        E.5G.001SS04 说明书 EA600N系列正弦波在线互动式1K
         Contents
1.                 Load         Transformer Filter       INVERTER    CHARGER                      BATTERY         2 3 Main power off     In main power off condition  batteries will supply power to the inverter promptly   then the power can be sent to user s equipments uninterruptedly after though  wave filter              ea Transformer Filter o                          2 4 Power supply by bypass     Bypass mode only happens in the following conditions  1 Over load   2 UPS failure   3 Switch on  keep pressing the ON button for 3seconds  UPS will be in the  process of soft starting within 15seconds   4 Switch off  keep pressing the OFF button for 3 seconds and UPS will turn to  bypass mode              Bypass      Load    Transformer Filter                   CHARGER          BATTERY    Hl    2 5 Battery and charging    1 Automatic self recharging occurs when UPS is connected to the main power   The charger can charge the batteries up to 90  within 8 hours    2 Please keep the batteries in full power condition  so as to prolong the  batteries  life as well as discharging time    3 There are high voltage power and electronic elements inside UPS  make sure  the machine not be opened by people without any technique  in case of electric  danger    4 Please construct and use according to this manual    3  Products features    3 1 Wide input voltage range   With online synchronous voltage regulation technology  and safe operating  input range 165 275Vac  optional  150 275V   it greatly 
2.       Overload in AC mode    110  transfer to bypass within 60sec        120  transfer to bypass within 30sec        Automatically recovery if the load capacity become normal       Short Circuit    Protected by Input Fuse       Inverter Mode       Output Voltage    100 110V 120V 220V 230V 240V  5        Output Frequency    50HZ 60HZ   1  self adaptive       Output P F    PF 0 6       Waveform Distortion     lt 5  for Liner Load       Battery Backup Time      10min  PC load        Transfer Time    Typical value 5ms  Max  8ms       Efficiency    80   INV Mode        Overload in INV mode    110  Shut down within 60sec  120  Shut down within 5sec        Auto shut down with  no load  optional      lt 5  Shut down within 1min       Short Circuit    System shut down automatically       Alarm       AC abnormal    Once per 4sec  be silent after 40s       Battery low    Once per 0 2sec                         Overload Once per 1sec   Battery   DC voltage 24V 24V 36V 48V H  48V  Configuration standard ups  tee 2X12V7AH   2X12V8AH   3X12V8AH   4X12V8AH          Recharge Time    90  Capacity after 8hours       Charging current long backup     10A maximum       Communication charging option     RS232 USB SNMP can be set to turn on off UPS automatically        Others       Output Sockets    Customized upon request                                              Surge protection optional  EMC EN62040 2 2006 EN61000 3 2 2006  EN61000 3 3 2008  IP Level IP20  Ambient Temperature oC   40  C  Ambie
3.      3  In normal using condition  the life time of battery is near 1 2 years  If battery  temperature and discharging frequency is high  the life time will be near 0 5 1 year   4  Along with the running time  the performance of battery is generally degraded   If the discharging time reduces to be 80  of initial time  performance is degrading  fast  So  battery maintenance should be done every month     5  Battery maintenance of long backup UPS keep doing the maintenance is vital   to protect the precision equipment on main power off condition      Clear the dust on battery    Check the connection cables between batteries are loose or not  if necessary   replace the cable even the battery     Keep the battery and cable connection tight    Note  The discharging test above is just a simple test to check the battery charging  status and performance  If needing know more exact information about  battery charging status  should contact with battery supplier locally     7 3 Trouble shootings    UPS can offer reliability to load  If abnormal accident occurs  advise you  go to local service center  so as to prevent more damage and  unnecessary fee  When UPS is in abnormal status  you can refer the  following trouble shootings  If can t solve problem  please get in touch  with local distributor  or contract direct with our company       15       Phenomenon    Confirmation and Solution       Main power is normal  main  power indicator is off    1  whether Cable is loose   2  whether fu
4.      Place having severe vibration     Outdoor     Use powder extinguisher if there is fire around UPS  Not to use liquid  extinguisher in case danger of electric shock      Place sockets nearby UPS  so as to pull out sockets and cut off the power  in an emergency situation      The product can provide 100  power output within range of rated voltage   25   if out of the range  the output power meets as followings      P      100    75   50    25      U v   145 175 280    Input voltage and output power    Warning  Equipment must be connected to the ground  1  The equipment must be connected to the ground  Make sure connect UPS  to the ground well while connecting AC to supply power  2  The power sockets must be 15A 250V or above this specification if the  capacity of UPS is above 2KVA  3  Incorrect operation may cause heavy loss  Please make sure to use the ups  correctly according to this manual    2  Working principle  2 1 System circuit diagram    Bypass  AVR    MAINS _            _ N Load  Transformer    INVERTER                          CHARGER          BATTERY       2 2 Normal power supplies  When UPS works in normal condition  miscellaneous waves of high frequency of  main power are eliminated by wave filter  after this  batteries group are charged  by the chargers in one route and keep the batteries in full power condition   another route is through UPS stabilizer  the power will be sent to user s  equipment after the wave filter        r Bypass    aly AVR     MAINS   
5.    Pure Sine Wave UPS  1 3KVA    OUTDOOR UPS    a              CONTENTS           Safety And Summary      Product components    Installation and usage    Maintenance            Packing List             Working principle      lt   lt  lt    lt s s 546 4seseeeeseo   sProd  cts features Torani see an      Technical specification                             1  Safety And Summary  Please obey the items below to ensure the security     Charge battery longer than 12hrs before using    After battery discharge or being stored more than three months  12hrs  recharging in time is required    The product is designed for group computers  could not connect with the  sensitive load  motor  fridge etc      Keep above 50cm away from the display while installing the product    It is normal that the case surface temperature go up to 50  C during using    Do not use UPS with overload    Do not open UPS cover in case danger of electric shock  maintenance and  battery replacement should be handled by technicians     UPS inner short circuit will cause electric shock or fire danger  Do not put any  liquid vessel on UPS    Cut off power rapidly if equipment work abnormal    Make sure not to keep or use the product in following environment     No good air circulation     Place having flammable gas  corrosive material or lots of dust     Place under abnormal high or low temperature  above 40  C or below 0  C    and high humidity  above 90       Place having direct sunlight or close to heater equipment 
6.   red is positive  black is negative      12       2 Secondly  please plug UPS into main power  then turn on the input switch on the  rear panel  And then use multimeter to ensure UPS and battery connector s  polarity identification and voltage to be compliant  1 15 times as the ups rating  DC voltage if the batteries are full      7  Maintenance  7 1 Preventative Maintenance    Preventative maintenance to UPS system can guarantee the reliability and long    time service  do some test per month as follows    1  Shut down UPS  Refer the operation steps for details    2  Check the vents not be blocked   3  Check whether there is so much dust covering the surface   4  Check the connection of input  output as well as batteries to see whether itis   firm and the insulating barrier of cable also     Make sure UPS not damp     Start UPS  Refer the operation steps for details    7  Keep UPS working for 5 minutes on battery mode with little testing load until it  alarm because of battery low voltage  there is supposed to be no other alarm    ou    information during this period  if any  please contact the local service center or  the supplier     7 2 Battery Maintenance    Valve Regulated Lead Acid battery is used in this UPS  The life time can be  reduced by bad operating environment  frequently discharging  and sharply  temperature rising  Even battery is not used  the performance can be gradually  degraded  That is why we advise to do a discharging every 3 months if there is no  po
7.  bypass  the LCD will display   PWR DN   as well as the icon   A  or the word  full      3 10 Intelligent communication ports  with intelligent computer  monitoring function    option   This series UPS can be monitored by PC through RS232  USB or SNMP card   it can provide UPS on  off control and auto file saving function for different  kinds of systems  such asWINDOWS98 NT 2000  ME 2003 XP Vistar  1 This series UPS can automatically detect the condition of the mains failed  and battery in low voltage  as well as UPS other working data  LCD UPS   2 When the mains is failed  the system will make countdown to automatically  save files  shut down system and UPS   3 It can set system power supply time  make history record of UPS working  status  the mains status and so on   When the system is in shut down countdown  it can set UPS self detection and  time for UPS on and off      7    4  Technical specification                               VA Rating 500VA 1000VA 1500VA 2000VA 3000VA  Real Power Rating 300W 600W 900W 1200W 1800W  Display   Indicator on Panel LED  LCD plus LED display  LED for outdoor UPS    AC Mode       Types Of Load    Ancillary equipments such as PC  display  group computers and so on       Input Voltage    100 110V 120V 220V 230V 240V 25     35    25  optional        Input Frequency    45 65 Hz  transfer to battery mode if out of this range        Output voltage    100 110V 120V 220V 230V 240V 25        Input PF AC DC     98        Efficiency    96   AC Mode  
8.  switch on rear panel of  UPS firstly  and then press the start button on front panel for 3 seconds  UPS will  output power normally from Inverter    1  Daily start  Press the start button   ON   for 3 seconds  UPS will output  normally in 15 seconds    2 Daily shut down  Press the shut down button   OFF   on front panel for 3  seconds  UPS will turn to bypass mode if the main power is on  And bypass  LED will be on at the moment  Otherwise the ups will shut down     Cautions    1  Please start UPS then computer load when starting computer and shut down  the computer load then UPS   2  Normally it s unnecessary to switch off UPS so as to charge the batteries   3  It will transfer to battery mode once the mains power goes off  please save your  files or do other emergency deal to PC or other load    6 3 ON and OFF operation after long time storage of UPS   1 If exceeds 7 days  please shut down as follows  press the OFF button on front  panel  and then switch on the input breaker on the rear panel    2 1f you will use the ups after more than 3 months storage  please start the UPS as  same as the initial starting  and make sure it working more than 12 hours to  charge battery  keeping the battery full condition is good to prolong the life span     6 4 Installation of Long backup type UPS    Warning  In order to ensure equipment and human safety  it must be installed by  qualified technicians     1 Firstly  please connect batteries with battery cable and install them well   Note 
9. make the batteries   discharging and recharging less often than usual   and prolong the batteries     using life effectively     3 2 Auto switching machine function  Please turn off the input  switch in the rear if no need the automatic switch on function        Supply the main power and turn on the input switch in the rear of the ups  it  will start automatically 15s later  forming stabilized power for the load      Batteries will supply power promptly when the main power is off  after finishing  discharging  UPS will shut down automatically with long ringing      UPS will restart automatically if main power recovers after auto shutting down   and recharge the batteries as well     3 3 Humanized alarm system     UPS will alarm 1 5seconds when main power is off and normal inverter gets  to work  the sound will be dispelled automatically after 40 seconds  in order  not to disturb the working environment      UPS starts the alarm automatically with long ringing  when the batteries will  be nearly exhausted  the frequency is 1 0 2seconds  in order to remind people  that batteries are used up and UPS will be off soon      When batteries are almost used up  UPS will shut down automatically to   protect the batteries        3 4 Protective functions of online UPS       Overload on main power condition  on main power condition  UPS will alarm for  60s if the load is over 110   then it will turn to bypass mode  with ringing  disappeared either  Normal condition will recover if load ha
10. nt Humidity 10    90   No Condensing   Noise  lt 45dB  f   420X145X215  Dimension  mm  DxWxH 355X145X215 355x145X315 H  475X190X335  i n P 510X325X245  Packing Dimension mm  450X 325X245 750x325x245 H  590X320X465  Net Weight  kg  14 5 15 5 18 5 27  Gross Weight  kg  15 5 16 5 19 5 28 60                   j     Note    1   Data after with      H      means the ups is long backup type with external  battery    2   The data above is for the standard ups  varying from the special units  of  customers   3  Dimension of outdoor UPS is subject to the real machine     5  Product components  5 1 LCD front panel    1  Brief view of front panel     1  LCD display screen    2  Bypass indicator  orange    3  Output indicator  green    4  UPS working status indicator  6     ON    Starting button   5  AC power indicator  orange     7     OFF    Shut down button       2 Introduction of the indicative lamp     1  LCD display screen  Display input and output voltage  frequency  battery and  load capacity    2  Bypass indicator orange   the light is off when UPS is working with main power  input   3  Output indicator  green   the light is on when UPS is working    4  UPS Working condition indicator green red   the green light is on when there is  main power input  red light is on when main power is off   5  AC indicator  orange   the light is on when there is input main power    6   ON  Starting button  Start UPS by pressing it for 3 seconds  UPS output power  normally in 15 seconds daily star
11. occurring at the transfer between AC and batteries  so as to  ensure the disturbance and damage to equipment in the lowest level     3 6 LCD and LED display panel     The intuitive LED and LCD display makes users can easily learn the  information of battery capacity  load capacity as well as the whole system  working status     a    3 7 Automatically shut off when there is no load in inverter mode     option      When UPS is in inverter mode  the alarm will disappear after 40 seconds  and  at the same time it will automatically detect the load capacity  if the load is  less than 5   UPS will consider as no load and will automatically shut off after  1 minute to ensure the battery full and prolong the battery life     3 8 Automatically distinguish output frequency     The mains  frequency is 50HZ or 60HZ  when the UPS is connected with the  mains  it can automatically detect the mains  frequency  and the UPS output  frequency will keep the same as the mains  frequency  50HZ or 60HZ  before  even the main power failed     3 9 Battery detection     The product can work with monitor software to detect battery at fix time  if there  is any fault such as battery cable open circuit or battery failure  the UPS can  detect the faulty information through communication ports to inform user   Meanwhile  the UPS has self protection function to shut down the charging  system and will turn to bypass mode  for the UPS with bypass model   when the  mains is normal  then itis power supplied by
12. s been decreased  to anormal range      Overload on normal inverting condition  on inverting power condition  UPS will  alarm with long ringing if load is over 110   it will supply power again if load was  decreased to a normal range within 60 seconds and stop ringing at the same  time  Otherwise it will be shut down itself  Users need to turn on it manually by  pressing the ON button in the front panel or wait for the recovering of main power      Overload on abnormal inverting condition  on inverting power supply condition   UPS will alarm with long ringing when load is over 125   ups will automatically  shut down after 5s  end users need to turn on it manually by pressing the ON  button in the front panel or wait for the recovering of main power      Short circuit protection on inverting power condition  if the output of the ups  meets transient crest current and short circuit strike  it will be limited in some  degree  if over 10ms  system will shut down automatically  Users should turn on    manually  press the ON button in the front panel  or wait for the mains recovered      If on main power supply condition  the input fuse will get broken as the first  protection  and then ups will turn to inverting mode      3 5 Phase lock function   On main power condition  system tracks the main power phase position  automatically  which can ensure the wave form of inverting output voltage  going simultaneously with the main power s  It can lower the spike pulse and  surge voltage 
13. se is burnt        UPS can not stay in mains mode    The mains power indicator is off with  the buzzer ringing  even the UPS input  plug has been inserted to main power  socket  and power switch is pushed     whether fuse is burnt or not   After pulling out the UPS plug  use  screwdrivers to revolve the fuse  counterclockwise and get it out   Check that whether the fuse is fusing   if so  need replacement       Mains Mode no problem  battery  mode can not work    Whether the battery is not charged or  not  Whether UPS is not switched on       When power is off  computer will  stop working    When main power is normal  start  UPS  Charge the battery for more  than ten hours  and then start the UPS       When mains connected  UPS beeps  for 60 seconds  then transfer to  bypass  When noAC input  UPS shut  of automatically after 60 seconds  beeping    Check UPS is overload or not       When UPS transfer to battery mode   but shut off immediately  When AC  connected  UPS stay in bypass mode   and LCD shows  PWR ON      A me  or  Fault           Battery connection cables open  circuit or battery damage       8  Packing List  1  UPS  1 unit    2  User Manual  1 copy   3  Warranty   1 copy    3  Battery connection cable  1 piece  only for long backup model    4  Others are according to customer needs    16          
14. ting    7   OFF  Shut down button  shut down UPS by pressing it for 3 seconds working  through bypass with main power input and the bypass light is on  daily shut down       9       5 2 Brief diagram and introduction of back panel           10          1 SNMP  Optional   i      2  Output sockets    3  USB RS232  Optional                  gt  4  Input switch       5  Fuse    6  Input                                                 7  DC input                                    6  Installation and usage   6 1 Product installation   1 Close the equipments for example  computer master   pull out the power wire  from the main power socket   2 Put the UPS to the suitable position with good ventilation  at least 150mm  ambient space around the vent and fan    3 The power wire of equipments which need UPS  for sample  computer master  and so on  should be connected to output sockets of UPS  Others should be  connected to the common main power sockets   4 Connect the input plug of the ups to main power socket  make sure L  N be right  and the ground line is ok        11    6 2 Start shut down     1  On main power condition  Turn on the input switch on back panel of UPS  UPS  will start self testing and output through bypass and will be in normal condition  in 15 seconds  the output indicator and working status indicator green  of UPS  will be on  the bypass indicator is off  user can start PC and other load at this  moment    2  On battery condition  main power off   Turn on the input
15. wer off for long time  There are maintenance steps in the following  the  performance will get degraded very fast  please keep the following operations   of battery maintenance in mind      1  Connect AC input  switch on UPS  and charge battery up to 8 hours  Look out  load running status which is connected to UPS    2  Keep the load  and record the total power  then shut off AC input  UPS transfer  to battery mode  till shut off automatically  record the discharging time  Also  keep the discharging time record  in order to refer it later        13    7 3 Outdoor UPS Parts        Lightning arrester  Maintenance bypass switch    DC input switch  Input output switch  Host connection cable    Indicator    Manual DC PW ON key   Manual PW Off key   Dry contact RS232 SNMP   O Option    DC input Red  anode  Black   cathode   Power supply input  output terminals    Input fuse                         Inner battery i 2   Power DC voltage space Dimension  mm   500VA 24VDC 40AH 2 245 430 550   40AH 2 245 430 550  1000VA 24VDC   120AH 2 245 470 900  1500VA 36VDC 120AH 2 245 470 900   40AH 4 penta  2000W 48 24VDC 120AH 2 245 470 900                   14       OThe total power of load  power consumption  is calculated in unit of  Watt    Olf the marking of UPS just shows power capacity in  VA   we need to  multiply power factor if no marking  it is 0 6  to calculate in unit of  Watt    Olf there is just Ampere value marked  then multiply rated voltage and power  factor to calculate in  Watt
    