CB200 Fire Alarm User Manual

image

Contents

1. immediately Press SILENCE FAULT to silence the buzzer Circuit Isolation To isolate or de isolate a zone manual release or the actuator circuit press the ISOLATE button once The zone 1 fault LED will pulse rapidly every 2 seconds This is the flashing cursor Page 1 of 2 Doc CB200e User Guide Rev 0 Written By RP Checked By AJC Date 06 05 05 Press the ACCESS button to move the flashing cursor to the desired circuit fault LED Press the ISOLATE button to Isolate or De isolate the selected circuit The selected circuit fault LED will illuminate continuously to indicate that the circuit is isolated Press the RESET SYSTEM button to exit the Circuit Isolate mode The isolated circuits will remain isolated the fault Relay will be activated and the buzzer will sound intermittently The buzzer cannot be silenced Test Display The RESET SYSTEM button should be operated every week as part of the system test routine for checking correct operation of the panel buzzer and all LEDs Press and hold to test the LEDs Test Routine This should be carried out in accordance with BS5839 Part 1 Refer to Fire Alarm System Logbook User Controls and Indications Pulses when Manual Release is activated steady once alarms are silenced Pulses when Abort Input is activated Zone Fire LEDs flash paes aei when the zone is in fire Pulses for a fault on Zone Fault LEDs flash steady once alarms the Manual Release for zone fault or devi
2. Doc CB200e User Guide Rev 0 Written By RP Checked By AJC Approved By JBJ Date 06 05 05 CB200 Extinguishing Control Panel User Instructions WARNING This equipment contains hazardous voltages To avoid electric shock do not remove the cover This equipment contains no user serviceable parts For servicing contact suitably qualified personnel Fire General The RED zone fire LEDs will pulse the alarms will sound and the internal buzzer will operate Locate the source of the fire an LED will be visible on the detector which has been activated To silence the alarms press SILENCE ALARMS The alarms will silence and the red fire LEDs will change to a steady illumination When the fire has been extinguished press RESET SYSTEM Should the system have activated for no apparent reason please note which detector has been activated before pressing the RESET SYSTEM button and then contact your service engineer If necessary the alarms can be reactivated by pressing EVACUATE Fire Zones 1 or 2 Automatic Mode If a fire is detected on either zone 1 or zone 2 the relevant red zone fire LEDs will pulse and the 1 stage alarms will sound If a fire is detected on both zones 1 amp 2 both zone fire LEDs will pulse the 15 stage alarms will sound the 2 stage alarm will pulse and the TIMER ON LED will pulse to show that the Extinguishant Release Timer is running e When the Timer ends the TIMER ON LED will be extingu
3. ce have been silenced Abort Fault LED Input steady when removed steady for pulses for any fault isolated zone isolated on the Abort Input Flashes for a fault on any of the 3 alarm circuits Toggles the panel mode between Auto amp Manual Pulses when delay timer is Slide in insert for running zone location text Pulses for a fault on the Actuator Circuit Steady when isolated llluminates when Actuator circuit is Flashes when energised an Earth fault is detected Auto amp Manual LEDs illuminate to Flashes when show Auto mode activate activate Panel is in or Manual mode circuit isolate code entry PE t One man Test mode mode mode Press to Silence Press to Reset the Alarms the panel after during a fire a fire alarm condition Press to test Press to silence the LEDs in the buzzer quiescent activate alarm _lluminates when llluminates Flashes when a during a fault mode circuits 1 amp 2 both the Mains when controls processor fault condition supply and Battery are enabled occurs supply are present Press to Press to Flashes when Press to Page 2 of 2
4. ished the ACTUATOR OPERATED LED will illuminate the pulsing 2 stage alarm will change to continuous and the Extinguishant will be released e The Timer can be stopped amp the Extinguishant Release prevented by operating an Emergency Abort switch The Abort LED will pulse and the Abort condition will remain until the Abort switch and panel are reset Fire Zones 1 or 2 Manual Mode If a fire is detected on either zone 1 or zone 2 or on both zones the relevant red zone fire LEDs will pulse and the 1 stage alarms will sound The Extinguishant Release Timer will not start In this case the Extinguishant can only be released by operation of a Manual Release call point or switch Automatic or Manual Mode Manual Release If a Manual Release switch is operated the Manual Release LED will pulse the 2 stage alarms will pulse and the TIMER ON LED will pulse to show that the Extinguishant Release Timer is running e When the Timer ends the TIMER ON LED will be extinguished the ACTUATOR OPERATED LED will illuminate the pulsing 2 stage alarm will change to continuous and the Extinguishant will be released e The Timer can be stopped amp the Extinguishant Release prevented by operating an Emergency Abort switch The Abort LED will pulse and the Abort condition will remain until the Abort switch and panel are reset Fault Indication The internal buzzer will pulse and the appropriate fault LED will pulse Call your service engineer

Download Pdf Manuals

image

Related Search

Related Contents

Manuel d`utilisation  Encimera Step - KitchenAid® Chile  

Copyright © All rights reserved.
Failed to retrieve file