Home

34-XY-25-08 - Honeywell Process Solutions

image

Contents

1. The above listed wireless transmitters include a directional high gain antenna The high gain antenna may be installed remote from the XYR 5000 with the cable length not to exceed 100 ft 30m The antenna cable shield shall be bonded to earth ground XYR 5000 MODEL WT 531R REMOTE RTD INPUT amp DUAL CONTACT CLOSURE INPUT SEE NOTE 10 HAZARDOUS CLASSIFIED LOCATION CLASS Il III DIV 1 GROUPS A B C D E F amp Gor CLASS ZONES 0 OR 1 GROUP IIC ALL WIRES TO BE ROUTED THROUGH HOLE AND OUT OF THE CONDUIT ENTRY AT THE REAR OF THE HOUSING SHIELD OPTIONAL GROUND AT TRANSMITTER END ONLY RTD 4 WIRE ONLY SIMPLE APPARATUS NO CONNECTIONS PERMITTED TO J2 WHEN INSTALLED IN A HAZARDOUS ks LOCATION I Shame Show CONTACT CLOSURE INPUTS SIMPLE APPARATUS 90001377 SCALE NONE NONE REV E DATE 5 8 06 SH 3 0f5 o Sievers Rog Manual Rev 8 Honeywell Process Solutions Wireless Differential Pressure Transmitter XYR 5000 MODEL WT 531T DUAL REMOTE THERMOCOUPLE INPUT amp DUAL CONTACT CLOSURE INPUT SEE NOTE 10 HAZARDOUS CLASSIFIED LOCATION CLASS Il Ill DIV 1 GROUPS A B C D E F amp Gor CLASS ZONES 0 OR 1 GROUP IIC Honeywell SHIELDS OPTIONAL GROUND AT TRANSMITTER ALL WIRES TO BE ROUTED END ONLY THROUGH HOLE AND OUT OF THE CONDUIT ENTRY AT THERMOCOUPLES THE REAR OF THE HOUSING SIMPLE APPARATUS NOTE CHANNELS 1 AND 2 ARE
2. and _ Default of BLANK ___ Note The Baud Rate determines the maximum speed of the Transmission Rates and the Transmission Rates daternine the minimum speed of the Sample Rates lf a user enters a value that is not within these bounds the value of the entered bound will be changed automatically to allow proper operation 0 300 SEC Default of 0 Default of enabled NEXT DISABLE m NEXT NEAT ever E dies cual cuir ere ae le al Ne IF YES Is SELECTED NEW TRIM IS SAVED IF ab NO IS SELECTED TRIM POINT IS tiie poe MEXT DISCARDED RESET IF NO IS PRESSED NEW TRIM IS Rev 8 User Manual 45 Appendix D 46 Pressure Units InH20At 68F InHgAtOC FtH20At 68F MMH20At 68F MMHgAt OC Pol BAR MilliBAR GMPerSqCm KGPersqCm Pascals KiloPascals Torr Atmospheres PSIA FtH20At4C MetHgAt0OCc MegaPascals InH2O0At4C MMH20At 4C oo oF OF DB WN A E O 1 i S tt t t wea HeH w N NA 14 175 i77 179 237 238 235 ff J Volumetric Flow Units CuFtPerMin GalPerMin LiterPerMin ImpGalPerMin CuMeterPerHr GalPerSec MillionGalPerDay LiterPerSec 15 16 17 18 19 22 23 24 f f f Wireless Differential Pressure Transmitter Modbus Register Definit
3. and sub saharan Honeywell Southern Africa Honeywell S A Pty Ltd Phone 27 11 6958000 FAX 27 118051504 NORTH AMERICA Canada Honeywell LTD Phone 1 800 737 3360 FAX 1 800 565 4130 USA Honeywell Process Solutions Phone 1 800 423 9883 Or 1 800 343 0228 Email ask ssc honeywell com SOUTH AMERICA Argentina Honeywell S A 1 C Phone 54 11 4383 3637 FAX 54 11 4825 6470 Brazil Honeywell do Brasil amp Cia Phone 55 11 7266 1900 FAX 55 11 7266 1905 Chile Honeywell Chile S A Phone 56 2 233 0688 FAX 56 2 231 6679 Mexico Honeywell S A de C V Phone 52 55 5259 1966 FAX 52 55 5570 2985 Puerto Rico Honeywell Inc Phone 809 792 7075 FAX 809 792 0053 Trinidad Honeywell Inc Phone 868 624 3964 FAX 868 624 3969 Venezuela Honeywell CA Phone 58 2 238 0211 FAX 58 2 238 3391 Honeywell 2009 10 Honeywell International Inc
4. grams per milliliter kilograms per liter grams per liter pounds per cubic 2nch short tons per cubic yard degrees twaddell degrees baume heavy degrees baume light degrees API percent User Manual Rev 8 Honeywell Process Solutions Wireless Differential Pressure Transmitter FM APPROVED amp CSA CERTIFIED INSTRINSICALLY SAFE INSTALLATION CONTROL DRAWING NOTES 1 Intrinsically safe installation shall be in accordance with ANSI NFPA 70 NEC Articles 504 and 505 for the USA the Canadian Electrical Code CEC part Section 18 for Canada and ANSI ISA RP12 6 2 FM or CSA ENTITY approved apparatus shall be installed in accordance with the manufacturer s Intrinsic Safety Control Drawing or shall be Simple Apparatus Simple Apparatus are devices that will neither generate nor store more than 1 2V 0 1A 25mVWV or 20uJ such as switches thermocouples and RTDs 3 The Intrinsic Safety ENTITY concept allows the interconnection of two ENTITY Approved Intrinsically safe devices with ENTITY parameters not specifically examined in combination as a system when Uo or Voc or Vt in the USA lt Ui or Vmax lo or Isc or It in the USA lt li or Imax Ca or Co Ci Ccable La or Lo Li Lcable Po lt Pi Where two separate barrier channels are required one dual channel or two single channel barriers may be used where in either case both channels have been Certified for use together with combined enti
5. The Abnormal Transmission Rate is identical to the Normal Transmission Rate with one exception The Abnormal Transmission Rate only applies while the Transmitter is in an abnormal condition see Section 6 6 This allows an increase or decrease in the frequency of information you receive depending on the operating conditions of the process being monitored In order to properly set the Abnormal Transmission Rate determine how often updates are needed from the Transmitter when the process being monitored is operating under normal conditions The Transmitter has a selectable range of 1 5 10 15 20 40 seconds and 1 minute Figure 6 3 is an example of how the device switches transmission rates from Normal Transmission Rate to Abnormal Transmission Rate Note how the first abnormal transmission is sent immediately when the Normal Upper Value set point is exceeded The next transmission will then follow this immedi ate transmission by 10 seconds or whatever the Abnormal Transmission Rate is set to The transmissions will continue at this interval until the process value drops below the Normal Upper Value set point Once the process value drops below this set point another transmission is sent to the Base Radio The transmissions will then be sent at the Normal Transmission Rate of one minute the current setting for the Normal Transmission Rate from the time of the last abnormal transmission The user should also note that the transmission time
6. The factory default is 10 seconds If all of the data does not get through the data is resent the following sec ond This prevents data from being lost However if the Transmission Rate is set to the maximum 1 second 76 8K baud then the data cannot be resent the following second because the next set of data must be sent in order to meet the Transmission Rate The Wireless Management Toolkit software can be used to configure this setting An explanation of how to select the Normal Transmission Rate using the Wireless Management Toolkit software can be found in Section 6 6 of this manual m oe e e e e e o e e es 1 i OPERATIONS SEQUENCE NEXT A A A l Default of 10 Seconds 1 5 10 SEC 15 SEC 20 SEC 40 SEC 1 MIN Figure 6 1 Menu Map to Normal Transmission Rate Setting Rev 8 User Manual 21 Honeywell Process Solutions 6 2 Selecting the Normal Sampling Rate Input Volts 10 8 6 Normal Sample 0 1 00 2 00 Time min With a Normal Sampling Rate of 30 Seconds Figure 6 2 Incorrect Sampling Rate Input Volts 10 6 Normal 0 1 00 2 00 Time min With a Normal Sampling Rate of 15 Seconds Figure 6 3 Correct Sampling Rate 22 communication range speed of Transmit Rates Greater Greater Sampling Rates Rate or Less Rate or Less Rate or Less Wireless Differential Pressure Transmitter The Normal Sampling Rate is the interval in which the Transmitter reads the monitored proces
7. check the following e Is the Transmitter set to the above listed configurations e Is the Base Radio on e Do the Transmitter and Base Radio settings match See Section 5 of the Transmitter and Base Radio User Manuals e Are the Base Radio and Transmitters unable to communicate due to obstructions or distance See Transmitter Manual Transmitter Placement section e Have you run the RSSI Diagnostics See Section 3 2 1 Transmitter RSSI Diagnostic User Manual 3 Section 3 Wireless Differential Pressure Transmitter Installation 3 1 Mechanical Installation In this section mechanical installation instructions are discussed for the various setup capabilities of the Differential Pressure Transmitter The subsections are as follows 3 1 1 Transmitter Positioning 3 1 2 Installation in Liquid Flow Service 3 1 3 Installation in Gas Service IN A 3 1 4 Installation in Steam Service A Warning During installation do not apply force to the in Each Honeywell Differential Pressure Transmitter is a rugged device strument housing or antenna Use a proper wrench which provides optimal performance when installed with careful TOT A nse AUOGS EAUUEE CONS COLnEeE INE consideration It may be utilized in any ultrasound measurement service so tion procedures can cause damage to the Transmit te long as care is exercised to prevent exposing the sensing elements to excess stress or temperature Installation practices greatly affect the
8. ee A USER PROMPTED FOR PASSWO NEXT ENTER NEXT NEXT Default of 19 2K Figure 5 2 Menu Map to Baud Rate Setting Each Transmitter is identified by the Base Radio and WMT according to the RF ID given to that particular unit Two Transmitters CANNOT have the same RF ID and be on the same RF Channel if you do not know the RF Channel see section 5 1 If the Transmitter is in the Operations Sequence pressing the ENTER button displays the Read Only Sequence on the LCD The RF ID of that unit will be displayed in this format ID 3 All Transmitters in your system are set to a default RF ID number upon shipment For example if you have ordered a Base Radio and three Trans mitters the Transmitters will be configured to RF ID s 0 0 and 0 You must set these units to three different IDs between 1 and 100 The Transmitters in this example could be set to RF IDs 1 2 and 3 First determine the RF ID s you d like to give each unit Then follow the menu map shown in Figure 5 3 to configure the RF ID The factory default is RF ID 0 which disables the RF communication of the unit User Manual 19 Honeywell Process Solutions Wireless Differential Pressure Transmitter I e e e e 5 23 Continued OPERATIONS SEQUENCE Nex Pao eiee 1 ENTER RF CHAN NEXT NEXT ENT ID RED kewrer Default of 000 Figure 5 3 Menu Map to RF ID Setting Once you have selected the RF ID you wish to use for this particular Transmitt
9. sent the Transmitters will only search for the Base Radio every one hour or so Turning the Transmitters off and back on will cause them to begin searching immediately Rev 8 This section summarizes what must be done in order to get the device in stalled configured and in operation quickly However it does not provide detailed or how to information to perform the tasks outlined Install the Transmitter in the desired location of operation Turn on the Transmitter by simultaneously pressing and holding the ENTER and NEXT buttons until the unit powers up 3 Hit the NEXT button until the CONFIG message appears then hit ENTER Enter the default password OOOO to enter the CONFIG menu Enter the SET RF menu Set RF CHAN setting equal to the Base Radio s RF Channel Set BAUD RT setting equal to the Base Radio s Baud Rate Set RF ID number to be a unique value between 1 and 100 Select normal transmission rate 10 Select normal sampling rate 11 Select abnormal transmission rate 12 Select abnormal sampling rate 13 Set normal upper and lower values 14 Select engineering measurement units 15 Zero the sensor 16 Trim and Offset the measurement if appropriate N e Se oe a If the RF OFF message is being displayed on the Transmitter LCD per form the following e Set the RF CHAN setting equal to the Base Radio s RF Channel If a NO RF message is being displayed on the Transmitter LCD
10. 6 13 Condition Chatter Elimina tion Due to Time Deadband Using Wireless Management Toolkit If you have the Wireless Management Toolkit software this menu option will not be accessible via the Transmitter once the Transmitter detects that the software is being used See Appendix A for more details An explanation of how to select the Abnormal Sampling Rate using the Wireless Management Toolkit software can be found in section 6 7 Indicates that Menu is Disabled if Wireless Management Toolkit is detected See Appendix A 26 User Manual Rev 8 Honeywell Process Solutions 6 7 Selecting Rates Thresh olds and Deadbands via the WMT Differential Pressure Properties 00009044 9 44 General Range Operation Mode Sensor Offset Sampling Bands Alarms Sampling Rates Update Rates Normal Transmit Aate 10 Sec Abnormal Transmit Rate 5 Sec Normal Sampling 1 Sec Abnormal Sampling 1 Sec Smart Smoothing The Smart Smoothing feature rejects noise and glitches by averaging samples within the deadband and ignoring the first sample outside the deadband C Enable Smart Smoothing 1 255 Seconds Percent Sqr Rt SmartRate The SmartRate feature causes the field unit to transmit its data immediately any time the primary value changes by the amount set C Enable SmartRate Figure 6 14 Sample and Transmission Rate Selection Using WMT Differential Pressure Properties 00009044 9 44 General R
11. Honeywell Bucharest Phone 40 0 21 2316437 FAX 40 0 21 2316439 Russian Federation RF ZAO Honeywell Phone 7 095 796 98 00 FAX 7 495 797 99 64 34 XY 25 08 Rev 8 April 2010 Slovak Republic Honeywell s r o Phone 421 2 58247 410 FAX 421 2 58247 415 Spain Honeywell S A Phone 34 0 91313 61 00 FAX 34 0 91313 61 30 Sweden Honeywell AB Phone 46 8 775 55 00 FAX 46 8 775 56 00 Switzerland Honeywell AG Phone 41 18552448 FAX 41 1 855 24 45 Turkey Honeywell Turkey A S Phone 90 216 578 71 00 FAX 90 216 575 66 35 Ukraine Honeywell Tel 380 44 201 44 74 Fax 380 44 201 44 75 United Kingdom Honeywell Control Systems Ltd Phone 44 0 1344 655251 FAX 44 0 1344 655554 MIDDLE EAST Abu Dhabi U AE Middle East Headquarters Honeywell Middle East Ltd Phone 971 2 4041246 FAX 971 2 4432536 Sultanate of Oman Honeywell amp Co Oman LLC Phone 968 24 701153 Ext 33 FAX 968 24 787351 Saudia Arabia Honeywell Turki Arabia Ltd Jubail Office Phone 966 3 341 0140 Fax 966 3 341 0216 Honeywell ATCO Dammam Office Phone 0096638304584 Fax 0096638338059 Kuwait Honeywell Kuwait KSC Phone 965 242 1327 to 30 Fax 965 242 8315 And Phone 965 326 2934 1821F ax 965 326 1714 AFRICA Mediterranean amp African Distributors Honeywell SpA Phone 39 02 250 10 604 FAX 39 02 250 10 659 South Africa Republic of
12. NOT ISOLATED FROM EACH OTHER GROUNDED THERMOCOUPLES MAY ONLY BE USED INA SINGLE CHANNEL SHIELDS OPTIONAL CONFIGURATION GROUND AT TRANSMITTER NO CONNECTIONS END ONLY PERMITTED TO J2 WHEN INSTALLED IN A HAZARDOUS LOCATION Ar LT CONTACT CLOSURE INPUTS SIMPLE APPARATUS 90001377 SCALE NONE NONE REV E DATE 5 8 06 Rev 8 User Mant 8 SH 40f5 User Manual 51 Honeywell Process Solutions Wireless Differential Pressure Transmitter XYR 5000 MODEL WW 591 amp WW592 DUAL CONTACT CLOSURE INPUT SEE NOTE 10 HAZARDOUS CLASSIFIED LOCATION CLASS Il Ill DIV 1 GROUPS A B C D E F amp Gor CLASS ZONES 0 OR 1 GROUP IIC ALL WIRES TO BE ROUTED THROUGH HOLE AND OUT OF THE CONDUIT ENTRY AT THE REAR OF THE HOUSING A i SHIELDS OPTIONAL GROUND AT TRANSMITTER NO CONNECTIONS END ONLY PERMITTED TO J2 WHEN INSTALLED IN A HAZARDOUS LOCATION LT q1 D CONTACT CLOSURE INPUTS SIMPLE APPARATUS PA 50001377 A4 REV E DATE 5 8 06 SH 5 of 5 52 User Manual Rev 8 Sales and Service For application assistance current specifications pricing or name of the nearest Authorized Distributor contact one of the offices below ASIA PACIFIC Malaysia a Control Products Honeywell Engineering Asia Pacific Headquarters Sdn Bhd Phone 65 6355 2828 phe 60 3 7950 Fax 65 6445 3033 Fax 60 3 7958 8922 Asia Pacific Global Technical Support Field Instruments Phone 65 6
13. USER PROMPTED FOR I l Figure 3 4 Menu Map to RSSI Mode Now that the Transmitter is in the RSSI mode bring the Transmitter close to the equipment you wish to monitor Look at the LCD notice the gt will constantly fluctuate You should estimate an average value based on these fluctuations The ideal signal integrity is seven arrows Once you have verified that you are receiving a signal you should check to make sure the Transmitter is communicating properly with the Base Radio To do so exit the RSSI by pressing ENTER and then navigate to the EXIT of the diagnostic menu and return to the Operations Sequence shown in Figure 4 1 in Section 4 1 If you see a NO RF message then you do not have satisfactory RF communication with the Base Radio If your application allows move the Transmitter to a different position and check again for communications If your application only allows you to mount at this particular point you may want to try a slower baud rate setting for an increased range One final solution is to reposition the Base Radio However this may affect communications with previously installed Transmitters and if so may require the use of a second Base Radio for your application To select a better spot for the Base Radio see Section 3 1 1 of the Base Radio User Manual The Link Test measures the wireless link performance of a Transmitter running in its normal operating mode Messages are sent from the Transmi
14. User Manual Rev 8 Honeywell Process Solutions 3 1 2 Installation in Liquid Flow Service EF Figure 3 2 Installation in Liquid Flow 3 1 3 Installation in Gas Service The piping between the process and the transmit ter must accurately convey the process pressure to the transmitter sensor In transferring the pres sure there are several sources of error These are leaks pressure loss due to friction particularly if purging is used in the application gas that is trapped in a liquid line liquid that is trapped in a gas line temperature induced density variations between the legs other density variations between the measurement legs The actual installation must be made to minimize these errors 3 1 4 Installation in Steam Service A7 a a ao a F g ff P Fa d y F 1 Pi F iv Fi i roy Fay i fy am il f fils F na J i i ot iy f i P j J F lof f _ i kA pe a A I il ae 4 hl i Fi T a an M a Me at A Ea iif y a hl I i p a i o F o Jii Figure 3 3 Installation in a Steam Application Rev 8 Wireless Differential Pressure Transmitter In liquid service you want all of the impulse lines to be completely full of liquid Itis generally best practice to place the process taps in the side of the liquid process line This minimizes the entrance of gas bubbles which tend to form at the top of the process line It also tends to minimize the entrance of sl
15. You will need to check the position zero reading on the transmitter The Differ ential Pressure Transmitter is a sensitive device Its elevation and its ori entation in the field may be different from the orientation in the factory where it received its last configuration To compensate for position changes you may need to perform a sensor position adjustment once the unit 1s installed For this step power the unit and apply zero pressure Be sure that the unit is installed in its final location or that it is oriented exactly as it will be in its final installation If you have a differential pressure device you will also need to go through a series of operations to fill the impulse lines to the device See Section 3 2 Commissioning If you have a transmitter pressure reading of zero that is the transmit ter reading is within the specified accuracy of 0 07 of the full scale value when zero pressure is applied there is no need to zero the sensor If your zero reading is outside of this value you will need to execute the position zero adjustment by following the menu map shown in Figure 7 3 When P ZERO is selected the sensor is zeroed However the displayed value is calculated relative to the offset point The unit will display an amount equal to the keypad configured offset added to the WMT configured level offset if applicable If the intent is to have the unit dis play 0 the offsets must be zero befor
16. buttons for a few moments 3 Remove the 4 set screws on the sides of the Transmitter housing with a standard screw driver 4 Remove the housing and locate the battery Warning When remov ing the housing do not twist or bend the green flex cable Doing so may cause the tether to improperly seat next to the antenna and greatly reduce operable RF distances Do not allow the housing to flop around while hanging by the tether 5 Remove the old battery and replace it with the new battery positive end first Note that the positive end of the battery clip is the end with the red wire 6 Plug the green wire flex cable back in if unplugged and replace the housing Then screw the housing back on and power up the unit by pressing either of the buttons Properly dispose of used battery User Manual Rev 8 Section 1 Wireless Differential Pressure Transmitter Technical Specifications Differential Pressure Input Characteristics Range Limits Accuracy Zero Temperature Effect Combined Zero amp Span Temperature Effect 10 to 400 H2O 4500 psig 0 10 of calibrated span or 0 15 of span per 28 C 50 F 0 225 of span per 28 C 4 C 39 2 F upper range value URV 50 F 310 bar whichever is greater When URV is below reference point 50 H20 effect When URV is below refer When URV is below reference ence point 50 H20 effect point 25 H20 Accuracy 0 15 x 60 H2O span 0 07
17. by select ing the Sensor Offset tab within the configuration menu Rev 8 User Manual 37 Section 9 Wireless Differential Pressure Transmitter Maintaining the Transmitter 9 1 Changing the Battery A Warning A When removing the housing do not twist or bend the green flex cable Do ing so may cause the tether to improp erly seat next to the antenna and greatly reduce operable RF distances Do not allow the housing to flop around while hanging by the tether 38 The Differential Pressure Transmitter is extremely easy to maintain in that it requires no periodic calibration or system checks The Transmitter has a self diagnostic that is constantly checking the internal system If any errors are found they are reported via the LCD Base Radio or in the WMT A simple yearly visual inspection for the following is all that is needed e Is the Transmitter still securely fastened to the equipment being monitored e Are there any visible corrosions cracks or residue build ups on the unit e Has anything about the application changed from the original intended use The battery will need to be changed within one month of seeing a LOW BAT message on the Transmitter This is a simple process 1 Make sure you have the correct replacement battery TADIRAN Lithium Inorganic Battery non rechargeable Size C 3 6Volts TL2200 S 2 Power down the Transmitter by pressing and holding both the NEXT and ENTER
18. in three separate 7 character flashes on the Transmitter LCD The user may choose from A Z 0 9 a dash and an underscore _ The underscore has a special meaning to the software inside the Transmit ter For example if you have a Tag Name that is only 5 characters long then you do not want to wait for the rest of the 16 characters to be dis played on the LCD So if your Tag Name was TRAPI you would want to enter the Tag Name like this TRAPI _ a The Tag Name is entered via the Wireless Management Toolkit To do so when the software is in the Transmitter view See Section 8 1 of the Wire less Management Toolkit User Manual right click the Transmitter icon select Rename then enter the Tag Name you wish the Transmitter to have This Tag Name will then be uploaded to the Transmitter and can be dis played by pressing the ENTER button when the unit is in the Operations Sequence See Section 4 1 1 of this manual 16 User Manual Rev 8 Honeywell Process Solutions Wireless Differential Pressure Transmitter 4 4 Setting a User Password Each Transmitter has a password that will lock out undesired users from making changes to the Transmitter Any user may still view some of the Transmitter settings by pressing the ENTER key during the Operations Differential Pressure Properties 00009044 9 44 Sequence and viewing the Read Only Sequence Sampling Rates Sampling Bands Alarms Range Operation Mode S
19. life that you can expect from your Honeywell Differential Pressure Transmitter Give careful consideration to the environment where you will be installing your instrument Avoid installations that expose the device to excess temperature high vibration considerable shock or exposure to dripping condensate or corrosive materials Also avoid installing the device in an unserviceable location Most often these problems can be avoided with some thought at the time of installation The practices noted below are generally recommended but they can only act as a guideline and cannot cover all possible variations The final installation must be made at your discretion and approval You must be the judge of the actual installation Dimensioned mechanical drawings for aid in mechanical installation are located in Section 10 Technical Specifications 4 User Manual Rev 8 Honeywell Process Solutions Wireless Differential Pressure Transmitter 3 1 1 Transmitter Positionin g Correct positioning of the Transmitter will ensure the best performance of the device When planning the positioning of the Transmitters there are a few parameters that must be paid attention to e The top of the Transmitter should point upwards The bottom of the Transmitter should NOT point directly at the Base Radio and the Transmitter LCD should point away from the Base Radio e All Transmitters should maintain an approximate spacing of at least six feet apart from one an
20. must go to the configuration menu of the Transmitter Sampling Rates o Alarms e via the Software For further instructions on getting to the configuration catia Rises Ee menu see Section 9 2 of the Wireless Management Toolkit User Manual Mode Pressure Once you have opened the configuration menu select the Operation Pressure Units Psi Mode tab at the top of the menu You should then see a menu like the one shown in Figure 8 1 To select the Differential Pressure mode select Pressure in the Mode drop down box This will display another drop down box which will al low the selection of differential pressure engineering units You should select the units that are appropriate for your application All possible units are listed below BAR Figure 8 1 Differential Pressure Setting ae NOTE Square root is OFF Once engineering units have been selected a 22 point sensor offset curve can be enabled it is disabled upon delivery from the factory by selecting the Sensor Offset tab within the configuration menu 32 User Manual Rev 8 Honeywell Process Solutions Wireless Differential Pressure Transmitter 8 2 Orifice Flow In this mode the user has the option of setting up volumetric or mass flow calculations through an orifice plate if the density units are selected and Differential Pressure Properties 9 44 entered mass flow calculations are available The user must enter a differ Sampling Rates Alarms ential pr
21. recommended for all installations The 4 20 mA loop shield shall be grounded at the supply barrier end to the barrier ground bus only when grounded Zener barriers are used The 4 20 mA loop shield shall be grounded at the transmitter end only when galvanically isolated barriers are used 12 Divisions 1 amp 2 and Zone 0 WARNING EXPLOSION HAZARD SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR USE IN HAZARDOUS LOCATIONS 13 Division 2 WARNING EXPLOSION HAZARD DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON HAZARDOUS 14 NO REVISION OF THIS CONTROL DRAWING IS PERMITTED WITHOUT AUTHORIZATION FORM FM APPROVALS AND CSA Hoey release approvals see ECO 0005032 XYR 5000 Field Transmitter Associated Apparatus Ui or Vmax 30V Ui or Vmax Vt Uo Voc or Vt lt 30 V li or Imax 100 mA li or Imax lo Isc or It lt 100 mA Associated Apparatus Ca Ccable Ci of other transmitter Ca or Co gt 0 nF connected to two channel barrier Associated Apparatus La Lcable Li of other transmitter connected La or Lo gt 0 mH to two channel barrier SCALE NONE NONE REV E DATE 5 8 06 SH 2 of 5 Rev 8 User Manual 49 Honeywell Process Solutions Wireless Differential Pressure Transmitter Models with high gain antennas VWA565 VWA566 VWWA575 WA576 WG561 VWG562 WG563 WG564 WG565 VWWG566 VWL561 VWWL566 VWL571 WL576 W553 W554 WT534R VWT534T WAAS92
22. test Then select the Normal Transmit rate that matches that of the Transmitter If the Transmitter is transmitting at a different rate than the one you Select in this menu your results will be invalid Once the Normal Transmit Rate is selected the Link Test will immediately start The Base Radio will begin to test the link from the Transmitter During this time the word TEST will appear on the LCD display When the test is complete the Base Radio will display the quality of the link Be aware that the length of time it takes to perform this test is dependent upon how fast the Transmitter is normally transmitting 10 User Manual Rev 8 Honeywell Process Solutions 3 2 2 2 Continued Wireless Differential Pressure Transmitter ENTER NK TST LENTERS REID XXX_ ENTER aos gt gt gt gt gt gt gt gt gt gt gt gt gt gt gt gt gt gt NO LINK Figure 3 6 Menu Map to Base Radio Link Test When enough messages have been observed a link strength will be shown on the display gt gt gt gt gt indicates the strongest link while gt indicates the weakest link The Link Test will continue to be evaluated and the rating on the screen may adjust itself Keep in mind that the longer the Link Test runs the more data the Transmitter will have to evaluate The Transmitter installation site should strive to place the Transmitter in a location where it receives the highest number possible A stronger link means les
23. the field unit to transmit its data immediately any time the primary value changes by the amount set Enable SmartRate Send a sample when primary value Percent changes by Sqr Rt Load from File Figure 6 9 Smart Rate Configuration Using WMT Rev 8 Wireless Differential Pressure Transmitter The Smart Rate is a feature used to trigger radio transmission of the measured data sooner than the normal or abnormal rate specified by the user This feature is used to construct a more accurate graph of the measured process value vs time than is possible with the fixed transmission rates while using less battery power First you must decide the amount that the process variable must change since the last data sample to trigger a new transmission of the process value If the process value changes by more than the entered Smart Rate amount within the normal or abnormal sampling rate whichever is active then the process variable is transmitted immediately The normal abnormal transmit clock is then reset upon this transmission If no Smart Rate amount exceeding change takes place in the next normal abnormal sample then the next transmission will be the normal abnormal transmit rate period The amount entered is in the same units as were selected by the user to be displayed on the Transmitter If the measured process value does not change by more than the entered Smart Rate amount within the time between the sampling rates whicheve
24. tion fdoneela India Ltd for PT Honeywell Indonesia a Phone 62 21 535 8833 SH Lanka FAX 62 21 5367 1008 India Automation India Ltd EUROPE Austria Honeywell Ltd Phone 91 5603 9400 Fax 91 5603 9600 Honeywell Austria GmbH Phone 43 316 400123 FAX 43 316 40017 Japan Honeywell Inc Phone 81 3 6730 7150 Fax 81 3 6730 7228 Belgium Honeywell SA NV Phone 32 0 2 728 24 07 FAX 32 0 2 728 22 45 Honeywell Process Solutions 1860 West Rose Garden Lane Phoenix AZ 85027 www honeywell com ps Bulgaria Honeywell EOOD Phone 359 2 40 20 900 FAX 359 2 40 20 990 Czech Republic Honeywell spol s r o Phone 420 242 442 232 FAX 420 242 442 131 Denmark Honeywell A S Phone 45 39 55 55 55 FAX 45 39 55 55 58 Finland Honeywell OY Phone 358 0 20752 2753 FAX 358 0 20752 2751 France Honeywell SA Phone 33 0 1 60198075 FAX 33 0 1 60198201 Germany Honeywell AG Phone 49 69 8064 299 FAX 49 69 806497336 Hungary Honeywell Kft Phone 36 1 451 4300 FAX 36 1 451 4343 Italy Honeywell S p A Phone 3902921 46307 FAX 39 0292146377 The Netherlands Honeywell B V Phone 31 0 20 5656200 FAX 31 0 20 5656210 Norway Honeywell A S Phone 45 39 55 55 55 Poland Honeywell Sp zo o Phone 48 22 6060900 FAX 48 22 6060901 Portugal Honeywell Portugal Lda Phone 351 21 424 5000 FAX 351 21 424 50 99 Romania
25. 2 point curve table indicating the relationship between height and volume Level Density Pounds Cubic Foot To set the Transmitter to this operation mode you must go to the configu ration menu of the Transmitter via the Software For further instructions Tank Height a on getting to the configuration menu see Section 9 2 of the Wireless Man Sains rae agement Toolkit User Manual Full Tank Pressure Level Offset Feet Once you have opened the configuration menu select the Operation Mode tab at the top of the menu and select Fluid Level from the mode menu You should then see a menu like the one shown in Figure 8 4 Level Units Feet Dis play Characters NOTE Square root is OFF BBL Centimeters Cubic Feet Figure 8 5 Level Mode Feet Gallons NOTE Grams For Level a 22 point curve table must be filled out for correct operation mperial Gallons Z sis I Q O oOlololn lt gt Cc CICISIS lt sin oj Jal T amp A e f O nches DEA iquid Barrels m iters ong Tons tric Tons Normal Cubic Meters Ounce Centimeters wice U ea o Gaons SSS ems SS Normal Gubic Weters ounce SS Percent Heght Percent Height o O D l lt ped n n UlLUiIO a lt lt 5 m i O11 J d S 5 lt Tle S BI o Once engineering units have been selected a 22 point sensor offset curve must be enabled it is disabled upon delivery from the factory
26. 5 0 15 50 H2O0 0 125 0 05 25 H2O span span WD622 5to 100 PSID 4500 psig _ 0 10 of calibrated span or 0 15 of span per 28 C 50 F 0 225 of span per 28 C URV whichever is greater 50 F 310 bar When URV is below reference When URV is below reference point 30 psi effect When URV is below refer point 20 psi Accuracy ence point 30 psi effect 0 15 x 30 psi span 0 125 0 05 20 psi span 0 075 0 15 30 psi span 100 to 3000 PSID 4500 psig _ 0 10 of calibrated span or 0 20 of span per 28 C 50 F 0 225 of span per 28 C URV whichever is greater 50 F 310 bar When URV is below reference When URV is below reference point 500 psi effect When URV is below refer point 300 psi Accuracy ence point 500 psi effect 0 20 x 500 psi span 0 125 0 05 300 psi span 0 10 0 20 500 psi span Output Resolution e See the Base Radio description for analog and digital output options Rev 8 User Manual 39 Honeywell Process Solutions 40 Wireless Differential Pressure Transmitter Operating Temperature Range e 40 F to 220 F 40 C to 104 C process connection temperature steady state e 40 F to 185 F 40 C to 85 C electronics e 4 F to 158 F 20 C to 70 C display full visibility e 40 F to 185 F 40 C to 85 C display with reduced visibility e Humidity Limits 0 to 100 Sampling and Transmission Characteristics The D
27. 580 3156 Fax 65 6445 3033 Process Instruments Phone 603 76950 4777 Fax 603 7958 8922 New Zealand Honeywell Limited Phone 64 9 623 5052 Fax 64 9 623 5060 Toll Free 0800 202 088 Philippines Honeywell Systems Philippines Inc Australia Phone 63 2 633 2830 Honeywell Limited 31 Phone 61 7 3846 1255 636 1661 62 FAX 61 7 3840 6481 Fax 63 2 638 4013 Toll Free 1300 36 39 36 Toll Free Fax 1300 36 04 70 Singapore Honeywell Pte Ltd Phone 65 6580 3278 China PRC Beijing Fax 65 6445 3033 Honeywell China Inc Phone 86 10 8458 3280 Fax 86 10 8458 4650 South Korea Honeywell Korea Co Ltd Phone 822 799 6315 Fax 822 792 9015 China PRC Shanghai Honeywell China Inc Phone 86 21 5257 4568 Fax 86 21 6237 2826 Thailand Honeywell Systems Thailand Ltd Phone 662 693 3099 China PRC Chengdu FAX 662 693 3089 Honeywell China Inc Phone 86 28 8678 6348 Fax 86 28 8678 7061 Taiwan R O C Honeywell Taiwan Ltd Phone 886 2 2245 1000 China PRC Xian FAX 886 2 2245 3241 Honeywell China Ltd Xi an SE Asia Countries Phone 86 29 8833 see Honeywell Pte Ltd 7490 Singapore Fax 86 29 8833 7489 for Pakistan Cambodia Guam Laos Myanmar China PRC Shenzhen Vietnam East Timor Honeywell China Inc Phone 86 755 2518 SE Asia Countries 1226 see Honeywell Automa Fax 86 755 2518 1221
28. Differential Pressure Transmitter If you are running WMT a 22 point sensor offset curve may be entered for the Transmitter To do so open the configuration dialog box Once in the configuration dialog box click the Sensor Offset tab to bring up the offset information as shown for Level in Figure 7 6 Differential Pressure Properties 00009044 9 44 Sampling Rates Sampling Bands Alarms General Range Operation Mode sensor Offset Disable Sensor Offset Curve Enable Sensor Offset Curve Curve Parameters Indicated Actual value Indicated Actual Value Value Value Humber of Pairs of alues 2 Paint 0 Paint 1 All values are in units of Fsi Figure 7 6 Setting a 22 Point Curve Using WMT User Manual 31 Section 8 Wireless Differential Pressure Transmitter Selecting and Configuring Operation Modes In this section the four operation modes differential pressure orifice flow open channel flow and level are discussed in order to aid the user in se lecting the right mode for his or her application and properly configuring the Transmitter for that specific application The subsections are as fol lows 8 1 Differential Pressure 8 2 Orifice Flow 8 3 Open Channel Flow 8 1 Differential Pressure This mode simply calculates and displays the differential pressure value from the Differential Pressure sensor To set the Transmitter to this op Differential Pressure Properties 9 44 eration mode you
29. Honeywell Wireless Differential Pressure Transmitter User Manual Americas 900 MHZ ISM Band XYR 5000 Line 34 XY 25 08 Rev 8 April 2010 User Manual Wireless Differential Pressure Transmitter Versions 1 70 or later Important Information tothe User 4 amp Changes or modifications not expressly approved by the manufacturer may void the user s authority to operate the equipment This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation This device is for mobile and fixed use only not portable or body worn A separation distance of 20 cm must be maintained at all times between the antenna and the body of the user and bodies of nearby persons If the Wireless Management Toolkit RF Server software is shutdown the RS 485 network MUST be physically disconnected from the PC as the serial port is no longer being controlled by the software and may disrupt communications between the Base Radio s and Analog Digital Output Module s This device has been designed to operate with an antenna having a maximum gain of 9 dBd Antenna having a higher gain is strictly prohibited per regulations of Industry Canada The required antenna impedance is 50 ohms To reduce potential radio interference to other users the ant
30. Rate 6 5 Setting the Smart Rate Threshold 6 6 Selecting the Normal Upper and Lower Values 6 7 Selecting Rates Thresholds and Deadbands via the Software 6 1 Selecting the Normal The Normal Transmission Rate is the interval in which the Transmitter transmits data to the Base Radio The Transmitter is in a sleep mode to save power during the operations sequence This mode turns off most of the electronics on the unit with the exception of the LCD in order to pre serve battery life The Transmitter will then wake up every Normal Sam pling Period and take the necessary process value readings The Transmit ter will then transmit these readings to the Base Radio on an interval deter mined by the Normal Transmission Rate Transmission Rate Notice that the fastest update rate of the Normal Transmission Rate is de pendent on the baud rate setting you selected earlier see Section 5 2 The transmission rates cannot update data faster than their communication speed allows Thus if you selected the 19 2K Baud Rate setting your fast est transmission rate will be 5 seconds The Transmitter automatically determines these settings and adjusts the menu options accordingly A complete table of these parameters is shown in Section 6 2 In order to properly set the Normal Transmission Rate you must first de termine how often you need updates from the Transmitter You have a selectable range of 1 5 10 15 20 40 seconds and 1 minute
31. Setting 24 Wireless Differential Pressure Transmitter The Abnormal Sampling Rate is identical to the Normal Sampling Rate with one exception The Abnormal Sampling Rate only applies while the Transmitter is in an abnormal condition see 6 6 Selecting the Normal Upper and Lower Values This allows an increase or de crease of the frequency of information you receive depending on the operating conditions of the process being monitored In order to properly set the Abnormal Sampling Rate determine how often updates are needed from the Transmitter when the process being monitored is operating under normal conditions The Transmitter has a selectable range of 1 5 10 15 20 40 seconds and 1 minute Figure 6 7 is an example of how the device switches sampling methods from Nor mal Sampling Rates to Abnormal Sampling Rates Note how the first abnormal sample is taken a few seconds after the Normal Upper Value set point is exceeded The next sample will then follow this sample by 5 seconds or whatever the Abnormal Sampling Rate is set to These samples will continue at this interval until the process value drops be low the Normal Upper Value set point Once the process value drops below this set point the sampling rate will return to the Normal Sampling Rate Also the Abnormal Sam pling must be equal to or faster than the Abnormal Transmission Rate The user should also note that the transmission time depends on the sample rate and when t
32. ange Operation Mode Sensor Offset Sampling Rates Sampling Bands Alarms Upper Limits Use Input 1 Limit Value 0 0 Time Deadband 0 0 Seconds LCD Message BAND1 Percent Sqr At Lower Limits C Use Input 1 Limit This tab allows the user to set the Sampling Bands of the field unit The unit uses Normal sampling transmission rates when the primary values are within the bands When the value is outside of the bands it is considered Abnormal and Abnormal rates are used Load from File Figure 6 15 Normal Upper and Lower Value Selection Using WMT Rev 8 Wireless Differential Pressure Transmitter To configure the Normal and Abnormal Sampling and Transmission menu options using the Wireless Management Toolkit software enter the con figuration menu See Section 9 2 of the Wireless Management Toolkit User Manual Once in the configuration menu click on the Sampling Rates tab to bring up the sampling rate information as shown in Figure 6 14 To select the Normal Transmission Rate select one of the time periods from the drop box Next select an Abnormal Transmission Rate in the same manner Note that the Normal and Abnormal Transmission Rate can be the same Once the transmission rates have been selected the user should select the desired sampling rates Note that the sampling rate must be equal to or faster than the associated transmit rate For example in Figure 6 14 the Normal Transmission Rate is
33. ase Radio i e NO RF all underscore characters will be displayed _______ Ji The RSSI is measured every time the Transmitter receives a message from the Base Radio The signal strength of the received message from the Base Radio is calculated during this time The actual signal strength in dBm for each range is shown below nar 105 dBm amp 100 dBm amp 95 dBm amp 90 dBm amp 85 dBm amp 105 dBm 100 dBm 95 dBm 90 dBm 85 dBm 80 dBm 80 dBm 8 User Manual Rev 8 Honeywell Process Solutions 3 2 1 Continued While using slower baud rate increases communication distance it also increases the minimum transmit rate See Section 5 2 for a list of the fastest transmit rates for each baud rate This may not be suitable for your application 3 2 2 Link Test The Link Test may only be conducted from Transmitters Base Radios and WMT versions 1 7 and higher However a Link Test being run from WMT version 1 7 may test communications with Transmitters older than version 1 7 The version number may only be checked when the Transmitter is powered up See Figure 4 1 Rev 8 Wireless Differential Pressure Transmitter To place the Transmitter in RSSI Diagnostic mode follow the menu map shown in Figure 3 4 Note that the RSSI menu is under the DIAGNSE menu and not the CONFIG menu ee ee ee ee eee 1 i OPERATIONS SEQUENCE Next DIAGNSE Next gt FACTORY NExt ENTER Re Somes
34. ceipt of the shipment inspect the container for any signs of damage in transit Especially take note of any evidence of rough handling Report any apparent damage immediately to the shipping agent Please note that sometimes units are assembled with accessories when shipped Inspect the shipment carefully if you think that something is missing This is rare as we take considerable care to pack units for ship ment but it does sometimes happen Please give us a call and we may be able to resolve this matter quickly over the phone The carrier will not honor any claims for damage unless all shipping ma terials are saved for their examination If you find any damage while you are examining and removing the contents save the packing material and the carton 1 4 SOFTWARE Software for Honeywell is revised periodically Internal device software may contain portions that are not compatible with previous versions of the COMPATIBILITY Wireless Management Toolkit software To ensure software compatibility Wireless Management Toolkit software version 1 70 138 or later must be used If you believe you are experienc ing software compatibility issues please call Honeywell Technical Support at 800 423 9883 or email ACE Honeywell com 2 User Manual Rev 8 Section 2 Quick Start A Warning A Warning If the Transmitters have been running for an extended period of time with no signal from the Base Radio the Base Radio is off or not pre
35. d by other Honeywell Wireless Systems as this can cause com munication problems 18 User Manual Rev 8 Honeywell Process Solutions 5 2 Baud Rate Selection If you change the baud rate of a Transmitter you must also change the baud rate of the Base Radio and all other Transmitters that are communicating with that Base Radio 5 3 RF Identification RF ID Selection Rev 8 Wireless Differential Pressure Transmitter The RF Baud Rate refers to the speed at which the Base Radio and Trans mitters communicate The RF baud rate for the Base Radio and the Trans mitter must be the same in order for successful communication to occur There are three selectable settings with the fastest update times and ranges listed below e 4 8K Rate of 4 8 Kbaud Update every 20 seconds Range of 3000ft Line of Sight e 19 2K Rate of 19 2 Kbaud Update every 5 seconds Range of 2000ft to 2500ft Line of Sight e 76 8K Rate of 76 8 Kbaud Update every 1 second Range of 500ft to 750ft Line of Sight A faster RF Baud Rate allows the user to transmit more information in a given period of time but it will also limit the Transmitter s range If you need more distance out of your Transmitters or are encountering difficul ties by frequently losing communications then select a slower baud rate Follow the Base Radio menu map shown in Figure 5 2 to configure the RF Baud Rate The factory default is the 19 2K Baud Rate es e
36. depends on the sam pling rate and when the process value is sampled If the Normal Sampling Rate is 30 seconds then the process value may be above the Normal Up per Value for up to 29 seconds before an abnormal condition is detected This means that the transmission could be as late as 29 seconds after the process value exceeded the Normal Upper Value The Wireless Management Toolkit software can be used to configure this setting An explanation of how to select the Abnormal Transmission Rate using the Wireless Management Toolkit software can be found in section 6 6 of this manual ee ee ee eee a a oJ NEXT NEXT AMPLING FENTER NORM XR NEXT NEXT CABRECKR Lenten 1 5 SEC 10 SEC 15 SEC 20 SEC 40 SEC 60 SEC Figure 6 6 Menu Map to Abnormal Transmission Rate Setting User Manual 23 Honeywell Process Solutions 6 4 Selecting the Abnormal Sampling Rate If you do not need more or less frequent samples and updates from a Transmitter for a given appli cation then there is no need to complete this sec tion Simply set the Normal Transmission and Sampling Rates to the desired speeds and make sure that the Normal Upper and Lower Values are configured to Disabled Input Volts 10 Abnormal Condition Abnormal Sample Normal Upper Value Normal Sampling Rate of 15 Sec Abnormal Sampling Rate of 5 Sec Normal Upper Value of 2 5 Figure 6 7 Example of Abnormal Sampling Rate
37. e e Type 316 stainless steel diaphragm e Type 316 stainless steel process heads and bolts e DC 200 silicone sensor filling fluid e Weight WD62x 3 7 kg 8 1 Ibs e Lexan cover V O rating and UV stable Operating Vibration and Shock Characteristics e Certified per IEC 60068 2 6 vibration and 2 27 shock Random Vibration Characteristics e Certified to withstand 6 g s 15 minutes per axis from 9 500 Hz Electromagnetic Compatibility CE Compliance e Operates within specification in fields from 80 to 1 000 MHz with Field strengths to 10 V m Meets EN 50082 1 general immunity standard and EN 55011 emissions standard User Manual Rev 8 Honeywell Process Solutions Rev 8 Wireless Differential Pressure Transmitter Certifications e Rated for industrial use 40 F to 185 F 40 C to 85 C e EM and CSA Enclosure Type 4x e FM Approved Intrinsically Safe for Classes I H I Division 1 Groups A B C D E F amp G Class I Zone 0 AEx ia IHC T4 Ta 85 C per 50001377 Class I Division 2 Groups A B C D Suitable for Class II and III Division 2 Groups F amp G Class I Zone 2 AEx nA IC T4 Ta 85 C per 50001377 Enclosure Type 4 e CSA Certified Intrinsically Safe Class I Div 1 Groups A B C amp D Class II Div 1 Groups E F amp G Class III Div 1 Ex ia IIC Class I Zone 0 T4 Ta 85 C Enclosure Type 4 Class I Div 2 Groups A B C amp D Class II Div 2 Groups F amp G Class HI T4 Ta 85 C Enclosu
38. e 3 8 The name of the Transmitter being tested appears in the title bar in parenthesis Wireless Link Test Unit 14041 Configure Test Hours Minutes Seconds Progress 00 00 01 left Piscat Link Quality gt gt gt Figure 3 8 Wireless Data Loss Test Restoring old configuration User Manual Rev 8 Honeywell Process Solutions 3 2 2 3 Continued Rev 8 Wireless Differential Pressure Transmitter In the top of the window you can configure the test to run for a specified amount of time The longer the test the more data the test will have to do an evaluation Type the length of time that you want to run the test and click Begin to start Once the test starts WMT will reconfigure the Transmitter s Transmit Rate to the fastest possible for the selected Baud Rate These rates are listed in Section 5 2 After the test has completed it will restore the previously configured Transmit Rate During the test the communications reliability 1s evaluated while the Transmitter is running under normal operating conditions As the test runs a link strength will be shown in the lower right hand corner of the window gt gt gt gt gt indicates the strongest link while gt indicates the weakest link The Link Test will continue to be evaluated and the rating on the screen may adjust itself for the specified amount of time User Manual 13 Honeywell Process Solutions 3 3 Commissioning 3 3 1 Liquid Service Zero
39. e Sampling and Transmission Rates This section aids the user in selecting the amount of time between each sample of the process and the time between each transmission of this sample to the Base Radio Also discussed is the use of setting an abnormal threshold in which sampling and transmission times may change during a period when the process variable is within the abnormal region Section 7 Configuring the Process Variable This section helps the user to zero the sensor as well as discussing the setting of a measurement offset and trimming the process measurement Section 8 Selecting and Configuring Operation Modes In this section the four operation modes pressure orifice flow open chan nel flow and level of the Differential Pressure Transmitter are discussed in order to aid the user in selecting the right mode for his or her applica tion and properly configuring the Transmitter for that specific application Section 9 Maintaining the Transmitter This section explains how the Transmitter should be cared for once it has been placed into service and how to change the battery Section 10 Technical Specifications This section explains the technical specifications that are associated with this device such as power characteristics accuracy and operating charac teristics Rev 8 User Manual 1 Honeywell Process Solutions Wireless Differential Pressure Transmitter 1 2 ABOUT THE DEVICE The Honeywell Differential Pressure Transmi
40. e applying P ZERO For example if 3 PSI of pressure is applied to a sensor an offset of 5 PSI is entered into the keypad and P ZERO is applied the unit will display 5 PSI If the pressure is then raised by 1 PSI to 4 PSI the unit will display 6 PSI SS ee ee USER PROMPTED FOR PASSWORD NEXT NEXT NEXT ENTER If ENTER is pressed while YES is being displayed the value is F saved lf ENTER is pressed while NO is being displayed the value ENTER is NOT saved When YES is selected the new displayed value ENTER will be equal to the offset Figure 7 3 Menu Map to Pressure Zero Setting Rev 8 User Manual 29 Honeywell Process Solutions Wireless Differential Pressure Transmitter 7 3 Setting a Measurement For various applications the user may wish to display an offset value rather than the actual value To enter an offset navigate to the OFFSET Offset command as shown in Figure 7 4 Then enter the offset to be added or subtracted from the actual measured value ee ee RRA nay oe USER PROMPTED FOR PASSWORD NEXT NEXT NEXT NEXT NEXT ENTER gt INPUT T JENTER CXXXX XX Figure 7 4 Menu Map to Offset Setting The Transmitter interface allows you to set a two point correction curve 7 4 Trimming the for the sensor This process is often called trimming because the dis Measurement played value is trimmed up or down to reflect the actual value being ap plied To set a trim p
41. e information see Section 3 of the Base Ra dio User Manual Place the Base Radio in the desired area and power on Make sure that the Base Radio and Transmitter are on the same RF Chan nel and Baud Rate See Section 5 You may also have to increment the number of Transmitters with which the Base Radio is communicating See the Base Radio User Manual Section 4 3 Once both the Base Radio and Transmitter are set up to be on the same network make sure communication is established by looking at the Trans mitter LCD for the RF OK message in the Read Only Sequence see Section 4 1 1 After communications have been established go to Section 3 2 1 for the RSSI Diagnostic or Section 3 2 2 for the Link Test 3 2 1 Transmitter RSSI Diagnostic The Transmitter should be placed in RSSI Diagnostic mode to determine the signal strength at the location of the equipment to be monitored The RSSI Diagnostic located in the Transmitter s diagnostic menu displays the RF signal strength in one of seven ranges The signal strength ie RSSI Diagnostic cae 2 be etree so is displayed on the LCD using a combination of gt and _ characters DO eye ee ee Full signal strength is displayed as gt gt gt gt gt gt gt while minimum signal version number may only be checked when the j e Transmitter is powered up See Figure 4 1 strength is displayed as gt __ 22 L If the transmitter is not communicating with the B
42. e set to one of 16 different RF channels The only Transmitters recognized by a particular Base Radio are the units that are on the same RF Channel as that Base Radio This allows During installation do not apply force to the in the user to decide which Transmitters communicate with each Base Radio strument housing or antenna Use a proper wrench ee The RF Channel can be thought of as a set of walkie talkies If both tion procedures can cause damage to the Transmit ne walkie talkies are on channel one they can communicate If a walkie talkie is on channel one and the other is on channel two they cannot com municate Likewise if two walkie talkies are on channel one and two other walkie talkies are on channel two the walkie talkies on channel one cannot hear what is being transmitted by the walkie talkies on channel two Warning Each Transmitter comes from the factory with the RF Channel set to OFF This means the Transmitter will not communicate to any Base Radio To set the Transmitter for communication first determine the channel that you want to use Then follow the Transmitter menu map shown in Figure 5 1 to configure the RF Channel Fa m eee 1 i OPERATIONS SEQUENCE NEXT l a ee SEE l USER PROMPTED FOR PASSWORD Figure 5 1 Menu Map to RF Channel Setting Once in the RF Channel menu increment it by pressing the NEXT button When selecting this value do not choose an RF Channel that is currently being use
43. ection 4 Wireless Differential Pressure Transmitter General Configuration This section discusses the generalities for configuring the Transmitter via the NEXT and ENTER buttons The subsections are as follows 4 1 Transmitter Displayed Messages 4 1 1 The Read Only Sequence 4 2 The Overall Configuration Menu Map 4 3 Setting a Transmitter Tag Name 4 4 Setting a User Password 4 5 Resetting All Transmitter Settings 4 1 Transmitter Displayed To turn the Transmitter on press and hold both the NEXT and ENTER buttons for a few seconds Upon power up the Transmitter will display Messages the Power Up Sequence and then go into the Operations Sequence These Sequences are shown in Figure 4 1 below east SS oa TAG MO UNITS POWER UF SEQUENCE pE WOP VER X X eae u ee eee a b and During configuration and testing keep Transmit a ters at least six feet from the Base Radio and other STATUS Transmitters to ensure good communications WORF Saas RF SYNC SEN ERR J RF OK LOW BAT k a Ma i YES hr YES ZRF on gt cfr ROR gt T a a a a h Pai _1_ Pee t i OPERATIONS SEQUENCE H XXX e UNITS ERROR TE s Fh si H in Fa Pa a eae w RF ERR HI SEN ERR LOWY BAT RF OFF w No RF Figure 4 1 Transmitter Power UP and Operations LCD Sequences 4 1 1 The Read Only Sequence Once the Transmitter is in the Operations Sequence a user may access the READ ONLY Sequence without a passw
44. een selected Grams Hr lt g mperial Gal Day mperial Gal Hr mperial Gal Min mperial Gal Sec iters Hr iters Min iters Sec Grans H ALALTATALTS LS 2 9 8 8 35 5 OQI i LTO LY U Rev 8 User Manual 33 Honeywell Process Solutions 8 2 Orifice Flow cont Percent Volume Flow may only be selected from the Flow Units list It does not appear in the Flow list Selecting Percent Volume Flow enables the Square Root Function See section 8 2 1 for more information 8 2 1 Square Root Calculation Differential Pressure Properties 9 44 Sampling Rates Sampling Bands Alarms General Range Operation Mode Sensor Offset Mode Orifice Flow v Flow d Differential Pressure 5 Psi v Flow 10 Cubic Feet Sec v Full Scale Flow Cubic Feet Sec Truncation Point 5 Cubic Feet Sec Flow Units Percent Yol Flow v NOTE Square root is ON Ua Figure 8 3 Orifice Flow with Square Root Calculation Enabled 34 Wireless Differential Pressure Transmitter STD Ft Cubic Ft Min Once engineering units have been selected a 22 point sensor offset curve can be enabled it is disabled upon delivery from the factory by selecting the Sensor Offset tab within the configuration menu When the Transmitter is in Orifice mode a Square Root calculation is performed You have the option to display the Square Root Calculation If th
45. enna type and its gain should be so chosen that the equivalent isotropically radiated power EIRP is not more than that required for successful communication The installer of this radio equipment must ensure that the antenna is located or pointed such that it does not emit RF field in excess of Health Canada limits for the general population consult Safety Code 6 obtainable from Health Canada s website www hc sc gc ca rpb FCC Certification This product is a frequency hopping RF transceiver module for the 900MHz ISM band designed to meet FCC 15 247 and is used in industrial control and moni toring applications The antenna is factory installed and MUST NOT be removed or modified by user Honeywell Process Solutions Copyright 2008 by Honeywell International Inc Rev 8 April 2010 1860 West Rose Garden Lane While this information is presented in good faith and believed to be accurate Honeywell disclaims the implied warranties of merchantability and fitness for a particular purpose and makes no express warranties except as may be stated in its written agreement with and for its customers Phoenix AZ 85027 In no event is Honeywell liable to anyone for any indirect special or consequential damages The information and specifications in this document www honeywell com ps are subject to change without notice Honeywell and TotalPlant are U S registered trademarks Of Honeywell International Inc Other brand or product na
46. ensor Offset EN The password is a four digit password The factory default is 0000 If you asao wish to select a different password one may be entered via the Wireless Management Toolkit software To do so enter the configuration menu See Section 9 2 of the Wireless Management Toolkit User Manual Once in the configuration menu click on the General tab to display the general information as shown in Figure 4 4 Date Installed Comments The Transmitter password for this device can be set by entering a four TERE digit number in the Transmitter Password field Once a password has Monitored Equipment been entered click OK to save and download the password to the Trans Field Unit Password 0000 mitter Please note that the password only protects the Transmitter from unauthor ized configuration via the NEXT and ENTER buttons The Wireless Man agement Toolkit requires a user login password to gain access to all con figuration parameters However user accounts are available and can be set with different access levels and restrictions For more information on user accounts see the Wireless Management Toolkit User Manual Section 8 4 NOTE Device is in Pressure mode and units are in Psi Figure 4 4 Setting a User Password 4 5 Resetting All Transmitter To reset all Transmitter settings to their default state the user must navi Set tings gate to the DEFAULT menu option in the CONFIG menu via the keypad Once at the default m
47. enu option pressing the ENTER button will display RESET on the LCD which asks if you are sure you want to reset the device to its default configuration You will then be prompted with NO on the LCD Pressing the ENTER button while NO is being displayed will NOT reset the device Pressing the NEXT button will display YES Resctune Me Transmitter by use tie DEFAULT on the LCD If you press the ENTER button while YES is being dis menu option will not reset the TRIM or OFFSET ieosd nena Ib t vaes played the device will be reset Rev 8 User Manual 17 Section 5 Configuring the RF Communications In order for the Transmitter and the Base Radio to communicate they must be on the same RF Channel and must be transmitting at the same Baud Rate While all Transmitters and Base Radios are set to default con figurations at the factory if any configuration differences are present the Base Radio will not be able to communicate with the Transmitters The subsections are as follows 5 1 RF Channel Selection 5 2 RF Baud Rate Selection 5 3 RF Identification Selection 5 1 RF Channel Selection The RF Channel defines a set of frequencies on which communication takes place between the Base Radio and the Transmitter Each RF Channel has a different set of frequencies thus allowing the user to have multiple different wireless networks co existing throughout the same facility All Base Radios and Transmitters can b
48. er exit the menus and return to the Operations Sequence The Transmitter should now be successfully configured to the Base Radio To check this press ENTER while the Transmitter is in the Operations Sequence for the Read Only Sequence to be displayed You may see an RF SYNC message displayed on the Transmitter LCD This means that the Transmitter and Base Radio are attempting to synchronize communica tions If this is successful the RF Status will display an RF OK message If this is unsuccessful the RF Status will display a NO RF message Also notice the two small arrows on either side of the LCD if they are fluctuating up and down that indicates the Transmitter and Base Radio are successfully communicating If only one or none of the arrows are moving then RF communication is unsuccessful 20 User Manual Rev 8 Section 6 Wireless Differential Pressure Transmitter Configuring the Sampling and Transmission Rates The Differential Pressure Transmitter is very versatile with many pro grammable features and can be used in numerous different applications Because no two applications are the same some configuration is required for each unit This section will walk you through the initial configuration of these sample and transmit settings The subsections are as follows 6 1 Selecting the Normal Transmission Rate 6 2 Selecting the Normal Sampling Rate 6 3 Selecting the Abnormal Transmission Rate 6 4 Selecting the Abnormal Sampling
49. essure value and a flow value corresponding to the pressure value Enea CBRE S pS Using these two points the PC will calculate the flow value that corre Mode Orifice Flow sponds to the full scale pressure value of the Transmitter 1 e FS Flow Finally the user also must enter a truncation point value This information A is used to calculate flow in the units selected by the user Differential Pressure 5 Psi To set the Transmitter to this operation mode you must go to the configu no ls Cubic Feet 2 Sac ration menu of the Transmitter via the Software For further instructions Full Scale Flow 8 4929 Cubic Feet Sec on getting to the configuration menu see Section 9 2 of the Wireless Man Truncation Point 5 Cubic Feet Sec agement Toolkit User Manual Flow Units Cubic Feet Sec Once you have opened the configuration menu select the Operation Mode tab at the top of the menu and select Orifice Flow from the mode menu You should then see a menu like the one shown in Figure 8 2 Select the units that are appropriate for your application All possible units NOTE Square root is ON are listed below Orifice Flow Units Dis play Characters Barrels Day BBL D Barrels Hr BBL H stints Ee Cubic Feet Hr O TI lt 5 Q C z lt DIDIOIODIOLOIOOTO Ea FIelelclelel l 5 D ClCyEIE ale z15 8 5 2 85 bic Meter Hr NOTE Starred units are only available once the Density check box has b
50. he process variable is sampled If the Normal Sampling Rate is 30 seconds then the process variable may be above the Normal Upper Value for up to 29 seconds before abnormal condi tion is detected This means that the transmission could be as late as 29 seconds after the process variable exceeded the Normal Upper Value The Wireless Management Toolkit software can be used to configure this setting An explanation of how to select the Abnormal Sampling Rate using the Wireless Management Toolkit software can be found in section 6 6 of this manual l OPERATIONS SEQUENCE NEXT a oe oe oe od Srp NEXT ara NEXT AMPLIN ENTER gt NORM XR NEXT NEXT NEXT CABRECSR ENTER 1 5 SEC 10 SEC 15 SEC 20 SEC 30 SEC 60 SEC Figure 6 8 Menu Map to Abnormal Sampling Rate Setting User Manual Rev 8 Honeywell Process Solutions 6 5 Setting the Smart Rate Threshold Differential Pressure Properties 00009044 9 44 Operation Mode Sensor Offset Sampling Bands Alarms General Range Sampling Rates Update Rates Normal Transmit Rate 10 Sec Abnormal Transmit Rate 5 Sec Normal Sampling 1 Sec Abnormal Sampling 1 Sec Smart Smoothing The Smart Smoothing feature rejects noise and glitches by averaging samples within the deadband and ignoring the first sample outside the deadband C Enable Smart Smoothing 1 255 Seconds Percent Sqr Rt SmartR ate The SmartR ate feature causes
51. ifferential Pressure Transmitter samples differential pressure or flow at regular in tervals The data may then be transmitted to the Base Radio for centralized monitoring and data acquisition The user specifies how frequently the process is monitored and how often data is transmitted e Differential Pressure Flow user designates low rate and high rate conditions e Sampling rate user selectable from 1 to 60 seconds low rate and from 1 to 30 seconds high rate e Transmission rate user selectable from 1 second to 60 seconds low and high rate Power Characteristics e Self contained power e C Size 3 6 V lithium battery e Upto five year battery life depends on sample rate and RF update rate field replaceable RF Characteristics e 902 MHz 928 MHz Frequency Hopping Spread Spectrum FHSS FCC certified ISM license free band e Upto 3000 range from Base Radio with clear line of sight 500 to 1000 range with ob structions e The RF module in each transmitter is individually tested and calibrated over the full tem perature range to ensure reliable wireless operation Self Diagnostics Low battery alarm indicates the need to replace the battery approximately one month warning e Contains extensive self checking software and hardware that continuously monitors the operation Any sensor or device parameter out of spec is identified and reported Materials of Construction e Type 304 stainless steel bas
52. ing Using a 3 Valve Manifold Wireless Differential Pressure Transmitter In this section commissioning instructions are discussed for the various setup capabilities of the Differential Pressure Transmitter The subsec tions are as follows 3 3 1 Liquid Service Commissioning Using a 3 Valve Manifold 3 3 2 Liquid Service Zeroing Using a 3 Valve Manifold Be careful when commissioning your transmitter Transient pressure shock waves that can overpressure the sensor causing zero shifts These are most always generated on the upstream side of the instrument By design mini mum zero shift is generated when the transmitter is over pressured on the side Sensors are protected for overpressure on either side to the full pressure rating of the process flanges Differential Pressure Sensors in flow service need to be periodically re zeroed The procedure for re zeroing assumes that the sensor in service and that the line shut off valves are open that the and manifold valves are open and that the manifold bypass valve is closed To then re zero the transmitter use the following procedure L a 3 4 Close the manifold bypass valve The sensor is now in service Open the manifold bypass valve fully Close the Downstream manifold block valve Check the zero output and adjust if necessary If you suspect gas or air in the impulse lines these should be purged Open the Downstream manifold block valve User Manual Rev 8 S
53. ions inches of water at 68 degF inches of mercury at 0 degC feet of water at 68 degF millimeters of water at 68 degF millimeters of mercury at 0 degF pounds per square inch bars Mijtliibare grams per square centimeter kilograms per square centimeter pascals kilopascals Lorricellis atmospheres pounds per square inch absolute feet of water at 4 degC meters of mercury at 0 degC megapascals inches of water at 4 degC millimeters of water at 4 degC a cubic feet per minute gallons per minute liters per minute imperial gallons per minute cubic meter per hour gallons per second million gallons per day liters per second MillionLiterPerDay 25 million liters per day CuFeetPersec CuFeetPerDay CuMeterPersec CuMeterPerDay ImpGalPerHr ImpGalPerDay NormCuMeterPerHr NormLiterPerHr StdCuFtPerMin CuFeetPerHour CuMeterPerMin BarrelPerSec of BarrelPerMin BarrelPerHr BarrelPerDay GalPerHr ImpGalPersec LiterPerHr GalPerDay 26 27 f 28 29 30 ay 121 i22 i23 130 131 132 133 134 135 136 137 138 235 J7 cubic feet per second cubic feet per day cubic meters per second cubic meters per day imperial gallons per hour imperial gallons per day normal cubic meter per hour MKS System normal liter pe
54. is option is enabled it will be displayed as Percent Square Root in WMT and sent to a ModBus Register To display the Square Root Calculation first make sure you have selected Orifice Flow from the mode menu Then from the Flow Units drop down list select Percent Vol Flow If the Density check box is selected then Percent Mass Flow can also be selected from the Flow Units drop down list to show the Square Root Calculation User Manual Rev 8 Honeywell Process Solutions Wireless Differential Pressure Transmitter 8 3 Open Channel Flow This mode lets the user setup flow calculations for open channel flow measurements for weirs In order to make this calculation the user must Differential Pressure Properties 9 44 enter the density of the material a differential pressure value and a match Sampling Rates SamplingBands Alams ing flow value In addition a truncation point value must be entered Fi A nae paseo nally the user must fill out the 22 point curve table indicating the rela Mode Open Channel Flow tionship between column height and flow rate To set the Transmitter to this operation mode you must go to the configu ration menu of the Transmitter via the Software For further instructions on getting to the configuration menu see Section 9 2 of the Wireless Man agement Toolkit User Manual d Differential Pressure 5 Psi Flows 10 Cubic Feet Sec Full Scale Flow 7 213 Cubic Feet 7 Sec Truncati
55. itter to 200 F take 50 F divided by 20 F per foot 2 5 feet of condensate pip ing Drain valves on the vertical portion of the condensate lines are gener ally a good idea to help keep the system clean and free from a build up of sludge 1 Tap into the side of the steam line 2 Run vertical impulse lines to allow the steam to condense and cool Mount the transmitter below the line taps but above the drain valves 3 Fill the impulse lines with water when commissioning the device User Manual Honeywell Process Solutions Wireless Differential Pressure Transmitter 3 2 Testing Communications Remember proper placement of the Transmitter will optimize your RF communication range and capabilities Perhaps the best test to perform before mechanically mounting the unit is a quick hand held test There are two types of tests you can conduct the RSSI Received Signal Strength Indicator Diagnostic and the Link Test The RSSI Diagnostic measures the strength of the signal at the Transmitter The Link Test measures the throughput of data sent to and from the Transmitter The Link Test may be conducted from the Transmitter Base Radio or through WMT The RSSI Diagnostic should be conducted first to determine if the Base Radio is communicating with the Transmitter Then the Link Test may be performed to test the validity of the installation To perform these tests you should have a good idea of where the Base Radio will be placed for mor
56. mes are trademarks of their respective owners Rev 8 User Manual April 2010 Honeywell Process Solutions Wireless Differential Pressure Transmitter About This Document Revision Notes The following list provides notes concerning all revisions of this document 34 XY 25 08 03 05 Initial Release C a pL Reve 08 06 Updated for version 1 70 software release pL Rev 02 08 Updated for new WD6xx models a PL Reve Apr 10 Improvement to Local User Interface LUI Contacts World Wide Web The following lists Honeywell s World Wide Web sites that will be of interest to our industrial automation and control customers Telephone Contact us by telephone at the numbers listed below United States and Canada Honeywell Process Solutions 1 800 423 9883 Sales 1 800 343 0228 Service Global Technical Support Center 1 800 423 9883 Asia Pacific Honeywell Asia Pacific Inc 65 6580 3156 Hong Kong Europe Honeywell PACE 32 0 2728 24 07 Brussels Belgium Latin America Honeywell Inc 805 364 2355 Sunrise Florida U S A II User Manual Rev 8 Honeywell Process Solutions Rev 8 Table of Contents Section 1 Introduction 1 1 Using This Manual 1 2 About the Device 1 3 Unpacking 1 4 Software Compatibility Section 2 Quick Start Section 3 Installation 3 1 Mechanical Installation 3 2 Testing Communications 3 3 Commissioning Section 4 General Configuration 4 1 Transmitter Displayed Messages 4 2 Overall C
57. of these buttons for one second will turn the unit on Pressing the NEXT button at any time while the Transmitter is cycling through the normal messages causes the Transmitter to enter the setup mode The NEXT button is then used to step through menu options and the ENTER button is used to enter a sub menu of what is displayed on the LCD at that time If no button is pressed within a 30 second period the unit goes back to the normal display mode If you enter a sub menu that requires a numerical input such as 001 the left most 0 will be blinking This indicates that pressing the NEXT button will increment this value with each press from 0 to 9 and back to O again Pressing the ENTER button will move to the next available value If the last value is blinking pressing ENTER will save the entered values and return from the sub menu If both the NEXT and ENTER buttons are depressed at once a message on the LCD displaying OFF will appear If both buttons are released upon appearance of this message the user will be returned to the scrolling main screen If both buttons are not released for the duration of the OFF message the unit will power down and turn off Note If the unit is turned off while entering values in a sub menu those values will NOT be saved As shown throughout the document this mark indicates that these menu options will automatically turn off if the Wireless Management Toolkit Software is used All changes to these Transmit
58. oint take the Transmitter offline and navigate to the TRIM menu as shown in Figure 7 5 and select the input to be trimmed Then select the point you wish to enter After selecting the point you will have the option to trim the device or reset the trim If NEW TRIM is selected you will be prompted to enter the lower point first Type the value and ENTER buttons Point 2 MUST be greater than press ENTER The Transmitter will prompt you to apply the indicated Point 1 in order for the trim to work properly process value to the Transmitter Apply the process value and press EN TER Repeat the process for the higher point After both points have been trimmed you can choose to save or discard the new trim If entering a two point trim via the NEXT and LO PNT 0000 00 FENTER gt APPLY _FENTER gt www eww ewww l l l eee pP e es ee l a E EREE ae 3 9 IF YES IS OPERATIONS SEQUENCE LNEXT CONFIG SELECTED NEW ee a li ali alli all aM Ml J ENTER TRIM IS SAVED pete MRS IF NO IS USER PROMPTED POINT IS FOR DISCARDED PASSWORD 4 E ea IF YES IS RESET ever ENTER PRESSED TRIM IS ENTER RESET NEXT NEXT IF NO IS PRESSED NEW NO ENTER TRIM IS CANCELLED NEXT t TRIM ENTER gt INPUT 1 NEXT a Figure 7 5 Menu Map to Trim Setting 30 User Manual Rev 8 Honeywell Process Solutions 7 5 Entering a 22 Point Curve Rev 8 Wireless
59. olutions Wireless Differential Pressure Transmitter Section 1 Introduction 1 1 USING THIS MANUAL This manual is designed to assist in installing operating and maintaining the following Differential Pressure Transmitters Models WD620 WD622 WD624 The manual is broken into sections as follows Section 2 Quick Start This section summarizes what must be done in order to get the device in stalled configured and in operation quickly However it does not provide detailed or how to information to perform the tasks outlined Section 3 Installation This section covers general considerations regarding correctly commis sioning the Transmitter as well as unique applications such a flow service commissioning Also covered in this section are mechanical installation considerations such as Transmitter placement Section 4 General Configuration In this section general configuration options such as password protection and selecting a user password are discussed Also covered is the setting of a Transmitter tag name resetting of all Transmitter settings and a discus sion of the various messages that are displayed on the Transmitter LCD Section 5 Configuring the RF Communications This section covers the setup of the Transmitter RF Communications which allow the Transmitter to achieve communication with the Base Ra dio Parameters discussed are the Transmitter RF ID the RF channel set ting and Baud Rate Section 6 Configuring th
60. on Point 5 Cubic Feet Sec Once you have opened the configuration menu select the Operation eee TEA Mode tab at the top of the menu and select Open Channel Flow from the mode menu You should then see a menu like the one shown in Figure 8 3 Select the units that are appropriate for your application All possible units are listed below Figure 8 4 Open Channel Flow Mode NOTE Square root is OFF NOTE For Open Channel Flow a 22 point curve table must be filled out for correct operation Rev 8 User Manual 35 Honeywell Process Solutions Wireless Differential Pressure Transmitter 8 3 Open Channel Flow cont Once engineering units have been selected a 22 point sensor offset curve must be enabled it is disabled upon delivery from the factory by select ing the Sensor Offset tab within the configuration menu 36 User Manual Rev 8 Honeywell Process Solutions Wireless Differential Pressure Transmitter 8 4 Level In this mode the user has the option of entering the density of material or the full tank pressure Also the user must enter tank height and tank vol Differential Pressure Properties 9 44 ume Finally the user must select level units which can be in units of Sampling Rates SampingBands Alms height volume or mass The entered information is used to make level REEE EE A calculations in the units selected by the user For non uniform tanks the Mode Fluid Level user must also fill out the 2
61. onfiguration Menu Map 4 3 Setting the Transmitter Tag Name 4 4 Setting a User Password 4 5 Resetting All Transmitter Settings Section 5 Configuring the RF Communications 5 1 RF Channel Selection 5 2 RF Baud Rate Selection 5 3 RF Identification Selection Section 6 Configuring the Sampling and Transmission Rates 6 1 Selecting the Normal Transmission Rate 6 2 Selecting the Normal Sampling Rate 6 3 Selecting the Abnormal Transmission Rate 6 4 Selecting the Abnormal Sampling Rate 6 5 Setting the Smart Rate Threshold 6 6 Selecting the Normal Upper and Lower Values 6 7 Selecting Rates Thresholds and Deadbands via the WMT Section 7 Configuring the Process Variable 7 1 Selecting Units of Measure 7 2 Zeroing the Sensor 7 3 Setting a Measurement Offset 7 4 Trimming the Measurement 7 5 Entering a 22 Point Curve Section 8 Selecting and Configuring Operation Modes 8 1 Differential Pressure 8 2 Orifice Flow 8 3 Open Channel Flow 8 4 Level Section 9 Maintaining the Transmitter 9 1 Changing the Battery Section 10 Technical Specifications Appendix A Navigating User Menus Appendix B Displayed Message Definitions Appendix C Transmitter Menu Map Appendix D Modbus Register Definitions Appendix E FM amp CSA Control Drawing ___ User Manual oh BWNN NR Wireless Differential Pressure Transmitter MI Honeywell Process Solutions Wireless Differential Pressure Transmitter IV User Manual Rev 8 Honeywell Process S
62. ord by simply pressing the EN TER button at any time The Read Only Sequence as shown in Figure 4 2 displays extra information about the current settings of the Transmitter that are not seen during the Operations Sequence but does not allow any changes to be made to these settings Figure 4 2 The Read Only Sequence Rev 8 User Manual 15 Honeywell Process Solutions Wireless Differential Pressure Transmitter 4 2 Overall Configuration A complete Transmitter Menu Map 1S shown in Appendix C Below is an M M overall view of the configuration menu to aid the user in setting up the enu vap Transmitter for proper operation is ie NEXT NEXT NEXT DIAGNSE NEXT o FACTORY _NExt C EXIT ENTER USER PROMPTED FOR PASSWORD UF CSET EHD Menus are disabled if use of Wireless NEXT Instrumentation Manager is detected ET TA SAMBUNG enter o NORMIXR NEXT The user must enter a four digit password to enter the CONFIG and DIAGNSE The FACTORY menu is for factory use only The default user password is 0000 For more information on the password see Section 4 4 NEXT jo mim o aio NEXT Figure 4 3 Overall Configuration Menu Map 4 3 Setting the Transmitter Tag Each Transmitter has a user settable Transmitter Tag Name This Tag Name is displayed upon Transmitter power up and when the Read Only Name Sequence is selected The Tag Name is a 21 character string that is dis played
63. ored Notice how the rise in the voltage level falls between two normal samples and thus goes completely undetected Figure 6 3 is an example of what happens when the Normal Sampling Rate is correctly set for the device that is being monitored Notice how this set ting makes it possible to sample the rise in the voltage level The Wireless Management Toolkit software can be used to configure this setting An explanation of how to select the Normal Sampling Rate using the Wireless Management Toolkit software can be found in section 6 7 of this manual a 1 l OPERATIONS SEQUENCE NEXT p ee ee ee ee gt ENTER NEXT Default of 1 Second NORMTSR JENTER 1 5 10 SEC 15 SEC 20 SEC 30 SEC 1 MIN Figure 6 4 Menu Map to Normal Sampling Rate Setting User Manual Rev 8 Honeywell Process Solutions 6 3 Selecting the Abnormal Transmission Rate If the device is not configured to check for abnor mal process conditions using Sample Bands section 6 6 the Abnormal Transmission rate is not used and this section can be ignored Input Volts 10 Abnormal Condition Abnormal Transmission Normal Transmission Normal Upper Normal Transmit Rate of 1 Min Abnormal Transmit Rate of 10 Sec Normal Upper Value of 2 5 Figure 6 5 Example of Abnormal Transmission Rate Setting Rev 8 o U g o w m O Cc m O m a m e Wireless Differential Pressure Transmitter
64. other e The line of sight range between a Transmitter and Base Radio is 2000 feet at the 19 2K baud rate setting Note that this range is reduced by the amount of RF noise present obstructions and the material properties of the obstruction e Only place the Transmitter in ambient operating temperatures of 40 F to 185 F 40 C to 85 C Figure 3 1 gives examples of incorrect setups according to the previously mentioned parameters f 4 1 a ci Q Tranemitters loo close together Outside Base Radio range N Bottom aimed at Base Radio oo great of an bstacle for the distance to Base Radio Obstruction Figure 3 1 Examples of Incorrect Transmitter Positioning Rev 8 User Manual 5 Honeywell Process Solutions Wireless Differential Pressure Transmitter 3 1 1 Continued Because there are so many setup possibilities we cannot cover them all A correct setup would make sure that the above warnings are heeded and that the Transmitter and Base Radio are capable of communication The Testing Communications section will help you to determine if you have selected the correct installation points and orientations for your applica tion 3 1 1 1 Technique for Close Positioning of Transmitters may be placed closely together by carefully following this Transmitters procedure If this procedure is not followed the communication range of the Transmitters will be significantly reduced and the T
65. ow Units GramPerSec 70 grams per second GramPerMin 71 grams per minute GramPerHr 72 grams per hour KGPerSec 73 kilograms per second KGPerMin 74 kilograms per minute KGPerHr 75 kilograms per hour KGPerDay 76 kilograms per day Met TonPerMin 77 metric tons per minute MetTonPerHr 78 metric tons per hour Met TonPerDay 79 metric tons per day PoundsPersec 80 pounds per second PoundsPerMin 81 pounds per minute PoundsPerHr 82 pounds per hour PoundsPerDay 83 pounds per day ShTonPerMin 84 short tons per minute ShTonPerHr 85 short tons per hour ShTonPerDay 66 short tons per day 7 LongTonPerHr 87 long tons per hour LongTonPerDay 68 long tons per day Rev 8 User Manual 47 Honeywell Process Solutions 48 Density Units SGU 90 fe GramPerCuCm 91 75 KGPerCuMeter 92 i PoundsPerGal 03 al PoundsPerCuFt 94 oe GramsPerML 95 o KGPerLiter 96 r GramsPerLiter 97 oe PoundsPerCuIn 98 fe ShTonPerCuYard 99 i DegTwad 100 DegBaumHeavy 102 DegBaumLight 103 y DegAPI 104 Analytical Units Percent 57 ee Special Units SpecialUnits 253 Wireless Differential Pressure Transmitter Specific gravity unite grams per cubic centimeter kilograms per cubic meter pounds per gallon pounds per cubic foot
66. r hour MKS System standard cubic feet per minute US System cubic feet per hour cubic meters per minute barrels per second 1 Barrel 42 US gallons barrels per minute barrels per hour barrels per day gallons per hour imperial gallons per hour liters per hour gallons per day User Manual Rev 8 Honeywell Process Solutions Wireless Differential Pressure Transmitter Volume Units Gallons 40 gallons Liters Al 7 Jiters ImpGallons 42 imperial gallons CuMeters AG cubic meters Barrels 46 barrels Bushels 110 bushels CuYard Sill 7 cubic yarda y CuFeet 112 cubic feet CuInch 113 cubic inches BarrelsLiquid 124 liquid barrels 1 bbl lig 31 5 US gallons at NormalCuMeter 166 normal cubic meter MKS System NormalLiter 167 normal liter MKS System StdCuFeet 168 standard cubic feet US System HectoLiter 236 hectoliters Length Units Feet 44 feet Meters 45 meters Inches s Ay inches CM 46 centimeters MM 49 millimeters FtInSixteenths 151 see Note 1 in HART document HCF_SPEC 183 Mass Units Gram 60 grams KG 61 kilograms MetricTon 62 metric tens y Pound 63 pounds ShortTon 64 short tons 7 LongTon 65 long tons Ounce 125 ounce Mass Fl
67. r is active then the process value is transmitted on the next transmit rate If changes in the process value which exceed the Smart Rate Amount continue to occur the process value is transmitted repeatedly To configure the Smart Rate using the Wireless Management Toolkit software enter the configuration menu See Section 9 2 of the Wireless Management Toolkit User Manual Once in the configuration menu click on the Sampling Rates tab to bring up the sampling rate information as shown in Figure 6 9 To enable the Smart Rate click the check box labeled Enable SmartRate The user will then be allowed to enter a delta or amount changed value which will trigger a transmission Once a value has been entered click OK to save and download the configuration changes to the Transmitter User Manual 25 Honeywell Process Solutions Wireless Differential Pressure Transmitter 6 6 Selecting the Normal Each Transmitter is equipped with an analog input level upper and lower se value As the analog input is measured it is compared to a set threshold Upper and Lower Values value Depending upon the setting of that value whether it is enabled or not and what the Time Deadband 1s the Transmitter will enter an Abnor mal condition as seen in Figure 6 10 Input Normat Upper Value Normal Lower Value A The Normal Upper Value would be an indication that the analog input is Abnormal Condition high and the Normal Lower Value wo
68. ransmitters may eventually lose communication with the Base Radio entirely This procedure is easy to implement but please read carefully for a full understanding The Base Radio synchronizes with the Transmitters in Synch Groups of 7 organized by their RF ID numbers If you want to place two Transmitters closer than 6 feet make sure that you have set them in different groups Note that this only applies to Transmitters that are communicating with the same Base Radio The groups are defined in the following table For example if two Transmitters are placed one foot apart and the first Transmitter has an RF ID number of 027 that means it is in the 4th group 22 28 The second Transmitter must have an RF ID number that is in another group less than 22 or greater than 28 Setting the RF IDs of two closely spaced Transmitters so that the RF ID numbers are greater than 7 apart ensures that the Transmitters are in different Base Radio sync groups This allows the closely spaced Transmitters to properly receive their synchronization signal from the Base Radio and maintain their proper communication and range You can also ensure that closely spaced Transmitters maintain their synchronization with their Base Radio by simply assigning each of the two closely spaced Transmitters to talk to a different Base Radio Either way following this process will keep the Base Radio and Transmitters properly synchronized for long term communication 6
69. re Type 4 Intrinsic Safety Entity Parameters e Maximum operating temperature 85 C e Temperature Class T4 Configuration The Wireless Management Toolkit is required for initial set up and ongoing configuration Options include a 22 point custom curve capability The Wireless Management Toolkit can also be used for monitoring of the process infor mation The user can set thresholds to represent alarm or abnormal conditions A local display provides e Integrated LCD display with membrane switch buttons e Display provides pressure reading and error messages if applicable e Configure RF parameters locally using membrane switch buttons Mounting Bracket When ordered with unit When ordered using Installation Drawings using 34 XY 16 10 Model 34 XY 16 07 Selection Guide Accessory Selection Guide WD620 Table II Selection 30752770 503 50032092 aaSH 50032093 WD622 Table II Selection 30752770 503 50032092 aaSH 50032093 WD624 Table II Selection 30752770 503 50032092 aaSH 50032093 User Manual 4 Honeywell Process Solutions Wireless Differential Pressure Transmitter Dimensions Models WD62x 42 User Manual Rev 8 Appendix A Wireless Differential Pressure Transmitter Navigating User Menus Pressing either the NEXT or ENTER buttons located on the front of the Transmitter or Base Radio just below the Liquid Crystal Display LCD screen is all that is needed to navigate the respective menus Pressing both
70. s data re transmits and better battery life 3 2 2 3 Conducting a Link Test from WMT To conduct a Link Test from WMT make sure that WMT is running on Rev 8 the PC attached to the Base Radio Then go to the Transmitter view and right click on the Transmitter you want to test Received data transmission from Figure 3 7 User Manual 11 Honeywell Process Solutions 3 2 2 3 Continued 12 Wireless Differential Pressure Transmitter py Honeywell Wireless Management Toolkit Connected AHA File View Help Field Units O All Field Units mep Total Field Units 2 O Alarming Field Units alegi 7 A Alarming Field Units 1 2 ee nena Warning Field Units 1 ield Unit Groups O Base Radios 7 Selected Field Unit 9 Field Unit Types Honeywell Dual 4 20 m Input Field Units All Field Units d _TagName Monitored Equipment ID___ Device Type Status Primary amp Secondary Values 00014009 14 009 Temperature RTD ISENSOR FAULT 1 0 Sie oaa 4 l Ra 14 041 Dual 4 20 m Input OK IN1 35 00 m 1 0 Tasks SS View Field Unit Data Configuration Export Data ey Wireless Link Test 7 13 2006 11 12 10 AM Device discovery completed 0 new devices found 0 devices removed Events Chat 2 Total Field Units 1 Alarming Field Unit Figure 3 7 WMT Transmitter View Select Wireless Data Loss Test from the popup menu The Wireless Data Loss Test window appears see Figur
71. s value As previously mentioned the Transmitter is in sleep mode to save power during the operations sequence This mode turns off most of the electronics on the unit with the exception of the LCD in order to preserve battery life The Transmitter will then wake up for every Normal Sampling Period and take the necessary process value readings Notice that the minimum speed of the Normal Sampling Rate is dependent on the Normal Transmission Rate setting selected see Section 6 1 The Sampling Rate cannot be set slower than the Normal Sampling Rate Thus if you selected the Normal Transmit Rate setting to be 10 Seconds the Normal Sampling Rate must be set to 10 Seconds or faster A complete table of these parameters is shown below 500 750 feet 2000 2500 feet 3000 feet 5 Seconds 20 Seconds 20 Seconds or Greater Baud Rate 5 Seconds or In order to properly set the Normal Sampling Rate determine how often updates are needed from the Transmitter when the process being moni tored is operating under normal conditions The Transmitter has a select able range of 1 5 10 15 20 30 and 60 seconds depending on the Normal Transmission Rate The factory default is 1 second However the more frequently the Transmitter wakes up to check the monitored device the faster you will use up the battery life of the Transmitter Figure 6 2 is an example of what happens when the Normal Sampling Rate is too slow for the process being monit
72. set to 10 seconds and the Normal Sampling Rate is set to 1 second This is a valid configuration If the user incorrectly enters the Transmission and Sampling Rates a mes sage will be displayed explaining this to the user The user will not be allowed to leave this screen before the setting is corrected To configure the Normal Upper and Lower Value menu options using the Wireless Management Toolkit software enter the configuration menu See Section 9 2 of the Wireless Management Toolkit User Manual Once in the configuration menu click on the Sampling Bands tab to bring up the sampling band information as shown in Figure 6 15 To set a limit to the normal condition enable the limit by clicking on the Use Input 1 Limit check box Then enter the value and time deadband for the limit User Manual 27 Section 7 Wireless Differential Pressure Transmitter Configuring the Process Variable This section helps the user in the selection of engineering units as well as discussing the setting of a measurement offset and trimming the process measurement The subsections are as follows 7 1 Selecting Units of Measure 7 2 Zeroing the Sensor 7 3 Setting a Measurement Offset 7 4 Trimming the Measurement 7 5 Entering a 22 Point Curve 7 1 Selecting Units of Measure The Transmitter can be used in many different types of applications To accommodate these various options there are various engineering units that can be selected Displa
73. ter menu options should be made through software instead This is to prevent simultaneous changes from taking place If you wish to discontinue use of the software and want these menus re instated you must contact your Honeywell Sales Repre sentative Rev 8 User Manual 43 Appendix B Wireless Differential Pressure Transmitter Transmitter Displayed Message Definitions This section covers the various messages displayed on the Transmitter LCD that occur during operation of the device Operations Sequence e RF Link Status gt RF OK Transmitter and Base Radio are communicating properly gt RF SYNC Transmitter and Base Radio are attempting to synchronize communications RF OFF Transmitter s RF Channel is set to RF OFF NO RF Transmitter and Base Radio have no communica tions e Differential Pressure Input Level gt XX XX Currently measured differential input level gt gt Error Messages If an error is detected with the operation of the Transmitter a message will be displayed on the Transmitter LCD a corresponding message may also appear on the Base Radio LCD There are few types of error messages warning and fatal Warning mes sages are displayed as part of the normal cycling message sequence These are e LOW BAT battery should be replaced as soon as possible e NORF can not detect Base Radio e S FAULT there is an open sensor or excitation wire detected Also if a sensor value goes abo
74. time the word TEST will appear on the LCD display When the test is complete the Transmitter will display the quality of the link Be aware that the Transmitter uses the configured Baud Rate and transmission rate to perform this test The length of time it will take to perform this test is dependent upon how fast the device is normally transmitting When enough messages have been observed a link strength will be shown on the display gt gt gt gt gt indicates the strongest link while gt indicates the weakest link The Link Test will continue to be evaluated and the rating on the screen may adjust itself Keep in mind that the longer the Link Test runs the more data the Transmitter will have to evaluate The Transmitter installation site should strive to place the Transmitter in a location where it receives the highest number possible A stronger link means less data re transmits and better battery life When the Link Test is conducted from a Base Radio it measures the link strength between a selected Transmitter and the Base Radio The Link Test data must be configured to match the communication parameters of the Transmitter from which you want to test The Link Test is located in the Base Radio s diagnostic menu see Figure 3 6 3 2 2 2 Conducting a Link Test from the Base Radio To conduct a Link Test from the Base Radio Navigate to Link Test and press the Enter button Next enter the RF ID for the Transmitter that you want to
75. tter is a reliable Radio Fre quency RF transceiver coupled with a differential pressure sensor that can be used to monitor a variety of processes in hazardous and hard to reach areas The time and expense of running wires often makes it diffi cult to measure parameters that have an economic impact on your plant operation but the Differential Pressure Transmitter allows you to quickly and accurately monitor those devices at a fraction of the cost which gives you bigger and faster returns on your instrumentation investments The Transmitters communicate in a secure digital protocol over a band of frequencies from 902MHz to 928MHz This data communication tech nique has been the backbone of the military s secure communications pro tocols for many years These devices require no wires permits or licenses and they are easily set up and installed right out of the box You can use this device for long term monitoring in remote locations for short term data gathering on process conditions or to quickly test the eco nomic viability of a new installation The purpose of this manual is to help you install and maintain your Hon eywell Differential Pressure Transmitter BEFORE setting up and install ing the Transmitter please setup and configure the Base Radio 1 3 UNPACKING Remove the Packing List and check off the actual equipment received If you have any questions about your shipment please call your Honeywell Representative Upon re
76. tter to the Base Radio at a predefined interval called the Transmit Rate see Section 6 1 Each message contains data for the previous time period since the last transmit The Link Test looks at the wireless performance going in both directions from the Transmitter to the Base Radio and vice versa and comes up with a rating The result that appears on the display shows the determined link strength In order to perform this test the Transmitter must be communicating on the same channel and baud rate as the Base Radio See Section 5 to configure communications The Link Test may be conducted from the Transmitter Base Radio or through WMT Running the Link Test from WMT is ideal for testing communications for an installation with remote or hard to get to Transmitters To conduct the Link Test from a Base Radio see Section 3 2 2 2 To conduct the Link Test from WMT see Section 3 2 2 3 User Manual 9 Honeywell Process Solutions Wireless Differential Pressure Transmitter 3 2 2 1 Conducting a Link Test from the The Link Test is located in the Transmitter s diagnostic menu see Figure Transmitter 3 5 oS a aa NEXT gt gt gt gt gt gt a ao aoe gt gt gt NO LINK Figure 3 5 Menu Map to Transmitter Link Test Using the NEXT and ENTER buttons navigate to Link Test and press the ENTER button to begin the test The Transmitter will begin to test the link in both directions to and from the Base Radio During this
77. ty parameters that meet the above equations system Parameters XYR 5000 and Field Transmitter Vmax Voc or Vt in the USA Imax Isc or It in the USA XYR 5000 Ci Field Transmitter Ci Ccable lt Ca XYR 5000 Li Field Transmitter Li Leable lt La When the electrical parameters of the cable are unknown the following values may be used Capacitance 197pF m 60 pF ft Inductance 0 66uH m 0 020 WH ft For Class I and Class III installations where rigid metal conduit is not used seal cable entries against dust and fibers using a NRTL listed cable gland fitting Control equipment that is connected to Associated apparatus must not use or generate more than 250 V Associated apparatus must be FM ENTITY listed in the USA and CSA Certified under the ENTITY Concept in Canada Associated apparatus may be installed in a Class Division 2 Hazardous Classified location if so approved Non Galvanically isolated apparatus grounded Zener Barriers must be connected to a suitable ground electrode per NFPA 70 Article 504 and 505 in the USA and CEC Part I Section 10 in Canada The resistance of the ground path must be less than 1 0 ohm gt gt gt x D on P Transmitters installed with remote field wiring connections contact closure inputs remote RTD remote thermocouples or 4 20 mA loop shall have the enclosure grounded locally in the hazardous location Shielded two wire cable is required for EMC conformity and is
78. udge and particulates that tend to accumulate in the bottom of the line 1 Tap into the side of the process line 2 Mount the transmitter beside or below the taps 3 Position the vents level with or above the point where the im pulse lines connect to the transmitter This will give the best way to vent all of the air out of the impulse lines and flanges Here you want the impulse lines and manifold to be full of gas Placing the taps in the top of the line generally prevents liquid from entering the transmitter Mounting the transmitter above the process piping allows any liquid or condensate that does form in the impulse lines to drain back into the process piping 1 Tap into the top of the line 2 Mount the transmitter above the taps Steam service is slightly more complex Here you want to tap into the side of the steam lines to keep from collecting sludge and particulates Process steam temperatures almost always exceed the working tempera tures for the differential pressure transmitter To surmount this problem allow the impulse lines to condense and cool the steam by exposing the impulse lines to the general ambient temperature Make the vertical sec tion of the impulse lines long enough to make sure the steam condenses in the impulse lines A good rule of thumb is that each foot of condensate line reduces the temperature by 20 F Example Saturated steam at 15 psig is approximately 250 F To lower the temperature at the transm
79. uld be an indication that analog input is low Thus the normal operating condition for the analog input application would be found in between the two Normal Values Time min sec Abnormal Condition ot Figure 6 10 Normal Upper and Lower Value Example Input Volts Abnormal Condiien Abnormal Cersi Aboornal Candin Abnormal Coord itner A Pua 7 PE MEN J L jer ENDE ERE fe MRA ERIS Jen PT ey me SEE WENT eaa mt a at Tie f Oetaut ts erates mme mt ENS Eo BLED ex xx fENTER aiiai ea r soma Usps Vale Normal Condition commer pons 4 or 0 1 00 200 00 aa aaa Figure 6 11 Menu Map to Normal Upper and Lower Value Settings Figure 6 12 Condition Chatter Without Time Deadband The Time Deadband refers to the number of seconds that the measured reading must stay in a certain condition before the Transmitter will actu ally switch to that condition To select a proper Time Deadband consider the example in Figure 6 12 Input Notice that the Transmitter continues to cycle from Normal to Abnormal ham Conditions due to the fact that the input value is fluctuating around the 7 5 Volt Normal Upper Value This is undesired The addition of a few second i ee delay before the Transmitter switches conditions will eliminate this g E7 chatter as seen in Figure 6 13 4 _ Ne pore P prim Normal Condition or E 0 1 00 2 00 3 00 Time min sec Figure
80. ve below logical limits The unit will display 9999 99 for measurement sensor fault mode but will con tinue sampling and recover if the problem desists e OVERRNG the device is measuring a value above below sensor dependent bound values For example the Analog Input device will report over range if measurement is above 105 range of the Analog Input sensor If the measurement goes above 150 full range the unit will go into Sensor Fault mode In over range mode the measurement is continued to be displayed with the OVERRNG message to re mind the user that the specified range of the sensor and the calibrated range of the device is being exceeded Fatal error messages will replace the normal cycling message sequence and will flash A fatal message indicates the Transmitter is no longer oper ating normally and requires repair These are e RFERR fatal error within RF communications e SEN ERR fatal error within the sensor electronics e SYS ERR fatal error within the microprocessor system e REFCAL fatal error within the RF calibration system 44 User Manual Rev 8 Appendix C Wireless Differential Pressure Transmitter Transmitter Menu Map c m i aye a ae ae es Factory passwords wall be hard READ ONLY nome wr 1 pit ay ales ii coded User password will be reer 2 apis 0000 from factory pm e _ l ENTER amp NEXT AT ANY TIME Default of 19 2K Default of 000 0 9 A Z
81. y Characters Pounds per in2 To select units of measurement follow the Transmitter menu map shown in Figure 7 1 The units are listed on the left The factory default is PSI _ OPERATIONS SEQUENCE NEXT corse Pressure Properties 1 10 Default of PSI Figure 7 1 Menu Map to Units Setting Description If you have the Wireless Management Toolkit software this menu option will not be accessible via the Transmitter once the Transmitter detects that the software is being used See Appendix A for more details The process variable units should be entered using the Wireless Management Toolkit software To do so enter the configuration menu See Section 9 2 of the Wireless Management Toolkit User Manual Once in the configuration menu click on the General tab to bring up the general information as shown in Figure 7 2 Location Date Installed Comments General Monitored Equipment To select the units click the drop down box labeled Input Units Select units you wish to use from the available list Field Unit Password 0000 Units Pressure psi lv Once a valued has been entered click OK to save and download the con figuration changes to the Transmitter Figure 7 2 Units Selection Using Wireless Management Toolkit 28 User Manual Rev 8 Section 7 Wireless Differential Pressure Transmitter 7 2 Zeroing the Sensor Zeroing the sensor can only be performed from the Transmitter

Download Pdf Manuals

image

Related Search

Related Contents

Origin Storage KB-RX215  3.4 - ARIB 一般社団法人 電波産業会  Alpine CDE-9852 Car Stereo System User Manual  Istruzioni per l`uso  Sony HT-SF1200 User's Manual  Manual de instruções VEGABAR 67  Bedienungsanleitung - CONRAD Produktinfo.  User manual  DECOLAV 9720-BLK Instructions / Assembly  HT PV Catalog - Clean Energy Brands  

Copyright © All rights reserved.
Failed to retrieve file