KIMO CP111 - CP112
Contents
1. co J a a 3 Power supply terminal block Output terminal block 3 5 a 3 t W aV U a i K 4 g ir K W 2 3 7 X 7 a l i a H i it Tr a S 1 4 Left DIP Hi sotencid valve connection switch Right DIP only CP111 Cable gland switch LCC S Pressure connections ELECTRICAL CONNECTIONS as per NFC15 100 standard A This connection must be made by a qualified technician To make the connection the transmitter must not be energized To make a 3 wire connection before powering up the transmitter please connect the output ground to the input ground See drawing below For CP111 112 113 AO models and CP111 112 113 AN models with 0 10 V or 4 20 mA output active 4 wires VP GND IP o p FE 123 4 5 67 VP GND IP i a toe Regulator display or PLC BMS Power supply 24 Vdc Power supply 24 Vac class Il PLC BMS passive type Regulator display or PLC BMS passive type Power supply 4 wi 24 Vac wires PN 3 wires For CP112 113 PO models and CP112 113 PN models with 4 20 mA output passive Power supply eee lal 16 30 Vde fo active type a t A l Display regulator PLC l passive type or SETTINGS AND USE OF THE TRANSMITTER gt Auto calibration CP 111 pressure transmitter has a temperature compensation of the gain from 0 to 50 C and an auto calibration process that guarantee
2. 3 3 m e To access the configuration via software Set the DIP switches as shown beside Nota the on off switch 1 of the right DIP switch can be in 4 E 4 E any position selection of the analogue output 0 10 V or 4 20 mA Left DIP switch Right DIP switch Connect the cable of the LCC S to the connection of the transmitter e Please refer to the user manual of the LCC S to make the configuration The configuration of the parameters can be done either with the DIP switch or via software you can not combine both solutions e 75 mm _ MOUNTING en To mount the transmitter mount the ABS plate on the wall drilling 6 mm screws and pins are oe supplied Insert the transmitter on the fixing plate see A on the drawing beside Rotate the housing in z l clockwise direction until you hear a click which confirms that the transmitter is correctly installed L O O Demm LO i Once the transmitter is installed and powered up please make an autozero to E guarantee the correct working of the transmitter in any position D14 mm 4 5mm o Co A O E lt l 7 5 MM _ MAINTENANCE Please avoid any aggressive solvent Please protect the transmitter and its probes from any cleaning product containing formalin that may be used for cleaning rooms or ducts OPTIONS AND ACCESSORIES e KIAL 100A Power supply class 2 230 Vac input 24 Vac output e Connection tube e Straight
3. connections e KIAL 100C Power supply class 2 230 Vac input 24 Vdc output e Connection fittings e Spherical coupling nut e LCC S configuration software with USB cable e Through connections Distributed by fae EXPORT DEPARTMENT Tel 33 1 60 06 69 25 Fax 33 1 60 06 69 29 Qualit e mail export kimo fr FTang transmitter_CP111 112 113 12 11 13 RCS 24 P rigueux 349 282 095 Non contractual document We reserve the right to modify the characteristics of our products without prior notice
4. KIMO Technical Data Sheet INSTRUMENTS Pressure Temperature Humidity Air Velocity Airflow Sound level Differential pressure transmitter a CP M CP 12 CP 118 KEY POINTS CP 110 Ranges from 100 100 Pa to 10000 10000 Pa according to models a Configurable intermediary ranges 0 10 V or 4 20 mA output active power supply 24 Vac Vdc 3 4 wires or 4 20 mA e m output passive loop power supply from 16 to 30 Vdc 2 wires ABS VO housing IP65 with or without display i ij _ 1 4 turn system mounting with wall mount plate Housing with simplified mounting system Solenoid valve for auto calibration only on CP111 model FEATURES OF THE HOUSING oT 46 mm Material ABS VO as per UL94 Protection IP65 Display LCD 10 digits Size 50 x 17 mm Height of digits Value 10 mm Unit 5 mm Connections ribbed 6 2 mm Cable gland for cables 8 mm maximum Weight 143 g i TECHNICAL FEATURES Measurement units Pa mmH O inWG mmHG daPa kPa hPa mbar Accuracy CP111 1 of reading 2 Pa CP112 1 5 of reading 3 Pa CP113 1 5 of reading 3 mmH O Response time 1 e 63 0 3 s Resolution 1 Pa 0 1 mmH O 0 01 mbar 0 01 inWG 0 01 mmHG 0 1 daPa 0 001 kPa Autozero Manual with push button Automatic by solenoid valve only on CP111 model Type of fluid Air and neutral gases Overpressure tolerated CP111 112 21000 Pa CP113 69 000 Pa
5. Operating temperature From 0 to 50 C Storage temperature From 10 to 70 C All the accuracies indicated in this technical datasheet were stated in laboratory conditions and can be guaranteed for measurements carried out in the same conditions or carried out with calibration compensation PART NUMBER To order just add the codes to complete the part number Example CP 113 AO Pressure transmitter measuring range 10 000 10 000 Pa CP11 0 10 V or 4 20 mA active with display Display Measuring range O with display 1 100 100 Pa N without display 2 1000 1000 Pa 3 10 000 10 000 Pa Power supply Output A Active 24 Vac Vdc 0 10 V or 4 20 mA P Passive 16 30 Vdc 4 20 mA TECHNICAL SPECIFICATIONS Output Supply active sensor 0 10 V or 4 20 mA alim 24 Vac Vdce 10 3 4 wires passive loop 4 20 mA power supply 16 30 Vdc 2 wires maximum load 500 Ohms 4 20 mA minimum load 1 K Ohms 0 10 V Consumption 2 VA 0 10 V or max 22 mA 4 20 mA Electromagnetical compatibility EN61326 Electrical connection Screw terminal block for cables from 0 05 to 2 5 mm or from 30 to 14 AWG Communication to PC USB mini DIN cable Environment Air and neutral gases CONNECTIONS Inside the front housing Fixed back housing Removable front face F4618 1246 VE s amp gt gt i PE s s g wos F a A ee A sess 0 it title s 7 aa INF IG i i
6. h 4 as indicated beside Example 0 100 Pa Full scale 0 0 100 Pa E a Central zero E 50 Pa 0 50 Pa Combinations Eo M Please follow carefully the combinations beside with the DIP switch If the combination is wrongly done the following message will appear A on the display of the transmitter CONF ERROR In that case you will have to unplug the transmitter place the DIP switches correctly and then power the transmitter up gt Output setting right DIP switch CP111 112 113 AO and CP111 112 113 AN models To set the type of analogue output please put the on off switch of the output as shown Configurations 4 20 mA 0 10 V beside 1 E in a i 9 C Combinations 3 3 7 n gt Units setting right DIP switch To set a measurement unit put the on off switches 2 3 and 4 of the units as shown in the table below Configurations Pa InWG mmHG daPa kPa hPa 1 4 tial LS 1 a Z 4 2 Combinations x 3 E E 3 OU Hoo mh oom 4 4 E 4 4 B CONFIGURATION VIA LCC S SOFTWARE option An easy and friendly configuration with the software Configuration via PC You can configure your own intermediary ranges 4 1 Caution the minimum difference between the high range and the low range is 20 2 2 For example it is possible to set the instrument from 20 to 0 Pa from 0 to 20 Pa or from 10 to 10 Pa
7. s over the time an excellent stability and a perfect reliability of the measurement on low and high ranges Auto calibration principle the microprocessor of the transmitter drives a solenoid valve that compensates the possible drifts on the sensitive element over the time The compensation is performed by the permanent adjustment of the zero So the measurement of the differential pressure is then independent from the environmental conditions of the transmitter Advantage no drift Frequency of auto calibration resetable or from 1 to 60 minutes gt Autozero To perform an autozero unplug the 2 pressure connections tubes and press the Autozero key On the CP111 transmitter it is not necessary to unplug the 2 pressure connection tubes When an autozero has been performed On green light turns off then turns on and on transmitters equipped with a display autoZ is displayed gt Configuration drawing below When the transmitter is configured you can power it up On off switch zal DIP switch Right DIP switch 1 Output setting 2 WE 3 A L gt Units setting Standard range or 4 central 0 setting Off On Off On A To configure the transmitter it must not be energized Then you can make the settings required with the DIP switches as shown on the a To configure the transmitter unscrew the 4 1 screws from the housing then open it DIP 2 switches allowing the different settings are 3 a Meas
8. uring ranges setting then accessible gt Measuring range settings left DIP switch To set a measuring range put the 1 2 and 3 on off switches as indicated in the table below E E E 2 M 2 WO 2 M 3 M 3 M 3x E 4 E O si Combination 1 Combination 2 Combination 3 Combination 4 Combination 5 Type of CP112 CP113 CP111 transmitter CP112 CP113 CP111 CP112 CP113 CP111 900 5 0 75 0 750 0 10 0 100 0 1000 0 CP111 CP112 CP113 CP111 100 500 100 0 3 0 25 0 250 0 4 0 ka 0 020 0 100 1 00 0 030 0 250 250 0 040 0500 5 00 0 050 0 750 0 100 1 000 10 00 hPa 0 20 1 00 10 00 0 30 2 90 25 00 0 40 9 00 50 00 0 50 7 50 75 00 1 00 10 00 100 00 e Measuring ranges of the CP111 transmitter on the 100 Pa range according to the measurement unit e Measuring ranges of the CP112 transmitter on the 1000 Pa range according to the measurement unit e Measuring ranges of the CP113 transmitter on the 10 000 Pa range according the the measurement unit Example e From 0 to 750 mmH O measuring range is 750 mmH O e From 500 Pa to 500 Pa measuring range is 1000 Pa gt Standard range central zero setting left DIP switch Configurations Full scale Central zero To set the type of measuring range put the on off switc