Data sheet DB EN AXL F BK PN - Phoenix Power Supplies Stocked

image

Contents

1. 4 Technical data Dimensions nominal sizes in mm 45 LX Duc Lo 125 9 Width Height Depth Note on dimensions General data Color Weight Ambient temperature operation Ambient temperature storage transport Permissible humidity operation Permissible humidity storage transport Air pressure operation Air pressure storage transport Degree of protection Protection class Mounting position Connection data Designation Connection method Conductor cross section solid stranded Conductor cross section AWG Interface PROFINET Number Connection method Transmission speed Transmission physics Transmission length Interface Axioline F local bus Connection method Transmission speed 45 mm 125 9 mm 74 mm The depth is valid when a TH 35 7 5 DIN rail is used according to EN 60715 traffic grey A RAL 7042 177g with connector and bus base module 25 C 60 C Mounting position wall mounting on horizontal DIN rail 25 C 55 C Mounting position any 40 C 85 C 5 95 non condensing 5 95 non condensing 70 kPa 106 kPa up to 3000 m above sea level 70 kPa 106 kPa up to 3000 m above sea level IP20 Ill IEC 61140 EN 61140 VDE 0140 1 Any observe temperature derating Axioline F connector Push in te
2. Local bus Internal wiring of the terminal points Functional earth ground Service interface Reset button Axioline F local bus hereinafter referred to as local bus RJ45 interface Power supply unit with electrical isolation Microcontroller Power supply unit LED Electrically isolated area 105731 en 01 www phoenixpowersupply co uk PHOENIX CONTACT 6 AXL F BK PN 6 Connecting PROFINET and supply 6 1 Connecting PROFINET Connect PROFINET to the bus coupler via an 8 pos RJ45 connector RJ45 Pin 1 dl Pin 4 Pin 5 Pin 6 Pin 7 Pin 8 Pin assignment of the Ethernet socket RJ45 LI m Figure 2 Only one twisted pair cable with an impedance of 100 O may be connected to each Ethernet interface in RJ45 format The data transmission speed is 100 Mbps The 100Base TX port of the bus coupler is able to detect a pair of incorrectly con nected receive cables RD RD and to correct them using the auto polarity correction function For the pin assignment please refer to the following table Pin Assignment TxD transmit data TxD transmit data RxD receive data Reserved Reserved RxD receive data Reserved Reserved CO N Oo AJO N Auto crossover Both Ethernet interfaces are provided with the auto crossover function Shielding The shielding ground of the connected twist
3. ed pair cables is electrically connected with the socket When connecting network seg ments avoid ground loops potential trans fers and voltage equalization currents via the braided shield Observe bending radii The housing dimensions specified under Di mensions refer to the bus coupler with I O connectors without Ethernet connection When installing the bus coupler in a control box observe the bending radii of the Ethernet cables and the connectors used e g FL CAT5 FLEX 30 mm for fixed installation and FL CAT5 HEAVY 30 mm without outer sheath and 45 mm with outer sheath If re quired use angled RJ45 connectors to main tain these bending radii 6 2 Connecting the supply voltage terminal point assignment Figure 3 Terminal point assignment Termi Color Assignment nal point Supply voltage input al a2 Red 24 V DC Supply of the logic voltage Ui internally jumpered bi b2 Blue GND Reference potential of the supply voltage internally jumpered 7 Connection example Ethernet d Figure 4 Connection of the cables 105731 en 01 PHOENIXCONTACT 7 www phoenixpowersupply co uk AXL F BK PN 8 Local status and diagnostic indicators BF e RDY SF m mD DE Uw
4. alarms are enabled how ever they can be disabled with parameters on startup An incoming alarm informs the PROFINET controller that di agnostic information has been stored When the diagnostic information has been removed an out going alarm is transmitted to the controller If atleast one piece of diagnostic information is stored the SF LED is on If no diagnostic information is present the SF LED is off 11 Startup Default upon delivery default settings By default upon delivery the following functions and fea tures are available PROFINET name No name assigned IP parameters 0 0 0 0 Module designation AXL F BK PN Vendor ID OOBOhex Device ID 1000hex Firmware started Once you have supplied the bus coupler with power or pressed the reset button the firmware is started After com pletion of the firmware boot process the BF LED is either on or flashing 105731_en_01 PHOENIX CONTACT 10 www phoenixpowersupply co uk AXL F BK PN Reset button The reset button is located beneath the top marking label on the bus coupler Reset button Figure 6 1 Labeling field 2 Reset button The reset button has two functions Restarting the bus coupler Resetting of the default settings Holding down the button during the initialization phase re stores the default settings If you wish to restore the default settings proceed as fol lows e Disconnect the power to the module e Press and
5. file are integrated into PC Worx If several versions of the configuration file are available make sure that you are working with the file version that corre sponds to the firmware hardware version used Other tools The PROFINET device is parameterized using the configu ration tool of the PROFINET controller Please integrate the corresponding GSDML file of the bus coupler into the rele vant software tool STEP 7 HW Config Make sure you always use the latest version of the FDCML GSDML file and the latest doc umentation for the bus coupler The latestfiles and documentation can be found on the Inter net at phoenixcontact net products D 14 Device replacement Devices can be replaced without having to reconfigure them within the PROFINET network The station name and ad dress are assigned by the control system to the newly added PROFINET bus coupler using the neighborhood detection function 15 Phoenix Redundancy Layer PRL The Phoenix Redundancy Layer PRL makes it possible to design a redundant system with two PROFINET controllers One controller is configured as the primary I O controller and the other as the backup I O controller Depending on which PROFINET controller provides valid values the bus coupler operated at field level adopts these values or uses failsafe values PRL or shared device and MRP can be used simultaneously if the PROFINET update time is gt 8 ms and the PROFINET watchd
6. hold the reset button e Switch on the power The LEDs indicate the initialization phase LED State Meaning RDY OFF Starting firmware RDY Yellow ON Initializing firmware RDY Green Initialization complete e When the RDY LED lights up green release the button The default settings are restored Documentation D How to assign the PROFINET names and the IP address as well as how to startup a device within a PROFINET system is described in the following documents PC WORX quick start guide Configuring INTERBUS devices in a PROFINET network using the example of STEP 7 quick start guide For the order designations please refer to the odering data The documentation can be found on the Inter net at phoenixcontact net products 12 Service interface The service interface is located beneath the top marking field on the bus coupler The service interface is used for diagnostics for parameter ization and for testing I Os before startup EUN Figure 7 Service interface 1 Labeling field 2 Service interface 105731 en 01 PHOENIX CONTACT 11 www phoenixpowersupply co uk AXL F BK PN 13 Parameterization PC Worx Parameterization of the PROFINET device in PC Worx re quires at least PC Worx Version 6 30 This is part of the AUTOMATIONWORX Software Suite 1 80 and 1 81 An online data sheet of the device with important technical data and a configuration
7. 00 Figure 5 Local status and diagnostic indicators Designation Color Meaning State Description UL Green ULogic ON Communications power supply present OFF Communications power supply not present BF Red Communica ON No link status available on any port tion error Bus Fail Flashing SF LED not flashing Link status available no communication con nection to the PROFINET controller Flashing SF flashing Hardware watchdog triggered OFF A PROFINET controller has established an active communication connection to the PROFINET device SF Red System failure ON PROFINET diagnostics available PROFINET OFF PROFINET diagnostics not available Flashing Flashes only together with the BF LED watchdog triggered RDY Green Ready Green Device is ready for operation yellow ON red Flashing Communications power undervoltage or surge voltage green Overtemperature yellow Flashing Device is in standby mode green yellow on Yellow Firmware bus coupler is booting ON Yellow Firmware update is being performed flashing Flashing Firmware update has failed yellow red Red Faulty firmware flashing OFF Device is not ready to operate 105731_en_01 PHOENIX CONTACT 8 www phoenixpowersupply co uk AXL F BK PN Designation Color Meaning State Description D Green Diagnostics Green Run Data exchange status and data from the higher level syste
8. AXL F BK PN Axioline F bus coupler for PROFINET Peng TI Im 1 Description The bus coupler links a PROFINET network with the Axioline F system You can connect up to 63 Axioline F devices to an existing PROFINET system with the help of the bus coupler Features Up to 63 additional Axioline F devices can be connect ed 2 Ethernet ports with integrated switch Typical cycle time of the Axioline F local bus is around 10 us PROFINET RT and IRT PROFIsafe support Minimum cycle time of PROFINET for RT and IRT is 250 us Runtime in the bus coupler is negligible goes to O us Firmware can be updated MRP Client Web based management I amp M 1 4 Shared device Diagnostic and status indicators A This data sheet is only valid in association with the UM EN AXL F SYS INST user manual For information on PROFINET basics please refer to the UM EN PROFINET SYS user manual DOD OO GD GD OGD OO OD istite dD INSPIRING INNOVATIONS www phoenixpowersupply co uk AXL F BK PN Table of contents 1 B eiepa D 1 2 Ree Ree LE c eh 2 3 CJC STING Po AU DM RR A M M TM RE RN 3 4 fierce pe PE 4 5 Internal circuit diagram iere e edes ot plebani RR Rd Land Cog RR E o eee 6 6 Connecting PROFINET and supply ier ee d tae er ruin Lek oen E HR UE Ee eek Enn Rcs 7 EI Connecting PROFINET aa eas a E a a E E Magee ened 7 6 2 Connecting the sup
9. ates in the event of an error LED Meaning Measure remedy in the event of an error SFOFF PROFINET de No error BF flash vice is waiting ing for communica tion with the PROFINET con troller The logic com Check the connection be munication con tween the PROFINET con nection has troller and the PROFINET been inter device Make sure that the rupted The PROFINET device name of PROFINET con the PROFINET device is troller can no identical with the configura longer be ac tion cessed The PROFINET Assign the PROFINET de device is not as vice name using the relevant signed a PROFI tool NET device name SFOFF The physical Restore the physical con BF ON communication nection between the path has been PROFINET controller and interrupted The the PROFINET device PROFINET con troller can no longer be ac cessed SFON _ Diagnostic data Read the diagnostic mes BF OFF is available sage using the relevant tool SF flash Hardware Execute a reset Replace ing watchdog has the device when the error BF flash been triggered occurs again ing The firmware update can take several min utes The bus coupler is restarted automatically af ter a successful update D 10 Diagnostic alarms PROFINET enables the PROFINET device to store diagnos tic information together with the error location and error type In the default upon delivery the
10. chnology 0 2 mm 1 5 mm 0 2 mm 1 5mm 24 16 2 RJ45 socket auto negotiation and autocrossing 100 MBit s Full duplex Ethernet in RJ45 twisted pair max 100m Bus base module 100 MBit s 105731 en 01 PHOENIX CONTACT www phoenixpowersupply co uk 4 AXL F BK PN Interface Service Number Connection method System limits Number of supported devices 1 Micro USB type B max 63 per station Observe the logic current consumption of each device when configuring an Axioline F station It is specified in every module specific data sheet The current consumption can differ depending on the individual module The permissible number of devices that can be connected therefore depends on the specific station structure D NOTE Electronics may be damaged when overloaded Protocols supported Protocols supported Supply of the bus coupler Supply of communications power UL Maximum permissible voltage range Current supply at U gus Current consumption from UL Power consumption at UL PROFINET FTP TFTP PTCP LLDP SNMP MRP DDI Boot P 24V DC 19 2 V DC 30 V DC including all tolerances including ripple 2A typ 105 mA without I Os and U 24 V max 570 mA with 2 A at Upys for the I Os and U 24 V typ 2 5 W without I Os max 13 7 W with 2 A load at Ug for the I Os Provide external fuses for the 24 V U area The power supply unit must be able to supply fou
11. he Factory Manager This document can be found on the Internet at phoenixcontact net products Please refer to the Diagnostic indicators for PROFINET section for the LED states during the firmware update 105731 en 01 PHOENIX CONTACT 12 www phoenixpowersupply co uk AXL F BK PN 20 Simple Network Management Protocol SNMP The bus coupler supports SNMP v1 and v2c Management Information Base MIB on the Internet at phoenixcontact net prod A The corresponding latest MIBs are available ucts For the object descriptions please refer to the ASN1 de scriptions for this product The password for read access is public and cannot be changed By default upon delivery the password for write read access is private and can be modified at any time 105731_en_01 www phoenixpowersupply co uk 13
12. m is yellow ON transmitted red Green Active configuration is active data exchange with invalid process flashing data PDI channel can be used Yellow Ready Device is ready to operate no data is exchanged ON Yellow Access from Startup device is in Force mode flashing Flashing Local bus error device is in Force mode yellow red Red Local bus error on startup flashing Configuration cannot be generated information is missing from a de vice Chip version of a device is V1 1 The desired and actual configuration are different No local bus device connected The maximum number of local bus devices is exceeded Red ON General local bus error Communication error Local bus device has been removed or configured device is missing Reset at a local bus device Serious device error at a local bus device local bus device can no lon ger be reached E Yel Error Yellow I O warning at a local bus device low ON red Red ON 1 O error at a local bus device 105731 en 01 PHOENIX CONTACT 9 www phoenixpowersupply co uk AXL F BK PN 9 Diagnostic indicators for PROFINET States during operation States during firmware update LED Meaning SFOFF PROFINET controller was able to establish BF OFF communication without errors LED Meaning RDY BootP requests are sent and the firmware con flashing tainer is loaded via tftp RDY ON Firmware is saved MON St
13. og time is 200 ms D 16 Dynamic configuration on the local bus You can use the Dynamic configuration function with this bus coupler Dynamic configuration is the specification and configuration of a maximum configuration Any subgroup of this maximum configuration can be operated 17 Substitute value behavior When PROFINET communication breaks down or an error occurs in the local bus all outputs of the Axioline F station are setto the parameterized substitute values The local bus continues to run with these values 18 WBM Web based management The device has a web server which generates the required pages for web based management and depending on the requirements of the user sends them to a standard web browser Web based management can be used to access static information e g technical data MAC address or dy namic information e g IP address status information Calling web based management The device web server can be addressed using the IP ad dress if configured accordingly The homepage web page of the device is accessed by entering the URL http ip address Example http 172 16 113 38 19 Firmware update In orderto update the firmware of the bus coupler the device must be provided with a firmware container via a TFTP server You can use any TFTP server e g Factory Man ager D The TFTP FIRMWARE UPDATE application note describes how to update the firmware us ing t
14. otection sleeve 2 pieces green for crossed cables for assembly on site For connections that are crossed it is recommended that the connector set with green bend protection sleeves is used Connector Adapter Crimping pliers for assembling the RJ45 plugs FL PLUG RUJ45 for as sembly on site Tools Zack marker strip for Axioline F device labeling in 2 x 20 3 mm pitch un printed 25 section for individual labeling with B STIFT 0 8 X PEN or CMS P1 PLOTTER Marking Zack marker strip flat in 10 mm pitch unprinted 10 section for individual labeling with M PEN 0 8 X PEN or CMS P1 PLOTTER Marking Insert label Roll white unlabeled can be labeled with THERMOMARK ROLL THERMOMARK X THERMOMARK 1 1 Mounting type snapped into marker carrier Lettering field 35 x 18 7 mm Marking Documentation User manual English Axioline F System and installation User manual English Axioline F Diagnostic registers and error messages Type AXL F BK PN Type AXL BS BK AXL CN S UL FL PLUG RJ45 GR 2 FL PLUG RJ45 GN 2 FL CRIMPTOOL ZB 20 3 AXL UNPRINTED ZBF 10 5 8 AXL UNPRINTED EMT 35X18 7 R Type UM EN AXL F SYS INST UM EN AXL F SYS DIAG Order No 2701815 Order No 2701422 2701421 2744856 2744571 2744869 0829579 0829580 0801831 Order No Pcs Pkt Pcs Pkt 25 50 Pcs Pkt 105731 en 01 www phoenixpowersupply co uk PHOENIXCONTACT 3 AXL F BK PN
15. ply voltage terminal point aSsigNnMent sssssssssssrsrrrsrrnersnnnnrrnnrnrnrnnnnrennnnennnn 7 7 Weieen e EN 7 8 Local Status and diagnostic IndIGalors ien ede e e RE eesti tl vase Up p Masthead neces 8 9 Diagnostic indicators for PDROEINET enn nemen nennen nnne 10 10 Diagnosuc alarms e o ede esty bete m Ru det utentes Lice aad ee edere RM Pet Pug 10 11 ripe Mc PETS 10 12 SSrvice Ier 3E E 11 SEN SE Ein e eec E 12 14 Device EE e LE 12 15 Phoenix Redundancy Layer ER use erecta eene Uer d e Rv ee een ku Pe Re dorus 12 16 Dynamic configuration on the local D s rooted dicerent ete a estan e ed ee nicus 12 17 Substitute EE 12 18 WBM Web based management eesesseseeseeeeetneneeen nnne 12 KC SE ue 12 20 Simple Network Management Protocol SNMP nenne 13 105731 en 01 PHOENIXCONTACT 2 www phoenixpowersupply co uk AXL F BK PN 3 Ordering data Description Axioline F bus coupler for PROFINET including bus base module and con nector Accessories Axioline F bus base module for housing type BK Replacement item Axioline F short power connector for e g AXL F BK Replacement item RJ45 connector shielded with bend protection sleeve 2 pieces gray for straight cables for assembly on site For connections that are not crossed itis recommended that you use the connector set with gray bend protection sleeve Connector Adapter RJ45 connector shielded with bend pr
16. r times the nominal current of the external fuse D NOTE Electronics may be damaged when overloaded to ensure that it blows in the event of an error Error messages to the higher level control or computer system None Mechanical tests Vibration resistance in acc with EN 60068 2 6 IEC 60068 2 6 Shock in acc with EN 60068 2 27 IEC 60068 2 27 Continuous shock according to EN 60068 2 27 IEC 60068 2 27 Conformance with EMC Directive 2004 108 EC Noise immunity test in accordance with EN 61000 6 2 Electrostatic discharge ESD EN 61000 4 2 IEC 61000 4 2 Electromagnetic fields EN 61000 4 3 IEC 61000 4 3 Fast transients burst EN 61000 4 4 IEC 61000 4 4 Transient surge voltage surge EN 61000 4 5 IEC 61000 4 5 Conducted interference EN 61000 4 6 IEC 61000 4 6 Noise emission test according to EN 61000 6 3 Radio interference properties EN 55022 Approvals For the latest approvals please visit phoenixcontact net products 5g 30g 11 ms period half sine shock pulse 10g Criterion B 6 kV contact discharge 8 kV air discharge Criterion A Field intensity 10 V m Criterion B 2 kV Criterion B DC supply lines 0 5 kV 0 5 kV symmetrical asymmetrical field bus cable shield 1 kV Criterion A Test voltage 10 V Class B 105731 en 01 PHOENIXCONTACT 5 www phoenixpowersupply co uk AXL F BK PN 5 Internal circuit diagram Figure 1 Key FE Service Reset Local bus LE EL 8 I B