Contents

1. Note Prior to hookup of the module to the existing alarm system disconnect the whole 1 2 3 4 5 system from the mains supply Push in the snap catches in the lower part of module plastic casing and remove the cover Pass the lead through the opening in the lower part of the casing Attach the lower part of the casing to the wall The terminals DTA CLK and COM connect with wires to the expander bus on the control panel PCB Using the DIP switches set the keypad address The address should be set by means of the switches 1 to 5 the status of the other switches is irrelevant This address must differ from those of the other modules connected to the control panel expander bus In order to determine the keypad address add up the numbers set on particular DIP switches according to Table 1 INT SK GR SATEL 3 Switch number 1 2 3 4 5 Numerical equivalent DIP switch in ON position 1 2 4 8 16 Table 1 address 6 address 22 Figure 3 Addressing examples Five switches make it possible to assign addresses to 32 expanders numbers from 0 to 31 The addresses of expanders connected to one bus cannot be repeated but the addressing order can be random It is recommended that consecutive addresses starting from zero be assigned to expanders and modules connected to one bus This will allow to avoid problems during expansion of the system 6 Connect the module supply to the 12V te
2. of the user code changing Signaling Alarm signaling fixed time acoustic alarm signaling in the given partition through the total duration of alarm Alarm signaling latch acoustic alarm signaling in the given partition until the alarm is cleared Signaling entry delay acoustic signaling of the countdown of entry delay time Signaling exit delay acoustic signaling of the countdown of exit delay time Auto Arm delay countdown the keypad will be acoustically signaling the countdown of the auto arming delay in the partition it has been assigned to Confirming this option defines the way of communication between the control panel and the partition keypad user No the function of keypad operation acknowledgement is disabled Sound the keypad will generate beeps as described in the user manual for the alarm control panel Backlight the audible signaling will be replaced by the blinking keypad illumination as described in the user manual for the alarm control panel Backlight defines the mode of keypad illumination No keypad backlighting disabled Auto keypad backlighting goes on automatically on pressing any key the function has additional options submenu Auto backlight in LCD keypad no auto backlight illumination only activated by pressing one of the keys INT SK GR SATEL 7 zone violation backlighting activated by pressing a key or by violation of the zo
3. the trouble signaling Alternative blinking of all the LEDs from top to bottom indicates lack of communication between the keypad and the control panel This situation may take place when the STARTER program is running in the control panel or when the cable connecting the keypad and the control panel is damaged Note All LEDs may be OFF in the arming mode depending on the control panel settings Information on the use of the partition keypad can be found in the user manual of INTEGRA control panel 2 SATEL INT SK GR 2 Description of electronics board Explanations to Fig 2 1 package of DIP switches for setting individual address of the keypad 2 tamper contact The spring should be pressed against the COM wall NO NO IN 42V DTA CLK Figure 2 Schematic view of the keypad electronics board Description of the terminals NO relay terminals The NO terminals are used for control of the door electromagnetic lock IN door status control input NC If not used it should be short circuited to the common ground COM common ground 12V power supply input CLK DTA expander bus 3 Installation and connection of the module The partition keypad is designed for indoor installation It may be mounted either directly to the wall or in the OBU M LED metallic casing The OBU M LED casing is closed with a key which makes access of unauthorised persons to the keypad more difficult
4. Satel wrsker _ C int sk_en 07 08 The INT SK GR partition keypad is designed for work in conjunction with INTEGRA and CA 64 alarm control panels It is used to control the arming mode in one partition to perform a function of monitoring access and controlling operation of the electromagnetic door locks as well as monitoring closure of those doors The keypad makes it possible to change the user code and call the functions controlling the external devices This manual applies to the partition keypad with firmware version 1 11 or later 1 Description of partition keypad S Satel Figure 1 Partition keypad The partition keypad has 12 keys with permanent or temporary automatically activated mode backlight and LED indicators rp ALARM red color steady light indicates an alarm in the keypad controlled partition LZ while blinking indicates that an alarm was triggered in the partition Eo ARMED green color steady light indicates that the partition to which the keypad is assigned has been armed Blinking indicates countdown of the exit delay r A TROUBLE yellow color blinking indicates that a technical problem has occurred The L signaling applies to troubles from the entire alarm system not only from the keypad controlled partition The type of trouble can be checked on the LCD keypad Arming the keypad controlled partition will disable the trouble signaling Disarming the partition will restore
5. es access to the lock feature options The options Lock feature L_CD DLOAD64 and Lock DLOADX refer to operating the electromagnetic door lock or another device that requires the access control to be operated by means of the partition keypad This function is made available to any user selected in the Users option The operation is effected by controlling the NO relay contacts closed open The normal basic state of the relay contacts depends on how the Relay type option is set Description of the function refers to a typical application Lock feature DLOADX Lock DLOAD64 ON if partition armed selecting this option sets the bistable operating mode of the relay i e it is active when the partition is armed and normal when the partition is disarmed INT SK GR SATEL 5 Note When operating in this mode the relay will change its state automatically if the partition is disarmed from the given keypad When the partition is disarmed from another keypad the state of the relay will change on entering the CODE and pressing the key on the given partition keypad Fixed ON time ON time this option sets the monostable operating mode of the relay When the door opening function is called by the user CODE the relay gets activated for the time period entered in the Relay ON time and then returns to its normal state Fixed ON time OFF if door open ON open off the relay is active until the doo
6. ing Relay ON time fo j sec T Exit delay clearing enable T Alarm signal J until canceled Rela mn I Authorization control I Sign entry delay fe NO C NC E Alarm on unauth ace Sign exit delay J Auto Arm delay countdown Max door open time ja sec Acc Code sign hardware Dependent on door 1 7 CHIME not present GaGa els O o Ww I No auto reset after 3 tamp 2 Laboratory Dependent on door 2 Confirming rotpresent O C no Sound O Backlight fy 4 Commercial dept Backlight 5 Zonet amp output 7 Code do not disarm C no Auto C Permane 6 Addressable Boin mAuto backlight Q 10 Zone w supp no 3 Zone violation fi E Users Entry delay part fi Open door if fire l no Part fire alarm C Object fire alarm Fire alarm Comments Figure 4 DLOADX program window with partition keypad options Name the option to give an individual 16 character name to the module This option can be accessed in the LCD keypad as follows gt Service mode gt Structure Hardware gt Expanders gt Names gt expander selection Partition assignment of the keypad to a partition selected from the list Lock feature the option available in the LCD keypad its activation provides access to the Lock submenu Lock DLOADX Lock feature DLOAD64 its activation provid
7. l and activate the audible alarm The duration can be set from 0 to 255 seconds Dependent on door 1 or Dependent on door 2 this function provides a list to choose the door which must be closed for the lock to operate Monitoring of the door state is effected through the IN input in the partition keypad code lock or CA 64 SR CA 64 SR expander of proximity card readers or through the zone type 57 TECHNICAL DOOR OPEN Two dependent doors can be selected The function allows to create a sluice type passage Code do not disarm Code n disarm with this option enabled entering the code confirmed by pressing the key will neither disarm the partition nor activate the relay will prevent the door from being opened Access when armed Code in arm with this option enabled entering the code confirmed by pressing the key will not disarm the partition but it will activate the relay and enable opening of the door The option is available when the CODE DO NOT DISARM Code n disarm is enabled Master users Users this function defines master users users authorized to use the given keypad Alarms FIRE alarm holding down the key will trigger the fire alarm 6 SATEL INT SK GR AUX alarm Medical alarm holding down the key with digit 0 will trigger the auxiliary alarm PANIC alarm holding down the key will trigger the PANIC alarm Silent PANIC alarm with this option selec
8. lay cccccecceeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeess 24V Maximum current switched over by relay ccccccceceeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeeneeseseseeeeeeeees 2A Environmental Class sancin0 sive oat an iii audition oh EAA EA II Operating temperature TANS secseteccteswis seks sade sionals seks ipa acaccenigeniacslaenicasteanteesiel 10 C 455 C Dimensions length x height x Width 00 0 0 ceeeeeecceseeeeee eee eeeeeeeeaeeeeeeeeeeeeeeeeeees 144x80x27 mm The latest EC declarations of conformity and certificates are available for downloading on the website www satel pl CE SATEL sp Z 0 0 ul Schuberta 79 80 172 Gda sk POLAND tel 0 58 320 94 00 info satel pl www satel pl
9. n keypad 4 Quit the service mode or the communication session with PC and save the data in the FLASH memory 5 Programming the partition keypad settings The partition keypad can be programmed by means of the LCD keypad Service mode gt Structure gt Hardware gt Expanders gt Settings gt expander selection or a computer with 4 SATEL INT SK GR the DLOADX DLOAD64 program Described below are settings and options available for programming Abbreviations from the LCD keypad display are shown at some of the functions Structure lolx System Hardware Module INT S address 3 xx Integra mainboard EB B LCD keypads m dditional featu z 0 Directors office Name Warehouse E FIRE alam E 1 Secretary office tion 1 Secretary office 1 AUX alarm 3 Sunovtic Board Shi 4 JZ PANIC alam IV silent ii 5 ETHM 1 IV Lock Alarm 3 incorrect codes 6 Syn tabl addr Lock features M Quick arming Dloadx RS 232 ON if partition armed E Control BI ouput DloadX modem Fixed ON time E Control MONO output 3 Expansion modules Bus 1 Fixed ON time OFF if door open x Pattition blocking 42 0 CA 640 00h Fixed ON time OFF if door closed Guard round control ao Changing access code fia 1 CA 64 O 01h CA 64 O 03h CA 64 PP 04h CA 64 E 05h CA 64 ADR 06h ACuU 100 08h E EF Expansion modules Bus 2 1 Bookkeep
10. ne entry delay part backlighting activated by pressing a key or by starting the countdown of entry delay time in the indicated partition Note Automatic keypad illumination is ON for approx 40 seconds from the moment of its activation or from the last press of any key Permanent keypad backlighting is permanently ON No auto reset after 3 tampers each expander automatically disables the tamper alarming in the given expander after three consecutive not cleared tamper alarms This prevents multiple recording of the same events in the control panel memory The option allows this feature to be disabled Open door if fire Doors on fire control mode for the door blocking during fire alarm no fire alarm has no effect on the door blocking Partition fire alarm fire alarm in the partition will unblock the door controlled by the module Object fire alarm fire alarm in the object will unblock the door controlled by the module fire alarm fire alarm in the system will unblock the door controlled by the module 6 Technical data Nominal supply voltage 15 4 cavscawcanevunevsacnsaracanucanacanucanaamuranucamuamaacurcacanics cance 12V DC Maximum current Consumption oe scieaetetiavecosnitar es eistore eon inven earnest 65 mA Average Current CONSUMPUON casks scccshctestoestosns cescasat gen casat cesses ges daaatgende dunks auieubbs aeleaaebaeehan 19 mA Maximum voltage switched over by re
11. r is opened the IN input disconnected from common ground but not longer than for the relay ON time Fixed ON time OFF if door closed ON close gt off the relay is active during the time when the door is open the IN input cut off from the common ground and deactivates on closing the door reconnection of the IN input to common ground but not longer than for the relay ON time Relay ON time the time period during which the relay is active Duration of the relay ON time can be from 1 to 255 seconds Relay this option defines the operating mode of the relay contacts NO the NO contacts are normally open they close on activating the relay during its active state NC the NC contacts are normally closed they open on activating the relay during its active state Authorization control Unauth event opening the door without entering a password from the keypad e g with the key will generate an Unauthorized door opening event it can also be signaled on the output type 93 UNAUTHORIZED ACCESS Alarm on unauth access Unauth alarm when the partition to which the module is assigned is armed unauthorized opening of the door will trigger the alarm and can be additionally signaled on the output type 94 ALARM UNAUTHORIZED ACCESS Max door open time this option defines the time after expiry of which the module will report the Long opened door event to the control pane
12. rminal The keypad supply does not have to be provided from the control panel main board An additional power supply unit or expander with power supply can be used for this purpose Details regarding the cable connections are described in the installer s manual for the alarm control panel 7 Connect the wires of the door state control sensor to the IN and COM terminals 8 If the keypad is to serve as a code lock connect the wires to control the electromagnetic door lock or another device to the NO terminals 9 Close the casing 4 Starting the partition keypad 1 Switch on the alarm system power supply 2 Call the Expander identification function gt Service mode gt Structure gt Hardware from the LCD keypad After identification all the settings have either the value of zero or none and the options are inactive No acknowledgement when pressing the keys makes one think that the module fails to respond to entering a code Note During the identification process the control panel saves in the module memory a special 16 bit number used for checking the module presence in the system Replacement of the module with another one even having the same address set on the switches without a new identification will result in triggering the alarm module tamper verification error 3 Using the LCD keypad or DLOADX DLOAD64 program configure the keypad functions and define the users authorized to use the given partitio
13. ted triggering the panic alarm from the keypad will not set off the loud signaling instead a message will be sent to the monitoring station and the output type 12 SILENT ALARM will be activated Alarm 3 incorrect codes 3 wrong codes entering a code unknown to the control panel three times will trigger alarm Options Quick arming quick partition arming fully armed mode press in turn the 0 and keys CA 64 and INTEGRA control panels with any firmware version or the 1 and keys INTEGRA control panel with firmware version 1 05 fully armed mode plus bypassing zones with BYPASSED IF NO EXIT option enabled press in turn the 1 and keys INTEGRA control panel with firmware version1 06 armed without interior press in turn the 2 and keys INTEGRA control panel with firmware version 1 05 or later armed without interior and without entry delay press in turn the 3 and keys INTEGRA control panel with firmware version 1 05 or later Control BI output the keypad accepts the B outputs type of codes Control MONO output the keypad accepts the MONO outputs type of codes Partition blocking entering the guard code when the partition is armed will temporarily bypass the partition Guard round control entering the guard code CODE or CODE will be recorded as completion of the round Changing access code this option enables the function

Download Pdf Manuals

image

Related Search

INT SK GR instagram instagram login instagram logo instagram web instagram icon instagram png int skola karlskoga inte skrika int skills 5e

Related Contents

Fujitsu 2GB DDR3-1066MHz  Installation Guide and User Manual  Samsung Samsung SGH-i780 Bruksanvisning  Virtual Disk Manager User`s Guide  Samsung CLP-365 Color Laser (18 / 4 ppm) Kullanıcı Klavuzu  Giant SEDONA W User's Manual  Carrier 48XL Air Conditioner User Manual      User`s Guide Model 380580 Battery Powered Milliohm Meter  