        Basic User Software Var. 1 - stand-alone systems (Manual)
         Contents
1.              cccccceeeeeeeeeee eeeeeeceeeeeeeeeeseseeeeeees 34  6 2 Pushbutton operation of the USerMenu                ccccceeeeeeeeee ceeeeeeeeeeeeeeeentaeeeees 35  6 3 Brightness   Contrast adjustment              cece ceeeeee eee eeeeee eeeeeeeeeeeeeeeeeeeeeteeeeeeeeeees 35    KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  3 of 64    cc  TROZ Echn itm    6 4  Lang  age Selection soisissa enini ee yenne a ianea i akanai 35  6 5 Main page for menu navigation             ceeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeteeeneeeeee renent 36  6 6 Locking   safety function iccrtccnsncteetceetecyilnias bit otcau teeta eiceteayahee indy Mniceulol eaves 38  6 7 Message DAG as ccneccosecseceevtsgnondepdeerdedcenstcesiseuselsapeanjapceentedsanotuentatens Eneee Ennet 39  6 8 Page for single control cca aceasta cette rrioanasg ep atmaanttatan eet a tmossaretecsemnertieds 41  6 9 Page for maintenance FUN             cccccceeesseeeeecee ceeeeeeeeeeeeeeaaeeeeeeeesseneeeeseeeeeeeeees 43  6 10 Page for SQUUNOS xis cict pe cosasanadnnnnecathadnentadxtrsnndestsenaduenoucneuacuenendeuanadanbdanatnes 45  6 11 Structure of the standard designations                ccccceeeeeeeeeeceeeeeeeeteeeeeeeeeeees 48  6 12 Adaptation of the designations               ccccceeeceeeeeeeeeeeeeeeeeeeeeeeeeeeeesseeeeeeeeeees 49  7 Operation and set up              osseneeeeeeeenneeeeerttrrtettnttttrterrtntntn nnn tnnnnnnnnennnn nennen 50  7 1 Cable and fuse protection for power supplies                ec eeeeee
2.     Exx AS iX    is displayed    7  If    ifm electronic  controllerE     standard page  page 0  or    Exx AS iX    is  displayed  press the    MENU    button  left button  of the AS i controllerE in  order to access the internal menu    8  Select the menu point Slave lists using the    T  and    J    buttons of the AS i  controllerE and acknowledge with    OK     left button     9  Select the requested AS i master using the    T    and    J    buttons of the AS i  controllerE and acknowledge with    OK     left button     10 Select the menu point    LDS Master x    using the    T    and    4    buttons of the AS i  controllerE and acknowledge with    OK     left button     11 Existing slaves are indicated by a dot   S stands for single slaves which  occupy a whole address  A B stands for slaves with A B capability which share  an address   Further slaves of this AS i master can be displayed using the    T     and    J buttons    12  Using the    ESC    button  right button  you can return to the main menu    13  If no button is pressed and the program is active in the AS i controllerE  yellow  LED PLC RUN lights   the display automatically returns to the fire damper    visualisation after a predefined time     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  59 of 64    cc  TROZ Echn itm    7 7 Projection adaptation    The projection of the PLC configuration  activated AS i slaves  must be adapted so  that the AS i master s  of the AS i controllerE detect s  the sla
3.    KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  63 of 64    cc  TROZ Echn itm    Important note  The software purchased with this system may only be used in combination with the  TroxNetCom system     Any other use  especially in combination with products of other manufacturers is not    allowed and results in a loss of all warranty claims     Every user has to ensure by qualified personnel that the required safe functionality of    the system according to the operating instructions is guaranteed     Only qualified companies expressly authorised by TROX GmbH are allowed to make  the required software adaptation     Reproduction with and without changes of the program as well as the documentation  is not allowed and will be prosecuted     May 2006  TROX GmbH     amp     ifm electronic gmbh    KIE me Manual_TNCBUS _V1_44 e Last updated  04 09 06 page  64 of 64    
4.    Ot   CS S ifin    oc    1 6 2 Commands and messages for groups    With the slave addresses 1   30 group error messages of the system are given via    potential free contacts     O1   O2   O3   O4     group OK  no fire damper in the group CLOSED  no smoke in the group    maintenance run of the group not active    With the slave addresses 1   30 the following group control signals can be    transmitted to the module via potential free contacts        acknowledgement  reset of stored errors   opening of all fire dampers of the group   pulse to reset all smoke detectors of the group  free  not used     Figure 1 6 1  Input output module with relay contacts    KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  12 of 64    dg    TROZ  tcnn o itm    1 7 Illuminated pushbutton module    TNC A2018 connection  Via light indicators centralised error messages of the system are indicated and the  system can be operated via pushbuttons  e g  acknowledgement      Light indicators     Light indicator green  system OK  no error  Light indicator red  flashing   system error  not acknowledged   Light indicator red  continuously on   system error  present and  acknowledged   Pushbutton   Pushbutton red  pressed  gt  200 ms   acknowledgement     reset of stored errors   Pushbutton green  pressed  gt  200 ms   open all fire dampers  Pushbutton red  pressed  gt  5s   close all fire dampers  priority   Pushbuttons red and green  pressed  gt  3s  test reset of the RM O VS  smoke detector    
5.    TECHNIK itn    1 Module types    In fire damper systems the following connections are possible     1 1 Fire damper with one mechanical limit switch    AS EP4 connection   The operating mode for detecting four dampers with only one end position is called  AS EP4  This operating mode is the default setting  It is possible to use an NC or NO  contact per damper  This is set via the operating and display panel of the AS i    controllerE           The setting is the same for all AS EP4 modules connected to this AS i controllerE   It is not possible to combine AS EP and AS EP4           A combined use with all other modules described in this manual on an AS i  controllerE is possible     The AS EP4 module is one of the possible 31 or 62 bus participants of the system   So 31x4 124  for TNC A1303  1 AS i master with 31 slaves  or 2x31x4 248  TNC   A1304  2 AS i masters with 31 slaves each   fire dampers can be connected to an  AS i controllerE using AS EP4        Figure 1 1 1  AS EP and AS EP4 connection    KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  6 of 64         TROZ Tecan itm    DY    1 2 Fire damper with two mechanical limit switches    AS EP connection   Here the same connection as described above is used  However  two fire dampers  with two limit switches each are connected to the module  An intermediate position of  the damper  timeout error due to missing end position  or an error by actuating both  limit switches  manipulation  is detected and evaluated  
6.   The operating mode is called AS EP and is set via the operating and display panel of  the AS i controllerE           The setting is the same for all AS EP modules connected to this AS i controllerE   It is not possible to combine AS EP and AS EP4           A combined use with all other modules described in this manual on an AS i    controllerE is possible     The AS EP module with the two fire dampers is one of the possible 31 or 62 bus    participants of the system     So 31x2 62  for TNC A1303  1 AS i master with 31 slaves  or 2x31x2 124  TNC   A1304  2 AS i masters with 31 slaves each  fire dampers can be connected to an  AS i controllerE using AS EP     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  7 of 64    dg    TROZ  tcm o itm    1 3 Fire dampers with inductive dual sensor to detect both end positions    AS E connection   Using the inductive dual sensor both end positions are detected without wear    The AS E module is one of the possible 31 or 62 bus participants of the system    The AS E module is directly connected to the  yellow  bus cable    An intermediate position of the damper  timeout error due to missing end position  or  an error by actuating both limit switches  manipulation  or maladjustment is detected  and evaluated    The AS E module is a bus participant per damper    A combined use with all modules described in this manual on an AS i controllerE is    possible        Figure 1 3 1  AS E connection    KIE me Manual_TNCBUS_V1_44 e Last upda
7.  04 09 06 page  25 of 64         TROZ  Tecan itm    DY    4 6 Diagnosis    The connections AS EP  2 fire dampers with 2 end positions each   AS E  AS EM B  provide the option for an enhanced diagnosis due to their 2 end positions  The    diagnostic options are as follows     4 6 1 Manipulation    Manipulation or switch error means that both limit switches  AS EP  AS EM B  are  actuated or both end positions of the inductive sensor  AS E  are damped  Normally  only one end position is allowed to be signalled  The manipulation can be monitored  via the program and transmitted as an error message  centralised error message    The operating and display panel of the AS i controllerE indicates a detailed text    message for the manipulation     4 6 2 Exceeded timeout    It is possible that the timeout of the fire damper is too long  e g  due to mechanical  wear of a fire damper or voltage drops on the cables  This can be monitored via the  program and transmitted as an error message  centralised error message   For  motor driven fire dampers the timeout for opening and closing the fire dampers is  different  opening  180 s  closing  25 s   The operating and display panel of the AS i  controllerE indicates a detailed text message for the exceeded timeout     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  26 of 64    cc  TROZ  Techn itm    4 7 Deactivation   Ignoring of smoke signals    To set up and clean fire damper systems it is usual to remove the sensing heads of  the
8.  5  setting options  must  always be activated    e There must be commands for opening  or NOT closing  of the motor driven fire  dampers at the inputs of the input output modules  Without external commands   the motor driven fire dampers can NOT be opened  If it is not possible to generate  commands from external systems during the first set up  they can be simulated by    means of jumpers     The assignment of the commands or jumpers for opening the motor driven fire    dampers is described below     When the slave address 31  centralised messages and commands  is used   e Contact I  to 12    e Contact I  to I3    When the slave addresses 1   30  commands and messages for groups  are used     e Contact I  to 12    KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  55 of 64    cc  TROZ tecunik itm    7 3 Addressing of the AS i slaves   modules   The AS i slaves can be addressed via the standard menu of the operating and  display panel of the AS i controllerE or via a handheld addressing unit  For reasons  of flexibility we recommend a handheld addressing unit  The handheld addressing  unit can be connected to the AS i slaves by means of an addressing plug  It is also  possible to directly connect the AS i slaves  e g  AS E or module upper part of the    AS EP  to the addressing unit by insertion  The addressing procedure using the    handheld addressing unit is as follows   1  Read the address  when delivered the address is 0      Set the address to the requested addr
9.  Last updated  04 09 06 page  15 of 64    cc  TROZ recunik ifin    2 3 Cable length  signal amplification    If the cable length of 100 m  total length including all branches of the tree structure  is  not sufficient  it can be extended via a signal amplifier  This signal amplifier is called  AS i repeater  The AS i line from the AS i master is connected to the input  line 1  of  the AS i repeater  The output of the AS i repeater  line 2  must be supplied with AS i  voltage via another AS i power supply  Another AS i line of 100 m can now be  connected to this repeater line  If this length is not sufficient either  the first AS i  repeater can be followed by another repeater  Another length of 100 m is then  available  It is NEVER allowed to use more than 2 AS i repeaters connected in  series  Further repeaters must be connected again to the master line     Master and repeater lines must be electrically separated      i  1     i  1  i   i  i   i  i   i  i   i  i   i  i  1  i  1  i        gt  100 m for complete system    Maximum of 300 m i power supply      per AS i master   7100m   100m               _   _   er ee    __ a    number of Slaves 1  31      max  2 rep eater in a line    Figure 2 3 1  Structure of an AS i system with AS i repeaters    KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  16 of 64    cc  TROZ Echn itm    2 4 Further information about the system    More details such as technical data of the components and graphic representations  concerning the d
10.  RM O VS D smoke detectors  As a result of this  the smoke detectors indicate  smoke and so the assigned motor driven fire dampers close or cannot open  For set   up and cleaning a forced opening  emergency operation  is required to continue the  operation of the ventilation system during this process  This means that in case of a  forced opening the fire dampers are open or in the process of opening and the  signals of the smoke detectors are ignored  As this state does not correspond to the  normal state the centralised error message is given in case of a forced opening  A  forced opening of the fire damper system can be released via a command  relay  contact     Due to safety regulations forced opening  ignoring of smoke detector signals   must be set up by a qualified company    With the forced opening being active the installation has NO APPROVAL     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  27 of 64    cc  TROZ  Techn ifin    5 Setting options   The AS i controllerE can be set for the different applications using the TroxNetCom   Basic User Software for fire damper systems  For AS i controllerE the settings are  made via the integrated operating and display panel     The following settings can be made     5 1 AS EP or AS EP4    With this setting the type AS EP  2 fire dampers with 2 mechanical limit switches  each  or the type AS EP4  4 fire dampers with 1 mechanical limit switch each  can be  selected for the complete AS i controllerE  It is NOT possibl
11.  button  you can return to the main menu    12  If no button is pressed and if the program is running in the AS i controllerE   yellow LED PLC RUN flashes  you automatically return to the fire damper  visualisation after a certain predefined time    After successful projection adaptation via quick setup  no red LED for CONF   PF and  no yellow LED for PROJ must light     KIE me Manual_TNCBUS _V1_44 e Last updated  04 09 06 page  60 of 64    TROA tecHnkK itm    oc    7 8 Start Stop of the AS i controllerE program    To activate or deactivate the program described above the following steps must be    taken   1   2   3     10   11     Power on the AS i controllerE    Wait until the AS i controllerE has completely started up    Is the standard page shown on the display of the AS i controllerE   ifm  electronic  AS i controllerE     standard page  no  0  or  Exx AS iX    displayed    If    no    go to point 4  if    yes    go to point 7        Is the    ESC    field displayed     If    no    go to point 5  if    yes    go to point 6         Press the left button and the    4    button simultaneously for 3 seconds until the       ESC    field is displayed   unlocking of the program lock       Press the    ESC    button  right button  of the AS i controllerE until    ifm    electronic  AS i controllerE     standard page  no  0  or    Exx AS iX    is displayed       If    ifm electronic  controllerE     standard page  page 0  or    Exx AS iX    is    displayed  press the    MENU    b
12.  type AS EM B for    mounting on Trox fire dampers can be obtained from TROX GmbH     7 2 1 AS i flat cable insulation displacement connectors    Important mounting note  When connecting the AS i modules  e g  module types  AS E  AS EM B  AS RM BD  to the AS i flat cable using the flat cable insulation  displacement connector note that upper and lower parts must be separated before  mounting  The orange lower part of the flat cable insulation displacement connector  is only snapped onto the AS i flat cable after separation from the upper part  Only  after snap on the upper part is screwed into the orange lower part  If the flat cable  insulation displacement connector is erroneously attached unseparated  e g  using  pliers  contacting is NOT possible  This would also bend the contact pins  The flat  cable insulation displacement connector must not be used as a connection element  for two cable ends  The flat cable insulation displacement connector is to be solely    used for connection to the AS i module     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  51 of 64    cc  TROZ tecunik itm     gt          upp er part    Figure 7 2 2 1  AS i flat cable insulation displacement connector with separated components    7 2 2 Cable branching    As junction box for branching cables a standardised AS i module lower part with  cover  TNC A5000   TNC A3000   a special AS i splitter  TNC 70200 when motor     driven fire dampers are used  or a common splitter can be used        Fi
13.  voltage supply for the power supplies in the AS i  control boxes    e Power on the AS i control boxes    e Lay the profiled AS i cable  AS i flat cable     e Connect the AS i modules to the AS i cable  first separate the FC insulation  displacement connectors     e Address the AS i modules  AS i slaves  with the addresses 1 to 31    e Document the AS i addresses and the inputs channels of input modules  for AS   EP and AS EP4  in a list in combination with the ventilation related designation of  a damper or a smoke detector    e Carry out the projection adaptation of the AS i PLC configuration    e Start the software    e Carry out settings  e g  sequential interlocking  via the integrated operating and  display panel of the AS i controllerE    e Test the functions of the system specified by the engineering consultants or    customer     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  50 of 64         TROZ Tecan ilim     ER    7 1 Cable and fuse protection for power supplies   Due to the system the power supplies required for an AS i controllerE  AS i power  supplies and 24 V DC power supply  must be supplied with 230 V AC via one cable   e g  NYM J 3x1 5 mm   and protected by a fuse     7 2 Installation and connection of the AS i slaves    To minimise installation work for AS i modules it is useful to order them premounted  at the fire dampers in the factory  module types AS E  AS EM B  from TROX GmbH   If they are not premounted  a mounting bracket for the module
14. Figure 6 10 2  Menu navigation     middle of the list       Maintenance run 2  Manual operation    Smoke detectors    OK j ESC             Figure 6 10 3  Menu navigation     end of the list    By pressing the    ESC    button you can return to the main page of the UserMenu     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  45 of 64    cc  TROZ  Techn itm    The following settings can be made   e Module type AS EP or AS EP4  1 or 2 limit switches per fire damper   e Contact assignment of AS EP AS EP4 as NC or NO contacts  e Text selection for AS EP4  CLOSED  NOT CLOSED or NOT OPEN  OPEN  e Sequential interlocking ON OFF  e Control via a relay contact ON OFF  e Maintenance run 1  close or open again the fire damper in case of an error  e Maintenance run 2  maintain all dampers successively or at the same time  e Manual operation ON OFF    e Activate deactivate smoke detector    If a setting is selected using the    OK    button  the current status of the setting is  indicated by means of dark highlighted text  Another setting can be selected using  the    T    or    L    button  This selection must be acknowledged using the    OK    button   Exceptions are manual operation and the deactivation of the smoke detectors   forced opening  ignoring of smoke signals   These can only be activated by  simultaneously pressing the    OK    button and the    7 button  The settings can  be deactivated just like all other settings  They can be verified by returning to the  menu pa
15. T required  The max  cable length including all branches is 100 m  To save cable  length the AS i master controlling the communication with the AS i slaves should be  installed in direct vicinity of the AS i slaves in small control cabinets or control boxes   The so called AS i master can be a module plug in card of a PLC  To reduce cost the  AS i master from ifm electronic gmbh is integrated in the AS i controllerE     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  14 of 64    cc  TROZ recunik itm    The AS i controllerE has three tasks or functions     1  Control of the communication with the AS i slaves in the field  e g  AS EM B    2  Interface for coupling with other systems via networks  e g  operating and  control panel  BSA  DDC  PLC     3  Integrated programmable PLC functionality    2 2 System supply    To ensure the communication of the AS i slaves with the AS i master as well as the  voltage supply of the AS i slaves via the AS i flat cable or other cable types one AS i  power supply per AS i master must be installed  The AS i power supply provides the  AS i voltage  29 5   31 6 V DC  and includes the required data decoupling for  communication  The AS i power supplies are rated depending on the requirements   The AS i controllerE must be supplied with operating voltage via a 24 V DC power    supply        Figure 2 2 1  Wiring example of an AS i controllerE with 1 AS i master     AS i power supply and 24 V DC power supply    KIE me Manual_TNCBUS_V1_44 e
16. TROZ  techn See o    Manual  on the    TroxNetCom Basic User Software  for fire dampers and smoke detectors    Variant 1  stand alone     TroxNetCom   AS interface system  for AS i controllerE  TNC A1303 04    written by   Martin Kluge    KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  1 of 64         TROZ  Tecan ilim     ER    DEMETRI GOIN DOAA 5  1 Mod  le typ  S mirnesa aa eee A ee eee 6  1 1 Fire damper with one mechanical limit switch               ccceeceeeeeeeeeeeceeeeeeeeeeeteees 6  1 2 Fire damper with two mechanical limit switches                cccceeeeeeeeeeeeeeeeeeeeeeenees 7  1 3 Fire dampers with inductive dual sensor to detect both end positions               8  1 4 Fire damper with spring return actuator            c eee eeeeeeee eee eeeeee eeeeeeeeeeaeeeeeeeeeeenaees 9  1 5 RM O VS D smoke detector              cccccccceeeeeeeeeee ceeeeeeeeeeeeeeseeenaeeeeeeeeeee menneen ne 10  1 6 Signal contacts and control signals             cccccececeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeseeseeeeees 11  1 6 1 Centralised messages and COMMANAS             cccccccccecceeeeeeeesesssntttnaeeeeeees 11  1 6 2 Commands and messages fOr groups           ccceceeeeeeeeeeeeeeeeeceeeeeeeeenneeeeeees 12   1 7 Illuminated pushbutton module sisi cies cececetiesiocznadseeaccicusdeniiavelaeeldianialiaeaanee 13   2 General system StruCtUre                  cccccccceeee cece eee eeeeeeeeeeeeeeeeeeeaaeeee seaneeeeeeeeeee 14  2 1 System principle cies cenestricaecacclcaaroctidentadnb a oce
17. The module is a participant of the bus system        Figure 1 7 1  Illuminated pushbutton module    KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  13 of 64         TROZ Tecan ilim     ER    2 General system structure   Short description AS interface   The structure of fire damper systems under the name  TroxNetCom AS i  is based on  the actuator sensor interface  AS interface or AS i     AS interface is a manufacturer independent standard for industry offered by the  companies TROX GmbH and ifm electronic gmbh as wiring and field bus system for  fire damper systems in building system automation    To reduce installation and set up cost the ventilation and fire damper components of  TROX GmbH are fitted in the factory with the AS interface system components from  ifm electronic gmbh     2 1 System principle    The system is based on the master slave principle  The modules indicated above   AS EP  AS E  AS EM B  AS RM BD  etc   which are premounted on the fire  dampers and smoke detectors are distributed in the system  These are the so called  AS i slaves  They are connected via a 2 wire profiled yellow cable  AS i flat cable   with a wire cross section of 2 x 1 5 mm  in an open tree structure  An easy and quick  insulation displacement technology     similar to that used in lighting     is applied   Other cable types  e g  NYM J 3x1 5 mm  can also be used but this eliminates the  advantage of the easy insulation displacement technology  Terminating resistors are  NO
18. There it is then indicated  whether a maintenance run has been finished with or without error  This message    can be cancelled by pressing the    ESC    button        Maintenance run  Choice of group  All groups    Start     ESC             Figure 6 9 1  Maintenance run can be selected for all groups       Maintenance run  Choice of group  Group  2    Start     ESC             Figure 6 9 2  Maintenance run can be selected for one group    KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  43 of 64    gg  TROZ  Techn ilim       Maintenance run  Choice of group  All groups    r g ESC             Figure 6 9 3  Maintenance run cannot be activated because fire damper is closed       Maintenance run  Maintenance act   All groups    STOP             Figure 6 9 4  Maintenance run for all groups active    By pressing the    ESC    button on the maintenance run page you can return to the  main page of the UserMenu     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  44 of 64    gg  TROZ  Techn itm    6 10 Page for settings  There is a menu navigation on this page to perform settings  You can scroll through  the settings menu by pressing the buttons    T    and    J     A setting with dark highlighted    text can be selected by pressing the    OK    button        AS EP   AS EP4  Contact type EP  Texts AS EP4    OK i  ESC             Figure 6 10 1  Menu navigation     top of the list       Seq  interlocking  Control via relay  Maintenance run 1    OK A i ESC             
19. a fusible  link release  fire   the mechanical limit switch mounted at the damper signals the  state of the damper to the AS i controllerE via the AS EP module  The centralised  error message  e g  relay contact or red light indicator  is switched via the program  and the signal  damper closed  is given  e g  via a relay contact   The operating and  display panel of the AS i controllerE indicates a detailed text message for the closed  damper     4 1 2 AS E connection    If a fire damper is closed by manual actuation  e g  for maintenance  or by a fusible  link release  fire   the AS E module mounted at the damper signals the state of the  damper to the AS i controllerE  The centralised error message  e g  relay contact or  red light indicator  is switched via the program and the signal  damper closed  is  given  e g  via a relay contact   The operating and display panel of the AS i  controllerE indicates a detailed text message for the closed damper     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  20 of 64    cc  TROZ Echn ifin    4 1 3 AS EM B connection    If a fire damper is closed by manual actuation  e g  for maintenance  or by releasing  the thermo electric release mechanism  fire   the AS EM B module mounted at the  damper signals the state of the damper to the AS i controllerE  The centralised error  message  e g  relay contact or red light indicator  is switched via the program and the  signal  damper closed  is given  e g  via a relay contact   The ope
20. acknowledged in order to be able to open  the motor driven fire dampers again     Messages that can be displayed for fire dampers are     OPEN  CLOSED  NOT CLOSED  or OPEN  NOT OPEN   Timeout error   Manipulation   Switch error    Messages that can be displayed for duct smoke detectors are   Smoke detected  Airflow OK  Pollution  System error RM O VS D    KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  41 of 64    gg  TROZ  Techn ilim       Designation  Damper open  AS EM B ON    CTRL      ESC             Figure 6 8 1  Single control of a triggered fire damper       Designation  Damper closed  AS EM B OFF    CTRL   l ESC             Figure 6 8 2  Single control of an untriggered fire damper    By pressing the    ESC    button you can return to the main page of the UserMenu     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  42 of 64    gg  TROZ  Techn ilim    6 9 Page for maintenance run    Via this page  a group of fire dampers to be maintained or all groups simultaneously  can be selected by means of the         and         buttons  Using the    START    button a  maintenance run can be started  A maintenance run can only be started if all fire  dampers connected to the AS i controllerE are open  This is indicated by the visible  or non visible    START    button  Using the    STOP    button a maintenance run can be  stopped  If the maintenance run is finished without manual intervention  the display  changes to the message page after a predefined time  
21. amper in case of an error  e Maintenance run 2  maintain all dampers successively or at the same time   e Manual operation ON OFF    e Activate deactivate smoke detector    For further general details concerning the functionalities assigned to the settings see  chapter 5 of this manual   For further details concerning settings via the UserMenu  operating and display panel    of the AS i controllerE  please refer to chapter 6 10 of this manual     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  62 of 64    cc  TROZ Echn itm    8 Functional test  Once all of the steps described above have been completed it is necessary for the    user commissioning engineer to perform a functional test of the system     The user commissioning engineer is personally responsible for the safe and reliable  functioning of the whole system     Please ensure you have read and observe the important note given at the end of this    manual     General notes   The TroxNetCom Basic User Software user manuals are detailed training manuals  and may be used as operating instructions    Technical support and instruction by telephone for the TroxNetCom Basic User     Software is therefore not provided free of charge    We reserve the right to make technical alterations without prior notice    No manual can be entirely free of errors    Some mistakes may have been overlooked despite repeated proof reading  We    therefore welcome your comments concerning any errors you may notice in these    manuals  
22. an AS i controllerE are then CLOSED and OPENED in parallel  If  special types of motor driven dampers are connected to the system  they can NOT    be tested by carrying out a simultaneous maintenance run     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  24 of 64    cc  TROZ  Techn itm    4 5 4 Maintenance run in general    If during opening or closing of the tested fire dampers a timeout error occurs  this can  be evaluated as an indication of a mechanical failure of the fire dampers by the  operating and display panel of the AS i controllerE  A manipulation or switch error   both end positions are switched  can also be evaluated as an error during the  maintenance run  The errors can be acknowledged only after the maintenance run  has been finished  The maintenance run can be interrupted by a further input pulse  on the input output module  slave address 31  or by a pulse from the operating and  display panel of the AS i controllerE    An operating signal of the active maintenance run is transmitted via the NC contact of  the input output module  slave address 31     With the default setting a failure of a fire damper during the maintenance run  leads to an automatic closing of the fire damper  Checking the faulty fire  damper on site is thus absolutely necessary    This default setting of the maintenance run can also be deactivated  The settings are    made via the operating and display panel of the AS i controllerE     KIE me Manual_TNCBUS_V1_44 e Last updated 
23. can ilim     ER    5 9 Deactivation   Ignoring of smoke signals   This function enables a forced opening  emergency operation  of motor driven fire  dampers to set up or clean ventilation systems  With the setting being activated the  smoke signals of smoke detectors are ignored so that the motor driven fire dampers  can be opened  The sensing heads of the RM O VS D smoke detectors can thus be  removed for cleaning the ventilation system and the motor driven fire dampers can  be opened    With the forced opening being active the installation has NO APPROVAL    For legal reasons  setting of this function via the operating and display panel of the  AS i controllerE is secured by an additional locking  This setting can only be made by   simultaneously    pressing the buttons  T    and  OK        The factory default setting is  OFF    5 10 Group A for ventilation systems  group B for smoke detector groups   This setting can only be used in combination with manual adaptations in the  TroxNetCom Basic User Software  With this setting fire dampers or smoke detectors  can be assigned to a ventilation system via a group A and smoke detectors can be  assigned to motor driven fire dampers via group B    The factory default setting is  OFF    5 11 Activate group B  2nd group assignment    This setting can only be used in combination with manual adatations to the  TroxNetCom Basic User Software  Via this setting a motor driven fire damper or a  smoke detector can be assigned a second grou
24. cechcdpsnssecdiccca pies usadebedaaenebcdiesviectoccateeccedeicbuens 63  Important Note eeose uate cactus eae aE weneuedelmenmneuboadced EAE SA Ha aE 64    KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  4 of 64    cc  TROZ Echn itm    Introduction    The TroxNetCom Basic User Software for fire dampers and smoke detectors is used  to cover the most important basic functions in fire damper and ventilation systems   Variant 1 provides the option to set up easy stand alone systems without adapting  the software     Applications for the TroxNetCom Basic User Software  variant 1 are as follows     1  1 AS i controllerE with 1 or 2 AS i masters and up to 31 or 62 participants  each  depending on the version up to 248 fire dampers       2  Grouping  see 3 1  by taking RM O VS D smoke detectors and input output  modules with relay contacts into account   3  Transmission of centralised error messages and group error messages via  relay contacts   4  Visualisation and operation of the system via integrated display of the AS i  controllerE    The functionality of this system can cover approx  90  of the fire damper systems   Special functions can be implemented on the basis of standardised program blocks     The scope and use of the functions of the TroxNetCom Basic User Software are  described in the following text        1 The different types of participants are described in the following text   KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  5 of 64    oc    TROZ 
25. ctivation   Ignoring of smoke Signals                 cccccceeeeeeeeceteeeeeeeeeeseeneeeeees 27  5 Setting Cpt ea cect spear du ctl det We aisla pet icleaiedeweeaele Nadieedsaee 28  5 1 elec  aati gee ee en ee eee ee nee eee 28  5 2 AS EP with inverted contacts iscezscctertae zareteete ce eieenteeesneleeet stata eieaiece eceestecaiiey 28  5 3 Text selection for AS EP4          ee cc cceeeceeesesececcee ceeeeeeeeeeeesaaeeeeeeeeeesenaeeeesseneeeaeees 29  5 4 Sequential interlocking scree evsvsscetceeaslevestdeevsventuanteseembutderneantdeeeee extent eenouees 29  5 5 Control via a relay COMMA safes docs ca wentiewed ideclereicesiesteniatanbonsntedenmenvademendedesaniatesls 29  5 6 Close faulty damper during the maintenance rUN                   eeeeeeeseeeeeeeeeeeeeeees 30  5 7 Maintenance run one after the other or simultaneously                eeeeeeeeeeeees 30  5 8 Manual operation sasdhsccccpcatacansostimccceuamceteedennecaucientniesthatengpaseteeoatnaraudiecdunetnas 30  5 9 Deactivation   Ignoring of smoke Signals                 cccccceeeeeeeeeceeeeeeeeeeeeeeteeeeees 31  5 10 Group A for ventilation systems  group B for smoke detector groups          31  5 11 Activate group B  2nd group aSSiQNMenh              cceeeeeeeeeeeeeeeeeeeeeeeeneeeeeeees 31  5 12 Change standard type of motor driven damper                      seeseeeeeeeeeeeeeeees 32  6 Operating and display panel of the AS i controllerE  UserMenu                  33  6 1 Standard page of the AS i controllerE    
26. e to combine AS EP and  AS EP4 modules within an AS i controllerE    The factory default setting is  AS EP4     5 2 AS EP with inverted contacts    This setting distinguishes between type AS EP and type AS EP4  If type AS EP  2  fire dampers with 2 mechanical limit switches each  is used  NC contacts can be  used instead of NO contacts with the setting being active  inverted contacts ON   If  type AS EP4  4 fire dampers with 1 mechanical limit switch each  is used  NO  contacts can be used instead of NC contacts with the setting being active  inverted  contacts ON   It is NOT possible to combine NO and NC contacts within an  installation     The factory default setting is  OFF    KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  28 of 64    cc  TROZ  Techn itm    5 3 Text selection for AS EP4    If this setting is activated  the messages    NOT CLOSED    when the fire damper is not  closed and    CLOSED    when the fire damper is closed are indicated on the integrated  display of the AS i controllerE  This setting can be used when the CLOSED position  is monitored by means of an NC contact  If the OPEN position is monitored by means  of an NO contact  this setting can be deactivated  If this setting is deactivated  the  messages    OPEN    when the fire damper is open and    NOT OPEN    when the fire  damper is not open are indicated on the integrated operating and display panel of the  AS i controllerE    The factory default setting is  ON    5 4 Sequential interlock
27. eeeeeeeeee eeeeeeeeeaeeeees 51  7 2 Installation and connection of the AS i slaves               ccceeeeeeeeeeeeeee eeeeeeeeneeeeees 51  7 2 1 AS i flat cable insulation displacement connectors          ssssssssseeeessesereeee 51  7 2 2 Cable branching          eeeseeseeeseeeseeeeesenrrrreserrrnrrrneerrrnnnrneerrenrnseerrtnnneeerreenn 52  7 2 3 AS i module lower parts                  ccceeeeeesseeee eeeseeeeeeeeeeeeeeeaeeeeeeseeeae eeeeenenes 52  7 2 4 Connection of input output modules  e g  TNC A2258              eeee 54  7 2 5 Opening of motor driven fire dampers by assigning commands  jumpers   to the input output MOGUIES           eect e cess cece eee eeeaeeeeeeeeeeeeaaaaeeeecaaeeeeeeeeenees 55  7 3 Addressing of the AS i slaves   MOGUIES                 cccceeesecceeeeceeeeeeeeeeeeeeeeeeees 56  7 4 Documentation of the SYStOM             cccccceeseeceeeeeeeceeeeeeeeeeeaaeeeeeeeeeeseeaeeeceeaaees 57  7 5 Linking unused inputs for AS EP and AS EP4           cece cc cceeeeeeeeeeeeee eeeeeeenneeeees 58  7 6 Checking of connected SIAVES            cccceeessccceeeeeeeceeeeeeeeeaaeeeeeeseeteeseaeeeeaaaaaees 58  7 7 Projection adaptation gaa ctircasiitendecedotvaterdactne teunttcapesiala eam wmctadectnecnacsnanandtens 60  7 8 Start Stop of the AS i controllerE Program             ccccceccceseeeeeeeeceeeeeeeeseesteeeeees 61  TD  SNS i A estes te tnd exc A EEE pre eo tem tei des ce xe eevee 62  8 Functional teSt  easnnornene a e 63  General notes isis ces dectene se asec de edes
28. enezeuased cancel seta sau dastoancenerarcuenmmenes 14  2 2 System SU DY salt theeearctetelg de esos cata eel daloatdld Se adetgd a eleaainecodaeedaate 15  2 3 Cable length  signal amplification               ceccceeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeseeeeeeeeeees 16  2 4 Further information about the SyStemm                 cccceeeeeeeeee eeeeeeeeeeeeeeeeeeeneeeeeeees 17   3 Design of a fire damper System                   cccceeeeeeeee ce eeeeeeeeeeeeeeeeeneeeeeeeeeteeeeees 18  SDM  GrOUPIN G rss aene aE tees eaten EENE E S TEE aenGeenee 18  3 2 Sequence of the module types          ee eeeecccceeeeeeeeceeeeeeeeeaaeeeeeeeeeseeaaaeeeeeaaeaees 19  3 3 Documentation by Excel list                cc ceeesseccceceeeceeeeeeeeeeeaaeeeeeeeeesseeeaeee ceneeaeeees 19   4 Basic function of the system       0      cece cece cece ee eeeeeeeeeeeeeseaaaeeeeeeeeaeeeeeeees 20  4 1 Functionality in case of thermal release                 cccceeeeeeeeee ceeeeeeeeeeeeeeeeneeeees 20  4 1 1 AS EP and AS EP4 connection              cccccceeseeecceee ceceeeeeetesteseeeeeeteeeneees 20  4 1 2 AS E connection sis ccinssesnucwnncestvnsdeded ante saad eteecbewinancbcksedesedeciussvedetacebewnransune 20  4 1 3 AS EM B Connect esis spoe nE aAA 21   4 2 Functionality in case of smoke detection              ccccccccceeeeeeeeceneeeeeeeeeeeeeeneeeees 21  4 2 1 Global release of all smoke detectors                cccceeeeeeeeeeeee eeeeeeeeeeeeeeeeeeees 21  4 2 2 Individual release of smoke detectors  manual operat
29. esign of fire damper systems with AS interface are provided in the  system manual  TroxNetCom   It can be obtained on a data carrier from TROX    GmbH or downloaded at www trox de     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  17 of 64    cc  TROZ  Techn itm    3 Design of a fire damper system  The electric design of a fire damper system is detailed in the system manual   TroxNetCom   As the functions of the TroxNetCom Basic User Software are defined    by assigning the AS i slave addresses  the following definitions apply     3 1 Grouping    Fire dampers which are used together in a plant or plant section are considered to be  a group if they are assigned to and triggered by one or several smoke detectors or  input output modules  slave address 1   30     If no smoke detectors or input output modules  slave addresses 1   30  are used in  the plant  all fire dampers integrated in the system form one group    1 to 31 or 62 motor driven fire dampers or     when AS EP modules are used for end  position detection     up to 124 or 248 fire dampers can be combined in a group   Grouping is made by assigning the AS i slave addresses  Every group begins with  one or several smoke detectors or input output modules which have the lowest  addresses in the group  A new group can also be formed by one or several  input output modules  also in combination with smoke detectors  at the lowest slave  addresses within this group  AS EM B  AS E and AS EP or AS EP4 then follow in  
30. ess with the     buttons of the unit     2  3  Write the address   4      Read the address again to check it        Figure 7 3 1  Addressing of an AS i module via the addressing plug    KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  56 of 64    TROA tecunkK   O    CS itm    cc       Figure 7 3 2  Addressing of an AS i module upper part by direct insertion    7 4 Documentation of the system    Every module which is addressed must be documented in a list with the assigned    AS i address and the ventilation related designation of the damper or smoke detector    connected to the AS i module  Furthermore the assignment of the inputs with regard    to the ventilation related designation must be documented when using AS EP  2 fire    dampers with 2 mechanical limit switches each  or AS EP4  4 fire dampers with 1    mechanical limit switch each   An example of such a list is given below and can also  be obtained from TROX GmbH     The following points must be documented     Ventilation related designation of fire dampers or smoke detectors  AS i controllerE no    AS i master no    AS i slave address  AS i module no     AS i line   Type of the AS i slave  AS i module    Ventilation system   Mounting location    Note on mounting    KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  57 of 64    cc  TROZ  Techn itm    7 5 Linking unused inputs for AS EP and AS EP4    If for AS EP modules only one instead of two fire dampers with two end positions is  connected  a jumpe
31. ge for settings by means of the    ESC    button and reloading the previously  selected menu item  Only some of the possible settings are presented in the  following  The functions which lie behind these settings are described in detail in    chapter 5     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  46 of 64    DY       TROA tecHnkK   Ot    CS i       AS EP4  4FD 1 Limit S   2FD 2 Limit S     OK    ESC             Figure 6 10 4  Selection of the module type AS EP4 or AS EP       AS EP4  NO contacts    NC contacts    OK i ESC             Figure 6 10 5  Setting of NO or NC contacts       Seq  interlocking  active   ON  not active   OFF    OK i ESC             Figure 6 10 6  Setting of sequential interlocking    By pressing the    ESC    button you can return to the menu page for settings     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  47 of 64    cc  TROZ Echn itm    6 11 Structure of the standard designations    To be able to assign the messages in the display to the different AS i  modules slaves  standard designations are programmed by default  The structure of    the standard designations is   e g  C1_M2S14 A    Cx  Number of the AS i ControllerE   important when using several AS i ControllerE units  e g  in networks     Mx  Number of the AS i master  1 or 2  of the AS i ControllerE  Sxx  Number of the AS i slave module  1 to 31     A  B  C  D   Channel designation of the AS i slave module  Except for the module types AS EP and AS EP4 there alway
32. gs necessary for the  TroxNetCom Basic User Software can also be carried out via the display  For  messages to be shown via the display of the AS i controllerE  UserMenu   the  program in the AS i controllerE must be active  yellow LED PLC RUN permanently  lit         Figure 6 1  User Menu display     correct operation    KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  33 of 64    cc  TROZ tecunik itm    6 1 Standard page of the AS i controllerE   The standard page is always shown when the AS i controllerE is switched on  It is  the main page of the internal menu of the AS i controllerE  page 0   This menu can  be accessed by pressing the    MENU    button  By pressing the    USER    button the so   called    UserMenu       for the TroxNetCom AS i application can be accessed        Figure 6 1 1  Standard page    The menu navigation of the internal menu as well as the associated functions are not  described in more detail here  They are described in the manual of the AS i    controllerE of ifm electronic gmbh   www ifm electronic com     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  34 of 64    cc  TROZ  Techn ifin    6 2 Pushbutton operation of the UserMenu    The pushbuttons for the control of the display  UserMenu  not in the standard menu   are programmed so that the next possible message can be shown by briefly pressing  the buttons  If the buttons are pressed longer  the next messages are automatically  displayed one after the other until the button
33. gure 7 2 2 1  AS i splitter    7 2 3 AS i module lower parts   AS i module lower parts can be used as connection elements between the AS i flat  cable and the AS i module upper part and as junction box  If the module lower part is  to be used only for cable branching  a cover is mounted instead of the module upper  part  e g  AS EP      KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  52 of 64    cq  TROZ    tecunik itm       Figure 7 2 3 1  Insertion of the AS i flat cable in the black AS i module lower part    Important mounting note  To ensure a good contact in the module lower part the  AS i flat cable is inserted in the module lower part with the profile lug first in a half   round movement  The flat cable back is then pressed into the cradle with your finger   The electrical contact is established by screwing an AS i module upper part  e g  AS   EP consisting of 2 orange components  or a cover  When the screws are tightened    the flat cable is pressed into the pins        Figure 7 2 3 2  Pressing the AS i flat cable into the yellow cradle    If after removing the AS i flat cable a yellow flat cable cradle is to be used a second    time for contacting  it has to be brought back to its initial position with a screwdriver     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  53 of 64    cc  TROZ tEcunik itm    7 2 4 Connection of input output modules  e g  TNC A2258     For voltage supply and communication with the AS i master the terminals A  and A   of 
34. ignal of a duct smoke detector RM O VS D       1 1 message  C1_M2S6_C  Damper closed    Reset             Figure 6 7 4  Closed fire damper with 1 end stop    By pressing the    ESC    button you can return to the main page of the UserMenu     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  40 of 64    cc  TROZ  Techn ifin    6 8 Page for single control    On this page the status of the individual fire dampers and smoke detectors can be  displayed  Furthermore  motor driven fire dampers and smoke detectors can be  individually triggered by pressing the    CTRL    button  By pressing the    T  and    4     buttons  further fire dampers and smoke detectors can be displayed  If a connection  for smoke detectors or motor driven fire dampers can be triggered  this is indicated  by the visible    CTRL    button  If a motor driven fire damper is triggered  this is  indicated by means of dark highlighted text  ON   A motor driven fire damper which is  not triggered is visualised by means of brightly highlighted text  OFF   The system is  in manual operation while the page for single control is active  This means that  the user himself is responsible for opening and closing the motor driven fire  dampers or testing triggering the smoke detectors  When this page is left  the  motor driven fire dampers are moved back into the positions assigned to them by the  program  If smoke detectors have been triggered during single control in manual  operation  the smoke messages must be 
35. ing    The effect of an activated sequential interlocking  ON  is that if a fire damper of a  group closes  all other motor driven fire dampers of this group must also close  The  motor driven fire dampers can be opened again by acknowledgement    The factory default setting is  OFF    5 5 Control via a relay contact    If the setting for control via a relay contact is activated  ON   signals which are  present at the inputs of the group related input output modules  slave addresses  1   30  for opening or closing motor driven fire dampers are directly evaluated  If this  setting is deactivated  OFF   only signals for closing motor driven fire dampers can  be evaluated  The signals commands for opening motor driven fire dampers must be  provided via the central input output module or via the integrated operating and  display panel of the AS i controllerE while this setting is deactivated  Signals of  central  slave address 31  or group related  slave addresses 1   30  input output  modules have priority over commands of higher level systems like  open all fire  dampers  or  close all fire dampers     The factory default setting is     For the first set up of installed input output modules  ON  otherwise OFF    KIE me Manual_TNCBUS _V1_44 e Last updated  04 09 06 page  29 of 64    cc  TROZ  Techn itm    5 6 Close faulty damper during the maintenance run    A failure of a fire damper during a maintenance run by exceeding the timeout or  manipulation  both end positions  leads t
36. ion                 06 21  4 2 3 Release of smoke detectors in QroUpS                cceceeeeeeeeeeeee eeeeeeeeeeeeeeeeeees 21   4 3 Functionality in case of a pollution Warning               ccceceeeeeeeeeeeeseeeeeeeeeeeeeeenees 22    KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  2 of 64         TROZ  Tecan ilim     ER    4 4 Closing and opening of motor driven fire damperS           sssssssersessserrrene erreen 22  4 4 1 Global closing and opening of all motor driven fire dampers                   22  4 4 2 Single control of motor driven fire dampers  manual operation                22  4 4 3 Closing and opening of motor driven fire dampers in groupS               65 22  4 4 4 Closing of motor driven fire dampers by sequential interlocking               23   4 5 Maintenance run of motor driven fire dampers  damper test                 00 24  4 5 1 Maintenance run of motor driven fire dampers for AS i controllerE          24  4 5 2 Maintenance run of motor driven fire dampers by groupS                ee 24    4 5 3 Maintenance run of fire dampers one after the other or simultaneously   24    4 5 4 Maintenance run in Genet al aise cscontarctencicteseavevener deuce ii aeee eens wien 25  4 6 DIAGNOSIS rec eects cece een neue estas econ eve aces wack Naa aAA eE ENEE bares 26  4 6 1  PAI DUN AMON sce ts cocci eset oneonae a iti ieee teen aaa AEA i 26  4 6 2 Exceeded timeout               ccccccecsecceceee ceceeeeeeeeeeaaeeeeeeeeeeeeaaee ceneneeeeeeeeeeeees 26  4 7 Dea
37. le supplies the smoke detector with energy and is directly  connected to the bus cable    The AS RM BD module is one bus participant per smoke detector    A combined use with all modules described in this manual on an AS i controllerE is    possible        Figure 1 5 1  AS RM B D  connection    KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  10 of 64         TROZ Tecan ilim     ER    1 6 Signal contacts and control signals    Input output module connection  e g  TNC A2258    The input output module is mainly used to receive commands and transmit  messages  Like the module AS RM BD the input output module can be used for  grouping  see 3 1  fire dampers  In addition centralised messages and commands  can be assigned to the input output module     The module is a participant of the bus system and has four signal contacts     1 6 1 Centralised messages and commands    With the slave address 37 centralised error messages of the system are given via  potential free contacts     O1  system ok   02  no fire damper CLOSED  O3  no smoke   O4  maintenance run not active    With the slave address 31 the following control signals can be transmitted to the    module via potential free contacts     l1  acknowledgement  reset of stored errors     12  opening of all fire dampers   l3  closing of all fire dampers  priority  NC contact    14  start or stop pulse for the maintenance run  damper test     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  11 of 64    TROA tecHnkK
38. o the automatic closing of the fire damper  with the setting being activated  ON   This default setting of the maintenance run can  also be deactivated    The factory default setting is  ON    5 7 Maintenance run one after the other or simultaneously    With this setting being activated  maintenance runs of fire dampers are always  carried out successively  When deactivated  a simultaneous maintenance run of fire  dampers can be carried out  A simultaneous maintenance run is only possible for  motor driven fire dampers and NOT when special types of motor driven dampers are  integrated    The factory default setting is  ON    5 8 Manual operation    When manual operation is activated  a single control of motor driven dampers or  smoke detectors via the integrated operating and display panel of the AS i  controllerE is possible  Single control in manual operation is for example necessary  for maintenance  The signals of input output modules for the opening and closing of  dampers are ignored when this setting is activated  Moreover  the centralised error  message of the system is active when this setting is activated    For legal reasons  setting of this function via the operating and display panel of the  AS i controllerE is secured by an additional locking  This setting can only be made by     simultaneously    pressing the buttons    T    and    OK        The factory default setting is  OFF    KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  30 of 64         TROZ Te
39. p    The factory default setting is  OFF    KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  31 of 64    cc  TROZ Echn itm    5 12 Change standard type of motor driven damper   The standard type of motor driven damper is the motor driven fire damper with AS   EM B AS i connection  As an alternative  motor driven smoke extraction dampers  with AS EM S AS i connection can be automatically detected  The performed setting  applies to all motor driven dampers connected to the AS i controllerE  The setting of  motor driven smoke extraction dampers can only be used in combination with  manual adaptations in the TroxNetCom Basic User Software    The factory default setting is  ON  AS EM B     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  32 of 64    cc  TROZ  Tecan ifin    6 Operating and display panel of the AS i controllerE  UserMenu    The integrated operating and display panel of the AS i controllerE is used to display  and operate the connections of the TroxNetCom AS i system for fire damper systems  described in the preceding chapters  All messages of the individual fire dampers and  smoke detectors can be displayed in detail via the integrated display of the AS i  controllerE  UserMenu   Stored messages can be acknowledged via the display   Furthermore  motor driven fire dampers and smoke detectors can be controlled or  triggered for test purposes via the display  For motor driven fire dampers a  maintenance run can be initiated via the display  The settin
40. r must be used for the second channel for the end position OPEN   jumper between terminal l  and terminal Ix   The input to be selected depends on  the switch type  NO NC contacts   If fire dampers with one end position are  connected to AS EP4 modules  the inputs which are not used for limit switches must    be linked  jumper between terminal l  and terminal Ix      7 6 Checking of connected slaves    If all slaves are addressed and connected to the AS i line  the list of the detected  slaves  LDS  can be indicated via the standard menu of the AS i controllerE  The    preset and current situation of the AS i system can thus be easily checked     gt     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  58 of 64    cc  TROZ Echn itm    The procedure is as follows     1  Power on the AS i controllerE    2  Wait until the AS i controllerE has completely started up    3  Is the standard page shown on the display of the AS i controllerE     ifm  electronic  AS i controllerE     standard page  no  0  or    Exx AS iX    displayed    If    no     go to point 4  if    yes    go to point 7      4  Is the    ESC    field displayed   If    no     go to point 5  if    yes    go to point 6      5  Press the left button and the    J    button simultaneously for 3 seconds until the     ESC    field is displayed   unlocking of the program lock    6  Press the    ESC    button  right button  of the AS i controllerE until    ifm  electronic  AS i controllerE     standard page  no  0  or
41. rating and display    panel of the AS i controllerE indicates a detailed text message for the closed damper     4 2 Functionality in case of smoke detection   If smoke is detected by one or several smoke detectors of a group  the assigned  motor driven fire dampers  AS EM B module  are closed  The centralised error  message  e g  relay contact or red light indicator  is switched via the program and the  signal  smoke  is given  e g  via a relay contact   The operating and display panel of  the AS i controllerE indicates a detailed text message for the smoke signal    After smoke detection the system must be acknowledged to delete the stored smoke  signal  Only then can the motor driven fire dampers be opened again     4 2 1 Global release of all smoke detectors    If an acknowledgement  gt  5 s is made by an illuminated pushbutton module  all  smoke detectors can be released at the same time     4 2 2 Individual release of smoke detectors  manual operation     Smoke detectors can be released individually via the operating and display panel of  the AS i controllerE     4 2 3 Release of smoke detectors in groups    Smoke detectors of a group can be released via a relay contact of an input output    module     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  21 of 64    cc  TROZ Echn itm    4 3 Functionality in case of a pollution warning    If a pollution warning is given by one or several smoke detectors of a group  the  centralised error message is switched via the p
42. rising order    Gaps are allowed in the addressing of the modules AS EM B  AS E and AS EP or  AS EP4 of a group if for example installation of bus participants in such a group is  planned at a later point in time    If a group is to be operated without smoke detectors or and input output modules  it  can be formed starting with address 1  This group has the number 0  The end of this  group is defined by the next smoke detector which then starts group 1    The individual fire dampers connected to AS EP or AS EP4 are always assigned    together to one group which depends on the slave assignment     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  18 of 64    TROA tecHnkK itm    oc                                                                            OmMmNDTOON WAAADTNYDTOOANAD Ot  ANDO TO ON oOo e H eH eH HATA TT NN NN ON ON ON OD OD  Q Ol o  Q  o  a  a T  o  a  aj a a  59 o  a  a  a  a  a  a  22  2 2  2  3    2 2 3    3 SS Sl Sl 5   D ma or  i  i i E f w T go aaa aa aa  N NoN AININ NINN DM  ol NAN AN NN WM  W  W  L  L  L L  L  L  L  L  L   lt  L  S  L  L  L  L  L  L  L   lt   Group 0 Group 1 Group 2                                        Figure 3 1 1  Grouping    3 2 Sequence of the module types    The TroxNetCom Basic User Software expects modules within a group which are    NOT sorted by types  The module types can be freely assigned     3 3 Documentation by Excel list    It would be useful to create the complete documentation of the AS i fire damper    system 
43. rogram  e g  relay contact or red light  indicator   The operating and display panel of the AS i controllerE indicates a detailed    text message for the pollution warning     4 4 Closing and opening of motor driven fire dampers    4 4 1 Global closing and opening of all motor driven fire dampers    All motor driven fire dampers can be closed via a relay contact or operation via an  illuminated pushbutton module  If no input output modules or illuminated pushbutton  modules have been installed  all motor driven fire dampers are opened via    acknowledgement  At the program start an automatic acknowledgement is given     4 4 2 Single control of motor driven fire dampers  manual operation     Motor driven fire dampers can be triggered individually via the operating and display  panel of the AS i controllerE  If the individual operation  manual operation  is  enabled  the sequential interlocking is deactivated during this enable period     4 4 3 Closing and opening of motor driven fire dampers in groups    If input output modules have been set up as modules with group assignment  slave  addresses 1   30   the assigned motor driven fire dampers  AS EM B module  can be  opened by an input signal  signal present  or closed  signal not present   The  centralised error message  e g  relay contact or red light indicator  is switched via the  program in case of closed fire dampers and the signal  damper closed  is given  e g     via a relay contact      KIE me Manual_TNCBUS_V1_44 e Las
44. s are released  So  several messages  can be conveniently displayed one after the other and the buttons of the AS i    controllerE are only subjected to minimum wear     6 3 Brightness   Contrast adjustment    If the text in the display of the AS i controllerE  UserMenu  is difficult to read  the  contrast can be adjusted by simultaneously pressing the right button and the    T       button  display too bright  or the    4    button  display too dark      6 4 Language selection   The text in the standard menu and in the UserMenu of the AS i controllerE can be  displayed in German and in English  By pressing the buttons    T  and    4     simultaneously  the menu navigation changes between German and English  In order  to protect the selected language against power failure it has to be stored in the  standard menu of the AS i controllerE  The storage is carried out as follows     1  Power on the AS i controllerE    2  Wait until the AS i controllerE has completely started up    3  Is the standard page shown on the display of the AS i controllerE   ifm electronic   AS i controllerE     standard page  no  0  or  Exx AS iX    displayed   If    no    go to  point 4  if    yes    go to point 7     4  Is the    ESC    field displayed    If    no    go to point 5  if    yes    go to point 6     5  Press the left button and the    J    button simultaneously for 3 seconds until the     ESC    field is displayed   unlocking of the program lock    6  Press the    ESC    button  right but
45. s is only 1  channel  A   For AS EP there are 2 channels  A and B  for 2 dampers with 2  limit switches   For AS EP4 there are 4 channels  A  B  C  D for 4 dampers    with 1 limit switch      System specific or customer specific modifications to the designations can be carried    out  For more information please read the following chapter 6 12     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  48 of 64    gg  TROZ  Techn ilim    6 12 Adaptation of the designations   The designations for the respective AS i participants slaves or for the respective fire  dampers can be freely assigned  This can for example be carried out at the factory to  customer specifications  Furthermore  programming of designations can be made by    a Trox system integrator        2 3 messages  C1_M2S15_A  Timeout error    Reset T I             Figure 6 12 1  Fire damper message with the standard designation in line 2       2 3 messages  L8 BSK E 06  Timeout error    Reset T l             Figure 6 12 2  Fire damper message with a customer specific designation in line 2    KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  49 of 64    cc  TROZ Echn itm    7 Operation and set up  To enable set up of a fire damper system using AS interface the steps described  below must be taken     The general procedure is as follows    e Install the fire dampers and smoke detectors incl  AS i modules    e Install the control boxes for AS i controllerE and power supplies    e Lay and connect the 230 V AC
46. st     All motor driven fire dampers can be tested for example by an input pulse at an  input output module  slave address 31  or by a pulse from the operating and display  panel of the AS i controllerE via an automatic maintenance run    A maintenance run cannot be started until all fire dampers with two end    positions are in the OPEN position     4 5 1 Maintenance run of motor driven fire dampers for AS i controllerE    For this automatic maintenance run all motor driven fire dampers connected to the  AS i controllerE are CLOSED and OPENED again one after the other     4 5 2 Maintenance run of motor driven fire dampers by groups    A maintenance run by groups  ventilation systems  is also possible  Only one group  can be tested  The group to be tested is determined via the operating and display  panel of the AS i controllerE  For the automatic maintenance run by groups all motor   driven fire dampers of the group are also CLOSED one after the other and then  OPENED again  An operating signal of the active maintenance run of the group is  transmitted via the NC contact of a group related input output module  slave address  1   30      4 5 3 Maintenance run of fire dampers one after the other or simultaneously    If the default setting is activated  maintenance runs are always carried out  successively  However  it is also possible to carry out maintenance runs of fire  dampers simultaneously  All fire dampers connected to an AS i controllerE or a group  of fire dampers of 
47. t updated  04 09 06 page  22 of 64         TROZ  Tecan ilim     ER    4 4 4 Closing of motor driven fire dampers by sequential interlocking    If motor driven fire dampers and other module types are divided in groups via slave  assignment  by smoke detectors or input output modules  or if all fire dampers are  independent of a group  it is possible to activate a so called sequential interlocking   The effect of this sequential interlocking is that if one fire damper of a group closes   all other motor driven fire dampers must also close  The type of the  first closing  fire  damper  AS EP or AS EP4  AS E  AS EM B  is unimportant  Even if for example a  fire damper with a mechanical limit switch of a group closes  the motor driven fire  dampers of this group must also close due to the sequential interlocking    The centralised error message  e g  relay contact or red light indicator  is switched  via the program in case of closed fire dampers and the signal  damper closed  is  given  e g  via a relay contact     Only after acknowledgement of the error message the motor driven fire dampers  open again    The sequential interlocking can be set in the TroxNetCom Basic User Software  The  setting is made via the operating and display panel of the AS i controllerE  The    default setting is a deactivated sequential interlocking     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  23 of 64    cc  TROZ  Techn itm    4 5 Maintenance run of motor driven fire dampers  damper te
48. ted  04 09 06 page  8 of 64    dg    TROZ  tcm o itm    1 4 Fire damper with spring return actuator    AS EM B connection   The spring return actuator enables a remote actuation of the fire damper  With the  actuator the damper can be opened and closed via remote actuation for test  purposes  Via the AS EM B module which is connected to the spring return actuator  the actuator is triggered and the two end positions are detected  Closing the dampers  can also be triggered by alarm messages  e g  smoke detector or higher level system  via relay contacts   The evaluation options  incorrect position  timeout  depending on  the direction   error by switching both limit switches  manipulation     AS EM B is one bus participant per damper    A combined use with all modules described in this manual on an AS i controllerE is    possible        Figure 1 4 1  AS EM B connection    KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  9 of 64    oc    TROZ    TECHNIK ifin    1 5 RM O VS D smoke detector    AS RM BD connection   With the AS RM BD module a plug in connection of the corresponding RM O VS D  smoke detector is possible    The module AS RM BD is particularly important as it allows grouping  see chapter  3 1  of fire dampers    The errors  smoke detected  and  RM O VS D system error  as well as the warning   pollution of the sensing head  gt 70   and the message  airflow  are detected  The  test function of the RM O VS D can be triggered with the module    The AS RM BD modu
49. the message page is automatically loaded  see chapter  6 7         Messages  Single control    Maintenance run    OK i  ESC             Figure 6 5 1  Menu navigation   top of the list    KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  36 of 64    TROA tecHnkK ifin    oc       Messages  Single control  Maintenance run    OK fi    ESC             Figure 6 5 2  Menu navigation   middle of the list       Single control  Maintenance run  Settings  OK ii ESC             Figure 6 5 3  Menu navigation   end of the list    The following menu points can be selected     Messages  Single control  Maintenance run    Settings    The other pages and their contents  which can be selected via the menu points  are    described in the following     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  37 of 64    gg  TROZ  Techn ilim    6 6 Locking   safety function   If no button is pressed on the AS i controllerE for a certain time  the message page is  automatically loaded  Furthermore  a locking of the display  UserMenu  is activated  and the    ESC    button becomes inactive  By simultaneously pressing the    Reset    and  the    J    button for 3 seconds  the locking can be deactivated  The    ESC    button is  then visible again    When the display is locked  it is protected against unauthorised manipulation        System OK  TroxNetCom AS i    Reset             Figure 6 6 1  Locked display without    ESC  button       System OK  TroxNetCom AS i    Reset ESC             Fig
50. the module must be connected to the corresponding AS i line  AS i    AS i      External command contacts must be supplied via the terminal l  and connected to  the corresponding input  11 to 14   Do not connect any of the terminals I   I   11  12  13   14 to an external potential as they are electrically connected to the AS i cable  The  voltage supply of sensors or mechanical switches must come from the corresponding  AS i module to which they are connected    The output signals are programmed so that OK signals are given via the NO contacts   e g  11 14  21 24  etc    Plant sections can thus be switched off easily  Several  output signals can be combined per series connection     For the assignment of the input and output signals see chapter 1 6        At  AS i   Ae  AS i        Sensor  supply LEDs 1   24   LEDs 2  l   Sensor  supply OV ADR  11   14  Switching  input LEDs 3  sensor  1   4  11 21  common  12 22  NC  14 24  NO  31 41  common  32 42  NC  34 44  NO 01 02 03 04    12 14 22 24 32 34 42 44    LS         11 21 31 41    Figure 7 2 4 1  Wiring of input output modules    KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  54 of 64    cc  TROZ Echn ifin    7 2 5 Opening of motor driven fire dampers by assigning commands  jumpers  to   the input output modules   If digital input output modules are integrated into the AS i fire damper system  it is   imperative to take into account the two following points    e The setting  Control via a relay contact   see chapter
51. ton  of the AS i controllerE until    ifm electronic     AS i controllerE     standard page  no  0  or    Exx AS iX    is displayed   KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  35 of 64    cc  TROZ  Techn ifin    7  If    ifm electronic  controllerE     standard page  page 0  or    Exx AS iX    is displayed   press the    MENU    button  left button  of the AS i controllerE in order to access the  internal menu    8  Select the menu point System Setup using the    T    and    J    buttons of the AS i  controllerE and acknowledge with    Ok     left button     9  Select Store System using the    T    and    4    buttons of the AS i controllerE and  acknowledge with    OK     left button     10 Using the    ESC    button  right button  you can return to the main menu    11 If no button is pressed and if the program is running in the AS i controllerE  yellow  LED PLC RUN flashes  you automatically return to the fire damper visualisation    after a certain predefined time     6 5 Main page for menu navigation   Every other page  menu  of the UserMenu can be accessed from this page  You can  scroll through the menu by pressing the buttons    T    and    J  A page with dark  highlighted text can be selected by pressing the    OK    button  By pressing the    ESC     button you can return to the standard page of the AS i controllerE  The main page is  automatically loaded by the program several seconds after program start  If no button  is pressed for a certain time  
52. ure 6 6 2  Unlocked display with    ESC    button    KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  38 of 64    gg  TROZ  Techn ilim    6 7 Message page    All messages are displayed on this page  Furthermore  the total amount of messages  and the sequential number of the current message are displayed  For every  participant or for every smoke detector and fire damper a specific designation is  displayed  Chapter 6 12 describes how the corresponding designations can be  adapted    By pressing the    T    and    J    buttons  further fire dampers and smoke detectors can be  displayed  In the following  only a selection of possible messages is presented  By  pressing the    Reset    button  messages or error messages stored by the program can  be acknowledged     Messages that can be displayed for fire dampers are   CLOSED  Timeout error  Manipulation   Switch error  Messages that can be displayed for duct smoke detectors are   Smoke  Airflow OK  Pollution  System error RM O VS D  Global messages     Manual operation via higher level system  Fire alarm  AS i system error  etc        System OK  TroxNetCom AS i    Reset T l             Figure 6 7 1  Correct operation    KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  39 of 64    gg  TROZ  Techn ilim       2 4 messages  C1_M1S2_A  Damper closed    Reset i l             Figure 6 7 2  Closed fire damper with 2 end stops       3 4 messages  C1_M1S5_A  Smoke detected    Reset il J             Figure 6 7 3  Smoke s
53. utton  left button  of the AS i controllerE in    order to access the internal menu       Select the menu point PLC Setup using the    T    and    J    buttons of the AS i    controllerE and acknowledge with    OK     left button        Select either Run or Stop using the    T    and    J    buttons of the AS i controllerE    and acknowledge with    OK     left button     Using the    ESC    button  right button  you can return to the main menu    If no button is pressed and if the program is running in the AS i controllerE   yellow LED PLC RUN flashes  you automatically return to the fire damper  visualisation after a certain predefined time     If the yellow LED PLC RUN does not light although the instructions have been    carried out correctly  it must be assumed that no program has been loaded to the    AS i controller or that it has been deleted manually     KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  61 of 64    cc  TROZ Echn itm    7 9 Settings  For a complete set up of the system settings must be made  These can be  made parameterised via the operating and display panel of the AS i controllerE     The following settings can be made     e Module type AS EP or AS EP4  1 or 2 limit switches per fire damper    e Contact assignment of AS EP AS EP4 as NC or NO contacts   e Text selection for AS EP4  CLOSED  NOT CLOSED or NOT OPEN  OPEN  e Sequential interlocking ON OFF   e Control via a relay contact ON OFF   e Maintenance run 1  close or open again the fire d
54. ves connected to the  AS i line and can trigger them via the program  The procedure is as follows    1  Power on the AS i controllerE    2  Wait until the AS i controllerE has completely started up    3  Is the standard page shown on the display of the AS i controllerE   ifm  electronic  AS i controllerE     standard page  no  0  or  Exx AS iX    displayed    If    no    go to point 4  if    yes    go to point 7     4  Is the    ESC    field displayed    If    no    go to point 5  if    yes    go to point 6     5  Press the left button and the    J    button simultaneously for 3 seconds until the     ESC    field is displayed   unlocking of the program    6  Press the    ESC    button  right button  of the AS i controllerE until    ifm  electronic  AS i controllerE     standard page  no  0  or    Exx AS iX    is displayed    7  If    ifm electronic  controllerE     standard page  page 0  or    Exx AS iX    is  displayed  press the    MENU    button  left button  of the AS i controllerE in  order to access the internal menu    8  Select the menu point Quick Setup using the    T    and    J    buttons of the AS i  controllerE and acknowledge with    OK     left button     9  Select the menu point Config all using the    T  and    J    buttons of the AS i  controllerE and acknowledge with    OK     left button     10  Acknowledge the question on projection adaptation for the AS i masters 1 and  2 with    OK    and wait for the message WAIT    11 Using the    ESC    button  right
55. via an Excel list  This list should contain     AS i addresses of the modules   AS i master  1 or 2    AS i controllerE no    Assignment of the fire dampers to smoke detectors ventilation systems  groups   PLC configuration of the AS i system   Data points of the individual fire dampers   Data points for the operating and display panel   Assignment of external commands to inputs and centralised messages for    external systems  relay contacts  to outputs    KIE me Manual_TNCBUS_V1_44 e Last updated  04 09 06 page  19 of 64         TROZ Tecan ilim     ER    4 Basic function of the system   Programming covers the basic functions for fire damper systems which are described  below  Special functions requested by the end user exceeding the scope of the basic  functions can be implemented by qualified personnel  Special functions can for  example be further types of motor driven dampers  e g  multileave dampers  or  customer specific group assignments of dampers to ventilation systems without  smoke detectors or input output modules    In general it can be said that a failure in the system or error messages remain stored  until they have been acknowledged  So one acknowledgement option  e g  relay  contact  illuminated pushbutton module  operating and display panel  must be  definitely provided for a fire damper system     4 1 Functionality in case of thermal release    4 1 1 AS EP and AS EP4 connection    If a fire damper is closed by manual actuation  e g  for maintenance  or by 
    