Home

Bulletin 1608P ProDySC User Manual 200 Amp

image

Contents

1. A n 16 PM123456 1204 B n 16 PM123457 126 C n 16 PM123458 1204 COMM Qi 12 PM123459 1204 PLC C1 5 Station Addr 288 HOME Table 9 Model Information Description Function odel Number System Model number Model Details Serial Number System serial number System Rating System voltage and current ratings Node The location index for the details listed to the right Firm The firmware version for the location indexed Type Unique code specifying firmware part number for the location indexed Serial The serial number for the location indexed Volts The rated voltage for the locations Amps The rated current for the location indexed Unit Details Rockwell Automation Publication 1608P UM003A EN P September 2013 Display Screen Chapter 5 Run System Tests Press the RUN SYSTEM TESTS to enter the System Tests screen Press 2 MINS to run the system fans for 2 minutes See Figure 25 Figure 25 System Tests System Tests Fan Tests Diagnostics Mode This is not a user function It is numerical code protected for authorized service personnel Rockwell Automation Publication 1608P UM003A EN P September 2013 27 Chapter5 Display Screen Notes 28 Rockwell Automation Publication 1608P UM003A EN P September 2013 Chapter 6 Maintenance Preventative Maintenance The ProDySC requires very little preventative maintenance The ProDySC should be checked periodically for proper
2. Branch circuit protection upstream of the ProDySC is required Recommended circuit breakers and maximum allowed circuit breaker ratings are listed in Table 1 Branch circuit protection rated less than the ProDySC current rating may result in nuisance tripping Table 1 Recommended Branch Circuit Protection ProDySC Rating 200A Rockwell Automation Publication 1608P UM003A EN P Max MCCB Rating 250A September 2013 Electrical Terminations Accessing Terminations Installation Chapter 2 The ProDySC must be installed by a qualified electrician in compliance with all local and national electric codes The ProDySC input line and output load terminals are located behind the right door Terminal details are shown in Figure 5 on page 12 For top entry remove the top gland plate shown in Figure 2 to access input and output terminals This plate may be removed for drilling or punching holes for conduit Alternate bottom entry should utilize the bottom gland plate shown in Figure 1 Access to the communications port is above the front doors as shown in Figure 6 on page 13 A separate conduit knock out is provided for top entry of communications conductors as shown in Figure 2 Note When punching or drilling holes for conduit fittings take care to avoid dropping metallic particles inside the enclosure Metallic contamination will void the product warranty Figure 2 Top Conductor Entry MINIMUM 12 305 CLEARAN
3. ambient temperature or humidity is beyond the specified limits given in this manual Rockwell Automation Publication 1608P UM003A EN P September 2013 Chapter2 Installation Floor Mounting Clearance Bypass Switch Circuit Breaker Recommendations The ProDySC is to be secured to the floor using fasteners and fittings appropriate for the type of floor Holes are provided in the base channels see Figure 1 for mounting dimensions Note Top or bottom cable entry is allowed See Figure 1 and Figure 2 on page 9 Figure 1 Bottom View Floor Mount Dimensions 40 00 Holes AX 0 625 P 16 essemus 2s A 12000 _ UE Em i 305 28 00 711 Y Y _ 1 000 6 105 25 155 IL Y 7T i 3 500 i Area Recommended for 89 sers ret 133 t omme 66 Bottom Conduit Entry l 1 000 i 25 ProDySC doors hinge on both right and left See Figure 26 on page 34 for dimensions including door swing Leave required clearances e Door swing must allow doors to open at least 90 degrees e 12 300mm clearance on left side and rear for cooling airflow e 4 100mm on right side for air filter clearance when right door opens Installation of an external maintenance bypass switch is recommended for service and or maintenance Typical switch arrangements are shown in Figure 3 on page 10 and Figure 4 on page 11 Contact Rockwell Automation for recommendations and requirements
4. minute after which the alarm will automatically reset Rockwell Automation Publication 1608P UM003A EN P September 2013 15 Chapter4 Applying Power Notes 16 Rockwell Automation Publication 1608P UM003A EN P September 2013 Chapter 5 Display Screen Overview The ProDySC touch screen display is a window to voltage sags and ProDySC protection The display provides system status voltage sag notification and history runtime statistics and system history in a simple and intuitive touch based user interface When the system first starts a welcome screen displaying the ProDySC product logo appears This screen disappears after 5 seconds when the Home screen appears Note The touch screen is optimized for use with a plastic stylus or bare finger At installation time perform the following steps to configure your system Step 1 Press the CONFIG button Figure8 Home Screen at the bottom of the HOME screen See Figure 8 See Figure 8 Pas ec ca 25 9A 25 0 25 00 90 Voltage Sags Detected Total Up Time 365d h 12m Step 2 Begin calibration by pressing Figure 9 System Configuration CALIBRATE TOUCH SENSOR System Configuration See Figure 9 VIEW MODEL INFORMATION SET SYSTEM CLOCK CALIBRATE TOUCH SENSOR RUN SYSTEM TESTS ENTER DIAGNOSTIC MODE i 5 Rockwell Automation Publication 1608P UM003A EN P September 2013 17 Chapter5 Display Screen Step 3 The Touch Scre
5. packing materials and restraints have been removed The ProDySC is placed in its installed location All conduits and cables are properly routed to the ProDySC All power cables are properly terminated A ground conductor is properly installed and terminated If neutral connection is required that it is properly terminated on the ProDySC The area around the installed ProDySC is clean and dust free Adequate work space exists around the ProDySC Adequate lighting is provided around the ProDySC Operational checks have been reviewed and completed Lift only at the base with a fork truck or pallet jack Carefully inspect the outer packaging for evidence of damage during transit Do not install a damaged cabinet Report any damage to the carrier and contact your local sales or service immediately Check the ProDySC label for correct model number with the packaging list to ensure you have received the correct voltage current and wiring configurations After removing the packaging material inspect the contents for any evidence of physical damage and compare each item with the Bill of Lading If damage has occurred or shortages are evident contact your carrier immediately The ProDySC must be installed in a protected environment The location must provide adequate airflow around the ProDySC in an atmosphere free from excessive dust corrosive fumes or conductive contaminants Do not operate the ProDySC in an environment where the
6. power If the upstream power is interrupted before CBI is opened the fast discharge circuit will not be triggered In that case wait at least 30 minutes before opening the ProDySC doors to avoid exposure to charged capacitors High voltage 32 Rockwell Automation Publication 1608P UM003A EN P September 2013 Connection Configuration Chapter 7 Specifications and Dimensions Table 12 Technical Specifications 200 A ProDySC Electrical Input Output Normal Mode Static Switch Series connected with load Under normal line condition the static switch passes utility voltage directly to the load Standard Input Voltages 3 phase 208 380 400 415 480V Voltage Range 10 Current Overload Static Switch 150 30Sec 400 5 Sec 600 0 5 Sec Frequency 50 60 Hz Auto Sensing Frequency Range 48 62 Hz TVSS Output SPD 25kA mode Protects L L amp L G on all models L N amp N G 4 wire models Efficiency gt 9996 480V Electrical Output Sag Correction Mode Inverter Output Voltage Pre sag rms voltage Voltage Regulation 596 typical 4 5 96 13 of nominal max ProDySC Output Current 200 Aus Not rated for DC loads max allowable 296 DC loading Crest Factor at nameplate rms load 145 Voltage Waveform Sine wave Voltage Sag Correction Times Single Event 3 phase 8796 to 5096 Voltage Remaining 5 seconds All three phases to zero voltage remaining 3 cycles based on nam
7. product notification updates For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect support programs For more information contact your local distributor or Rockwell Automation representative or visit http www rockwellautomation com support Installation Assistance If you experience a problem within the first 24 hours of installation review the information that is contained in this manual You can contact Customer Support for initial help in getting your product up and running United States or Canada 1 440 646 3434 Outside United States or Canada Use the Worldwide Locator at http www rockwellautomation com rockwellautomation support overview page or contact your local Rockwell Automation representative New Product Satisfaction Return Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manufacturing facility However if your product is not functioning and needs to be returned follow these procedures United States Contact your distributor You must provide a Customer Support case number call the phone number above to obtain one to your distributor to complete the return process Outside United States Please contact your local Rockwell Automation representative for the return procedure Documentation Feedback Your comments will help us serve your documentation need
8. 122 44 162 6 122 44 162 6 summary Table 5 Voltage Sag Detail Description Description Function Sag Summary Sag Magnitude ID Unique ID within the list 0 60 to identify the voltage sag Time Start time of the voltage sag RMS Worst case RMS voltage L N and percent of rated voltage across all phases Duration Duration of the voltage sag Frequency Frequency of the line prior to the start of the voltage sag Temperature Internal temperature of the PRODySC prior to the start of the voltage sag Line Voltage Line RMS voltage and percent of rated L N Voltages lt 80 of nominal are displayed in red Load Voltage Load RMS voltage and percent of nominal L N Correction Result The Correction Result is displayed in a box in the upper right hand corner of the Event Summary section The Correction Result conveys how the PRODySC performed correcting the voltage sag The possible values are Protected The output RMS voltage on all phases is gt 85 percent of nominal and the PRODySC correction was active for the duration of the voltage sag will be displayed in green Run Error An unexpected system event occurred during the sag will be displayed in orange Run Inhibited The PRODySC system was inhibited when the sag occurred will be displayed in orange Note The Voltage Sag Detail for the most recent event can also be accessed by pressing the Last Voltage Sag area of the HOME scr
9. 5 04 20 2009 64 36 05 04 19 2009 21 39 25 04 19 2009 14 42 45 04 19 2009 67 46 05 04 19 2009 00 49 25 Table 4 Voltage Sag Log Description Description Function Unique ID within the list 0 60 to identify the voltage sag Time Start time and date of the voltage sag Check Mark Denotes the ProDySC protected the voltage sag RMS 96 Worst case RMS voltage percent of nominal across all phases Duration Duration of the voltage sag Note Use the up down arrows to navigate through the list Press the SELECT button to view additional details about the voltage sag Rockwell Automation Publication 1608P UM003A EN P September 2013 Voltage Sag Detail Display Screen Chapter 5 Voltage Sag Detail screen See Figure 16 displays all information related to the selected event Details for the most recent sag event can also be accessed by pressing anywhere in the Last Voltage Sag area of the HOME screen The worst case RMS voltage recorded during the event is displayed in the upper window along with the corresponding voltage percentage and the event duration Table 7 describes the remaining screen content Figure 16 Voltage Sag Detail amp 8U L N 5 for 1 9 cycles Sag Summary ID 38 Time 65 23 2611 15 63 56 RMS 6 6 L N 5 Duration 1 9 cycles Protected Frequency 66 8 Hz Temperature 29 0 C Line L M 6 6U 5 6 24 6U 26 6 36 8 25 805 Load L H 122 44 162 6
10. 65 67 2613 63 25 22 INV_OC User Attention 65 66 2613 26 28 42 OUTPUT lU User Attention 05 13 2013 13 41 Table 7 System Event Log Description Description Function Unique ID 0 39 to identify the system event unique within the list Time Start time of the system event Name Short name of the system event Severity Severity of the system event Note Use the up down arrows to navigate through the list Press the SELECT button to view additional detail about the system event Rockwell Automation Publication 1608P UM003A EN P September 2013 23 Chapter5 Display Screen System Event Detail The System Event Detail screen is displayed when a specific system event is selected by pressing on the SELECT button on the SYSTEM EVENT LOG screen See Figure 19 on page 23 It provides detailed information that was recorded during the event See Figure 20 Figure 20 System Event Detail System Event Detail Time Duration Time 87 82 2813 66 09 27 Duration 32 sec Tvpe Event ID 14 Description Code DC OU 15 DC Bus Over Voltage Severity User Attention Component Location Phase C Area Inverter Reading 123 688VDC Table 8 System Event Detail Description Function Time Date and start time of the system event Time Duration Duration The amount of time the event lasted Event ID Unique ID within the list 0 39 to identify the event Code Abbreviation of the ev
11. CE TO BE MAINTAINED FROM SIDE AND BACK LOUVERED VENTS FOR PROPER COOLING AREA RECOMMENDED FOR TOP CONDUIT ENTRY 3 50 88 9 2 61 647 66 3 164 3 12 00 304 8 1 0 KNOCKOUT 52 SHOWN WITH OUT COVER i DOORSWING ee 21 89 556 1327 3 N WARNING Metallic particles inside the enclosure will void the warranty Rockwell Automation Publication 1608P UM003A EN P September 2013 Chapter2 Installation 3 Wire VS 4 Wire ProDySC models are available for use with either 3 wire L1 L2 L3 or 4 wire C fi ti L1 L2 L3 N sources The input N conductor must be connected to 4 wire ontigurations models for proper operation Do not connect a N conductor to 3 wire models 3 Wire Models Bulletin 1608P part numbers containing V3 are configured for 3 wire source L1 L2 L3 and 3 wire loads X1 X2 X3 Do not connect a N conductor to 3 wire models Figure 3 shows the 3 wire ProDySC system wiring schematically including the recommended Bypass Switch Figure 3 ProDySC 3 Wire Configuration Customer supplied circuit breaker 3 WIRE SOURCE LL B Ea L ie MAKE BEFORE BREAK BYPASS SWITCH Output to Loads ProDySC Note The 3 wire ProDySC models rated greater than 240V have not been evaluated by Underwriter s Laboratories Inc R for connection to a corner grounded or ungrounded delta power source Contact R
12. Erat e ERE UE PEN Exe e 9 Accessing Terminations eoa ui snig acted ui eode tC dla b fedet daga ad rurd 9 3 Wire vs 4 Wire Confgurqtions is os vesdeddxevvo Ro RAO OPER ERR P e as 10 BPW IEG Modelsc o deut teat utet ette tac os Ase dte Spb ditio tenes 10 4 WireModels c vete CIUS Tees ar reb ET e oo eL eMe pesa 11 Electrical Terminations and Ratings iio cis sacs estere rre Lr pet ena 12 Dry ContactSaz ec ettet n ect dense ae N a pep redde d 13 Serial Communications Porr i aseaiss os dene e er tre EE RERO WeERE es 14 OVGEYIeW ien age as gE eaa pre ale DEDE eb ERUIT E Re 17 Home SCREEN oso ORI A aAA eerie ire d fiie ataca 19 Syste StAtUs Ao ra aE Er p ET ON deesse sd Cute er A 19 Voltage Sag Eventsirnre nipari neigi E E E EE TE E RNE 20 Voltage Sag Logs Piatt bustin ceo eI Erde oe terr bae 20 Voltage Sar Detillss ijcve cree eden E 21 Voltage Sag RMS Voltage CBE nc sa peie ue one RE UTERE a a 22 Voltage Sag N tificatiO He aA erue ver an center NF ee M GEE ENREGA 22 System Events 5 dee en patet eese led ee da edet fe e rbd 23 System Event Log x ooeca cere Seta eni endo aan eres 23 System Event Detail racos asarre ELE E PRR e EE pneu 24 System Event Notification s s s ium aive be o Sx UTE ees 25 System Configurations dest ER ene debeo E ER redo REN EN ERES 26 Model Information esses esee e Le a ehe Metered aa a pte ea a 26 Run System Pests rs trie anegia P a eq ei e daar 27 Diagnostics Modes uses Dei a n e a Neth e E IWS 27 Prevent
13. Inverter DySC output voltage was greater than 115 of nominal during sag correction Call service 25 SYNC_ERR Line Synchronization Error Call Service Inverter Inverter not synchronized to line when sag detected Call service 31 CONFIG Configuration Alert Call Service Inverter Controller configuration has changed Call service 32 CNTRL MEM Controller Memory Busy Auto Resetting Inverter Controller is loading new data into Flash memory No action needed 33 UNBALANCE Start Up Test DC Bus Unbalance Call Service Inverter Positive and negative halves ofthe DC bus did not charge equally during powerup Call service 34 AC V CHK Start Up Test AC Voltage Check Call Service Inverter Output voltage was detected out of tolerance during the start up test Call service 35 ROLL CALL Start Up Test Controller Roll Call Timeout Call Service Unit Controller communication problem detected during start up test Call service 36 COM VER Start Up Test Communication Compatibility Mismatch Call Service Unit Firmware communication compatibility problem detected during start up test Call service 37 CNFG TO Start Up Test Controller Configuration Timeout Call Service Unit Controller communication problem detected during start up test Call service 38 CNFG ERR Start Up Test Controller Configuration Mismatch Call Service Unit Controller firmware configuration problem detected during start up test Call service 39 FIRM TO Start Up Test Controller Firmware Check Timeout C
14. The relay contact ratings are 24V at 1A For access remove the small metal cover from the top of the ProDySC See Figure 6 e All wiring is to be Class 2 limited to 24 Volts AC or DC e Acceptable wire gauges range from 24AWG to 12AWG 0 205 2 5mm2 Torque connections to 5 0 Ib in 0 6 N m e For permanent installation of communications conductors a standard conduit knockout is located on the cabinet top See Figure 2 Figure 6 Access Cover Location CIRCUIT BREAKER Rockwell Automation Publication 1608P UM003A EN P September 2013 13 Chapter3 Communications Serial Communications Port The ProDySC serial port is a DE 9 female connector The pin out follows standard RS 232 protocol pin 2 is RxD pin 3 is TxD and pin 5 is common return All other pins are unused Contacts are galvanically isolated from the system power and grounds Protection The RS 232 port is ESD protected to 15kV Protocol 57 6k bps 8 data bits one stop bit no parity flow control off Data packets are SLIP encoded with 2 byte length field Data accessible through this port includes load voltages load currents status and event and diagnostic logs Consult Rockwell Automation technical support for specifications to the ProDySC SLIP protocol Figure 7 Serial Communications Port oo C T i ud up m O gt BE 93 E i S E Pin 5 Return 1 Pin 3 TxD Pin 2 RxD i eooo 00
15. User Manual Allen Bradley Bulletin 1608P ProDySC Dynamic Voltage Sag Corrector 1608P 200 Amp Models Allen Bradley Rockwell Software Automation Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls publication SGI 1 1 available from your local Rockwell Automation sales office or online at http www rockwellautomation com literature describes some important differences between solid state equipment and hard wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software descr
16. air flow and status indicator operation Monthly Checks e Ensure the touch screen display is working and no active events are displayed e Update system time if needed Figure 11 on page 18 e Use a soft cloth to clean the touch display DO NOT USE harsh detergent abrasive sponges alcohol ammonia toluene or acetone on the touch display e Ensure air intake and exhaust filters are not covered or obstructed 3 6 Month Checks e Check air filters and clean when necessary Air filters for the ProDySC will require periodic cleaning with the frequency depending on the environment Filters are located on the front side of the ProDySC and can be accessed with the door closed The ProDySC need not have power removed for this operation Remove the grill covers by unscrewing the knurled nuts the washable foam filter pads are behind the grill cover Gently wash the foam filter pads as needed with a light non abrasive soap and water mixture Towel dry do not wring out Place the filter and grill cover back into their location and replace the screw caps by rotating clockwise until finger tight Replace filter if damaged Consult Rockwell Automation technical support for replacement filters Replacement filters must be no more restrictive to air flow than the original equipment filters e Check fan for proper operation Tap on CONFIG on the touch screen display Tap on Run System Test This will bring up a System Test
17. all Service Unit Controller communication problem detected during start up test Call service 40 FIRM DIFF Start Up Test Controller Firmware Revision Mismatch Call Service Unit Controller firmware revision mismatch detected during start up test Call service 41 SRL TO Start Up Test Controller Serial Number Check Timeout Call Service Unit Controller communication problem detected during start up test Call service 30 Rockwell Automation Publication 1608P UM003A EN P September 2013 Chapter 6 Maintenance jek Code Name Full Name Severity Area Event Description Event Resolution 42 SRL_DIFF Start Up Test Serial Number Mismatch Informational Unit Controller serial number mismatch detected during start up test No action needed 44 T_INV_TO Inverter Test Timeout Call Service Unit Phase control board failed to respond to Comm board s Inverter test Call service 46 DOOR_OPEN DySC Cabinet Door Open Manual Reset Unit DySC door was opened Mechanical bypass commanded Close door Manually reset DySC Verity ambient temperature is within 47 CRIT OT Critical Over Temperature Manual Reset Unit Internal DySC temperature exceeded maximum rating Mechanical bypass DySC specification Check for damaged commanded fans Check for dirty or obstructed air filters Manually reset DySC 48 FUSE OPEN Fuse Open Call Service Unit One ofthe DySC fuses was detected open Mechanical bypass commanded C
18. all service 49 OPEN SCR A Open SCR Phase A Call Service Static Switch The SCR on the phase A module was detected open Call service 50 OPEN SCR B Open SCR Phase B Call Service Static Switch The SCR on the phase B module was detected open Call service 51 OPEN SCR C Open SCR Phase C Call Service Static Switch The SCR on the phase C module was detected open Call service 53 DYN BRAKE Dynamic Brake Error Call Service Unit A problem was detected with the DySC dynamic brake controller Call service 58 PLC ERR Programmable Logic Controller Error Call Service PLC PLC error detected Call service 59 PLC ST MM Programmable Logic Controller State Mismatch Call Service Unit PLC feedback error detected Call service Fuse Replacement Fast acting fuses are included to protect the ProDySC in the event of a load short circuit If the screen is dark when power is applied it may indicate a blown fuse Check the fuse s for continuity WARNING Turn the power to the ProDySC off by placing the Bypass Switch into BYPASS or opening the branch circuit breaker before replacing the fuse Failure to comply with this warning can result in injury or death The ProDySC has high voltage remaining up to 5 minutes after disconnection from the AC line Touching exposed or disconnected terminals cables or parts of the ProDySC can lead to serious injuries or even death Wait for a minimum of 5 minutes before performing any service or testing on the DySC after power is removed Keep t
19. ative Maintenance eise weaves tues yer hh y he a 29 Monthly Ghecks oko epo e ten See harn E aE AE M sepa id 29 So Mont CHECKS ss soe de oi tetas obert E ales dee d EEE 29 Fuse Repldcetnenta socer eros Et nine Be Te HB RE NEXT RE DRETS 31 Buse Rating Charts ce ucn n VEO TEREO PO EV RU DP REDPRPADERUREEERIA 32 Transient Voltage Surge Suppressor TVSS csc cece scene eee ee eee 32 Circuit Breaker CBI Safety Interlocks and Stored Energy 32 Technical Sp cifications serrssissineniion iene da fedi KE eu ad 33 Approximate Dimensions 2 ieina veto pU veneno qeperg rege veteres d 34 Rockwell Automation Publication 1608P UM003A EN P September 2013 3 Table of Contents Notes 4 Rockwell Automation Publication 1608P UM003A EN P September 2013 Safety Considerations Chapter 1 Introduction The Allen Bradley Bulletin 1608P ProDySC Dynamic Sag Corrector is engineered to provide years of trouble free voltage sag dip protection The patented DySC technology does not use batteries requires only routine maintenance includes three stage transient voltage surge suppression and has unparalleled energy efficiency Most electronic devices found in industry today are susceptible to power disturbances A momentary sag in line voltage can reset or damage sensitive production equipment The ProDySC provides instantaneous dynamic sag correction to help your equipment ride through these common events The ProDySC connects
20. d latched securely when the wiring is completed Figure 5 Electrical Terminations NEUTRAL BUS AC INPUT CONNECTIONS GROUND BUS AC OUTPUT CONNECTIONS Input Output mechanical lugs conductor range AWG 6 to 350 kcmil 16 to 150 mm2 Lugs require 5 16 hex key tool for installation Torque to 250 Ib in 28 2 N m Lugs are mounted on threaded studs and may be removed if desired Studs are 3 8 9 525mm diameter and nuts should be torqued to 192 Ib in 21 7 N m e Neutral Bus and Ground Bus are provided with 3 8 16 threaded studs 9 525mm diameter Tighten nuts to 25 Ib ft 300 Ib in 33 9 N m Electric Code In addition all local state and federal regulations applicable to the installation of electrical systems as well as accident prevention regulations must be strictly observed WARNING The ProDySC must be safety grounded according to the National 12 Rockwell Automation Publication 1608P UM003A EN P September 2013 Dry Contacts Chapter 3 Communications Both dry contacts relays that indicate status and a Serial Communications Port RS 232 are available for monitoring the ProDySC Three relay contacts indicate ProDySC status The contacts are form A and close upon occurrence of the named event a any SAG EVENT when rms input voltage drops below 88 5 of rated value b OUTPUT OK when output voltage remains between 87 and 110 and c a system ALARM event
21. een Rockwell Automation Publication 1608P UM003A EN P September 2013 21 Chapter5 Display Screen Voltage Sag RMS Voltage Charts Voltage Sag Notification 22 The line and load RMS voltage L N of each phase is recorded for 8 cycles prior to the start of the voltage sag followed by the first 300 cycles of the voltage sag See Figure 17 Reach this screen by pressing CHARTS on the Voltage Sag Detail screen as shown in Figure 16 on page 21 Figure 17 RMS Voltage Charts RMS Voltage Charts LINE Dot rase a LOAD VOLTAGE 120 AUTO LIS ate o 68 128 186 386 Cycles SUMMARY carrs HOME Line voltage is shown in red and load voltage is shown in green By pressing the check boxes in the right column you can toggle each data series Off and On as well as enable y axis auto scaling Note 300 cycles 5 0 seconds at 60 Hz or 6 seconds at 50 Hz While the voltage sag is in progress a flashing red box in the upper left hand corner will display SAG IN PROGRESS This box will appear on every screen until the voltage sag ends See Figure 18 Figure 18 Voltage Sag Detected SRG IN PROGRESS Availability Ucitage 267 9U 207 90 207 90 Eurrem 2500 250r 250A mmu Frea 600 coone coon Last Voltage Sag Statistics 1 9 cycles 90 Voltage Saas O Detected Total Up Time 365d Gh 25m Last Power Up Date 65 68 2613 09 18 Rockwell Automation Publication 1608P UM003A EN P Sep
22. en Calibration screen will then appear See Figure 10 Press and hold on the center of the touch target release when the touch target begins to flash Repeat with the next two touch targets Step 4 The screen uses the new calibration configuration You can test the calibration before saving by pressing anywhere on the screen to ensure the touch target appears where you press After testing press the SAVE button Press the BACK button to return to the System Configuration screen Step 5 Set date and time by pressing SET SYSTEM CLOCK in System Configuration Press SAVE when completed Note To recalibrate from any screen hold anywhere on the screen for 10 seconds You will see a small progress bar at the bottom of the screen When the progress bar reaches 100 percent the calibration screen will open Figure 10 Touch Screen Calibration Touch Screen Calibration HOME Figure 11 Set System Date and Time Date Time Settings System Clock PEN 21 200 2 3 OO Date Format 04 21 2003 Time Format 18 Rockwell Automation Publication 1608P UM003A EN P September 2013 Display Screen Chapter 5 Home Screen The HOME screen of the display provides a snapshot view of the status of the entire system See Figure 12 You can return to this screen from any other screen by pressing the HOME button After 5 minutes of inactivity i e not pressing the screen the touch screen will automaticall
23. ent followed by a numeric event code in parentheses For a Type list of codes and abbreviations see Table 10 on page 30 Severity Severity of the event Description Name ofthe event see Table 10 on page 30 Location The location in the system where the event originated i e Phase A Phase B Phase C etc Area The specific area within the location where the event originated i e Inverter etc Reading a data value relevant to the System Event may be recorded in some cases e g detail for an Inverter Over Current alarm would include a reading of the causal high current value The reading N A is displayed if no appropriate data value exists Component 24 Rockwell Automation Publication 1608P UM003A EN P September 2013 Display Screen Chapter 5 System Event Notification When the ProDySC system first detects an event condition the System Fault Detection dialog box will be displayed See Figure 21 Within the System Fault Detection box the name severity and location of the event will be displayed Figure 21 System Fault Detection em Fault Detection System Fault Detected Name INV_OC Severity Auto Resetting Location Phase B Touch OK to view additional details about the fault VOLTAGE SAGS Pressing the OK button will open the System Event Detail screen The event will appear in the event list after the event is over The window can be closed by pressing the CANCEL butt
24. eplate ratings with a power factor of 0 7 and frequency of 60Hz Multiple Event Max Sag Correction Time 5 seconds cumulative usage Sequential Sag Recovery 0 seconds assuming cumulative run time available Full Recovery Time Max 5 minutes Mechanical Enclosure Ratings NEMA 1 IP20 Cable Entry Top or Bottom Cooling Filtered Forced Air Access Front for servicing and connections Audible Noise less than 60 dBA at 1m Weight 1470 Ib 667 kg Environmental Ambient Temperature 0 to 40 C Storage Temperature 40 C to 75 C Relative Humidity 0 to 95 non condensing Altitude Rated current available to 1000m 3300ft De rate output current 10 per 1000m from 1000m to 3000m 9900ft Safety and Compliance Agency Approvals cULus Listed UL 1012 Standards Compliance Exceeds SEMI F47 Standard IEEE Std C62 41 1 and UL 1449 3rd Ed compliant 1 ProDySC has not been evaluated for use in Corner Grounded or Ungrounded Delta Power Systems in systems rated over 240V 2 When using ProDySC with motor drive loads either insert 3 to 5 line reactance at ProDySC output or limit motor drive loads to 60 of ProDySC rating Rockwell Automation Publication 1608P UM003A EN P September 2013 33 Chapter7 Specifications and Dimensions Table 13 Heat Dissipation Rating V Heat Loss W Heat Loss Btu h Efficiency 96 208V 1035 3534 98 6 480V 1325 4524 99 2 Approximate Dimensio
25. he cabinet doors closed to ensure proper cooling airflow and to protect personnel from dangerous voltages inside the ProDySC IMPORTANT A qualified electrician must replace the fuse Open the front cabinet door s to access the fuse holders and fuses To maintain protection ofthe ProDySC be sure to replace the fuse with the same type and rating These fuses are available from the factory Provide the factory with the ProDySC model number located on the outside of the enclosure 31 Rockwell Automation Publication 1608P UM003A EN P September 2013 Chapter6 Maintenance Fuse Rating Charts Transient Voltage Surge Suppressor TVSS Circuit Breaker CBI Safety Interlocks and Stored Energy Replace fuse with the same type or equivalent cross referenced rating You may order these fuses through Rockwell Automation or the manufacturer listed Table 11 Pro DySCFuse Ratings Fuse Reference Fuse Location Fuse Rating puit F1 F2 F3 ain Cabinet Main Power Input 600A 500V Mersen A500S600 4IL F4 F5 F6 ain Cabinet Cross Coupling Transformer 100A 600V Mersen AJT100 F7 F8 F9 3 wire models only ain Cabinet Neutral Forming Transformer 4A 600V Mersen TRS4R F10 F11 200 220V models ain Cabinet Input Control Transformer 2A 600V Mersen TRS2R F10 F11 380 480V models ain Cabinet Input Control Transformer 1A 600V Mersen TRS1R F12 F13 ain Cabinet Cross Coupler Auxiliary 2A 600V Merse
26. ibed in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited Throughout this manual when necessary we use notes to make you aware of safety considerations WARNING Identifies information about practices or circumstances that can cause an explosion in a hazardous environment which may lead to personal injury or death property damage or economic loss ATTENTION Identifies information about practices or circumstances that can lead to personal injury or death property damage or economic loss Attentions help you identify a hazard avoid a hazard and recognize the consequence SHOCK HAZARD Labels may be on or inside the equipment for example a drive or motor to alert people that dangerous voltage may be present BURN HAZARD Labels may be on or inside the equipment for example a drive or motor to alert people that surfaces may reach dangerous temperatures PPPP IMPORTANT Identifies information that is critical for successful application and understanding of the product ProDySC Allen Bradley Rockwell Software Rockwell Automation and TechConnect are trademarks of Rockwell Automation Inc Trademarks not belonging to Rockwell Automation are property of their respective companies Additional Resources These documents contain additional information concerning related products from Rockwell Automation Re
27. n ATQR2 F14 F15 200 220V models ain Cabinet Output Control Transformer 8A 600V Mersen TRS8R F14 F15 380 480V models ain Cabinet Output Control Transformer 4A 600V Mersen TRS4R F16 F17 F18 F20 ain Cabinet TVSS Input 40KA surge 600V Mersen VSP40 2 F19 Main Cabinet Input Control Transformer 4A 600V Bussmann FNQ R 4 F1 F2 Power Module x3 Voltage Feedback 2A 600V Mersen ATQR2 F3 Power Module x3 Not Field Replaceable F4 F5 F6 F7 Power Module x3 Dynamic Brake 20A 600V Mersen ATM20 The ProDySC includes an internal TVSS device or SPD protecting the output load Indicator lights on the TVSS show if surge protection is active Power to the TVSS module may be removed by opening the block of fuses F16 F17 F18 F20 F20 is present only in 4 wire models If the cabinet doors are opened while the ProDySC is operating the circuit breaker CBI will be automatically opened and load power will be interrupted Doors should be kept locked to avoid this situation CBI is rated 250A 3 pole with thermal magnetic trip and automatic shunt trip capability The ProDySC includes a fast discharge circuit to quickly dissipate stored energy when the internal circuit breaker CBI is opened CBI may be operated automatically by the door interlock switches or other protection devices CBI can also be operated manually The recommended procedure for performing any service inside the ProDySC begins with opening CBI before removing upstream
28. normal utility power directly to the load until a voltage sag occurs During a sag the ProDySC inverter is activated adding missing voltage to keep the load voltage within the normal range When utility power returns to normal the inverter is deactivated and the ProDySC is quickly ready to correct the next sag The ProDySC reports these voltage sag events through its integrated touch screen display and provides system status voltage sag notification and history runtime statistics and system history in a simple and intuitive touch based user interface The ProDySC is designed to operate in industrial applications Follow these guidelines to ensure that the safety and installation of the ProDySC are handled with appropriate care after disconnection from the AC line Touching exposed or disconnected terminals cables or parts of the ProDySC can lead to serious injuries or even death Wait for a minimum of 5 minutes before performing any service or testing on the ProDySC after power is removed High voltage remains if red LED indicators above capacitor banks are lighted Keep the cabinet doors closed and locked to ensure proper cooling airflow and to protect personnel from dangerous voltages inside the ProDySC SHOCK HAZARD The ProDySC has high voltage remaining up to 5 minutes a temperature and humidity controlled indoor environment free of conductive contaminants Avoid installing the ProDySC directly near heat emitting equipment
29. ns 64 21 2669 16 29 A Phase Voltage L L Current Freq Switch A B 267 9 99 9 25 60 166 6 660H2 37 5 C B C 207 9U 99 9 25 8R 100 0 Rockwell Automation Publication 1608P UM003A EN P September 2013 19 Chapter5 Display Screen Table 3 System Status Description Description Function System Status Overall system status including current operational status availability to correct sags and internal cabinet temperature Phase Status Voltage current frequency and static switch temperature are displayed for all phases The percentage displayed following the voltage and current is the percent of nominal value for the ProDySC Nominal values are listed on the View Model Information screen Waveforms A sample of a 4 cycle waveform that includes real time line voltage load voltage or load current can be selected for display Voltage Sag Events 20 A voltage sag is defined as the period when input RMS voltage drops to less than 88 5 of the rated DySC voltage Details of each voltage sag and corresponding ProDySC protection are captured and saved to the voltage sag log Voltage Sag Log The Voltage Sag Log screen See Figure 15 displays a list of the last 61 voltage sags Reach this screen by pressing VOLTAGE SAGS button on the HOME screen Figure 15 Voltage Sag Log Protected Sag Duration 64 21 2009 15 19 25 84 21 2009 08 22 45 84 21 9 cycles 04 20 2009 11 32 4
30. ns MINIMUM 12 305 CLEARANCE TO BE MAINTAINED Dimensions are shown in inches millimeters Dimensions are not intended to be used for manufacturing purposes Figure 26 200 A ProDySC Dimensions 3 50 FROM SIDE AND BACK h LOUVERED VENTS 89 TI 261 647 FOR PROPER COOLING 66 164 i cA 12 00 305 AREA 1 O KNOCKOUT RECOMMENDED 5225 FOR TOP CONDUIT ENTRY 1327 SHOWN WITH OUT COVER T F 2 X 21 89 556 cen REM 42 36 L 1076 OVERALL WIDTH RAS PORT E ACCESS i iC DISPLAY T E 78 06 1983 OVERALL f arcur HEIGHT 2 BREAKER AIR INTAKES 34 Rockwell Automation Publication 1608P UM003A EN P September 2013 Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products At http www rockwellautomation com support you can find technical manuals technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools You can also visit our Knowledgebase at http www rockwellautomation com knowledgebase for FAQs technical information support chat and forums software updates and to sign up for
31. o c oJ Rockwell Automation Publication 1608P UM003A EN P September 2013 Chapter 4 Applying Power e Before applying power to the ProDySC make certain there are no metal filings or any conductive debris in or on any components inside the ProDySC e Verify ProDySC voltage rating matches ac source voltage e Ensure that all input output wiring including grounding has been completed all covers are replaced and that access doors are closed and locked e Place the ProDySC internal circuit breaker in the OFF position e Apply power from the upstream branch protection device Power will not flow through to the load The ProDySC touchscreen will become active e Place the ProDySC internal circuit breaker in the ON position e Ensure that the touchscreen displays OK in the upper left corner and that the nominal voltage current and frequency in the status display are correct e Ifa Critical or Fatal system event appears on the touch screen call for technical support e Verify that the output load voltage is present and within its nominal rating System is in operation will trip the internal circuit breaker and result in loss of WARNING The ProDySC is interlocked Opening ProDySC doors while the power to protected loads NOTICE Cycling ProDySC input power in the sequence OFF ON OFF ON within a one minute period will cause a Limit Cycle Timeout alarm In such case sag correction will be inhibited for one
32. ockwell Automation Technical Support for assistance 10 Rockwell Automation Publication 1608P UM003A EN P September 2013 Installation Chapter 2 4 Wire Models Bulletin 1608P part numbers containing V4 are configured for 4 wire source L1 L2 L3 N and either 3 wire or 4 wire loads The source N conductor must be connected for proper operation of these models Connect both input and output N conductors to the bus bar labeled NEUTRAL See Figure 5 Figure 4 shows the 4 wire ProDySC system wiring schematically including the recommended Bypass Switch Figure 4 ProDySC 4 Wire Configuration Customer supplied circult breaker 4WIRE SOURCE M eet eee H e ji H I i i I i gn I CB 1 1 1 I I i i H i P o 1 i a i I i TIENS 1 MAKE BEFORE BREAK BYPASS SWITCH H 3 2 Output to Loads 1 H I LN LJ i 1 EL HET a ees eee m A N S 2 ee eee 1 GND GND 3 1 x ProDySC GND QGNO Rockwell Automation Publication 1608P UM003A EN P September 2013 11 Chapter2 Installation Electrical Terminations and Input terminal blocks are marked L1 L2 and L3 for the source connections Ratin gs Output terminal blocks are marked X1 X2 and X3 for the load connections See Figure 5 In 4 wire models only connect both input and output N conductors to the NEUTRAL bus bar Do not connect to the NEUTRAL bus bar in 3 wire models The door must be closed an
33. on or waiting 15 seconds When the event condition clears a new dialog box will be displayed Press OK to view the complete event detail or CANCEL to close the dialog box See Figure 22 Figure 22 System Fault Detection Cleared The system fault has cleared Touch OK to view fault details Ucisde Sags Detected If a Call Service severity event is detected record the event details including name description location and reading Contact product support immediately If the event clears the touch screen will automatically go back to normal operation Rockwell Automation Publication 1608P UM003A EN P September 2013 25 Chapter5 Display Screen System Configuration Model Information 26 Press the CONFIG button at the bottom of the HOME screen to enter the System Configuration screen See Figure 23 The SET SYSTEM CLOCK and CALIBRATE TOUCH SENSOR functions are described at the start of this chapter Figure 23 System Configuration System Configuration VIEW MODEL INFORMATION SET SYSTEM CLOCK CALIBRATE TOUCH SENSOR RUN SYSTEM TESTS ENTER DIAGNOSTIC MODE BACK HOME 12 16 2616 11 36 Touch VIEW MODEL INFORMATION to go to the Model Information screen See Figure 24 Figure 24 Model Information Model Information Model Details Model Number 1668P 825A288U3S Serial Number PM654321 System Rating 208U L L 25A Unit Details Node Firm Type Serial Volts
34. s better If you have any suggestions on how to improve this document complete this form publication RA DU002 available at http www rockwellautomation com literature www rockwellautomation com Power Control and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Automation NV Pegasus Park De Kleetlaan 12a 1831 Diegem Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Asia Pacific Rockwell Automation Level 14 Core F Cyberport 3 100 Cyberport Road Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Publication 1608P UM003A EN P September 2013 Copyright 2013 Rockwell Automation Inc All rights reserved Printed in the U S A
35. screen to test the fans After tapping the Fan Test button you should hear the fans run for two minutes Rockwell Automation Publication 1608P UM003A EN P September 2013 29 Chapter 6 Maintenance Table 10 System Event Table e Code Name Full Name Severity Area Event Description Event Resolution 1 POWER ON DySC Power On Informational Unit Power re applied to the DySC No action needed 4 T FAN ST Fan Test Start Informational Unit Start acknowledgment of DySC fan test No action needed 5 T IN ST 1 Inverter Test 5 cycles Start Informational Unit Start acknowledgment of DySC 0 5 cycle inverter test No action needed 6 T_IN_ST_2 Inverter Test 3 cycles Start Informational Unit Start acknowledgment of DySC 3 cycle inverter test No action needed 7 T_IN_ST_3 Inverter Test 5 5 seconds Start Informational Unit Start acknowledgment of DySC 5 5 second inverter test No action needed 9 EXTERNAL External Inhibit Auto Resetting Inverter Controller is inhibited by another phase controller pete a details from other phase 11 RUN TO Inverter Run Timeout Auto Resetting Inverter DySC inverter had a total cumulative runtime of more than rated No action needed 12 LIM CYCLE Inverter Limit Cycle Timeout Auto Resetting Inverter Power was re applied more than once within a 58 second period No action needed Verify ambient temperature is
36. source Description Provides general guidelines for installing a Rockwell Automation industrial system Industrial Automation Wiring and Grounding Guidelines publication 1770 4 1 Product Certifications website http www ab com Provides declarations of conformity certificates and other certification details You can view or download publications at http www rockwellautomation com literature To order paper copies of technical documentation contact your local Allen Bradley distributor or Rockwell Automation sales representative Ch 1 Introduction Ch 2 Installation Ch3 Communications Ch 4 Applying Power Ch 5 Display Screen Ch 6 Maintenance Ch 7 Specifications and Dimensions Table of Contents Important User Information ser jos T VERRE HAMO Mee BHO Rec ete Roni cd 2 Additional Reso rcesisissc renerne ioiii t re o ERU ERE E OEE EA 2 S f ty Considerati sessa bip ales de sets Lied a a a 5 Installation Check DISU side redeo ool e Res E E E E opted 7 Inspecting and Unpacking incr qeoppteren ter sam onnmenaememiacmer nett T Location Environment 00 e cece cence ene n ene mea 7 Floor Mounting o egeat oka ween be thea dee XR ee bas UPS ERR Dd 8 amp catanee o o cdiee ted oD to Fe tpud uon Ar beds T daa ELE 8 Bypass Switch aces paws sephe PR RARE KE ERE wean aes VERE RR CREE E 8 Circuit Breaker Becommendations iis Less wien keds apa repel nhe Ras 8 Electrical Termi ations s055 5 erre E
37. such as ovens heaters or furnaces Ambient temperature must not exceed 40 C 104 F Do not operate near water or excessive humidity 95 max When punching or drilling holes for conduit fittings take care to avoid dropping metallic particles inside the enclosure as this can result in electrical damage The system is not intended for outdoor use The operating environment should be maintained within the parameters stated in this manual Only authorized service personnel should perform service on the ProDySC Ensure all power is disconnected before performing installation or service ATTENTION To reduce the risk of fire or electric shock install this ProDySC in Rockwell Automation Publication 1608P UM003A EN P September 2013 Chapter 1 discharge ESD Do not touch circuit boards or electronic components with hands or metal objects The ProDySC is not rated to directly power life support equipment Ensure the area around the ProDySC is clean and uncluttered Observe all DANGER CAUTION and WARNING notices affixed to the inside and outside of the equipment ATTENTION Internal components can be easily damaged by electrostatic Rockwell Automation Publication 1608P UM003A EN P September 2013 Installation Check List Inspecting and Unpacking Location Environment Chapter 2 Installation Before proceeding please take a few minutes to review the necessary steps to install your ProDySC All
38. tember 2013 System Events The ProDySC tracks all operational events which are classified into five groups based on severity Display Screen Chapter 5 Table 6 System Event Description Description Function Informational Purely informational No action is required Auto Resetting The PRODySC will reset within 60 seconds No user action is required User Attention seconds after the error condition is corrected User action may be required to correct a problem The PRODySC will reset 60 Manual Reset DySC system will be required For system events that cause circuit breaker CBI to open a manual reset of the Call Service For events classified as Call Service factory trained service support will be required Contact Rockwell Automation technical support System Event Log The System Event Log screen displays a list of the last 40 system events in chronological order See Figure 19 Reach this screen by pressing SYSTEM EVENTS on the HOME screen Figure 19 System Event Log System Event Log Severity 65 69 2613 17 55 22 SLAVE_2 Auto Resetting 65 69 2613 18 58 42 SLAVE_1 Auto Resetting 65 69 2613 64 62 02 SYNC ERR Call Service 65 88 2613 21 65 22 GATE_ERR Call Service 65 68 2613 14 68 42 STAT Call Service 65 88 2613 87 12 82 IGBT User Attention 65 68 2613 88 15 22 ULL OU Call Servi 85 87 2813 17 18 42 OUTPUT OU Call Service 65 67 2613 10 22 02 DC UU User Rttention
39. within 13 STAT OT Static Switch Over Temperature User Attention Static Switch Static switch heatsink temperature was greater than maximum rating DySC specification Check for damaged fans Check for dirty or obstructed air Reduce load In parallel DySC systems 14 OVERLOAD Overload User Attention Unit Inverter inhibited because load current exceeded maximum rating verify proper current sharing among slave cabinets Verify line voltage is within ratings 15 DC_OV DC Bus Over Voltage User Attention Inverter Positive or negative half of DC bus voltage exceeded maximum rating Verify proper DySC application Call service 16 CNTRL_UV Controller Power Under Voltage User Attention Inverter DySC control power supply is out of tolerance Verify DySCis online and Tine voltage is within ratings Call service T DySC output voltage was Tess than 80 of nominal during sag correction Sag Verify line voltage is within ratings 17 OUTPUT UV Output Under Voltage UserAttention inserter condition likely outside of DySC specification Verify proper DySC application Verify load current is within ratings 18 INV_OC Inverter Over Current User Attention Inverter Inverter current exceeded maximum rating during sag correction Verify mechanical bypass switch is open Verify proper DySC application 19 DC UV DC Bus Under Voltage UserAttention Inverter DC bus voltage below operational range SA ES is within ratings 20 OUTPUT_OV Output Over Voltage Call Service
40. y return to the HOME screen The HOME screen is divided into four main areas described in Table 2 Figure 12 Home Screen Availability OK Last Voltage St Voltage Sags 1 9 cycles 90 Detected Total Up Time 365d Gh 12m Elapsed Time Since Restart 12m 56 8s EM Table 2 Home Screen Description Description Function Siti us time system operation available runtime output Tine to neutra requency Last Voltage Sag Rotating information about the last voltage sag event start time event duration and sag depth Statistics Summary view of ProDySC performance based on sags detected plus a rotating display of last power up date elapsed time since power up and total up time The menu buttons at the bottom of the screen navigate through E A Main Menu VOLTAGE SAGS Displays the Voltage Sag Log screen delis iiis icis rias a creen CONFIG Displays the System Configuration screen ERES y 9 System Status The System Status screen displays the real time overall system status Reach this screen by pressing STATUS on the HOME screen or the Status area at the top of the HOME screen Figure 13 System Status Summary Figure 14 System Status Waveforms System Status System Status Availability DvSC Cabinet OK 58 secs 290 C CNN B Bie en Phase Status z 66 6H2 37 5 C C A 207 9 99 9 25 0A 100 0 666H2 375 C summary WAVEFORMS SUMMARY waveror

Download Pdf Manuals

image

Related Search

Related Contents

Severin KA4566 coffee maker  PDFダウンロード(664KB)  取扱説明書  PRO-SERIES CMG5 Instructions / Assembly  Gaggenau AH 590-720 User's Manual    Goodway AN2480  laissez-vous conter  

Copyright © All rights reserved.
Failed to retrieve file