1. Industrial Electronic Devices User Manual Revision 1 000 English M Bus Slave Serial Converter Order Code HD67018 B2 For Website information www adfweb com Product HD67018 For Price information www adfweb com Price HD6 7018 B2 Benefits and Main Features Very easy to configure 4 Temperature range 40 C 85 C 40 F 185 F User Manual ADFweb com S r l User Manual M Bus Slave Serial Document code MN67018 ENG Revision 1 000 Page 1 of 21 For others M Bus products see also the following link Converter M Bus Master to www adfweb com Product HD67021 RS232 www adfweb com Product HD67022 RS485 www adfweb com Product HD67024 USB www adfweb com Product HD67030 Ethernet M Bus Analyzer Scanner Sniffer www adfweb com Product HD67031 M Bus Repeater Isolator www adfweb com Product HD67032M Converter M Bus Master www adfweb com Product HD67029M 485 Modbus Slave www adfweb com Product HD67044 Modbus TCP Slave www adfweb com Product HD67051 B2 CANopen www adfweb com Product HD67053M PROFIBUS www adfweb com Product HD67056 B2 BACnet Slave www adfweb com Product HD67058M DeviceNet Slave www adfweb com Product HD67077 B2 EtherNet IP Slave www adfweb com Product HD67078 B2 PROFINET M Bus Concentrator Datalogger www adfweb com Product HD67054M M Bus Slave Modbus Master Converter www adfweb com Product HD67059M 232 Do you have an your customer proto
2. Serial Document code MN67018_ENG Revision 1 000 Page 15 of 21 Industrial Electronic Devices SET COMMUNICATION This section define the fundamental communication parameters of two buses M Bus and serial By Pressing the Set Communication button from the main window for SW67018 Fig 2 the 7 window Set Communication appears Fig 3 SW670 1 Set Communication Setting The means of the fields for the Serial section are Serial Baudrate 2400 In the field Baudrate the baudrate for the serial line is defined Inthe field Parity the parity of the serial line is defined Parity EVEN The means of the fields for the M Bus Slave section are aan Baudrate 9600 In the field Baudrate the baudrate for the M Bus line is defined are Inthe field Parity the parity of the M Bus line is defined Panty ODD oF OK Figure 3 Set Communication window ADFweb com S r l Industrial Electronic Devices k Document code MN67018_ENG User Manual M Bus Slave Serial Revision 1 000 Page 16 of 21 UPDATE DEVICE By pressing the Update Device button it is possible to load the created Configuration into the device and also the Firmware if necessary In order to load the parameters or update the firmware in the device follow these instructions s amp Turn off the Device Connect the RS2
3. 32 cable form your PC to the Converter Put Jumperi in Boot position see FUNCTION MODES section Turn on the device Select the COM port and press the Connect button Check the Device state LED It must blink quickly see LEDS section Press the Next button Select which operations you want to do Press the Execute update firmware button to start the upload When all the operations are OK turn off the device Put Jumperi in Normal position Disconnect the RS232 Cable Turn on the device At this point the configuration firmware on the device is correctly updated Figure 4 Update Device windows saan oars Ver 1 100 INIT Waiting FIRMWARE Waiting PROJECT Waiting n ADFweb com S r l SW67 018 Update Device Using the Serial Port Follow these steps to update from RS232 1 Turn OFF the Device 2 Insert the Boot Jumper to set the Boot Mode 3 Select the COM Port for the Update 4 Turn ON the Device SW6 018 Update Device Using the Serial Port Update Device Options Firmware Read Firmware After Write Configuration Read Configuration After Write ut Execute Update Firmware User Manual M Bus Slave Serial Document code MN67018_ENG Revision 1 000 Page 17 of 21 Industrial Electronic Devices e J TA Note When you install a new version of the software if it is the first time it is better you do the update o
4. 485 Line Boot configuration T M Bus Connector 2200hm 3 Ga M Bus Slave Serial Converter EF ee i E HD67018 B2 www ADFweb com ak On 220 ohm a a m ED Oo IOV Ground i V Positive wire V AC min 8V max 21V V DC min 8V max 35V Yes Jumper Boot Mode No Jumper Normal Mode OOS vOOQOQ000 Connectors3 RS232 port D SUB9 Male me PIN3 TX PINS GND to Isolated Ground Used for Programmation port Serial communication To connect the device to the COM port of a PC in order to set it you have to use the programming cable AC34107 or a cable made as showed here CABLE Side B CABLE Side A Figure 1 Connection scheme for HD67018 B2 ADFweb com S r l M Bus Slave Serial Document code MN67018_ENG Revision 1 000 Page 5 of 21 User Manual M Bus Slave Serial Document code MN67018_ENG Revision 1 000 Page 6 of 21 Industrial Electronic Devices CHARACTERISTICS The HD67018 B2 is a M Bus Slave Serial Converter It allows to insert RS232 RS485 devices that uses M Bus protocol into a M Bus physics network It allows for the following characteristics Two directional information between M Bus bus and Serial RS232 RS485 bus Mountable on 35mm Rail DIN Wide power supply input range 8 21V AC or 8 35V DC Wide temperature range 40 C 85 C 40 F 185 F CONFIGURATION You need Compositor SW67018 software on y
5. DFweb com S r l shall not be liable for consequences of improper use OTHER REGULATIONS AND STANDARDS WEEE INFORMATION Disposal of old electrical and electronic equipment as in the European Union and other European countries with separate X collection systems m This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish Instead it should be taken to an applicable collection point for the recycling of electrical and electronic equipment If the product is disposed correctly you will help prevent potential negative environmental factors and impact of human health which could otherwise be caused by inappropriate disposal The recycling of materials will help to conserve natural resources For more information about recycling this product please contact your local city office your household waste disposal service or the shop where you purchased the product RESTRICTION OF HAZARDOUS SUBSTANCES DIRECTIVE 4 The device respects the 2002 95 EC Directive on the restriction of the use of certain hazardous substances in electrical OHS and electronic equipment commonly referred to as Restriction of Hazardous Substances Directive or ROHS 2002 95 EC CE MARKING The product conforms with the essential requirements of the applicable EC directives ADFweb com S r l User Manual M Bus Slave Serial Document code MN67018 ENG Revision 1 000 Page 21 of 21 Industrial Electronic D
6. asker p n C522 2x 24AWG twisted pairs conductor foil shield braid shield ADFweb com S r l User Manual M Bus Slave Serial Document code MN67018_ENG Revision 1 000 Page 11 of 21 Industrial Electronic Devices RS232 The connection from RS232 socket to a serial port example one from a personal computer must be made with a NULL MODEM cable a serial cable where the pins 2 and 3 are crossed It is recommended that the RS232 cable not exceed 15 meters M BUS The M Bus is a unpolarized bus A two wire standard telephone cable JYStY N 2 0 8 mm is used as the transmission medium for the M Bus The maximum distance between a slave and the repeater is 350m this length corresponds to a cable resistance of up 290 This distance applies for the standard configuration having Baud rates between 300 and 9600 Baud and a maximum of 250 slaves The maximum distance can be increased by limiting the Baud rate and using fewer slaves but the bus voltage in the space state must at no point ina segment fall below 12V because of the remote powering of the slaves In the standard configuration the total cable length should not exceed 1000m in order to meet the requirement of a maximum cable capacitance of 180nF Taken from M Bus specifics ADFweb com S r l Connectors RS232 port D SUB9 Male PIN2 RX PINS TX PINS GND to Isolated Ground Used for Programmation port Serial communication To
7. bbe me P5485 port tenner EE OLSERO 6000000 2 m i 106 mm 60 mm 4 17 inch 2 36 inch Housing PVC Weight 200g Approx Figure 6 Mechanical dimensions scheme for HD67018 B2 ADFweb com S r l User Manual M Bus Slave Serial Document code MN67018 ENG Revision 1 000 Page 19 of 21 Industrial Electronic Devices ORDERING INFORMATIONS The ordering part number is formed by a valid combination of the following HD67018 B 2 L Connectors Type 2 Fixed 5mm Screw Terminal Enclosure Type B 6M 35mm DIN Rail mounting Device Family HD67018 M Bus Slave Serial Converter Order Code HD67018 B2 M Bus Slave Serial Converter Serial RS232 RS485 ACCESSORIES Order Code AC34001 35mm Rail DIN Power Supply 220 240V AC 50 60Hz 12 V AC Order Code AC34002 35mm Rail DIN Power Supply 110V AC 50 60Hz 12 V AC ADFweb com S r l User Manual M Bus Slave Serial Document code MN67018 ENG Revision 1 000 Page 20 of 21 Industrial Electronic Devices DISCLAIMER All technical content within this document can be modified without notice The content of the document is a under continual renewal For losses due to fire earthquake third party access or other accidents or intentional or accidental abuse misuse or use under abnormal conditions repairs are charged to the user ADFweb com S r l will not be liable for accidental loss of use or inability to use this product such as loss of business income A
8. cates that non observance of the safety instructions is a danger for people that could lead to serious injury or A death and or the possibility of damage CE CONFORMITY The declaration is made by our company You can send an email to support adfweb com or give us a call if you need it ADFweb com S r l User Manual M Bus Slave Serial Document code MN67018_ENG Revision 1 000 Page 4 of 21 Industrial Electronic Devices i EXAMPLE OF CONNECTION ai a gt M Bus Network SOOVODOGOOOS OOO000980 OV V Boot configuration M Bus 8 21V AC on a _ PE or g Jumper 1 reared A M Bus Master maawa CE S M Bus Slave Serial Converter s i 2 HD67018 B2 u Bah y www ADFweb com P Qn 220 ohm Termination g SASS En o mo Converter used to insert RS485 devices that uses M Bus protocol into a physics M Bus network oo 8 Gere A 8 S32 A SNe S amp S DB Oe A 8 SNCs eg eC eve c amp 8 Orau BD SB 8 M Bus Slave meters with M Bus interface Gi CALEFF 4 7554 s popan Nman Nas c LLL Ka i e086 82 S Sente S Oyere T T B84 O E Be o T amp Ghee o MT Ml Se ie 82 HT Fie e 8 M Bus Slave meters with RS485 interface ADFweb com S r l Industrial Electronic Devices i User Manual CONNECTION SCHEME S Shield to Isolated Ground B Negative wire A Positive wire Jumper2 Termination RS
9. col www adfweb com Product HD67003 Do you need to choose a device do you want help www adfweb com Cmd helpme Industrial Electronic Devices INDEX UPDATED DOCUMENTATION REVISION LIST WARNING TRADEMARKS SECURITY ALERT EXAMPLE OF CONNECTION CONNECTION SCHEME CHARACTERISTICS CONFIGURATION POWER SUPPLY FUNCTION MODES LEDS RS485 RS232 M BUS USE OF COMPOSITOR SW67018 NEW CONFIGURATION OPEN CONFIGURATION SOFTWARE OPTIONS SET COMMUNICATION UPDATE DEVICE MECHANICAL DIMENSIONS ORDERING INFORMATIONS ACCESSORIES DISCLAIMER OTHER REGULATIONS AND STANDARDS WARRANTIES AND TECHNICAL SUPPORT RETURN POLICY PRODUCTS AND RELATED DOCUMENTS ADFweb com S r l ONDDUAWNNNNNYG 9 User Manual M Bus Slave Serial Document code MN67018_ENG Revision 1 000 Page 2 of 21 UPDATED DOCUMENTATION Dear customer we thank you for your attention and we remind you that you need to check that the following document is Updated Related to the product you own m To obtain the most recently updated document note the document code that appears at the top right hand corner of each page of this document With this Document Code go to web page www adfweb com download and search for the corresponding code on the page Click on the proper Document Code and download the updates REVISION LIST Revision Date Author Chapter Description 1 000 28 04 2014 Fl All First R
10. connect the device to the COM port of a PC in order to set it you have to use the programming cable AC34107 or a cable made as showed here CABLE CABLE Side A Side B FEM FEM User Manual M Bus Slave Serial Document code MN67018_ENG Revision 1 000 Page 12 of 21 Industrial Electronic Devices USE OF COMPOSITOR SW67018 To configure the Converter use the available software that runs with Windows called SW67018 It is downloadable on the site www adfweb com and its operation is described in this document This manual is referenced to the last version of the software present on our web site The software works with MSWindows XP Vista Seven 8 32 64bit When launching the SW67018 the window below appears Fig 2 SW6 018 M Bus Slave Serial Converter Opened Configuration of the Converter Begin Examplel Step 1 gt New Configuration Open Configuration Step 2 gt Set Communication Step 3 JE Update Device www ADFweb com Figure 2 Main window for SW67018 ADFweb com S r l User Manual M Bus Slave Serial Document code MN67018_ENG Revision 1 000 Page 13 of 21 Industrial Electronic Devices i NEW CONFIGURATION OPEN CONFIGURATION The New Configuration button creates the folder which contains the entire device s configuration SW67 018 Create New Configuration Name of the new Configuration Examples A device s configuration can also be impo
11. ectronic Devices C The device has got three LEDs that are used to give information about the functioning status The various meanings of the LEDs are described in the table below LED 1 Device state green 2 Serial communication green 3 M Bus communication green ADFweb com S r l Normal Mode Boot Mode Blinks slowly 1Hz Blinks quickly Blinks slowly 1Hz when no characters are received by the serial or Blinks quickly for a while when receives something from the serial Blinks slowly 1Hz when no characters are received Blinks quickly for a while when receives something from the M Bus Ledi Green Device state jcommunication communication 7 User Manual M Bus Slave Serial Document code MN67018_ENG Revision 1 000 Page 10 of 21 Industrial Electronic Devices RS485 To terminate the RS485 line with a 220 resistor it is necessary to insert the Jumper2 like in figure Jumper2 Termination RS485 Line Open iS Shield to Isolated Ground IB Negative wire 220 ohm A Positive wire The maximum length of the cable should be 1200m 4000 feet Here some codes of cables Belden p n 8132 2x 28AWG stranded twisted pairs conductor foil shield braid shield Belden p n 82842 2x 24AWG stranded twisted pairs conductor foil shield braid shield Tasker p n C521 1x 24AWG twisted pair conductor foil shield braid shield T
12. elease WARNING ADFweb com reserves the right to change information in this manual about our product without warning ADFweb com is not responsible for any error this manual may contain TRADEMARKS All trademarks mentioned in this document belong to their respective owners User Manual M Bus Slave Serial AL Document code MN67018 ENG Revision 1 000 Page 3 of 21 Industrial Electronic Devices SECURITY ALERT GENERAL INFORMATION To ensure safe operation the device must be operated according to the instructions in the manual When using the device legal and Safety regulation are required for each individual application The same applies also when using accessories INTENDED USE Machines and systems must be designed so the faulty conditions do not lead to a dangerous situation for the operator i e independent limit switches mechanical interlocks etc QUALIFIED PERSONNEL The device can be used only by qualified personnel strictly in accordance with the specifications Qualified personnel are persons who are familiar with the installation assembly commissioning and operation of this equipment and who have appropriate qualifications for their job RESIDUAL RISKS The device is state of the art and is safe The instruments can represent a potential hazard if they are inappropriately installed and operated by untrained personnel These instructions refer to residual risks with the following symbol This symbol indi
13. evices WARRANTIES AND TECHNICAL SUPPORT For fast and easy technical support for your ADFweb com SRL products consult our internet support at www adfweb com Otherwise contact us at the address support adfweb com RETURN POLICY If while using your product you have any problem and you wish to exchange or repair it please do the following Obtain a Product Return Number PRN from our internet support at www adfweb com Together with the request you need to provide detailed information about the problem Send the product to the address provided with the PRN having prepaid the shipping costs shipment costs billed to us will not be accepted If the product is within the warranty of twelve months it will be repaired or exchanged and returned within three weeks If the product is no longer under warranty you will receive a repair estimate ADFweb com S r l Via Strada Nuova 17 IT 31010 Mareno di Piave TREVISO Italy Phone 39 0438 30 91 31 Fax 39 0438 49 20 99 www adfweb com ADFweb com S r l
14. f the Firmware in the HD67018 B2 device lt K Note When you receive the device for the first time you also have to update the Firmware in the HD67018 B2 device Warning A If Fig 5 appears when you try to do the Update try these points before seeking assistance Ver 1 100 INIT PROTECTION Check if the serial COM port selected is the correct one Check if the serial cable is connected between the PC and the device FIRMWARE PROTECTION Try to repeat the operations for the updating Soa RR EA If you are using a USB D gt RS232 converter try to use a native COM port Try with another PC SSS SSS Try to restart the PC If you are using the program inside a Virtual Machine try to use in the main Figure 5 Protection window Operating System If you are using Windows 8 Seven or Vista make sure that you have the administrator rights Take attention at Firewall lock A In the case of HD67018 B2 you have to use the software SW67018 www adfweb com download filefold SW67018 zip ADFweb com S r l User Manual M Bus Slave Serial AL Document code MN67018_ENG Revision 1 000 Page 18 of 21 Industrial Electronic Devices MECHANICAL DIMENSIONS 96 D Ww Ww Wa Ws a t W 3O ki Boot configuration M Bus on Connector oer Eam Ee we CE re ree ar Bey Gq M Bus Slave Serial Converter E FLST HD67018 B2 uo a mee i on i i Gn wD 220 ohm
15. our PC in order to perform the following Define the parameters of M Bus line Define the parameters of serial RS232 RS485 line Update the device ADFweb com S r l User Manual M Bus Slave Serial Document code MN67018_ENG Revision 1 000 Page 7 of 21 Industrial Electronic Devices POWER SUPPLY The devices can be powered at 8 19V AC and 8 35V DC For more details see the two tables below Consumption at 24V DC Device Consumption W VA Caution Do not reverse the polarity power Positive wire VAC min 8V max 21V V DC min 8V max 35V HD67018 B2 ADFweb com S r l User Manual M Bus Slave Serial Document code MN67018_ENG Revision 1 000 Page 8 of 21 Industrial Electronic Devices FUNCTION MODES The device has got two functions mode depending of the position of the Jumperi of HD67018 B2 The first without the jumper inserted is used for the normal working of the device The second with the jumper inserted is used to upload the Project Firmware For the operations to follow for the updating see UPDATE DEVICE section According to the functioning mode the LEDs will have specific functions see LEDS section Jumperi Functioning mode EE Yes Jumper No Jumper Boot Mode Normal Mode ADFweb com S r l LEDS User Manual M Bus Slave Serial Document code MN67018_ENG Revision 1 000 Page 9 of 21 Industrial El
16. rted or exported To clone the configurations of a programmable M Bus Slave Serial Converter in 2E es order to configure another device in the same manner it is necessary to maintain the SW6 0 18 folder and all its contents Open an Existing Configuration To clone a project in order to obtain a different version of the project it is sufficient List of Avaliable Configurations to duplicate the project folder with another name and open the new folder with the button Open Configuration ADFweb com S r l User Manual M Bus Slave Serial Document code MN67018_ENG Revision 1 000 Page 14 of 21 Industrial Electronic Devices k SOFTWARE OPTIONS By pressing the Settings gt button there is the possibility to change the language of the software and check the updatings for the compositor In the section Language it is possible to change the language of the software SW670 1 8 Software Options SW6 018 Software Options Connection Options Enable Internet Connection Check Software Update at Start of Program Check Available Update In the section Connection Options it is possible to check if there are some updatings of the software compositor in ADFweb com website Checking the option Check Software Update at Start of Program the SW67018 check automatically if there are updatings when it is launched ADFweb com S r l User Manual M Bus Slave

Download Pdf Manuals