Home

Manual

image

Contents

1. SWITCH 6 PUMP DELAYS ON 12 SEC DELAYS F 6 SEC DELAYS WITCH 5 BLINKER NO BLINK OFF BLINK ALARMS WITCH 4 AUX RELAY s ON ALARM OFF HORN N WITCH 3 SEAL INPUTS UN INVERT SEALS OFF SEALS NORMAL SWITCH TEMP FAIL S ON NO LATCH UP OFF LATCH UP SWITCH 1 FAIL TO START TEST ENABLE TEST OFF DISABLE TEST ORDER S2 DUT GROUND S1 OUT Te DUT T1 OUT De BUT D1 DUT 12 VDC HIGH HORN P2 FLOATS DIS RUN 1 DIS RUN2 SEAL 1 SEAL 2 TEMP 2 RES MUTE 161514113 12 1110 9 8 7 6 5 4 3 8 1 4 PC 2000 BACK VIEW PRIMEX 10 PC 2000 Specifications
2. 2 2 00 DUPLEX PUMP CONTROLLER User Manual Ashland OH 800 363 5842 PRI LC Detroit Lakes MN 888 342 5753 WWW PRIMEXCONTROLS COM Milford OH 513 831 9959 PN 1038550A 2013 SJE Rhombus Rev 09 13 PRIMEX is a trademark of SJE Rhombus 1 0 INTRODUCTION The model PC 2000 is a float switch based dual pump controller intended primarily for wastewater lift stations and other pump down applications It has inputs for five normally open float switches and sensor inputs for the seal fail and temperature fail sensors normally found in submersible pumps The controller has indicator lamps and test push button switches on each of the float inputs as well as an indicator which illuminates if the floats do not close in the correct order The controller has built in alternation and a three position switch to select automatic alternation or to select between pump 1 and pump 2 if alternation is off The controller has disable inputs for each of the pumps The controller has built in support for an alarm horn with inputs for an external mute button and also mute button on the controller front panel There are two alarm outputs One for the high alarm and one for the low alarm These output relays can be setup to cycle on and off during an alarm to support blinking panel alarm light The controller has five output relays Two are for the two pumps one each for the high and low level alarms and one to drive t
3. Each pump has an input for the temperature fail sensor often found in pumps This sensor should be shorted if the pump is good If the pump overheats then this sensor will open The sensor is connected to ground and to the sensor input for that pump If the pump controller detects an open condition in the sensor then the temperature fail lamp and output are activated The temperature fail condition will disable the pump The controller can be set using an option switch on the bottom of the controller to latch up the temperature fail condition If this option is selected then once a temperature fail condition is detected the fault will not clear until the fault condition is cleared and the reset push button is pushed or external reset input is closed If this option is not selected then the fault will clear when the sensor in the pump closes again DISABLE PUMP RUNNING INPUTS Each pump has an input which has two possible functions If the fail to start test is not activated by an option switch on the bottom of the controller these inputs are pump disables Under this condition if this input is shorted to ground then that pump will be disabled If the fail to start test is activated these inputs are pump running inputs and should be shorted to ground when ever the pump is running FAIL TO START TEST If the fail to start test is activated using the option switches on the bottom of the controller then the following sequence is used each ti
4. INPUT 10 PUMP 2 SEAL FAIL SENSOR INPUT 11 PUMP 2 TEMPERATURE SENSOR INPUT 12 MUTE RESET INPUT CONNECTOR J3 PIN FUNCTION 1 12 VDC VOLTAGE FOR EXTERNAL RELAYS 2 PUMP 1 DISABLE OUTPUT 3 PUMP 2 DISABLE OUTPUT 4 PUMP 1 TEMPERATURE FAIL OUTPUT 5 PUMP 2 TEMPERATURE FAIL OUTPUT 6 PUMP 1 SEAL FAIL OUTPUT 7 GROUND 8 PUMP 2 SEAL FAIL OUTPUT 9 FLOATS OUT OF SEQUENCE OUTPUT 10 RS232 RECEIVE 11 RS232 TRANSMIT 12 AUXILIARY INPUT PRIMEXTM 6 PC 2000 Specifications ih PC 2000 DUPLEX PUMP CONTROLLER ALT AUX RELAY 2 1 2 SJ 2 1 ALTERNATION HIGH O ALARM PUMP2 PUMP1 O FLOATS OUT OF k Sasa PUMP 2 SEAL FAIL PUMP 1 1 FRONT PANEL PRIMEXTM PC 2000 Specifications MOUNTING CUTOUT 9 200 PRIMEX 8 PC 2000 Specifications PRIMEX HIGH FLOAT LAG FLOAT LEAD FLOAT OFF FLOAT LOW FLOAT SEAL FAIL TEMP FAIL DISABLE CONTROL FEN O PHASE MONITOR 4 Ji 1 1 4 J1 5 ope H HIGH ALARM VIN 2 op EE Je 5 5 1 J2 6 l ere COCHA hu alo 1 22 10 Ji 9 TES 3 J1 3 ETM m RESET MUTE gesti J2 12 Ri EXAMPLE PANEL WIRING PC 2000 Specifications 12345678 9 10 Mi PRIMEX PC 2000 DUPLEX PUMP CONTROLLE S N
5. es to rise and closes the lag float then the lag pump will be called If the level drops enough to open the lag lead and off floats then the two pumps will be turned off When both pumps are turned off there is a 4 second delay between the first and second pump turning off If the water level continues to rise and closes the high alarm float then the high alarm condition will be set This will cause the high alarm relay and light to come on This alarm condition will clear when the level is low enough to open the high float Any time a pump is started an internal timer is started which will prevent the other pump from starting for a period of time which is selected by one of the option switches on the bottom of the controller This time can be either 6 or 12 seconds The controller has three pairs of inputs for setting pump related alarms or faults PRIMEXTM 2 PC 2000 Specifications SEAL INPUTS Each pump has an input for the seal fail moisture sensor commonly found in submersible pumps The controller measures the resistance of the sensor In normal operation the seal fail condition is set if the resistance is less than 50 000 ohms One of the option switches can be used to change this to set the alarm if the resistance is greater than 50 000 ohms If a seal fail alarm is set then that pump is demoted to lag pump and its seal fail lamp and output are activated The seal fail does not disable the pump TEMPERATURE FAIL INPUTS
6. float inputs two seal fail sensor inputs two temperature fail inputs and two disable inputs They use current limiting resistors filter capacitors and zener diodes for transient protection They also have both hardware and software filter on these inputs to improve immunity from noise They have the following specifications PRIMEXTM 4 PC 2000 Specifications Short Circuit Current less than 2 mA Open Circuit Voltage 5 0 VDC 3 2 Mute Reset Input The mute reset input is intended for use with a momentary push button switch mounted on the dead front or on the side of the enclosure It has the following specifications Short Circuit Current less than 2 mA Open Circuit Voltage 5 0 VDC 3 3 Relay Outputs There are five relays which are used for pumps and alarms All of them except the low alarm relay are form A SPST relays The low alarm is a form C SPDT relay They have the following specifications Maximum current at 120 VAC 7 Amps with a resistive load Maximum voltage 140 VAC 3 4 Power Inputs The controller is designed to run on 120 VAC control power It is internally fused at 1 Amp and transient protected with a MOV transient protector It uses transformer isolation and internal current limited voltage regulators It has the following specifications Input Voltage 120 or 1096 50 to 70 Hz Maximum Current 0 4 amps 3 5 Operating and Storage Temperature Range Operating Temperature 10 deg
7. he horn The controller has indicator lights and external relay drivers for the following conditions floats out of sequence seal fail for pumps 1 and 2 temperature fail for pumps 1 and 2 pump disabled for pumps 1 and 2 2 0 OPERATION The PC 2000 uses five normally open float switches for level sensing When the tank is empty all of the floats are open The lowest float is the low alarm float If it is not used the low float input should be shorted with a jumper When the tank is empty the controller will be in the low alarm condition On rising water when the level is high enough to close the low float switch then the low alarm will turn off As the level rises the off float will close and then the lead float will close When this happens the pump controller will call for the lead pump Which pump is the lead will be determined by the alternator If the alternator is set for pump 1 then pump 1 will be called If the alternator is set for pump 2 then it will be called If the alternator is set in the on position then each pump cycle the lead pump will change If one of the pumps has and existing leak failure then the other pump will be called as the lead If any pump has existing temperature failure or is disabled then that pump will not be called If the lead pump lowers the water level far enough to open both the lead and off floats then the lead pump will be turned off and the lead pump changed if alternation is on If the water level continu
8. me a pump is called 1 When a pump is called a timer is started 2 After a start up time has expired set by switch 6 the pump running input is checked If the pump is not running at the end of the time then a pump fail to start condition is set and the pump is disabled The pump will remain disabled until the reset button is pushed a high level alarm is set or until the external reset input is activated ALARM RELAY OUTPUTS The controller has two relays for level alarm Option switch 5 can be used to cause these relays to cycle on and off This is useful to provide blinking on the external alarm lights AUXILIARY RELAY There is one relay which can have either of two functions selected by option switch 4 PRIMEXTM 3 PC 2000 Specifications 1 horn option is selected then this relay can be used to drive an external horn or bell Whenever either a high or low alarm condition starts the relay is activated closed If the alarm condition is cleared then the relay is also cleared If the reset button is pushed or the external reset mute input is activated then the horn relay is cleared If the horn is muted then it will not reactivate until the alarm condition is cleared and another starts 2 If the common alarm option is selected then this relay will be activated when any of the following conditions exist e High alarm Low alarm Pump Temperature Failure Pump disabled by fail to start test This common alarm condi
9. rees C to 60 degrees C 0 to 95 relative humidity non condensing Storage Temperature 20 degrees C to 65 degrees C 0 to 95 relative humidity non condensing 3 6 Fault Driver Outputs The controller has seven open drain FET driver outputs for driving external relays lights telephone dialers or remote terminal units The outputs short to ground when activated and have the following specifications Maximum voltage 12VDC Minimum voltage 0 0 VDC Maximum continuous sink current 0 4 Amps Maximum on resistance 2 ohms Notes Header and plugs use copper conductors only Torque requirement for plugs 1 47 Ft Lbs Unit operates at Pollution Degree 2 PRIMEXTM 5 PC 2000 Specifications 4 0 CONNECTOR PIN DEFINITIONS 41 PIN FUNCTION 120 HOT POWER INPUT TO THE CONTROLLER 120 NEUTRAL POWER INPUT TO THE CONTROLLER GROUND GROUND AUX RELAY CONTACT AUX RELAY CONTACT HIGH ALARM RELAY CONTACT HIGH ALARM RELAY CONTACT PUMP 2 RELAY CONTACT 10 PUMP 2 RELAY CONTACT 11 PUMP 1 RELAY CONTACT 12 PUMP 1 RELAY CONTACT 13 GROUND 14 LOW ALARM RELAY NORMALLY OPEN CONTACT 15 LOW ALARM RELAY COMMON CONTACT 16 LOW ALARM RELAY NORMALLY CLOSED CONTACT CONNECTOR J2 PIN FUNCTION 1 PUMP 1 TEMPERATURE SENSOR INPUT 2 HIGH FLOAT INPUT 3 LAG FLOAT INPUT 4 LEAD FLOAT INPUT 5 OFF FLOAT INPUT 6 LOW FLOAT INPUT 7 PUMP 1 DISABLE RUNNING INPUT 8 PUMP 2 DISABLE RUNNING INPUT 9 PUMP 1 SEAL FAIL SENSOR
10. tion can be used to drive an alarm light telephone dialer or telemetry system OPTION SWITCHES There are six switches on the back of the controller which select several different options SW1 When this switch is set the fail to start test is enabled SW2 When this switch is set the temperature fail condition is latched up until reset SW3 When this switch is set the seal fail input is inverted open is fault SWA When this switch is set the aux relay is the common alarm If it is not set then the aux relay is the horn output SW5 When this switch is set the low and high alarm relays will cycle to cause a lamp blink SW6 When this switch is set the time between pump starts and the delay for the fail to start test is 12 seconds instead of 6 seconds FAULT OUTPUTS There are seven fault lamps with corresponding driver outputs They are use to display the following fault conditions Floats out of sequence Pump 1 seal fail Pump 2 seal fail Pump 1 temperature fail Pump 2 temperature fail Pump 1 disabled Pump 2 disabled Each of these has a corresponding relay drive output These outputs are designed to drive the coil of a 12VDC relay external to the controller A source of 12VDC is also provided To use these outputs one side of the relay coil is connected to 12VDC and the other coil connection is connected to the driver output IDA 3 0 SPECIFICATIONS 3 1 Float and Sensor Input There are five

Download Pdf Manuals

image

Related Search

Manual manual manual forklift manualslib manual stacker manual car manuale digitale manual hoist manually meaning manual timesheet manual transmission manual wheelchair manual arts high school manually update your device drivers windows manual definition manual j load calculation manual for courts martial manual labor manual lawn mower manual muscle testing manually register devices with autopilot manual muscle testing grades manual transfer switch manualidades manual blood pressure cuff manual handling