        PACSystems RX3i CPUs, IC695CPU310-GW, v. 6.00, GFK
         Contents
1.     Unlike the Series 90 30  the RX3i CPU   s SNP ID does not appear in the Machine  Edition programmer Show Status display  Service Request 11 will always return zeros        Second programmer can  change logic while in Test  amp   Edit mode    While currently active in a Test and Edit session using Machine Edition on one PC   Machine Edition running on another PC is not prevented from storing new logic to  the controller        Must have logic if powering up  from flash    If the application will configure the CPU to retrieve the contents of flash memory at  power up  be sure to include logic along with hardware configuration when saving to  flash memory        CPU may not detect  low battery condition    A battery with very low capacity may still have a terminal voltage high enough to report  that it is a good battery  In this case  when the battery starts supplying the memory  power  battery backup   the battery voltage quickly drops to unacceptable levels  with  little warning to the user before failure    To insure against data loss  users should replace batteries in accordance with the  guidelines provided in the CPU Reference Manual  GFK 2222  Additionally  users  could save logic and hardware configuration to flash           Two loss of module faults for  Universal Analog Module       Occasionally  the hot removal of the Universal Analog Input Module  IC695ALG600   results in two    Loss of I O Module    faults instead of one           GFK 2329Z    RX3i CPU       Sub
2.  a port  and then try to use Winloader on the  same port  Winloader will often say    Waiting for Target    until the hyperterm session is  closed   Hot Swap of power supplies or CPUs is not supported   With the following combination of circumstances  it is possible to render serial  communications with the CPU impossible   User configuration disables the Run Stop switch  User configures the power up mode to Run or Last  Logic is stored in FLASH and user configures CPU to load from FLASH on  power up  User application issues COMMREQs that set the protocol on both of the  serial ports to something that does not permit communications to the  Machine Edition programmer   The program name for PACSystems is always  LDPROG1   When another program  name is used in a COMM_REQ accessing  L memory  an Invalid Block Name  05D5   error is generated   Scan sets on the master do not work properly for the first operation of the scan set  after entering RUN mode  They do work properly for subsequent scans   After downloading a new hardware configuration and logic  a power cycle may be  required to resume FANUC I O operation   Use controllers of similar performance in FANUC I O networks  If a master or slave is  located in an RX3i system  the other controllers should be RX3i or Series 90 30  CPU374     Repeated power up down cycles of an expansion rack containing FANUC I O slaves  may result in failure of the slaves    operation  with the RDY LED off           RX3i CPU 11    GFK 2329Z    Lost
3.  count at power up for The serial IO Processor  IC693APU305  will lose the first count after every power up  Serial IO Processor or every time the module receives a configuration    COMMREQ status words In previous releases  the CPU allowed configuration of COMMREQ Status Words in  declared in bit memory types bit memory types on a non byte aligned boundary  Even though the given reference  must be byte aligned  was not byte aligned  the firmware would adjust it the next lowest byte boundary    before updating status bits  overwriting the bits between the alignment boundary and  specified location  To ensure that the application operates as expected  release 3 50  requires configuration of COMMREQ Status Words in bit memory types to be byte   aligned  For example if the user specified status bit location of  I3  the CPU aligns  the status bit location at  l1  Release 3 50 firmware requires the user to specify the  appropriate aligned address   l1  to ensure that the utilized location is appropriate for  their application  Note that the actual reference location utilized is not changed  but  now is explicitly stated for the user     Suspend IO Function Block In a Series 90 70 the SUSPEND_IO function block suspends EGD in addition to IO  does not Suspend EGD Scan  In PACSystems controllers the SUSPEND IO only suspends IO Scan    STOP and RUN mode The PACSystems CPU receives requests to change between stop and run mode from  transition priority many different sources  These incl
4.  impact to the sweep is reduced to 15ms or less           6    RX3i CPU    GFK 2329Z    New CPU Features and Enhancements in Release 6 00    User Defined Types     Create contiguous data structures for use within logic  These structures can be used as  arguments to blocks  be members of user defined function blocks  etc     Variable Indexed Arrays     Support for using variables to index arrays within logic     Logic Driven Write to Flash     Ability to write up to 64 bytes of reference memory to non volatile storage from the user  application  This data is automatically loaded at power up when the user application is read from user flash  Reads of  the data can be commanded from the user application as well  This feature is independent of the programmer version   used  See the PACSystems CPU Reference Manual  GFK 2222N or later for more information about this feature     Backplane Operations Controller Enhancement     The Backplane Operations Controller was enhanced to detect  conditions where a PCI module is in an indeterminate state and reset them  With the enhanced operation  the offending  module will be reset if this occurs  In addition to a loss fault being logged for the module a    Non Critical CPU Software  Fault    with error code 445 will be logged  In previous releases a PCI module behaving in this manner could result in the  CPU going into reset  lights out  due to a hardware watchdog timeout  This feature is independent of the programmer  version used     Restr
5.  less bits or bytes of data  the controller  will return a Completion Ack message without Text Buffer  The protocol specifies that  the returned data will be in the Completion Ack message  but it may not be        GBC30 may not resume  operation after power cycle    In rare instances  a GBC30 in an expansion rack may not resume normal operation  after a power cycle of either the expansion rack or the main rack     To restore GBC operation  power cycle the rack again        Configuration of third party  modules    Do not specify a length of 0 in the configuration of a third party module  The module  will not work properly in the system        Power supply status after CPU  firmware update    The controller will report a Loss of or Missing Option Module fault for the  IC695PSD140 RX3i power supply following an update of CPU firmware  Also  the slot  will appear empty in the programmer s online status detail view  The power supply  continues to operate normally  Power cycle to restore normal status reporting        Power supply status after  power cycling    Rarely  turning a power supply on or off may not result in an Add or Loss fault  Also   the slot will appear empty in the programmer   s online status detail view  The power  supply continues to operate normally  Power cycle to restore normal status reporting        Don   t use multiple targets    In a system in which the hardware configuration is stored from one target and logic is  stored from a different target  powering 
6. GFK 2329Z  June 2010    The RX3i CPU can be used to perform real time control of  machines  processes  and material handling systems  The  CPU communicates with the programmer and HMI  devices via a serial port using SNP Slave protocol  It  communicates with I O and Intelligent Option modules  over a dual backplane bus that provides     m High speed  PCI backplane for fast throughput of new  advanced I O     m Serial backplane for easy migration of existing  Series 90 30 I O     Features    m Contains 10 Mbytes of battery backed user memory  and 10 Mbytes of non volatile flash user memory     m Provides access to bulk memory using reference  table  W     m Configurable data and program memory     m Programming in Ladder Diagram  Structured Text   Function Block Diagram  and C     m  Supports auto located Symbolic Variables that can  use any amount of user memory     m Reference table sizes include 32Kbits for discrete  l  and  Q and up to 32Kwords each for analog  Al  and  AQ     m  Supports most Series 90 30 modules and expansion  racks  For a list of supported I O  Communications   Motion  and Intelligent modules  see the PACSystems  RX3i Hardware and Installation Manual  GFK 2314     m Supports up to 512 program blocks  Maximum size for  a block is 128KB         Bit in word referencing allows you to specify individual  bits ina WORD reference in retentive memory as  inputs and outputs of Boolean expressions  function  blocks  and calls that accept bit parameters     m In s
7. ariables in C Blocks      The C Toolkit for PACSystems is also distributed with Proficy   Machine  Edition Logic Developer 5 0 or greater  Toolkit Release 2 50 build 50A1 or  later is required for use with the RX3i  Please note  The Series 90 Toolkit   1C641SWP709 719  is not compatible with PACSystems     Note  All C blocks must be recompiled using the new toolkit before  downloading to a RX3i CPU that contains Release 5 00 firmware     Backplanes  power supplies As listed in the PACSystems RX3i System Manual  GFK 2314C or later   and system modules    COMMRE Q to PBM300 In Release 3 0  the behavior of the COMMREQ fault output on a COMMREQ  sent to the PROFIBUS master module IC695PBM300 was changed to be  compatible with the Series 90 30 CPU366 PROFIBUS Master  Previously  the  fault output was enabled when the module received a COMMREQ and it was  busy  Now  the busy condition does not result in the fault output being  enabled     Recommended IC200ALG240 When a VersaMax    system Genius   Network Interface Unit  IC200GBI001    revision interoperates with a Genius Bus Controller located in a PACSystems RX3i   and the VersaMax system contains an IC200ALG240 Analog Input Module  it  is recommended to update the IC200ALG240 firmware to Revision 1 10 or  later     However  it is preferable to update the IC200ALG240 firmware to Revision  1 20  which contains resolutions for all issues found after Revision 1 10     Upgrade kits are available at http   www ge ip com support  Use fi
8. fault Station Address  is 1  If the RX3i is added to a multi drop network  care must be taken that the RX3i is  configured with a unique Station Address  Nodes with duplicate Station Addresses on  the same network will not work correctly        10 RX3i CPU  GFK 2329Z    Timer operation    Constant sweep    Large number of COMMREQs  sent to module in one sweep  causes faults    C block standard math  functions do not set errno       Upgrading firmware    Hot swap    Serial port configuration  COMMREQs    Incorrect COMMREQ status for  invalid program name    FANUC I O Master and Slave  operation          Care should be taken when timers  ONDTR  TMR  and OFDTR  are used in program  blocks that are NOT called every sweep  The timers accumulate time across calls to  the sub block unless they are reset  This means that they function like timers  operating in a program with a much slower sweep than the timers in the main program  block  For program blocks that are inactive for large periods of time  the timers should  be programmed in such a manner as to account for this catch up feature    Related to this are timers that are skipped because of the use of the JUMP instruction   Timers that are skipped will NOT catch up and will therefore not accumulate time in  the same manner as if they were executed every sweep     Constant Sweep time  when used  should be set at least 10 milliseconds greater than  the normal sweep time to avoid any over sweep conditions when monitoring or  perfor
9. ge 6    IC695CPU310 GV 5 70 Enabled support that is functionally identical to the IC695CMX128 for the  IC695RMX128    IC695CPU310 FU 5 61 Corrected the problem described in GFK 2329X    IC695CPU310 FU 5 60 Added support for the IC695PMM335 PACMotion Multi Axis Motion Controller and  other new features  and corrects the problems listed in GFK 2329X    IC695CPU310 FT 5 50 Introduced run mode store of EGD and LREAL data type  See GFK 2329V for  problems resolved    IC695CPU310 FS 5 03   IC695CPU310 ER 5 02   IC695CPU310 EP 5 00   IC695CPU310 EN 3 83   IC695CPU310 EM 3 82   IC695CPU310 EL 3 81   IC695CPU310 DK 3 52   IC695CPU310 DJ 3 51   IC695CPU310 DH 3 50   IC695CPU310 CG 3 12   IC695CPU310 CF 3 11   IC695CPU310 CD 3 00   IC695CPU310 CC 2 90   IC695CPU310 CB 2 80   IC695CPU310 CB 2 51   IC695CPU310 BB 2 51   IC695CPU310 AA 2 50 Initial release        Important Product Information for Release 6 00  This CPU firmware release provides   User Defined Types  UDTs     Variable Indexed Arrays    Logic Driven Write to Flash    Backplane Operations Controller Enhancement    See    New Features and Enhancements in Release 6 00    on page 6 for descriptions of the features     Updates    IC695CPU310 is field upgradeable to firmware version 6 00 using the Winloader firmware upgrade utility and upgrade kit  44A752290 G23  which can be downloaded from http   www ge ip com support        4 RX3i CPU  GFK 2329Z    CPU Functional Compatibility    Subject Description    Programmer Version Profic
10. hanging target  name     If you store a hardware configuration to flash that sets    Logic Config Power up Source     to    Always Flash    or    Conditional Flash    and then subsequently changes the name of  the target in the programming software  the hardware configuration will go Not Equal  and will not Verify as equal        Controller and IO Fault Tables  may need to be cleared twice  to clear faulted state     Both Controller and IO fault tables may need to be cleared to take the CPU out of  Stop Fault mode  If one of the tables contains a recurring fault  the order in which the  tables are cleared may be significant  If the CPU is still in Stop Fault mode after both  tables are cleared  try clearing the fault tables again        Setting Force On Off by  storing initial value     Once a force on or force off has been stored to the controller  you cannot switch from  force on to force off or vice versa directly by downloading initial values  To turn off the  force on or off  download the project        Number of active programs  returned as zero     The SNP request Return Controller Type and ID currently returns the number of active  programs as zero        Serial I O fails at 115K during  heavy interrupt load    Rare data corruption errors have been seen on serial communications when running at  115K under heavy interrupt load on the controller  Under heavy load applications   users should restrict serial communications to 57K or lower        SNP ID not always provided
11. ictions and Open Issues in Release 6 00          Subject Description  The Ethernet module fails to Very rarely  after experiencing multiple rapid power cycles  the CPU may fail to  exchange EGD properly during   establish communication with one or more modules in the backplane at power up   power cycling When this occurs a  Loss of  or missing option module  fault will be logged in the    controller fault table  To recover from this issue  cycle power again   The following faults will be logged if this issue occurs    Loss of  or missing option module   Error Code 31   Group 4   Action 3 Fatal   Task Num 9       Reset of option module  Error Code 11   Group 8   Action 2 Diagnostic  Task Num 9       Loss of  or missing option module  Error Code 94   Group 4   Action 3 Fatal   Task Num 9             Loss of Power Supplies after A Loss of Power Supplies after firmware update may occur  This does not happen with    firmware update all firmware updates and will not occur if the system is power cycled after the firmware    upgrade has completed  The following fault is displayed when this issue occurs     Loss of  or missing option module       Error Code 36  Group 4   Action 3 Fatal  Task Num 9    Fault Extra Data  01 58 02 4f 80 08 Oa 07 00 00 00 00 00 00 00  00 00 00 00 00 00 00 00 00    To correct this condition  power cycle the system                 RX3i CPU    7  GFK 2329Z       Subject    Description       Battery installation    When installing a battery  when there current
12. ject    Description       Power up of Series 90 30 HSC  module may take as long as 20  seconds    As power is applied to a 90 30 High Speed Counter  the  module ready  bit in the  status bits returned each sweep from the module may not be set for as long as 20  seconds after the first controller sweep  even though there is no Loss of Module  indication  I O data exchanged with the module is not meaningful until this bit is set by  the module  For details  see    Data Transfer Between High Speed Counter and CPU    in  the Series 90 30 High Speed Counter User   s Manual  GFK 0293C        Informational fault at power up    Intermittently during power up  an Informational non critical CPU software fault may be  generated with fault extra data of 01 91 01 D6  This fault will have no effect on the  normal operation of the controller  But  if the hardware watchdog timer expires after  this fault and before power has been cycled again  then the outputs of I O modules  may hold their last state  rather than defaulting to zero        Extended memory types for IO  triggers     R   W and  M cannot be used as IO triggers        Possible Machine Edition  inability to connect    Infrequently  an attempt to connect a programmer to an RX3i via Ethernet will be  unsuccessful  The normal connection retry dialog will not be displayed  Rebooting the  computer that is running the programmer will resolve the behavior        SNP Update Datagram  message    If an Update Datagram message requests 6 or
13. lease 5 00 or later  if an attempt is made to download a C block containing  undefined symbols  the download will fail  Machine Edition will display the following  message in the Feedback Zone  Error 8097  Controller Error     Controller aborted the  request  0x05  OxFF    Prior to Release 5 00  C blocks containing undefined symbols could be successfully  downloaded  but if they were executed the CPU would transition to Stop Halt mode      Release 5 0 or later  The  Set Up Input Buffer Function  always allocates a buffer  containing 2049 bytes  This is one byte more than previous PACSystems releases     A battery is shipped with the CPU unit behind the battery door on the faceplate but it is  not connected  Do not connect the battery until the CPU is installed in the rack and the    rack powered on  The battery may then be attached to either of the two terminals in  the battery compartment  Once that is done  the CPU may be powered down and  normal battery back up operation will begin  To save battery life  do not connect the  battery for the first time until the CPU is powered up     Storing a hardware configuration with a new IP address to the RX3i while connected  via Ethernet will succeed  then immediately disconnect because the RX3i is now using  a different IP address than the Programmer  You must enter a new IP address in the  Target Properties in the Machine Edition Inspector window before reconnecting     The default serial protocol for the RX3i is Modbus RTU  The de
14. lot causes  module to not be recognized     If a PCI module  IC695  is configured in a slot where a Serial module  IC694   IC693  is physically located  a module mismatch fault was be logged as expected   In prior releases the mismatched module would not work properly after  downloading new configuration to match the physical configuration        ALG392 hot inserted after  clearing the RAM causes CPU  Stop Halt     Previously when an ALG392 was hot inserted after clearing RAM on a CPU rack  with point faults enabled  the CPU would go into Stop Halt mode        Modified cam profile is treated  as a new cam profile     Previously when a modified cam profile  i e  a profile with the same name exists on  the controller  was downloaded to a running controller it was treated as a new  profile instead of a modified profile  This may result in a cam profile not being  delivered to the IC695PMM335 if an unlinked variable is used to reference the file   This could also result in a MC_CamlIn not warning that a profile has changed on  the controller  Because the profile is treated as a new profile it could also cause a  failure to download because the number of profiles on the controller exceeded  2048        Sweep time increase of 60ms  on the backup controller when  powering down the active  controller        In previous releases powering down the active controller could cause a 60ms  increase in sweep time on the backup controller when using two redundant links   With release 6 00 the
15. ly is no battery installed  the battery must  be installed while the CPU has power  Failing to follow this procedure could result in  the CPU not powering up     If a battery is installed while power is off  and there was no battery previously  installed   and the CPU fails to power up  simply remove the battery  power cycle the  CPU and then install the battery        Hot Swapping some Analog  modules slowly may result in  modules not being recognized    Occasionally during a hot insertion  hot swap  of  C695 Non lsolated Analog Input  Modules  input channels may take up to 2 seconds to reflect actual input values after  the module OK bit is enabled in the module status word  This delay has only occurred  when the hot insertion has been done slowly  i e  approximately 1 5 seconds to insert  the module        Ethernet disconnect during  Word for Word change     If the Ethernet connection is broken during a word for word change  the programmer  may not allow a subsequent word for word change after reconnecting due to the fact  that it thinks another programmer is currently attached  If this occurs  you should go  offline and then back online again        Simultaneous Clears  Loads  and Stores not supported     Currently  PACSystems CPUs do not support multiple programmers changing CPU  contents at the same time  The programming software may generate an error during  the operation  Simultaneous loads from a single CPU are allowed        Hardware configuration not  equal after c
16. ming on line changes with the programmer  Window completion faults will occur  if the constant sweep setting is not high enough     A large number of COMMREQs  typically greater than 8  sent to a given board in the  same sweep may cause Module Software faults to be logged in the RX3i fault table   The fault group is MOD_OTHR_SOFTWR  16t  10h  and the error code is  COMMREQ_MB_FULL_START  2   When this occurs  the    FT    output of the function  block will also be set  To prevent this situation  COMMREQs issued to a given board  should be spread across multiple sweeps so that only a limited number  typically 8 or  less  of COMMREQs are sent to a given board in each sweep  In addition  the FT  output parameter should be checked for errors  If the FT output is set  meaning an  error has been detected   the COMM_REQ could be re issued by the application logic        In C Blocks  standard math functions  e g  sqrt  pow  asin  acos  do not set errno to  the correct value and do not return the correct value if an invalid input is provided     Upgrading the CPU firmware with the WinLoader utility may fail when multiple IO  modules are in the main rack  due to the time it takes to power cycle the rack system   If the upgrade process fails  move the CPU to a rack without IO modules and restart  the upgrade process   Winloader initial connect baud rate is fixed at 19200 baud  Note that the firmware  download will occur at 115 2K baud by default   Note that if you have hyperterm open on
17. ng information is for products bearing the UL marking for Hazardous Locations     WARNING   EXPLOSION HAZARD   SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I   DIVISION 2     WARNING   EXPLOSION HAZARD   WHEN IN HAZARDOUS LOCATIONS  TURN OFF POWER BEFORE REPLACING  OR WIRING MODULES  AND    WARNING   EXPLOSION HAZARD   DO NOT CONNECT OR DISCONNECT EQUIPMENT UNLESS POWER HAS  BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NONHAZARDOUS     EQUIPMENT LABELED WITH REFERENCE TO CLASS I  GROUPS A  B  C  amp  D  DIV  2 HAZARDOUS LOCATIONS IS  SUITABLE FOR USE IN CLASS I  DIVISION 2  GROUPS A  B  C  DOR NON HAZARDOUS LOCATIONS ONLY    The tightening torque range for the control terminals is 9 6   11 5 in  lb  Use only wire rated for 90  C  Be sure to observe  any additional ratings that are provided with the modules     Batteries  Replace Battery with Matsushita Part No  BR2477A Only  Use of another battery may present a risk of fire or  explosion        Caution  Battery may explode if mistreated  DO NOT recharge  disassemble or dispose of in fire     The correct  battery type is available as Accessory Kit IC698ACC701     
18. rget   To proceed with  the upgrade  press the  abort  button and disconnect the other application that is using  the COM port        CPU320  CRU320 user  application and values cleared  after power cycle    Under rare circumstances during multiple rapid power cycles the CPU320 CRU320 will  power up with the user application and data in RAM cleared  There will be a     Corrupted user memory    fault in the controller fault table  Group 130  Error code 1      This will not occur if the user application and data are loaded from flash on power up      Always Flash    or    Conditional Flash            WinLoader does not display  error when it can t connect  serially with PACS CPU           WinLoader does not display an error message if it cannot connect to the PACS CPU  when attempting to connect to a PACSystems CPU to perform a firmware upgrade   This occurs if the cable is physically not connected to the CPU or if the CPU s serial  port is not configured for the same baud as WinLoader  In this case Winloader  displays the status  trying to connect  followed by  waiting for target   To proceed with  the upgrade  press the  abort  button and correct the cable or baud rate setting        Operational Notes    Undefined symbols in  C blocks    Length of serial I O buffer    Important installation  instructions for battery    Changing IP address of  Ethernet interface while  connected    Duplicate station address for  Modbus will conflict with other  nodes       Description    In Re
19. rmware  update kit 44A752313 G01 to update the IC200ALG240 firmware to Revision  1 10  or upgrade kit 44A752313 G02 to update the IC200ALG240 firmware to  Revision 1 20     Configuration of IC694MDL754   Always configure 16 bits of module status when using this module   Configuring 0 bits of module status will result in invalid data in the module   s  ESCP status bits        RX3i CPU    5    GFK 2329Z    CPU Problems Resolved by Release 6 00       Subject    Description             MC_CAMFILEWRITE does not  validate some fields     In this release validation has been expanded to include NAN  not a  number checking for all lreal  64 bit   Specific error codes are now returned for the  following fields when a NAN is encountered     Initial boundary first derivative   Initial boundary second derivative  Final boundary first derivative   Final boundary second derivative  Master axis range   Master axis low limit   Slave axis range   Slave axis low limit   Master position   Slave position   Slave relative velocity  if applicable   Slave relative acceleration  if applicable        RX3i CMX RMX did not disable  transmitter in Stop Halt mode     In previous releases the automatic transmitter disable feature for  IC695CMX128 RMX1 28 did not automatically turn off the fiber optic transmitter  when the CPU went to Stop Halt mode  With release 6 00 the fiber optic  transmitter will be turned off when the CPU goes to Stop Halt mode        Switching between Serial  amp  PCI  modules in a s
20. ude  but are not limited to  Proficy Machine Edition     HMls  the user application  and the RUN STOP switch  Since there are many potential  sources for a mode change request  it is possible to receive a new mode change  request while another is already in progress  When this occurs  the CPU evaluates the  priority of the new mode change request with the mode change that is in progress  If  the new mode change request has an equal or higher priority than the one already in  progress  the CPU transitions to the new mode instead of the one in progress  If   however  the new mode change request has a lower priority than the one in progress   the new mode request is discarded and the CPU completes the mode change that is  in progress    The sweep mode priorities are  listed from highest to lowest priority   STOP HALT   STOP FAULT  STOP  and RUN   Note  The IO ENABLED DISABLED state is not part  of the mode priority evaluation      For example  a CPU is in RUN IO ENABLED mode and a Service Request 13 function  block is executed to place the CPU into STOP IO DISABLED mode  Before the  transition to STOP IO DISABLED is completed  the RUN STOP switch is changed  from RUN IO ENABLED to RUN IO DISABLED  In this case  the CPU ignores the new  request from the RUN STOP switch to go to RUN IO DISABLED mode because it is  already processing a request to go to STOP IO DISABLED mode and STOP mode  has a higher priority than RUN mode           Installation in Hazardous Locations  The followi
21. up from flash will not work  The observed  behavior is that  following a power up from flash  Machine Edition reports hardware  configuration and logic  not equal           Missing Loss of Terminal  Block fault     The IC695ALG600 608 616 analog input modules do not produce a Loss of Terminal  Block fault when hardware configuration is stored or the module is hot inserted  and  the terminal block is not locked into place        Sequence Siore failure     In systems with very large hardware configurations  it is possible to encounter a  Sequence Store Failure error when writing the configuration to flash  To work around  this error  either   1  Perform an explicit clear of flash prior to performing the write   2  Increase the operation timeout used by Machine Edition software prior to  performing the write        IC694MDL754  Must configure  module status bits    Always configure 16 bits of module status when using this module  Configuring 0 bits  of module status will result in invalid data in the module   s ESCP status bits        IC695ALG600 Lead Resistance  Compensation setting    A configuration store operation will fail if a channel is configured for 3 wire RTD and  Lead Resistance Compensation is set to Disabled  A Loss of Module fault will be  logged in the I O Fault table at the end of the store operation  To recover the lost  module  the configuration must be changed to enable Lead Resistance Compensation  and module must be power cycled           C Toolkit PlcMemCop
22. us support  RX3i PCI and 90 30 style serial  System designed to be electrically compliant with PCI 2 2 standard  Up to 512 program blocks  Maximum size for a block is 128KB        Memory     l and  Q  32Kbits for discrete   Al and  AQ  configurable up to 32Kwords     W  configurable up to the maximum available user RAM    Symbolic  configurable up to 10 Mbytes          For environmental specifications and compliance to standards  for example  FCC or European Union Directives   refer to the  PACSystems RX3i Hardware and Installation Manual  GFK 2314        Ordering Information                                  Description Catalog Number   RX3i VME 300Mhz CPU IC695CPU310  Lithium Battery Pack IC698ACC701  Auxiliary Battery Module  optional  IC693ACC302  RX3i Power Supplies   40 Watt High Capacity Universal AC   IC695PSA040   40 Watt High Capacity 24 VDC IC695PSD040  For additional power supplies  see the  PACSystems RX3i System Manual   GFK 2314    Optional  RS 232 Cable IC200CBL001  Rx3i 12 Slot Universal Backplane IC695CHS012  Rx3i 16 Slot Universal Backplane IC695CHS016          Note  For Conformal Coat option  please consult the factory for price and availability        RX3i CPU    Release History    3  GFK 2329Z                                                                                  Catalog Number FW Version Comments   IC695CPU310 GW 6 00 For details  see    Problems Resolved by Release 6 0    on page 5 and    New Features  and Enhancements in Release 6 00    on pa
23. y   Machine Edition Logic Developer PLC version 6 0 or later is required  Requirements to use the new Release 6 00 features with the RX3i CPU   Proficy Machine Edition Logic Developer 5 9 SIM1 or later versions required to  use the Release 5 70 features with the RX3i CPU   Proficy Machine Edition Logic Developer 5 9 is required to use the new  Release 5 60 features with the RX3i CPU   Proficy Machine Edition Logic Developer 5 8 is required to use the new  Release 5 50 features with the RX3i CPU   Proficy Machine Edition Logic Developer 5 7 is required to use the new  Release 5 0 features with the RX3i CPU     Proficy Machine Edition Logic Developer 5 5 with Service Pack 2 Sim 4 is  required to use the new CMM serial modules with the RX3i CPU     Proficy Machine Edition Logic Developer 5 5 with Service Pack 1 is required to  use the eight ETM feature with the RX3i CPU     Proficy Machine Edition Logic Developer 5 5 or later must be used to for new  features in PACSystems 3 50 and later     Proficy Machine Edition Logic Developer 5 0 or later must be used to configure  and program the RX3i  Service Pack 3 is required to support the new features  in PACSystems 3 00     C Toolkit Compatibility C Toolkit Release 5 50 is required to use the LREAL data type     C Toolkit Release 5 00 Build 16C1 is required when the PACSystems CPU  contains firmware Release 5 00 or later     C Toolkit Release 3 50 Build 34A1 is required for new features in  PACSystems Release 3 50 and later  Use of v
24. y  Documentation Incorrect       This routine does allow the destination and source pointers to be outside of reference  memory  If the destination points to discrete reference memory  overrides and  transitions will be honored  Note that the header for PlcMemCopy has been updated in  Release 3 50 of the C toolkit           RX3i CPU    9  GFK 2329Z       Subject    Description       WinLoader may stop operating    On computers running Windows 2000 and using some versions of Symantec Antivirus  protection  WinLoader will fail if used in advanced mode  Recovery requires cycling  the computer s power        Logic and HWC not equal after  power cycle    If the Hardware Configuration from Target 1  with Logic Configuration Power up  Source and Data Source both set to    Always from Flash     is stored in Flash  then Logic  and Hardware Config from Target 2  with Logic Configuration Power up Source both  set to    Always from RAM     is stored to RAM and there is a good battery  then when  power is cycled the programmer may show that Logic and Hardware Config are not  equal    The remedy is to clear Flash and then store the Logic and Hardware Config from  Target 2        WinLoader does not detect PC  COM port in use when  upgrading PACSystems CPU     WinLoader does not detect if a PC s COM port is in use when attempting to connect to  a PACSystems CPU to perform a firmware upgrade  If the port is already in use it  displays the status  trying to connect  followed by  waiting for ta
25. ystem upgradeable firmware     m Two serial ports  an RS 485 serial port and an  RS 232 serial port     PACSystems    RxX3i    IC695CPU310  Central Processing Unit    Ethernet communications via the rack based Ethernet  Interface module  IC695ETMO001   For details on  Ethernet capabilities  refer to TCP IP Ethernet  Communications for PACSystems User   s Manual   GFK 2224     Time synchronization to SNTP Time Server on  Ethernet network when used with an Ethernet module  with firmware release 5 0 or later        CPU OK       RUN      OUTPUTS DISABLED  VO FORCE      BATTERY      SYSTEM FAULT       M1 ACTIVE  COM1AC J          COM2ACTIVE                  2  GFK 2329Z    Specifications    RX3i CPU       Battery  Memory retention    Program storage    Power requirements    Operating Temperature   Floating point   Boolean execution speed  typical  Time of Day Clock accuracy    For estimated battery life under various conditions  refer to the PACSystems CPU    Reference Manual  GFK 2222   Up to 10 Mbytes of battery backed RAM  10 Mbytes of non volatile flash user memory     3 3 VDC  1 25 Amps nominal   5 VDC  1 0 Amps nominal    0 to 60  C  32  F to 140  F    Yes   0 195ms per 1000 Boolean instructions  Maximum drift of 2 seconds per day       Elapsed Time Clock  internal timing   accuracy    0 01  maximum       Embedded communications  Serial Protocols supported  Backplane   PCI compatibility   Program blocks    RS 232  RS 485  Modbus RTU Slave  SNP  Serial I O    Dual backplane b
    