1. GWLIB_POLL_MODE or GWLIB_POLL_COS_ MODE used to send poll requests to this RTU MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 18 MOSCAD RTU Update Interval Enter the frequency in configurable units milliseconds seconds minutes hours at which the values of items will be read polled from this MOSCAD RTU Historical Data Update Interval Enter the frequency in seconds at which the values of specially marked items item point name with suffix h or H will be stored in the historical file see the sections Item Point Naming and Historical File The value is stored only if it has been changed Ping Status Update Interval Enter the frequency in seconds at which this MOSCAD RTU status is requested The RTU status ping command requests this RTU first Table s first Table is from the RTU Types Definition file not Table 1 first element column 0 row 0 Ping request is disabled if value of Ping Status Update Interval is 0 Once all entries have been made click on OK to process the configuration for the Topic The Topic Definition dialog box will appear again SUSPEND Topic On Start Up The MDLC Gateway Server supports the possibility to protect communication from data flow impact at connection start up If SUSPEND checkbox is selected then no poll messages of the topic will be sent State of this SUSPEND Topic On Start Up checkbox is assigned to spec
2. Server Infrastructure does not support using MDLCGATE Server as a Windows Service and remote access to MDLCGATE Server when DDE SuiteLink Client is not located on same computer as MDLCGATE Server To uninstall the MDLCGATE Server start Control Panel select Uninstall a program Add Remove Programs on XP 2003 and select the MDLCGATE SuiteLink and DDE Server from the list of available software products Click on Uninstall Add Remove on XP 2003 and proceed as directed by the Uninstall Wizard Licensing by using HASP HL key The following should be done to enable the licensing by HASP HL key The HASP Device driver and HASP Files are selected during the MDLCGATE Server installation in Custom Setup dialog that causes correspondingly haspdinst exe and hasp_windows_4442 dll files are copied to MDLCGATE Server folder and Sentinel LDK Run time Environment HASP HL Runtime Package is installed and started enabling the MDLCGATE Server can detect the HASP HL USB dongle insert the received HASP key into USB port and wait until Installing device driver software message disappears and Device driver software installed successfully message appears MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 6 start MDLCGATE Server and check if Sofware key or HASP HL key not found message does not appear then it means ev
3. queue will be reseted After setting RESET QUEUE xxx xxx xxx xxx to 1 replies on previous requests are not expected The capacity of write requests queue becomes equal to Max Pending Write Requests see chapter MDLCGATE Gateway Node Settings and capacity of read poll requests queue becomes equal to Max Pending Read Requests Value can be switched to 1 and both queues will be emptied In case of redundant Gateway use only Primary Gateway address in the item name because RESET QUEUE_xxx xxx xxx xxx item belongs to MDLCGATE Gateway node see also Guidelines on Server Performance section READ COUNTER_Xxx xxx xxx xxx Integer Read Only used for monitoring of read poll message queue initial value of this item is Max Pending Read Requests see chapter MDLCGATE Gateway Node Settings Value decrease by each read request sending and increase by answer receiving Value of item represents how many reads can be sent to active Gateway In the reads included active Gateway STATUS message For Gateway STATUS message one position is reserved because it must be sent in its update interval It means that actually amount of reads is Max Pending Read Requests 1 If value of item becomes 1 only Gateway STATUS message can be sent In this case the warning message Read Poll Message Queue is FULL Only GW STATUS can be requested appears in the WWLogger If value of item is 0 read poll queue is full and server waits for answer on sent requests In case of r
4. E mdlegate names txt Browse For topic creation press OK Server will report about successfully created topics number of clones should be equal to Number of Clones configuration value New topics will appear in the Topic Definition window All Topics Done GATEWAYS Modify Delete Update Interval 7 Topic s Update Interval for Multiple Topics The MDLC Gateway Server supports the possibility to enter the new MOSCAD RTU Update Interval value for multiple Topics in a single operation At first these multiple Topics must be selected in the MDLCGATE Topic Definition dialog box by holding the CTRL key while clicking on the selected ones MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 21 All Topic s Gane GATEWAYS RTUOO3 TUS Modify RTU500 SIMULATOR Delete Clone 7 Topic s Then click on Update Interval The UPDATE INTERVAL dialog box will appear UPDATE INTERVAL Ed Change Update Interval for Selected T opic s MOSCAD RTU fis minute s Cancel Enter the new value in the MOSCAD RTU Update Interval field and click on OK to change this value for all selected Topics or click on Cancel The Topic Definition dialog box will appear again The MOSCAD RTU Update Interval can be change also at run time i e when Topics are activated by client application see Guidelines on Serv
5. Gateway fails and if Secondary Gateway status is O K then GMODE_SET_ xxx xxx xxx xxx where XXx XXX XXX XXX is the Secondary MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 15 Gateway IP address value must be switched from 0 to 1 and then Secondary Gateway is changed to Primary 3 The Primary Gateway can be set to Secondary by switching the Discrete item GMODE_SET_ XXX XXX XXX XXX value where XXX XXX XXX XXxx is the Primary Gateway IP address to 0 The Secondary Gateway can be set to Primary by switching the Discrete item GMODE_SET_ xxx xxx xxx xxx value where XXX XXX XXX XXX is the Secondary Gateway IP address to 1 Saving MDLCGATE Configuration File If the configuration file does not currently exist or a new configuration path has been specified the Server will display the Save Configuration dialog box Save Configuration Configuration File Directory C mdlegate Defaults MV Make this the default configuration file This dialog box displays the path where the MDLCGATE Server is going to save the current configuration file The path may be changed if necessary Also the path can optionally be recorded in the WIN INI file by selecting the Make this the default configuration file option Doing so will allow the MDLCGATE Server to find the configuration file automatically each time it is started This option is available only when the configuration
6. NT systems NetDDE extends the standard Windows DDE functionality to include communication over local area networks and through serial ports Network extensions are available to allow DDE links between applications running on different computers connected via networks or modems For example NetDDE supports DDE between applications running on IBM compatible computers connected via LAN or modem and DDE aware applications running on non PC based platforms under operating environments such as VMS and UNIX MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 2 SuiteLink uses a TCP IP based protocol and is designed by Wonderware specifically to meet industrial needs such as data integrity high throughput and easier diagnostics This protocol standard is only supported on Microsoft Windows NT 4 0 or higher SuiteLink is not a replacement for DDE FastDDE or NetDDE The protocol used between a client and a server depends on your network connections and configurations SuiteLink was designed to be the industrial data network distribution standard and provides the following features Value Time Quality VTQ places a time stamp and quality indicator on all data values delivered to VTQ aware clients Extensive diagnostics of the data throughput server loading computer resource consumption and network transport are made accessible through the Microsoft Windows NT operating system Performan
7. Rtutypes cfg is the last in the message end column mb lt gt last mailbox number of poll read message Note Read message disappears when the last item is unadvised Write Message item shows general write message in the following format W T lt gt R lt s gt R lt e gt C lt s gt C lt e gt mb lt gt Where W letter representing the write message T lt gt table number from Rtutypes cfg R lt s gt from which row the message starts start row R lt e gt which row is last in the message end row C lt s gt from which column from Rtutypes cfg the message starts start column C lt e gt which column from Rtutypes cfg is last in the message end column mb lt gt last mailbox number of poll read message Note Write message disappears when reply is received By mouse right button clicking it is possible to access the submenu The submenu contains the following items Log All Sends selects all Log Send treeview items of topics of the current gateway node Log All Receives selects all Log Receive treeview items of topics of the current gateway node Log All Bursts selects all Log Burst treeview items of topics of the current gateway node No Log Sends unselects all Log Send treeview items of topics of the current gateway node No Log Receives unselects all Log Receive treeview items of topics of the current gateway node No Log Bursts unselects all L
8. T2R0 R0 CO CO mb6 where Gateways Nodes and special topic Gateways Initialized Topic Name and Topic ID Log On Shows which type of data Send Receive Burst will be logged Log Off Shows which type of data Send Receive Burst will be not logged Log On or Log Off mode can be set by mouse left button double click on the item These settings are in use if Custom Log menu subitem of Log Send Log Receive menu item is selected in the Server s system menu s Requests STATUS I item shows Gateway Status Poll Message with it s last mailbox number STATUS II item shows Redundant Gateway Status Poll Message if redundant Gateway is configured with it s last mailbox number Ping item shows Topic Ping Status message with its last mailbox number Read Message item shows general read message in the following format R T lt gt R lt s gt R lt e gt C lt s gt C lt e gt mb lt gt Where R letter representing the read message T lt gt table number from Rtutypes cfg R lt s gt from which row the message starts start row R lt e gt which row is the last in the message end row C lt s gt from which column from Rtutypes cfg the message starts start column MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 43 C lt e gt which column from
9. an arbitrary name that will be used by InTouch to refer to the topic For simplicity it is recommended that the name defined for the topic in MDLCGATE Server also be to be used here MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 31 Node Name If the data resides in a network I O Server in the Node Name box type the remote node s name Application Name In the Application Name box type the actual program name for the I O Server program from which the data values will be acquired In case the values are coming from the MDLCGATE Server the MDLCGATE is used Do not enter the exe extension portion of the program name Topic Name Enter the name defined for the topic in the MDLCGATE Server to identify the topic the MDLCGATE Server will be accessing The Topic Name is an application specific sub group of data elements In the case of data coming from a MDLCGATE Server program the topic name is the exact same name configured for the topic in the MDLCGATE Server Note This will usually be the same as the Access Name although if desired they may be different However it must be the same name used when the topics were configured in section Configuring the MDLCGATE Server Which protocol to use Select the protocol DDE or SuiteLink that you are using When to advise server Select Advise all items if you want the Server program to poll for all data whether or not it i
10. file path is changed Configuration File Location When the MDLCGATE Server starts up it first attempts to locate its configuration file by first checking the WIN INI file for a path that was previously specified If the path is not present in the WIN INI file the Server will assume that the current working directory is to be used To start the Server from an application directory configuration file other than the default configuration file a special switch d is used For example invoke the File Run command and enter the following MDLCGATE d c directoryname Note There is no limit to the number of configuration files that may be created although each must be in a separate directory MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 16 Topic Definition Command The user provides each MOSCAD Remote Terminal Unit with an arbitrary name that is used as the topic for all references to the RTU More than one Topic can be defined for the same RTU To define the Topics MOSCAD RTUs attached to one or more MDLC Gateways invoke the Configure Topic Definition command The Topic Definition dialog box will appear Topic Definition All Topic s Modify Delete Clone Update Interval 1 Topic s To modify or examine an existing topic select the topic name and click on Modify To define a new topic click on New The MDLCGATE Topic Defi
11. is capable of acting as a DDE FastDDE or SuiteLink Client may use the MDLCGATE Server Communication Protocols Dynamic Data Exchange DDE is a communication protocol developed by Microsoft to allow applications in the Windows environment to send receive data and instructions to from each other It implements a client server relationship between two concurrently running applications The server application provides the data and accepts requests from any other application interested in its data Requesting applications are called clients Some applications such as Wonderware InTouch and Microsoft Excel can simultaneously be both a client and a server FastDDE provides a means of packing many proprietary Wonderware DDE messages into a single Microsoft DDE message This packing improves efficiency and performance by reducing the total number of DDE transactions required between a client and a server Although Wonderware s FastDDE has extended the usefulness of DDE for our industry this extension is being pushed to its performance constraints in distributed environments The MDLCGATE Server supports the FastDDE Version 3 an extension to Wonderware s proprietary FastDDE Version 2 This extension supports the transfer of Value Time Quality VTQ information The original DDE and FastDDE Version 2 formats are still supported providing full backward compatibility with older DDE clients FastDDE Version 3 works on Windows 9x systems as well as Windows
12. proceed as directed by the UnInstallShield program Note The I O Server Infrastructure installation will be rejected if Wonderware FS2000 Common Components are already installed on same computer The I O Server Infrastructure does not support using MDLCGATE Server as a Windows Service and remote access to MDLCGATE Server when DDE SuiteLink Client is not located on same computer as MDLCGATE Server Configuring the MDLCGATE Server After the MDLCGATE Server is initially installed a small amount of configuration is required Configuring the Server automatically creates a MDLCGATE CFG file that holds all of the Gateway Node and Topic definitions entered This file will automatically be placed in the same directory in which the MDLCGATE Server is located unless the path where the configuration file will be placed is specified via the Configure Server Settings command To perform the required configurations start up the MDLCGATE Server If the Server starts up as an icon double click on the icon to open the Server s window The following will appear Z MDLCGATE Of x Configure Help To access the commands used for the various configurations open the Configure menu F MDLCGATE Jol x ieee Help Gateway Node Definition Topic Definition Server Settings MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 10 Note The Configure Topic Defin
13. topic GATEWAYS items READ _COUNTER_xxx xxx xxx xxx does no become equal to Max Pending Read Request or WRITE_COUNTER_Xxx xxx xxx xxx and does not become equal to Max Pending Write Request see chapter MDLCGATE Gateway Node Settings and chapter Item Point Naming It means that servers performance is reduced less and less pending request can be sent after each non answered request because Server waits FOREVER answer on the sent request except Gateway Status message RESET _READS_xXxx xxx xxx xxx item For special topic GATEWAYS one additional item RESET READS_xxx xxx xxx Xxx where xxx xxx xxx xxx is the IP address of the Primary Gateway of the node can be used This is a Read Write discrete item If this item value is changed from 0 to 1 then only read part of queue will be reseted After setting RESET READS_ xxx xxx xxx xxx to 1 replies on previous poll requests are not expected and READ _COUNTER_Xxx xxx xxx xxx becomes equal to current Gateway Node Max Pending Read Requests parameter value see chapter MDLCGATE Gateway Node Settings RESET WRITES _ xxx xxx xxx xxx item For special topic GATEWAYS one additional item RESET _WRITES_ xxx xxx xxx xxx where Xxx XxXxx XXxX xXxx is the IP address of the Primary Gateway of the node can be used This is a Read Write discrete item If this item value is changed from 0 to 1 then only write part of queue will be reseted After setting RESET WRITES _ xxx xxx xxx xxx to 1 r
14. 00 0000 Transfer Software Key Cancel 3 Take the screenshot from ArchestrA SMC Logger or MDLCGATE Internal Log file window containing the Software License Key removal message like below MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 8 Message Details x No t 58090684 Date Time 2014 05 11 08 44 Pro 102 Le Software Key 76e4 909 8f10 9514 removed PC Code 2496 c475 8b8b 6291 Product Code DR21010 120 or take the string with Software License Key removal message directly from ArchestrA SMC Logger or MDLCGATE Internal Log file like following Software Key 76e4 e909 8f10 9514 removed PC Code 2496 c475 8b8b 6291 Product Code DR21010 120 Provide the obtained Software License Key removal message screenshot or string together with new Customer PC Code when applying for new Software License Key without purchasing the new license in situations when it is necessary to move Klinkmann software to other computer or operation system change is planned Note Without providing the Software License Key removal message screenshot or string the new Software License Key will not be assigned Starting the MDLCGATE Server The Server can be started in some different ways 1 At MS Windows startup from Startup group 2 Manually before client Wonderware InTouch MS Excel startup 3 When star
15. DE Configuration File Directory Specify the path disk drive and directory in which MDLCGATE Server will save its current configuration file MDLCGATE Server will use this path to load the configuration file the next time it is started Note Only the path may be modified with this field The configuration file is always named MDLCGATE CFG Note There is no limit to the number of configuration files created although each must be in a separate directory When using the MDLCGATE Server with InTouch it is good practice to place the configuration file in the application directory Once all entries have been made click on OK MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 11 Gateway Node Definition Command To configure the MDLC Gateway Node invoke the Configure Gateway Node Definition command The MDLCGATE Gateway Node Settings first dialog box will appear MDLCGATE Gateway Node Settings MDLCGATE Gateway Nodes To modify or examine an existing Gateway Node select the Node name and click on Modify To define a new Gateway Node click on New The MDLCGATE Gateway Node Settings second dialog box will appear The following is an example of MDLCGATE Gateway Node Settings dialog box where the default configuration is entered single Primary Gateway no Hot Standby Gateway Node Name No i i CS C S Computer Internet Address pooo M Use Default Prim
16. LINKMANN AUTOMATION MDLC Gateway DDE Server ReMDLCGATE History First Release Hot Standby Principles of Operation section added Guidelines on Server Performance section added Installing and starting the MDLCGATE Server section modified Gateway Node Definition Command section modified Topic Definition Command section modified Historical File section modified Item Point Naming section modified Manual file name changed Minor changes Changes in Item Point Names section added Topic Definition Command section modified Troubleshooting Menu section modified Troubleshooting section modified Topic Definition Command section modified Guidelines on server performance section modified Item point naming section modified Item point naming section modified Gateway Node Definition Command section modified Communication Protocols section modified Other minor changes Suite Link support added Max Pending Read and Write Requests added in MDLCGATE Gateway Node Settings dialog Installation from CD information added Installing and starting the MDLCGATE Server section modified Licensing by using HASP HL key and Software license key sub sections added MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110
17. MDLC Gateway Communication Server for Microsoft Windows and InTouch Applications User Manual Ver 1 x Rev 1 10 DR 21010 KLINKMANN AUTOMATION P O Box 38 FIN 00371 Helsinki Finland tel int 358 9 5404940 fax int 358 9 5413541 www klinkmann com Klinkmann Automation MDLC Gateway Communication Server i Table Of Contents OVGINIOW aae a E a a a E A E ot 1 Communication Protocols ccc stents cites that cntdandtinttcaiicee adress eedate tet adcad i dediaaed td cedddebtauide 1 Accessing a Remote Items via MDLCGATE Servet ceeceeeeceeeeeeeeeeeeeeeeeeesentneeeeeeeees 2 Installing and starting the MDLCGATE Servet ccccccceeeesseeeecceeeeeeeeeeeeesnneeeeeeeeees 3 Installing the SERV siena aa a EE a Aa EAS 3 Licensing by using HASP HL key cccccceeceeeeeeeeneeeeeeeeeeeeeeeecaeeeeeeeeeeeeeeeeeaaees 5 Software license key cccccceeeeeeeeeeeeeeeeeeeeeeeeeeeseeaaaeaeeeeeeeeeeeeeceaeaeeeeeeeeeeenees 6 Transferring the software license to other COMPUtEL ccceeeeeeeeeeeeeteeeeeeeees 7 Starting the MDEGGATE SQrve licgcees iets toes sada cics totes vasvodaaucs duds constucarvesdelacuenisestwentecs 8 Installing the I O Server Infrastructure cccceeeeeeeeeeeeeeceeeeeeeeeeeeeeneeeeeeeeeees 9 Configuring the MDLCGATE Servet ccccceeceeeeeneeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeecenaeeeeeeeeeeeeeee 9 Server Settings COMMANG esses tctaee ce eat alah aate habia tesa tanta San
18. ON 1 0 Definition of RTU Types Number_of_Types 3 Type_name No_of_tables Type Pump 3 Table_no N_cols Col_0 Col_1 Col_2 Col_3 Col_4 Col_5 Col_6 Col_7 Table 0 5 Bit Bit Bit Bit Bit Table 2 8 C Bit C_Bit C_Bit C_Bit C_BitC_Bit C_Bit C Bit Table 3 3 Float Val Bit Type_name No_of_tables Type Valve 1 Table_no N_cols Col_0 Col_1 Col_2 Col_3 Col_4 Col_5 Col_6 Col_7 Table 10 3 Float Val Bit Type_name No_of_tables Type PoleTop 1 Table_no N_cols Col_0 Col_1 Col_2 Col_3 Col_4 Col_5 Col_6 Col_7 Table 1 1 Bit MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 46 MOSCAD System Definition In the MOSCAD System Definition file the association of RTU RTU Type is defined Each RTU defined by its Site_id is assigned an RTU Type defined in the RTU Types Definition file The file is case insensitive File_ Type SYSTEM Version XXX Site_id Type name Example MOSCAD System File Version FILE _TYPE SYSTEM VERSION 1 0 f No of RTUs N_RTU 4 Site_id Type_name RTU 1 Pump RTU 2 Pump RTU 3 PoleTop RTU 4 Valve MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 47 Sep 96 Nov 96 Dec 96 Feb 97 Sep 97 Oct 97 Oct 98 Mar 2000 Apr 2000 Mar 2002 Jun 2014 Rev 1 0 Rev 1 1 Rev 1 2 Rev 1 3 Rev 1 4 Rev 1 5 Rev 1 6 Rev 1 7 Rev 1 8 Rev 1 9 Rev 1 10 K
19. URN Marks the end of the macro The following is an example of Excel macro used to poke value from cell B2 to topic RTU1 item T1CORO PokeMacro Ctrl a INITIATE MDLCGATE RTU1 POKE A2 T1C0RO B2 ON TIME NOW 0 01 TerminateDDEChannel RETURN TerminateDDEChannel TERMINATE A2 RETURN Note Refer to the Microsoft Excel manual for complete details on entering Remote Reference formulas for cells Troubleshooting WIN INI entries The first time you run the MDLCGATE Server configuration most of the items in the following list will automatically appear in the WIN INI file It is usually in the C WINDOWS directory It is an ASCII file and can be altered manually if you wish with any text editor e g MS Windows Notepad do not use a program that formats text such as MS Word or Write unless the file is saved as DOS text The following is a typical entry for the MDLCGATE Server MDLCGATE ProtocolTimer 50 Protocol Timer Tick ConfigurationFile C MDLCGATE Configuration File Path Winlconic 0 Server starts up minimized if 1 WinFullScreen 0 Server starts up maximized if 1 WinTop 112 Position and size of Server s window at Server startup if not minimized or WinLeft 0 maximized WinWidth 200 WinHeight 168 DebugMenu 1 Show Troubleshooting menu if 1 ShowSend 0 ShowSend is checked if 1 ShowReceive 0 ShowReceive is checked if 1 ShowErrors 1 ShowErrors is checked if 1 DumpScreen 0 DumpScreen i
20. _ xxx xxx xxx xxx Integer Read Only used for storing of return values from MDLC Gateway API functions gwlib_poll gwlib_send_data gwlib_send_command gwlib_set_time gwlib_get_time RECEIVE_ERROR _ xxx xxx xxx xxx Integer Read Only used for storing of return values from MDLC Gateway API functions gwlib_receive_bufferl gwlib_get_message DUMP Discrete all information about gateway nodes topics messages and data items are logged This can be used to find out how many messages are actually sent to the network Example GS_LSB_192 17 33 160 Integer Read Only used for storing of Gateway mode indication for the Gateway with IP address 192 17 33 160 2 The special items points which can be created for each topic RTU POLL_NOW Discrete used for immediately one time polling of all active items see Guidelines on Server Performance section this one time polling is performed when POLL NOW value switches from 0 to 1 no effect when switches from 1 to 0 UPDATE_INTERVAL Integer used for run time changing of MOSCAD RTU Update Interval for this Topic see Guidelines on Server Performance section SET_TIME Discrete used for downloading of Server date and time by calling gwlib_set_time to a specified RTU GET_TIME Discrete used for uploading of a specified RTU date and time the date and time request by calling MDLC Gateway API function gwlib_get_time is sent when GET_TIME value switches from 0 to 1 no ef
21. ary Gateway IP Address fs2168013 GecondayGatewaylPAddess onoo NotUsed Reply Timeout 10 sec Gateway Status Update Interval 30 sec Max Pending Read Requests oe Max Pending Write Requests 5 _ Automatic Hot Standby Topic s The following describes each dialog field in this dialog box Gateway Node Name Enter the Gateway Node name and later use it in Topic Definition MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 12 Computer Internet Address Enter the Computer Internet Address IP Address if it has more than one If there is only one Internet Address for computer then Use Default can be checked to use this Address If Computer is multi homed more than one Internet Address used and Use Default is checked then it is impossible to know which Address must be used Primary Gateway IP Address Enter the Primary Gateway Internet Address IP Address Secondary Gateway IP Address Enter the Secondary Gateway Internet Address IP Address If Not Used is checked then Secondary Gateway is not used for this Gateway Node Reply Timeout Enter the reply timeout value in seconds for the TCP IP communications this value is used as a timeout parameter for the MDLC Gateway API function gwlib_receive_buffer Gateway Status Update Interval Enter the interval in seconds at which the Gateway status both for the Primary and Secondary Gateways wil
22. ation for all Gateway Nodes has been performed Note If this is the first time the Gateway Nodes have been configured the user will be prompted to save configuration to an existing directory MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 14 Hot Standby Principles of Operation The MDLC Gateway redundancy is supported as an option to increase the reliability of the system Two MDLC Gateways can be configured in a Primary Secondary mode If Primary Gateway is not available then Secondary Gateway can be used Each Gateway has to be configured with unique IP address Also redundant Hosts computers with MDLC Gateway Server running and redundant MDLC and LAN communication devices can be used The following are examples of possible configurations 1 A single Primary Gateway with a single Host No MDLC Gateway redundancy No MDLC Gateway Server redundancy the Server is running only on one computer 2 A single Primary Gateway with multiple Hosts No MDLC Gateway redundancy The redundant MDLC Gateway Servers are used the Server is running on multiple computers and if some of them fail then data from RTUs can sill be accessed by other ones 3 Dual redundant Primary Secondary Gateway with a single Host The MDLC Gateway redundancy supported no MDLC Gateway Server redundancy 4 Dual redundant Primary Secondary Gateway with multiple Hosts The MDLC Gateway redundancy suppor
23. ce Monitor This feature is critical for the scheme and maintenance of distributed industrial networks Consistent high data volumes can be maintained between applications regardless if the applications are on a single node or distributed over a large node count The network transport protocol is TCP IP using Microsoft s standard WinSock interface The Suite Link FastDDE Version 3 and DDE support for MDLCGATE Server is implemented by Wonderware I O Server Toolkit ver 7 2 1 6 Accessing a Remote Items via MDLCGATE Server The communication protocol addresses an element of data in a conversation that uses a three part naming convention that includes the application name topic name and item name The following briefly describes each portion of this naming convention application name The name of the Windows program Server that will be accessing the data element In the case of data coming from or going to MOSCAD RTUs the application portion of the address is MDLCGATE topic name Meaningful names are configured in the Server to identify specific devices These names are then used as the topic name in all conversations to that device For example Node1 The MDLCGATE Server considers each MOSCAD RTU to be a separate topic Note You can define multiple topic names for the same RTU to poll different items at different rates item name Item is a specific data element within the specified topic For the MDLCGATE Server an item ca
24. cense key entered the MDLCGATE Server will run one hour in demo mode After purchasing the MDLCGATE Server the appropriate HASP key or software license key is provided and no re installation of MDLCGATE Server is needed In case HASP Device driver and HASP Files are not selected then HASP USB key will not be supported and only the software license will be available files needed for HASP USB key will not be installed ji MDLCGATE SuiteLink and DDE Server Setup ioj xj Select the way you want features to be installed Click the icons in the tree below to change the way features will be installed Sentinel LDK Run time Environment X HASP Files HASP HL Runtime Package This feature requires OKB on your hard drive MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 4 In case HASP Device driver and HASP Files are selected then HASP USB key will be supported and both HASP key and software license will be available files needed for HASP USB key will be installed ji MDLCGATE SuiteLink and DDE Server Setup O x custom setup Select the way you want features to be installed Click the icons in the tree below to change the way features will be installed Sentinel LDK Run time Environment HASP HL Runtime Package This feature requires 14MB on your hard drive Location C Program File
25. control the range of values that will be accepted from the Server and how the values are scaled If no scaling is desired Min EU should be equal to Min Raw and Max EU equal to Max Raw Enter the MDLCGATE item name to be associated with this tagname in the Item field in the Details box MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 34 Initial Value jo Min EU 32768 Mas EU 32767 Deadband O Min Raw 32768 Max Raw 32767 i Conversion Eng Units sie Sie Linear 4 RTUTI C Square Root ltem TICORO M Use Tagname as Item Name flog Destband co Refer to the Item Names section for complete details Where applicable the Use Tagname as Item Name option may be selected to enter automatically the tag name in this field Note The tag name can only be used if it follows the conventions listed in the Item Names section Once all entries have been made click on the Save button in the top dialogue box to accept the new tag name To define additional tagnames click on the New button To return to the WindowMaker main screen select Close Monitoring the Status of Communication with InTouch InTouch supports built in topic names called DDEStatus and lOStatus that are used to monitor the status of communications between the Server and InTouch For more information on the built in topic names DDEStatus and OStatus see your online InTouch Use
26. edundant Gateway use only Primary Gateway address in the item name because READ_COUNTER _ xxx xxx xxx xxx item belongs to MDLCGATE Gateway node WRITE_COUNTER_Xxx xxx xxx xxx Integer Read Only used for monitoring of write message queue initial value of this item is Max Pending Write Requests see chapter MDLCGATE Gateway Node Settings Value decreases by each write request sending and increase by answer receiving Value of item represents how many writes can be sent to Gateway If value of item is 0 write queue is full and server waits for answer on sent requests In this case the warning message Write Pending Message Queue is FULL appears in the WWLogger In case of redundant Gateway use only Primary Gateway address in the item name because WRITE_COUNTER_xxx xxx xxx xxx item belongs to MDLCGATE Gateway node GS_LSB_xxx xxx xxx xxx Integer Read Only used for storing of two LSBytes with Gateway mode indications GS_MSB_ xxx xxx xxx xxx Integer Read Only used for storing of two MSBytes with Error and Warning indications MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 28 GMODE_SET_xxx xxx xxx xxx Discrete used for setting of the Gateway operation mode when switched from 0 to 1 then MDLC Gateway API function gwlib_set_mode is called with mode set to GWLIB_PRIMARY_MODE if switched from 1 to 0 then called with mode set to GWLIB_ SECONDARY_MODE SEND_ERROR
27. eplies on previous write requests are not expected and WRITE_COUNTER_Xxxx xxx xxx xxx becomes equal to current Gateway Node Max Pending Write Requests value see chapter MDLCGATE Gateway Node Settings SUSPEND item Discrete Read Write item Very important and usable possibility against wavelike data flow impact This item gives control on data exchanging The initial value of the SUSPEND item the MDLCGATE Server takes from the SUSPEND Topic On Start Up checkbox see chapter MDLCGATE Topic Definition If value of item is 0 reads polls executes in general way If SUSPEND item value becomes 1 only writes of this topic will be executed Read poll requests can be executed only by item POLL_NOW using MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 24 POLL_NOW item The Server supports Discrete Write Only item POLL_NOW used for immediately one time polling of all active items from some RTU This one time polling can be used when MOSCAD RTU Update Interval value has been changed at run time and it is necessary to receive fresh data from RTU before previous MOSCAD RTU Update Interval is elapsed At start up the value of the POLL_NOW item is 0 The Server issued all poll messages of corresponding topic when value of item changes from 0 to 1 The changing of POLL_NOW value from 1 to 0 does not take effect Note The Server does not change resets value from 1 to 0 This reset operation
28. er Performance section Select Done when configuration for all MOSCAD RTUs has been performed MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 22 Guidelines on Server Performance Depending on the complexity of the MOSCAD environment where the MDLC Gateway Server is used the following guidelines should help to achieve the optimum Server performance Update Intervals The optimum usage of Update Intervals is very important There are three Update Intervals listed according to their priority which greatly affect the performance of the Server 1 Gateway Status Update Interval 2 Ping Status Update Interval 3 MOSCAD RTU Update Interval If Gateway Status and Ping Status Update Intervals are very short less than one second or for very complex systems less than ten seconds and also data from RTUs are requested very often MOSCAD RTU Update Intervals also are some seconds then it is very possible that there is not enough time to execute all poll requests 20 60 seconds could be a reasonable value for Gateway Status and Ping Status Update Interval in not too complex systems Gateway Status poll and RTU Ping are intended for error detection Theoretically one poll should be equal up to three RTU Ping and up to ten Gateway Status Intervals because it gives some time to Server for error processing It should protect the server from useless polling reading and writin
29. erver 40 Custom Log No Logging Show Receive Log All Data 3 For PING of topic poll message in the following format lt lt Topic Name gt PING gt where lt Topic Name gt name of sender topic lt size of request gt size of request in bytes lt gt number of mailbox for request and reply lt request in hexadecimal format gt hexadecimal queue of the request For example the Gateway Status request number 144 for node Node2 Poll mailbox 144 Node2 GW STATUS size 36 00 01 7F FD 00 00 Each next string of log if such is necessary has the following format lt type of request gt lt request in hexadecimal format gt where lt type of request gt Poll or Write type same as in the first string of the log lt request in hexadecimal format gt continuation of the hexadecimal queue of the request For example Poll 00 00 00 00 messages will be logged to the WWLogger corresponding to settings in the Server s main window no messages will be logged to the WWLogger When the Server starts the default selection is No Logging This default value can be changed by settings in the WIN INI file Subitems has the following values Log All Data 1 Custom Log 2 No Logging 0 The following is an example for Log All Data subitem selection in the Server s system menu MDLCGATE LogSend 1 this system menu item is provided for organizing of received package logging to t
30. erything is done correctly and MDLCGATE Server runs in full mode with licensing by HASP HL key enabled Software license key MDLCGATE Server supports the computer dependent software licensing The following steps are required to enable it 1 Start MDLCGATE Server click on Help menu item also short cut Alt H can be used and pop up menu with Help menu commands will appear Select License and License dialog will appear x Product Code pR21 010120 Customer PC Code 2496 0475 8b8b 6251 Transfer Software Key Cancel 2 Here the Customer PC Code is computer dependent string generated by MDLCGATE Server and it is unique for this computer Write it down or Copy Paste to e mail when ordering the MDLCGATE Server 3 After purchasing the MDLCGATE Server you will get the software license key 16 character alphanumeric string Open the License dialog again and Copy Paste it to Software Key field x Product Code DR21 010120 Customer PC Code 2496 0475 8b8b 6251 Transfer Software Key 96e1 e9D9 8f20 981d Cancel 4 Click OK and restart MDLCGATE Server MDLCGATE Server software license now is enabled Note the Software Key string is saved to MS Windows system directory e g C Windows WIN INI file MDLCGATE section to enable it is automatically detected at MDLCGATE Server next start up MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Kl
31. eue of requests will be empty and Server can send the total amount of poll Max Pending Read Requests or default value 20 and write requests Max Pending Write Requests or default value 5 MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 26 Item Point Naming The MDLC Gateway Server item point naming is based on information contained in the RTU Types Definition file The item point name generally may be described as TzCxRy TSn b h where z table number x number of column starting from 0 in the table y number of row starting from 0 in the table TSn used only if data type is Timestamp1 and Timestamp2 n can be 1 or 2 for these items the corresponding element type in the RTU Types Definition file must be float b optionally used address of bit if data type is Compressed Bits and only one bit must be accessed h or H optionally used suffix indicating that this item value will be stored in the historical file Examples T1C2RO0 Column 2 Row 0 in Table 1 T1C2R5h Column 2 Row 5 in Table 1 values will be stored in the historical file T12C0R1 4 bit 4 in Column 0 Row 1 in Table 12 T12COR1 4H bit 4 in Column O R1 in Table 12 values will be stored in the historical file T1C2ROTS1 Column 2 Row 0 in Table 1 data type is Timestamp1 The following item types are supported Item Type Value Range Bit Discrete Bit in Compressed Bits D
32. f MultiWrite is 1 Can be used in cases when it is necessary to see that general poll issue is missed Parameter has two valid values 0 Off 1 On Default parameter value is 0 If above described situation presents then warning message should appear in the WWLogger file For example 98 07 09 09 30 00 227 MDLCGATE GW node Node2 Topic RTU01 Table 1 21010m110 Klinkmann Automation MDLC Gateway Communication Server 38 WarningOnPollDelay 5 DelayBetweenPolls 600 FirstBadTryMsgBox 0 MDLCGATE Server Ver1 x User Manual Rev 1 10 Missed Poll Issue during Update Interval 900 seconds Can be used in cases when it is necessary to see that general poll issue is not missed yet but only delayed some time Valid values of parameter are between 0 and 86400 seconds No message will be logged if value is 0 Default this parameter value is 0 If above string is included then warning message should appear in the WWLogger file For example 98 07 09 09 15 05 215 MDLCGATE GW node Node2 Topic RTU01 Table 1 Poll issue delay is 5 seconds The possibility to configure special poll mode Value can be from 0 to 86400 seconds Value 0 of this parameter means that general polling mode is used and poll execution depends on update interval Non zero value defines time interval in seconds between STARTINGS of each consecutively processed topic polling not between last request of currently processed topic and the first request of the ne
33. fect when switches from 1 to 0 the result is stored in the item DATE_TIME DATE_TIME Message Read Only used for storing of character string containing the specified RTU date and time in the following format YY MM DD hh mm ss where YY is year MM month DD day hh hours mm minutes and ss seconds SUSPEND Discrete Read Write used for suspending of poll messages of topic value 0 allows poll message sending but value 1 disables all current polls and only write messages can be sent poll can be executed to each topic by POLL_NOW 1 see also Guidelines on Server Performance section MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 29 Historical File Only data marked with suffix h or H are stored in the historical file This file is updated at the historical data update interval The name of historical file is Hyymmdad LOG where yy is year mm month and dd day For example H960702 LOG is the name of a historical file with data received from all connected Gateways at July 2 1996 This single file record row contains a single received item data The format of this single file record is as follows yy mm dd HH MM SS MSEC ID STAT TzCxRy value where yy is year 00 99 mm month 0 11 dd day 1 31 HH hours 00 23 MM minutes 00 59 SS seconds 00 59 MSEC milliseconds 000 999 ID RTU Site ID STAT the RTU Status TzC
34. g The optinum MOSCAD RTU Update Interval value depends on the total number of connected active RTUs to which poll requests are sent and also on total amount of active items for the corresponding Topic It is very difficult to suggest some default value for MOSCAD RTU Update Interval because it highly depends on current environment This Update Interval must give enough time to execute all poll requests receive burst data and not to overload the system or the radio airtime usage Typically RTU Update Intervals in radio based systems are 10 30 minutes or 1 12 hours depending on system requirements Note Unlike other SCADA systems MOSCAD uses an unsolicited soontaneous burst mechanism to update important data changes Therefore it is less critical to poll RTUs frequently QUEUE_IS FULL_xxx xxx xxx xxx item The Server supports Discrete Read Only item QUEUE_IS FULL_xxx xxx xxx xxx where XXX XXX XXX XXX is the Gateway IP address used for indication of polling queue or write queue overflow This item is connected to whole active Gateway not to some RTU special Topic GATEWAYS is used This item value is OFF 0 if the current number of poll requests for current active Gateway does not exceed Max Pending Poll Requests see chapter MDLCGATE Gateway Node Settings or if the current number of pending write commands does not exceed Max Pending Write Requests see chapter MDLCGATE Gateway Node Settings This item value changes to ON 1 if there a
35. g of send package logging to the WWLogger file This item has the following subitems Log All Data Custom Log No Logging if checked then all outgoing user data is logged to the WWLogger file Each message s log contains 1 or more strings First string format differs from each next ones of message s log First string of message s log has the following format date time and application name are skipped lt type of request gt lt node name gt lt contents of request gt size lt size of request gt mailbox lt gt lt request in hexadecimal format gt where lt type of request gt Poll or Write types of request are possible lt node name gt name of sender node lt contents of request gt 1 For Gateway status poll message in the following format lt GW lt gt STATUS gt where is I for PRIMARY Il for SECONDARY Gateway 2 For Poll or Write requests format is the following lt lt Topic Name gt Table lt gt StartRow lt gt EndRow lt gt StartCol lt gt EndCol lt gt gt Request contains the Name of sender Topic and the RTU table number The StartRow and EndRow shows the smallest and the greatest row numbers of active items of the table of the topic The StartCol and EndCol shows the smallest and the greatest column numbers of active items of the table of the topic MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication S
36. has to be performed by client e g InTouch Changing MOSCAD RTU Update Interval at run time At run time the MOSCAD RTU Update Interval can be changed in two different ways 1 Manually for single or multiple Topics as described in the Topic Definition Command section In this case configurable units milliseconds seconds minutes hours can be used 2 In the client application for single Topic by defining the Integer Read Write item UPDATE_INTERVAL If this item value is changed in the client application e g manually or by InTouch script then the Server uses this value in the further processing of poll requests In this case only seconds can be used It is important to understand that new MOSCAD RTU Update Interval value becomes effective only after the previous MOSCAD RTU Update Interval has elapsed i e there is no automatic all RTU data polling performed at Update Interval change This is done in order to prevent additional overload if the system is still overloaded QUEUE_IS FULL_ XXX XXX XXX XXX iS ON To perform immediate poll when MOSCAD RTU Update Interval has been changed the POLL_NOW item can be used Several MDLCGATE Servers connected to one Gateway It is possible to connect to one Gateway from two or more MDLCGATE Servers running on different PCs In this case several things has to be observed 1 If Servers are communicating with same Gateway simultaneously then Max Pending Read Requests and Max Pending Write Requests
37. he WWLogger file This item has the following subitems Log All Data Custom Log No Logging if checked then all incoming user data is logged to the WWLogger file Each message s log contains 1 or more strings First string format differs from each next ones of message s log First string of message s log has the following format MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 41 Custom Log No Logging lt type of message gt lt node name gt size lt size of message gt lt contents of message gt mailbox lt gt lt message in hexadecimal format gt where lt type of message gt Receive or Burst types of message are possible lt node name gt name of receiver node lt size of request gt size of received message in bytes lt contents of message gt 1 Reply acknowledge on the Gateway status or mode poll contains the following string GET_MODE_ACK or GET_STATUS_ACk 2 Reply acknowledge format on Poll PING Set time Get time Write and request is the following lt lt Topic Name gt lt acknowledge type gt gt Request contains the name of sender Topic and type of acknowledge POLL_ACK GET_TIME_ACK SET_TIME_ACk COMMAND_ ACK 3 For Burst unsolicited message in the following format lt lt Topic Name gt BURST_MSGs gt where lt Topic Name gt the name of sender topic lt mailb
38. hooting onne a Natale tigate lala ttc tatoo tel etic tacos ott 36 WINN entries ssc eect sec eee se hdr gs ca ee le Sete ede 36 Troubleshooting menllc7 sara aaa ANA AMA GANA AMADA NAL ANAL ASA rah 39 MOSCAD System Definition Files scious ieee ce tee te ee ted he he Neel ea ec 44 RTU Types Definitions snie aa a a a aaa a iaaa 44 MOSCAD System Definition sczeictsictesstecncatetdigtnind satacetcigtarehdiniesatdietaigibiadnieilaccetiees 46 MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 1 MDLC Gateway Communication Server Overview The MDLC Gateway Communication Server hereafter referred to as the MDLC Gateway Server or MDLCGATE Server or MDLCGATE or Server is a Microsoft Windows application program that acts as a communication protocol Server and allows other Windows application programs access to data from the MOSCAD Remote Terminal Units using Motorola MDLC Gateway for TCP IP The MDLC Gateway Server requires an Ethernet card and TCP IP protocol supporting Windows Sockets interface installed on the computer to communicate with the MDLC Gateway s connected to the Ethernet network The MDLC Gateway Server calls MDLC Gateway API routines to establish the connections with Gateway and to send data commands and data requests to the field RTUs The MDLCGATE Server is primarily intended for use with Wonderware InTouch but any Microsoft Windows program that
39. ial SUSPEND see Item Point Naming chapter item of the Topic if such item is activated in user s InTouch application Further communication control can be performed using SUSPEND item of corresponding topic if value of item is set to 0 then polling is stopped otherwise polling is executed in general way Note This option does not take effect to write messages execution Clone of Topic Since MDLCGATE supports up to 500 topics per Gateway the configuration of topics could be time consuming It is possible to make clones similar copies of any topic except special GATEWAYS topic Only difference between clone s and base topic is name Name can be generated by MDLCGATE Server or extracted from text file To clone some topic select it and press Clone button Topic Clone dialog box will appear TOPIC CLONE x Topic to Clone RTU1 Number of Clones E Base Name SAMPLE IV Pad withO is File Hame ej E BiGWwse Cancel MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 19 Topic to Clone Appears topic name of cloned topic Number Of Clones Enter the number of copies clones will be created Base Name Enter the Base Name for created Topic Names Name of created topic will be BaseName NumberOfClone Examples 1 if Base Name is SAMPLE and Number of Clones is 3 and Pad with 0 checkbox is not checked the
40. in Custom Setup dialog the Sentinel LDK Run time Environment HASP HL Runtime Package is installed during the MDLCGATE Server installation and will be uninstalled during the MDLCGATE Server uninstallation The presence of Sentinel LDK Run time Environment can be checked after the MDLCGATE Server installation by looking up in Control Panel Administrative Tools Services the Service Sentinel Local License Manager must be started Notes 1 The MDLCGATE Server is developed with Wonderware I O Server Toolkit ver 7 2 1 6 and needs the Wonderware FS 2000 Common Components to be installed on computer where the MDLCGATE Server is running If using Wonderware InTouch 8 0 or newer install the FS 2000 Common Components before installing InTouch see also Wonderware Tech Notes 404 and 313 The Wonderware FS2000 Common Components are installed automatically when any of Wonderware product e g InTouch or some Wonderware I O server is installed 2 If MDLCGATE Server Suite Link amp DDE version will run on PC where Wonderware FS2000 Common Components are not installed then a special I O Server Infrastructure installation package can be obtained from Klinkmann see Installing the I O Server Infrastructure section below This I O Server Infrastructure installation package contains the minimum set of software needed to run the MDLCGATE Server and these infrastructure files must be install prior to executing the MDLCGATE Server The I O
41. inkmann Automation MDLC Gateway Communication Server 7 Transferring the software license to other computer The transfer of Software License Key might be needed in very rare situations when it is necessary to move Klinkmann software to other computer or operation system change is planned for same computer Such transfer PERMANENTLY removes the Software License Key so be very careful when deciding to use this option The following steps are required to transfer the Software License Key 1 Start the MDLCGATE Server For MDLCGATE Server Suite Link amp DDE version the ArchestrA SMC Log Viewer or Wonderware Logger must be started For MDLCGATE Server OPC amp DDE version the MDLCGATE Internal Logger and Log to File should be enabled see Troubleshooting menu and Internal Logger sections at the end of this manual Select Help License from main menu and click the Transfer button on License dialog 8 x Product Code DR21 010120 Customer PC Code 2496 0475 8b8b 6251 Transfer Software Key 96e1 e9D9 8f20 981d Cancel 2 Confirm the transfer of Software License Key by clicking on Yes button MDLCGATE xj Do you really want to transfer Software Key to other computer and permanently remove Software Key from this computer The License dialog now will contain the empty Customer PC Code and Software Key fields xi Product Code Customer PC Code o000 0000 00
42. iscrete Compressed Bits 0 255 Integer represents a Row of up to 8 Bits in a Table Analog Integer bit floating value TS1 Timestamp Message Notes 1 The Type is the item point type used in the Wonderware InTouch 2 The Bit in Compressed Bits TS1 and TS2 are Read Only all other types are Read and Write 3 The TS1 items have the format yy mm dd hh where yy is year 00 99 mm is month 01 12 dd is day 01 31 and hh is hour 00 23 4 The TS2 items have the format MM SS MSC where MM is minutes 00 59 SS is seconds 00 59 and MSC is milliseconds 000 999 MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 27 The additional items points can be used for special actions 1 The special topic GATEWAYS items points xxx xxx xxx xxx is the Gateway IP address QUEUE_IS FULL_xxx xxx xxx xxx Discrete Read Only used for indication of polling queue overflow this item value is 0 if the current number of poll requests for active Gateway does not exceed Max Pending Read Requests see chapter MDLCGATE Gateway Node Settings this item value changes to 1 if there are more than Max Pending Read Requests for this Gateway see also Guidelines on Server Performance section RESET QUEUE xxx xxx xxx xxx Discrete Read Write used for reset of polling and writing queue overflow If this item value is changed from 0 to 1 then both read and write
43. ition command invokes the configuration dialogs for System s all Topics for System s all Nodes if multiple gateways are used To configure Topics on a per Node basis the Configure Gateway Node Definition command should be invoked Server Settings Command A number of parameters that control the internal operation of the Server can be set In most cases the default settings for these parameters provide good performance and do not require changing However they can be changed to fine tune the Server for a specific environment To change the Server s internal parameters invoke the Configure Server Settings command The Server Settings dialog box will appear Protocol Timer Tick 50 msec I NetDDE being used Cancel Configuration File Directory c mdicgate I Start automatically as Windows NT Service The following describes each field in this dialog box Protocol Timer Tick This field is used to change the frequency at which the Server is continuously activated the Server checks for work to do If the computer is very busy or some other MS Windows application is taking over the computer then the Server could be is activated less frequently than the setting in the Protocol Timer Tick Note The default value is 50 If a value lower than 50 is entered the Server uses 50 milliseconds For Windows NT the minimum value is 10 milliseconds NetDDE being used Select this option if you are networking using NetD
44. l be read Max Pending Read Requests The possibility to configure the maximum number of pending read requests which are allowed to be sent to the Gateway This parameter value depends on MOTOROLA Gateway hardware model and current settings In two Gateways using mode this number cannot exceed weaker Gateway capacity MDLCGATE Server allows set up to 128 pending read poll requests Smallest possible value is 2 1 Gateway STATUS read poll request and one regular read poll request Default value is 20 Max Pending Write Requests The possibility to configure the maximum number of pending write requests which are allowed to be sent to the Gateway This parameter value depends on MOTOROLA Gateway hardware model and current settings In two Gateways using mode this number cannot exceed weaker Gateway capacity MDLCGATE Server allows set up to 128 pending write command requests Smallest possible value is 1 Default value is 5 Automatic Hot Standby This setting enables or disables the automatic hot standby to indicate how the hot standby is implemented if this setting is ON checkbox is checked then hot standby is processed by the Server if this setting is OFF checkbox is unchecked then hot standby must be processed by the client program using special items points created for topic GATEWAYS see the Hot Standby Principles of Operation and Item Point Naming sections Topic s To configure only the current Gateway Node s Topics
45. n be a variable from RTU Communication Table or some special purpose item The item point names are fixed by the MDLCGATE Server as described in the Item Point Naming section Note In some cases the term point is used interchangeably with the term item MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 3 Installing and starting the MDLCGATE Server Installing the Server The MDLCGATE Server installation package is supplied as a Microsoft Installer file DR21010_xxx msi where xxx is the current latest version of MDLCGATE Server To install the MDLCGATE Server run the DR44010_xxx msi and proceed as directed by the MDLCGATE Server Setup Wizard The installation is simple and straightforward only it is important to select the correct protection HASP key or software license in Custom Setup dialog The HASP key or software license key is needed for full time running of MDLCGATE Server The HASP key is an USB key dongle to be installed into PC USB port and needs the SafeNet Sentinel LDK Run time Environment HASP HL Runtime Package to be installed and running see details in Licensing by using HASP HL key section below The software license key is a 16 character alphanumeric computer dependent string provided after purchasing the MDLCGATE Server for more information see Software license key section below Without HASP key installed or software li
46. n will be created 3 topics with following names SAMPLE1 SAMPLE2 SAMPLES 2 if Base Name is SAMPLE and Number of Clones is 3 and Pad with 0 checkbox is checked then will be created 3 topics with following names SAMPLE001 SAMPLE002 SAMPLE003 File Name To extracted clone name s from the text file check the radio button nearby File Name static control Browse button and File Name static control and editbox becomes enabled Do not type the file name into File Name editbox but press Browse button to select the file with topic names Browse and file format To enter file name press Browse button Load TXT file common dialog box will appear Load TXT file Look in Ly mdicgate names File name names iOpen i Files of type TXT List x Cancel Select the file with topic names The file with topic names must be plain text file previously created by any text editor e g NOTEPAD Each line of such file must contain either one topic name or comment Comment starts by or Default file extension is TXT The following is contents of example file names txt RTU003 RTU2 RTU3 MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 20 RTU500 SIMULATOR TOPIC CLONE x Topic to Clone ATUT Number of Clones 5 Base Wane l iM Pad witht icy File Name
47. nition dialog box will appear MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 17 MDLCGATE Topic Definition Topic Name ATU T GATEWAYS Special Topic Name Gateway Node Name Nodet v RATU Site ID ATU 2 x Type Name BURST r Poll Mode GWLIB_POLL_MODE GWLIB_POLL_COS_MODE Update Intervals MOSCAD ATU 3 minute s 7 Historical Data 300 sec Ping Status 60 sec M SUSPEND Topic On Start Up C K f Cancel The following describes each dialog field in this dialog box Topic Name Enter the Topic Name that corresponds to the Topic Name in the Access Name Definition dialog box described in the Using the MDLCGATE Server with InTouch section GATEWAYS Special Topic Name If this checkbox is checked then this is a special topic GATEWAYS containing only some special predefined items see the Item Point Naming section Gateway Node Name Select the Gateway Node to associate it with the topic Additional topics may be associated with the same Gateway Node at a later time RTU Site ID Enter this RTU Site ID The corresponding value must be present in the MOSCAD System Definition file RTU Type Name This RTU Type Name value from the RTU Types Definition file is displayed here The new value can not be entered This field is used only for information Poll mode Select the poll mode
48. og Burst treeview items of topics of the current gateway node Dump dump internal data of the Server to WWLogger Data will be logged depending on treeview item that is under mouse cursor the clicking on topic initiates the internal info logging for this topic All debug information except Dump Screen is displayed via the Wonderware Logger which must be active for these commands to work Warning if you check Log Send Log All Data and or Log Receive Log All Data debug output grows very fast and it is possible that computer becomes very slow MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 44 MOSCAD System Definition Files The definition of the entire MOSCAD System all RTUs for all Gateway Nodes is stored in the two files 1 RTU Types Definition file 2 MOSCAD System Definition file RTU Types Definition In the RTU Types Definition file the RTU TYPES in the MOSCAD System are defined Each RTU Type Definition includes Number of Tables Il For each Table A Table Number in the MOSCAD application B Number of columns in the Table C Type of each column The file is case insensitive File Type RTU_TYPE Version XXX Table_no No_of_columns Column_type_0 Column_type_i MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 45 Example RTU Types File Version FILE TYPE RTU_TYPE VERSI
49. ox lt gt gt the number of mailbox for Receive type of message This parameter is not used for Burst messages lt request in hexadecimal format gt the hexadecimal queue of the request messages will be logged to the WWLogger corresponding to settings in the Server s main window no messages will be logged to the WWLogger At Server first start up the default selection is No Logging This default value can be changed by settings in the WIN INI file Subitems has the following values Log All Data 1 Custom Log 2 No Logging 0 The following is an example for Log All Data subitem selection in the Server s system menu MDLCGATE LogReceive 1 MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 42 Show Errors if checked then all information about errors is logged Dump all information about gateway nodes topics messages and data items are logged This can be used to find out how many messages are actually sent to the network Dump Screen if checked then information about open connections and active messages is displayed as a tree of communication component structure and it is drawn in the Server s main window F MDLCGATE iol x Configure Help Node Log Send On Log Receive On Aa STATUS mb9 RTU1 ID 2 Log Send Off Log Receive Off Log Burst Off PING mb4 Da R T1 RO R CO CO mb Da A
50. parameters must be set These parameters are set in the see chapter MDLCGATE Gateway Node Settings on each PC where Server is running These parameters should be set according the following rule the sum of Max Pending Read Requests for all connected Servers cannot exceed allowed capacity of pending poll requests of Gateway and the sum of Max Pending Write Requests cannot exceed allowed capacity of pending write requests of Gateway w If Servers are communicating with Gateway not simultaneously client performs swapping from one Server to another then Max Pending Read Requests can be up to maximum of Gateways capacity of pending read requests and Max Pending Write Requests can be up to Gateways capacity of pending write requests for each Server The Server is not resetting queue of requests when connection with Gateway by some reason is lost This allows to process replies after reconnecting This feature usually is not working during Servers swapping When swapping is performed then queue of requests of just connected Server must be reset because Server waits forever for reply on sent request The client e g InTouch must write value 1 to GATEWAYS MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 25 topic special item RESET _QUEUE_xxx xxx xxx xxx or write value 1 to GATEWAYS topic special items RESET _READS_ xxx xxx xxx xxx and RESET_WRITES_xxx xxx xxx xxx Reset ensures that qu
51. ppear Tag Types Ed Memory Discrete 1 0 Discrete Indirect Discrete Memory Integer v 1 0 Integer Memory Real 1 0 Real Indirect Analog Memory Message 1 0 Message Indirect Message Group Var Hist Trend Tag ID Cancel Detail To access MDLCGATE device items the type must be I O Discrete I O Integer or I O Message Select the Tag type The Details dialogue box for the tagname will appear MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 33 Initial Value jo Min EU 32768 Max EU 32767 Deadband jo Min Raw 1 232768 Max Raw 22767 7 m Conversion Eng Units Linear Unassigned E Square Root ltem I Use Tagname as ltem Name Log Deadband jo Select the Access name for MDLCGATE Server by clicking on the Access Name button The Access Names dialogue box will appear Access Names Select the appropriate Access Name and click on Close If the Access Name has not been defined as previously described click on Add and define the Access Name now The Details dialogue box will appear displaying the selected Access Name Initial Value jo Min EU 32768 Max EU 32767 Deadband o Min Raw 1 32768 Max Raw 22767 Eng Units paa i ATU Sue a ltem es cen F Use Tagname as ltem Name Log Dasdband E For integers fill in the Min EU Max EU Min Raw and Max Raw fields These fields
52. press the Topic s pushbutton The Topic Definition dialog box see the Topic Definition Section will appear Up to 500 Topics can be configured for one Gateway Node MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 13 Notes 1 The channel type opened both for Primary Gateway and if configured for Secondary Gateway and used to send receive poll messages and to receive burst messages is GWLIB_BURST_CHANNEL_TYPE GWLIB_SEND_ CHANNEL_TYPE GWLIB_RECEIVE_CHANNEL_TYPE 2 The Gateway status is requested at Gateway status update interval both for Primary Gateway and if configured for Secondary Gateway The data from all connected RTUs are accessed through the Primary Gateway The following is an example of MDLCGATE Gateway Node Settings dialog box where the Secondary Gateway IP Address is entered and Automatic Hot Standby is used Gateway Node Name No Computer Internet Address pooo M Use Default Primary Gateway IP Address fs2168 013 t Secondary Gateway IP Address fi 92 168 0 11 I NotUsed Reply Timeout 10 sec Gateway Status Update Interval 30 sec Max Pending Read Requests So m 5 Max Pending Write Requests Topic s Cancel Once all entries have been made click on OK to process the configuration for the Gateway Node The MDLCGATE Gateway Node Settings first dialog box will appear again Click on Done when configur
53. r s Guide The status of communication between the Server and InTouch can be read into Excel by entering the following DDE reference formula in a cell on a spreadsheet in following examples RTU1 is the Topic Name configured for MDLCGATE Server view DDEStatus RTU1 or view lOStatus RTU1 MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 35 Notes on Using Microsoft Excel Data from MDLCGATE topics RTUs may be accessed from Excel spreadsheets To do so enter a formula like the following into a cell on the spreadsheet MDLCGATE topic item Sometimes Excel requires the topic and or item points to be surrounded by apostrophes In the formula topic must be replaced with one of the valid topic names defined during the Server configuration process Replace item with one of the valid item point names described in the Item Point Naming section Reading Values into Excel Spreadsheets Values may be read directly into Excel spreadsheets by entering a DDE formatted formula into a cell as shown in the following examples MDLCGATE RTU2 T1C2R0 MDLCGATE RTU3 T2C5R1 3 MDLCGATE RTU10 T1C2ROTS2 Note Refer to the Microsoft Excel manual for complete details on entering Remote Reference formulas for cells Writing Values to MDLCGATE Points Values may be written to the Server from Microsoft Excel by creating an Excel macro that uses the POKE command The p
54. re more than maximum pending poll requests or maximum write requests allowed for this Gateway Node If QUEUE_IS_FULL_xxx xxx xxx xxx item is specified in the client application e g in InTouch then the system load can be monitored If QUEUE_IS FULL_xxx xxx xxx xxx MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 23 is ON too long then operator can modify increase the MOSCAD RTU Update Interval value for single or multiple Topics see Changing MOSCAD RTU Update Interval at run time subsection RESET QUEUE_xxx xxx xxx xxx item For special topic GATEWAYS one additional item RESET _QUEUE_xXxx xxx xxx xxx where xxx xxx xxx xxx is the IP address of the Primary Gateway of the node can be used This is a Read Write discrete item If this item value is changed from 0 to 1 then both read and write queue will be reseted After setting RESET QUEUE _xxx xxx xxx xxx to 1 replies on previous requests are not expected The capacity of write requests queue becomes equal to Max Pending Write Requests value and capacity of read poll requests queue becomes equal to Max Pending Read Requests value Value can be switched to 1 and both queues will be emptied This possibility is usable in case when data exchange is wavelike Unreachable Gateway or data flow impact can be a reason for non answering requests Such situation can be recognized at communication silence when the special
55. roper command is entered in Excel as follows channel INITIATE MDLCGATE topicname POKE channel itemname Data_Reference TERMINATE channel RETURN The following describes each of the above POKE macro statements channel INITIATE MDLCGATE topicname Opens a channel to a specific topic name defined in the Server in an application with name MDLCGATE the executable name less the EXE and assigns the number of that opened channel to channel Note By using the channel INITIATE statement the word channel must be used in the POKE statement instead of the actual cell reference The applicationname and topicname portions of the formula must be enclosed in quotation marks POKE channel itemname Data_Reference POKEs the value contained in the Data_Reference to the specific operand in the MDLCGATE via the channel number returned by the previously executed INITIATE function Data_Reference is the row column ID of the cell containing the data value For itemname use some of the valid item names specified like described in the Item Names section MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 36 TERMINATE channel Closes the channel at the end of the macro Some applications have a limited number of channels Therefore they should be closed when finished Channel is the channel number returned by the previously executed INITIATE function RET
56. s x86 Klinkmann Browse Automation MDLCGATE SuiteLink and DDE Server Reset Disk Usage Back Next conei Note In case the SafeNet Sentinel LDK Run time Environment HASP HL Runtime Package is already installed on your computer separately or by some other software then it can be disabled Sentinel LDK Run time Environment HASP HL Runtime Package This feature requires OKB on your hard drive When installation is finished the subdirectory specified as a folder where to install the MDLCGATE Server files will contain the following files MDLCGATE EXE The MDLCGATE Server Program This is a Microsoft Windows 32 bit application program MDLCGATE CHM The MDLCGATE Server Help file MDLCGATE CFG An example configuration file RTUTYPES CFG An example configuration file MSYSDEF CFG An example configuration file hasp_windows_44 Dynamic Link Library installed only if HASP Files is selected 42 dll during the installation in Custom Setup dialog MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 5 haspdinst exe Sentinel LDK Run time Environment Installer HASP HL Runtime Package copied to MDLCGATE Server folder only if HASP Device driver is selected during the installation in Custom Setup dialog LICENSE RTF Klinkmann Automation software license file In case the HASP Device driver is selected during the installation
57. s checked if 1 MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 37 Following optional entries for MDLCGATE Server can be used if default values of parameters must be changed DelayAfterLostRequest 10 LogSend 1 LogReceive 1 MultiWrite 0 WarningOnPollMiss 1 MDLCGATE Server Ver1 x User Manual Rev 1 10 Time in seconds of delay after LOST REQUEST message received from Gateway till next request sending Value can be from 1 to 65535 seconds The possibility to configure which subitem of the Log Send system menu item will be selected at start up Subitems has the following values Log All Data 1 Custom Log 2 No Logging 0 At Server first start up the default selection is No Logging The possibility to configure which subitem of the Log Receive system menu item will be selected at start up Subitems has the following values Log All Data 1 Custom Log 2 No Logging 0 At Server first start up the default selection is No Logging Can be used in cases when write command execution order is important for user application the Server must be configured to transfer only one non answered write message to each topic Value 0 enables only one non answered write sending to each topic In this case Max Pending Write Request parameter see chapter MDLCGATE Gateway Node Settings value is disabled Default value o
58. s in visible windows alarmed logged trended or used in a script Selecting this option will impact performance therefore its use is not recommended Select Advise only active items if you want the Server program to poll only points in visible windows and points that are alarmed logged trended or used in any script Click OK to accept the new Access Name and close the Add Access Name dialogue box The Access Names dialogue box will reappear displaying the new Access Name selected in the list Click Close to close the Access Names dialogue box MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 32 Defining the Tag Names To define the Tag names associated with the new Access Name invoke the Special Tagname Dictionary command in WindowMaker The Tagname Dictionary dialogue box will appear Tagname Dictionary Ed C Main Details Alarms Details amp Alarms tembe HEW Bestre Delete Save Select gt Cancel Close Tagname Rtu Ticona Memory Integer Group ssustem C Feadonly Read white Comment AccessLevel l LogData Log Events I Retentive Value Retentive Parameters Click on New and enter the Tagname The tagname defined here is the name InTouch will use The MDLCGATE Server does not see this name Select the tag type by clicking on the Type button The Tag Types dialogue box will a
59. s lita seat tacen tenia ace 10 Gateway Node Definition COMMANG ccccceee eee eeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeteee 11 Hot Standby Principles of Operation ccccceecccceeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeesaeeees 14 Saving MDLCGATE Configuration File ccccccceeeceeeeeeeeeeeeeeeeeeeeeeneeeeeeeeeeeteees 15 Configuration File EOCauon 6 srstecnne uated eteseetieeee ease ses 15 TOpPIG D finition Command iit cect ci ccectiel Sots st seacte vtec a aE 16 Guidelines on Server Performance cceeeeeeeeeccceeeeeeeeeeeeeeeeeeeeeeeeeeeeseenaeeeeeeeeeeeeeeee 22 tem Fonti INITIO esis can st eet oracle lie ame 26 PUIG ORICA NG osc ste a aie eats tye a a A Aaa AE Cosas AEA 29 Using the MDLCGATE Server with IN TOUCH 0 eeeececcececeeeeeeeeeeeeeeaeeeeeeeeeeeeeenennaaeees 30 Defining the DDE Access NAMes cccccceeeeeeeseeecceeeeeeeeeeeeeeaaeeeeeeeeeeeeeeeenaaeees 30 Defining the Tag Names 00 ccceeeeeeeececeeeeeeeeeeeeeeaeeeeeeeeeeeeeseenaaaaeeeeeeeeeeeseennaaaees 32 Monitoring the Status of Communication with INTOUCN ccccceeeeeeeeeeeeeeeeeeees 34 Notes on Using Microsoft Excel sis iccs tds c ives os Sade Cals syed anes unde eee ives cedaaned cnessedamensetunectnte 35 Reading Values into Excel Spreadsheets ccccccceessseeeceeeeeeeeeeeeeeeneneeeeeeees 35 Writing Values to MDLCGATE Points ceecceeeeeeeeeeeeenneeeeeeeeeeeeeeeennneeeeeeeees 35 Troubles
60. ted redundant MDLC Gateway Servers are used Depending on necessary reliability level the above mentioned dual Gateway configurations can be used with single communication device with redundant communication devices and with multiple redundant communication devices The Hot Standby feature implemented in the MDLC Gateway Server supports the redundant MDLC Gateways in the following way 1 After startup the Gateway status is requested at Gateway status update interval both for Primary and Secondary Gateways The data from all connected RTUs are accessed through the Primary Gateway 2 If the communication with Primary Gateway fails no answer to gwlib_get_gw_status command or returned Gateway status is Secondary then depending on the automatic hot standby setting the hot standby is processed in the following way If automatic hot standby is ON and if communication with Secondary Gateway is O K returned status is GWLIB_ SECONDARY then Secondary Gateway is changed to Primary oy MDLC Gateway API function and data from all connected RTUs now are accessed through this Gateway s channels If automatic hot standby is OFF then the status of each Gateway can be monitored and changed if special topic GATEWAYS containing items GS_LSB_XXX XXX XXX XXX GS_MSB_xxx xxx xxx xxx and GMODE_SET_ xxx xxx xxx xxx where XXX XXX XXX XXX is the Gateway IP address is created see the Item Point Naming section In this case if Primary
61. ting client e g Wonderware InTouch with Server name in the path At Server startup the MDLC Gateway API function gwlib_init_api is called to build the internal data structure used to identify the MOSCAD system The names of two files RTU Types Definition file and MOSCAD System Definition file can be specified in the Server command line or default file names RTUTYPES CFG and MSYSDEF CFG can be used For example the following command will start the MDLCGATE Server with non default definition files mdicgate mdlc_typ cfg mdlc_sys cfg MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 9 where mdlc_typ cfg is RTU Types Definition file and mdlc_sys cfg is MOSCAD System Definition file The structure of these files is described in the MOSCAD System Definition Files section Installing the I O Server Infrastructure The I O Server Infrastructure installation package is supplied as a self extracting archive lOServerlnfrastructure exe and can be downloaded from Klinkmann s web site To install the I O Server Infrastructure from the self extracting archive run the lOServerlnfrastructure exe and proceed as directed by the I O Server Infrastructure Setup program To uninstall the I O Server Infrastructure start Control Panel select Add Remove Programs and select the IO Server Infrastructure from the list of available software products Click on Add Remove and
62. xRy the address of item table column and row value received value If the same table contains TS1 and TS2 elements then RTU data and time are stored otherwise the computer data and time are stored The following would be an example of one this file record if RTU Site ID is 13 RTU Status is 0 item address is Table 2 Column 5 Row 0 and received data value is 1 96 02 07 09 48 40 760 13 0 T2C5RO 1 MDLCGATE Server Ver1 x User Manual Rev 1 10 21010m110 Klinkmann Automation MDLC Gateway Communication Server 30 Using the MDLCGATE Server with InTouch To access items points on the MOSCAD RTUs from InTouch the Access names and Tag names should be defined in WindowMaker Defining the DDE Access names To define the Access Names in WindowMaker for each node invoke the Special Access Names command The Access Names dialog box will appear Access Names Click on Add The Add Access Name Dialog Box will appear Add Access Name Access Name ATU2 r i Node Name Cancel Application Name MDLCGATE Topic Name RTU2 Which protocol to use C DDE SuiteLink When to advise server Advise all items Advise only active items Note If Add is selected this dialogue box will be blank when it initially appears Data has been entered here to illustrate the entries that are made The following fields are required entries when entering an Access Name Definition Access Name Enter
63. xt topic Topics are polled consecutively one by one in the order of the initiation If parameter DelayBetweenPolls appears in the MDLCGATE section of the WIN INI file and its value differs from 0 then following changes in the Server performance are expected 1 All topics are suspended Value of SUSPEND item for each topic is equal to and cannot be changed 2 MOSCAD RTU Update Interval is disabled 3 Ping Update Interval is disabled The Pings to RTU are not executed Writes are executed in general way The possibility to disable the first connection alert message box Default value is 1 21010m110 Klinkmann Automation MDLC Gateway Communication Server 39 ResetMode 0 If this parameter value is 0 the pending requests queue will be emptied when no connection to Gateways happens Default value is 1 ie MDLCGATE Server remembers pending request numbers till the Server shutdown Only by reset command can clear pending read and write requests queue see chapter Item Point Naming Troubleshooting menu The following debugging choices are appended to the Server s System Menu the menu that appears when you click the window box in the upper left hand corner of the Server Suspend Protocol Resume Protocol these choices permit you to turn protocol Log Send Log All Data processing on and off which means that you can suspend access to the RTUs this system menu item is provided for organizin