7.    which is installed below the high level switch     When there is no stop level switch in an installation  the  pump instead can be stopped after a specified time  This  time starts to run once the level in the pump sump drops  below the start level switch  That is  the start level switch  first have to revert to its normal position     5 3 1  Using a Stop Level Switch    To use a stop level switch     1  Select  Digital  in the Control mode menu  7_1      2  Select  Stoplevel switch  in the Stop condition menu   7_2      When ready  continue with    Maximum Motor Current    on  page 22     5 3 2  Stopping a Pump After a Time    To specify after how long time a pump should be stopped     1  Select  Digital  in the Control mode menu  7_1      2  Select  Run on time  in the Stop condition  menu  7_2      3  Enter the time in the Run time menu  7_3      When ready  continue with    Maximum Motor Current    on  page 22     5 4  Configuring a Level Sensor    To configure a level sensor     1  Select  Analogue  in the Control mode menu  7_1      2  Enter the sensor range in the Sensor range  menu  2_4   For information on the range  refer to the  documentation delivered with the sensor     3  In the pump sump  raise the sensor from the water     4  Return to the FGC  and read the current level in the  Level menu  2_      Since the sensor is raised from the water  the level  should read  0 00  or some other acceptable value   for example  0 01   Since values are rounded  it is  no
8.  be found after following the  instructions above  contact a FLYGT service agent     8 2 4  Blocked Pump    Problem     Relay status LED  is continuously lit red     Checklist     1  If the pump fails to start     a  Check if  Auto  is selected in the P1 State  menu  5_1      b  If not  select  Auto  in the P1 State menu  5_1    The LED should stop being lit red     c  If the LED still is lit red  check if  On  is selected in  the Ex mode menu  7_5      d  If selected  the FGC is set to Ex mode  see also     EX classified Environment    on page 23  The  pump will be blocked as long as there is no liquid  in the pump sump  When there again is liquid in  the pump sump  the LED should stop being lit red     5  If the pump starts with the LED continuously lit red   contact a FLYGT service agent     8 3  Diagnostic Programs    Diagnostic programs are used to test the hardware          All other functions are disabled when a diagnostic  program is run  that is  normal pump control and  operation are prevented          After 10 minutes of idle time the FGC will  automatically revert to normal operation     To run a diagnostic program     1  Display the Diagnos  Program menu  7_9      2  Select one of the diagnostic programs  Available  programs are listed below   The rest of the programs  are for future use      To manually stop a diagnostic program  select   Off  in the Diagnosis  Program menu     Reset    Program Description  Results    10  Digital inputs  Shows the digital input 
9.  has to be fulfilled    during this time for an alarm to be generated  For  example  if the level in the pump sump drops below the  configured high level alarm limit before the delay time has  elapsed  no alarm will be generated     There are two delay types          General alarm delay that affects all alarms  except  power fault alarms  This delay is 3 seconds          Alarm delay for power failure alarms     To specify the alarm delay for power failures  enter the  delay time in the Al delay Powfail menu  6_1      6 4 2  Audible or Visual Alarm Indication    The common alarm output can be connected to an  audible or visual device  for example a lamp or siren  The  output turns on the device when an alarm is generated     To configure the output     1  Display the Common alarm menu  7_4      2  Select either           Continuous  for a steady indication           Intermittent  for a flashing indication     No alarm condition  present  Alarm condition  present    Time    Condition active  shorter time than  the alarm delay    Alarm  delay  Alarm  generated    20     22     22     29     Issued  Supersedes     24    4 12    7 1  Introduction    This chapter describes basic operation  For information  on configuration  refer to previous chapters     7 2  Viewing Runtime Data    The following runtime data can be shown in the FGC          Level in the pump sump  When a level sensor is  used  you can view the current level in the Level  menu  2_    When level switches are used  t
10.  level sensor  a start level switch  or both start  and stop level switches  As backup  a high level switch  can be used together with the start and stop level  switches  as well as with a level sensor     3 3 1  Cabling    Cables carrying different types of signals must be run  separately  For example  make sure cables to an  analogue level sensor are run separately from cables to  digital level switches     3 3 2  Pneumatic Sensor LTU 301    The pneumatic sensor LTU 301 is used together with an  open bell system  The system includes a cast bell and a  pneumatic tube     There are two versions of LTU 301  One is for ATEX   installations     To install LTU 301     1  Install the open bell system in the pump sump  see  also example in figure below     For more information  refer to the Installation and  operation manual for the open bell system     2  Check that the open bell is free from solid matter     3  Make sure that no solid matter collects at the bottom  of the sump below the open bell     4  Mount LTU 301 in the FGC     5  Connect the pneumatic tube from the open bell  system to LTU 301     6  Connect LTU 301 as follows  see also figure below          Connect the black wire to terminal 18              Connect the white wire to terminal 19          Connect the red wire to terminal 20         3 3 3  4   20 mA Level Sensor    To install a 4   20 mA level sensor     1  Install the level sensor in the pump sump     For more information  refer to the Installation and  opera
11.  pump cycle is complete  the FGC returns to  Auto mode     To return immediately  press the  button     7 4 3  Blocked Pump  Blocked Mode     In Auto mode  you can manually block the pump  This  changes the mode to Blocked mode     Block the Pump Manually    Press the  button  The display will briefly show   Blocked      How Long Will the Pump Remain Blocked     The pump will now remain blocked until the  button  is pressed     Return to Auto Mode    Press the  button  The display will briefly show   Auto      7 4 4  View Control Status    View control status in the P1 state menu  5_1      OK    OK    The exception is EX mode  see also    EX   classified Environment    on page 23   In Ex mode  the pump will not start if there is  no liquid detected in the pump sump     1    Alarm log  Manual mode    0    0    1    1    7  Basic Operation    22     Issued  Supersedes     25    4 12    7 5  Pump Failure Block    The pump can also be blocked due to a pump failure  For  example  the motor temperature is too high or the pump  has run longer that the configured maximum time     When the problem is corrected  press the  button to  remove the automatic block     7 6  Handling Alarms    An alarm alerts the receiver that something needs  attention  The FGC can generate alarms  for example   when the temperature in a pump motor is too high  or the  pump has run longer that the configured maximum time     For a complete list of alarms  see also    Alarm  Descriptions    on page 30     Wi
12.  starts  It runs until the sump level drops below a  specified stop level          Start and stop level switches  When the level in the  pump sump exceeds the start level switch  the pump  starts  It runs until the sump level drops below the  stop level switch          Only start level switch  When the level in the pump  sump exceeds the start level switch  the pump starts   It runs a specified time  and then stops     For each configuration  there is a set of default values     FGC 211    Reset  Esc  OK    1    0    Push buttons to  navigate menus    Display  Power  LED  High level  LED  Pump status    LED    Relay status  LED    Alarm status  LED    Reset  push button  Push button to change  between automatic and  manual pump control    Push button to block  pump operation    Language   lt Not selected gt     OK    If the following is  installed    Use the following default  values       4 20 mA level sensor  Compit analogue  Start and Stop level  switches  Level regulator    Only Start level switch  Level reg  time  FGC is used in PSS  application  PC Pump    General     7_    OK    Set default val   No  7_8    LPSS    30 32     Issued  Supersedes     7    4 12    To select defaults     1  Press the  button to be able to change the value  in the displayed Set default val  menu     2  Press the  button repeatedly to until the name of  the defaults is displayed     For example  if the installation includes both start and  stop level switches  select  Level regulator      3  
13.  states  for example  1001100100000000  11      LED output      Common  alarm output    Flashes at 1 second  interval     20  Analogue input  Shows the raw input  values  0 16383    24  P1 current input  Shows the raw input  values  0 16383   This  starts the pump     22     28    Troubleshooting    c  Check if the impeller is jammed or damaged     d  If used  check if the level sensor is faulty     e  When the problem is corrected  press the  button  The LED should no longer be continuously  lit     6  If the error cannot be found after following the  instructions above  contact a FLYGT service agent     8 2 4  Blocked Pump    Problem     Relay status LED  is continuously lit red     Checklist     1  If the pump fails to start     a  Check if  Auto  is selected in the P1 State  menu  5_1      b  If not  select  Auto  in the P1 State menu  5_1    The LED should stop being lit red     c  If the LED still is lit red  check if  On  is selected in  the Ex mode menu  7_5      d  If selected  the FGC is set to Ex mode  see also     EX classified Environment    on page 23  The  pump will be blocked as long as there is no liquid  in the pump sump  When there again is liquid in  the pump sump  the LED should stop being lit red     5  If the pump starts with the LED continuously lit red   contact a FLYGT service agent     8 3  Diagnostic Programs    Diagnostic programs are used to test the hardware          All other functions are disabled when a diagnostic  program is run  that is  no
14. 1 state  5_1  Stop delay range  5_2  Stop delay time  5_3  Hi lev  run time  5_4  Max run time  5_5    Alarm setup  6_  Al delay Powfail  6_1  Resp  err  alarm  6_2    General  7_  Control mode  7_1  Stop condition  7_2  Run time  7_3  Common alarm  7_4  EX mode  7_5    Automatic reset  7_6  H  lim retry del   7_7  Set default val   7_10    Diagnos  Program  7_11    Language  8    Hold out run time  5_6  Blocking enable  5_7    L  lim retry del   7_8  System version  7_9    A    B    Issued  Supersedes     9    4 12    3  Installation    3 1  Introduction    The installation descriptions and figures can refer to  terminals on the main board  For information on  locations  see also    Wiring Diagram    on page 16  The  following symbols can also be used in the figures     3 2  Installing the FGC    3 2 1  Explosive or Flammable Environment    3 2 2  Equipment Cubicle    The FGC can be installed in an equipment cubicle   Ensure that its operating temperature is between   4  F to  113  F          Heating will normally be required in winter if the  cubicle is located outdoors or in a similarly cold  environment          Heating of the cubicle is also recommended to avoid  condensation          The cubicle temperature may become too high in  summer if ventilation is inadequate     Normally open  Normally closed    The FGC must not be installed in an explosive  or flammable environment     15    Issued  Supersedes     10    4 12    3 3  Installing Sensor or Switches    Use either a
15. 2 1  Backup Pump Control                               6 2 2  Stop Delay                                                 6 3  Pump Control                                            6 3 1  Fixed Pump Delays                                   6 3 2  Automatic Maintenance Run                     6 3 3  High Temperature                                      6 3 4  EX classified Environment                         6 3 5  Maximum Run Time for a Pump                6 3 6  Pump Response                                        6 4  Alarm Configuration                                  6 4 1  Alarm Delay                                               6 4 2  Audible or Visual Alarm Indication              7  Basic Operation                                       7 1  Introduction                                               7 2  Viewing Runtime Data                               7 3  Resetting Runtime Data                            7 4  Controlling the Pump                                7 4 1  Automatic Control  Auto Mode                 7 4 2  Manual Control  Manual Mode                 7 4 3  Blocked Pump  Blocked Mode                 7 4 4  View Control Status                                7 5  Pump Failure Block                                   7 6  Handling Alarms                                        7 6 1  Acknowledge an Alarm                             7 6 2  Viewing Alarms                                          7 6 3  Clear the Alarm Log                                     
16. 3  Start  run and stop    The following describe the possible LPSS scenarios     10 3 1  Scenario A   Normal pressure    1  Sewage level in the well rises above the start level     2  Pressure at the pump outlet is below the pressure  sensor   s threshold value     3  FGC starts the pump     4  Pumping lowers the sewage level in the well below  the start level     5  FGC stops the pump     10 3 2  Scenario B   High pressure at start    1  Sewage level in the well rises above the start level     2  Pressure at the pump outlet is above the pressure  sensor   s threshold value     3  FGC blocks the pump from starting     4  Count down to next start attempt begins     5  The pressure at the pump outlet is checked          Pressure is above sensor   s threshold   Continued  blocking  3           Pressure is below sensor   s threshold   Blocking  no longer in effect  6      6  FGC starts the pump     7  Pumping lowers the sewage level in the well below  the start level     8  FGC stops the pump     10 3 3  Scenario C   High level    1  Pressure at the pump outlet is above the pressure  sensor   s threshold value     2  FGC blocks the pump     3  Sewage level in the well rises above the High level     4  FGC ignores the high pressure blocking     5  FGC starts the pump     6  Pumping lowers the sewage level in the well below  the start level     7  FGC stops the pump     10 3 4  Scenario D1   Over current at start    1  FGC starts the pump     2  FGC immediately registers over curre
17. 8  Troubleshooting                                             8 1  Introduction                                               8 2  Basic Problems                                         8 2 1  Power Supply                                            8 2 3  Pump Failure                                             8 2 4  Blocked Pump                                           8 3  Diagnostic Programs                                      18  18    19    19  20  20  20  20  20  21  21  21  21    22    22  22  22  22  22  22  22  22  22  23  23  23  23  23    24    24  24  24  24  24  24  24  24  25  25  25  25  25    26    26  26  26  26  27  27    Issued  Supersedes     3    4 12    9  Appendix A  FGC Descriptions              9 1  LED Descriptions                                      9 2  Alarm Descriptions                                   9 3  Menu Descriptions                                     10  Appendix B  LPSS Scenarios               10 1  Operation variants                                  10 2  Permanent blocking                               10 3  Start  run and stop                                  10 3 1  Scenario A   Normal pressure                10 3 2  Scenario B   High pressure at start        10 3 3  Scenario C   High level                           10 3 4  Scenario D1   Over current at start         10 3 5  Scenario D2   Current rising                     28    28  29  30    33    33  33  33  33  33  33  33  33    Contents    Issued  Supersedes     4    4 12
18. Auto  Program controlled automatic or blocked  state for Pump 1    5_2  1 Stop delay range  m  Writable Interval  0 00 To 2 50  0 00  0 22  0 00  0 00  0 00  Specifies an additional height  below the  Stop level  to be pumped down   The RTU calculates the stop delay time  required to lower this height   0   Inhibits the function  5_3  Stop delay time  min s  Writable Interval  00 00 To 59 59  00 00  00 45  01 00  00 00  00 01  Delays the stop of the pump with the set  time   NOTE  If the calculated stop delay  function is activated  this set point defines  the maximum allowed calculated stop  delay time    Appendix A  FGC Descriptions    Issued  Supersedes     31    4 12    5_4  Hi lev  run time  min s  Writable Interval  00 00 To 59 59  01 00  00 20  01 00  02 00  01 00  Backup control activated when there is a  level sensor failure  The high level switch  activates the start of the pump  which will  then run for the period set in this menu   5_5  Max run time  min s  Writable Interval  00 00 To 59 59  30 00  30 00  30 00  30 00  30 00  The maximum time the pump is allowed to  run continuously   0   disables the function   5_6  Hold out run time  min s  Writable Interval  00 00 To 59 59  00 00  00 00  00 00  00 00  00 00  The pump will continue running for the  duration of the interval   0   disables the function   5_7  Blocking enable  Writable  Alternative      No      Yes    No  No  No  No  No     Yes    enables blocking by an external  blocking relay  such as a purge tim
19. C2  Connection for display unit    LED    L2  Power on indicator    L1  Power Fault Indicator    Location Description  Terminal    24 VDC    Issued  Supersedes     16    4 12    Denomination    Model  Part  no Pumps LCD Display    FGC 211 2000001 40 501830 1  Yes    1Consists of   Qty  1     Circuit Board  Qty  1     Display Card  Qty  1     Ribbon Cable  Qty  1     Overlay    Power Supply    Rated voltage  24 VDC  20 28 VDC   Current consumption  internal 100 mA at 24 VDC    Rated pump current  1 phase  Max  9 9 A  Min  0 5 A    Basic fuses  Internal fuse  100 mA  non replaceable     Approvals and Standards    EMC emission standard  EN61000 6 3  EMC immunity standard  EN61000 6 2  LVD electrical safety  EN IEC 61010 1  CE Marking    Environment    Operational temperature2    4   F to  113   F  Storage Temperature    4   F to  158   F  Humidity  non condensing   90  RH  Operator Panel  Class 1  IP 54  CAT II  Altitude  Max  6562 ft  Pollution degree  2    2 The LCD display will update slower below 32   F     Material    Operator Panel  ABS V0    Data Processing Power    Processor  PIC18F4620  Executed word length  8 bits  Clock frequency  32 MHz  Text memory  64 kB  Watchdog  Yes    User Interface    Display  LCD 2x16 characters  Push buttons  9 pcs  Alarm indications  4 LEDs  FGC status indications  3 LEDs    Digital Inputs    Start switch  Stop switch  High level switch  Thermal contact    Relay Outputs    Common alarm Voltage free  Max load 230 VAC  5 A     Analogue input 
20. Diagnos  Program  Writable  Alternative      Off      1 39    Diagnostic program for test of the RTU    8     Language  Writable  Alternative      English      Deutsch      Nederlands      Fran  ais      Dansk      Svenska      Norsk      Espa  ol      Magyar      Suomi      Italiano      PycckNN      Polski    Select display language    No  Menu Name  Menu Options    Factory  Settings    Compit  Analogue    Level  Regulator    Level Reg   Time    PC Pump    Description    1 Menu shown only when Control mode menu  7_1  is set to  Analogue    4   20 mA level sensor     2 Menu shown only when Control mode menu  7_1  is set to  Digital    Level switches     Appendix A  FGC Descriptions    Issued  Supersedes     33    4 12    10 1  Operation variants    The scenarios presented below  each describing a  complete cycle  assume that the equipment is set up as  described in chapter 3 8  FGC 211 in a LPSS application     In these examples  pumping stops when the sewage  level gets below the stop level  Alternatively or in addition  to this  FGC 211 can be configured to stop the pump after  a certain run time  This may cause pumping to stop while  the sewage level is still above the stop level  In case the  sewage is also above the start level  this will result in a  new count down to pump start     10 2  Permanent blocking    Should the maximum number of allowed pump start  attempts be exceeded  the FGC will block the pump  permanently   Otherwise  blocking  is just temporary      10 
21. Issued  Supersedes     1    4 12    FGC 211  Installation and user manual    This manual is applicable to the following versions     Hardware  FGC 211    Display board  AFH1901 Rev 1 01  Main board  AHH1901 Rev 1 01    System Software  2 42 or later    Issued  Supersedes     2    4 12    Contents    1 Read This First                                           1 1  Introduction                                                 1 2  Safety Regulations for Owner Operator     1 3  Guarantee                                                    1 4  Used Symbols                                             1 5  Safety Instruction                                          2 Short Guides                                               2 1  Installation Checklist                                  2 2  Getting Started                                            2 3  Menu Reference Chart                                  3 Installation                                                  3 1  Introduction                                               3 2  Installing the FGC                                     3 2 1  Explosive or Flammable Environment        3 2 2  Equipment Cubicle                                      3 3  Installing Sensor or Switches                   3 3 1  Cabling                                                         3 3 2  Pneumatic Sensor LTU 301                         3 3 3  4   20 mA Level Sensor                                 3 3 4  ENM 10 Level Regulators                 
22. On    Off  On  Off  Off  Off  When EX mode is on  the pumps are not  allowed to start unless water can be  detected in the sump  The function is used  primarily in explosive environment  7_6  Automatic reset  Writable Interval  0 To 200  1  0  1  1  1  Automatic reset of the pump following an  Over current failure   0  Inactivated function  The RTU blocks  the pump on first Over current   1   200  Activated function  The RTU will  attempt to start the pump 1   200 times  before blocking     No  Menu Name  Menu Options    Factory  Settings    Compit  Analogue    Level  Regulator    Level Reg   Time    PC Pump    Description    Appendix A  FGC Descriptions    31    Issued  Supersedes     32    4 12    33    Appendix A  FGC Descriptions    7_7  H  lim retry del   min s  Writable Interval  00 00 To 59 59  00 00  00 00  00 00  00 00  30 00  The value entered is the highest possible  value for the randomized start retry delay   7_8  L  lim retry del   min s  Writable Interval  00 00 To 59 59  00 00  00 00  00 00  00 00  10 00  The value entered is the lowest possible  value for the randomized start retry delay   7_9  System version  Read only  The RTU system version  Please have  this number ready when calling Flygt  support   7_10  Set default val   Writable  Alternative      No      Compit  analogue      Level regulator      Level reg  time    Restores all parameter values to the  selected set of default values   Operating data and the language setting  are not affected    7_11  
23. Press the  button to save the changes     The FGC is restarted and initialised with the selected  set of default values     Specify Maximal Motor Current    If the motor current for the pump exceeds this limit  the  pump is stopped and blocked  An alarm is also  generated     To specify the maximal current     1  Press the  button repeatedly until the display  shows the P1 current menu   The shown current can  differ from 0 0 A      2  Press the  button to access the submenu  The  display will show the High current P1 menu     3  Press the  button to be able to change the value  in the displayed menu     A flashing cursor will appear     4  Press the  button repeatedly to specify the first  digit  For example  if the maximal current for the  pump is 6 0 A  enter the digit  6      5  Press the  button to move the cursor a step to  the right     6  Press the  button repeatedly to specify the last  digit  For example  if the maximal current for the  pump is 6 0 A  enter the digit  0      7  Press the  button to save the changes     The display will show  Value stored   and then the  new parameter value     8  Press the  button to exit the submenu  The  display will again show the P1 current menu   The  shown current can differ from 0 0 A      Checking the Installation    When the above configuration is complete  the unit is in  automatic mode  and should be ready for operation     The LEDs on the front panel indicate unit status   including potential problems  If there is a prob
24. able menus     No  Menu Name  Menu Options    Factory  Settings    Compit  Analogue    Level  Regulator    Level Reg   Time    PC Pump    Description    1  Alarm log  Writable  Number of recorded alarms     2_  1 Level  m    Read only  NA  00 00  m    NA  NA  NA  Level in pump sump    2_1  1 Start Level 1  m  Writable Interval   99 99 To 99 99  NA  00 15  m  NA  NA  00 50  m  Start level for the pump     2_2  1 Stop Level 1  m  Writable Interval   99 99 To 99 99  NA  00 10  m  NA  NA  00 20  m  Stop level for the pump     2_3  1 High Level  m  Writable Interval   99 99 To 99 99  NA  00 25  m  NA  NA  00 70  m  High level alarm limit     2_4  1 Sensor range  m  Writable Interval  0 00 To 20 00  NA  02 50  m  NA  NA  02 50  m  Sensor range     2_5  1 Sensor calib   m  Writable Interval   99 99 To 99 99  NA  00 00  m  NA  NA  00 00  m  Sensor calibration offset     3_  P1 current  A    Read only  Interval  0 0 To 99 9    Measured current for the pump     3_1  High current P1  A  Writable Interval  0 0 To 9 9  5 3 A  5 3 A  5 3 A  5 3 A  5 3 A  High current alarm limit for the pump     4_  Operating data  Read only  Menu group for operating data    4_1  P1 start counter  Writable  0  0  0  0  0  Number of start for the pump    4_2  P1 run hour  h min  Writable  0 00  0 00  0 00  0 00  0 00  Run hour for the pump    5_  Pump control     Read only  Menu group for pump control    5_1  P1 state  Writable  Alternative      Auto      Blocked      Manual mode    Auto  Auto  Auto  Auto  
25. ay initiate the flush when necessary     3 8 8  System overview    This is a schematic view of the standard     and  optional      components of the LPSS application     Standard components are the Tank  T   Pump  P    FGC 211 and Open Bell level system  OB   with  LTU 301 sensor  Optionally a High level float  H    Pressure Switch  PS  and Flush Timer  FT  may be fitted     P     PS      FT      FGC211     H    T     OB     system     22     Issued  Supersedes     15    4 12    3 9  Wiring Diagram    Main board AHH 1901 is used to control 1 pump  The layout and contents are specified below     Power    P1  Power supply  1  4  P2  Earth terminal  4 pcs 6 mm2   5   8  P3  Fuse F2  T100mA L for internal use   P4  Current transformer for the pump    I O    I1  Common alarm output  potential free contact  Max  250 VAC   5 A   9    11  I2  Thermal contact input for the pump   12   13  If not used  make sure a jumper lead is placed on the input    I3  Stop level switch input  14  15  Terminal 14 is a common terminal for all level switches  stop  start and high level     I4  Start level switch input  14  16  Terminal 14 is a common terminal for all level switches  stop  start and high level     I5  High level switch input  14  17  Terminal 14 is a common terminal for all level switches  stop  start and high level     I6  Analogue level sensor input  4 20 mA  18   20    Connector    C1  Jumper pins for internal buzzer   Main board version 1 00 has no internal buzzer   and no pins    
26. cked Pump  Blocked Mode     on  page 24         The FGC is set to Ex mode  and there is no liquid in the pump sump  see also     EX classified Environment    on page 22     Pump failure  Possible causes         Pump start is delayed  see also    Fixed Pump Delays    on page 22     Pump status  Green  on     Red  on     The pump is running     The pump is stopped and blocked from restarting  Possible causes         Pump current exceeds its configured maximum  see also    Maximum Motor  Current    on page 21         Temperature in the pump is too high  see also    High Temperature    on  page 22         Pump has run longer than the configured maximum time  see also    Maximum  Run Time for a Pump    on page 23     High level    Red  on   The level in the pump sump is high  Possible causes         Level exceeds a high level switch  The pump is started automatically  see  also    Backup Pump Control    on page 22         Level exceeds the configured high level limit  see also    Start  Stop and High  Levels    on page 21  This is only relevant if a level sensor is used     17     Issued  Supersedes     29    4 12    9 2  Alarm Descriptions    The FGC can generate the alarms listed in the table below  The columns describe the following         The alarm text shown in the Alarm log menu  1          The event or error that caused the alarm         Whether the pump is stopped and blocked from restarting due to the event or error         Whether any LED  except the Alarm status LED  i
27. configuration   The right most rectangles contain footnotes     Analogue level  sensor  Digital level  switches    Stop after a    time    Stop level    switch  If necessary  enter an offset for the sensor  in the Sensor calib  menu  2_5     Enter when the pump should start  in the Start level 1 menu  2_1     Enter when the pump should stop in  in the Stop level 1 menu  2_2     Enter when a high level alarm is generated  in the High level menu  2_3     Enter the range for the sensor  in the Sensor range menu  2_4   How to  stop the pump     How to  measure the level in  the pump sump     Enter the maximum pump current in the High current menu  3_1     5  Configuration    6      20    20    20    20    21    21    22    24    30 32     Issued  Supersedes     20    4 12    5 2  Startup    To measure the level in the pump sump  you can use  either          Digital level switches  Continue with    Configuring  Level Switches    on page 21          Analogue level sensor  Continue with    Configuring a  Level Sensor    on page 21     5 3  Configuring Level Switches    When the level in the pump sump          Exceeds the start level switch  the pump is started          Drops below the stop level switch  the pump is  stopped   In some installations  there is no stop level  switch  as described below           Exceeds the high level switch  a  High level  alarm is  generated     Since a pump is used to drain a pump sump  the stop  level switch is installed below any start level switch
28. deleted     e  Press the  button to delete the inactive  alarms  The message  Log cleared  is displayed     Reset    Reset    OK    Esc    OK    OK    OK    29     Issued  Supersedes     26    4 12    8 1  Introduction    This chapter describes troubleshooting     8 2  Basic Problems    8 2 1  Power Supply    Problem     Power LED  is not lit     Checklist     1  The main power supply is off  Check the external  main switch and main fuse     2  If the error cannot be found after following the  instructions above  contact a FLYGT service agent     Make sure mains power supply is  disconnected before any maintenance work  on the FGC or pump     8 2 3  Pump Failure    Problem     Pump status LED  is continuously lit red     Checklist     1  Check if the Alarm log menu  1  contains the alarm   P1 high temp      2  If the log contains the alarm  the thermal contact in  the motor winding has opened due to high  temperature   The contact is normally closed      a  Check that the thermal contact is wired as shown  in the wiring diagram  see also    Connecting  Thermal Contact    on page 13     b  Check if the pump is damaged  for example   bearing or winding failure     c  Check if pump impeller is jammed     d  When the problem is corrected  press the  button  If the pump has cooled down  the LED  should no longer be continuously lit  Otherwise   wait a while for the pump to cool down and then  press the button again     5  Check if the Alarm log menu  1  contains the alarm   P1 Hig
29. e the block  If the pump has  cooled down  it will be allowed to start  Otherwise  try  again a little later     6 3 4  EX classified Environment    When a pump is used in an EX classified environment   you can set the FGC to EX mode  If no liquid is detected  in the pump sump  the FGC will prevent the pump from  starting  The starting method will not matter  that is  any  manual start attempt  or maintenance run will be blocked     To configure Ex mode     1  Display the Ex mode menu  7_5      2  Select either           On  to set the FGC to EX mode           Off  to disable EX mode     If the pump is installed in an EX classified  environment  check the pump approvals  before pumping below the stop level     Make sure to disconnect mains power supply  before any maintenance work  since the pump  will start automatically every 96 hours as long  as mains power supply is on     6  Additional Configuration    19     Issued  Supersedes     23    4 12    6 3 5  Maximum Run Time for a Pump    This is the maximum time a pump can run continuously   When this time has elapsed  the pump is stopped and  blocked from restarting   An alarm is also generated      This limit is useful  for example  to stop a clogged pump  from running too long  The alarm indicates that  something is wrong  for example  that the pump impeller  is damaged and delivers insufficient flow  or that a level  sensor is faulty     The specified limit must exceed one pumping cycle   Consider that the following setti
30. er     6_  Alarm setup     Read only  Menu group for alarms    6_1  Al delay Powfail  min  Writable Interval  0 To 960  1 min  1 min  1 min  1 min  1 min  The delay of a Power failure alarm before  it is recorded     6_2  Resp  err  alarm  Writable  Alternative      No      Yes    Yes  Yes  Yes  Yes  Yes  When the pump current is below 0 5 A the  RTU will register a pump response error  alarm   To disable the pump response error alarm  function  select  No      7_  General     Read only  Menu group for general set points    7_1  Control mode  Writable  Alternative      Digital      Analogue    Digital Anal   Digital Digital Anal   Selects if an analogue sensor or level  switches are used for starting and  stopping the pumps   Also referred to as analogue and digital  mode   7_2  2 Stop condition  Writable  Alternative      Run on time      Stoplevel switch    Stop  level  switch    NA  Stop  level  switch    Run  on  time    NA  Selects if a stop level switch is present or  the pump is stopped after a time   Applies to digital mode only     7_3  2 Run time  min s  Writable Interval  00 00 To 59 59  00 00  00 00  00 00  00 20  00 00  The pump running time when configured  to Run on time  i e  no stop level switch is  used   Applicable to digital mode only   7_4  Common alarm  Writable  Alternative      Continuous      Intermittent    Cont   Inter   Cont   Inter   Cont   Type of common alarm output   Continuous or pulsating     7_5  EX mode  Writable  Alternative      Off      
31. h cur      Reset    6  If the log contains the alarm  the pump current has  exceeded its configured maximum     a  Check that the High current P1 menu  3_1  is set  to the correct maximum current  see also     Maximum Motor Current    on page 22     b  Check if the pump is damaged  for example  bearing failure or winding fault     c  Check if the pump impeller is jammed     d  When the problem is corrected  press the  button  The LED should no longer be continuously  lit     5  Check if the Alarm log menu  1  contains the alarm   P1 Max run      6  If the log contains the alarm  the pump has run longer  than the configured maximum time     a  Check that the Max run time menu  5_5  is set to  the correct maximum current  see also    Maximum  Run Time for a Pump    on page 24     b  Check if the pump is clogged     Reset    8  Troubleshooting    12     21     23     3     4     c  Check if the impeller is jammed or damaged     d  If used  check if the level sensor is faulty     e  When the problem is corrected  press the  button  The LED should no longer be  continuously lit     7  If the error cannot be found after following the  instructions above  contact a FLYGT service  agent     Reset    Issued  Supersedes     27    4 12    28    Troubleshooting    c  Check if the impeller is jammed or damaged     d  If used  check if the level sensor is faulty     e  When the problem is corrected  press the  button  The LED should no longer be continuously  lit     6  If the error cannot
32. he installed  unit     Use cables that minimize interference from  electrical and magnetic fields  Run the cables  in a way that further minimize interference     The many potential sources of such  interference include relay coils  solenoid  valves  switches  thyristor units  earth   ground  currents and static discharges     Susceptibility to interference also varies with  the electrical environment i e  to factors such  as cable lengths  screening and the use  or  otherwise  of interference suppression  Many  problems can be prevented by good planning     1 5  Safety Instruction    Electrical wiring must be carried out only by a  qualified electrician  All electrical installation  work must be carried out with the equipment  disconnected from the power supply  without  any possibility of being made live  and in  accordance with local regulations     1  Read This First     Issued  Supersedes     5    4 12    2  Short Guides    2 1  Installation Checklist    This is a short installation checklist  It is included for convenience only  and is in no way a replacement for the  Installation manual     Check   Installation step  More information  mark    Plan the installation of the FGC to       Avoid all danger due to electricity      Comply with the safety regulations      Comply with the guarantee regulations      Observe precautions for electrostatic sensitive devices      Avoid unnecessary exposure of the FGC      Minimize interference from electrical magnetic fields  Make su
33. he internal buzzer sounds  automatically  To deactivate the buzzer functionality   remove the jumper to the buzzer  see also below     Suitable for LPSS application    In the standard LPSS application  a flush timer   essentially a type of stop relay  can be used     When a pump is installed in an explosive  environment  the thermal contact for the pump  must be connected to the FGC     4 20mA    12  13  14  0  2  9  1  8  1  7  1  6  1  5  1  1  1  0  1  9    4 20mA    12  13  14  0  2  9  1  8  1  7  1  6  1  5  1  1  1  0  1  9    4 20mA    12  13  14  0  2  9  1  8  1  7  1  6  1  5  1  1  1  0  1  9    4 20mA    12  13  14  5  1  1  1  0  1  9  0  2  9  1  8  1  7  1  6  1  8  7  6    Wire with supply        9  10  11           9  10  11           Passive output  Active output    J16    On    Fail    Power    Jumper pins for buzzer    Issued  Supersedes     13    4 12    3 7  Installing Power Supply    3 7 1  Cabling    Make sure to run power and signal cables separately     3 7 2  Power Supply    A separate fuse must protect the FGC power supply   Flygt recommends the use of automatic switch acting on  all poles     If a Flygt pump is connected in accordance with the  instructions for its electrical connection  its direction of  rotation will always be correct     3 7 3  Earthing  Grounding     An equipment earthing  grounding  conductor must be  connected to one of the earth terminals in the FGC   terminal 5   8      The earthing conductor should be connected to the be
34. he menu   and change it if necessary     To change the value  press the  button  A  flashing cursor will appear   If a value cannot be  changed  the message  Read only  will be displayed  instead      3  Enter or select the new value          Press the  button to increase the value          Press the  button to decrease the value          Press the  button to move the cursor a step  to the right   Only valid when you enter a text or a  numerical value           Press the  button to move the cursor a step to  the left   Only valid when you enter a text or a  numerical value      4  Either          Press the  button to save the changes          Press the  button to exit the menu without  saving the value     5  When a parameter value is saved  a message will  show the result           Value stored   The value has been saved           High value   The value is too high  Enter a lower  value           Low value   The value is too low  Enter a higher  value     For information on allowed values  see also    Menu  Descriptions    on page 31     4 6  Pump Control    Use the  and  buttons to change between  automatic and manual pump control  see also     Controlling the Pump    on page 25     4 7  Reset Function    With the  button  you can acknowledge a new alarm  or remove a pump fault block  see also             Pump Failure Block    on page 26             Acknowledge an Alarm    on page 26     4 8  Display Language    The display language is changed in the Language  menu  8_   Lo
35. his menu  is hidden           Pump current  View the present current in the  P1 current menu  3_           Number of pump starts  View how many times the  pump has started in the P1 start counter menu   4_1           Run time for a pump  View how long time the pump  has run in the P1 run hour menu  4_2      7 3  Resetting Runtime Data    You can reset the following runtime data          Number of pump starts shown in the P1 start  counter menu  4_1           Run time for a pump shown in the P1 run hour  menu  4_2      To reset runtime data     1  Display the relevant menu  for example  the  P1 start counter menu     2  Reset the value  that is     a  Press the  button to be able to reset the  value  The message  Reset value   is displayed     b  Press the  button to select  Yes      c  Press the  button to reset the value     7 4  Controlling the Pump    7 4 1  Automatic Control  Auto Mode     Normally  the FGC starts and stops the pump  automatically  This is called Auto mode     7 4 2  Manual Control  Manual Mode     In Auto mode  you can manually start the pump  This  changes the mode to Manual mode     Start the Pump Manually    Press the  button for 5   10 seconds until the display  briefly shows  Manual mode      Example     How Long Will the Pump Run     The pump will now run until the level in the pump sump  drops below the stop level     If the level in the pump sump already is below the stop  level  the pump will run for 5 minutes     Return to Auto Mode    When the
36. lem  check  that everything is installed and configured correctly     For information on how to interpret the LEDs and  troubleshoot  refer to             LED Descriptions    on page 29            Alarm Descriptions    on page 30            Troubleshooting    on page 27    What   s Next    When ready          FGC is now initialized with default values for the  specific installation         Pump is now ready to run     Trimming the FGC    If necessary  use the FGC menus to trim the installation   see also             Menu Reference Chart    on page 9            Configuration    on page 20            Additional Configuration    on page 23    OK    Set default val   Level regulator    OK    P1 current  00 0 A  3_    OK    High current P1  5 3 A  3_1    OK    High current P1  5 3 A    High current P1  6 3 A    OK    High current P1  6 0 A    Esc    P1 current  00 0 A  3_    28    29    26    8    19    22    Issued  Supersedes     8    4 12    2 3  Menu Reference Chart    This chart shows the menu structure in the FGC     Only shown when the Control mode menu  7_1  is set to    Analogue      4 20 mA level sensor     Only shown when the Control mode menu  7_1  is set to    Digital      Level switches     A  A  A  A    A    B  B    A  A    Alarm log  1    Level  2_  Start level 1  2_1  Stop level 1  2_2  High level  2_3  Sensor range  2_4  Sensor calib   2_5    P1 current  3_  High current P1  3_1    Operating data  4_  P1 start counter  4_1  P1 run hour  4_2    Pump control  5_  P
37. ngs can add time to a  pumping cycle          If the pump is set to run on time  see also     Stopping a Pump After a Time    on page 21          High level run time  see also    Backup Pump  Control    on page 23          If a stop delay is used  see also    Stop Delay    on  page 23     To specify the maximum run time     1  Display the Max run time menu  5_5      2  Enter either          Maximum run time          00 00  to disable the function   There will be no  limit for how long a pump can run      6 3 6  Pump Response    When the FGC has set the pump to start and the pump  current exceeds 0 5 A  the pump is considered to have  started     When the FGC has set the pump to start  but the pump  current remains below 0 5 A  the pump is considered not  to have started  An alarm can be generated     To disable pump response alarms  select  0  in the  Automatic reset menu  7_6   Otherwise  enter a number  from  1  to  200  in this menu     6 4  Alarm Configuration    An alarm alerts the receiver that something needs  attention  The FGC can generate alarms  for example  if  the temperature in a pump motor is too high  For a  complete list of possible alarms  see also    Alarm  Descriptions    on page 30     6 4 1  Alarm Delay    When the condition for an alarm is fulfilled  for example if  the level in the pump sump exceeds the configured high  level alarm limit  the alarm is generated     However  alarm generation can be delayed for a  specified time  The alarm condition then
38. nt and the over  current protection trips the pump     3  FGC blocks the pump     4  The  number of consecutive blocks  counter is  updated by  1 in the FGC          Total number of allowed start attempts is  exceeded   Permanent blocking  5           Total number of allowed start attempts is not  exceeded   Count down to start  6      5  FGC blocks the pump permanently   Alarm   end     6  Count down to next start attempt begins          Motor protection trips the pump   Blocking  3           Current is below motor protection threshold    Blocking no longer in effect  7      7  FGC starts the pump     8  The  number of consecutive blocks  counter in the  FGC is reset to 0     9  Pumping lowers the sewage level in the well below  the start level     10 FGC stops the pump     10 3 5  Scenario D2   Current rising    1  During pumping  resistance in the system increases     2  FGC registers over current and the over current  protection trips the pump     3  FGC blocks the pump   Updating of consecutive  blocks counter  Scenario D1  4  etc      Appendix B  LPSS Scenarios  10  Appendix B  LPSS Scenarios    
39. ok for the symbol  It is shown in the  top left corner of the Language menu     OK    Esc    OK    OK    Esc    1  0    Reset    Language  English  8    30     24     25     25     Issued  Supersedes     19    4 12    5 1  Introduction    This chapter describes how to configure basic parameters and set points in the FGC   For simpler configuration  refer  to    Getting Started    on page 7      To configure the FGC  follow the flow chart below     For a complete list of menus  refer to    Menu Descriptions    on page 31   33     For more information  refer to     A    Configuring Level Switches    on page 21  E    Start  Stop and High Levels    on page 22    B    Using a Stop Level Switch    on page 21  F    Maximum Motor Current    on page 22    C    Stopping a Pump After a Time    on page 21  G    Additional Configuration    on page 23    D    Configuring a Level Sensor    on page 21  H    Basic Operation    on page 25    D  A  B  C    D    A  C  A  B    A  C    D    E    E    E    F    G  H    The basic configuration is now finished  and the pump is ready to run     Refer to the rest of the manual for information on operation  as well as additional configuration options     Select    Stoplevel switch     in the Stop condition  menu  7_2     Select    Run on time     in the Stop condition  menu  7_2     Enter pump run time  in the Run time  menu  7_3     Select    Digital     in the Control mode menu  7_1   Select    Analogue     in the Control mode menu  7_1     Start the 
40. p that empties the sewage tank into the system     A few problems that need to be addressed are presented  here  in order to demonstrate how certain functions and  component accessories are employed in the application     Make sure to comply with the    Safety  Instruction    on page 5     When connecting a pump of a different brand   the direction of rotation must always be  checked  even if the Phase fault LED does  not light up     Power Supply  24 VDC    4     Below describes how to connect the power supply to  the FGC     Issued  Supersedes     14    4 12    15    3 8 2  Preventing over pressure in system    Problem  The individual pump controls must prevent  dangerous pressure levels by regulating the number of  pumps allowed to operate simultaneously     Solution  High pressure in the system is detected by a  pressure switch connected to the pumping outlet  When  pressure is too high  the FGC is prevented from starting  the pump  As a result  some units may have to wait for  other units to finish pumping     High pressure is also detected indirectly by the FGC   while monitoring the pump current  Should the work load  on the pump be too high  the current protection  i e  motor  protection  trips the pump  This not only protects the  pump from damage but also protects the whole system  from high pressure     Note  Using over current protection in this manner is  viable for PC pumps  For centrifugal pumps on the other  hand  over current is more likely caused by solids o
41. r  debris clogging the pump  necessitating a service stop     3 8 3  Avoiding simultaneous pump starts    Problem  The work load on the system is highly variable   Many households will be pumping sewage during  approximately the same morning and evening hours     Should a power down occur  the situation will be further  aggravated  When power is re established  many pumps  may attempt to start pumping simultaneously  causing  sudden pressure increases in the system     Solution  This problem is already handled in the FGC by  the power on delay  see    Fixed Pump Delays    on  page 23  which randomizes the start of individual pumps  within a 120 s time frame     3 8 4  Handling pressure increases during  operation    Problem  When the pump starts  pressure in the outflow  increases and may exceed the sensor   s limit     Solution  The pressure switch may only block the pump  start  i e  when the pump is already running  only over  current protection can stop the pump prematurely     3 8 5  Preventing over flow at high pressure    Problem  A high sewage level suggests that the tank may  be in danger of over flowing  This must be avoided     Solution  When the high sewage level is reached  the  pressure switch signal is no longer allowed to block the  pump start and the FGC can start the pump normally     Note  Over current will still block the pump from running   In order for the pump control to operate appropriately  the  blocking function is modified by the settings for numbe
42. r  of restart attempts described under the next heading     3 8 6  Resetting over current protection    Problem  In the LPSS application  it is likely that over  current protection will occasionally stop a pump   Previously FGC 211 could only handle a single restart  attempt  If this failed  due to the over current state still  remaining  restarting would be permanently blocked and  a service technician would be required before the pump  could be started again     Solution  It is now possible to enter a value for the  number of allowed restarts from 1 to 200  As soon as  the FGC successfully restarts the pump  the internal  counter of the number of consecutively blocked start  attempts is nullified     3 8 7  Flushing sewage from the system    Problem  In normal operation  sewage in the tank seldom  rises above the start level  This may cause residue to  build up around the tank wall  Additionally  the limited  volumes pumped out of the tank with each pumping cycle  may not create sufficient flush to clear out the sand that  may be settling in the pipes     Solution  A flush timer is used for blocking pump start for  a given time period   Xylem Inc  does not advocate  any particular settings for time delay or interval  as these  are determined by the actual situation   In this way  the  sewage is occasionally allowed to rise above the start  level  The increased sewage volume aids in flushing the    To prevent over flow  the high level switch over rides the  flush timer and m
43. re the main power supply for the FGC is off   Mount the FGC  Ensure that the temperature in any  equipment cubicle will be neither too high  nor too low   Install desired level sensor or switches in the pump  sump  and connect them to the FGC   If used  connect the thermal contact for the pump to the  FGC   If not used  make sure to place a jumper lead on the  thermal contact input in the FGC   If used  connect an external alarm device to the  common alarm output   Make sure a separate fuse is used for the main power  supply   Connect an earthing  grounding  conductor to the FGC    Recommended  Provide the main power supply with  overvoltage protection   Connect the FGC both to the main power supply and to  the pump   Check that all connections are correctly installed   Turn on the main power supply   Configure the FGC     Chapter    Read This First    on page 4  especially  Chapter    Safety Instruction    on page 4     Chapter    Installing the FGC    on page 9     Chapter    Installing Sensor or Switches    on  page 10   Chapter    Connecting Thermal Contact    on  page 12     Chapter    Connecting Alarm Output    on page  12   Chapter    Power Supply    on page 13     Chapter    Earthing  Grounding     on page 13   Chapter    Overvoltage Protection    on page 13     Chapter    Installing Power Supply    on page 13     Chapter    Getting Started    on page 6     Issued  Supersedes     6    4 12    2 2  Getting Started    This is a short description on how to get started wi
44. rmal pump control and  operation are prevented          After 10 minutes of idle time the FGC will  automatically revert to normal operation     To run a diagnostic program     1  Display the Diagnos  Program menu  7_9      2  Select one of the diagnostic programs  Available  programs are listed below   The rest of the programs  are for future use      To manually stop a diagnostic program  select   Off  in the Diagnosis  Program menu     Reset    Program Description  Results    10  Digital inputs  Shows the digital input  states  for example  1001100100000000  11      LED output      Common  alarm output    Flashes at 1 second  interval     20  Analogue input  Shows the raw input  values  0 16383    24  P1 current input  Shows the raw input  values  0 16383   This  starts the pump     Issued  Supersedes     28    4 12    9  Appendix A  FGC Descriptions    9 1  LED Descriptions    The front panel of an FGC includes a set of LEDs  see also    Front Panel    on page 18  The LEDs are described in the  table below     LED  Indication  Cause    Power    Green  on     Off    The power supply is on     The power supply is off  or a fuse is blown     Alarm status  Red  flashing     Red  on     A new alarm has occurred     The new alarm has been acknowledged  but is still active     Relay status    Green  on     Red  on     Red  flashing    The pump relay is activated     The pump is stopped and blocked from restarting  Possible causes         Pump is blocked manually  see also    Blo
45. s lit due to the event or error     Text in  Alarm Log  s  i  p  m  u  P  e  s  u  a  C  m  r  a  l  A  Blocked  LED Indication    High level  High level in pump sump  Alarm from the level sensor   No  High level  Mains error  The main power has been disrupted  Yes  Relay status  for phase  failures     Hi lev float  The level in the sump reaches the high level switch  The pump  will be started     No  High level    P1 Tripped  High current pump 1  Alarm from the analogue current  measurement   The pump is blocked by this alarm     Yes  Pump status    P1 No resp   There is no response signal from pump 1  The pump has  probably not started despite activation of the power relay     No    s  u  t  a  ts  p  m  u  P  s  e  Y     1  p  m  u  p  ni  e  r  u  t  a  r  e  p  m  e  t  h  gi  H  p  m  e  t  h  gih  1  P  Inval  setp   The level setpoints are incorrect  The specified setpoints for  Start  Stop or High level is either outside the calibration range or  they are mutually not corresponding  i e  the high level setpoint is  lower than the start level setpoint     No    P1 Max  run  The pump 1 has exceeded the maximum allowed run time  The  pump is blocked by this alarm   See also the Max run time set point     Yes  Pump status    Sensor Fault  An error in the analogue sensor has been detected  The  measured level is outside the sensor range     No    Appendix A  FGC Descriptions    Issued  Supersedes     30    4 12    9 3  Menu Descriptions    The table below describes avail
46. st  possible earth  such as an earthed mounting plate or an  earth rod  Remember that the earthing conductor must  be as short as possible     The shields of all shielded cables must be earthed by  connecting them to one of the earth terminals in the FGC     3 7 4  Overvoltage Protection    Flygt recommends that the mains power supply unit be  provided with overvoltage protection  with lightning  protection   Since this will make the FGC less sensitive to  overvoltage  the FGC can be used in more severe  environments     The protection should be connected in series with the  power supply  preferably to a separate earth  ground    such as an earth rod  although connection to the earth  busbar in the distribution box may sometimes suffice     A 6   10 mm   conductor should be used to connect the  overvoltage protection to earth     3 7 6  FGC 24 VDC Power Supply  3 phase 400 VAC  With Neutral Input     Below it is described how to connect the power supply to  the FGC     3 8  FGC 211 in a LPSS application    3 8 1  Background    In response to demands for a simple  efficient and  reliable solution for a LPSS system  Xylem Inc   proposes an application where FGC 211 is  used in combination with a Flygt PC pump  i e  a  Progressive Cavity  pump      The application presented here is typically intended for  situations where a number of family houses  e g  villas    each with its individual sewage tank  are connected to a  common pressurised sewage system  The FGC controls  the pum
47. stop level switch     To restore default values     1  Select the relevant set in the Set default value  menu  7_10      2  Wait while the FGC restarts     High level    Start level    Stop level    22     24     Issued  Supersedes     22    4 12    6 1  Introduction    Besides the basic parameters and set points described in     Configuration    on page 20  you may want to change the  ones described in this chapter     6 2  Level Configuration    6 2 1  Backup Pump Control    As backup  an installation can include a high level switch   It can be used together with start and stop level switches   as well as with a level sensor     If the start switches or the level sensor malfunctions  the  pump is started when the level in the pump sump  exceeds the high level switch   A  High level  alarm is  also generated      When the level in the pump sump drops below the high  level switch  the pump will continue to run for some  additional time     Specify this additional run time in the Hi  lev  run time  menu  5_4      6 2 2  Stop Delay    If a level sensor or level switch cannot be installed low  enough in a pump sump  a stop delay allows the pump to  empty the sump completely     A pump stop can be delayed until          The specified time has elapsed          The pump has lowered the level in the pump sump a  specified height   Only available for an analogue  level sensor      To delay the pump stop a specific time     1  If you use an analogue level sensor  enter  0 0  in the  S
48. t necessary to have  0 00      5  Optionally  you can calibrate the sensor     a  Make a note of the displayed level value   for example  00 20 m      b  Calculate the offset needed to display the  level  0 00 m   For example  if the displayed level  is  00 20 m   the offset needed is   00 20 m      c  Enter the offset in the Sensor calib  menu  2_5      d  Read the current level in the Level menu  2   and  make sure the displayed level is acceptable     5  In the pump sump  lower the sensor in the water     When ready  continue with    Start  Stop and High Levels     on page 22     High level switch    Start level switch    Stop level switch    20     20     21     21     21     Issued  Supersedes     21    4 12    5 4 1  Start  Stop and High Levels    When the level in the pump equals specified          Start level  the pump is started          Stop level  the pump is stopped          High level  a  High level  alarm is generated     Since the pumps are used to empty or drain a pump  sump  stop level  lt  start level  lt  high level     To specify the levels     1  Enter the start level in the Start level 1 menu  2_1      2  Enter the stop level in the Stop level 1 menu  2_2      3  Enter when the high level alarm is generated in the  High level menu  2_3      When ready  continue below     5 5  Pump Configuration    5 5 1  Maximum Motor Current    This is the maximum allowed current for a pump motor   and is normally the same as the nominal current of the  pump  The FGC au
49. th alarms  you can          Acknowledge that you have received an alarm         View recorded alarms in the alarm log         Clear the alarm log from inactive alarms    7 6 1  Acknowledge an Alarm    The FGC can be connected to both a buzzer  and another  audible or visual device  for example a lamp or siren  The  devices will be turned on when an alarm is generated     Press the  button to acknowledge that you have  received the alarm  This will also silence any connected  buzzer or other device     7 6 2  Viewing Alarms    The last 50 alarms are recorded in the alarm log  It shows  both inactive and active alarms     To view the alarm log     1  Display the Alarm log menu  1   It shows the number  of recorded alarms     2  View the log  that is     a  Press the  button to show the log  The first  alarm shown is the oldest alarm     b  Either  press the  button to display the latest  alarm     or  press the  button repeatedly to browse  the log     c  Press the  button to exit the log     7 6 3  Clear the Alarm Log    To remove one or more inactive alarms from the log     1  Display the Alarm log menu  1   It shows the number  of recorded alarms     2  Clear the log of the alarms  that is     a  Press the  button to show the log     b  If necessary  press the  button repeatedly  until desired alarm is displayed     c  Press the  button     d  Press the  button to select either      Current    Only the displayed alarm will be  deleted      All    All inactive alarms will be 
50. th the  FGC 211  The description is included for convenience  only  and is in no way a replacement for the Installation  manual     The figure below shows the front panel of FGC 211     Selecting Language    When the FGC is started for the first time  the display will  show the following     To proceed     1  Press the  button repeatedly until the display  shows the desired language  for example  English      2  Press the  button to save selected language   The display will show  Value stored   and then  change its text to the specified language     Set Default Values   Browsing to the Menu    At delivery  the FGC is set to factory defaults   They are  listed in    Menu Descriptions    on page 31   33   To use a  different set of default values     1  Press the  button repeatedly until the display  shows the following     2  The underscore after the menu indicator  7_   indicates that there are submenus     Press the  button to access them     3  Press the  button repeatedly until the display  shows the following     The following information is shown in the menu          Menu name   Set default val           Menu indicator   7_8   This indicator is shown for 3  seconds only          Parameter value   No      Set Default Values   Changing Values    One of the following sensor configurations is installed in  the pump sump          An analogue level sensor  4 20 mA   The sensor  measures the level in the pump sump  When the  sump level exceeds a specified start level  the pump 
51. tion manual for the sensor     2  Connect the sensor shield to the earth  ground   terminal of the FGC  that is  connect the shield cable  to one of terminals 5   8     FGC 211 in LPSS application    The components recommended for employing  FGC 211 in a LPSS application are highlighted  in the following texts by this light bulb symbol     Suitable for LPSS application    In the standard LPSS application  the digital  terminals 15 and 16 normally reserved for  Start level and Stop level regulators are  occupied by a pressure switch and a stop  relay  Instead an analog sensor is used   LTU 301 is ideally suited for this application     If the ATEX version is used  the open bell and  only the open bell can be installed in an  explosive or flammable environment    200 mm    500 mm    Open bell    4 20mA    12  13  14  15  16  17  18  19  20    Black wire    White wire    Red wire     Issued  Supersedes     11    4 12    3  The analogue input in the FGC  terminals 18   20  has  its own power supply  and can carry a maximum total  load of 12 V     Connect the sensor as follows  see also figure below          Connect the black wire to terminal 19          Connect the red wire to terminal 20         3 3 4  ENM 10 Level Regulators  Level  Switches     To install one or more ENM 10 level regulators     1  Install the level regulators in the pump sump     For more information  refer to the Installation and  operation manual for the regulators     2  Connect the ENM 10 level regulators 
52. to FGC as  follows          If used  connect the Stop level switch to terminals  14 and 15          If used  connect the Start level switch to terminals  14 and 16          If used  connect the High level float to terminals  14 and 17     3 3 5  Pressure Switch    An optional pressure switch can be connected to the  pumping outlet  preventing the FGC from starting the  pump while the pressure in the sewage system is high          If used  connect to terminals 14 and 16   Switch  open    high pressure  closed    low           For more information  refer to the installation  instruction of the pressure switch     For normal operation  use the blue and the  black wires   The switches will be normally  open      Terminal 14 is the common power supply  terminal for all level switches       4 20mA    12  13  14  5  1  1  1  0  1  9  0  2  9  1  8  1  7  1  6  1  8  7  6    Black wire    Red wire  Shield wire    High level float    Start level switch    Stop level switch     Suitable for LPSS application    In the standard LPSS application  the High level  switch is used     Suitable for LPSS application    In the standard LPSS application  a pressure  switch can be used     4 20mA    12  13  14  0  2  9  1  8  1  7  1  6  1  5  1  1  1  0  1  9    Blue wire    Black wire    4 20mA    12  13  14  0  2  9  1  8  1  7  1  6  1  5  1  1  1  0  1  9    Blue wire    Black wire    4 20mA    12  13  14  0  2  9  1  8  1  7  1  6  1  5  1  1  1  0  1  9    Blue wire    Black wire    4 20mA 
53. tomatically adds a 5  margin to the  specified value     If the motor current exceeds this limit after a calculated  delay  the pump is stopped and blocked from restarting    An alarm is also generated   However  if the FGC is set  to  Automatic reset   the FGC will attempt to restart the  pump up to the specified number of times  This is  specified in the Automatic reset menu  7_6   Should all  attempts fail  the pump will remain blocked     If restart is successful  but the motor protection is tripped  again during the following pump cycle  the pump is again  stopped  and possibly also blocked from restarting  as  explained above      To specify the maximum motor current     1  Enter the maximum current in the High current P1  menu  3_1      2  To use automatic reset  enter  1  in the Automatic  reset menu  7_6   Otherwise  enter  0  in this menu  to disable automatic reset     When ready  the basic configuration is complete  If  desired  you can continue with             Additional Configuration    on page 23             Basic Operation    on page 25    5 6  Restoring Default Values    If needed  you can restore the FGC to a set of default  values  Available are           Compit analogue      a set of default values for an  analogue level sensor installed in a Compit pump  sump           Level regulator      a set of default values when  using both start and stop level switches           Level reg  time      a set of default values when using  a start level switch  but no 
54. top delay range menu  5_2   This will disable the  stop delay based on a specific height     2  Enter the time in the Stop delay time menu  5_3      To set the pump to lower the level in the pump sump a  specific height     1  Enter the desired height in the Stop delay range  menu  5_2      2  The FGC calculates the pump run time necessary to  lower the level the required height  To prevent the    pumps from running dry  enter a maximum run time in  the Stop delay time menu  5_3      6 3  Pump Control    6 3 1  Fixed Pump Delays    Fixed delays are used to smoothen pump operation   They cannot be re configured     Minimum Stop Time  When a pump is stopped  it cannot  be restarted until after at least 5 seconds     Power on Delay  This delay prevents pumps in different  sumps from restarting simultaneously after a power  failure  When power is turned on after the power fault   pump start is delayed 0   120 seconds  During the delay     the Relay status LED  displays a flashing red light     6 3 2  Automatic Maintenance Run    If a pump has not been started within 96 hours  the FGC  will start the pump for a maintenance run that lasts 1  second  This is useful to keep the mechanical seals in the  pump in shape     6 3 3  High Temperature    The thermocontact in the pump can be connected to the  FGC  When the temperature in the pump is too high  the  pump is stopped  and blocked from restarting     Wait a while for the pump to cool down  and then press  the Reset button to remov
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
  Octobre 2012 - Fondation Agir Contre l`Exclusion    Turnitin ANGEL® 6.3, 7.1, and 7.2 Administrator User Manual  DeLOCK Card Reader IDE 40pin male to 2x Compact Flash  Sylvania SDPF833 Digital Photo Frame User Manual    Copyright © All rights reserved. 
   Failed to retrieve file