Home
16-point Input Sink • Source Type" (FN-X16TS41)
Contents
1. C m Bottom View A Dip Switches cssccscsneaseeseausads Set communication speeds and S No first digit B S No station no Switch Sets S No last digit C Terminal Switch Changes termination ON OFF Turns ON only the unit connected at the end of the communica tion cable D Status LED acssciccescnotvoenses Indicates the unit s current operation status Switch Settings Examples of S No station no settings SW1 Reserved _Dip Switch SNo Station SW2 6 6 Mbps aoe no Setting 12 utes 12 Mbps OFF 0 ON 1 O 0 10h 16 SWS 4 First ON 1 6 18 o gt 7 wy Last OFF 0 EDE Arrow tip Setting values re N 1 N 1 ae co TERM OFF Termination OFF cee OFF ON ON Termination ON 5 Wiring the I O This section describes both the cables and crimp terminals used for wiring each type of cable The fastening torque for the ter minal screws should be 0 6 to 1 0 Nem lor 2 terminals can be connected to a single terminal screw E Communication Cable The Flex Network interface and the I O unit or all distributed I O units are connected using a cross wiring system T type systems cannot be used Use the following models of communication cables Distributor When preparing the cable wire ends Cover shielded wires with shield tape or with an insulation tube Use insulated crimp terminals If you use
2. ClassA EN61000 6 2 and EN61131 2 lt Caution gt While this unit is officially marked as conforming to the relevant EMC directives it is the user s final application of this unit in a larger system i e the machinery wiring control panel installation method etc that will determine if this unit maintains or loses this conformance marking Therefore it is strongly advised that the user investigate and confirm whether their overall system i e all related machinery and equipment also conforms with these EMC direc tives The National Electrical Code states that Class 2 power supplies and Class 2 transformers should not exceed an output of 30V and at 8A or less should not exceed IOOVA 2 Applies to selected low voltage directives Fal External Dimensions Part Names U nit mm in This section shows the external dimensions of the I O unit part names and part settings 12 1 0 48 A B D pid PEPi ri rt terete ttt tt ae i is ja z FNZ ISTSAI FA es U rena ea A N io Sunnu CIO OOOOOOOOOO B J 108 4 25 3 5044 t Front View Side View Factory Default settings Communication speed 6 Mbps S No station no 0 o eo GE Sy EY Ee 2
3. a pressure connection terminal without insula tion cover it with a shield tape or an insulation tube Cover uninsulated crimp terminals with shield tape or a tube type insulation Blue TR 3 8 0 15 Unit mm in White TR or less 5 2 0 20 OF or more Ob oO 5 Shield wire SLD 3 2 0 13 or larger E Power Cable e Use as large a cable as possible up to 1 25 mm and be sure to twist all wire ends before attaching crimp terminals e Use the same type crimp terminals as used for the commu nication cable E I O Cable e Use a cable that is 0 5 to 1 25 mm in diameter e Use the same type crimp terminals as used for the commu nication cable e Confirm that all I O unit terminal screws are se F TET curely tightened even if they are not used e Do not allow pieces of wire to fall inside the unit Note Please be aware that Digital Electoronics Corporation shall not be held liable by the user for any damages losses or third party claims arising from the uses of this product Head Office Digital Electronics Corporation 8 2 52 Nanko higashi Suminoe ku Osaka 559 0031 JAPAN Tel 81 0 6 6613 1101 Fax 81 0 6 6613 5888 URL http www pro face com Copyright 2000 Digital Electronics Corporation All rights reserved
4. Flex Network I O Unit 16 point Input Sink Source Type Installation Guide Thank you for purchasing Pro face s Flex Network I O Unit 16 point Input Sink Source Type FN X16TS41 unit To ensure correct use of this unit s functions and features be sure to carefully read this installation guide and the Flex Network DIO Unit User Manual downloaded from Pro face web site Safety Precautions This guide contains a variety of safety markings for safe and correct operation of this unit Please read this installation guide and any related manuals carefully to fully understand how to correctly use this unit s functions E Safety Symbols This guide uses the following symbols for important informa tion related to the safe and correct operation of this unit Please pay attention to these symbols and follow all instructions given Safety symbols and their meanings A hazardous situation that could result in serious injury or even death if instructions are not followed A potentially hazardous situation that could result in serious injury or even death if instructions are not followed A potentially hazardous situation that could result in minor injury or equipment damage if instructions are not followed 2 Specifications E Electrical Control section Rated Voltage DC24V Rated Voltage Range DC20 4 to DC28 8V Allowable Voltage 10ms or less Power Supply DC24V Interruption Power Consumption 1 5W or less Vol
5. X16TS41 is a UL c UL CSA recognized unit UL File No E195835 The FN X16TS41 unit conforms to the following standards E UL508 Electrical Control System for Industry E CAN CSA C22 2 No 1010 1 Safety requirements for electrical equipment for measure ment control and laboratory use FN X16TS41 UL Registration Model 2880063 02 lt Notes gt E Only use the unit installed with other equipment E If the unit is installed in an area with no air conditioning system be sure to install it in a vertical panel using a DIN rail or mounting holes Also be sure the unit is installed so it is at least 100 mm away from any adjacent structures or devices If these requirements are not met the heat gener ated by the unit s internal components may cause the unit to fail to meet UL standards requirements E The power supply unit connected to the I O unit must be a UL c UL CSA approved Class 2 power supply unit or Class 2 transformer When the GLC LT GP3000 or multiple I O units under load are operated with a single power supply the amount of current consumption and full load current of the I O units must be within the rated load of the Class 2 power supply unit or Class 2 power supply transformer Be aware that the number of points which can be turned ON simultaneously may be limited depending on the amount of load and load current value CE Marking Notes The FN X16TS41 is a CE Marked unit that conforms to EMC directives EN55011
6. ite http www pro face com If you require the manual on another type of media CD ROM etc please contact your local Pro face distributor E Input Circuit Connection Drawing 4 I O Unit Installtion E Installing on a DIN rail This procedure installs the unit on a 35mm DIN rail Installation Removal Hook the I O unit s top face Use a screwdriver to push the groove over the top edge of the attachment hook down and re DIN rail Next push the bottom lease the unit Then pull the unit of the I O unit forward until the forward and off the rail attachment hook clicks into place on the DIN rail DIN rail n Flat head screwdriver Push I O unit j nie Be sure that the top and bottom faces of the unit i are facing the correct direction and the unit is in stalled in a vertical position Incorrect installation may prevent heat from dissipating E Installing in a panel Create a panel cut for installing the unit using the dimensions given below Secure the I O unit in place with M4 size screws The torque should be 0 5 to 1 3 Nem E Important I O unit center ATMENT I O unit outline a a a E es Plata Center of DIN rail s3 T ee eee E a DY 5 25 8 O 48 1 to 50 3 1 89 to 1 98 50 3 1 98 98 4 to 100 6 3 87 to 3 96 UL c UL CSA Application Notes The FN
7. s wire pieces water or liq uids to enter inside this unit s case Otherwise a malfunction failure elec tric shock or fire may occur When disposing of this unit handle it as an industrial waste The input area shown here shows the connection wiring to a sink output type device The dotted line represents the connec tion wire to the source output type unit Internal Circuit Z The I O unit s power supply should be separated from Note the sensor s power supply to prevent the unit from being affected by external noise Dotted line shows the source output connection E To Avoid Damage e Avoid storing or operating this unit in either direct sunlight or excessively dusty or dirty environments e Because this unit is a precision instrument do not store or use it in locations where excessive shocks or vibration may occur e Avoid covering this unit s ventilation holes or operating it in an environment that may cause it to overheat e Avoid operating this unit in locations where sudden tem perature changes can cause condensation to form inside the unit e Do not use paint thinner or organic solvents to clean this unit Package Contents E Flex Network I O Unit 16 point Input Sink Source Type FN X16TS41 E Flex Network I O Unit 16 point Input Sink Source Type Installation Guide this guide You can download the Flex Network DIO Unit User Manual from Pro face s web s
8. space equipment medical life support equipment or transpor tation vehicles please contact your local Flex Network distributor A WARNINGS e Whenever installing dismantling wiring and conducting maintenance or in Spections be sure to disconnect power to this unit to prevent the possibility of electric shock or fire Do not disassemble or remodel this unit since it may lead to an electric shock or fire Do not use this unit in an environment that contains flammable gases since an explosion may occur Do not use this unit in an environment that is not specified in either the Installation Guide or User Manual Otherwise an electric shock fire mal function or other failure may occur Because of the possibility of an electric shock or malfunction do not touch any power terminals while the unit is operating Communication cables or I O signal lines must be wired separately from the main circuit high voltage large current line high frequency lines such as inverter lines and the power line Otherwise a malfunction may occur due to noise This unit must be properly installed according to directions in the installation guide and user s manual Improper installation may cause the unit to mal function or fail This unit must be properly wired according to directions in the Installation Guide and User Manual Improper wiring may cause a malfunction failure or electric shock Do not allow foreign substances including chip
9. tage Endurance AC1 500V 10mA minute between power Input and Output and FG terminals DC500V at 10MQ or higher between power Input and Output and FG terminals In rush Current 30A or less E Environmental Ambient Operating 0T to 55C Temperature Ambient Storage 25C to 70 C Temperature Ambient Humidity A E E A AAE wet bulb temperature less than 39 C Protection Rating IP20 Pollution Level Pollution Level 2 E Input Rated Input Voltage DC24V Max Input Voltage DC28 8V 16 available for both sink and source types Insulation Resistance No of Input Points Input ON Voltage DC15V or higher Input OFF Voltage DCS5V or less nul pede me LOFFON tamsos OO Input Delay Time C ono tamsos No of Exclusive Use Nodes A DANGERS e An emergency stop circuit and an interlock circuit should be constructed outside of this unit Constructing these circuits inside this unit may cause a runaway situation system failure or an accident due to unit failure Systems using this unit should be designed so that output signals which could cause a serious accident are monitored from outside the unit e This unitis designed to be a general purpose device for general industries and is neither designed nor produced to be used with equipment or systems in potentially life threatening conditions If you are considering using this unit for special uses including nuclear power control devices electric power devices aero
Download Pdf Manuals
Related Search
Related Contents
11病児保育室 Samsung SMART CAMERA DV300F Užívateľská príručka Quart de cercle - Deux portes Mikrokopter VSM User Guide Copyright © All rights reserved.
Failed to retrieve file