Installation Requirements for Conformance to Standards, GFK

image

Contents

1. Standards Overview 4 Conditions Environmental Vibration IEC 60068 2 6 0 006 inches p p 10 57Hz 1g at 57 500Hz Operating 0 C to 60 C Series 90 surrounding air Genius surrounding air VersaMax Temperature surrounding air O to 55 C Field Control surrounding air Storage 40 C to 85 C Temperature Humidity me 5 to 95 non condensing Enclosure IEC 60529 Series 90 Genius Versa Max and Field Control modules are considered open Protection equipment and for safety reasons must be installed in a minimum IP20 protective enclosure IP54 or greater as appropriate is recommended IP54 rated enclosures provide protection against multidirectional sprayed water and airborne contaminates EMC Emissions Radiated CISPR 11 Industrial Scientific amp Medical Equipment Conducted EN 55011 Group 1 Class A CISPR 22 EN 55022 Information Technology Equipment Class A 47 CFR 15 Referred to as FCC part 15 Radio Devices Class A EMC Immunity applies to CE Marked modules Electrostatic EN 61000 4 2 8KV Air 4KV Contact Discharge RF Susceptibility EN 61000 4 3 10V ms m 80Mhz to 1000Mhz 80 AM ENV 50140 o o ENV 50204 10V ms m 900Mhz 100 PM square wave 50 duty cycle Fast Transient EN 61000 4 4 2KV power supplies 1KV I O communication Burst Surge Withstand ANSVIEEE Damped Oscillatory Wave 2 5KV C37 90a power supplies I O 12V 240V IEC 2
2. The PLC products meet the CE Marking Directive 93 68 EEC indicating compliance to both EMC Directive Low Voltage Directive and ATEX Directive if required In addition we will issue Declarations of Conformity that specify the directive s and the catalog numbers of the products covered PLC products must be installed using the instructions in the installation manuals and in the applicable sections of this manual Manufacturers of machines to be installed within the EEA must also comply with the following directive m The Machinery Directive 89 392 EEC 91 368 EEC 93 44 EEC 93 68 EEC deals with machine safety The Machinery Directive applies to the entire machine and covers all safety aspects of the machine including electrical safety Compliance with the Machinery Directive is the machine manufacturer s responsibility We support machine manufacturers by complying with the safety requirements of EN61131 2 the applicable European standard for programmable controllers GFK 1179M Chapter 1 Installation Guidelines 1 3 EMC Directive The EMC Directive is concerned with the immunity of electrical equipment to a variety of interference sources and the emissions from electrical equipment that could interfere with the operation of other equipment The EMC Directive applies to complete installations and since GE Intelligent Plattorms PLCs are included in the installation we support the EMC Directive by testing and CE marking a subset o
3. Nut Metal Ring Enclosure Connector RF Shield Shielded Cables Figure C 2 Communication Cables Sharing an RF Shield GFK 1179M Appendix C Shielded Cable Alternative to Conduit C 3 Specialty Shielded Cable Vendors Eupen specializes in RF absorptive material outer coating cables CMS cables Ask for equivalent Genius cables Glenair Inc specializes in convoluted tubing Series 72 amp 74 and in flexible metal core conduit Series 75 They also carry various kinds of shield termination connectors Zippertubing Co specializes in after installation zip on shielding where different types of shielding can be selected Recommended types of shielding are SHN 3 SH1 and SH3 to provide 85 coverage C 4 Installation Requirements for Conformance to Standards I January 2010 GFK 1179M Appendix Radiated Emissions Compliant Products D The following list of products have been tested and found to be in compliance with FCC European Norme and CISPR standards for radiated emissions as defined in Appendix A without being installed in a metal enclosure and external wiring being routed in metal conduit The product catalog numbers with suffixes are listed below to indicate the module revision at which compliance was obtained All subsequent revisions shall also comply Although these products do not require installation in a metal enclosure they still must be installed in an enclosure with minimum IP20 rating in order to meet the Low
4. EEA GE Intelligent Platforms product manuals provide information required for the intended use of GE Intelligent Platforms products The product manuals are written for technically qualified personnel such as engineers programmers or maintenance specialists who have been specifically trained and are experienced in the field of automation control Such personnel must possess the knowledge to correctly interpret and apply the safety guidelines provided in the product manuals Should you require further information or face special problems that have not been dealt with in sufficient detail in the product manuals please contact your local GE Intelligent Platforms sales or service office or GE Intelligent Platforms authorized distributor Qualified Personnel GFK 1179M Only qualified personnel should be allowed to specify apply install operate maintain or perform any other function related to the products described in the product manuals Examples of such qualified persons are defined as follows m System application and design engineers who are familiar with the safety concepts of automation equipment m Installation startup and service personnel who are trained to install and maintain such automation equipment m Operating personnel trained to operate automation equipment and trained on the specific safety issues and requirements of the particular equipment 2 1 Proper Usage The equipment system or the system components may
5. Radiated Emissions Compliant Products eene D 1 Industrial Exemption Products vnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnvnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnee E 1 vi Installation Requirements for Conformance to Standards January 2010 GFK 1179M Chapter 1 Introduction GFK 1179M Installation Guidelines The information in this manual is applicable for the following product lines Series 90 70 Series 90 30 Field Control Genius VersaMax QuickPanel DataPanel and Operator Interface This manual describes the standards to which these products must conform for installation in industrial environments This chapter discusses the following regulations and directives m Government Regulations m New Approach Directives m EMC Directive m Low Voltage Directive m Machinery Directive m ATEX Directive The installation manuals for each product line provide detailed information regarding the equipment s proper installation startup and use This manual provides the additional installation requirements needed to comply with governing bodies and standards agencies such as Federal Communications Commission FCC Industry Canada and Standards Council of Canada SCC European Union EU and Australian Communications Authority ACA Related Publications For more information refer to the following publications These publications and additional product documentation are available on the Support webs
6. from noise within the enclosure and is terminated to the connector shell The outside shield is classified as an RF shield and should be insulated from the inside shield Another alternative to double shielded cable for Genius bus communications is Eupen CMS cable equivalent Genius cables with an RF absorptive material outer coating The shield should be terminated per standard Genius wiring guidelines http www eupen com All I O lines leaving the enclosure must have at least 85 braided shield coverage terminated at the entrance to the enclosure This 85 RF shield should not continue into the enclosure The 85 braided shield cable is a standard cable available with various wire sizes and quantities from many cable manufacturers Analog High Speed Cables GFK 1179M Analog or high speed lines which require shielded cable for immunity should be double shielded The outside braided shield should be terminated at the entrance to the enclosure and not continue within the enclosure The inside shield should be terminated per standard installation instructions The outside shield is classified as an RF shield and should be insulated from the inside shield C 1 Power Input to Enclosure An alternative to shielded input cables is to utilize RF filters to minimize the noise coupled back onto the power supply inputs If RF filters are used then unshielded wires may be used inside and outside the enclosure AC Power Input RF Filter m
7. Series 90 70 products 1 11 VersaMax products 1 16 Ground connections Series 90 30 products 1 8 Series 90 70 products 1 11 Grounding the controls enclosure 1 5 I O cables C 1 I O power sources 1 6 Industrial exemption U S and Canadian Installations 1 2 Index Installation requirements Field Control 1 14 1 16 Genius I O 1 13 Series 90 30 PLG 1 7 Series 90 70 PLG 1 11 L Low voltage directive 1 18 M Machinery directive 1 20 Mounting plate B 2 New Approach directives 1 3 P Power input to enclosure C 2 Proper usage 2 2 Q Qualified Personnel 2 1 R Radiated emissions compliant products D 1 E 1 Related publications 1 1 RFI standards 1 2 S Safety related guidelines European Union 2 1 Shield termination C 3 Specialty shielded cable vendors C 4 T Technical Support See page iii U U S regulations 1 2 V Verification U S and Canadian Installations 1 2 Index 1 Index Index 2 Installation Requirements for Conformance to Standards January 2010 GFK 1179M
8. Voltage Directive and UL requirements for safety since these PLC products are considered to be open equipment Also refer to page 1 21 for enclosure specifications to meet ATEX Directive Catalog Suffix Catalog IC693CPU350 AA IC693MDL748 IC693CPU360 AA IC693MDL753 IC693CPU363 A IC693MDL754 IC693CPU364 AA IC693MDL760 IC693CPU374 AA IC693MDL916 IC693DNM200 A IC693MDL931 IC693DNS201 IC693MDL940 IC693MDL260 IC693NIU004 IC693MDL634 IC693PBM200 IC693BEM331 IC693MDL645 IC693PBS201 IC693MDL646 IC693PIF350 IC693MDL648 IC693PRG300 IC693MDL655 IC693PWR321 IC693MDL660 IC693PWR322 IC693MDL730 IC693PWR330 IC693MDL731 IC693PWR331 IC693MDL740 IC693PWR332 IC693MDL741 IC693MDL742 osessemas To meet EN 55022 Group 1 Class A Radiated Emission levels this module requires two small turns on the incoming DC power lines to be placed around a ferrite clamp Steward Part A2029 0A0 or ferrite with similar characteristics GFK 1179M D 1 Appendix Industrial Exemption Products E The following products have taken the Industrial Exemption according to 47CFR15 Product Family Catalog Number Micro Greyline 524 524 B 524 4X 524 B 4X 525 525 B 525 4X 525 B 4X 1024 1024 B 1024 4X 1024 B 4X 1025 1025 B 1025 4X 1025 B 4X Operator Workstation 2024 2024 128 C 2024 230 2024 LV 2025 2025 128 C 2025 LV 2224 2225 2225 LV Monitors CRTXXXXXC1A CRTXXXXXC2A CRTXXXXXC3A CRTXXXXXC
9. only be used as described in the product manuals GE Intelligent Platforms PLC products have been developed manufactured tested and the documentation compiled in keeping with the relevant safety standards Handling instructions and safety guidelines described for planning installation proper operation and maintenance must be followed to ensure safe application and use of the products Guidelines for the Application Planning and Installation of the Product 2 2 GE Intelligent Platforms PLC products generally form a part of larger systems or installations These guidelines are intended to help integrate GE Intelligent Platforms PLC products into systems and installations without constituting a source of danger The following precautions must be followed Compliance with EN12100 1 and EN12100 2 Safety of Machinery as well as EN60204 1 Electrical Equipment of Industrial Machines must be observed during the design phase m Opening the housing or the protective cover exposes certain parts of this equipment system which could have a dangerously high voltage level m Only qualified personnel should be allowed access to this equipment system m These persons must be knowledgeable of potential sources of danger and maintenance measures as set out in the product manuals m Strictly adhere to applicable safety and accident prevention rules and regulations m A suitable isolating switch or fuses must be provided in the building wiring sys
10. specified in Appendix A for EN61000 4 4 and the 1 kilovolt common mode and differential mode with 420 source impedance for EN 61000 4 5 All Analog Modules All analog modules including RTD and Thermocouple modules must have shielded cable connections with the shield grounded at one end at source 1 6 Installation Requirements for Conformance to Standards I January 2010 GFK 1179M Series 90 30 Products General Installation Guidelines In order to meet U S Canadian Australian and European regulations for Class A digital devices all applicable products in the Series 90 30 PLC product line have complied with EN55022 standard when installed as follows m An external ground wire 16 AWG 1 32mm2 of shortest possible length approximately 6 7 15 24 17 78cm must be wired from the Series 90 30 power supply safety ground wire terminal to the metal base plate See Figure 1 4 m System EMC earth ground is required to be attached to the grounding point on the metal baseplate and not to the Series 90 30 power supply module In order to meet U S Canadian Australian and European regulations for Class A digital devices all applicable products in the Series 90 30 PLC product line except those listed in Appendix D have complied with EN55022 standard when installed as follows m The PLC system must be mounted in a minimum IP54 rated metal enclosure or the equivalent All surfaces of the enclosure must be adequately grounded to adj
11. two ferrite parts 0443167251 390 110 225 case and two ferrite parts 0443164151 500 125 250 case and two ferrite parts GFK 1179M Chapter 1 Installation Guidelines 1 13 Field Control Products General Installation Guidelines Genius Stations FIP Stations In order to meet U S Canadian Australian and European regulations for Class A digital devices all applicable products in the Field Control product line have complied with EN55022 standard when installed as follows m The Field Control product must be mounted on a conductive surface DIN rail Refer to the Field Control Distributed I O and Control System Genius Bus Interface Unit User s Manual GFK 0825 for dimensions m The DIN rail must be mounted on a metallic surface panel that is grounded to earth m The DIN rail must be grounded to the metallic surface panel every 6 inches 15 24 cm with screws and star washers m The safety ground wire 14 AWG 2 10 mm2 for the Bus Interface Unit and the I O bases must be a maximum of 4 inches 10 16 cm in length to the panel m The panel ground wire 14 AWG 2 10 mm2 for the auxiliary terminal strip for analog shields must be a maximum of 4 inches 10 16 cm in length to the panel m System earth ground is required to be attached to the grounding point on the metallic surface panel and not to the Field Control Bus Interface module The Genius Station IC670GBI002 and IC670GBI102 has no specific installation guidelin
12. 0 High Speed Counter The shield for the cable must have a high frequency ground within 6 inches 15 24 cm of the IC693APU300 module in order to meet the EN 61000 4 4 levels specified in Appendix A The cable s length is limited to 30 meters Installation Requirements for Conformance to Standards I January 2010 GFK 1179M IC693APU301 302 The Axis Positioning Modules have two faceplate connectors marked and B for User I O In order for Axis Positioning Modules IC693APU301 version I or earlier and IC693APU302 version K or earlier to meet the EN 61000 4 4 levels specified in Appendix A the shield wire must be connected directly to ground To make this connection disconnect the User I O connector cable IC693CBL311 drain wire from pin B12 frame ground of each I O connector and directly connect it to ground with a 16 AWG 1 32 mm wire 8 inches 20 32 cm maximum in length Optional cables IC693CBL317 3 m and IC693CBL320 1 m are already modified to the above dimensions The cable connected to the SNP port for downloading user programs must be less than 30 meters Please refer to Appendix C of the APM User s Manual for the I O connector cable specifications Axis Positioning Modules IC693APU301 version J or later and IC693APU302 version H or later do not require the cable connector to be disconnected The standard user I O cable IC693CBL311 3 m or IC693CBL319 1 m satisfies the EN 61000 4 4 requirements However for best
13. 55 4 Damped Oscillatory Wave Class II power supplies I O 12V 240V EN 61000 4 5 2 kV cm P S 1 kV cm I O communication modules w cables gt 30m 5 6 Conducted RE EN 61000 4 6 10V ms 0 15 to 80Mhz 80 AM comm modules w cables gt 30m5 Power Supply Input Dips EN 61000 4 11 During Operation Dips to 30 and 100 Variation for AC 10 Variation for Variations DC 20 EN 61000 4 x series of tests are technically equivalent to the IEC 61000 4 xs A 2 Installation Requirements for Conformance to Standards I January 2010 GFK 1179M Note 1 Note 2 Note 3 Note 4 Note 5 Note 6 GFK 1179M The agency approvals listed in this document and on the Declaration of Conformities are believed to be accurate however a product s agency approvals should be verified by the marking on the unit itself For more information please refer to the Support web site Refer to module specific data sheets amp installation guidelines in the following publications GFK 0600 Series 90 70 PLC Data Sheets Manual GFK 0262 Series 90 70 PLC Installation Manual GFK 0356 Series 90 30 PLC Installation Manual GFK 0898 Series 90 30 I O Specifications Manual GEK 90486 1 Genius I O System User s Manual GEK 90486 2 Genius I O Discrete and Analog Blocks User s Manual GFK 0825 Field Control Distributed I O and Control System Genius Bus Interface Unit User s Manual GFK 0826 Field Control Distributed I O and Control S
14. 5A IAT CRT C1A QuickPanel QPI21100S2P QPI21100S2P B QPI21100S2P CTC QPI21100S2P SFM QPI2D100C2P QPI2D100E2P QPI2D100L2P B QPI2D100L2P ETL QPI2D100S2P QPI2D100S2P B QPI2D100S2P CTC QPI ABR 002 QPI GEG 201 QPI MBP 201 QPJ2D100L2P QPJ2D100L2P B QPJ2D100L2P CTC QPJ2D100L2P S QPJ2D100S2P QPJ2D100S2P B QPJ2D100S2P CTC QPJ2D100S2P ETL QPJ ABR 201 RDP QPJ GEG 201 QPJ MBP 201 QPK2D100L2P QPK2D100L2P B QPK2D100S2P Smart Panel SP KC 01 SP KC 02 SP KTC 01 TCS Series Industrial Computers TCS100 11001S TCS100 43013S TCS100 44012S TCS100 44013S TCS100 44112S TCS110 44013S TCS120 43013S TCS150 43013S TCS150 43103S TCS150 44012S TCS CRT S01 TCS CRT V6A TCS CRT V6T GFK 1179M GFK 1179M A Analog high speed cables C 1 Application planning and installation 2 2 Approvals standards and specifications A 1 Radiated emissions compliant products D 1 E 1 ATEX directive 1 22 Australian regulations 1 2 C Cable shield clamping assembly description 1 6 features B 1 installing B 3 Cables analog high speed C 1 communication C 1 I O C 1 power input to enclosure C 2 shield termination C 3 Canadian regulations 1 2 Communication cables C 1 EMC directive 1 4 European regulations 1 2 European Union directives 1 3 F FCC notice 1 2 G General installation guidelines Field Control products 1 14 Genius I O products 1 13 Series 90 30 products 1 7
15. Common mode Differential mode line filter m Effective range between 30 300 megahertz m Leakage current 0 8 milliampere m Insertion loss gt 30 decibels 30 megahertz gt 20 decibels 100 megahertz gt 15 decibels 300 megahertz DC Power Input RF Filter m Feed through type EMI ceramic filter m Capacitance 1500 picofarads minimum m WVDC 100 volts m Current rating As needed for application m Insertion Loss gt 50 decibels amp 100 megahertz C 2 Installation Requirements for Conformance to Standards I January 2010 GFK 1179M Shield Termination Termination of RF shields is extremely important in the reduction of RF emissions The RF shields should be terminated at the entrance to the enclosure with a 360 degree contact between the shield and the enclosure wall Compression Connectors Compression connectors are standard hardware available for the termination of conduit The diameter of the connectors is not of significant importance other than to make sure the wires can actually fit through them The compression connector provides a metal ring for shield termination and compression The following figure shows an unshielded l O cable with a single shield side view Nut Unshielded l O Enclosure Connector PVC Jacket Shield Metal Ring Figure C 1 Unshielded I O Cable with a Single Shield The following figure shows multiple communication high speed cables that share a single RF shield side view
16. GE Intelligent Platforms Programmable Control Products Installation Requirements for Conformance to Standards GFK 1179M January 2010 GFL 002 Warnings Cautions and Notes as Used in this Publication Warning notices are used in this publication to emphasize that hazardous voltages currents temperatures or other conditions that could cause personal injury exist in this equipment or may be associated with its use In situations where inattention could cause either personal injury or damage to equipment a Warning notice is used Caution notices are used where equipment might be damaged if care is not taken Note Notes merely call attention to information that is especially significant to understanding and operating the equipment This document is based on information available at the time of its publication While efforts have been made to be accurate the information contained herein does not purport to cover all details or variations in hardware or software nor to provide for every possible contingency in connection with installation operation or maintenance Features may be described herein which are not present in all hardware and software systems GE Intelligent Platforms assumes no obligation of notice to holders of this document with respect to changes subsequently made GE Intelligent Platforms makes no representation or warranty expressed implied or statutory with respect to and assumes no responsibility for th
17. Optionally the ground wire and a high frequency ground for the cable shield within 12 inches of the module may be used The shield conductor should remain continuous to the module and insulation should be removed only at the grounding point For more information please refer to Cable Shield Clamping Assembly on page earlier in this chapter GFK 1179M Chapter 1 Installation Guidelines 1 9 IC693MCM001 In order to meet the EN 61000 4 2 levels specified in Appendix A when an IC693MCM001 module is installed in a control system the Series 90 30 PLC system must be mounted in a metal enclosure In order to meet EN55022 Group 1 Class A Radiated Emissions levels the metal enclosure should provide a metal on metal connection around the door In order to meet the EN 61000 4 4 and EN 61000 4 5 levels specified in Appendix A the continuous shielded servo command cables should be clamped at both ends at module and at servo using a high frequency ground For more information please refer to Cable Shield Clamping Assembly earlier in this chapter IC693MDL654 Conventional TTL wiring practices should be utilized when installing this module For noise immunity reasons I O control lines connected to this module must be less than 30 meters in length however signal attenuation considerations will constrain practical wiring length to less than this maximum specification IC693PRG300 For installations in which the Hand Held Programmer is perman
18. acent surfaces to provide electrical conductivity Wiring external to the enclosure must be routed in metal conduit or the equivalent Using shielded cables and power line filtering as detailed in Appendix G is equivalent to using metal conduit m The conduit must be mounted to the enclosure using standard procedures and hardware to ensure electrical conductivity between the enclosure and conduit The termination for the shielded cable alternative to conduit is detailed in Appendix C Series 90 30 PLC System Neutral Line 2 Power Supply Inputs Power Supply Safety Ground Keep as short as possible and 7 Metal Baseplate connect directly to mounting panel EMC Earth Ground Figure 1 4 Installed PLC System GFK 1179M Chapter 1 Installation Guidelines 1 7 Safety and Reference Ground The metal back of the baseplate is ground when properly installed Safety and reference ground connections should be made from one of the mounting tabs to earth ground using a minimum AWG 12 3 3 mm wire and a ring terminal The use of a nut and star washer for each wire on the ground connection lug is recommended to ensure adequate grounding The baseplate must be grounded to minimize electrical shock hazard which may result in severe personal injury All baseplates grouped together in a Series 90 30 PLC system must have a common ground connection This is especially important for baseplates that are not mounte
19. al operation m Suitable measurements must be taken to make sure that operating sequences interrupted by a voltage dip or power supply failure resume proper operation when the power supply is restored Care must be taken to ensure that dangerous operating conditions do not occur even momentarily If necessary the equipment must be forced into the emergency off state Negative Logic Input and Output Modules cannot be used Exception With safety agency approval Such as TUV on GMR Systems these devices may be used in safety system H configurations m Cable shielding and grounding are the responsibility of the machine builder GE Intelligent Platforms installation instructions and guidelines must be followed m Install the power supply and signal cables in such a manner as to prevent inductive and capacitive interference voltages from affecting the automation functions m Measures must be taken when interfacing the inputs and outputs of the automation equipment to prevent an undefined state from being assumed in the case of a wire break in the signal lines GFK 1179M Chapter 2 Safety Related Guidelines for Installation in the European Union 2 3 Appendix A Product Agency Approvals Standards and General Specifications The products covered by this manual are global products which are designed and manufactured with IS09001 quality assurance for application in industrial environments throughout the world They should be insta
20. ble clamp attaches to the ground plate by sliding it into two adjacent slots at the selected location for the cable The cable is inserted between the ground plate and the cable clamp after removing the required section of the cable s outer cover Tighten the cable clamp by turning the thumbscrew clockwise Do not over tighten the thumbscrew hand tighten or tighten lightly with a tool Note If you are installing the ground plate on a painted surface the paint must be removed where the ground plate is to be mounted to ensure a good ground connection between the plate and mounting surface a45519 Figure B 2 Example of Cable Shield Clamping Assembly Installation GFK 1179M Appendix B Cable Shield Clamping Assembly B 3 Maximum and Minimum Diameter Cable The maximum diameter cable that can be used with the cable clamp is 0 51 inches 13mm as shown below in Figure B 3 Minimum cable diameter that can be used with the clamp is 0 24 inches 6mm Multiple cables can be placed in the clamp if the cable diameter is smaller than the minimum 51 Ground Plate Cable Maximum Diameter 51 13mm Minimum Diameter Cable 24 6mm Clamp Figure B 3 Cross Section of Cable Secured by Clamp Removing Cable Cover The insulating cover on the shielded cable must be removed to allow maximum contact between the cable shield and the cable clamp as shown in Figure B 4 Cable Clamp Foot Shiel
21. d Figure B 4 Clamped Cable with Exposed Shield B 4 Installation Requirements for Conformance to Standards I January 2010 GFK 1179M Mounting on a Series 90 70 PLC Rack In addition to mounting to a flat surface near the PLC system the Cable Shield Clamping Assembly can be optionally attached directly to a Series 90 70 PLC rack as shown below For compatibility the following versions of racks are required for the Cable Shield Clamping Assembly m IC697CHS790E or later version W 1C697CHS791E or later version m 1C697CHS782C or later version m C697CHS783C or later version TWO SCREWS EACH END USE EXISTING MOUNTING HOLES IN RACK Figure B 5 Cable Shield Clamping Assembly Mounted on a Series 90 70 PLC Rack GFK 1179M Appendix B Cable Shield Clamping Assembly B 5 Appendix e Shielded Cable Alternative to Conduit This appendix describes the installation requirements for using shielded cable as an alternative to metal conduit for meeting radiated emissions requirements EN55022 47CFR15 The following practices could be used in place of conduit for systems or cables that require conduit or the equivalent Communication Cables I O Cables All communication lines should be double shielded The outside braided shield 85926 coverage must be terminated at the entrance to the enclosure and not continue within the enclosure The inside shield should be left intact since it shields the communication line
22. d in the same control cabinet The best way to provide proper ground connections is to ensure that the Series 90 30 PLC baseplate metal frame is directly connected to the control panel in which the baseplate or baseplates are mounted This can be accomplished by connecting a ground strap from one of the ground lugs on either side of the baseplate to the control panel or cabinet following applicable electrical safety codes Additional Guidelines for Specific Components The guidelines specified in this section must be followed in addition to the guidelines found in the general installation guidelines for the product line Expansion and Remote Cables Custom length expansion and remote cables must be 100 shielded to meet the immunity levels specified in Appendix A A 100 or continuous shield means that the braided cable shield is connected to the metal shell of the connector around the entire perimeter of the connector This shielding provides a low impedance path to earth ground for any noise energy that is coupled onto the cable shield Refer to the Series 90 30 Installation Manual GFK 0356L or later for details on cable construction IC693ALG 392 442 In order to meet the EN 61000 4 3 levels specified in Appendix A when an IC693ALG392 or IC693ALG442 module is installed in a control system the Series 90 30 PLC system must be mounted in a metal enclosure IC693APU300 Shielded cable must be used for cables connecting to the IC693APU30
23. d negative input to frame ground or at the power line input of a system enclosure A Littelfuse V36ZA80P MOV can be used for most applications Note Only the non isolated 24VDC supply requires an MOV AC Power Supplies In order to meet EN61000 4 5 levels specified in Appendix A external MOV suppression is required from both the positive and negative input to frame ground or at the power line input of a system enclosure The following MOVs manufactured by Littelfuse should handle most line transients V130LA20BP 120 VAC applications V27550LA40BP 240 VAC applications Measurement of actual transients may be required in extreme cases to determine which MOV is best Installation Requirements for Conformance to Standards I January 2010 GFK 1179M DataPanel Products IC752DFT100 101 If communications cable or DC power lines exceed 10 meters in length then an earth ground connection should be made to pin 3 of the DC power input terminal GFK 1179M Chapter 1 Installation Guidelines 1 17 Low Voltage Directive The Low Voltage Directive applies to products operating between 50 and 1000 VAC or 75 and 1500 VDC The emphasis of the Low Voltage Directive is on safety Low Voltage Directive 73 23 EEC 93 68 EEC GE Intelligent Platforms PLC Products Will Comply EN61131 2 Programmable Controllers Safety Requirements Technical File L GE Intelligent Platforms Declarations of Conformity Figure 1 6 Path to compl
24. e accuracy completeness sufficiency or usefulness of the information contained herein No warranties of merchantability or fitness for purpose shall apply indicates a trademark of GE Intelligent Platforms Inc and or its affiliates All other trademarks are the property of their respective owners Copyright 2010 GE Intelligent Platforms Inc All Rights Reserved Contact Information If you purchased this product through an Authorized Channel Partner please contact the seller directly General Contact Information Online technical support and http www ge ip com support GlobalCare Additional information http www ge ip com Solution Provider solutionprovider ip ge com Technical Support If you have technical problems that cannot be resolved with the information in this guide please contact us by telephone or email or on the web at www ge ip com support Americas 1 780 420 2010 if toll free 800 option is unavailable Technical Support Email support ip ge com Europe the Middle East and Africa 352 26 722 780 if toll free 800 option is unavailable or if dialing from a mobile telephone Asia Pacific support jp ip ge com ini i 21 3217 4826 su CN i customercare cn ip ge com China Contents Installation Guidelines esse beine 1 1 Introduell n stipendi edet Ath eh edad ree at Aude 1 1 Government Regulations 224u2s00nnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn
25. e using standard procedures and hardware to ensure electrical conductivity between the enclosure and conduit The termination for the shielded cable alternative to conduit is detailed in Appendix C m In order to meet EN 61000 4 2 and EN 61000 4 3 levels as specified in Appendix A all components in a Genius I O system must be mounted inside a metal enclosure Additional Guidelines for Specific Components The guidelines specified in this section must be followed in addition to the guidelines found in the general installation guidelines for the product line IC660BBA023 103 In the presence of severe RF interference EN 61000 4 3 the thermocouple lines must be shielded to minimize any inaccuracies that the interference may cause and to meet compliance IC660ELB921 ELB922 When the length of the Genius communication cable from the PC Interface Module PCIM to the first Genius drop exceeds 30 meters an external clamp on ferrites must be used Fair Rite Products Corporation ferrites as shown in the following table or equivalent parts may be used Fair Rite Max Cable Impedance 2 Impedance 2 Description Part No Diameter 25 MHz Minimum 25 MHz Minimum 2643164251 250 130 275 core only 2643167251 390 110 225 core only 2643164151 500 125 250 core only 0199164251 250 case 0199167251 390 case 0199164151 500 case 0443194251 250 130 275 case and
26. energy transformed into a high frequency and high amplitude current to the machine chassis without causing secondary interference The EMC ground requires the following GFK 1179M The EMC ground must be a low impedance low inductance path to the machine chassis ground The baseplate on which the PLC is mounted should be connected to the machine chassis ground by a wire with a 10 1 length to width ratio to provide a high frequency path A worst case installation simulated for EMC testing used a 2 meter 12 AWG wire Chapter 1 Installation Guidelines 1 5 Cable Shield Clamping Assembly A cable shield clamping assembly IC697ACC736 is available to provide higher EMC immunity for shielded cables in severe industrial environments This assembly provides a high frequency ground for shielded cables via a ground plate and six cable clamps A set of 12 additional cable clamps can be ordered IC697ACC737 Refer to Appendix B for detailed installation and usage information about the assembly As an alternative high frequency grounds for shields can be fabricated from suitable material An example is shown below with the insulating cover of the cable stripped back User provided clamp Strip wire to expose shield Figure 1 3 Alternative to Cable Shield Clamping Assembly I O Power Sources All power sources needed by the PLC equipment for I O discrete and analog must be appropriately conditioned to not exceed both the I O EMC levels
27. ently installed the shielded cable to the Hand Held Programmer must have a high frequency ground for the shield within 13 33 cm of the Hand Held Programmer in order to meet the EN 61000 4 4 levels specified in Appendix A The shield on the cable must continue to the Hand Held Programmer IC693PWR322 328 In order to meet EN55022 Group 1 Class A Radiated Emission levels this module requires two small turns on the incoming DC power lines to be placed around a ferrite clamp Steward Part 4A2029 0A0 or ferrite with similar characteristics Installation Requirements for Conformance to Standards I January 2010 GFK 1179M Series 90 70 Products General Installation Guidelines In order to meet U S Canadian Australian and European regulations for Class A digital devices all applicable products in the Series 90 70 PLC product line have complied with EN55022 standard when installed as follows m The PLC system must be mounted in a minimum IP54 rated metal enclosure with a metal on metal connection around the door or the equivalent All surfaces of the enclosure must be adequately grounded to adjacent surfaces to provide electrical conductivity Wiring external to the enclosure must be routed in metal conduit or the equivalent Using shielded cables and power line filtering as detailed in Appendix C is equivalent to using metal conduit m The additional safety ground wire provided with the Series 90 70 power supply must be wired fro
28. es to meet EN55022 Group 1 Class A Radiated Emission levels The communication cable from one Bus Interface Unit to another may be any cable approved for use with the communication network However the communication cable from the controlling equipment to the Bus Interface Unit must be conditioned per the requirements of the controlling equipment An example is shown in Figure 1 5 for a Genius Bus Interface Unit IC670FB1002 The IC670FBI002 FIP BIU has no specific installation guidelines to meet EN55022 Group 1 Class A Radiated Emission levels The communication cable from one Bus Interface Unit to another may be any cable approved for use with the communication network However the communication cable from the controlling equipment to the Bus Interface Unit must be conditioned per the requirements of the controlling equipment An example is shown in Figure 1 5 for a Genius Bus Interface Unit IC670FBI102 In order to meet the requirements for CE mark approval all components using the IC670FBI102 FIP Bus Interface Unit require the following m All components must be mounted in a metal enclosure or the equivalent All surfaces of the enclosure must be adequately grounded to adjacent surfaces to provide electrical conductivity m EMC filter must be installed on the power supply lines Installation Requirements for Conformance to Standards I January 2010 GFK 1179M m Ferrite core must be clamped around all discrete I O lines in FIP Sta
29. exceed 1 kilovolt common mode and differential mode with 420 source impedance for EN 61000 4 5 GFK 1179M Chapter 1 Installation Guidelines 1 15 VersaMax Products General Installation Guidelines In order to meet U S Canadian Australian and European regulations for Class A digital devices all applicable products in the VersaMax product line have complied with EN55022 standard when installed as follows e The VersaMax product must be mounted on a conductive surface DIN rail Refer to the VersaMax User s Manuals GFK 1503 GFK 1504 and GFK 1535 e The DIN rail must be mounted on a metallic surface panel that is grounded to earth e The DIN rail must be grounded to the metallic surface panel every 6 inches 15 24 cm with screws and star washers e The safety ground wire 14 AWG 2 10 mm for the power supply module must be a maximum of 4 inches 10 16 cm in length to the panel Refer to GFK 1515 or GFK 1516 e System earth ground is required to be attached to the grounding point on the metallic surface panel and not to the VersaMax power supply module IC200MDD841 To meet the EN 61000 4 4 levels specified in Appendix A shielded cable properly terminated to earth ground must be used to connect the count inputs of the IC200MDD841 High Speed Counter module DC Power Supplies In order to meet EN61000 4 5 levels specified in Appendix A external MOV metal oxide varistor suppression is required from both the positive an
30. f our equipment EMC Directive 89 336 EEC 92 31 EEC GE Intelligent Plattorms PLC Products Will Comply 93 68 EEC B Article 10 2 Competent Body Route to Compliance Technical Construction File GE Intelligent Platforms Declaration of Conformity Figure 1 1 Path to Comply with the EMC Directive The European Union allows manufacturers to self certify that their products comply with the EMC Directive Alternately manufacturers may base their compliance on a Technical Construction File TCF which is assessed by an EU authorized Competent Body We have elected the TCF approach Compliance specifications are summarized by the EMC Emissions EMC Immunity and Power Supply sections found in Appendix A GE Intelligent Platforms has issued Declaration of Conformity DoC documents for each family of products thereby indicating compliance with the CE Marking Directive 93 68 EEC The DoC documents contain a list of all products which are labeled with the CE mark These DoC documents can be accessed through the Support web site The following section specifies additional installation and application practices necessary to meet the EMC Directive for wiring that leaves the control cabinet and travels through a factory environment Wiring leaving the cabinet may be exposed to interference sources corresponding to the standards and levels specified in Appendix A The installation practices found in the individual product installation manuals m
31. ite Genius I O System User s Manual GEK 90486 1 Genius I O Discrete and Analog Blocks User s Manual GEK 90486 2 Series 90 70 PLC Installation Manual GFK 0262 Series 90 70 PLC Data Sheets Manual GFK 0600 Series 90 30 PLC Installation Manual GFK 0356 Series 90 30 I O Specifications Manual GFK 0898 Field Control Distributed I O and Control System Genius Bus Interface Unit User s Manual GFK 0825 Field Control Distributed I O and Control System I O Modules User s Manual GFK 0826 VersaMax I O and Option Modules Manual GFK 1504 VersaMax Network Interface Units Manual GFK 1535 1 1 Government Regulations U S Canadian and Australian regulations are intended to prevent equipment from interfering with approved transmissions or with the operation of other equipment through the AC power source The Series 90 70 Series 90 30 Field Control Genius and VersaMax products have been tested and found to meet or exceed the requirements of U S 47 CFR 15 Canadian ICES 003 Australian AS NZS 3548 and European EN55022 regulations for Class A digital devices when installed in accordance with the guidelines noted in the appropriate product section These various regulations share commonality in content and test levels with that of CISPR 22 and based on this commonality testing to the each individual standard was deemed unnecessary The FCC requires the following note to be published according to FCC guidelines Note This equip
32. llation Requirements for Conformance to Standards I January 2010 GFK 1179M Series 90 30 Products To avoid possible misrouting of wiring to I O modules the following is recommended m Label all wires to and from I O devices Record circuit identification numbers or other pertinent data on the inserts that go in the module s faceplate door m Wires should be dressed so that each field I O connector is fixed relative to its respective module Handling Modules Use the procedures found in the installation manual of your system for the safe and proper removal of PLC modules Exercise care when working around operating PLC equipment because devices may become very hot and could cause injury GFK 1179M Chapter 1 Installation Guidelines 1 19 Machinery Directive The Machinery Directive focuses on the safe operation of the entire machine and is the machine manufacturer s responsibility Machinery Directive 89 392 EEC Machine Manufacturer s Responsibility to Comply 91 368 EEC 93 44 EEC 93 68 EEC EN12100 1 2 Safety of Machinery EN60204 1 Electrical Equipment of Industrial Machine EN61131 2 Programmable Controllers Safety Requirements GE Intelligent Platforms Complies Figure 1 7 Path For Supporting Machine Manufacturer s Compliance with the Machinery Directive When applied in accordance with EN60204 1 Electrical Equipment of Industrial Machines and our installation instructions GE Intelligent Platform
33. lled and used in conformance with product specific guidelines as well as the following agency approvals standards and general specifications Agency Approvals Overview 1 Comments Quality Assurance in Design Development Production Installation amp Servicing N A Safety for Industrial Control Equipment N A Safety for Hazardous Locations Class I Division 2 Gas Groups A B C D European Safety for Hazardous Locations Equipment Group II Category 3 Gas Groups A B C ISO9001 2000 Certification4 by Price Waterhouse Cooper Certification by Underwriter s Laboratories to UL508 standard and equivalent CSA C22 2 No 142 M1987 standard for selected Series 90 Genius VersaMax and Field Control modules Certification by Underwriter s Laboratories to UL1604 standard and equivalent CSA C22 2 No 213 M1987 standard for selected Series 90 Genius Versa Max and Field Control modules Certification by Factory Mutual to FM3611 standard for selected Genius and Series 90 70 modules Certification in accordance with European ATEX Directive for selected Series 90 Genius Versa Max and Field Control modules Refer to ATEX Declaration of Conformity European Safety and EMC for Industrial Control Equipment GFK 1179M Certification in accordance with European EMC amp Low Voltage Directives for selected Series 90 Genius Versa Max and Field Control modules Refer to Declaration of Conformity
34. m the Series 90 70 rack ground stud to the power supply safety ground wire terminal Refer to the power supply installation section Chapter 3 in GFK 0262 m The conduit must be mounted to the enclosure using standard procedures and hardware to ensure electrical conductivity between the enclosure and conduit The termination for the shielded cable alternative to conduit is detailed in Appendix C Safety and Reference Ground The metal back of the baseplate is ground when properly installed Safety and reference ground connections should be made from one of the mounting tabs to earth ground using a minimum AWG 12 3 3 mm wire and a ring terminal Use of a nut and star washer for each wire on the ground connection lug is recommended to ensure adequate grounding The baseplate must be grounded to minimize electrical shock hazard which may result in severe personal injury All baseplates grouped together in a Series 90 70 PLC system must have a common ground connection This is especially important for baseplates that are not mounted in the same control cabinet The best way to provide proper ground connections is to ensure that the Series 90 70 PLC baseplate metal frame is directly connected to the control panel in which the baseplate or baseplates are mounted This can be accomplished by connecting a ground strap from one of the ground lugs on either side of the baseplate to the control panel or cabinet following applicable electrical safet
35. ment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense Industry Canada requires the following note to be published Note This Class A digital apparatus complies with Canadian ICES 003 Verification and Industrial Exemption for U S and Canadian Installations With regard to U S and Canadian installation regulations users may wish to consider the industrial plant provisions of FCC regulation 47 CFR 15 103 b and Industry Canada regulation ICES 003 Section 1 2 2 b Appendix E contains a list of products that have taken this Industrial Exemption Products not mentioned in Appendix E use the verification route to Canadian and U S compliance Installation Requirements for Conformance to Standards I January 2010 GFK 1179M New Approach Directives Historically the Member States of the European Union EU had separate laws and regulations relating to safe
36. nformity DoC for each family of products is issued with a list of all product numbers which are labeled with the ATEX symbol and CE mark These DoC documents can be accessed through the Support web site The following section specifies installation requirements that must be adhered to in order to maintain compliance with the ATEX Directive Installation Requirements 1 22 For compliance to the ATEX Directive Series 90 30 Series 90 70 Field Control Genius and Versamax systems must be installed within a protective enclosure meeting the following criteria m P54 or greater and m Mechanical strength to withstand an impact energy of 3 5 Joules In addition the following statement is required to appear WARNING EXPLOSION HAZARD DO NOT DISCONNECT REMOVE WIRE EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON HAZARDOUS Installation Requirements for Conformance to Standards I January 2010 GFK 1179M Chapter 2 Introduction General Safety Related Guidelines for Installation in the European Union This chapter provides a description of safety related guidelines for the installation of PLC systems It is assumed that personnel who install operate and maintain automation systems that include GE Intelligent Platforms products are trained and qualified to perform those functions This chapter specifically provides safety related guidelines for products to be installed in the European Economic Area
37. nity for shielded cables in PLCs installed in severe industrial environments The Cable Shield Clamping Assembly must be used in severe industrial environments to provide higher EMC immunity for shielded cables Shield grounding is accomplished using the ground plate and cable clamps provided in the kit The Cable Shield Clamping Assembly package includes W One ground plate m Six cable clamps m Four 6 self tapping screws Outline Drawing of Mounting Plate Figure B 1 is an outline drawing of the mounting plate showing dimensions required for mounting The figure also shows a cable clamp 2 95 je 19 00 483 mm 1595 0 250 6 35 mm dia QTY 2 465 mm xi A B 108 mm Mounting Surface Side View with Spacing Requirements Front View with Mounting Dimensions Cable Clamp Six cable clamps included with assembly Additional cable clamps available 12 per package catalog number IC697ACC737 Figure B 1 Ground Plate Outline Mounting Dimensions and Cable Clamp B 2 Installation Requirements for Conformance to Standards I January 2010 GFK 1179M Installing the Assembly The ground plate should be mounted near the PLC rack for both Series 90 70 and Series 90 30 PLC installations The cable clamp provides mechanical relief as well as electrical grounding A typical installation is shown in Figure B 2 below Figure B 5 shows the Cable Clamp Assembly installed on a Series 90 70 PLC rack The ca
38. nnnnnnnnnnnnnnnnannnnn 1 2 Verification and Industrial Exemption for U S and Canadian Installations 1 2 New Approach Directives sanansa taei a E a a n an 1 3 AS arret E EEEREN EEEREN TAEKES dende 1 4 Grounding the Controls Enclosure essen 1 5 Cable Shield Clamping Assembly sse 1 6 VO Power Sources 3 du da elect vete kledde a enda beviste 1 6 All Analog Modules vugge cie An 1 6 Series 90 30 Prod cts 1 se N nam 1 7 Series 90 70 Products nenn ct iia 1 11 Genius VO Products cccccceccccecsesceceeeeeeeeceeeaaeeeseeeaeeeesesaeeeeeeaeeessesaeeeesseneeeeseaas 1 13 Field Control PrOQUCTS cooooocccconocccccononnncccononcncnononnnncnnonnnncnnnn nn enema 1 14 VersaMax Products iia bedste test phd dsd aD e ERE re ines 1 16 DataPanel Prodlcls n area e a a E asia nesler 1 17 Low Voltage Directive uci een ads 1 18 Installation Requirements sss ener nnne nens 1 18 Aandling Modul8s 2 ria c ng 1 19 Machinery Directive oreet dd 1 20 ATEX DIr civ rasha ukas ee EE kreatin dd 1 22 Installation Requirements eesseeeeesseesieeeeee innen eren nnne en nnne 1 22 Safety Related Guidelines for Installation in the European Union 2 1 INTOdUCIO enr 2 1 eru cler 2 1 Qualitied P rsonnek aa 2 rer A a a a 2 1 Proper Usage e eate B ete aede p e det red 2 2 Guidelines for the Application Planning and Ins
39. results a high frequency ground for the cable shield should be used Optional cables IC693CBL317 3 m and IC693CBL320 1 m provide better noise suppression than the standard I O cables without the high frequency ground CMM311 PCM311 PCM301 PCM300 In order to meet the EN 61000 4 4 levels specified in Appendix A when any of these modules are installed in a control system the Series 90 30 PLC system must be installed in a minimum IP54 rated metal enclosure or the equivalent All surfaces of the enclosure must be adequately grounded to adjacent surfaces to provide electrical conductivity Wiring external to the enclosure must be routed in metal conduit or the equivalent Using shielded cables and power line filtering as detailed in Appendix C is equivalent to using metal conduit IC693CMM321 When the RS485 port of the Ethernet module is used in order to meet the EN 61000 4 4 levels specified in Appendix A a high frequency ground for the RS485 cable shield is required within 12 inches of the module The shield conductor should remain continuous to the module and insulation should be removed only at the grounding point For more information please refer to Cable Shield Clamping Assembly earlier in this chapter IC693CPU351 In order to meet the EN 61000 4 4 levels specified in Appendix A the ground wire and grounding bracket of the IC693CPU351 must be installed as outlined in the Series 90 30 Installation Manual GFK 0356L or later
40. s PLC products allow a machine manufacturer to comply with the electrical safety requirements of the Machinery Directive Other requirements of the Machinery Directive involving items such as displays languages instructions Emergency Stop functions machine operation protective guards and interlocks are the responsibility of the machine manufacturer 1 20 Installation Requirements for Conformance to Standards January 2010 GFK 1179M The specific requirements of EN60204 1 EN 61131 2 and GE Intelligent Platforms installation instructions are as follows Compliance with EN12100 1 and EN12100 2 Safety of Machinery as well as EN60204 1 Electrical Equipment of Industrial Machines must be observed during the design phase m The PLC products must be packaged within an IP54 or higher degree of protection enclosure m Negative logic input and output modules cannot be used Exception With safety agency approval these devices may be used in safety system H configurations m The PLC power supply must be supplied through an IEC rated isolation transformer m Power supply to the PLC must be controlled to ensure that it does not exceed overvoltage category ll per EN60204 1 m Cable shielding and grounding are the responsibility of the machine builder GE Intelligent Platform s installation instructions and guidelines must be followed m Installation operation and maintenance instructions in the language of the user country are
41. s than this maximum specification IC697PCM711 PCM712 CMM711 CMM712 ADC701 Continuous shielded cable must be used for cables connected to the ports on these modules in order to meet the EN 61000 4 4 levels listed in Appendix A The continuous shielded cable must have a high frequency ground within 18 inches 45 72 cm of the module to pass the EN 61000 4 6 levels listed in Appendix A Continuous or 100 shielded means that the braided cable shield is connected to the metal shell of the connector around the entire perimeter of the connector This shielding provides a low impedance path to frame ground for any noise energy that is coupled onto the cable shield Installation Requirements for Conformance to Standards I January 2010 GFK 1179M Genius I O Products General Installation Guidelines In order to meet U S Canadian Australian and European regulations for Class A digital devices all applicable products in the Genius product line have complied with EN55022 standard when installed as follows m The system must be mounted in a minimum IP54 rated metal enclosure or the equivalent All surfaces of the enclosure must be adequately grounded to adjacent surfaces to provide electrical conductivity Wiring external to the enclosure must be routed in metal conduit or the equivalent Using shielded cables and power line filtering as detailed in Appendix G is equivalent to using metal conduit m The conduit must be mounted to the enclosur
42. tallation of the Product 2 2 Product Agency Approvals Standards and General Specifications A 1 Cable Shield Clamping Assembly rrnvvnnnnnnnvvvnnnnnnnennnnnnnnvnnnnnnnnennnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn B 1 Fealulescuiu ot t Meo te Ca RU ee doe du ud eda e He ee ea B 1 iles B 2 Installing the Assembly sssrinin uiine eina narran nennen nnne nennen nnns B 3 Maximum and Minimum Diameter Cable rrrrnnrrrrnsnnrvrrrrnnvrvrrrnnrvrrrrnnrverrrnsrvenerrnnnn B 4 Removing Cable Cover sese enne enr nnns nnne en B 4 Mounting on a Series 90 70 PLC Rack sse B 5 Shielded Cable Alternative to Conduit eese C 1 Communication CableS oooonooccccnnnoccccnononcnonononncnonnnnnnnnnnnnnnnnnnn nn cnn nano nnne nennen nnns nnns C 1 exerc EET C 1 Analog High Speed Cables sse C 1 GFK 1179M Contents Power Input to Enclosure irissat ei ideiei ii adi ia LETEN gE A iaia EETA C 2 AC Power Input RF Filter isseire nhin aiiin diia iyi C 2 DC Power Input RF Filter ennemi C 2 Shield Termination aannvnnnrrnnnnrnnannnvnnnv renn nrnnnnnnnnenrennnrnnnnnnnnnnnenenr rene nnne entente stris nennen C 3 Compression ConnectorS nnensnnennsnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnsnnnnnnnnnnnnnnnnnn nn C 3 Specialty Shielded Cable Vendors 24404240442400nnnnnnnnnnnnnnnennnnnnnnnnnnnnnnnnnnnnnnnnn nn C 4
43. tem The equipment must be connected to a protective ground PE conductor m For equipment or systems with a fixed connecting cable but no isolating switch that disconnects all poles a power socket with the grounding pin must be installed m Before switching on the equipment make sure that the voltage range setting on the equipment corresponds to the local power system voltage m Inthe case of equipment operating on 24 V DC make sure that proper electrical isolation is provided between the main supply and the 24 V supply Use only power supplies that meet EN60204 1 requirements m PLC AC power supply must be supplied through an IEC rated isolation transformer m Power supply to the PLC must be controlled not to exceed overvoltage category II per EN60204 1 m Fluctuations or deviations of the new power supply voltage from the rated value must not exceed the tolerances specified in the technical specifications Otherwise functional failures or dangerous conditions can occur in the electronic modules equipment m Emergency tripping devices in accordance with EN60204 1 must be effective in all operating modes of the automation equipment Resetting the emergency off device must not result in any uncontrolled or undefined restart of the equipment Installation Requirements for Conformance to Standards I January 2010 GFK 1179M m Automation equipment and its operating elements must be installed in such a manner as to prevent unintention
44. the responsibility of the machine builder Appendix A includes a summary of existing agency approvals issued for our PLC products In addition to this summary selected Series 90 70 and Genius modules have been approved by T V for compliance with DIN VDE 0116 and class 5 of DIN VDE 0801 for use in redundant safety system applications These safety agency approvals demonstrate that our PLC products meet essential safety requirements GFK 1179M Chapter 1 Installation Guidelines 1 21 ATEX Directive The ATEX Directive focuses on the safe operation of equipment and protective systems intended for use in potentially explosive environments ATEX Directive 94 9 EC GE Intelligent Plattorms PLC Products Comply Group 2 Category 3 Il 3 G EN50014 1997 Electrical Apparatus for Potentially Explosive Atmospheres General Requirements EN50021 1999 Electrical Apparatus for Potentially Explosive Atmospheres Type of Protection n Technical File GE Intelligent Plattorms ATEX Declaration of Conformity Figure 1 8 Path to Comply with the ATEX Directive For Group 2 Category 3 type equipment compliance to the ATEX Directive is achieved through a manufacturer s self certification A Technical File is composed to document that a product has met the Essential Health and Safety Requirements ESHRs of the UK 1996 Regulations In addition we obtain an independent 3 party assessment for each product family A Declaration of Co
45. tion m In order to pass EN 61000 4 2 HF protection cover metal cover must be installed on the unused D sub connector Standard Genius Cable Conduit Double Shield or CMS Cable Figure 1 5 Communication Cable Requirements PROFIBUS Station In order to meet EN55022 Group 1 Class A Radiated Emission levels all components using the PROFIBUS Station IC670PBI001 require the following m All components must be mounted in a minimum IP54 rated metal enclosure or the equivalent All surfaces of the enclosure must be adequately grounded to adjacent surfaces to provide electrical conductivity Wiring external to the enclosure must be routed in metal conduit or the equivalent Using shielded cables and power line filtering as detailed in Appendix G is equivalent to using metal conduit m The conduit must be mounted to the enclosure using standard procedures and hardware to ensure electrical conductivity between the enclosure and the conduit The termination for the shielded cable alternative to conduit is detailed in Appendix C Additional Guidelines for Specific Components The guidelines specified in this section must be followed in addition to the guidelines found in the general installation guidelines for the product line IC670ALG320 The user supply input must be provided from a power supply in the cabinet conditioned by a 30 volt varistor or wired with a twisted pair shielded cable grounded at the source in order to not
46. ty and other technical issues These laws effectively represented technical barriers to trade between the member states and between them individually and external nations With the interest of promoting the free movement of goods across national borders the European Community agreed on a New Approach to technical harmonization These New Approach Directives provide only essential requirements which can be met either through the use of Harmonized Standards or by other defined means Compliance with standards is not a mandatory requirement of these directives The directives are given the force of law in Member States through enactment of national legislation harmonized through reference to a common source document The European free trade area has been extended under the European Economic Area Agreement 1993 to include 30 countries The CE Marking must be affixed to products meeting the requirements of all applicable EU directives that are in force and that require it Products bearing CE Marking are presumed to comply with the directive s EU directives that might apply directly to the PLC products included in this manual m The EMC Directive 89 336 EEC 92 31 EEC 93 68 EEC deals with electromagnetic emissions and immunity m The Low Voltage Directive 73 23 EEC 93 68 EEC deals with electrical safety m The ATEX Directive 94 9 EC deals with equipment and protective systems intended for use in potentially explosive atmospheres
47. ust also be followed Installation Requirements for Conformance to Standards I January 2010 GFK 1179M Grounding the Controls Enclosure Locally applicable grounding safety regulations and machinery directives should be followed for providing a protective ground to earth In addition the following safety guidelines should be followed Ground conductors should be as short and as large in size as possible The conductors must always be large enough to carry the maximum short circuit current of the path being considered Braided straps or ground cables typically green insulation with a yellow tracer AWG 12 3 3 mm2 or larger can be used to minimize resistance The PLC equipment other control equipment and the machine should be interconnected to maintain a common earth ground reference also called the machine chassis ground Ground conductors should be connected in a star fashion with branches routed to a central earth ground point This ensures that no ground conductor carries current from any other branch This method is shown in Figure 1 2 PLC Cabinet Motor Drives Machinery and other Electrical Rack O Control Equipment Programming Rack O Device Note Signal and power Earth connections ein Central are not shown Ground Point Figure 1 2 Recommended System Grounding The EMC ground deals with the ability of the system to conduct interference
48. y codes GFK 1179M Chapter 1 Installation Guidelines 1 11 Additional Guidelines for Specific Components The guidelines specified in this section must be followed in addition to the guidelines found in the general installation guidelines for the product line IC697BEM741 742 and IC687BEM741 742 In order to meet EN 61000 4 2 8 KV Air the communication ports channels 1 and 2 of the FIP Bus Controller should be connected to the FIP network with an ITT Cannon FBC 115 434 2 or FBC 115 434 3 cable or cable with a similar plastic connector shell otherwise the provided plastic connector cover and nylon screws should be used to cover the exposed metal connector of the FIP communication port IC697MC M001 In order to meet EN55022 Group 1 Class A Radiated Emissions levels as an alternative to conduit each shielded servo cable should have a ferrite located approximately 1 2 inches 2 54 5 08 cm away from the port and a high frequency ground at the entrance to the enclosure Also as stated in Power Mate I Connection Manual GFZ 62733 the continuous shielded servo cables should be clamped for proper grounding for compliance with immunity tests IC697MDL651 Conventional TTL wiring practices should be utilized when installing this module For noise immunity reasons I O control lines connected to this module must be less than 30 meters in length however signal attenuation considerations will constrain practical wiring length to les
49. y with the Low Voltage Directive The following sections specify installation and application practices necessary to meet the Low Voltage Directive Installation Requirements For compliance to the Low Voltage Directive Series 90 30 Series 90 70 Field Control VersaMax and Genius systems and their components are considered open equipment i e live electrical parts may be accessible to users and must be installed in a minimum IP20 protective enclosure IP54 or greater as appropriate is recommended In addition refer to the installation manual for your system and follow the guidelines for mounting spacing and if applicable shielding the devices in your system Locally applicable grounding safety regulations and machinery directives should be followed for providing a protective ground to earth Refer to Grounding the Controls Enclosure on page 1 5 as well as the general installation guidelines for Series 90 30 Series 90 70 Genius I O VersaMax and Field Control products found in the EMC Directive section of this manual for additional safety guidelines related to earth grounding Note Care should be taken regarding installation wiring to ensure proper connections and to protect against equipment damage or misoperation In addition to observing the system grounding procedures recommended for your system periodic inspections of the ground connections should be performed to ensure that the system remains properly grounded Insta
50. ystem I O Module s User s Manual GFK 1179 Installation Requirements for Conformance to Standards GFK 1503 VersaMax System PLC Reference Manual GFK 1504 VersaMax System I O and Option Modules GFK 1535 VersaMax System Network Communications User s Manual Selected modules may be derated Selected modules may also have lower operating surrounding air temperature Applies to products that are designed and built in Charlottesville Applies to all VersaMax power supply I O and communication modules Applies to all Field Control power supply I O and communication modules Appendix A Product Agency Approvals Standards and General Specifications A 3 Appendix B Features GFK 1179M Cable Shield Clamping Assembly This Appendix describes the Cable Shield Clamping Assembly for use with Series 90 30 and Series 90 70 Programmable Logic Controllers that are installed in severe industrial environments and must meet the requirements for higher EMC immunity The Cable Shield Clamping Assembly features the following Provides for higher EMC Electromagnetic Compatibility immunity for shielded cables Use for installations in severe industrial environments Use with all Series 90 30 and Series 90 70 PLC products Easy to assemble Mounts on panel rack enclosure or directly onto a Series 90 70 PLC rack B 1 Functions The Cable Shield Clamping Assembly IC697ACC736 contains the parts necessary for providing higher EMC immu