User Manual, Anybus Communicator for Modbus RTU

image

Contents

1. EN 50082 2 1993 EN 55011 1990 Class A EN 61000 6 2 1999 EN 61000 4 3 1996 10V m EN 61000 4 6 1996 10V m all ports EN 61000 4 2 1995 8kV Air Discharge T 4kV Contact discharge EN 61000 4 4 1995 2kVPower port 1kVOther ports EN 61000 4 5 1995 0 5kVPower ports DM CM 1kVSignal ports UL c UL compliance The certification has been documented by UL in file E214107 Galvanic isolation on subnetwork interface e EN 60950 1 2001 Pollution Degree 2 Material Group IIIb 250 Vrms or 250 VDCWorking voltage 500 VSecondaty circuit transient rating Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc Id SCM 1200 091 Appendix C C Troubleshooting Problem Solution Problem during configuration Upload Download Serial communication failed Try again The Config Line LED turns red in the ABC Config Tool The serial port seems to be available but it is not possible The serial port may be in use by another application to connect to the gateway Exit the ABC Config Tool and close all other applica tions including the ones in the system tray Try again Select another serial port Try again Poor performance e Right click subnetwork in the Navigation window and select subnetwork Status to see status diagnostic information about the subnetwork If the gateway reports very many retransmissions check your cabling and or try a lower baud rate setting for the subnetwork if possi
2. The term gateway refers to the Anybus Communicator e Hexadecimal values are written in the format OxNNNN where NNNN is the hexadecimal value e Decimal values are represented as NNNN where NNNN is the decimal value e As in all communication systems the terms input and output can be ambiguous because their meaning depend on which end of the link is being referenced The convention in this doc ument is that input and output are always being referenced to the master scanner end of the link Glossary Term Meaning ABC Anybus Communicator Broadcaster A protocol specific node in the configuration that handles transactions destined to all nodes RTU Modbus RTU Command A predefined transaction Configuration List of configured nodes with transactions on the subnetwork Fieldbus The higher level network to which the communicator is connected Fieldbus Control System Fieldbus master Frame Object Low level entities which are used to describe the different parts of a Transaction Monitor A tool for debugging the gateway and the network connections Node A device in the configuration which defines the communication with a node on the subnetwork The network that is logically located on a subsidiary level with respect to the fieldbus and to SURE WON which the Anybus Communicator acts as a gateway Transaction A generic building block that is used in the subnetwork configu
3. HMS Industrial Networks AB E Germany 49 721 96472 0 Japan 81 45 478 5340 Sweden 46 35 17 2920 U S A 1 312 829 0601 France 33 389327676 Italy 39 347 00894 70 China 86 10 8532 3183 lt ge sales hms networks com jp sales hms networks com sales hms networks com us Sales hms networks com fr sales hms networks com it sales hms networks com cn sales hms networks com User Manual Anybus Communicator for Modbus RTU Doc Id SCM 1200 091 Rev 3 00 AmS 44 Important User Information This document contains a general introduction as well as a description of the technical features provided by the Anybus Communicator including the PC based configuration software The reader of this document is expected to be familiar with PLC and software design as well as communication systems in general The reader is also expected to be familiar with the Microsoft Windows operating system Liability Every care has been taken in the preparation of this manual Please inform HMS Industrial Networks AB of any inaccuracies or omissions The data and illustrations found in this document are not binding We HMS Industrial Networks AB reserve the right to modify our products in line with our policy of continuous product development The information in this document is subject to change without notice and should not be considered as a commit ment by HMS Industrial Networks AB HMS Industrial Networks AB as
4. 81 82 8 84 85 86 87 88 89 90 91 92 93 94 95 a b C d e f g h j k m n 0 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 p q r S t u V Ww X y Z DEL 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091
5. Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 Control and Status Registers 69 14 2 Status Register Contents Gateway to Control Sys tem 14 2 1 General Information The Status Register is if enabled located at 0x000 0x001 and constitutes a bit field as follows bit s Name 15 Send SR_HS_SEND 14 Confirm SR_HS_CONFIRM Description These bits control the handshaking towards the fieldbus control system See also Handshaking Procedure on page 67 Control Register Contents Control System to Gateway on page 71 13 Data Valid This bit is set when all transactions have been executed successfully at least once Master Mode and DF1 Once set it will not change Master Mode Only 1 Data Valid 0 Data not Valid Note This bit is not used in Generic Data Mode 12 8 Status Code This field holds the last status report from the gateway 7 0 Dat See also Status Codes in Master Mode and DF1 Master Mode on page 69 Status Code in Generic Data Mode on page 70 Note Internally this is treated as a Motorola format word i e MSB first If the higher level network uses a different byte order the upper and lower bytes will appear swapped 14 2 2 Status Codes in Master Mode and DF1 Master Mode This table is valid only in Master Mode and DF1 Master Mode Condition Description 0x00 Retransmission Warning Counter
6. Master Mode on page 20 e Generic Data Mode In this mode there is no master slave relationship between the subnetwork nodes and the gate way any node on the subnetwork including the gateway may spontaneously produce or con sume messages For more information about this mode see Generic Data Mode on page 21 e DFI Master Mode In this mode the gateway acts as a master on the subnetwork using the DF1 protocol The serial communication takes place in a query response fashion For information about this mode see DF1 Protocol Mode on page 51 2 3 2 Protocol Building Blocks The following building blocks ate used in ABC Config Tool to describe the subnetwork communication How these blocks apply to the three protocol modes will be described later in this document e Nodes A node represents a single device on the subnetwork Each node can be associated with a number of transactions see below e Transactions A transaction represents a complete serial telegram and consists of a number of frame objects below Each transaction is associated with a set of parameters controlling how and when to use it on the subnetwork e Commands Commands are simply predefined transactions stored in the ABC Config Tool This simplifies common operations by allowing transactions to be stored and reused e Frame Objects Frame objects are low level entities used to compose transactions see above A frame object
7. network If enabled these registers occupy the first two bytes in the input and output data areas 0x000 0x001 and 0x200 0x201 respectively which means they can be accessed from the fieldbus just like any other data in these areas Note Internally these registers are stored in Motorola format 1 e MSB first If the higher level net work uses a different byte order the upper and lower bytes will appear swapped 14 1 1 Handshaking Procedure A special handshaking procedure which is illustrated in the two flowcharts below must be followed when accessing these registers to ensure that both parts receive proper information Read Status Register Write to Control Register Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 Control and Status Registers 68 14 1 2 Data Consistency The Data Valid bits in the Control and Status Registers are used to ensure data consistency during start up and fieldbus offline online transitions If the Status Control Word parameter in ABC Config Tool is set to Enabled the gateway will wait for the fieldbus control system to set the Data Valid bit in the Control Register before it starts exchang ing data on the subnetwork If the same parameter is set to Disabled or Enabled but no startup lock communication will start as soon as the fieldbus goes online State Machine The fieldbus network participation can be described using a state machi
8. A Modbus RTU Connector This connector is used to connect the gateway to the fieldbus See also Fieldbus Connector Modbus RTU on page 73 B Configuration Switches See also Configuration Switches on page 13 C Status LEDs See also Status LEDs on page 12 D PC connector This connector is used to connect the gateway to a PC for con figuration and monitoring purposes See also PC Connector on page 74 E Subnetwork Connector This connector is used to connect the gateway to the serial sub network See also Subnetwork Interface on page 75 F Power Connector This connector is used to apply power to the gateway See also Power Connector on page 73 Connector Pin Assignments on page 73 G DIN rail Connector The DIN rail mechanism connects the gateway to PE Protective Earth See also Hardware Installation on page 14 Connector Pin Assignments on page 73 Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 1 2 Status LEDs About the Anybus Communicator for Modbus RTU 12 State Status o e ee 1 Bus Error Off Normal operation nf 69 Red Bus error CRC mismatch gt 10 o O 2 Bus Ready Off Not powered Green Normal operation bus ready Red Bus is offline bus not ready 3 Processing Off Currently not processing query Green flashing Curr
9. CRC 2 bytes CRC 16 with OxFFFF polynome Modbus RTU standard LRC 1 byte All bytes are added together as unsigned 8 bit values The 2 s complement of the result will be used as a checksum e XOR 1 byte All bytes are logically XOR ed together The resulting byte will be used as a checksum ADD 1 byte All bytes are added together as unsigned 16 bit values The lowest 8 bits in the result will be used as a checksum e AddinvASCll 2 bytes All bytes are added together as unsigned 8 bit values The lowest 8 bits in the result are inversed and used as a checksum represented as hexadecimal ASCII 2 bytes Doc Id SCM 1200 091 Chapter 8 8 Commands This information is only valid for master mode and generic mode For DF1 master mode please refer to Services on page 54 8 1 General As mentioned previously commands ate actually predefined transactions that can be stored and reused Just like regular transactions commands consist of frame objects and are representations of the actual serial telegrams exchanged on the serial subnetwork Adding a command to a node actually results in a transaction s being added according to the directions specified in the command The frame objects in such a transaction may retrieve their values not only from parameters in the parameter section but also from other sources such as the SlaveAddress pa rameter see Node Parameters on page 32 In such case the paramet
10. Cyclically The transaction is issued cyclically at the interval specified in the Update time parameter On data change The data area is polled for changes at the time interval defined by Update time A transac tion is issued when a change in data is detected Single shot The Query is issued once at start up Change of state on trigger The Query is issued when the trigger byte value has changed This feature enables the control system to notify the gateway when to issue a particular Query To use this feature correctly the control system must first update the data area associated with the Query transaction then increase the trigger byte by one The location of the trigger byte is spec ified by the Trigger byte address parameter Update time 10ms This parameter specifies how often the transaction will be issued in steps of 10ms only rele vant when Update mode is set to Cyclically Doc Id SCM 1200 091 Transactions 36 6 3 2 Parameters Response To gain access to these parameters select a Response transaction in the Navigation Section Parameter Trigger byte Description This parameter is used to enable disable the trigger functionality for the response If enabled the gateway will increase the trigger byte by one when the gateway receives new data from the subnetwork This can be used to notify the control system of the updated data The location of the trigger byte is specified by the Tri
11. The number of retransmissions on the subnet Counter Updated work has increased If this problem persists this may eventually trigger a Single or Multi ple Node s Missing condition 0x01 Single Node Missing Error Slave address A single node is missing 0x02 Multiple Nodes Missing Error Number of nodes Multiple nodes are missing 0x03 Buffer Overrun Warning Slave address A node returned more data than expected 0x04 Other Error Error Slave address Undefined error Ox1F No Error Warning No errors Note Conditions of type Error will eventually be followed by a No Error condition when the cause has been resolved Conditions of type Warning are however considered informational and may not nec essatily be followed by a No Error condition later on Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc Id SCM 1200 091 Control and Status Registers 70 14 2 3 Status Code in Generic Data Mode This table is valid only in Generic Data Mode Code Condition Type DELE Description 0x00 Invalid Transaction Error Counter The number of invalid transactions i e received transac Counter Updated tions which doesn t match any of the consume transactions defined in the subnetwork configuration has increased 0x01 Frame Error Warning End character is enabled but a message delimiter timeout occurs prior to receiving it 0x02 Offline Timeout Error Counter The of number of timed out consume t
12. by a Query or Produce transaction Red Collision area has been allocated more than once Grey Reserved illustrates memory consumption area can be allocated if necessary Green Data allocated by Trigger byte Transmit Receive Counter or Control Status Registers Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 Chapter 11 11 Node Monitor 11 1 General The Node Monitor can provide valuable information when setting up the communication with the sub network by allowing individual commands to be issued manually and monitoring the response if ap plicable It also provides an overview of the memoty used by a particular node Note The node monitor has a negative influence on the overall performance of the gateway 1 e 1t should be used only when necessaty The Node Monitor behaves somewhat differently in the three protocol modes e Master Mode and DF1 Master Mode The selected Command Query Transaction or Service is sent to the subnetwork The response to the Query can be monitored in the Response Section Monitor New Node File Node Command Columns View 8sg2 mo Command Section Query Subnetwork Response Section In Area 1 bytes 512 Out Area 1 bytes 512 General Area 0 bytes 1022 e Generic Data Mode The selected command Transaction Produce is sent to the subnetwork It is not possible to monitor any responses etc generated by other nodes Monitor New Node File Nod
13. bytes This area can be read written by the higher lev el network in this case Modbus RTU General Data General Data Up to 1024 bytes This area cannot be accessed from the higher level network but may be used for transfers be tween individual nodes on the subnetwork or as a general scratch pad for data The actual size of this area depends on the amount of data that is exchanged on the subnetwork The gate way can handle up to 1024 bytes of general data 2 2 1 Memory Map When building the subnetwork configuration using the ABC Config Tool the different areas described above ate mapped to the memory locations addresses specified below Input Data Output Data General Data 0x000 0x200 0x400 Sub Network Read Write Fieldbus Read Only Sub Network Read Only Fieldbus Read Write Sub Network Read Write Fieldbus Ox1FF 0x3FF 0x22 Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 Basic Operation 18 2 2 2 Data Exchange Example In the following example a temperature regulator on the subnetwork exchanges information with a PLC on the higher level network via the internal memory buffers in the gateway PLC Modbus RTU Master PLC Memory Inputs PLC Memory Outputs Actual Temperature Temperature Setpoint The PLC exchange data between the internal PLC memory and the slaves in this case the MEM ABC on the Modbus RTU network The PLC Memory associated with the ABC
14. c a Configuration Devices D Alphabetic Categorized N Fieldbus A ABC E Ethernet TCP IP configuration Communicator IP address 192 168 0 1 Default Gateway 0 0 0 0 255 255 255 0 Enabled we Sub Network Y New Node C Read Holding Registers E3 Query EJ Response Preset Multiple Regs L3 Query El Response Subnet Mask TCP IP Settings Fieldbus Fieldbus Type A 10 Sizes IO Sizes Automatic Profinet IO o IO Sizes Sets whether the sizes ofthe IO areas are user defined or automaticly configured 2005 10 24 A Pull down Menus amp Tool Bar The second drop down menu from the left will change de pending on the current context The Tool Bar provides quick access to the most frequently used functions B Navigation Section This section is the main tool for selecting and altering dif ferent levels of the subnetwork configuration Entries preceded by a holds further configuration pa rameters or sub menus To gain access to these parame ters the entry must be expanded by clicking There are three main levels in the navigation window namely Fieldbus ABC and subnetwork Right clicking on entries in this section brings out addi tional selections related to that particular entry C Parameter Section This section holds a list of parameters or options related to the currently selected entry in the Navigation Section The para
15. can represent a fixed value a constant a range of values limit objects a block of data or a cal culated checksum Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc Id SCM 1200 091 Basic Operation 20 2 3 3 Master Mode In this mode the communication is based on a query response scheme when the gateway issues a query on the subnetwork the addressed node is expected to issue a response to that query Nodes are not per mitted to issue responses spontaneously i e without first receiving a query There is one exception to this rule the broadcaster Most protocols offer some way of broadcasting mes sages to all nodes on the network without expecting them to respond to the broadcasted message This is also reflected in the gateway which features a dedicated broadcaster node Control System Gateway Subnetwork Devices Node 1 Node 2 In Master Mode ABC Config Tool comes preloaded with most commonly used Modbus RTU com mands which can conveniently be reached by right clicking on a node in the ABC Config Tool and se lecting Insert New Command Note however that this does not in any way prevent other protocols based on the same query response message scheme to be implemented Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc Id SCM 1200 091 Basic Operation 21 2 3 4 Generic Data Mode In this mode there is no master slave relationship between the nodes on the subnetwork and the gate way Any node in
16. is exchanged Data from the Input Data area is copied to PLC Input Memory and PLC Output Memory is copied to the Output Data Modbus RTU area Input Data General Data Actual Temperature Temperature Setpoint not used in this example The ABC copies the Output Register of the Temperature Regulator to the Input Data area The ABC copies the Temperature Setpoint from the Output Data area to the Input Register in the Temperature Regulator Serial Device Temperature Regulator Sub Network Output Register Input Register The Temperature Regulator has two Actual Temperature Temperature Setpoint registers holding the Setpoint Temperature and the Actual Temperature respectively Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 Basic Operation 19 2 3 Subnetwork Protocol 2 3 1 Protocol Modes The gateway features three distinct modes of operation regarding the subnetwork communication called Master Mode DF1 Master Mode and Generic Data Mode Note that the protocol mode only spec ifies the basic communication model not the actual subnetwork protocol e Master Mode In this mode the gateway acts as a master on the subnetwork and the serial communication takes place in a query response fashion The nodes on the network are not permitted to issue messages unless they have been addressed by the gateway first For mote information about this mode see
17. the toolbar icons at the top of the v Toolbar main window we Status Bar e Status Bar This entry enables disables the status bar at the bottom of the main window Help This menu features the following entries Help Contents Search For Help On e Contents Display the table of contents of the online help system Note At the time of writing no online help sys About tem exists e Search For Help On Search for a particular topic in the online help sys tem Note At the time of writing no online help system exists e About Display general information about the gateway and the current build of ABC Config Tool Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 Navigating the ABC Config Tool 27 3 1 2 Toolbar Icons The toolbar features icons for the most commonly used functions New Open amp Save E See File on page 24 L ew pen e Upload from ABC amp Download to ABC See Tools on page 25 5 Upload Download e Up one Level re Clicking on this icon will move the selection in the navigation section Up one Level e Cut Copy Paste Delete Insert gt Z These icons are used for common editing func NH Cut Copy Paste Delete Insert tions in the navigation section e Connect Clicking on this icon will cause the ABC Config Tool to attempt to connect to the gateway ranea e Disconnect pe Clicking on this i
18. 091 About This Document Preface For mote information documentation etc please visit the HMS website www anybus com Related Documents Document name Author ABC RTU Installation Leaflet HMS Modbus Protocol Reference Guide PI MBUS 300 Rev J Modicon Inc DF1 Protocol and Command Set Reference Manual 1770 6 5 16 October 1996 Allen Bradley Document History Summary of Recent Changes 2 54 3 00 Change Page s Minor corrections amp updates New template added to document DF1 functionality information added to document Revision List Revision Date Author Chapter Description 2 00 2005 08 25 PeP All Second major release 2 50 2006 04 05 PeP All Major update 2 51 2006 06 01 PeP Minor corrections 2 52 2006 12 22 PeP Minor corrections 2 53 2007 11 23 PeP All Minor updates 2 54 2009 04 23 KeL All Misc minor corrections and updates 3 00 2011 02 08 KaD All Misc minor corrections new template and DF1 functionality Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc Id SCM 1200 091 About This Document P 8 Conventions amp Terminology The following conventions are used throughout this document e Numbered lists provide sequential steps e Bulleted lists provide information not procedural steps The term user refers to the person or persons responsible for installing the Anybus Communi cator in a network
19. 200 091 Frame Objects 42 7 5 Data Object Data Objects are used to represent raw data as follows e Produce Query Transactions The specified data block is forwarded from the higher level network to the subnetwork e Consume Response Transactions The specified data block is forwarded from the subnetwork to the higher level network To specify the properties of the object select it in the Navigation Section and enter the desired settings in the Parameter section as follows Parameter Description Byte Swapping e No Swapping No swapping is performed on the data Swap 2 bytes A B C D becomes B A D C Swap 4 bytes A B C D becomes D C B A Data Length The length of the data block in bytes In case of a Response or Consume transaction incom ing messages where the data size differs from the value specified here will be discarded Max imum data length allowed for one frame is 300 bytes Data Location The location of the data block in the internal memory buffer 7 6 Variable Data Object Note Only one Variable Data Object is permitted for each transaction This object is similar to the Data Object except that it has no predefined length Instead an End or Length character specifies the size of the data block as follows Variable Data Object Variable Data Object Data of arbitrary length End Character Length Character bytes of data e Produce Quety Transactions The specified data blo
20. 22 Tx I 470R 1 1 RS422 Tx s RS422 Rx 120R RS422 Tx l RS422 Rx l 470R TE 1 I Signal f Signal Ground Ground Cable J Shield Anybus Communicator Device Note Bias resistors are normally not needed on RS422 but may be required when using 4 wire RS485 A 4 7 Typical Connection RS232 RS232 Tx RS232 Rx I oa I 1 I a RS232 Rx RS232 Tx I a I Signal J Signal Ground Ground Cable Shield Anybus Communicator Device Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 Appendix B B Technical Specification B 1 Mechanical Properties Housing Plastic housing with snap on connection to DIN rail protection class P20 Dimensions 120 mm x 75 mm x 27 mm Lx W x H inches 4 72 x 2 95 x 1 06 Lx W x H B 2 Electrical Characteristics Power Supply Power 24V 10 Power Consumption Maximum power consumption is 280mA on 24V Typically around 100mA B 3 Environmental Characteristics Relative Humidity The product is designed for a relative humidity of 0 to 95 non condensing Temperature Operating 0 C to 55 C Non Operating 25 C to 85 C Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 Technical Specification 78 B 4 Regulatory Compliance EMC Compliance CE This product is in accordance with the EMC directive 89 336 EEC with amendments 92 31 EEC and 93 68 EEC through conformance with the following standards
21. 56 9 6 Integrity Check This service checks that a node is up and running correctly A telegram is sent to the node The node mirrors and returns the telegram No configuration is needed apart from the general parameters com mon to all services 9 7 Read Diagnostics This service reads diagnostic information from the module ABC DF 1 Master Untitled Devices Configuration Alphabetic Categorized E Command Params Size 0x02 CJ Integrity Check El Data Options C3 A ead Diagnostics Byte swap No byte swap T Node 2 Data Length 0x02 Offset 0x0000 E General Offline options for fieldbus Clear Offline options for sub network Clear Update mode Cyclically E Timing Retries Timeout time 10ms Update time 10ms E Trigger Request Trigger byte address OxD5FF Response Trigger byte Disabled Response Trigger byte address OxD5FF Read Diagnostics 2010 05 07 10 53 Config Line Command parameters The command parameter Size decides the amount of data that can be read The size is given in bytes which means that it always has to be an even number as only whole elements can be read from the slave One bit integer element is 2 bytes and one float element is 4 bytes The range of the size differs de pending on node type PLC 5 SLC500 Size range in bytes 1 28 Data options Parameter Description Valid settings Byte swap Determines if the data shall be swapped No byte swap Swap words Swap d
22. Counter in the internal memory buffer e Transmit Counter Location Specifies the location of the Transmit Counter in the internal memoty buffer Both counters are enabled by setting Statistics to Enabled Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc Id SCM 1200 091 9 3 Subnetwork Parameters To gain access to the parameters described in this section select Subnet work in the Navigation Section Communication DF1 Protocol Mode Fieldbus A ABC See Sub Network These parameters specify the actual communication settings used for the subnetwork Parameter Description Valid Settings 93 Bit rate baud rate Selects the bit rate 2400 4800 9600 19200 38400 Default Data bits Selects the number of data bits 8 Parity Selects the parity mode None Odd Even Physical standard Selects the physical interface type RS232 RS422 RS485 Start bits Number of start bits Stop bits Number of stop bits 1 DF1 Settings Parameter Description Master Node Address Node address of the master valid values 0 254 default 1 Poll time active slaves 10 ms Determines how often the slave shall be polled in steps of 10 ms default 100 ms Poll time inactive slaves 10 ms Determines how often the slave shall be polled in steps of 10 ms default 1000 ms a The default value is given as 10 in the parameter window Each change of 10 ms either increases or decrease
23. D iU 42 Checksun Be ec RE 44 Commands GN E EN S E E A ce et E A TE E EE E E E E E 45 Addie Manasmo Commands isien aN cla dianas 45 Pan AIONO N A RN Doo O O 46 LONA LO A D 46 TA as 47 AT ed e at e ds 47 5717991571710 AS T 47 II AVA INC 48 1317 7 RO ONO EERE TE A ORC RE TRONS NORCO SR TON TEE 49 Example Specifying a Modbus RTU Command in Master Mode eee 50 Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc Id SCM 1200 091 Chapter 9 DF1 Protocol Mode General A TENEN 51 des e TE E E O 52 Subnetwotrk Paran et ES A o 53 Node Paramete oie 54 O 54 IVA DESEE A A A eda AA AAA A 55 Paine uaa aa oru AR 56 Read Danos eii doe ra cddadibet casita a orbe 56 Read Daca PS 57 ARNO 2 Chapter 10 Subnetwork Monitor Chapter 11 Node Monitor Bs A E D MX D M EE E MU M EM E d 59 INavisatie the Node MONO unen lili 60 VD BODAS Rc 61 A HERE 62 Chapter 12 Data Logger S eur cea See X A 63 OPE O PD aula oct TCT aA Ree Ne rane een Serr 63 Confort tilda dl iia nets 64 Chapter 13 Configuration Wizards enar ER 65 oelecuno a Wizard Protec 65 Mazar Modbus JC LU MASTO aate tenet pit en on o on serit iore b onde 66 Chapter 14 Control and Status Registers SA RU TREO TOTO DPC aT TERE 67 VARAS DUETO TAPONES AREA AS AAA aoa Le vp E ess 67 D Nn vu ates tail 68 Status Resister Contents Gateway to COMO System ouest oot DR a 69 1714 071 TOV ULATION
24. E A aio niusiao 21 Dita Representation On Modbus RU quintana bible dedii eoe bte cicle 22 A 22 E A AAA A tenses UR 22 COTO E V E TN E 22 SAPP OCA EODD S ODE A qa binum isq adest etat aster ATE 22 Chapter 3 Navigating the ABC Config Tool E RRA 23 VIVEN NE ERROR hes E rcs Ir 24 RTT AAA NN A A E LN 27 Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 Chapter 4 Chapter 5 Chapter 6 Chapter 7 Chapter 8 Basic Settings O A eS duc nota oe MERE TEA ERE delta de qucd eT eter enn ere eran 28 A 29 Subtietwotkc Oo 71 0 9c Hox E Su ame Tear a e Lit Ron I RO TSS D 31 Nodes Generali reste aa alae ete ace al 32 deine Se Ma acimo Node aria iia 32 Heya femal Cert ork peel ce Set but iL CM M eu I E du M MM M ML Mt cis 32 Master Mode and Generic Data Mode ia 32 Transactions AETERNE 33 PG GIO Oe IATA Oe Leran ACON saec AA AAA 34 Transaction Parameters Master VIO ias 35 117107171 E A ONN E p 1017070 17750 REND i ch O 35 ATAR AO sis 36 Transaction Parameters Generne Dar Mo ts 36 PRD LI A ld E e Mas cs aid eto al a 36 COMETE LISA TONE o ld o o a O 37 Transaccional 38 Frame Objects General S 39 dcin and Beitdesbrame O Des sapito nd 39 Constant Objects Byte Word DWord evisos 40 imo Objects Byte Word DSVOERO li 41 DAO ll 42 Narable acr ODECE o ket omn dete tnu uu M vu M
25. Firmware to the Anybus tab and enter the desired number of buffer entries under Size of logbuffer valid settings range from 1 512 Restores Communicator firmware Factory Restore Block the current configuration in the COTRA PIDE Block Configuration Click Apply to validate the new settings Creates an error log file Create Error Log Click OK to exit Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 13 Configuration Wizards 13 1 General Chapter 13 When creating a new subnetwork configuration the ABC Config Tool provides a choice between start ing out with a blank configuration or using a predefined template a k a a wizard The wizard automatically creates a subnetwork configuration based on information supplied by the user i e the user simply has to fill in the blanks Note however that this will only work when the subnetwork fits the wizard profile in all other cases the Blank Configuration option must be used 13 2 Selecting a Wizard Profile The following window appears each time the ABC Config Tool is started or upon selecting the New entry in the File menu unless it has been disabled in the Options menu see Tools on page 25 Currently the following wizards are available e ABCC ExtLink Wizard This wizard is intended for use with the Anybus Com pactCom Modbus RTU fieldbus communication module e Wizard Modbus RTU M
26. Hex Decimal e Decimal Display the data in decimal format Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 Node Monitor 62 11 2 2 Toolbar Icons The toolbar features icons for the most commonly used functions e Start Node Stop Node O e These icons corresponds to the functions in the Node menu e o o See also Node on page 61 Start Stop e Select Command amp Send Command These icons corresponds to the functions in the Command menu ES Ead See also Command on page 61 Select Send Resume Refresh amp Stop Refresh When enabled the data displayed in the Monitor Section will be re freshed cyclically When disabled 1 e stopped the data will have to be refreshed manually using the Refresh icon see below D o Stop Resume e Refresh When clicking on this icon the data displayed in the Monitor Section will be re MH freshed Refresh Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 Chapter 12 12 Data Logger 12 1 General This feature allows the subnetwork traffic to be logged into a buffer for examination This may provide valuable information when debugging the lowest levels of the subnetwork communication Note that the logger function is part of the gateway itself and is separate from the ABC Config Tool This means that logging can be performed even if the gateway is physically disconnected from the PC running
27. M 1200 091 6 5 Transaction Editor Transactions 38 The Transaction Editor can be used to edit the individual frame objects of a transaction The same set tings are also available in the parameter section of the main window however the Transaction Editor presents the frame objects in a more visual manner Transz on Editor File Byte constant Ward constant Data Value Value Data location Data length 0x00 0x0000 0x0200 0x0010 Transaction Y Byte constant Lo ile constant Eram A E Checksum Objects Byte constant LOX 8 Checksum Byte constant Error check type Error check start byte Value CRC 0x0000 0x00 To edit the value of a parameter click on 1t and enter a new value using the keyboard When editing transactions which are based on predefined commands certain parts of the transaction may not be ed itable The File menu features the following entries Apply Changes Exit Ctr Q Example Transaction Editor File Byte constant Word constant Data Value Value Data location Data length 0x02 0x0008 0x0202 0x0008 Apply Changes This will save any changes and exit to the main window Exit Exit without saving Checksum Byte constant Error check type Error check start byte Value CRC 0x0001 0x03 The transaction created in this example are built up as follows The first byte holds the STX 0x02 followed by two bytes specifying the length of the data field in this c
28. Multiple Coils Output Data Area 0x200 Ox3FF 16 Force Multiple Registers 22 Mask Write Register 23 Read Write Registers Input and Output Data Area 0x000 Ox3FF a Subfunctions 0 10 12 13 and 14 are supported Refer to the Modbus Protocol Reference Guide PI MBUS 300 Rev J for more information 2 4 3 Coil amp Register Map The Input and Output Data areas are mapped to coils and registers as follows Register Coil Memory Location Area Comments 1 1 16 0x000 0x001 Input Data area 2 17 32 0x002 0x003 255 4065 4080 0x1FC 0x1FD 256 4081 4096 OxTFE OX1FF 257 1024 4097 16384 reserved 1025 16385 16400 0x200 0x201 Output Data area 1026 16401 16416 0x202 0x203 1279 20449 20464 Ox3FC OX3FD 1280 20465 20480 Ox3FE OX3FF Note Coils are mapped MSB first i e coil 0 corresponds to bit 15 of register 0 2 4 4 Supported Exception Codes Exception Code Name Description 0x01 Illegal function Function code not supported 0x02 Illegal data address Invalid address in query 0x03 Illegal data value Illegal data in request Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc Id SCM 1200 091 3 Navigating the ABC Config Tool 3 1 Main Window Chapter 3 The main window in the ABC Config Tool can be divided into 4 sections as follows 5 ABC Config Tool Untitled File Fieldbus Tools View Help D
29. TUERI CNRC MM TT 69 Status Codes in Master Mode und DET Master Modessiidnit tada tote te ai dva e rade 69 DUIS DI AG HOLD IOS A utatur dva A odie SA Ee 70 Control Register Contents Control System to Gateway eese nettement 7 SOARES A A AOS 71 Control Codes in Master Mode and DEF Master Mode eee eene 71 Control Godon Genere Dord Mode reire pla tux Cie ete labe ti eo eO eed sansa D an E eS deus 71 Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 Chapter 15 Appendix A Appendix B Appendix C Appendix D Advanced Fieldbus Configuration GS y lar srs o C TA o ts Coon rccte e e advan spec oU s occ tnis nut 12 Connector Pin Assignments Fielabus Connector Modbios des 73 Power CORA ECOS th A Meu Ut utu UE 73 PEO CONTEO tato ede Ebene edU AA AA 74 Suprelwor terrace Locri olus 75 12277 WE O I AI ERE ZB BAS RETO OH CUI Menor ORCC eem btt buta d cdosticu s aT Te n Haider afe 75 VERNOS TODO NGL ORI AAA A eade uie A A 75 COM CLONE OUT ODE A IA AS 75 R P T E A E T TE A E A E A 76 Typa COMMON IR SALT COA WIC S9 td N EEEE 76 ERIT T 72071 TRS 2 IL AAA c 76 Technical Specification Mechanical Eroperlosa Amon A E RI E E S AANA NAAA E S T Elcano T4 Environment C haractetistit ed t ttu cadit end eee t d al Keosulator Con punteo 78 Troubleshooting ASCII Table Anybus Communicator for Modbus RTU Doc Rev 3 00 VI Doc Id SCM 1200
30. These parameters specify the actual communication settings used for the subnetwork Parameter Description Master Mode and Generic Mode Bit rate baud rate Selects the bit rate 1200 2400 4800 9600 19200 35700 38400 57600 Data bits Selects the number of data bits 7 8 Parity Selects the parity mode None Odd Even Physical standard Selects the physical interface type RS232 RS422 RS485 Start bits Number of start bits 1 Stop bits Number of stop bits 1 2 Start and End Character Note These parameters are only available in Generic Data Mode Start and end characters are used to indicate the beginning and end of a serial message For example a message may be initiated with lt ESC gt and terminated with lt LF gt In this case the Start character would be 0x1B ASCII code for lt ESC gt and the End character OxXOA ASCII code for lt LF gt Parameter Description Valid settings End Character Value End character for the message ASCII 0x00 OxFF Use End Character Determines if the End character shall be used or not Enable Disable Start Character Value Start character for the message ASCII 0x00 OxFF Use Start Character Determines if the Start character shall be used or not Enable Disable Timing Message Delimiter The parameters in this category differs slightly between the different protocol modes e Master Mode The Message Delimiter specifies the time that separates two messages in steps
31. ase 8 The next 8 bytes are data and since this is a query transaction the data is to be fetched from the Output Area which starts at address location 0x202 No swapping will be per formed on the data This is followed by a two byte checksum The checksum calculation starts with the second byte in the transaction The transaction ends with a byte constant the ETX 0x03 Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc Id SCM 1200 091 Chapter 7 7 Frame Objects 7 1 General Each transaction consists of Frame Objects which makes up the serial telegram frame Each Frame Ob ject specifies how the gateway shall interpret or generate a particular part of the telegram There are 5 types of frame objects which are described in detail later in this chapter e Constant Objects Limit Objects e Data Objects e Variable Data Objects e Checksum Objects Example The following Transaction consists of several frame objects three constants a data object and a checksum object Transaction 7 2 Adding and Editing Frame Objects W Sub Network T New Node Transactions 1 To add a frame object to a Transaction right click on the Transac 2 E pm ER Edt Transaction tion in the Navigation Section and select one of the entries in the Add Data Add Variable Data menu that appears Add Checksum Add Byte Constant The entry called Transaction Editor will launch the Transa
32. aster This option is suitable for Modbus RTU based net works See also Wizard Modbus RTU Master on page 66 e Blank Configuration This option creates an empty configuration Highlight the desired wizard and click OK to continue Anybus Communicator for Modbus RTU Doc Rev 3 00 LC de 2 Me i is e o Cancel ABCC ExtLink Wizard Wizard Modbus Blank Configuration RTU Mast aster Select the desired topic to do and press the OK button A wizard option will guide you through and explain all steps of a configuration The output from a wizard will result in a working configuration ready to download It is also possible to edit the configuration in th dard configuration tool after Wizard completion The Blank Configuration option will open the standard configuration tool and a configuration can be created from scratch Here it is also possible to open an existing configuration from file or via upload from a Communicator module Don t show this Window again Doc ld SCM 1200 091 Configuration Wizards 66 13 3 Wizard Modbus RTU Master This wizard can be used to create a Modbus RTU based network configuration based on certain infor mation about the subnetwork The online help system explains each configuration step in detail e Important Notes Many OEM devices do not fully comply with the Modbus standard For example they may im plement a variati
33. ave an even value as only whole elements can be read from the slave Data Options Parameter Byte swap Description Determines if the data shall be swapped PLC 5 2 240 SLC500 2 236 MicroLogix 2 242 Valid settings No byte swap Swap words Swap double words Data length The number of bytes read from the DF1 network to write to the area determined lt Size by the Offset parameter Offset The offset in the internal memory buffer in the module where the data shall be read See Memory Map on page 17 Note If the control and status registers are enabled default first available data location will be Input area 0x002 Output area 0x202 9 9 Write Data This service is used to write data to the nodes in the subnetwork The parameters to be configured are the same as for the service Read Data The only difference is that data 1s read from the internal memory buffer in the Anybus Communicator and written to the subnetwork bus instead of being written to the internal memory buffer Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc Id SCM 1200 091 Chapter 10 10 Subnetwork Monitor General The Subnetwork Monitor is intended to simplify configuration and troubleshooting of the subnetwork Its main function is to display the data allocated for subnetwork communication and detect if any area has been allocated twice 1 e if a collision has occurred All configured nodes an
34. ble sthe Subnet Monitor in the ABC Config Tool active The subnetwork monitor has a negative influence on the overall performance of the gateway and should only be used when necessary e sthe Node Monitor in the ABC Config Tool active The node monitor has a negative influence on the overall performance of the gateway and should only be used when necessary No subnetwork functionality Use the Data logger functionality to record the serial data communication on the subnetwork e fno data is being transmitted check the configuration in ABC Config Tool e fno data is received check the subnetwork cables Also verify that the transmitted data is correct Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 Appendix D D ASCII Table NUL SOH STX ETX EOT ENQ ACK BEL BS HT LF VT FF CRIS SI 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 DLE DC1 DC2 DC3 DC4 NAK SYN ETB CAN EM SUB ESC FS GS RS US 16 17 18 19 20 21 22 23 24 235 26 27 28 29 30 31 sp i amp a i 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 0 1 2 3 4 5 6 7 8 9 lt gt 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 Q A B C D E F G H J K L M N O 64 65 66 67 68 69 70 71 72 73 T4 75 76 77 TO T9 P Q R S T U V W X Y Z _ 80
35. ch When removing the hatch avoid touching the circuit boards and components If tools are used to open the hatch use caution Emo m EE B e EE o Bo Emo a an Note that these settings cannot be changed during runtime i e the gate way must be restarted in order for any changes to have effect 1 3 1 Node Address Node Address Sw 1 Sw 2 Sw 3 Sw 4 Sw 5 Sw 6 Sw 7 reserved OFF OFF OFF OFF OFF OFF OFF 1 OFF OFF OFF OFF OFF OFF ON 2 OFF OFF OFF OFF OFF ON OF 126 ON ON ON ON ON ON OFF 127 ON ION ON ON ON JON ON 1 3 2 Baudrate Configuration Baudrate Sw 8 Sw 1 Sw 2 reserved OFF OFF OFF 1200 bps OFF OFF ON 2400 bps OFF ON OFF 4800 bps OFF ON ON 9600 bps ON OFF OFF 19200 bps standard ON OFF ON ON ON 38400 bps ON ON OFF 57600 bps ON ON ON 1 3 3 Parity amp Stop Bits Parity Sw 3 Sw 4 reserved OFF OFF No parity 2 stop bits OFF ON TAA Ao Even parity 1 stop bit ON OFF Odd parity 1 stop bit ON ON ON ON 1 3 4 Physical Interface Interface Type Sw 5 RS 485 OFF RS 232 ON VERRE UU EH 5 Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc Id SCM 1200 091 About the Anybus Communicator for Modbus RTU 14 1 4 Hardware Installation Perform the following steps when physically installing the Anybus Communicator module 1 Snap the gateway on to the DIN rail Th
36. ck will be forwarded from the higher level network to the subnetwork The control system must supply an End or Length character in order for the gateway to know the size of the data block The End or Length character itself may either be forwarded to the subnetwork or discarded e Consume Response Transactions The specified data block is forwarded from the subnetwork to the higher level network The End or Length character will be generated by the gateway automatically if applicable The End or Length character itself may either be forwarded to the higher level network or dis carded Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 Frame Objects 43 To specify the properties of the object select 1t in the Navigation Section enter the desired settings in the Parameter section as follows Parameter Description Byte Swapping No Swapping No swapping will be performed on the data Swap 2 bytes A B C D becomes B A D C e Swap 4 bytes A B C D becomes D C B A Fill unused bytes Enabled Fill unused data with the value specified in Filler byte Disabled Don t fill Filler byte Filler byte value Only used if Fill unused bytes has been enabled Data Location The offset in the internal memory buffer where the data shall be read from written to Object Delimiter Length Character Length character is visible in the internal memory buffer but not on the subnetwork Len
37. cluding the gateway may spontaneously produce or consume a message Nodes do not have to respond to messages nor do they have to wait for a query in order to send one Control System Gateway Subnetwork Devices Consume d Produce Node 1 Produce p Consume Produce p Consume Node 2 Consume d Produce In the figure above the gateway consumes data that is produced by a node on the subnetwork This consumed data can then be accessed from the higher level network This also works the other way around the data received from the higher level network is used to produce a message on the subnet work to be consumed by a node 2 3 5 DF1 Master Mode Please refer to DF 1 Protocol Mode on page 51 Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 Basic Operation 22 2 4 Data Representation on Modbus RTU 2 4 1 General The input and output data areas are mapped to Modbus registers 0 1279 and Coils 0 20479 2 4 2 Supported Function Codes The following function codes are supported Function Code Modbus Function Associated with Area s 1 Read Coil Input and Output Data Area 0x000 Ox3FF 2 Read Input Discretes 3 Read Holding Registers 4 Read Input Registers 5 Write Coil Output Data Area 0x200 Ox3FF 6 Write Single Register 8 Diagnostics 15 Force
38. col Mode on page 51 Theoretically the gateway supports up to 100 transactions The actual number may however be less de pending on the memoty requirements of the defined transactions Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 6 2 Adding amp Managing Transactions Transactions 34 Right click on a node in the Navigation Section to gain access to these functions Function Description Cut Cut a node to the clipboard Copy Copy a node to the clipboard Insert Insert a node from the clipboard Delete Delete a node Node Monitor Launch the node monitor Node Monitor on page 59 Add Transaction s On regular nodes this adds a Query and a Response The two transactions will be grouped in order to increase readability On the Broadcaster a single transaction will be added Add Transaction Consume Add transaction Produce Add a Consume transaction Add a Produce transaction Add Command Insert New Node save Node Insert from File Add predefined transactions to the node Insert a new node above the currently selected one Save the selected node Insert a previously saved node above the currently selected node Rename To increase readability each node can be given a unique name using this function a Only available in Master Mode b Only available in Generic Data Mode Anybus Communicator for Modbus RTU Doc Rev 3 00 38 F
39. con will cause the ABC Config Tool to disconnect from the gt gateway Disconnect Start Logging amp Stop Logging 29 4 2 4l i See Tools on page 25 amp Data Logger on page 63 ak Start Log Stop Log e Subnetwork Monitor Clicking on this icon will launch the subnetwork Monitor see Subnetwork Monitor on page 58 ae e Add Command v This icon is used to add commands to the currently selected node Add Command e Add Mailbox 7 Advanced functionality see Mailbox Editor on page 72 Add Mailbox e Add Node amp Add Broadcaster These icons are used to add nodes to the configuration k Node Broadcaster e Node Monitor Clicking on this icon will launch the Node Monitor see Node Monitor on page 59 Node Monitor e Add Transaction s p m an JE S These icons are used to add transactions to the currently selected node rr Fm Transactions Transaction Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 Chapter 4 4 Basic Settings 4 1 Fieldbus Settings a Select Fieldbus in the Navigation Section to gain access to the parame 2j ABC ters described in this section xn C ub Naetwnrk General During start up the fieldbus interface of the gateway is initialized to fit the configuration created in the ABC Config Tool Optionally some initialization parametets can be set manually to provide better con trol over how the data shall be treated by th
40. ction Add Word Constant Editor which is used to edit transactions and frame objects in a fen sie as A yte Limits mote visual manner For more information see Transaction Edi Add Word Limits tor on page 38 Add DWord Limits Rename Configuration Alphabetic Categorized General Data length 0x0001 Data location 0x0200 Operations O To edit parameters associated with a particular frame object select the frame object in the Navigation Section The settings for that frame object will be displayed in the Parameter Section Byte swap No swapping It is also possible to edit the frame objects in a transaction in a more visual manner using the Transaction Editor see Transac tion Editor on page 38 Data Object Parameters Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 Frame Objects 40 7 3 Constant Objects Byte Word Dword Constant Objects have a fixed value and come in three sizes e Byte 8 bits e Word 16 bits e Dword 32 bits Constants are handled differently depending on the direction of the transaction e Produce Quetry Transactions The gateway will send the value as it is without processing it e Consume Response Transactions The gateway will check if the received byte word dword matches the specified value If not the message will be discarded To set the value of the object select it in the Navigation Section and enter the desir
41. d by the node The data displayed in this section will be refreshed based on the refresh icons in the toolbar For more information see Toolbar Icons on page 62 Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 Node Monitor 61 11 2 1 Pull Down Menu File There is only one entry in this menu s Es Lh This will close the Node Monitor Note however that if the node has Exit been disabled using Stop Node see below it will not resume data exchange until enabled again using Start node Node This menu controls the data exchange for the node This feature can rade help isolate problems associated with a particular node Start Node Stop Node e Start Node Enable the transactions associated with the node e Stop Node Disable the transactions associated with the node Command This menu is used to specify and issue a command manually e Select Command Select a command to be sent to the subnetwotk Command Send Command Select Command Send the specified command to the subnetwork send Command Columns This menu specifies the number of columns in the Monitor Section Columns E Free Free 4 8 Multiple The number of columns depends on the width of the window 8 Multiple The number of columns will be fixed to 8 View This menu specifies the data representation in the Monitor Section m ERN Display the data in hexadecimal format v
42. d their transactions are listed in the middle of the screen B Selecting and de selecting single transactions makes 1t possible to view any combination of allocated data Note The subnetwork monitor has a negative influence on the overall performance of the gateway Therefore the monitor functionality should be used with care Operation Hms Sub network Monitor File Columns Y Y Nodel Node2 Barcodereader Sensor SelectAll Deselect All SelectAll DeselectAll SelectAll Deselect All SelectAll Deselect All Read Coil Status Read Coil Status Transactions 1 v trans actions 1 atus a 32 Mr atus ead Coil Status Out Area 0 bytes 512 General Area 0 bytes 989 C OoOoOoooooooooooooooooooco e Response LE Collision Trigger or Statusbytes Reserved A Start Network amp Stop Network Icons These icons controls the subnetwork activity To stop all subnetwork ier activity click on the red light To start the subnetwork again click on the green light Start B Nodes Transactions To view data blocks associated with a transaction select the transaction in the list The corre sponding data will then appear in the Monitor Section C C Monitor Section This section visualizes how data 1s allocated in the Input Output and General Data areas Color Meaning White Not allocated Yellow Data allocated by a Response or Consume transaction Blue Data allocated
43. e Command Columns View LE 2 738 Wr Command Section Produce Subnetwork Not used In Area 1 bytes 512 Out Area 1 bytes 512 General Area 0 bytes 1022 000 oo Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 Node Monitor 60 11 2 Navigating the Node Monitor Monitor New Node File Node mmand Columns View EES WS Read Coil Status Query Slave Address Function Starting Address Hi Lo Number of points Hi Lo Checksum Value Value Value Error check type Error check start byte 0x0000 0x0000 CRC 0x0000 Read Coil Status Response Slave Address Function Byte count Checksum In Area 4 bytes 512 Out Area 16 bytes 512 General Area 0 bytes 1004 00 00 DO DO DD DD DO DO DO DD 0D DO DO DO DD DD DO DO DO DO n A Pull down Menu amp Toolbar Icons See Pull Down Menu on page 61 and Toolbar Icons on page 62 B Command Section This section holds the currently selected command The individual frame objects in the com mand can be edited in a similar way as in the Transaction and Command Editors C Response Section Master Mode and DF1 Master Mode only This section holds the response to the selected Command z Monitor Section This section displays the data associated with the node Areas in dark grey are reserved for the Status amp Control Registers and areas displayed in light grey represent the data that is use
44. e DIN rail mechanism works as follows To snap the gateway oz first press it downwards 1 to compress the spring in the DIN rail mechanism then push it against the DIN rail as to make it snap on 2 To snap the gateway off push it downwards 1 and pull it out from the DIN rail 2 as to make it snap off from the DIN rail Connect the gateway to the Modbus RTU network Set the Modbus RTU communication settings using the on board switches Connect the gateway to the serial subnetwork Connect the gateway to a free COM port on the PC via the PC cable Connect the power cable and apply power QU Qv UA ge T Start the ABC Config Tool program on the PC Ihe ABC Config Tool software attempts to detect the serial port automatically If not success ful select the correct port manually in the Port menu 8 Configure the gateway using the ABC Config Tool and download the configuration Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 About the Anybus Communicator for Modbus RTU 15 1 5 Software Installation 1 5 1 ABC Config Tool System requirements Pentium 133 MHz or higher 10 MB of free space on the hard drive 8 MB RAM Screen resolution of 800x600 16 bit colour or higher Microsoft Windows NT4 2000 XP Vista 7 32 bit Internet Explorer 4 01 SP1 or newer Installation Anybus Communicator resource CD Insert the CD and follow the on screen instructions If the installati
45. e following entries Select Add the currently selected Command to the node Exit Exit without adding a command to the node Command This menu is used to manage the commands in the list Add Command Add a custom command to the list and open the new command in the Command Editor See also The Command Editor on page 47 Edit Command Edit the currently selected command using the Command Editor See also The Command Editor on page 47 Delete Command Commands 46 e Select Exit Ctrl Q Add Command Edit Command Delete Command Delete the currently selected command from the list Note that some commands are fixed and cannot be deleted 8 2 2 Toolbar Icons The toolbar features icons for the most commonly used functions Add Command Same as Add Command in the Command menu Edit Command Same as Edit Command in the Command menu Delete Command Same as Delete Command in the Command menu Anybus Communicator for Modbus RTU Doc Rev 3 00 Add Command Edit Command Delete Command Doc Id SCM 1200 091 Commands 47 8 3 The Command Editor 8 3 1 General The Command Editor is used to define new commands and edit existing ones This makes it possible to build a library of commands which can be stored and reused at a later stage Note that the Command Editor is somewhat protocol dependent in the sense that certain frame objec
46. e gateway Configuration Alphabetic Categorized E Fieldbus Fieldbus Type Profinet IO The ABC Config Tool supports a wide range of networking sys tems Make sure that this parameter is set to Modbus RTU Fieldbus Type Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 29 4 2 ABC Parameters Select ABC in the Navigation Section to gain access to the parameters e TE described in this section 2j R Sub Network Interface Currently only serial communication is supported Status Control Word See Control and Status Registers on page 67 Value Description Enabled Enable the Control and Status Registers The Data Valid bit in the Control Register must be set to start the subnetwork communication Enabled but no startup lock This setting is similar to Enabled except that the control system is not required to set the Data Valid bit to start the subnetwork communication Disabled This setting completely disables the Control and Status Registers Module Reset This parameter specifies how the gateway will behave in the event of a fatal error Value Description Enabled The gateway will be restarted and no error will be indicated to the user Disabled The gateway will halt and indicate an error Protocol Mode This parameter specifies which protocol mode to use for the subnetwork Value Description Ge
47. e node installing bias resistors on several nodes may compromise the signal quality on the network and cause transmission problems A 4 3 Termination RS485 amp RS422 Only To avoid reflections on the serial lines it is important to properly terminate the subnetwork by placing termination resistors between the setial receivers near the end nodes The resistor value should ideally match the characteristic impedance of the cable typically 100 120R A 4 4 Connector Pinout DB9F Pin Description RS232 RS422 RS485 1 5V Output 100mA max Y v v 2 RS232 Rx v 3 RS232 Tx v 4 reserved 5 female 1 5 Signal Ground Y Y Y 6 RS422 Rx v 7 RS422 Rx Y 8 RS485 D1 RS422 Tx v v 9 RS485 DO RS422 Tx v v housing Cable Shield v v v a Connecting this signal directly to Protective Earth PE of other nodes may in case of grounding loops etc cause damage to the on board serial transceivers It is therefore generally recommended to connect it only to Signal Ground if available of other nodes Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 Connector Pin Assignments 76 A 4 5 Typical Connection RS485 5V RS485 RS485 RS485 RS485 Signal Signal Ground Ground Cable Shield Anybus Communicator Node Node Node Node End Node A 4 6 Typical Connection RS422 4 Wire RS485 5V RS422 Rx gt RS422 Tx m I 1 I RS422 Rx L RS4
48. ed value in the Pa rameter section Parameter Description Value Constant value Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc Id SCM 1200 091 Frame Objects 41 7 4 Limit Objects Byte Word Dword Limit Objects have a fixed range and come in three sizes Byte 8 bits Word 16 bits Dword 32 bits Limit Objects are handled differently depending on the direction of the transaction Produce Query Transactions This object shall not be used for such transactions value will be undefined Consume Response Transactions The gateway will check if the received byte word dword fits inside the specified boundaries If not the message will be discarded There are 3 types of interval objects Byte 8 bit interval Word 16 bit interval Dword 32 bit interval To set the range of the object select it in the Navigation Section and enter the desired range in the Pa rameter section as follows Parameter Description Maximum Value This is the largest allowed value for the range Range 0x00 OxFFh byte 0x0000 OXFFFFh word 0x00000000 OxFFFFFFFFh dword Note Value must be larger than the Minimum Value below Minimum Value This is the smallest allowed value for the range Range 0x00 OxFEh byte 0x0000 OXFFFEh word 0x00000000 OxFFFFFFFEh dword Note Value must be less than the Maximum Value above Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc Id SCM 1
49. ently processing query 4 Switch Status Off Normal operation Red Invalid configuration switch setting 5 Subnet Status Of Power off Green flashing Running correctly but one or more trans action error s have occurred Green Running Red Transaction error timeout or subnet stopped 6 Device Status Off Power off Alternating Red Green Invalid or missing configuration Green Initializing Green flashing Running Red Bootloader mode Red flashing If the Device Status LED is flashing in a sequence starting with one or more red flashes please note the sequence pattern and contact the HMS support department a This led turns green when all transactions have been active at least once This includes any transactions using change of state or change of state on trigger If a timeout occurs on a transaction this led will turn red b The gateway is in bootloader mode and firmware must be restored in order for it to work properly Start up the ABC Config Tool and connect to the Anybus Communi cator Choose Tools Options ABC Click Factory Restore to restore firmware See Tools on page 25 Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc Id SCM 1200 091 About the Anybus Communicator for Modbus RTU 13 1 3 Configuration Switches The configuration switches determines the basic communication settings for the Modbus interface Normally these switches are covered by a plas tic hat
50. er byte Disabled option affects the data that is sent Noscanning Response rigger byte acess DICSIT out to the subnetwork Offline options for The action to take for this service Clear subnetwork if the subnetwork goes offline Freeze This option affects the data that is reported to the fieldbus master Update mode The update mode for this service Cyclically On data change Single shot Change of state on trigger Timing Parameter Description Default Retries The number of times to resend this service before the node is disconnected 3 Timeout time 10 ms The time to wait before resending this service in steps of 10 ms 1000 ms Update time 10 ms The minimum time between two services of this kind in steps of 10 ms 1000 ms a The default value is given as 100 in the parameter window Each change of 10 ms either increases or decreases this value by 1 i e 99 represents a poll time of 990 ms and 101 represents a poll time of 1010 ms Trigger Parameter Description Default Request Trigger byte The memory location of the trigger byte this service uses for updates on trigger Ox05FF address byte changes Response Trigger byte Enables disables the trigger byte Disabled Response Trigger byte The memory location of the trigger byte this service uses for updates on trigger Ox05FF address byte changes Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc Id SCM 1200 091 DF1 Protocol Mode
51. ers in the parameter section will be greyed out and cannot be edited directly In Master Mode ABC Config Tool comes preloaded with commands for most common Modbus RTU functions Additional commands can easily be added using the Command Editor see The Command Editor on page 47 For DF1 Master Mode see Services on page 54 In Generic Data Mode no pre defined commands exist but custom ones may be implemented as desired 8 2 Adding amp Managing Commands To add a command to a node right click on the node in the Navigation Section and select Add Com mand A list of commands will appear Select Command x Ele Command Dg Command Name Select the desired command in the list and select Add Command Command Name in the Command menu The specified command will be added Read Input Status Read Holing Registers to the node set Sing i ele iE Just like other transactions the frame objects of added command xU x0B Fetch Comm Event Ctr Fetch Comm Event Log may be edited in the Navigation Parameter Section or using the Force Multiple Coils SieveD Transaction Editor Note however that certain frame objects may rite 4X Register be locked for editing ead Write 4X Registers ad FIFO Queue 0x99 My Custom Command 1 0 My Custom Command 2 Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 8 2 1 Pull Down Menu File This menu features th
52. ettings are set up automatically by the gateway However advanced users can configure the Anybus S card for specific features This chapter assumes that the reader is fa miliar with the Anybus S and it s application interface For more information about the Anybus S plat form consult the Anybus S Parallel Design Guide The standard initialization parameters are determined by the subnetwork configuration Information about the amount of input and output data used for subnetwork communication is used by ABC Config Tool to create the configuration message that sets the sizes of the input and output data areas in the Dual Port RAM of the embedded Anybus S interface It is possible to add fieldbus specific mailbox messages to customize the initialization This is done in the Mailbox Editor see below A mailbox message is a HMS specific command structure used for low level communication with an Anybus S interface Consult the Anybus S Parallel Design Guide and the fieldbus appendix for the de sired fieldbus for further information 15 2 Mailbox Editor 88 Fieldbus To add a mailbox message to the configuration right click on atartinit c D c gt a Field ifi EndInit and select Insert New Mailbox e Fieldbus specific Pal Insert New Malbox xw Sub Network A mailbox message consists of a Header sec germ all tion and a data section where the Header con sists of 16 words 32 bytes and the data section consists of up t
53. f line This affects the data that is reported to the control system Clear Data is cleared 0 on the higher level network if the subnetwork goes offline Freeze Data is frozen on the higher level network if the subnetwork goes offline Reconnect time 10ms Retries This parameter specifies how long the gateway shall wait before attempting to reconnect a dis connected node A node will be disconnected in case the maximum number of retries below has been reached The unit is milliseconds ms and the entered value is multiplied by 10 which means that the shortest time is 10 ms Note This setting is not relevant for the Broadcaster node This parameter specifies how many times a timeout may occur in sequence before the node is disconnected Timeout time 10ms This parameter specifies how long the gateway will wait for a response from a node If this time is exceeded the gateway will re transmit the Query until the maximum number of retries see above has been reached The unit is milliseconds ms and the entered value is multiplied by 10 which means that the shortest time is 10 ms Anybus Communicator for Modbus RTU Doc Rev 3 00 Trigger byte address This parameter specifies the location of the trigger byte in internal memory only relevant when Update mode is set to Change of state on trigger Update mode This parameter is used to specify when the transaction shall be sent to the slave e
54. gger byte address parameter below Trigger byte address This parameter specifies the location of the trigger byte in the internal memory buffer Valid settings range from 0x000 Ox1FF and 0x400 OXNNN 6 4 Transaction Parameters Generic Data Mode 6 4 1 Produce Transactions To gain access to these parameters select a Produce Transaction in the Navigation Section Parameter Offline options for fieldbus Description This parameter specifies the action to take for this transaction if the higher level net work goes offline This affects the data that is sent to the subnetwork Clear Data is cleared 0 on the subnetwork if the higher level network goes offline Freeze Data is frozen on the subnetwork if the higher level network goes offline NoScanning Stop subnet scanning for this transaction if the higher level network goes offline Update mode Update time 10ms Anybus Communicator for Modbus RTU Doc Rev 3 00 The update mode for the transaction Cyclically The transaction is sent cyclically at the interval specified in the Update Time parameter On data change The data area is polled for changes at the time interval defined by Update time A transaction is issued when a change in data is detected Single shot The transaction is sent once at startup Change of state on trigger The transaction is sent when the trigger byte has changed This feature enables the contro
55. gs Value Description Depend This setting is only relevant for Responses in Master Mode The value will be retrieved from the corresponding part of the Query transaction Id The value will be retrieved from the Command ID setting see Basic Navigation on page 47 User The settings associated with the object can be edited by the user SlaveAddress The value will be retrieved from the SlaveAddress parameter see Node Parameters on page 32 other settings Other settings are no longer supported Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc Id SCM 1200 091 Commands 50 8 3 5 Example Specifying a Modbus RTU Command in Master Mode In the following example a Modbus RTU command is created in Master Mode In Modbus RTU a transaction always feature the following parts e Slave Address 1 byte e Function Code 1 bytes e A data field e CRC CRC 16 Furthermore each command always consists of a query and a response e Example Query DisplayName Slave Address Function Data Checksum Object Type Byte Object Byte Object Data Object Checksum Object Value SlaveAddress ID User User The value of this byte The value of this byte The size and location The checksum type constant will be set using the SlaveAd dress parameter see Node Parameters on page 32 e Example Response Response DisplayName Slave Address constant will be set
56. gth Character Visible The length character is visible both in the internal memory buffer and on the subnetwork End Character The end character is visible in the internal memory buffer but not on the subnetwork End Character Visible The end character is visible both in the internal memory buffer and on the subnetwork No Character No End or Length character is generated in the internal memory buffer End Character Value End Character value Maximum Data Length The maximum allowed length in bytes of the variable data object If the actual length of the data exceeds this value the message will be discarded The value must not exceed 300 bytes which is the maximum data length allowed for one frame a Only relevant for Consume Response transactions b Only used if Object Delimiter is set to End Character or End Character Visible Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc Id SCM 1200 091 Frame Objects 44 7 7 Checksum Object Most serial protocols features some way of verifying that the data has not been corrupted during trans fer The Checksum Object calculates and includes a checksum in a transaction Parameter Description Error Check Start byte This parameter specifies the byte offset in the transaction to start checksum calculations on Error Check Type This parameter specifies which type of algorithm to use Anybus Communicator for Modbus RTU Doc Rev 3 00 e
57. he Anybus Communicator for Modbus RTU acts as a gateway between virtually any serial application protocol and a Modbus RTU based network Integration of industrial devices is enabled without loss of functionality control and reliability both when retro fitting to existing equipment as well as when set ting up new installations 48 Modbus RTU Master e g a PLC 408 Modbus RTU Master e g a PLC INVERTER INVERTER Modbus RTU Network Modbus RTU Network PC configuration and monitoring PC configuration and monitoring Multi drop up to 31 nodes Serial communication o device Serial communication devices Single Node Serial Sub Network Multi Node Serial Sub Network Subnetwork The gateway can address up to 31 nodes and supports the following physical standards e RS 232 e RS 422 e RS 485 Modbus RTU Interface Modbus RTU connectivity is provided through patented Anybus technology a proven industrial com munication solution used all over the world by leading manufacturers of industrial automation products e Galvanically isolated bus interface e Coil and Register access e RS 232 or RS 485 operation e On board configuration switches e 1200 57600bps operation Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 About the Anybus Communicator for Modbus RTU 11 1 1 External View For wiring and pin assignments see Connector Pin Assignments on page 73
58. icator for Modbus RTU Doc Rev 3 00 Appendix A female Doc ld SCM 1200 091 Connector Pin Assignments 74 A 3 PC Connector Configuration Cable Wiring DP9F PC RJ11 ABC RJ11 4P4C modular ABC Pin Description 1 Signal ground 2 3 RS232 Rx Input 4 RS232 Tx Output DB9F PC Pin Description q 2 RS232 Rx Input 5 female 1 3 RS232 Tx Output 4 5 Signal Ground 6 9 1 The RJ11 4P4C modular is sometimes referred to as an RJ9 Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 Connector Pin Assignments 75 A 4 Subnetwork Interface A 4 1 General Information The subnetwork interface provides for RS232 RS422 and RS485 communications Depending on the configuration specified in the ABC Config Tool different signals are activated in the subnetwork con nectot A 4 2 Bias Resistors RS485 Only When idle RS485 enters an indeterminate state which may cause the serial receivers to pick up noise from the serial lines and interpret this as data To prevent this the serial lines should be forced into a known state using pull up and pull down resistors commonly known as bias resistors The bias resistors form a voltage divider forcing the voltage between the differential pair to be higher than the threshold for the serial receivers typically gt 200mV Note that bias resistors shall only be installed on on
59. ieldbus A ABC zw Sub Network TP E N Cut Copy Insert Delete Node Monitor Add Transaction Consume Add Transaction Produce Add Command Insert New Node Save Node Insert from File Rename Doc Id SCM 1200 091 Transactions 35 6 3 Transaction Parameters Master Mode 6 3 1 Parameters Query 8 Broadcast To gain access to these parameters select a Query or Broadcast transaction in the Navigation Section Parameter Minimum time between broadcasts 10ms Description This parameter specifies how long the gateway shall wait after transmitting a broadcast trans action before processing the next entry in the scanlist The value should be set high enough to allow the slave devices time to finish the handling of the broadcast The unit is milliseconds ms and the entered value is multiplied by 10 which means that the shortest time is 10 ms Note This setting is only relevant for the Broadcaster node Offline options for field bus This parameter specifies the action to take for this transaction if the higher level network goes off line This affects the data that is sent to the subnetwork Clear The data destined for the slave devices is cleared set to zero Freeze The data destined for the slave device is frozen NoScanning The updating of the subnetwork is stopped Offline options for sub network This parameter specifies the action to take for this transaction if the subnetwork goes of
60. if the Control Status Registers are set as Enabled 12 Execute Command If set the specified command will be executed by the gateway see below 11 8 Control Code This field holds commands which can be executed by the gateway see below 7 0 Data See also Control Codes in Master Mode and DF1 Master Mode on page 71 Control Codes in Generic Data Mode on page 71 Note Internally this is treated as a Motorola format word i e MSB first If the higher level network uses a different byte order the upper and lower bytes will appeat to be swapped 14 3 2 Control Codes in Master Mode and DF1 Master Mode Ihis table is valid only in Master Mode and DF1 Master Mode Code Instruction Data Description 0x00 Disable Node Actual node address Disables the specified node 0x01 Enable Node Actual node address Enables a previously disabled node 0x02 Enable Nodes Actual number of nodes to enable Enables the specified number of nodes start ing from the first node in the configuration Remaining nodes will be disabled 14 3 3 Control Codes in Generic Data Mode No Control Codes are currently supported in this mode Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc Id SCM 1200 091 Chapter I5 15 Advanced Fieldbus Configuration 15 1 General The fieldbus interface of the gateway consists of an embedded Anybus S communication interface Nor mally the Anybus S configuration s
61. l system to notify the gateway when to issue a particular transaction To use this feature correctly the control system must first update the data area asso ciated with the transaction then increase the trigger byte by one The location of the trigger byte is specified by the Trigger byte address parameter This parameter specifies how often the transaction will be issued in steps of 10ms only relevant when Update mode is set to Cyclically Doc Id SCM 1200 091 Parameter Trigger byte address Transactions 37 Description This parameter specifies location of the trigger byte in the internal memory buffer If Update mode is set to Change of state on trigger the memory location specified by this parameter is monitored by the gateway Whenever the trigger byte is updated the gateway will produce the transaction on the subnetwork This way the control system can instruct the gateway to produce a specific transac tion on the subnetwork by updating the corresponding trigger byte The trigger byte should be incremented by one for each activation Please note that the trigger byte address must be unique to each transaction lt can not be shared by two or more transactions Note This parameter has no effect unless the Update mode parameter is set to Change of state on trigger 6 4 2 Consume Transactions To gain access to these parameters select a Consume Transaction in the Navigati
62. me without lo sing any set network via the Communicator Wizard Modbus RTU Master Version 1 14 Revision 1 1 1 1 e ieldbus Mas tings by clicking Previous SERES Step 2 Physical Settings ws Wizard Modbus RTU Master Select the physical properties of the sub Physics sandea sz z Step 2 of 6 Bitrate bis s 3600 Select sub network netw ork properties Parity None y s Data bits g Click Next to continue es z This is where the properties for the sub network are selected Please see the sub network device s manual to determine the appropriate settings for a particular serial device St 3 6 Back Please see the manual for the e ps sub network device to determine Consult the online help system for fur ther information Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 Chapter 14 14 Control and Status Registers 14 1 General The Control and Status Registers are disabled by default but can be enabled using the ABC Config Tool see Status Control Word on page 29 These registers form an interface for exchanging status in formation between the subnetwork and the fieldbus control system The main purpose of these registers is to e Report subnetwork related problems to the fieldbus control system e Ensure that only valid data is exchanged in both directions Enable the fieldbus control system to start stop data exchange with selected nodes on the sub
63. meter value may be specified either using a selec tion box or manually depending on the parameter itself Values can be specified in decimal form e g 42 or in hexadecimal format e g Ox2A D Information Section This section holds information related to the currently se lected parameter Anybus Communicator for Modbus RTU Doc Rev 3 00 Config Line QA This menu entry is expanded Eg Fieldbus lt A Starthnit nia Fieldbus specific Sub entries ind nda Endlnit Aa ABC This menu entry holds additional sub entries parameters Configuration Alphabetic Categorized E Communication Bitrate bits s Data bits Parity Physical standard Start bits Stop bits E Timing Message delimiter 10ms Parameter Section Message delimiter 10ms The time between transaction Information Section Doc ld SCM 1200 091 3 1 1 Pull down Menu File This menu features the following entries e New Create a new configuration See also Configuration Wizards on page 66 e Open Open a previously created configuration e Save Save the current configuration e Save As Save the current configuration under a new name e Print Navigating the ABC Config Tool 24 Mew Open Save Save ds Print Properties Exit Ctrl N Ctri O Ctri 5 Ctri P Send details about the current configuration to a printer e Properties This b
64. ne as described below A Offline No data exchange 1 Clear the Data Valid bit in the Con trol Register A Offline no data exchange 2 Write initial data to the Output Area according to the subnetwork configu ration 3 Wait until the fieldbus control system 5 Online not yet exchanging data and the gateway are online on the field bus network and shift to state B B Online Not yet exchanging data 4 Wait until the Data Valid bit in the Status Register is cleared by the gate C way Online F Le exchanging data 5 Set the Data Valid bit in the Control Register 6 When the Data Valid bit in the Status Register is set by the gateway shift to state C 7 If the gateway goes offline on the fieldbus shift to state A C Online Exchanging data Exchanging valid data in both directions If the gateway goes offline on the fieldbus shift to state A Note The gateway cannot spontaneously clear the Data Valid bit in the Status Register Latency The Data Valid bit in the Status Register may in some cases be delayed This latency can be caused by a missing node or a bad connection to a node with a long timeout value assigned to it Therefore the fieldbus control system should not wait for this bit to be set before communicating with the subnetwork devices it should be considered as an aid for the fieldbus control system to know when all data has been updated
65. neric Data Mode This mode is primarily intended for Produce amp Consume based protocols where there are no Master Slave relationship between the gateway and the nodes on the subnetwork Master Mode This mode is intended for Query amp Response based protocols where a single Master exchanges data with a number of Slaves DF1 This mode is intended for the DF1 protocol The Anybus Communicator can only be con figured as a Master with half duplex communication Note This is the only mode available if you intend to configure an ABC module for DF1 See also Protocol Modes on page 19 Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 30 Statistics The Transmit and Receive Counters indicate how many transactions that have successfully been ex changed on the subnetwork This feature is primarily intended for debugging purposes e Receive Counter Location Specifies the location of the Receive Counter in the internal memory buffer e Transmit Counter Location Specifies the location of the Transmit Counter in the internal memory buffer Both counters are enabled by setting Statistics to Enabled Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc Id SCM 1200 091 31 4 3 Subnetwork Parameters Fieldbus A ABC ES al Sub Netwark To gain access to the parameters described in this section select Subnet work in the Navigation Section Communication
66. o 128 words 256 bytes All fields are editable except the Mes sage information field that is fixed to 0x4002 which means that only fieldbus specific mail box messages can be entered here a The mailbox message is presented as two col umns one contains header information A Allowuserto enable disable the other one contains the message data B To add message data simply change the Data size parameter in the header column A and the corresponding number of bytes will ap pear in the message data column B For more information about fieldbus specific mailbox messages consult the separate Anybus S Fieldbus Appendix for the fieldbus you are using For general information about the Anybus S platform consult the Anybus S Design Guide Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 A Connector Pin Assignments A 1 Fieldbus Connector Modbus RTU Pin Signal Description Housing Shield Bus cable shield connected to PE 1 2 TxD Transmit data RS 232 3 RxD Receive data RS 232 4 5 GND Ground galvanically isolated 6 5V 5V galvanically isolated 7 B RS 485 DO B line 8 A RS 485 D1 A line 9 Not connected A 2 Power Connector Pin Description 1 24V DC 2 GND Notes e Use 60 75 or 75XC copper CU wire only The terminal tightening torque must be between 5 7 lbs in 0 5 0 8 Nm Anybus Commun
67. oc ld SCM 1200 091 Commands 48 8 3 3 Pull down Menu File This menu features the following entries e Apply Changes L3 Save changes and exit to the main window Apply Changes Exit Exit Ctri Q Exit without saving Column The functions in this menu alters the structure of the command Append Column Column h Add another column to the command Append Column Insert Column Shift Ins Delete Column Shift Del e Insert Column Insert a column at the selected position e Delete Command Delete the column at the selected posi tion Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 Commands 49 8 3 4 Editing a Command As mentioned previously the transaction section in the Command Editor represents the actual transac tions associated with the command Each column represents a frame object within the transaction Each column features four rows with the following parameters e Query Response Produce Consume The upper right cell indicates the direction of the transaction e DisplayName Each column can be named so that the different parts of the command appears in a more user friendly manner when editing its settings in the Transaction Editor or in the Parameter Section of the Main Window e ObjectType This row specifies the type of frame object that shall be used for the column e Value This row specifies where the frame object shall retrieve its value settin
68. of 10ms If set to 0 zero the gateway will use the standard Modbus delimiter of 3 5 characters the actual number of ms will be calculated automatically based on the currently used communication settings e Generic Data Mode The Message Delimiter specifies the time that separates two messages in steps of 10us Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 5 Nodes 5 1 General Chapter 5 In ABC Config Tool a node represents a single device on the network While the gateway doesn t fea ture a scanlist in the traditional sense all nodes and their transactions will be processed in the order they have been defined in the ABC Config Tool The maximum number of nodes that can be created in the ABC Config Tool is 31 5 2 Adding amp Managing Nodes Right click on Sub Network in the Navigation Section to gain access to these functions Function Paste Description Paste a node from the clipboard z Subnetwork Monitor Launch the subnet monitor Subnetwork Monitor on page 58 Subnetwork Status Add Node Add a node to the configuration Add Broadcaster Add a broadcaster node to the configuration Load Node Add a previously saved node View diagnostic information about the subnetwork a This function is only available in Master Mode 5 3 Node Parameters 5 3 1 Master Mode and Generic Data Mode To gain access to the parameters described in this sec
69. on gg Fieldbus A ABC Sub Network Y Nodel Read Coil Status Query El Response CJ Diagnostics E Query LE Response T Node2 Sensor TT Barcodereader SelectAll DeselectAll a Transactions 1 mms Frame Editor Cox Fie Slave Address Function Starting Address Hi Lo Number of points Hi Lo Checksum Value Value Value Value Error check type Error check start byte 0x0000 Ox0000 CRC 0x0000 Alphabetic Categorized Sensor Transactions 1 2005 10 27 09 39 Config Line YA Response Trigger or Statusbytes Reserved lll Collision Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 Basic Operation 17 2 2 Data Exchange Model Internally the data exchanged on the subnetwork and the data exchanged on the higher level network resides ABC Internal Memory in the same memoty A This means that in order to exchange data with the sub gt Input Data network the higher level network simply reads and 512 bytes writes data to memory locations specified using the ABC Config Tool The very same memoty locations can then be exchanged on the subnetwork The internal memory buffer is divided into three areas gt Output Data 512 bytes based on their function e Input Data 512 bytes Sub Network This area can be read by the higher level net work in this case Modbus RTU Higher Level Network e Output Data 512
70. on Section Parameter Offline options for subnetwork Description This parameter specifies the action to take for this transaction if the subnetwork goes offline This affects the data that is sent to the higher level network Clear Data is cleared 0 on the higher level network if the subnetwork goes offline Freeze Data is frozen on the higher level network if the subnetwork goes offline Offline timeout time 10ms Trigger byte Trigger byte address Anybus Communicator for Modbus RTU Doc Rev 3 00 This parameter specifies the maximum allowed time between two incoming mes sages in steps of 10ms If this time is exceeded the subnetwork is considered to be offline A value of 0 disables this feature i e the subnetwork can never go offline Enable Enables the trigger byte The location of the trigger byte must be specified in the Trigger byte address below The trigger byte value will be increased each time a valid transaction has been consumed by the gateway This feature enables the control system to be notified each time new data has been consumed on the subnetwork Disable Disables the trigger byte functionality This parameter specifies the location of the trigger byte in the internal memory buffer Valid settings range from 0x000 Ox1FF and 0x400 OXNNN Please note that the trigger byte address must be unique to each transaction It can not be shared by two or more transactions Doc Id SC
71. on does not start automati cally right click on the CD drive icon and select Explore Execute setup exe and follow the on screen instructions From website Download and execute the self extracting exe file from the HMS website www anybus com Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc Id SCM 1200 091 Chapter 2 2 Basic Operation 2 1 General The Anybus Communicator gateway is designed to exchange data between a serial subnetwork and a higher level network in this case Modbus RTU Unlike most other gateway devices of similar kind it does not have a fixed protocol for the subnetwork and can be configured to handle almost any form of serial communication The gateway can issue serial telegrams cyclically on change of state or based on trigger events issued by the control system of the higher level network i e the fieldbus master or PLC It can also monitor cer tain aspects of the subnetwork communication and notify the higher level network when data has changed An essential part of the Anybus Communicator package is the ABC Config Tool a Windows appli cation which is used to supply the gateway with a description of the subnetwork protocol No program ming skills are required instead a visual protocol description system is used to specify the different parts of the serial communication mms ABC Config Tool Untitled DOR File Transactions1 Tools View Help osa x Devices Configurati
72. on is supported Status Control Word See Control and Status Registers on page 67 VENTE Description Enabled Enable the Control and Status Registers The Data Valid bit in the Control Register must be set to start the subnetwork communication Enabled but no startup lock This setting is similar to Enabled except that the control system is not required to set the Data Valid bit to start the subnetwork communication Disabled This setting completely disables the Control and Status Registers Module Reset This parameter specifies how the gateway will behave in the event of a fatal error VENTE Description Enabled The gateway will be restarted and no error will be indicated to the user Disabled The gateway will halt and indicate an error Protocol Mode This parameter specifies which protocol mode to use for the subnetwork ELITS Description DF1 This mode is intended for the DF1 protocol The Anybus Communicator can only be con figured as a Master with half duplex communication Note This is the only mode available if you intend to configure an ABC module for DF1 See also Protocol Modes on page 19 Statistics The Transmit and Receive Counters indicate how many transactions that have successfully been ex changed on the subnetwork This feature is primarily intended for debugging purposes e Receive Counter Location Specifies the location of the Receive
73. on of this standard or be limited to the use of specific Modbus commands other than the ones used by this wizard In all cases the user should consult the documentation of the devices that shall be used on the subnetwork for information about their serial communication requirements and if necessary contact the manufacturer of the device to obtain further informa tion about the serial communication protocol In the event that the wizard doesn t handle a particular Modbus command required by a device it is possible to specify this command manually as a transaction in the ABC Config Tool Using this wizard involves the following steps a Wizard Modbus RTU Master Step 1 Communicator Type SIUE die Select the fieldbus gt Fieldbus Type type Select Modbus RTU s i Y il The type M connected to the E a a a Communicator The purpose of this wizard is to help you through the process of gt e creating a project with a Modbus Click Next to continue F RTU sub network When the G9Anybus FIPIO Wizard is finished it is possible to Master Mode Modbus Plus continue editing the project in the Configuration Tool Tip It 1S po SS ible to return to a previous A Lp Modbus TCP The fieldbus is the higher layer LY 9 Ethemet IP 3 network that communicates with Installation Wizard mE the serial device s on the sub menu at any ti
74. ouble words Data length The number of bytes read from the DF1 network to write to the area determined lt Size by the Offset parameter Offset The offset in the internal memory buffer in the module where the data shall be read See Memory Map on page 17 Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc Id SCM 1200 091 9 8 Read Data This service is used to read data from the nodes in the subnetwork ABC DF 1 Master Untitled Configuration Alphabetic Categorized E Comman d Params File Type Siz e E Data Options ine options for fieldbus Clear ine options for sub network Clear Update mode Cyclically 3 100 Update time 10ms 100 E Trigger Request Trigger byte address O O05FF Resnonse Trinner hute Misahled Type The file type of the data file to be accessed DF1 Protocol Mode 57 2010 05 07 10 55 Config Line Command Parameters Parameter Description Element Number The element number of the data file to be accessed within the slave Valid settings PLC 5 0 999 SLC500 0 255 MicroLogix 0 255 File number The file number of the data file to be accessed PLC 5 3 7 8 10 999 SLC500 3 7 8 10 255 MicroLogix 3 7 8 10 255 File type The file type of the data to be accessed Integer Bit Float Size The number of bytes to read from the slave One bit integer element is 2 bytes and one float element is 4 bytes The parameter must h
75. ransactions has Counter Updated increased See also Consume Transactions on page 37 Offline timeout time 0x03 Buffer Overrun Warning A node returned more data than expected or the gate way was unable to finish processing a message prior to receiving a new one 0x04 Other Error Error Undefined error Ox1F No Error Warning No errors Note Conditions of type Error will eventually be followed by a No Error condition when the cause no longer is detected Conditions of type Warning are however considered informational and may not necessarily be followed by a No Error condition later on Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc Id SCM 1200 091 Control and Status Registers 71 14 3 Control Register Contents Control System to Gate way 14 3 1 General Information The Control Register is 1 enabled located at 0x200 0x201 and constitutes a bit field as follows bit s Name Description 15 Confirm These bits control the handshaking towards the gateway CR_HS_CONFIRM 14 Send See also CR_HS_SEND Handshaking Procedure on page 67 Status Register Contents Gateway to Control System on page 69 13 Data Valid This bit controls data consistency see Data Consistency on page 68 1 Output Area valid exchange data on the subnetwork 0 Output Area not valid do not exchange data on the subnetwork Note This bit is only relevant
76. ration and defines the data that is sent and received on the subnetwork User Person or persons responsible for installing the Anybus Communicator Higher Level Network In this case Modbus RTU Network Fieldbus Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc Id SCM 1200 091 Support About This Document P 9 For technical support consult the online FAQ www anybus com or contact the nearest support center HMS Sweden Head Office E mail support hms networks com Phone 46 0 35 17 29 20 Fax 46 0 35 17 29 09 Online www anybus com HMS North America E mail us support hms networks com Phone 1 312 829 0601 Toll Free 1 888 8 Anybus Fax 1 312 629 2869 Online www anybus com HMS Germany E mail ge support hms networks com Phone 49 721 96472 0 Fax 49 721 964 7210 Online www anybus com HMS Japan E mail jp support hms networks com Phone 81 45 478 5340 Fax 81 45 476 0315 Online www anybus com HMS China E mail cn support hms networks com Phone 86 10 8532 3023 Online www anybus com HMS Italy E mail it support Whms networks com Phone 39 039 59662 27 Fax 39 039 59662 31 Online www anybus com HMS France E mail fr support hms networks com Phone 33 0 3 89 32 76 41 Fax 33 0 3 89 32 76 31 Online www anybus com Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 Chapter 1 1 About the Anybus Communicator for Modbus RTU T
77. rings out the following window Item Description Select a Name for the A name for the configuration Configuration may be entered here Download Password 6 These fields can be used to Upload Password 6 password protect the configu ration in the gateway CAUTION Always keep a copy of the password in a safe place A lost password cannot be re trieved e Exit Close the ABC Config Tool Anybus Communicator for Modbus RTU Doc Rev 3 00 Download Password 6 ms Name the Configuration Select a Name for the Confiquration My confiquration Upload Password 6 mam Doc Id SCM 1200 091 Navigating the ABC Config Tool 25 Tools This menu features the following entries This entry selects the COM port used Port d for the configuration of the gateway Upload configuration from ABC e Upload configuration from ABC Down load configuration to ABC Upload the configuration from the Start Logging gateway to the ABC Config Tool Options e Download configuration to ABC Download the current configuration into the gateway e Start Logging Start the Data Logger see Data Logger on page 63 Note that when the Data Logger is active this menu entry is changed to Stop Logging e Options This will bring out the following window Item Description Warning on Delete A confirmation dialog is displayed each BEES time something is deleted nic MA Warning on unsa
78. s this value by 1 e 9 represents a poll time of 90 ms and 11 represents a poll time of 110 ms b The default value is given as 100 in the parameter window Each change of 10 ms either increases or decreases this value by 1 e 99 represents a poll time of 990 ms and 101 represents a poll time of 1010 ms Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc Id SCM 1200 091 9 4 Node Parameters To gain access to the parameters described in this section select a node in the navigation section For more information about nodes see Nodes on page 32 amp ABC Config Tool Untitled File Node 1 Tools View Help ABC DF 1 Master Untitled Devices Fieldbus ABC el Subnetwork TUN TT Node 2 Configuration Alphabetic Categorized E General Checksum CRC Slave address 2 Type PLC 5 Slave address The address of the slave 2010 05 07 10 38 Config Line 8 DF1 Protocol Mode 54 Fieldbus ABL uu 5 ubnetwork ZI 1 Node 2 Parameter Description Valid Settings Checksum Selects the type of checksum on the network BCC CRC default Slave Address The value entered here sets the node address 0 254 Type The PLC type of the slave PLC 5 SLC500 MicroLogix 9 5 Services Services are commands that can be stored and reused The user configures each slave with services that can be issued from the master A total of 50 services are allowed The Anybus Communicator supports a
79. selection of DF1 commands When the gateway is going to ex ecute a service it automatically chooses the appropriate DF1 command s that are used to perform the service on the selected DF1 node type Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc Id SCM 1200 091 DF1 Protocol Mode 55 9 5 1 Available Services Right click on the node and choose Add Command c A pop up window will show the four different servic ey Select Command es that are available File Command e Integrity check ime e Read diagnostics pm ere e Read data e Write data Integrity Check 002 Read Diagnostics O03 Read Data Ox04 Write Data E E E E A maximum of 50 services in total for all nodes can be selected The predefined setvices can be configured to suit the application Select a service to show the parameters General Configuration Parameters These parameters are common to all services but the settings are individual to each instance of a service Configuration Alphabetic Categorized E General Offline options for fieldbus Clear Offline options for sub network Clear Gener al Update mode Cyclically E Timing LM NUM Retries 3 Parameter Description Valid settings Timeout time 10ms 100 i Update time 10rms 100 Offline options for The action to take for this service Clear E Trigger i Request Trigger byte address OxD5FF fieldbus if the fieldbus goes offline This Freeze Response Trigg
80. sumes no responsibility for any errors that may appear in this document There are many applications of this product Those responsible for the use of this device must ensure that all the necessary steps have been taken to verify that the applications meet all performance and safety requirements in cluding any applicable laws regulations codes and standards HMS Industrial Networks AB will under no circumstances assume liability or responsibility for any problems that may arise as a result from the use of undocumented features timing or functional side effects found outside the documented scope of this product The effects caused by any direct or indirect use of such aspects of the product are undefined and may include e g compatibility issues and stability issues The examples and illustrations in this document are included solely for illustrative purposes Because of the many variables and requirements associated with any particular implementation HMS Industrial Networks AB cannot assume responsibility for actual use based on these examples and illustrations Intellectual Property Rights HMS Industrial Networks AB has intellectual property rights relating to technology embodied in the product de scribed in this document These intellectual property rights may include patents and pending patent applications in the US and other countries Trademark Acknowledgements Anybus 0 is a registered trademark of HMS Industrial Networks AB All o
81. the ABC Config Tool 12 2 Operation Start amp Stop Logging e Start logging Select Start Logging in the Tools menu ABC Config Tool will then prompt for the desired mode of operation see below e Stop logging Select Stop Logging in the Tools menu This will open the log window see below Modes of Operation Select the desired mode of operation and click OK to start logging data e Log until full Data will be logged until the log buffer is full Select Log Mode Log until full e Log continuously Data will be logged continuously until logging is stopped by clicking Stop Logging The log buffer will contain the most recent data Log Window The logged data is displayed in hexadecimal decimal and AS CII format for both directions The time between the log en tries is displayed in a separate column The data may optionally be saved in ASCII text format by clicking Create Text file Click Close to exit x zj se E Create Text file Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 Data Logger 64 12 3 Configuration By default the log buffer can hold 512 bytes of data in each i Hms Options direction To specify a different size for the buffer select Options in the Tools menu Size oflogbufer iE Oo aw Firmware Download A window with various settings will appear Select the ABC RUE
82. ther trademarks are the property of their respective holders Warning This is a class A product in a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures ESD Note This product contains ESD Electrostatic Discharge sensitive parts that may be damaged if ESD control procedures are not followed Static control precautions are required when handling the prod uct Failure to observe this may cause damage to the product Modbus RTU protocol mode for Anybus Communicator Rev 3 00 Copyright HMS Industrial Networks AB Feb 2011 Doc Id SCM 1200 091 Table of Contents Table of Contents Preface About This Document Rented DOCUS A A UH isons 7 Document hlstot A A A A A R Y Conventions cc Lerminol08 aaa ada 8 COS Ay ic aca aa I ad 8 SUP PO ri iii 9 Chapter 1 About the Anybus Communicator for Modbus RTU Externa Vii dad 11 EAN ERE 12 COMMGOU LATION SWIC Hes dida 13 NOLE NAT OSS etc E A tate ee teats 13 Banor are 8 CONSTA RENE RE 13 Tani 8705 DIE AAA A 13 Porca TUN E AM deco 13 Hardware Lota od 14 DOE Ware sta lla RR 15 ADS CON E E N MU ipi e 15 Chapter 2 Basic Operation cari TET AE 16 Data Bxchanse Modele ninio 17 IOS cto eq aiat n nd cud cU M E 17 ID TE DAI AT CAI NTC 18 Subnet wOrkuk FOLOCOl aria 19 1904771077 A ca hk car enc ea arene E 19 TPP OLOCO 85 71 17 108 577119 CS AAA A ARA ct 19 IVI ASTON NOOO RT HR EE 20 SIRIO GIA OD PHP 21 DITA MOD
83. tion select a node in the Navigation Section Parameter Slave Address Description The value entered here may be used to set the node address in certain commands For more information see The Command Editor on page 47 Anybus Communicator for Modbus RTU Doc Rev 3 00 SY Fieldbus A ABC e Sub Network Sub Network Monitor Add Node Add Broadcaster Load Node Sub Network Status SN Fieldbus Aa ABC A Sub Netwark Y Broadcaster Y ew Mode Doc ld SCM 1200 091 Chapter 6 6 Transactions 6 1 General As mentioned previously transactions are representations of the actual serial telegrams exchanged on the serial subnetwork While the gateway doesn t feature a scanlist in the traditional sense all nodes and their transactions will be processed in the order they have been defined in the ABC Config Tool Transactions are handled slightly differently in the three protocol modes e Master Mode For regular nodes transactions always come in pairs a query and a response The query is issued by the gateway while responses are issued by the slaves on the subnetwork The Broadcaster can only send transactions e Generic Data Mode Transactions can be added as desired for both directions Transactions sent to the subnetwork are called Transaction Produce and transactions issued by other nodes are called Transaction Consume e DF1 Master Mode Please refer to DF1 Proto
84. ts may not be deleted or altered The examples in this section use Master Mode The procedures involved are similar in Generic Data Mode but without the limitations imposed by the Modbus RTU protocol 8 3 2 Basic Navigation Open the Command Editor by selecting Edit Command or Add Command from the Command menu Command Editor Fil lumn Command Name New o Command ID 0x3 Allow O Query 1 2 3 4 DisplayName Slave Address Function Data Checksum ObjectType Byte Byte Data Checksum Value SlaveAddress ID User User Response 1 2 4 DisplayName Slave Address Function Checksum ObjectType Byte Byte Checksum Value SlaveAddress ID Depend A Pull down Menu See Pull down Menu on page 48 B Name of Command Actual name of the command in text form C Command Transactions This section holds the actual transactions associated with the command This can either be a que ry response pair or a single transaction depending on the protocol mode etc D Command ID This can be used as desired when building the command e g to specify the function code E Other Settings Setting Description Allow Broadcasting Specifies if it is allowed to broadcast the command only relevant in Master Mode Produce The command is producing data Generic Data Mode only Consume The command is consuming data Generic Data Mode only Anybus Communicator for Modbus RTU Doc Rev 3 00 D
85. ub network 9 1 General In DF1 master mode communication is based on services A service represents a set of commands and operations on the subnetwork that is predefined in the Anybus Communicator Each service 1s as sociated with a set of parameters controlling how and when to use it on the subnetwork The communication is based on a query response scheme where the gateway issues a query on the sub network The addressed node on the subnetwork is expected to issue a response to that query Nodes are not permitted to issue responses spontaneously 1 e without first recetving a query Control System Gateway Subnetwork Devices Query b Node mm 4 Response Query j D 4 Response d Node 2 Query y 4 In DF1 Master Mode ABC Config Tool comes preloaded with a number of services that can be select ed by the user The actual DF1 commands that perform the services during runtime ate predefined in the Anybus Communicator The configuration of the services is performed by right clicking on a node in the ABC Config Tool and selecting Add Command Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc ld SCM 1200 091 DF1 Protocol Mode 52 9 2 ABC Parameters Select ABC in the Navigation Section to gain access to the parameters e TE described in this section 2j 4 Sub Network Interface Currently only serial communicati
86. using the Command ID field Function of the data associated with this object is determined by the user Data etc can be selected by the user By default this is set to match the Modbus RTU stan dard Checksum Object Type Byte Object Byte Object Data Object Checksum Object Value SlaveAddress ID User Depend This value is linked to the SlaveAddress parameter in the parameter window The value of this byte constant will be set using the Command ID field The size and location of the data associated with this object is determined by the user This object will retrieve its settings from the correspond ing object in the Query By default the Modbus RTU specific frame objects are already in place and a data object is inserted between the function code and the CRC These objects cannot be moved or deleted however it is pos sible to add additional objects between the function code and the CRC as desired Name the new command by entering its name in the Command Name field and enter a suitable func tion code in the Command ID field If the command is allowed to be broadcasted check the Allow Broadcasting checkbox Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc Id SCM 1200 091 9 DF1 Protocol Mode Chapter 9 This mode makes it possible to let the Anybus Communicator act as a DF1 protocol master on the s
87. ved A confirmation dialog is displayed when El Shavowiserd down eU Nov manie souci data closing the ABC Config Tool with unsaved Ee data Show Wizard when The Wizard is displayed each time a new New menu is selected configuration is created Language next time the Selects which language to use The new program is launched setting will be active the next time the pro gram is launched Selecting the ABC tab will reveal additional properties Item Description Size of logbuffer By default the Data Logger can log up to 512 entries in each direction If necessary Apply it is possible to specify a different number of entries valid settings range from 1 512 Click Apply to validate the new Tc IU ecu settings See also Data Logger on page 63 Firmware Download Download firmware to the embedded field bus interface Warning Use with caution Factory Restore Restores the gateway firmware to it s orig inal state does not affect the embedded fieldbus interface Block Configuration When selected the downloaded configu ration will not be executed by the gateway Warning Use with caution Create Error log Creates an error log file Firmware Download Block Configuration Anybus Communicator for Modbus RTU Doc Rev 3 00 Doc Id SCM 1200 091 Navigating the ABC Config Tool 26 View This menu features the following entries View A e Toolbar This entry enables disables