1.           1 bit 1 bit    Fig  14     Measurement principle of the Bar graph modes    AB Differential voltage   The average voltage of the  1  part and  0  part is determined  The difference in voltage is the AB  Differential voltage  This mode is useful to see if the general voltage for a device is not too low  maybe  caused by long cable  wrong cable or a faulty bus interface     AB Diff stable voltage   The lowest voltage of the  1  part is determined and the highest voltage of the  0  part is determined   The difference is the AB Diff stable voltage  This mode is useful to detect reflections on the bus that  might corrupt the integrity of the signals  bit interpretation   Missing terminators can cause the voltages  to go too low    inside    the 1 and O bit  making the value lower than usual        For both modes only the range between 20 and 80   of the bit time is considered so that  normal  rise  and fall times do influence the results  If a value becomes lower than 2 5 V the bar will become red  instead of green     Version 1 6     7 October 2008 Page 35   80  ProfiTrace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    Profilrace 2     User Manual    5 4 Topology scan    Profilrace has the capability to generate the topology of the PROFIBUS network without shutting  down the installation  The Topology scan creates a clear network drawing that contains the location of  the devices and length of the cable that links them  see Fig  
2.        October 2008 Page 73   80    ProfiTrace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved       PROGENTEG    Profilrace 2     User Manual    Version 1 6       October 2008 Page 74   80  ProfiTrace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    17 Revision History    Version 1 2     Added ISO 9001 2000 certificate      Updated the Product description chapter     Updated the Installation chapter      Updated the FAQ chapter     Version 1 3     Added Proficore Ultra chapter      Updated the Introduction chapter     Updated the FAQ chapter      Updated Technical data of the ProfiCore Ultra     Updated the Installation chapter     Updated the Training chapter      Updated the Order codes      Updated the Distributors      Updated the Quick Start chapter     Updated the Glossary     Version 1 4    Added Appendix with hotkeys       Updated the Introduction chapter      Updated the Quick start chapter  added a description of the Bar graph modes      Updated the FAQ chapter      Updated the Installation chapter      Updated the Training chapter      Updated the Glossary     Version 1 5     Added Appendix with contents of the toolkit     Updated the Glossary      Updated the Distributors      Updated the Installation chapter     Version 1 6     Updated the Installation chapter     Updated the FAQ chapter      Updated the Distributors      Updated the Glossary        Version 1 6     7
3.    CHINA    CAMETA   Training  amp  Marketing Department  No  1 Jiao Chang Kou   Room 407  De Sheng Men Wai   BEIJING 100011  China   Tel    86 10 82285088 or 62055653  Fax   86 10 62055653   Email  training cameta org cn  Internet  www diewen com    Czech Republic    FOXON e shop   Polni 367 460 01   Liberec 12   Czech Republic   Tel    420 724 578 360   Fax   420 485 353 192   Email  jaromir peterka foxon cz  Internet  www foxon cz    DENMARK    HH Automation A S  Hovedgaden 451F   DK 2640 HEDEHUSENE  Denmark   Tel    45 70 20 52 01   Fax   45 70 20 52 02   Email  ph hh automation dk  Internet  www hh automation dk    FINLAND    Hantekno Oy  Halsuantie 2   FIN 00421 HELSINKI    Finland    Tel    358  0 9 530 66 570   Fax   358  0 9 530 66 530   Email  hannu aarrelampi hantekno com  Internet  www hantekno com    FRANCE    AGILICOM  Batiment B  1  rue dela    Briaudi  re    Z A  La Chataigneraie  37510 BALLAN MIRE    France    Tel    33 247 76 10 20  Fax   33 247 37 95 54  Email  jy bois agilicom fr  Internet  www agilicom fr    GERMANY    PROCENTEC GmbH  Haid und Neu Str  7  D 76131 Karlsruhe    Germany    Tel    49 721 9658 670  Fax   49 721 9658 672  Email  tkarnau procentec com    Internet  www de procentec com    Brandt Data GmbH  Friedrich Hayn Str  4  D 24582 Bordesholm    Germany    Tel    49  0 4322 699657   Fax   49  0 4322 699658  Email  hbrandtQbrandt data de  Internet  www brandt data de    profichip GmbH  Einsteinstrasse 6  D 91074 Herzogenaurach    Germany    T
4.    ProfiTrace 2     User Manual    15 Glossary    Address Unique number of a device connected to the network  With PROFIBUS this  can be 0 to 126  127 is a broadcast address     Analyzer software tool to observe the protocol traffic  Combi Analyzers can also  inspect the signal quality   Other term  Bus Monitor   Example  ProfiTrace     Bit Time  TBit  To help simplify timing calculations  it is convenient to normalize the time  units  One Bit Time is the time it takes to transmit one bit and is the  reciprocal of the baudrate and is calculated as follows  TBit   1  bit     baudrate  bps     Examples   12 Mbps    gt  TBit   83 ns  1 5 Mbps    gt  TBit   667 ns    Busparameters Settings that define the timing behaviour on the bus  They are defined in the  master  Examples  Tslot  MaxTSDR     C Capacitance     Data Exchange The state of a slave after parameterization and configuration has been  completed  in which it cyclically exchanges I O data with the master   Normally the slave stays forever in Data Exchange until the bus  communication or device are stopped     DGND Digital Ground   DIN German Institute for Standardization  www din de    DP VO DP VO is the basic stage of the PROFIBUS DP communication protocol  DP     VO devices  master and slaves  perform the following basic functionalities     Cyclic exchange of I O data between controlling and slave devices     Device  Identifier  module  and Channel related Diagnosis     Parameterization of DP slaves     Configuration 
5.   0 1292 311 613   Fax   44  0 1292 311 578  Email  sales itech troon co uk  Internet  www itech troon co uk    Hi Port Software Limited  The Hub 2 Martin Close  Lee on Solent  Hampshire  PO13 8LG    United Ringdom   Tel    44  0 8452 90 20 30  Fax   44  0 2392 552880  Email  sales hiport co uk    Internet  www hiport co uk    Page 64   80       PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    Profilrace 2     User Manual    UNITED STATES    Grid Connect Inc    1630 VV  Diehl Road  Naperville  Illinois 60563   USA   Tel    1 630 245 1445   Fax   1 630 245 1717   Email  sales gridconnect com    Internet  www factorycomm com  URUGUAY    ZyTECH  Kuolong s r l    Cerro Largo 788 Bis   11100 Montevideo   Uruguay   Tel    598 2 901 3311   Fax   598 2 901 3311   Email  javier zytech com uy    Internet  www zytech com uy  VIETNAM    Bavitech   42 Truong Son Street   Ward 2  Tan Binh District   Ho Chi Minh City   Vietnam   Tel    84 8 547 0976   Fax   84 8 547 0977   Email  hai  hoang bavitech com  Internet  www bavitech com    Version 1 6     7 October 2008 Page 65   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved       PROGENTEG    ProfiTrace 2     User Manual    13 Order Codes    30020 e ProfiCore Ultra  e USB cable  e Profilrace 2   no oscilloscope  bargraph and topology scan function     can be upgraded later           e ProfiCore Ultra  e USB cable  e Profil race 2    e ScopeVVare    Troubleshooting e Bar graph  Toolk
6.   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    7 5 Recording messages    Assignment 1 Starting a message trace   CI Make sure the installation works properly  No Syncs  Retries  etc    CI Click on    Messages     should be an empty screen     LJ Click on    Start message recording        The screen should now be filling up with messages and on the bottom you should see an indication  how full the message buffer is     CI Click on    Stop message recording    to stop the recording     LJ Investigate what you see  Timestamp  Frame  Addr  Service  MSG type  SAP  Datalen  Data      Assignment 2 Search function  Click again on    Start Message Recording      Switch a slave OFF   Click on    Stop message recording        Click on    Setup Search        Click on    Search Down        LI   LI   LI   LI   QI Search for    Repeated messages    and click OK   LI   LI You should have detected the moment of lost   LI    Fix all the faults  Check if the    Syncs    have stopped     Assignment 3 Trigger function   CI Click on    Messages       LJ Click on    Trigger    followed by    Setup message record trigger       QI Set  Enable  Retrigger  10 Messages before  10 Messages after  do not limit   off    LJ Click on    Setup trigger    and select repeated message     LJ Click on    Start Message Recording     should be an empty screen      Version 1 6     7 October 2008 Page 50   80  Profi Trace2 Man
7.   These are caused by the small spur line that is connected to the ProfiCore  Probably the cable  length is relatively short in this installation  Fig  21 shows an example of acceptable signals in  ScopeWare  Fig  11 shows an example of acceptable signals in the Bar graph     Gj Profitrace for ProfiCore Ultra   2 1  c  2004 2008 PROCENTEC ProfiCore Ser Nr  xxxxx00002   5  x   File Action Filter Trigger Toolbars View Report Settings Help    ProfiTrace ScopeWare   Bar graph   Topology   Network Manager   ProfiCaptain      Mode    BA Diff DI B A Diff scale  1V   Div  Address  36 vl Trigger  Message D Trig  Trigger delay      Content  EI                 ec   e F SD1  SD2  SD4 F Short Ack       1V idle level because  of powered  termination          sislsmmssssssdamss de dedesssdotslshbobssssshodesssss eM   sbossssssssssodsmmssdodohssslitbosshassselssmisssssssdesstsstbanbohosssssssdeossdsssss  t           No noise during idle state    Acceptable  SS ee SS ee eee tele Wi Sr           wjn  E SIS    n    Fig  21     Acceptable RS 485     DP Signals    Version 1 6     7 October 2008 Page 43   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    6 2 Termination missing or wire break    When termination is missing or there is a wire break  the signals will reflect on the cable with an up   down effect  These reflections lead to a rise in the average signal amplitude  The width of the  reflections can tel
8.   User Manual    Version 1 6       October 2008 Page 42   80  ProfiTrace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    6 Oscilloscope Measurements  RS 485     DP     PROFIBUS is high speed digital data communication  vvhich means a multi meter is not useable to  measure the signal quality  An oscilloscope is required to verify the electrical signals on the cable and  essential to detect  EMC problems  reflections  many less termination  wire breaks  etc  The difficulty is  how to identify one of these problems  This chapter describes example measurements on RS 485      DP  which are made with ScopeWare  You can compare them with your measurement  Important for  your measurements is that you are aware of the propagation time on the cable  With PROFIBUS this  is about 4 2 ns m  Disturbances travel with the same propagation time  By measuring the width of the  reflections we can conclude where the disturbance is physically located  ScopeWare can do this  calculation for you     6 1 Acceptable signals    Acceptable signals are almost    real    square waves with an average amplitude of 5V  When the  amplitude is higher  but the signals appear to be square waves  it is still acceptable  Modern RS 485  drivers can generate higher amplitudes  It is also important that the idle state has minimum noise  The  idle state has to be 1 V  This is because of the powered termination  The spikes on the bits are  normal
9.  Also the Live List and large parts of the statistics  are useable     What is the    Delta Time      It is the time from the first start bit of the previous message to the first start bit  of the current message     What is the    Idle Time       The Idle Time is the inactivity between 2 messages  It refers to the previous  message and the time that has elapsed before the current message is send  If  the current message is a response  it is called the slave Tsdr  slave response  time      What is the    Timestamp       The timestamp is calculated on the basis of a starting moment the user has  defined and subsequent messages add to a delta bittime to this beginning  This  means that the timestamp internally consists of 2 parts  the time date and the  delta bittimes that have passed     Version 1 6     7 October 2008 Page 60   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved       PROGENTEG    ProfiTrace 2     User Manual    Installation  Operating Systems and Interface hardware    I have problems installing the ProfiCore Ultra drivers with ProfiTrace  V2 1 1  Can you help me    On the day of the release of this version we discovered that the security  certificates of the ProfiCore Ultra drivers were expired  This means  everybody  who installs ProfiTrace gets a notification that the drivers were not installed  To  work around this problem  you have to set the date of the PC back to 28 August  2008 or earlier  then install ProfiTrace an
10.  O 2003 2008 PROCENTEC   All rights reserved  No part of this publication may be reproduced  stored in a retrieval system  or  transmitted  in any form or by any means  electronic  mechanical  photocopying  recording or  otherwise  without the prior written permission of the publisher     ProfiCore is a registered trademark of PROCENTEC  Other products or company names are or may  be registered trademarks and are the property of their respective companies     Safety Guidelines   This manual contains notices which you should observe to ensure your own personal safety  as well  as to protect the product and connected equipment  These notices are highlighted in the manual by a  warning sign and are marked as follows according to the level of danger        Draws your attention to important information on handling the product  a particular part of the  documentation or the correct functioning of the product     Warning   This device and its components may only be used for the applications described in this manual and  only in connection with devices or components that comply with PROFIBUS and RS 485 interface   This product can only function correctly and safely if it is transported  stored  set up  installed   operated and maintained as recommended     The ProfiCore Ultra is a CE class A product  In a domestic environment it may cause radio  interference in which case the user may be required to take adequate measures     Disclaimer of Liability   We have checked the contents of 
11.  October 2008 Page 75   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    18 Next version      Characteristics of the PB interface     ProfiCore   LEDs     Commissioning checklist     How to connect the ProfiCore     Screenshot of the installed directories     Reporting     Schematic Tapconnector     ProfiCaptain FAQs     Training     7 5     assignment 3 more explanation    PICC Certificate     PITL Certificate     Form for mailing list registration     Form for Bug reports   Product improvement    Glossary     Reflection     Retries     Class1 2 master    1 amp M    Version 1 6     7 October 2008 Page 76   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    Profilrace 2     User Manual    Version 1 6       October 2008 Page 77   80  ProfiTrace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    Profilrace 2     User Manual    ZesgerEEerEEEEEEEEEREEREEEREEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEREEEEEEREREEEEEEREEEEREREEEEREEEEEEEEEEEEEEEEEEEEEREEEEEREEEEEEEEEEEREEEEEEEEREEEREEEEEEEEEEER EEE EEE TRE TR EEE RER    Version 1 6     7 October 2008 Page 78   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    Profilrace 2     User Manual    ZesgerEEerEEEEEEEEEREEREEEREEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEREEEEEEREREEEEEEREEEEREREEEEREEEEEEEEEEEEEEEEEEEEEREEEEEREEEEE
12.  Ser Nr  000000057  File Action Filter Trigger Toolbars View Report EEE Help    ProfiTrace   ScopeWare   Bar graph   Network Manager Preferences    Plugins    Load Data   Save Data   File viewer   5   rt message recording   Stop message recording   Set record filter   Set view fiter      1 Scan GSD library i  iit Profit itra   Close ProfiCore Ultra   Auto detect baudrate   Set baudrate    500 kbps D  System activity  Live list   el Message recording   XI Record to file   XI    Info Panel         V Live list la Messages     Messages  with view filter applied      Station statistics view   P Data inspection      GSD library scan dialog       Click     Re Scan GSDs   to proceed     Version 1 6     7 October 2008 Page 20   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved       PROGENTEG    ProfiTrace 2     User Manual    GSD library scan dialog    Filename   C  Program Files Profilrace_ VE U Zapp   qed BARx2s05 450  results Errors     Awammgs 5  Rev 1  Filename   C  Program Files ProfiTrace VE U Zapp  wqed BUERBS22  GSD   results Erors     Warnings  6  Rev 1  Filename   C  Program Files ProfiTrace Ve 0 Zapp  ae EH 1501 G5D  resulte Eror     AWarmings  4  Rev 2  Filename   C  Program Files Frolitrace VE U Zapp  qsd4EURO2400 650  resulte  Eror     Warmings  1  Rev    Filename   C  Program Files Profilrace VE U Zapp   gsd MELCF232  GS LD  results  Errors     Warnings  0  Rev 1  Filename   C  Program Files Profit race VE U 2 app   ae MTT2F 037 
13.  fur Technik und Informatik  PROFIBUS Kompetenzzentrum  Jlcoweg 1   CH 3400 BURGDORF   Switzerland   Tel    41  0  34 426 68 32   Fax   41  0  34 426 68 13   Email  max felser bfh ch    Internet  www profitrace ch    Version 1 6     7 October 2008    ProfiTrace 2     User Manual    EndresstHauser Process Solutions  Kagenstrasse 2   CH 4153 REINACH   BL1   Switzerland   Tel    41  0  61 715 73 00   Fax   41  0  61 715 73 01   Email  michael ulrich solutions endress com  Internet  www solutions endress com    TAIWAN    Full Data Technology   5F  62  Sec 4  Cheng Gong Road   Neihu  TAIPEI    Taiwan 114   Tel    886 2 27930945   Fax   886 2 27930855    Email  curt fdt msa hinet net    TURKEY    Emikon Otomasyon   DES Sanayi sitesi 103 sokak B 7 blok No 16  Yukari Dudullu   Umraniye   Istanbul 34776   Turkey   Tel    90 216 420 8347   Fax   90 216 420 8348   Email  tolgaturunz emikonotomasyon com    Internet  www emikonotomasyon com  UNITED ARAB EMIRATES    Adaptive Measuring and Control   P O Box 123759 Unit No 424    Al Diyafah Building  Al  Diyafah Street   Satwa Dubai    United Arab Emirates   Tel    971 4 3982760   Fax   971 4 3982761    Email  scsanu emirates net ae    UNITED KINGDOM    Saftronics Limited   Pearson Street   Leeds   LS10 1BQ   United Kingdom   Tel    44  0 113 245 7170   Fax   44  0 113 236 4010   Email  ian robinson saftronics co uk  Internet  www saftronics co uk    iTech   Unit 1   Dukes Road   Troon  Ayrshire KA10 6QR  Scotland  United Kingdom   Tel    44
14.  the PLC  master  OFF ON  Wait until the complete installation  has restarted     D    Does the Live List correspond with your drawing     Version 1 6     7 October 2008 Page 47   80  ProfiTrace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    LJ Adjust the detected differences in your drawing   7 2 Basic faults with ProfiTrace    Assignment 1 Detecting basic faults  LJ Switch a slave OFF or remove the bus connector and investigate the Live List     CI Remove an UO card of a slave and investigate the Live List  With some slaves you can see  different behaviour when you switch it OFF ON after removing the card     QI Change the network address of a slave and investigate the Live List  don   t forget to switch the  slave OFF ON      LJ Fix all the faults after this assignment     Assignment 2 Statistics     Syncs  Station Lost and Retries    When a slave is not available and ProfiTrace is restarted afterwards  you can t see it in the Live List   For these situations the Statistics are a very important feature     LJ Switch a slave OFF or remove the bus connector and investigate the Live List   LJ Restart ProfiTrace and check the Live List    L  Open the statistics view    L  Go to the field    Syncs    and analyse the values     QI Switch ON the slave and analyse the field    Syncs    again  Repeat this with some other slaves     The Syncs will show you how many cycles the slaves were not available for the 
15.  will inform you that  it could NOT find a valid license file and an option will be offered to download it automatically     Version 1 6     7 October 2008 Page 26   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    Profilrace 2     User Manual         License S         Internet        a a te nt ae end          Mos k  mreg coven ogee    Automatic license  download from Profitre              www procentec com licenses    Possible Users          ProfiCore    Fig  5     Obtaining the license files    Version 1 6     7 October 2008 Page 27   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    Profilrace 2     User Manual    Version 1 6       October 2008 Page 28   80  ProfiTrace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    5 1 Starting ProfiTrace 2    Connect the ProfiCore with the USB cable to your laptop PC and the PROFIBUS connector to the  installation  After starting up the ProfiTrace software  the screen as in Fig  6 should appear  Click on     Init ProfiCore Ultra    to start the software     When you have a    PA Probe    attached to the ProfiCore Ultra it will be automatically detected     Gj ProfiTrace for ProfiCore Ultra   2 1  c  2004 2008 PROCENTEC       File Action Filter Trigger Toolbars View Report Settings Help    I Save Data   File viewer J    Init ProfiCore Ultra Close ProfiCore U
16. 0  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    3 5 Profilrace installation    After the ProfiCore Ultra driver has been installed the setup procedure continues vvith the installation  of ProfiTrace     Welcome to the InstallShield Wizard for  Profilrace Y2 0 1    The InstallShield R  Wizard will install ProfiTrace YZ  0 1 on your  computer  To continue  click Next     WARNING  This program is protected by copyright law and  international treaties       Back Cancel         Click    Next    to proceed     You have to accept the terms of the license agreement     License Agreement    Please read the Following license agreement carefully     Frofilrace   End User License  Copyright c  20042007 PROCENTEC  All Rights Reserved     Usage of this software requires compliance with this license  If you do not agree to  the following terms  please do not use or install this software     1 0 Defirutions     1 1 For the purpose ofthis Agreement   Software  shall mean the software identified  above  including but not luted to any updates  modifications  revisions  copies  and       Ce I accept the terms in the license agreement       Ido not accept the terms in the license agreement    Installshield     lt  Back Cancel         Click    Next    to proceed     Version 1 6     7 October 2008 Page 15   80  ProfiTrace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    Pr
17. 15      Gj Profitrace for ProfiCore Ultra   2 1  c  2004 2008 PROCENTEC ProfiCore Ser Nr  xxxxx00002    e  x   File Action Filter Trigger Toolbars View Report Settings Help  ProfiTrace   ScopeWare   Bar             Fig  15   Topology scan    5 4 1 Restrictions for using the topology scan     e Topology detection only works on 500 kbps and 1 5 Mbps    e ProfiCore Ultra must be connected to the beginning or the end of the segment    e You must know on which station address the ProfiCore Ultra is connected    e Distances  lt  2 m or  gt  230 m  relative to the measurement point  cannot be measured reliably    e The segment must be without disturbances  spurs  noise  incorrect termination  etc      e The segments network must be installed according to the PROFIBUS installation guidelines    e ltis assumed that there is at least 1 meter of cable between the stations    e Only the stations in the current segment measurement point are calculated    e You must know which devices are physically connected to the current segment and which are  NOT     Version 1 6     7 October 2008 Page 36   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    5 5 ProfiCaptain    Profilrace 2     User Manual    ProfiCaptain is a PROFIBUS DP V0 DP V1 class 1 and 2 master that has been designed for  applications like  I O tests  commissioning  parameterization and demonstrations  It fills the gaps that  other products leave open and makes working with PR
18. 2008 Page 23   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    Profilrace 2     User Manual    Version 1 6       October 2008 Page 24   80  ProfiTrace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    4 License System    4 1 Introduction    Profilrace 2 can be used Offline without licenses  For Online functionality  you need the license for the  parts you want to use     You can purchase a license for the following combinations     e ProfiTrace 2   e Profilrace 2   ScopeWare   Bar graph   Reporting   e Drot Trace 2   ScopeWare   Bar graph   Reporting   Topology scan  e  lt Every combination gt    ProfiCaptain    The license you have purchased now can later on always be enhanced with extra functionality     4 2 Characteristics of the license file name    The license is defined by a file with the extension  PLD  This file has to be copied automatically or  manually to the     APP    directory of ProfiTrace 2     The license file is related to the serial number of the ProfiCore Ultra  On the bottom of the ProfiCore  Ultra the serial number can be found  It is a 10 digit number  Fig  3 illustrates the serial number of the  ProfiCore Ultra     PROCENTEC ProfiCore Ultra  PROFIBUS   USB interface    Serial number   d       e  To download your  SI II   LI Il licenta  Visit    MMA EUA   wa procentes com   canes       Fig  3     ProfiCore serial number    The 
19. 26 or  corresponding individual product standards     Fieldbus Datalink Layer  Layer 2 of PROFIBUS     Generic Station Description  It is provided by the device manufacturer and  contains a description of the PROFIBUS DP PA device  GSD files provide a  way for an open configuration tool to automatically get the device  characteristics     Highest Station Address  The highest address to which the master will look  for new masters  This is done with the FDL Status message  It has nothing  to do with the configured slaves  Default value is 126  but the end user can  decrease it to a lower value  We recommend to keep it on 126 in order to  display not configured slaves in the Live List  This value does not influence  the I O cycle time of the network     A Hub refreshes a signal and passes the information on to all nodes which  are connected to the Hub  Data frames which were received on one port are  transferred to all the other ports  chicken foot topology      The primary device identification is an Ident Number  This is a unique 16 bits  number assigned by the PNO  It is stored within the device and defined in  the corresponding GSD file  In addition it is part of the GSD file name  At  runtime the Ident Number is used within the     Set slave address procedure     Parameterization telegram  byte 5   6      Standard part of a diagnosis message  byte 5   6    The Ident Number can be retrieved from a device  Its main purpose is to  make sure that a GSD file and configuration pa
20. 29  omy Me AOC ee en ee eee ee eee eee ee eee eee 29  EE 31  AE AD E O 33   COR ee ele re eee ne eee ee one eee A nee eet 35  94 POD OIO GY EE 36   5 4 1 Restrictions for using the topology ecan  36  ee PO EP EE 37  20     1   RTE 39  6 Oscilloscope Measurements  RS 485     DP             ccceceseeeeeeeeeeeeeeeneeeseaeeeessesneeeseeseeeseasaeeseaeneessnanes 43  OE CCS IS SION ee 2e ne 0 nee de ee Ge De ee nt 43  6 2 Termination missing or wire break iii 44  6 3 Short circuit between the A and B line  VV 45  TG AMONG WE 47  PS SDS ee ne ee eee E ee eee eee ee eee 47  7 2   Basic faults with  PFO ACC E 48  ZA Double address with Drot Trace    49  7 4 Cycle time with Profi Trace    49   so Recording VOSS AS E 50  6 Tips  nd BIC RS ciencia nuesa menen merce ue 53  8 1 Checklist to prepare your installation 0c cccceecccseeeceeeeeeeeeseeeeseeeeseeesaeeeseeeseeeeseeessneeseeeesees 53  8 2 Checklist to create a reliable installation    53   Version 1 6     7 October 2008 Page 5   80    ProfiTrace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    9 Technical Data of the ProfiCore Ultra                          12222112222222221a2anaaaaamaaianananinanannnnrnr 55  LN e Leid E 57  11 Frequently EE Re TE E 59  12 Sales offices and Dette eugegge geesde EVERE ECKE snet en esnemmeene teens erescetene 63  To ege Ee EE 66  14 Contents of the Troubleshooting TOolKit                 cccssseeseeeeeeeeeeeeeneeeeeseeseeseeeeeeee
21. 5 38 558 SD2 3 lt  43 B ta Exchange Res 2  21 Nov 2007 10 35 38 558 sD2 3  gt 10 SRD HIGH Data Exchange Req ri    21 Nov 2007 10 35 38 558 SD2 3 lt  10 Exchange Res Li  21 Nov 2007 10 35 38  SD2 3  gt 32 Exchenge Reg 2  21 Nov 2007 10 35 38  SD2 32 32 Exchange Res      21 Nov 2007 10 35 38  SD1 3  gt 105 FDL Status Req  2 SD4 3  gt 3 Token pa Pass token  2 SD2 3  gt 27 Exchenge Req 4  2 ACK Short acknowledge Res  2 SD2 3  gt 43 Date Exchange Req 2  2 SD2 32 43 E Da ta Exchange Res EK   gt              V Livelist E       Activity log Message data                    Plugin output                    Close ProfiCore Ultra   Auto detect baudrate   Set baudrate Vue      iii    ilter applied    DD                   Fig  20     ProfiTrace message recording    Profilrace2 Manual EN docx       N    sates    Messages  with view filter    Setup Seel Search Up   Search Down  J Raw frames       tistics view   P Data    _    Date Exchange                             10 Data Exchange mme 1  PROFIBUS DPVO Message  10 Data Exchange Reg 2  Data Exchange 10 Data Exchange Res      104 Req  10 35 38 556 Pass token  10 35 38 556 SD2 3  gt 27 ae 7 Exchange Req 4  10 35 38 556 ACK DOI Short acknowledge Res  10 35 38 556 SD1 3 76 Date Exchange Reg  od7 10 35 38 557 Repeat SD1 3 76 Date Exchange Req  21 Nov 2007 10 35 38 557 Repeat SD1 3 76 Data Exchange Req  21 Nov 2007 10 35 38 557 Repeat SD1 3  gt 6 Data Exchange Req  21 Nov 2007 10 35 38 557 Repeat SD1 3 76 Date Exchange Reg  21 Nov 2007 10 35 38 5
22. 58 Repeat  lost  SD1 3  gt 6 Data Exchange Req  21 Nov 2007 10 35 38 558 SD2 3  gt 43 Data Exchange Req 2  38156 21 Nov 2007 10 35 38 558 SD2 3 lt  43 BEN ta Exchange Res 2  38157 21 Nov 2007 10 35 38 558 SD2 3  gt 10 Data Exchange Req 11  38158 21 Nov 2007 10 35 38 558 SD2 3 lt  10 Exchange Res 1  38159 21 Nov 2007 10 35 38 559 SD2 3  gt 32 Exchange Req 2  38160 21 Nov 2007 10 35 38 559 SD2 3 lt  32 Exchange Res 6  38161 21 Nov 2007 10 35 38 559 SD1 3  gt 105 FDL Status Req  38162 21 Nov 2007 10 35 38 559 SD4 3  gt 3 token  38163 21 Nov 2007 10 35 38 559 sD2 3  gt 27 SRD HIGH Exchange Req 4  38164 21 Nov 2007 10 35 38 559 ACK DI Short acknowledge Res  38165 21 Nov 2007 10 35 38 559 SD2 3  gt 43 SRD HIGH Data Exchange Req 2  38166 21 Nov 2007 10 35 38 559 SD2 3 lt  43 Data Exchange Res ZS  v                                                       tation statistics view   P Data inspection             Version 1 6     7 October 2008       PROCENTEC 2003 2008   Copyright   all rights reserved                            Page 40   80    PROGENTEG    Profilrace 2     User Manual    After a GSD library is imported  it is also possible to inspect process values and see diagnostic  information in understandable text  All the other basic busmonitor features like  logging  file  management  search functions  etc are supported     Version 1 6     7 October 2008 Page 41   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    Profilrace 2   
23. EEEEEEREEEEEEEEREEEREEEEEEEEEEER EEE EEE TRE TR EEE RER    Version 1 6     7 October 2008 Page 79   80  ProfiTrace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    Profilrace 2     User Manual    ZesgerEEerEEEEEEEEEREEREEEREEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEREEEEEEREREEEEEEREEEEREREEEEREEEEEEEEEEEEEEEEEEEEEREEEEEREEEEEEEEEEEREEEEEEEEREEEREEEEEEEEEEER EEE EEE TRE TR EEE RER    Version 1 6     7 October 2008 Page 80   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rignts reserved    PROCENTEC  Turfschipper 41   2292 JC WATERINGEN  The Netherlands    Tel    31  0 174 671800   Fax   31  0 174 671801  Email  info procentec com  Web  www procentec com    Other PROCENTEC products    ProfiHub B5   v 5 Isolated channels    v Transparent for PROFIBUS DP   v DP   RS 485 specifications    v 31 devices per channel    V 9 6 Kbps to 12 Mbps    v 1200 m spur line length    v No Address required    v Integrated termination     V4 LEDs that indicate the onboard  termination        V4 Screw terminals and DB9 connectors   v IP 20 classification     ProfiHub A5   V5 Isolated channels    v Transparent for PROFIBUS DP   v DP   RS 485 specifications    v 31 devices per channel       9 6 Kbps to 12 Mbps    v 1200 m spur line length    v No Address required    v Integrated termination    v IP 65 classification        www procentec com profihub    
24. EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved       PROGENTEG    ProfiTrace 2     User Manual    The driver is ready for use  hovvever vve recommend rebooting the PC     Found New Hardware Wizard    Completing the Found New  Hardware Wizard    The wizard has finished installing the software for     Profilore Ultra Device    Click Finish to chose the wizard                                eer    Ps SC       Click    Finish    to close the install shield     When the ProfiCore Ultra is connected to another USB port or another ProfiCore Ultra to the same  USB port  the driver installation process will start again  only once for every port or ProfiCore Ultra      Version 1 6     7 October 2008 Page 19   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    Profilrace 2     User Manual    3 7 Installing GSD files in ProfiTrace    Profilrace has the capability to display the Model Name of the device in the Live List  The  Model Name comes from the GSD file of the device  If you want to use this feature  you have to copy    all the required GSD files to the     GSD  directory  You can also point to a GSD directory of another  application  in the setting menu      After the copy process  Profilrace has to scan the GSD files in order to create an internal catalogue   You only have to do this once  Unless you remove  add or edit a GSD file     Ka ProfiTrace for ProfiCore Ultra   2 0 2  c  2004 2008 PROCENTEC ProfiCore
25. GSD  results Errors     Warmings  9  Rev 1  Filename   C  Program Files Profil race VE U Zapp  ae  SlIEMB028 G5D  results Errors     AWarmings  12  Rev 1  Filename   C  Program Files Profil race VE 0 2  app   Vas SIP 804 G50  results Errors  0 MWamimgs A Rev 1  Filename   C  Documents and Settings G5SD 0V10F 232 650  results Errors  0 Warnings  0  Rev 1  Filename   C  Documents and Settings GSD 5800B45 G5D  results  Errors     Warnings  6  Rev 1  Filename   C  Documents and Settings GSD 46B  UD Dol results  Errors     AYarmings  0  Rev 2  Filename   C  Documents and Settings GS O0 GBE 0043 G50  results  Errors  0 AYarmings  1  Rev    Filename   C  Documents and Settings G5D 4bb O4c2 ged  results Errors     Warnings  0  Rev 2  Filename   C  Documents and Settings GSD 4BB O4c4 G50  results  Errors  0 AWarmings  7  Rev 2  Filename   C  Documents and Settings GS DO BE  DAD ged  results Errors  0 Warnings      Rev 2  Filename   C  Documents and Settings GSD 46B  Dol results  Errors  0 Avarmings  2  Rev      Filename   C  Documents and Settings GS CO SEE 0815 50  results  Errors     Warnings  0  Rev 2     Re jscan GSD   Close         Click    Close    to finish the GSD scanning     3 8 Installing GSD files in ProfiCaptain    The catalog update of the GSD files in ProfiCaptain is not automatically linked with ProfiTrace  The  scanning of GSD files has to be repeated in ProfiCaptain     Gj ProfiTrace for ProfiCore Ultra   2 1  c  2004 2008 PROCENTEC  l5  x   File   Settings Help    P
26. LANDS    Ehrbecker Schiefelbusch BV  Postbus 5505   4801 DG BREDA  Netherlands   Tel    31  0 76 5782860  Fax   31  0 76 5719261  Email  at eselektro nl  Internet  www eselektro nl    NORWAY    AD Elektronikk AS  Boks 641   N 1401 SKI   Norway   Tel    47 64 97 60 60  Fax   47 64 97 60 70  Email  kai ade no  Internet  www ade no    Grott Trace  Manual EN doc       Fieldbus International AS  Blindern Forskningsveien 1B  N 0314 OSLO   Norway   Tel    47 22 06 79 63   Fax   47 22 06 73 20   Email  hla fint no   Internet  www fint no    POLAND    INTEX Sp  z 0 0    ul  Wincentego Pola 16  44 100 GLIWICE   Poland   Tel    48 32 230 75 16  Fax   48 32 230 75 17  Email  intex intex com pl    Internet  www  intex com pl    SINGAPORE    ISEP  S  Pte Ltd   91 Defu Lane 10   04 02  Swee Hin Building  Singapore 539221   Tel    65 63564237   Fax   65 63467322  Email  chkoo ise p com    Internet  www ise p com    SOUTH AFRICA    IDX ONLINE CC   1 Weaver Street  Fourways  JOHANNESBURG   South Africa   Tel    27 11  465 7916   Fax   27 11  465 8890  Email  daveb idxonline com  Internet  www idxonline com    SPAIN and PORTUGAL    ER SOFT  SA   Av  Constitucion  4  E 28230 Las Rozas   MADRID    Spain   Tel    34 916 408 408  Fax   34 916 408 409  Email  ronn er soft com  Internet  www er soft com    SWEDEN    P amp L Nordic AB   Box 252    S 281 23 HASSLEHOLM  Sweden   Tel    46 451 74 44 00   Fax   46 451 89 833   Email  hans maunsbach pol se    Internet  www pol se  SWITZERLAND    Hochschule
27. OFIBUS a lot easier  faster and more fun  The  main platform is a configuration environment in which the user can setup his slaves with the respective  modules and parameters  See Fig  16   After setting up the master  the user converts the slaves to  Data Exchange without compilation or download     ProfiCaptain is a master that sends information on the bus  The user should be aware of the  consequences in multi master networks when the baudrate and or busparameters are not set    correctly     5 ProfiTrace II for ProfiCorg ss  File Settings Help    ProfiTrace   ScopeWare   Ba   vaster settings                Load Project   Om D   Setup Master   Class 2 Commands   DP41 Class2   Watch Modify 1 0    GSD   NetWork Sheet       SC202 P Yokogawa    a       SIPAN 32 ProfiCore     SIPART PS2 SIEMENS   SITRANS F 1 ProfiCore     oV S ON  i  SITRANS FM        SITRANS P SIEMENS         SITRANS T SIEMENS 10   Deltapilot S   SRD960 denses              SRD991    Stellungsregler TZID F     Stratos 222n X Series  L Temperatur Messumformer T     TF12 ABB  Le TMT184 E H     TP303      Transmitter 1 Al  PhyL 0       Transmitter 1 AI  Phyl 1    Transmitter AF800 ee  Transmitter TF211 ju     TRIOWIRL   _4000 5_400       TT303 SMAR      Slave Info   Modules      CE  Description o          GSD Filename EH3X1503 G5D    Vendor Name Endress   Hauser  Model Name Deltapilot S  2nd Generation  Ident Number 0x1503        Bitmap       EH1503_N  acketerrors 0    Fig  16     ProfiCaptain configuration utilit
28. PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    Gj Profitrace for ProfiCore Ultra   2 1  c  2004 2008 PROCENTEC ProfiCore Ser Nr  xxxxx00002  File Action Filter Trigger Toolbars View Report Set    ProfiTrace   ScopeWare Bar graph   Topology   Network M        18  x   Very high message    amplitude       Fig  12     Bar graph when it senses missing termination or a wire break  Gj Profitrace for ProfiCore Ultra   2 1  c  2004 2008 PROCENTEC ProfiCore Ser Nr  xxxxx00002  File Action Filter Trigger Toolbars View Report Settings Help    ProfiTrace   ScopeW are  Bar graph    Topology   Network Manager   ProfiCaptain     AB Diff stable voltage DI          l  lSl    Very low message  amplitude       Fig  13     Bar graph when it senses a low impedance    Version 1 6     7 October 2008  Profi Trace  Manual EN doc    Page 34   80  O PROCENTEC 2003 2008   Copyright   all rights reserved       PROGENTEG    ProfiTrace 2     User Manual    5 3 1 Bar graph Modes    The Bar graph has 2 modes   e AB Differential voltage  e AB Diff stable voltage    mm pm pm PL CS CE EE CE TS ES TE Spp    mem en ee  P P mm P mm P P mm mm d e sm P RR P mm mm mm mm lm mm mm P mm P A P mm P P P P wl e mm mm mm mm mm mm mm mm       AB Differential  voltage   average        AB Dif stable  voltage            DECKER he ee ee ee ee ee mm Cu Be mm mm mm mm mm mm mm mm eee dm    mm pm pm ee ee ee ee ee ee  o rz mm mm pm mm    Meas  range 20   60  Meas  range 20   60 
29. PROGENTEG         ULTRA       User Manual    Profilrace 2    PROFIBUS Combi Analyzer on USB    PROFIBUS analyzer with powerful statistics  High speed digital oscilloscope   Bar graphs   Topology scan   DP V0 V1 master   Reporting    PROFIBUS to USB interface   Suitable for PROFIBUS DP and PA   9 6 kbps to 12 Mbps   Profilrace 2 is suitable for XP and Vista platforms    Version 1 6     7 October 2008    PROGENTEG    Copyright O 2003 2008 PROCENTEC   All rights reserved  No part of this publication may be reproduced  stored in a retrieval system  or  transmitted  in any form or by any means  electronic  mechanical  photocopying  recording or  otherwise  without the prior written permission of the publisher     ProfiCore is a registered trademark of PROCENTEC  Other products or company names are or may  be registered trademarks and are the property of their respective companies     Safety Guidelines   This manual contains notices which you should observe to ensure your own personal safety  as well  as to protect the product and connected equipment  These notices are highlighted in the manual by a  warning sign and are marked as follows according to the level of danger        Draws your attention to important information on handling the product  a particular part of the  documentation or the correct functioning of the product     Warning   This device and its components may only be used for the applications described in this manual and  only in connection with devices or componen
30. Ultra V2 0 beta  c  2004 2007 PROCENTEC  Fie Action Filter Trigger Toolbars View Report Settings Help    ProfiT race   ScopeWare   Bar graph   Network Manager   ProfiCaptain    Load Data   Save Data   File viewer      Close ProfiCore Ultra    Init Profi   ore Ultra    Auto detect       System activity  Live list   el Message recording   x  F    Info Panel    Framestructure  SD1 message  Source address  3                            Destination address  6  Model Name  JK16IDP ACMI EE enee  eame e Pere esp eue Ps  Frametype  Request message 38141 i 10 35 38 5 SD2 3  gt 10 Exchange  38142 21 Nov 2007 ie aoe oer SD2 3 lt  10 Exchenge Ss M  PROFIBUS DF 0 Message  38143 21 Nov 2007 10 35 38 556 SD2 3  gt 32 Exchange Req 2  Data Exchange 38144 21 Nov 2007 10 35 38 556 SD2 3 lt  32 Exchange Res       38145 21 Nov 2007 10 35 38 556 SD1 3  gt 104 FDL Status Req  38146 21 Nov 2007 10 35 38 556 SD4 3  gt 3 Token   Pess token  38147 21 Nov 2007 10 35 38 556 SD2 3  gt 27 Exchange Req 4  38148 21 Nov 2007 10 35 38 556 ACK DI Short acknowledge Res  38149 21 Nov 2007 10 35 38 556 SD1 3  gt 6 Date Exchange Reg  21 Nov 2007 10 35 38 557 Repeat SD1 3  gt 6 Data Exchange Reg  21 Nov 2007 10 35 38 557 Repeat SD1 3  gt 6 Date Exchange Reg  21 Nov 2007 10 35 38 557 Repeat SD1 3 76 Data Exchange Req  21 Nov 2007 10 35 38 557 Repeat SD1 3  gt 6 Date Exchange Reg  21 Nov 2007 10 35 38 558 Repeat lost  SD1 3 76 Date Exchange Req  21 Nov 2007 10 35 38 558 SD2 3  gt 43 Data Exchange Reg 2  21 Nov 2007 10 3
31. Version 1 6     7 October 2008 Page 22   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rignts reserved    PROGENTEG    ProfiTrace 2     User Manual    For presentations it is recommended to set the AB Differential colour to Yellow     If you want to adjust the Live List colours  click on    Live List colours        3 10 Upgrades    It is the policy of PROCENTEC to release periodic upgrades  These upgrades do NOT overwrite the    previous version  If you do not want to use the previous version anymore  you can follow this  procedure     LJ Uninstall the previous version by means of the Control panel in Windows   L  Rename or move the directory of the previous version to a more suitable name   location     LJ Install the new version on top of the directory from the previous version  If you are confronted with  a warning about existing drivers which seems to be newer  see Fig  2   just click    Yes    and    overwrite them     CI Update the shortcut on the desktop     You have now access to all previous GSD  DAT  plugin and configuration files  After starting  ProfiTrace  scan the GSD files again  also in ProfiCaptain      Confirm File Replace    Source  CC hwindows systema  dryetores      Protilorellltra  sys   Target CAWINDOW  S  System se Onvers ProfiCorelltra  sys     The target file exists and is newer than the source     Overwvrite the newer file     Fig  2     Warning prior to replacing drivers  confirm with Yes        Version 1 6     7 October 
32. aptain   ScopeWare   ProfiCaptain   ScopeWare    General  communication faults    Wrong address    Device diagnostics    Short circuit  break  ProfiCaptain   ScopeWare   ProfiCaptain   ScopeWare  crossed wires  e Is    Configuration faults       Version 1 6     7 October 2008 Page 9   80  ProfiTrace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    1 4 System requirements    In order to use ProfiTrace 2 and all sub programs  your computer system should include the hardware  and software listed below     Minimum requirements   LJ Microsoft Windows XP or Vista    I 600 MHz Intel Pentium III processor or equivalent   I 256 MB of RAM   CI 50 MB of available disk space   I 1024 x 768 resolution display   I 1 free USB 2 0 high speed interface port supplying 400 mA    I 1 Mouse or other pointing device    Recommended  differences to minimum      I 1 GHz Intel Pentium III processor or equivalent  LJ 512 MB of RAM  I 1280 x 1024 resolution display or better    Attention Users of Windows 98  98 Second Edition and Millennium  Me   PROCENTEC is not able to offer software downloads or replacement CDs for Windows 98  98 Second    Edition  SE  or Windows Millennium  Me  for ProfiTrace 2  Microsoft has stopped supporting these  operating systems  and this change involves all suppliers     If you received a software CD that lists any of these operating systems on the CD label  be sure to  keep it in a safe place since it w
33. aves     Clock synchronization     Redundancy   PROFIBUS DP is standardized within IEC 61158 and IEC 61784   communication profile families 3 1 and 3 2   The term  PROFIBUS DP  also is a synonym for the RS485 based  deployments within factory automation     Acronym for  PROFIBUS for Process Automation   This is an application  profile based on PROFIBUS DP independent from the physical profiles   RS485  Fiber Optics  MBP   The requirements of continuous manufacturing  are covered within the application profile  PA Devices  and the extension  MBP to the physical profiles     Active physical layer device that receives and retransmits all signals over a  different port to increase the distance and number of devices for which  Signals can be correctly transferred for a given medium     Version 1 6     7 October 2008 Page 71   80    Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    SAP    Spur    SSAP    Stub    Tbit    Termination    Topology    ProfiTrace 2     User Manual    Service Access Point  This is a defined code command that tells the slave  what data is to be transmitted or which function is to be performed  There  are always 2 SAPSs in a message  SSAP  Source Service Access Point   and or DSAP  Destination Service Access Point   The SAPs are located on  the first 2 bytes of the data unit in the SD2 message  Other message types  do not carry SAPs  PROFIBUS DP V0 uses SSAP 62 and DSAP 54 to 62   Example  62 60   Get Diagn
34. ccessfully installed ProfiTrace  W2 0 1  Click Finish to exit the wizard       Back Cancel         Click    Finish    to close the install shield     Version 1 6     7 October 2008 Page 17   80  ProfiTrace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    3 6 Connecting ProfiCore Ultra to the USB port    After connecting the ProfiCore Ultra to the USB port  the last installation process vvill start     Found New Hardware Wizard    Welcome to the Found New  Hardware Wizard    Windows will search for current and updated software by  looking on your computer  on the hardware installation CO  or op  the Windows Update Web site  with your permission      Head out privacy policy    Can Windows connect to Windows Update to search for  software             Yes  this time only           Yes  now and every time   connect a device    Click Next to continue                    Click    Next    to proceed     Select the location of the drivers  Normally the first option is sufficient     Found New Hardware Wizard    This wizard helps you install software for     ProfiCore Ultra Device    9 If your hardware came with an installation CD  ES or floppy disk  insert it now     What do wou want the wizard to do         Install from a list or specific location  Advanced     Click Next to continue     Cas Jus                         Click    Next    to proceed     Version 1 6     7 October 2008 Page 18   80  ProfiTrace2 Manual 
35. ce 2     User Manual    Is ProfiTrace 2 the same as the Profibus Tester  PBT3 and other  analyzers2   ProfiTrace 2 is much better  it combines all the other clunky and expensive tools  to just 1 simple USB interface  You only have to do 1 investment to get  everything and it can do a lot more  Also you have integrated master  functionality that the others cannot provide     Can I get a trigger signal for an external oscilloscope from Proficore  Ultra    YES  ProfiCore Ultra still allows you to connect an external oscilloscope  But  we  prefer you to use the ScopeWare which makes electrical measurements much  easier     Sometimes ProfiTrace cannot detect the baudrate  When I set it to  manual  it works  What is the solution to solve this problem    Sometimes the combination PC  ProfiCore and PROFIBUS can make it difficult for  the software to detect the baudrate  This has to do with a certain timeout  This  timeout can be set in  Settings  gt Preferences  gt General  Here you find the  timeout for the baudrate detection  Set it to a higher value and in most cases this  will solve the problem     Message Recording    Can ProfiTrace 2 decode DP V2 messages   YES  ProfiTrace decodes DXB  SRD MCAST and Isochrone spare DP V2 related  functions     In networks that still have old FMS components  will I be able to see the  SAPs and hex data from messages of these components    YES  ProfiTrace will capture and display every PROFIBUS message  So  you can  inspect the SAPs and the data 
36. cs can also be captured and logged  The results  can also be exported to detailed reports which are accepted by the industry     This revolutionary tool has been developed because of technological limitations of other available  tools on the market  The service team of the PROCENTEC was frequently forced to invest heavily in  interface cards and eventually could no longer accept the frustrations of PC locked licenses  That the  prices of the tools are relatively high and the displayed information is too complex was another  contributing factor  Therefore PROCENTEC decided to initiate the development of a tool that was  ideally suited to our needs and those of the end user     This outstanding tool that fits in your pocket will boost the capabilities of service  maintenance and  engineering technicians     Version 1 6     7 October 2008 Page 7   80  ProfiTrace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    1 1 Product features    v Analyzer with powerful statistics  Enhanced version of Profilrace 1  Repeats  Fall outs  Corrupted messages  Diagnostics  Cycle  time  etc     v High speed digital oscilloscope  Differential voltage  A line  B line  Noise  Overshoots  Reflections  Triggers     v Bar graphs  Average  Min  and Max  values of the bus signals per device     v Topology scan  Automatic generation of the network topology     v Reporting  Automatic generation of detailed reports that are accepted by t
37. d after installation change the date back  to the correct setting     Can I install ProfiTrace 2 next to ProfiTrace 1   YES  it uses another default installation directory and the drivers are different   You can even run both applications at the same time     Can I run ProfiTrace 2 on a Windows 2000 system   This depends on 2 factors  the performance and the system has to be equipped  with high speed USB 2 0 ports     Can I run ProfiTrace 2 on a Windows Vista system   It might be necessary to run in Windows XP Compatibility mode  You can set this  in the properties of the exe file     I have a CP5611 card  Can I run ProfiTrace on it   NO  ProfiTrace works only with the ProfiCore hardware     For the latest FAQ list check out our website     Version 1 6     7 October 2008 Page 61   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    Profilrace 2     User Manual    Version 1 6       October 2008 Page 62   80  ProfiTrace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    12 Sales offices and Distributors    ProfiTrace 2     User Manual       HEADQUARTERS    PROCENTEC   Tur  schipper 41   2292 JC VVATERINGEN  Netherlands   Tel    31  0 174 671800  Fax   31  0 174 671801  Email  info procentec com    Internet  www procentec com    ARGENTINA    eFALCOM   Alcorta 241 1   B1744  Moreno   Buenos Aires   ARGENTINA   Tel    54 237 46 31 151   Fax   54 237 46 31 150   Email  enrique modai efalcom c
38. e   Bar graph   Network Manager   ProfiCaptain      Mode   B A Diff vl B A Diff scale  nv   Div DI    Diff scal fi liv z  Time scale  250 nSec od M SD1 Jv SD2 V SD4 jw Short Ack  Address  43 DI Trigger  Free running DI  gt    j     vi Freeze   J   Cursors active       Trigger delay     Reset      Cursor 1    Gass  A  Free dE    Frequenc    Bit Factor     Volt Cursors    Cursor 1    CursorDiff                Fig  24     Short circuit between the A and B line  nearby           ProfiTrace 2 for ProfiCore Ultra V2 0 beta  c  2004 2007 PROCENTEC      File Action Filter Trigger Toolbars View Report Settings Help  ProfiTrace Scopeware   Bar graph   Network Manager   ProfiCaptain      Mode   Eli vl B A Diff scale  IV   Div vl i   j     Time scale  250 nSec ZE M SD1 M SD2 M SD4  Address  43 vi Trigger  Message DI E   Trigger  Start of response vi iv Freeze M Cursors active  Trigger delay     Reset      Title Content    Time Cursors     Cursor 1    Cursor2      Distance  50m     Frequency  1479148 Hz    Bit Factor  J i                                                    ee              in El   l                                 Volt Cursors      Cursor 1    CursorDiff    Detected glitch  in the signalling    zhe  2an LA Rn LL gg gg gy a ee De De DD D DRE  SR  SR  SR  Sea A es Se Le El    Detected glitch  in the signalling       Fig  25     Short circuit between the A and B line  far     Version 1 6     7 October 2008 Page 46   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copy
39. e installation is  It displays all the important information that a user  especially a maintenance  man is really interested in    e The number of retry messages    e The number of fall outs    e The bus cycle time    e The number of diagnostic messages  etc    Because this feature is available  the user does not have to inspect messages or do difficult  operations to ensure the quality of the installation     Version 1 6     7 October 2008 Page 39   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    Profilrace 2     User Manual    VVhen the user vvants to record messages  he has a perfect visual representation on the screen  see  Fig  19 and Fig  20      Ki ProfiTrace 2 for ProfiCore Ultra V2 0 beta  c  2004 2007 PROCENTEC     18  x        File Action Filter Trigger Toolbars View Report Settings Help  Profit race   ScopeWare   Bar graph   Network Manager   ProfiCaptain      Load Data   Save Data   File viewer   Setup record tigger   Start message recording   Stop message recording Set record fiter   Set view fiter         Init Profiore Ultra    System activity  Live list     Message recording   x  Record to file   x   P Livelst El Messages  z Messages    Setup See earch ees Search Dg    Info Panel      Framestructure  SD1 message  Source address  3   Destination address  6   Model Name  JR16IDP ACMI  Frametype  Request message                FrameNr T                           er E    tput    5 ProfiTrace 2 for ProfiCore 
40. e used for all kinds of additional  functionality  ProfiTrace 2 uses the expansion connector to trigger an additional external oscilloscope     Version 1 6     7 October 2008 Page 12   80  ProfiTrace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    3 Software Installation Instructions  Windows XP     This chapter describes the installation for ProfiTrace 2 and the ProfiCore Ultra drivers  It is assumed  that you have a basic knowledge of Windows operating systems  All example and dialogs are based  on a US UK based windows installation and may differ slightly based on upgrades  updates and  enhancements  Please use the screenshots in conjunction with the description in order to press the  appropriate buttons and other user interface items     It is possible to install ProfiTrace 2 next to ProfiTrace 1  they are both using another default installation  directory and the drivers are different  You can even run both applications at the same time     3 1 Installation procedure    The installation of ProfiTrace has to be done with the following procedure     Preparations prior to installation     Installing the ProfiCore Ultra driver     Connecting the ProfiCore Ultra to the USB port     JI  JI  Q Installing ProfiTrace   E  CI Installing GSD files in ProfiTrace and ProfiCaptain   JI    Setting colour preferences     3 2 Prior to installation   Prior to installation  follow the steps below    I Make sure you al
41. el    49 9132 744 200  Fax   49 9132 744 204  Email  sales profichip com    Internet  www profichip com    INDIA    U L ELEC TRODEVICES P LTD  NIRMAN CLASSIC    KATRAJ KONDHWA ROAD   KATRAJ  PUNE 411046    India    Tel    91 202 696 0050  Fax   91 202 696 2079  Email  dileep miskin ulepl com    Internet  www ulepl com    Version 1 6     7 October 2008     PROCENTEC 2003 2008   Copyright   all rights reserved    Page 63   80       PROGENTEG    IRELAND    PROFIBUS Ireland   University of Limerick   National Technology Park  Plassey  LIMERICK  Ireland   Tel    353 61 202107   Fax   353 61 202582   Email  sales profibus ie    Internet  www profibus ie  ISRAEL    C Vision computer systems Ltd   9 Haomanut St    Poleg Industry Area   Natanya    Israel   Tel    972 9 8633066   Fax   972 9 8633065   Email  shay c vision co  il  Internet  www c vision co il    ITALY    C S M T Gestione S C A R L   via Branze n  43 45   25123 BRESCIA   Italy   Tel    39 030 3384030   Fax   39 030 396999   Email  r miglietti csmt it  Internet  www Cem  H    JAPAN    Japanese PROFIBUS Organization   C O Siemens K K    Takanawa Park Tower   3 20 14 Higashi Gotanda   Shinagawa ku  TOKYO   Japan   Tel    81 3 5423 8628   Fax   81 3 5423 8734   Email  shinichi motoyoshi siemens com    KOREA    Hi PRO Tech  Co   Ltd     812  SEOCHO PLATINUM  1445 13   SEOCHO DONG  SEOCHO GU  SEOUL   KOREA   Tel    82  0 2 522 5005   Fax   82  0 2 523 5149   Email  chays hiprotech co kr   Internet  www profibus co kr    NETHER
42. eneeseeneeseneeseenenens 67  ES RE S AU gcc esa a ec a ee a E ae as cree a oe E ees ee nee E eee ee res 69  10180 9001 2000 Re e dE 73  Ud REVISION  PISTON Y E 75  10 NEXT Etage 76  19 NOS o nee ee eee ns crestes 77  Version 1 6     7 October 2008 Page 6   80    ProfiTrace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    1 Product Description    ProfiTrace 2 is the most powerful analyzer  for PROFIBUS networks  It is the latest  generation in the line of busmonitor  technology because it combines all  primary tools in one      Analyzer      Oscilloscope      Bar graph      Topology scan      DP V0 V1 Master    Technicians can check and troubleshoot  the complete PROFIBUS network with 1  software package and 1 piece of hardware   This results in an enormous reduction in  equipment  weight  costs and required  knowledge     The advanced USB hardware  ProfiCore Ultra   is internally equipped with a high speed digital  oscilloscope and able to capture bus signals   running at 12 Mbps  It can also be used on PROFIBUS PA installations with the PA Probe Ultra        Profilrace 2 is an essential tool for maintenance  commissioning and troubleshooting as well as  product development  Typical failures such as noise  reflections  voltage drops  termination problems   double addresses  wire breaks and configuration faults are easily identified  Random errors such as  overshoots  error telegrams  repeats and diagnosti
43. eserved       PROGENTEG    Profilrace 2     User Manual    5 6 Profilrace    ProfiTrace itself is an analyzer to display a Live List  record messages  view statistics  inspect data   etc   see Fig  18      8  Profilrace II for ProfiCore Ultra  c  2004 2007 PROCENTEC    oa Filter Trigger Toolbars View Settings        la x     Load Data   Save Data   File viewer   Setup record   Start message recording   Stop message recording   Set record filter   Set view fiter    Init ProfiCore Ultra   Close ProfiCore   FC FA Probe Auto detect bauckate   Set baudrate    1 5 Mbps DI    System activity  Live list  a  Message recording   XI Record to file   x   Info Panel               V Live list   a   Messages  with view filter El   Station statistics view   P Data inspection          Activity log Message data  Plugin output      Fig  18     ProfiTrace functions          The Live List is a matrix that lists all the available devices  It is directly visible which devices are     troublemakers     With different background colours the status of the devices is displayed    e Green  Device is in Data Exchange   e Yellow  Device is lost   e Red  Parameter fault   e Purple  Configuration fault   e No colour  on the bus but not in Data Exchange   The Live List can also generate the product name of the devices when a diagnostic message is  captured  synchronized with the GSD library      The statistics matrix is the most powerful feature of the analyzer  This field can really indicate how  healthy th
44. he industry     v DP V0 V1 master  ProfiCaptain 1 has been completely integrated with even more features     v ProfiCore Ultra USB interface  Useable on PC platforms  no power supply required and elimination of spur lines     V DP and PA  The PA Probe Ultra makes a measurement on PA segments possible     VY 9 6 kbps to 12 Mbps     v Works on XP and Vista platforms     1 2 Application areas    v Troubleshooting  amp  Maintenance of PROFIBUS networks  ProfiTrace  ScopeWare  Topology  scan and ProfiCaptain      v Commissioning of PROFIBUS networks  ProfiTrace  ScopeWare  Topology scan and  ProfiCaptain      v PROFIBUS product testing and verification  Profilrace  ScopeWare and ProfiCaptain    v Passive cable testing  ScopeWare and ProfiCaptain     v I O testing of PROFIBUS devices  ProfiCaptain     v Address setting of PROFIBUS devices  ProfiCaptain      v Education     Version 1 6     7 October 2008 Page 8   80  ProfiTrace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    1 3 Detectable faults    Profilrace 2 can be used to detect almost all faults in PROFIBUS networks  The table below describes  the sub programs you need to find specific faults     Faults on DP Passive cable No master active Running   No devices connected   Slaves are connected  installation    a      Double address e ProfiCaptain   ProfiTrace  No termination ProfiCaptain   ScopeWare   ProfiCaptain   ScopeWare  Too many termination   ProfiC
45. ill no longer be available from PROCENTEC     NOTE  The information in this document version supersedes any information in the digital or printed  documentation  Although the software for Windows 98  98 Second Edition  and Windows Me will no  longer be available  it could be that Profilrace 2 works with these operating systems     Version 1 6     7 October 2008 Page 10   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    2 ProfiCore Ultra    The ProfiCore Ultra is the required hardware to use ProfiTrace 2  It has a robust industrial housing and  translates PROFIBUS to USB and vice versa  Because of the USB interface  Profilrace 2 can be used  on field laptops as well as desktop PCs     The USB interface also eliminates spur lines  Profilrace 2 can be connected almost directly to the bus  line and the laptop positioned on a distance  This is a perfect measurement solution for high speed  networks       When ProfiTrace 2 is in the analyzer mode  it passively records the data traffic  It does NOT behave  as a master or slave       When ProfiCaptain is activated  the ProfiCore Ultra acts as a master and transmits messages on the  bus     2 1 Internal structure    ProfiCore Ultra has an isolated RS 485 interface  DB9 connector  and is equipped with a high speed  digital oscilloscope that is able to capture bus signals running at 12 Mbps  see Fig  1    It can also be used on PROFIBUS PA installati
46. ion 1 6       October 2008 Page 58   80  ProfiTrace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    11 Frequently Asked Questions       Will the Topology scan be able to scan through repeaters    NO  You will not be able to scan through repeaters  but you can clearly see which  devices are behind a repeater  because the cable length between them will be 0  m     Can ProfiCore Ultra overload the bus when it is attached to a running  installation    ProfiCore Ultra is designed and produced around the latest RS 485 technology   1 5 of a standard bus load   This means the load of ProfiCore Ultra can be  ignored on a full bus segment  Spur cables are also no problem  because the USB  cable is the path to the PC  5 meters   ProfiCore Ultra can be connected very  close to the network and the PC can be on a distance from the tap point     The ProfiCore Ultra has an RS 485 interface for the DP  bus  Is it possible to analyze a PA segment    YES  if you want to use the ProfiCore Ultra on a PA bus   attach the PA probe to the ProfiCore Ultra  The PA probe  transforms the extracted signals from the PA bus to  information which is fed into the ProfiCore Ultra        Which USB version is supported   High speed USB 2 0 is supported by ProfiTrace 2     Why are slaves that are not in data exchange blinking in the LiveList with  a yellow background    Your bus cycle is slower than the ProfiTrace update of the LiveList  Yo
47. it Ultra e Topology Scan  e Reporting  e Tap Connector 2  e Blue carrying case    e ProfiCore Ultra  e USB cable  e Profil race 2    e ScopeVVare    Troubleshooting e Bar graph  Toolkit Ultra Pro e Topology Scan  e Reporting  e Tap Connector 2  e Blue carrying case    e PA Probe  e ProfiCaptain 2    Topology scan license 26010 License for existing customers        Version 1 6     7 October 2008 Page 66   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    14 Contents of the Troubleshooting Toolkit    PROFIBUS Troubleshooting Toolkit Ultra PRO  38021     CI ProfiCore Ultra   L  USB cable  AtoB    I USB cable   A to mini  for extra power supply if needed     Il CD ROM  download your license on www procentec com licenses    I TAP Connector 2   Il Manual   L  Pen   LI PA Probe  including 2 spare connectors   green      PROFIBUS Troubleshooting Toolkit Ultra PRO  37021     ProfiCore Ultra  USB cable  Ato B     USB cable   A to mini  for extra power supply if needed     CD ROM  download your license on www procentec com licenses    TAP Connector 2  Manual   Pen    D U D U U ULC       Version 1 6     7 October 2008 Page 67   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    Profilrace 2     User Manual    Version 1 6       October 2008 Page 68   80  ProfiTrace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG 
48. l us the distance to the    problem point   When the distance is nearby  the reflections  are compressed in the bit  Fig  22 shows an example of termination missing or wire break nearby  The    reflections corrupt the message because of the high amplitude  Fig  12 shows an example of the Bar  graph in this situation     Gj Profitrace for ProfiCore Ultra   2 1  c  2004 2008 PROCENTEC ProfiCore Ser Nr  xxxxx00002  File Action Filter Trigger Toolbars View Report Settings Help    Detected glitch  Profilrace ScopeWare   Bar graph   Topology   Network Manager   ProfiCaptain        i in the signalling  Mode   BA Diff v  BA Diff scale   1V Div x       Time scale   500 nSec  Address  24 vi Trigger  Message DI Trigger  Start d response v  M Freeze M Cursors ach    Trigger delay     Reset trigger delay    nten            mnt laro    Detected glitch  in the signalling       Fig  22     Termination missing or wire break  nearby     When the distance is far  the reflections end up in the adjacent bits  This effect corrupts messages   Fig  23 shows and example of termination missing or wire break when the distance is far  The user    can make a conclusion if termination is missing or that there is a wire break by means of the  installation drawings     Version 1 6     7 October 2008 Page 44   80    Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual        ProfiTrace 2 for ProfiCore Ult    8  x   File Action Filte
49. license file for the ProfiCore Ultra in Fig  3 is  ProfiCoreUltra2_00050 PLD    Version 1 6     7 October 2008 Page 25   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    4 3 Storage location of the license files    It is allowed to store multiple licenses in the APP  directory of ProfiTrace  It is also allowed to store  the licenses on multiple PCs  The ProfiCore Ultra you utilize will determine the functionality of  Grott Trace Fig  4 illustrates how licenses can be stored on multiple PCs         lt     License Server www procentec com licenses    Internet    H  License File License File    It is allowed to   copy the license     on multiple PCs    Possible Users             ProfiCore    Fig  4     License files on multiple PCs    4 4 Obtaining the license files  There are 2 ways to obtain the license files  See Fig  5      1  You can download the license file through our website  www procentec com licenses   Fill in your data and serial number of the ProfiCore Ultra  See paragraph 4 2 where to find the serial  number     Automatically a web page will open where you can directly download the license  After download you  have to copy it to the APP  directory  see paragraph 4 3 for the storage location      2  If your PC has internet connection  you can download the license automatically through ProfiTrace   Connect the ProfiCore Ultra to the USB port and click on Init ProfiCore  ProfiTrace
50. ltra    System activi elit  vs Ver Te x   Info Panel            Set record fiter   Set view filter                     v Live ist      Messages       Messages  with view filter applied    D Station statistics view   pP Data inspection    NC l Hsa0 Reset selected station   Info Panel data   Diagnostics    I Auto update Info Panel                   Fig  6   ProfiTrace start up screen    After clicking on    Init ProfiCore Ultra   The ProfiTrace software     1  Detects if ProfiCore Ultra is connected to the USB port   2  Checks if the required license has been installed   3  Scans the baudrate of the network     After the baudrate has been detected  the Live List and the detected baudrate as in Fig  7 should be  visible     Version 1 6     7 October 2008 Page 29   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    Profilrace 2     User Manual    Gj ProfiTrace for ProfiCore Ultra   2 1  c  2004 2008 PROCENTEC ProfiCore Ser Nr  xxxxxO00002          File Action Filter Trigger Toolbars View Report Settings Help   PioliTrace ll Scopeware   Bar graph   Topology   Network Manager   ProfiCaptain                              LoadData     SaveData   Fieviewer   Setup record tigger   Start message recoding   Stop  Init Proficore  lira Close Profit ore Litra           Set baudiate       Info Panel   Messages  with view filter applied      Station statistics view      Data inspection      S alion   Info Panel data   Diagnostics    I Auto 
51. master  You can also  check how many times the slaves were not available     LJ Go to the field    Station Lost    and analyse the values   Fix all the faults  Check if the    Syncs    have stopped   Click on    Reset All    to clean up all the statistics     Go to the field    Retries  total for this station      switch OFF a slave and analyse the values     Doo oO    Fix all the faults  Check if the    Syncs    have stopped     Version 1 6     7 October 2008 Page 48   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    7 3 Double address with ProfiTrace    Assignment 1 Double address    ProfiTrace can easily detect a double address   CI Generate a double address and check it in the Live List and the    Syncs    in    Statistics        LJ Go to the field    Illegal responses to requests    and investigate what happens  on some masters this  might not work      LJ Fix all the faults  Check if the    Syncs    and the    Illegal responses to requests    have stopped     7 4 Cycle time with ProfiTrace    Assignment 1 Cycle time   CI Click on    Reset All    to clean up all the statistics    LJ Go to the field    Data Exchange Interval  msec      What is the cycle time of the installation   LI Switch a slave OFF or remove 80  of the devices     L  What is the cycle time of the installation     LJ Fix all the faults  Check if the    Syncs    have stopped     Version 1 6     7 October 2008 Page 49 
52. ng items can be implemented in and around your installation to make it more reliable     CI Repeater backbones with repeaters ProfiHubs  isolation of problems    LJ External powered termination  removing adding devices   I Reduce the baudrate  improves signal quality    LJ Increase the repeats retries  increases success rate    I Reduce the spur stub lines or use repeaters ProfiHubs  improves signal quality    I Cable as close as possible to ground  decreases EMC sensitivity   I Additional grounding points  decreases EMC sensitivity   CI Activate the watchdog on all devices  safety    I Use fibre optic for long distances  isolation of problems     Version 1 6     7 October 2008 Page 53   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    Profilrace 2     User Manual    Version 1 6       October 2008 Page 54   80  ProfiTrace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    9 Technical Data of the ProfiCore Ultra    Technical Data ProfiCore Ultra    Dimensions and vveight    Dimensions L x W x H  mm  with DB9 108 x 68 x 28 mm  Weight Approximately 125 g       Ambient conditions    Operating temperature 0 to  60   Celsius  Storage temperature  20 to  70   Celsius  Isolation class IP 20  DIN 40 050        Power supply specifications    USB current consumption  without 400 mA  adapter     Adapter Voltage 9 V  Adapter current consumption 400 mA       Connect
53. of DP slaves    DP V1 DP V1 is the first extension of PROFIBUS DP V0  DP V1 devices comply  with the following features     Device related diagnosis is replaced by status and alarms     The first three octets of the user parameterization data are standardized   Optionally these devices may support     Acyclic communication  MS1  MS2      If alarms are used  MS1 is supported     Version 1 6     7 October 2008 Page 69   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    DP V2    DSAP    Electromagnetic  Compatibility    EMC    FDL    GSD file    HSA    Hub    Ident Number    ProfiTrace 2     User Manual    DP V2 is the second stage of extension of PROFIBUS DP after DP V1  DP   V2 devices shall comply with the following features      Data Exchange Broadcast  DxB  for slave to slave communication   publisher subscriber principle       lsochronous Mode  time tick synchronized operating slaves  e g  drives      Up  and or download of Load Region Data  domains      Clock Control  synchronization within slaves  and Time Stamping     Redundancy     See SAP     See EMC     The extent to which an electric or electronic device will tolerate electrical  interference from other equipment  immunity   and will interfere with other  equipment  Within the European Community as well as in other countries it  is regulated by law that electric and electronic components and equipment  comply with basic standards such as IEC 61000 6 2 or IEC 613
54. ofiTrace 2     User Manual    Fill in your name and organization     Customer Information    Please enter your information     User Name     tennis van Boome    Organization     PROCENTEC    Install this application For     fe Anyone who uses this computer  all users         Only For me  Dennis van Booma     Installshield     lt  Back Cancel         Click    Next    to proceed     Select your destination folder     Destination Folder    Click Next bo install to this Folder  or click Change to install to a different Folder     A Install ProfiTrace Y2 0  1 bo   C  Program Files Profitrace wz 0 11    InstallShield     lt  Back Cancel         Click    Next    to proceed     Version 1 6     7 October 2008 Page 16   80  ProfiTrace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    Check your settings     Ready to Install the Program    The wizard is ready to begin installation     IF you want to review or change any of your installation settings  click Back  Click Cancel to  exit the wizard     Current Settings     Setup Type     Destination Folder   C appiFrofiTrace wzi    User Information   Name  Dennis van Boormea    Company  PROCENTEC    InstallShield     lt  Back Install Cancel         Click    Install    to start the installation process     After the installation process  ProfiTrace is ready for use  however we recommend rebooting the PC     InstallShield Wizard Completed    The InstallShield Wizard has su
55. om  Internet  www efalcom com ar    AUSTRALIA    IS Systems Pty Limited   14 Laverick Ave   Tomago    NSW  Australia  2322   Tel    61 2 4964 8548   Fax   61 2 4964 8877   Email  fritz woller issystems com au    Internet  www issystems com au    Tyco Flow Control Pacific   1 Percival Road  Smithfield   NSW  Australia  2164   Tel    61 2 9612 2323   Fax   61 2 9612 2324    Email  nhsmith typac com au    AUSTRIA    Dipl Ing  Christoph Gudenus  Rotenmuehlgasse 40 5  1120 WIEN   Austria   Tel    43 1 812 34 20   Fax   43 1 812 31 55   Email  office gudenus at    Internet  www gudenus at    BELGIUM    Bintz Technics N V   Brixtonlaan 25    1930 ZAVENTEM  Belgium   Tel    32 2 720 49 16  Fax   32 2 720 37 50  Email  bloemen bintz be  Internet  www bintz be    Grott Trace  Manual EN doc    BRAZIL    Westcon Instrument  Indl Ltda  Rual Alvaro Rodrigues  257  Sao Paulo     SP   Brazil   CEP 04582 000   Tel    55 11 5561 7488   Fax   55 11 5093 2592  Email  paolo wii com br  Internet  www wii com br    Solution Engenharia de Automa    o   Av  do Contorno  7962  100  andar      Santo Agostinho  Belo Horizonte  Minas  Gerais     Brasil     CEP 30110 120   Tel    55 31 3335 7000   Fax   55 31 3335 7000   Email  solution solution   engenharia com br    Internet  www solution engenharia com br    CHILE    RP Ingenieria Limitada   Tucapel 92 oficina 52   Concepcion   Chile   Tel    56  0 41 2522592   Fax   56  0 41 2522592   Email  rodrigopinto rpingenieria cl  Internet  www rpingenieria cl 
56. ons with the PA Probe Ultra     The RS 485 driver is 1 5th of a standard PROFIBUS busload  The chance of disturbing a working  installation is therefore reduced to a minimum     ProfiCore Ultra has the capability to cache data in its on board memory in case of windows  performance problems or    higher    priority tasks like the hard disk  ProfiCore Ultra will NOT lose a  single message     Isolated USB Support  RS 485   DP Technology     pd  PROFIBUS Interface USB  Connector Connector        RDL EN si High Speed Expansion    wm Expansion    Oscilloscope RAM Cache Connector  Technology       Fig  1   Internal structure of the ProfiCore Ultra    Version 1 6     7 October 2008 Page 11   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    2 2 Support power connectors    In normal cases ProfiCore Ultra does NOT REQUIRE AN ADDITIONAL POWER SUPPLY  because of the USB connection     If your laptop PC is for some reason not able to supply the power to the ProfiCore  there are 2 options   1  Micro USB connection     This requires an additional USB port of your laptop PC  The Micro USB cable is provided with the  Troubleshooting Toolkit     2  Adapter  The adapter has to supply 9 V   500 mA with a power plug according to  NES J 21  NES J 21 W   NES J 210 XNES J 210  The adapter is NOT supplied with the product     2 3 Expansion connector    ProfiCore Ultra has an expansion connector  RJ 45  which can b
57. or descriptions    DB9  female      PROFIBUS Pin 3  B line  Pin 8  A line  Pin 6  VP  Pin 5  DGND  Case  Ground Shield    Expansion connector Pin 1  3 3 V output power  Pin 4  Trigger GND  Pin 5  Trigger  Pin 8  Power GND    Power connector Opening  6 0 mm  Center pin  1 95 mm    Plug according to  NES J 21  NES J 21 W  NES J 210  XNES J 210       Version 1 6     7 October 2008 Page 55   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    Technical Data ProfiCore Ultra    Oscilloscope specifications    Frequency 2 x 192 MHz  A line and B line   384 MHz  Differential measurement     Bandwidth 100 MHz    Voltage Differential   9 to  9 V  Single ended   4 5 to  8 5 V   with the PA Probe ultra these values are different        Version 1 6     7 October 2008 Page 56   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    10 Hotkeys    General    F1    Messages    F2  F3  F4  F5    Help     Toggle between RAW frames and decoded frames   Switch the Timestamp column between Tbit  sec  ms  us  date and time   Switch the Idle Time and Deltatime column between Tbit  sec  ms  us  date and time     Toggle between Hex data and Decimal data     Version 1 6     7 October 2008 Page 57   80    Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    Profilrace 2     User Manual    Vers
58. ostics  62 61 Set Parameters   Data Exchange messages do not use SAPs     A cable connecting to a bus segment  Spurs are not recommended in  PROFIBUS DP and prohibited with 12 Mbps and PROFIsafe operations   German term is  Stichleitung      See SAP   See Spur   See Bit Time     A powered resistor network at both ends of a segment to prevent reflections   for PROFIBUS DP      In a communications network  the pattern of interconnection between  network nodes  e g  bus  ring  star configuration     Version 1 6     7 October 2008 Page 72   80    Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    16 ISO 9001 2000 Certificate       QualityMasters    Stichting QualityMasters hereby declares that    PROCENTEC  VVATERINGEN    Has a management system that meets the requirements of the standard    NEN EN ISO 9001 2000    For the scope    Providing training courses  technical support  product development  and the exploitation of the test laboratory     Date of issue 11  April 2008  Valid until 11  April 2013  Certificate number NL 4792    de behalf of Stichting QualityMasters           SRTCI    N B  The failure to meet the conditions as set forth in the certification agreement  or non compliance  vvith the given standard and or guidelines  may lead to the suspension or cancellation of the certificate     ACCREDITED  This certificate remains the property of Stichting Quality Masters  EU9706010F  Version 1 6
59. play cursors for level and time analysis  click on    cursors        To have the oscilloscope carry out an A and B measurement  select  mode   The oscilloscope will now  display the A and B line separately     A powerful feature of the oscilloscope is the Bit Interpretation Engine  It displays the bits that  Profilrace detects on the bus  The end user can compare this with the signals that are measured with  the oscilloscope and make a judgment about the signal quality  see Fig  10      Version 1 6     7 October 2008 Page 31   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual              El ProfiTrace for ProfiCore Ultra   2 1  c  2004 27   File Action Filter Trigger Toolbars View Repo  Profilrace ScopeWare   Bar graph   Topology   Net       li x   Freezing the    screen   Mode   B A Diff vl B A Diff scale  1V   Div  vii Trigger  Start of response vl  Reset trigger delay    Address 136 sl Trigger   Message       M Cursors active    Trigger delay     z    Measurement    Displays cursors  Mode    Double click onthe  devices for triggering       Fig  9     ScopeWare       ProfiTrace H for ProfiCore Ultra  c  2004 2007 PROCENTEC q i  18  xi  File Action Filter Trigger Toolbars View Settings Help    Profilrace ScopeWare   Bar graph   Network Manager   ProfiCaptain     Mode  B A Dit   El B A Dif scale  1V Div mA A Dif scale        Time scale  1 uSec JH PF 801  sD2  SD4 P Short Ack  Address  27 vl T
60. r Trigger Tooli    ProfiTrace ScopeWare   Bar grap    Mode    B A Diff DI DA Di vl Time scale  250 nSec dre VW SD1 M SD2 Jv SD4 jw Short Ack    Address  43 DI Trigger   Message    Freeze IV Cursors active         Detected glitch  in the signalling                orl  CA  mea   Distance 177m    1544889 Hz  it Factor   0 97 Bits  Volt Cursors    4 88 V   Cursor 2     1 228    CursorDiff    Detected glitch  in the signalling    Fig  23     Termination missing or wire break  far     6 3 Short circuit between the A and B line    When there is a short circuit between the A and B line  the reflection will step by step crash the signal  to very low amplitude  The width of the steps can tell us the distance to the    problem point   When the  distance is nearby  the reflections are compressed in the bit  Fig  24 shows an example of a short  circuit nearby     When the distance is far  the reflections end up in the adjacent bits  but the signal amplitude does not  crash completely  The loop resistance causes left over amplitude that could be enough for the devices  to remain in Data Exchange  Fig  25 shows an example of a short circuit when the distance is far     Version 1 6     7 October 2008 Page 45   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    ProfiTrace 2     User Manual    ProfiTrace 2 for ProfiCore Ultra V2 0 beta  c  2004 2007 PROCENTEC n  18 x     File Action Filter Trigger Toolbars View Report Settings Help  Profilrace ScopeWwar
61. rameterization data between  master class 1 and its slave are matching     Version 1 6     7 October 2008 Page 70   80    Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    Live List    MPI    PA    PCB    Pl    PNO    PROFIBUS DP    PROFIBUS PA    Repeater    ProfiTrace 2     User Manual    The Live List is a matrix that lists all the available devices  It is directly visible  which devices are    troublemakers     With different background colours the  status of the devices is displayed  The Live List can also generate the  product name of the devices when a diagnostic message is captured   synchronized with the GSD library      Multiple Protocol Interface  Protocol defined by Siemens which uses the  layer 1 and 2 of PROFIBUS  FDL      See PROFIBUS PA     Printed Circuit Board     PROFIBUS International   The International PROFIBUS Organization based in Karlsruhe     PROFIBUS Nutzer Organization   The German PROFIBUS Organization based in Karlsruhe     Acronym for  PROFIBUS for Decentralized Peripherals   Specification of an  open fieldbus system with the following characteristics      Polling master slave system  cyclic communications  MSO      Flying masters with robin round token passing coordination  MM      Connection based  MS1  and connectionless  MS2  MS3  acyclic  communication between masters and slaves   Options  e g        Data exchange broadcast  DXB   i e  slave to slaves communication    lsochronous mode of sl
62. rigger  Message  j  2 Trigger  Start of response la iv Freeze l Cursors active   Trigger delay           Bit interpretation Detected glitch  in the signalling                Fig  10     Bit interpretation    Version 1 6     7 October 2008 Page 32   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved       PROGENTEG    Profilrace 2     User Manual    5 3 Bar graph    The Bar graph illustrates an average level of the signals from all available devices  see Fig  11   It is a  helpful utility to see an overall signal quality of the network        a ProfiTrace for ProfiCore Ultra V2 1  c  2004 2008 PROCENTEC ProfiCore Ser Nr  xxxxx00002 l    e  x     File Action Filter Trigger Toolbars View Report Settings Help             ProfiTrace   Scopeware  Bat Ser   Topology   Netwa  AB Diff stable voltage mem                   Fig  11     Bar graph    The average amplitude should be around 5 V  When there are bus problems the Bar graph will display  different Voltage levels and the colour of the bars will change     Fig  12 shows an example of the Bar graph when the bus cable is missing termination or when there  is a wire break  The voltage levels are much higher because of the extensive reflections     Fig  13 shows and example of the Bar graph when there is low impedance or short circuit in the bus  cable  The voltages are lower than normal and some bars are coloured red     Version 1 6     7 October 2008 Page 33   80  Profi Trace2 Manual EN docx    
63. right   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    This chapter contains some exercises to enhance the practical knowledge of ProfiTrace 2   7 1 First steps    Assignment 1 Software installation    Install the ProfiTrace software on the PC Laptop    Copy Install the required license file in the  APP directory    Copy the required GSD files to the GSD directory of ProfiTrace   Connect the ProfiCore Ultra to the PC Laptop    Test the installation by starting the software and click on    Init ProfiCore        D UDU DULD    When the software is running  the Live List of the PROFIBUS Installation should be visible     LJ Scan the GSD files and check the Live List by switching the PLC ON OFF     Assignment 2 Drawing of the installation    LJ Create a technical drawing of the PROFIBUS installation  finish it within 15 minutes    Instructions      Indicate clearly the location of the devices with its name and if it is a master or slave      Indicate the network addresses by looking at the dip switches or rotary switches      Indicate how the cable is going in and out the connectors       Indicate the location of the termination     Do not remove cable tray covers or open connectors     Assignment 3 Assessment of the connected devices   LJ Start and initialise ProfiTrace    What is the detected baudrate    How many masters and or slaves does this installation have     Does the Live List correspond with your drawing     D UU U    scan the GSD library and switch
64. rof  Add Copy GSD to catalog  e 6 Catals         Loe eee mera Zoom in   Zoom out   J Draw Wire  Setup Master   Class 2 Commands   DP41 Class2   Watch Modify 1 0      GSD   Network Sheet             Generate Catalog                                                        SITRANS FM  SITRANS P  SITRANS T SIEMENS  SRD960   SRD991   Stellungsregler TZID F  Stratos 222n X Series  Temperatur Messumformer T  TF12 ABB   TMT184 E H   TP303   Transmitter 1 Al  PhyL 0   Transmitter 1 Al  Phyl 1   Transmitter AF800  Transmitter TF211  TRIOWIRL Y_4000 S_ 400  TT303 SMAR   UFC 3 Beam   VEGAPULS 40 50 V2 0  VK 636 GMC AG    YPOIFC300  MBF  Rev 2  gt   La    Slave Info   Modules      tem Description       i                Packeterrors 0    Click    Settings    followed by    Generate Catalog    to scan the GSD files     To remove a GSD file from the catalog you need to manually delete the file from the GSD directory  and generate the catalog again  Settings  gt Generate Catalog      Version 1 6     7 October 2008 Page 21   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved       PROGCENTEG    Profilrace 2     User Manual    3 9 Setting colour preferences    The colours of the ScopeWare  signals and background  can easily be set adjusted in the  Settings Preferences menu     3 ProfiTrace for ProfiCore Ultra   2 1  c  2004 2008 PROCENTEC                                           Preferences       Click on    ScopeWare    to set the oscilloscope colours     
65. s reserved    PROGENTEG    Profilrace 2     User Manual    Version 1 6     7 October 2008 Page 4   80  ProfiTrace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    1 Product DESCHIDUUOM BE 7  ML  Produ OaE S en eee ee eee ee TE me ed ee eee 8  te eelere E 8  To DoR TAPIS en one eee een eee ee ee eee ee 9  t4 NS IEC CIU CIC    oo eee een nee etat Cnet ee eae ee er eee mes een ere 10  E  PORC OF E 11  Al WACO UNS UIC dE 11  22 Support power ee TE te 12  23 Expansion CONC TO eege 12  3 Software Installation Instructions  Windows XP             cccccessseesseeeeeseeeeeeeeneeeseeeeeeeeeneesseaneeeseneeens 13  3    Lu Een PROCS OUI EEN 13  OD MIO VO TINS E NO EE 13  eo EE 14  3 4  ProfiCore Ultra driver installation  ss  14  39  Pronlraceinstalatior  EE 15  3 6 Connecting ProfiCore Ultra to the USB port 2 0 0    cece ccccceeeeeeeeeae cece eeseeeesaeeeseeeseeeeseeeeseeeeaes 18  3 7 Installing GSD files in Profi Trace sisi  20  3 8 Installing GSD files in ProfiCaptain iii  21  AH Setting Colour preferences               ccccccccssecccesecceeecescecaucecueeceeesaeecsueecsueesueesseessueessueessaeeseueeseeeess 22  OO  NI SS a detonate deste deans dacteaeeoseecaa  23  A LICENSES SY StCM caient sentiments tim   siumenesanesst   s   smitursimenomss sis 25  dl OC ROM E 25  4 2 Characteristics of the license file name    25  4 3 Storage location of the license files    26  4 4 Obtaining the license files A 26  OUI RSA E 
66. this manual as much as possible  Since deviations cannot be  precluded entirely  we cannot guarantee full agreement  However  the content in this manual is  reviewed regularly and any necessary corrections included in subsequent editions  Suggestions for  improvement are welcomed     PROCENTEC Tel    31  0 174 671800  Turfschipper 41 Fax   31  0 174 671801  2292 JC WATERINGEN Email  info procentec com  The Netherlands Web  www procentec com  Version 1 6     7 October 2008 Page 2   80    ProfiTrace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    Important Information    Purpose of the Manual  This user manual provides information how to work with ProfiTrace 2     Recycling and Disposal  The parts of the ProfiCore Ultra can be recycled  For further information about environment friendly  recycling and the procedure for disposing of your old equipment  please contact     PROCENTEC  Turfschipper 41   2292 JC WATERINGEN  The Netherlands    Tel    31  0 174 671800  Fax   31  0 174 671801  Email  info procentec com    Document Updates   You can obtain constantly updated information on PROCENTEC products on the Internet at  www procentec com   You can also contact PROCENTEC Customer Support    e By phone at  31  0 174 671800   e By fax at  31  0 174 671801   e By email at support procentec com    Version 1 6     7 October 2008 Page 3   80  ProfiTrace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all right
67. ts that comply with PROFIBUS and RS 485 interface   This product can only function correctly and safely if it is transported  stored  set up  installed   operated and maintained as recommended     The ProfiCore Ultra is a CE class A product  In a domestic environment it may cause radio  interference in which case the user may be required to take adequate measures     Disclaimer of Liability   We have checked the contents of this manual as much as possible  Since deviations cannot be  precluded entirely  we cannot guarantee full agreement  However  the content in this manual is  reviewed regularly and any necessary corrections included in subsequent editions  Suggestions for  improvement are welcomed     PROCENTEC Tel    31  0 174 671800  Turfschipper 41 Fax   31  0 174 671801  2292 JC WATERINGEN Email  info procentec com  The Netherlands Web  www procentec com    Version 1 6     7 October 2008    PROGCENTEG    ProfiTrace 2     User Manual    CIRE  ULTRA       User Manual    Profilrace 2    PROFIBUS Combi Analyzer on USB    PROFIBUS analyzer with powerful statistics  High speed digital oscilloscope   Bar graphs   Topology scan   DP V0 V1 master   Reporting    PROFIBUS to USB interface   Suitable for PROFIBUS DP and PA   9 6 kbps to 12 Mbps   ProfiTrace 2 is suitable for XP and Vista platforms    Version 1 6     7 October 2008 Page 1 80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    Copyright
68. u should  make the update time higher  You can do this in the settings menu  Preferences    gt Live List settings  gt Assume station lost after     Why are some devices in the Live List blinking from Red to Green    The blinking devices  are devices that have master and slave functionality at the  Same time Red means master  Green a slave in Data Exchange  Nothing is  wrong  But a lot of people make mistakes with the busparameters  because they  have to be identical on all masters     With other tools that use PCMCIA and PCI cards  the Live List stops when  I select another function  Is this better organized with ProfiTrace    YES  because of the ProfiTrace 2 structure everything keeps on running  You can  select multiple options and processes that run separately     For generating a PDF file of the report  can you advice a freeware PDF  creator    For creating PDF files you can use the freeware tool PDFill  You can download it  at  www pdfill com    When I order ProfiTrace without the ScopeWare  Topology scan and Bar  graph  can I buy these modules later   YES  licenses for every single software option can be purchased at any time     Can the Topology scan create a network drawing of the Profibus PA  network    At the moment it is only RS 485  DP   For PA it will be very difficult due to  junction boxes and Ex barriers     Version 1 6     7 October 2008 Page 59   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTra
69. ual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    Profilrace 2     User Manual    LJ Switch a slave OFF  screen should be filling with 20  messages      LI Investigate what you see     LJ Fix all the faults  Check if the    Syncs    have stopped     Version 1 6     7 October 2008 Page 51   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    Profilrace 2     User Manual    Version 1 6       October 2008 Page 52   80  ProfiTrace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    ProfiTrace 2     User Manual    8 Tips and Tricks    This chapter contains some tips and tricks to make working with ProfiTrace a lot easier     8 1 Checklist to prepare your installation    The following items can be implemented in and around your installation to simplify PROFIBUS  troubleshooting     C1 Measurement connectors on every segment  start of the cable    CI Every segment has its own addressing range  10  19  20  29  etc    Individual repeaters OLMs can be powered up down   Individual devices can be powered up down   PLC DCS at the beginning of the cable   Diagnostics is enabled in the devices   Installation drawing on 1 or 2 pages  with cable lengths and addresses   Addresses clearly marked on the devices    All GSD files are available in ProfiTrace       UUUUUULU    Access to the PLC DCS configuration    8 2 Checklist to create a reliable installation    The followi
70. update Info Panel  2          Fig  7     Live List after initialization    From this point the software can be easily navigated to different modes by just clicking on its  representing tab  see Fig  8     e Profil race  Live List  Message Recording  Statistics and Data Inspection   e ScopeWare   e Bar graph   e Topology scan   e ProfiCaptain DP VO V1 class 1 and 2    All modes work parallel  Navigating to another mode will NOT erase the information from the previous  mode     Version 1 6     7 October 2008 Page 30   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    Profilrace 2     User Manual    a ProfiTrace for ProfiCore Ultra   2 1  c  2004 2008 PROCENTEC ProfiCore Ser Nr  xxxxx00002 E      x   File Action Filter Trigger Toolbars View Report Settings Help          Fig  8     Navigating in ProfiTrace    5 2 ScopeWare    The ScopeWare is a real time oscilloscope for the inspection of the signal quality  After selecting this  tab the first time after starting ProfiTrace  the oscilloscope runs immediately in differential mode   displaying all signals that are measured  see Fig  9   The time base and voltage levels can easily be  adjusted     The screen refresh can be halted by clicking on    freeze        By double clicking on the devices in the Live List  the oscilloscope triggers on the respective device  and only displays its signals  This is a perfect mode to inspect the signal quality for individual devices     To dis
71. ways use the latest version of ProfiTrace and ProfiCore Ultra drivers  Updates  can be downloaded from  www procentec com    CI Install the latest service packs and    hot fixes    for Windows    LJ Boot the PC in the normal mode of Windows  NOT in the safe mode      CI Under multi user versions installations of Windows make sure you have administrator rights        Do NOT connect the ProfiCore Ultra to the USB port  yet      Version 1 6     7 October 2008 Page 13   80  ProfiTrace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    Profilrace 2     User Manual    3 3 Setup program    Insert the Drot Trace CD in the CD ROM drive and or start the Setup exe  The install shield will  display an introduction screen  see next screenshot      emm    MdinstalllProfiCore Ultra drivers Ll           _    install ProfiTrace 2  heal JE Con      Y    Busmonitor   Oscilloscope   Master    PROCENTEC       Click    Install    to install ProfiTrace and the ProfiCore Ultra driver  If you only want to install one of  them  just unselect the option you want to skip     3 4 ProfiCore Ultra driver installation  The install shield will first install the ProfiCore Ultra driver  In a window the results of the installation    can be followed  Blue letters are OK  red letters indicate a problem  The driver can also be installed  manually by starting    Driverlnstall exe        INSTALLING driver ProftCoreUltra_driverint       Version 1 6     7 October 2008 Page 14   8
72. y       l x                               Li    11   Deltapilot S       The I Os can be easily watched and manipulated  If needed  class 2 functions and DP V1 services can  be applied on all devices in the network  even when they are not configured or belong to another    master  see Fig  17      Version 1 6     7 October 2008    Profi Trace  Manual EN doc       Page 37   80     PROCENTEC 2003 2008   Copyright   all rights reserved    PROGENTEG    Profilrace 2     User Manual    5  ProfiTrace II for ProfiCore Ultra  c  2004 2007 PROCENTEC I d laj xi  File Settings Help  ProfiTrace   ScopeWare   Bar graph   Network Manager ProfiCaptain      Load Project   Save Project   Zoom in   Zoomout   J Draw Wire  Setup Master   Class 2 Commands   DP4 1 Class2   Weatch Modify 1 0    NetWork Sheet                                11   Deltapilot S      Stellungsregler TZID F      Stratos 222n X Series    aw Temperatur Messumformer T     TF12 ABB      TMT184 E H      TP303      Transmitter 1 Al  PhyL 0       Transmitter 1 Al  PhyL 1       Transmitter AF800      Transmitter TF211      TRIOWIRL V_4000 S_400       TT303 SMAR z  Se  4 La    Slave Info   Modules     tem Description     GSD Filename EH3 1503 GSD   Vendor Name Endress   Hauser       Model Name Deltapilot 5  2nd Generation    Ident Number 0x1503  Bitmap EH1503_N       Fig  17     ProfiCaptain special functions    Version 1 6     7 October 2008 Page 38   80  Profi Trace2 Manual EN docx    PROCENTEC 2003 2008   Copyright   all rights r
    